1. Safety precautions
1.1. General safety precautions
• Read this manual carefully. It contains important instructions that need to be followed during installation,
operation and maintenance.
• Save these instructions for future reference on operation and maintenance.
• Danger of battery explosion from sparking.
• Danger of electric shock.
• Install the product in a heatproof environment. Ensure therefore that there are no chemicals, plastic parts,
curtains or other textiles, etc. in the immediate vicinity of the equipment.
• The product is not allowed to be mounted in a user accessible area.
• Ensure that the equipment is used under the correct operating conditions. Never operate it in a wet
environment.
MPPT solar charger manual
• Never use the product at sites where gas or dust explosions could occur.
• Ensure that there is always sufficient free space around the product for ventilation.
• Refer to the specifications provided by the manufacturer of the battery to ensure that the battery is suitable
for use with this product. The battery manufacturer's safety instructions should always be observed.
• Protect the solar modules from incident light during installation, e.g. cover them.
• Never touch uninsulated cable ends.
• Use only insulated tools.
• This product is designed and tested in accordance with international standards. The equipment should be
used for the designated application only.
• Connections must always be made in the sequence described in the Installation [9] chapter of this
manual.
• The installer of the product must provide a means for cable strain relief to prevent the transmission of stress
to the connections.
• In addition to this manual, the system operation or service manual must include a battery maintenance
manual applicable to the type of batteries used.
1.2. Wiring safety precautions
• Use flexible multi-stranded copper cable for the battery and PV connections.
• The diameter of the individual strand of the cable used should not exceed 0.4mm (0.016 inch) or have a
surface area exceeding 0.125mm² (AWG26).
• The maximum operating temperature is 90°C (194°F).
• For MC4 models only: The maximum current rating of a MC4 connector is 30A.
• A 25mm² cable, for example, should have at least 196 strands (class 5 or higher stranding according to
VDE 0295, IEC 60228 and BS6360). An AWG2 gauge cable should have at least 259/26 stranding (259
strands of AWG26). Example of suitable cable: class 5 “Tri-rated” cable (it has three approvals: American
(UL), Canadian (CSA) and British (BS)).
• In case of thicker strands the contact area will be too small and the resulting high contact resistance will
cause severe overheating, eventually resulting in fire. See below figure for examples of what cable to use
and not to use.
Page 1Safety precautions
MPPT solar charger manual
1.3. Symbols used on the enclosure
The following symbols are used on the solar charger enclosure:
SymbolNameMeaning
Danger of electric shock
warning
Hot surface warningDo not touch the surface of the appliance, while it is running, it will get hot.
Read the manual
instruction
Ingress protection value
Ground symbolIndicates the position of the chassis ground connection
Do not touch the electric connections, there is danger of electrical shock.
Read the product manual before installation and use.
IP43 - The electronic components are protected from tools and small wires
greater than 1 millimetre and protected from water spray less than 60 degrees
from vertical.
1.4. FCC and Industry Canada compliance
This device complies with part 15 of the FCC Rules and to RSS of Industry Canada. Operation is subject to the following two
conditions:
1. This device may not cause harmful interference, and
2. This device must accept any interference received, including interference that may cause undesired operation.
Le présent appareil est conforme aux CNR d'Industrie Canada applicables aux appareils radio exempts de licence. L'exploitation
est autorisée aux deux conditions suivantes : (1) l’appareil ne doit pas produire de brouillage, et (2) l’utilisateur de l’appareil doit
accepter tout brouillage radioélectrique subi, même si le brouillage est susceptible d’en compromettre le fonctionnement.
Changes or modifications not expressly approved by the party responsible for compliance could void the user’s authority to
operate the equipment.
Note: This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of
the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment
is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not
installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation
of this equipment in a residential area may cause radio interference in which case the user will be required to correct the
interference at his own expense.
This Class A digital apparatus complies with Canadian ICES-003.
Cet appareil numérique de Classe A est conforme à la norme Canadienne ICES-003.
Page 2Safety precautions
MPPT solar charger manual
2. Introduction
The Victron Energy BlueSolar charge controller is an ultra fast Maximum Power Point Tracking (MPPT) solar charger with an
outstanding conversion efficiency and is suitable for a wide range of battery and PV voltages.
2.1. Battery voltage, PV voltage and current rating
The solar charger can charge a lower nominal-voltage battery from a higher nominal voltage PV array. The controller will
automatically adjust to the battery voltage and will charge the battery with a current up to its rated current.
The product name of the solar charger incorporates the maximum PV voltage and the maximum battery charge current.
For example: A 150/70 model has a maximum PV voltage of 150V and can charge the battery with a maximum of 70A.
The table below indicates the maximum PV voltage and maximum battery charge current of the solar chargers that are covered
by this manual:
Solar charger modelMaximum PV voltageMaximum battery charge currentSuitable battery voltages
MPPT 150/60150V60A12, 24, 36 and 48V
MPPT 150/70150V70A12, 24, 36 and 48V
MPPT 250/60250V60A12, 24, 36 and 48V
MPPT 250/70250V70A12, 24, 36 and 48V
2.2. TR or MC4 model
The solar charger is available in two different models, namely:
• The TR version - The PV terminals are screw terminals
• The MC4 version - The PV terminals are MC4 terminals
The 60A MC4 model has 2 MC4 male and female connector pairs.
The 70A MC4 model has 2 MC4 male and female connector pairs.
From left to right: Example of solar chargers with screw terminals and MC4 PV connections
Page 3Introduction
MPPT solar charger manual
3. Features
3.1. Automatic battery voltage detection
The solar charger automatically detects supported (e.g 12V, or 24V, or 48V) system voltage (battery voltage) on first power up. If
a different system voltage is required at a later stage, or if the solar charger is connected to a 36V system, this can be manually
configured in the solar charger settings.
3.2. Outstanding MPPT algorithm
Ultra fast MPP tracking
The solar charger contains an ultra fast MPPT controller. This is especially beneficial when the solar light intensity is constantly
changing, as is the case during cloudy weather. Because of the ultra fast MPPT controller, 30% more energy is harvested
compared to solar chargers with a PWM controller and up to 10% more compared to slower MPPT controllers.
Optimal solar yield
The solar charger has an innovative tracking algorithm. It will always maximize energy harvest by locking to the optimum MPP
(Maximum Power Point). If partial shading occurs, two or more maximum power points may be present on the power-voltage
curve. Conventional MPPTs tend to lock to a local MPP, which may not be the optimum MPP.
3.3. Outstanding conversion efficiency
The solar charger has an outstanding conversion efficiency. The maximum efficiency exceeds 98%. One of the benefits of the
high efficiency is that the solar charger does not have a cooling fan and the maximum output current is guaranteed up to an
ambient temperature of 40°C (104°F).
3.4. Extensive electronic protection
The solar charger is protected against over-temperature. The output is fully rated up to an ambient temperature of 40°C (104°F).
Should the temperature further increase, the output current will be derated.
The solar charger is equipped with PV reverse polarity protection and PV reverse current protection.
3.5. VictronConnect app
The VictronConnect app can be used to:
• Monitor the solar charger and view real-time solar and battery data.
• Operate solar charger features.
• Access up to 30 days of historical data and error history.
• Configure solar charger settings.
• Update firmware.
Screenshot of the VictronConnect app, showing real-time data and historical data.
The VictronConnect app can be downloaded from app stores or from the Victron Energy downloads page.
Page 4Features
MPPT solar charger manual
The app is available for the following platforms:
• Android.
• Apple iOS, note that USB is not supported, it is only possible to connect via Bluetooth.
• MacOs.
• Windows, note that Bluetooth is not supported, it is only possible to connect via USB.
The app can connect to the solar charger in the following ways:
• Via Bluetooth, using an optional VE.Direct Bluetooth Smart Dongle.
• Via USB, using an optional VE.Direct USB interface.
• Via internet or LAN, through the VRM portal, using an optional GX device or GlobalLink 520.
Connection via Bluetooth.Connection via USB.
Connection via Internet or LAN.
3.6. Display
There are a number of display options:
• The VictronConnect app.
• A GX device.
• The VRM Portal, note that a GX device or a GlobalLink 520 is needed.
• The SmartSolar Control display - an (optional) external display that plugs into the front of the solar charger.
• The MPPT Control - an (optional) external display that connects to the VE.Direct port. Note that the required VE.Direct cable is
not included with the MPPT Control.
Page 5Features
MPPT solar charger manual
3.7. VE.Direct port
The VE.Direct port is used to communicate with the solar charger. It can be used for several purposes:
• To connect to a monitoring device, such as a GX device or the GlobalLink.
• To connect with the VictronConnect app.
• For external control.
Special cables or interfaces are needed to connect to this port:
• VE.Direct cable - used to connect to a GX device or the GlobalLink.
• VE.Direct to USB interface - used to connect via USB to the VictronConnect app.
• VE.Direct Bluetooth Smart dongle - used to connect via Bluetooth to the VictronConnect app.
• VE.Direct TX digital output cable - used for streetlight control or to create a virtual load output.
• VE.Direct non inverting remote on/off cable - used to remotely switch the solar charger on or off.
3.8. Load output
The solar charger is equipped with a virtual load output.
3.8.1. Virtual load output
A virtual load output can be established to compensate for the absence of a physical load output in the solar charger.
To create a virtual load output:
• Use the programmable relay and enable it to act as a virtual load output via the VictronConnect App Relay function. Refer to
the ??? chapter.
• Use the VE.Direct TX cable and enable it to act as a virtual load output via the VictronConnect App RX port function. Refer to
the RX port settings [27] chapter.
The virtual load output can be set up within the VictronConnect app and controlled using battery voltages or the BatteryLife
algorithm. For details on the configuration process, please consult the Load output settings [22] chapter.
3.8.2. BatteryLife
This chapter only applies if the virtual load output is used.
When the solar charger is not able to recharge the battery to its full capacity within one day, the result is often that the battery will
continually be cycled between a ‘partially charged’ state and the ‘end of discharge’ state. This mode of operation (no regular full
recharge) will destroy a lead-acid battery within weeks or months.
The BatteryLife algorithm will monitor the state of charge of the battery and, if needed, day by day slightly increase the load
disconnect level (i.e. disconnect the load earlier) until the harvested solar energy is sufficient to recharge the battery to nearly the
full 100%. From that point onward, the load disconnect level will be modulated so that a nearly 100% recharge is achieved about
once every week.
3.9. Battery charging
3.9.1. Adaptive 3-stage battery charging
The solar charger is a 3-stage charger. The charge stages are: Bulk – Absorption – Float.
Bulk
During the bulk stage, the solar charger delivers the maximum charge current, to rapidly charge the batteries. During this stage,
the battery voltage will slowly increase. Once the battery voltage has reached the set absorption voltage, the bulk stage stops and
the absorption stage commences.
Absorption
During the absorption stage, the solar charger has switched to constant voltage mode. The current flowing to the battery will
gradually decrease. Once the current has dropped below 2A (tail current), the absorption stage stops and the float stage will
commence.
When only shallow discharges occur the absorption time is kept short. This is to prevent overcharging of the battery. But if the
battery was deeply discharged, the absorption time is automatically increased, to make sure that the battery is fully recharged.
Page 6Features
MPPT solar charger manual
Float
During the float stage, the voltage is reduced, and the battery's fully charged state is maintained.
A storage stage is not needed for solar chargers, unlike for AC chargers, since at night there is no solar
power, so battery charging will stop.
3.9.2. Flexible charge algorithm
The VictronConnect app allows selection of 8 pre-set charge algorithms, or alternatively the charge algorithm is fully
programmable. The charge voltages, stage duration and the charge current can be customized.
In addition to this, 8 pre-programmed algorithms can be set with a rotary switch.
3.9.3. Equalization charging
Some lead-acid battery types need a periodic equalization charge. During equalization the charge voltage will be increased above
the regular charge voltages to achieve cell balancing.
If an equalization charge is required it can be enabled using the VictronConnect app.
3.10. Temperature sensing
Temperature sensing allows for temperature compensated charging. The absorption and float charge voltages are adjusted based
on either the battery temperature (accessory needed) or otherwise on the solar charger internal temperature.
Temperature compensated battery charging is needed when charging lead-acid batteries in hot or cold environments.
The temperature compensation can be enabled or disabled in the solar charger settings and the amount of compensation, the
compensation coefficient (mV/°C), is adjustable.
3.10.1. Internal temperature sensor
The solar charger has a built-in internal temperature sensor.
The internal temperature is used to set the temperature compensated charge voltages. For this, the internal temperature when
the solar charger is "cold" is used. The solar charger is "cold" when there is only little current flowing into the battery. Be aware
that this is only an estimation of the ambient and the battery temperature. Should a more accurate battery temperate be needed,
consider using an external battery temperature sensor, see chapter External temperature and voltage sensor [7].
The temperature compensation range is 6°C to 40°C (39°F to 104°F).
The internal temperature sensor is also used to determine if the solar charger is overheated.
3.10.2. External temperature and voltage sensor
The (optional) Smart Battery Sense is a wireless battery voltage and temperature sensor and can be used with the solar charger.
It measures the battery temperature and the battery voltage and sends this via Bluetooth to the solar charger.
The solar charger uses the Smart Battery Sense measurements for:
• Temperature compensated charging using the actual battery temperature, rather than the solar charger's internal temperature.
An accurate battery temperature measurement will improve charging efficiency and prolong the life of lead-acid batteries.
• Voltage compensation. The charge voltage is increased to compensate in case there is a voltage drop over the battery cables
during high current charging.
The solar charger communicates with the Smart Battery Sense via Bluetooth using a VE.Smart Network. For more detail on the
VE.Smart network see the VE.Smart Networking manual.
Alternatively, a VE.Smart Network that measures battery temperature and battery voltage, can also be set up between a solar
charger and a BMV-712 Smart or SmartShunt battery monitor that has been equipped with a Temperature sensor for BMV,
without the need for a Smart Battery Sense.
Note that a VE.Smart Network can only be set up if the solar charger is capable of Bluetooth communication,
has Bluetooth enabled or is equipped with a VE.Direct Bluetooth Smart dongle.
Page 7Features
MPPT solar charger manual
Example of a VE.Smart Network of a Smart Battery Sense and a solar charger.
3.11. Voltage sensing
An optional Smart Battery Sense or battery monitor measures the battery terminal voltage and sends this via Bluetooth using the
VE.Smart [29] network to the solar charger. If the battery voltage is less than the solar charge voltage, the solar charger will
increase its charge voltage to compensate for voltage losses.
3.12. Remote on/off
A virtual remote on/off terminal can be created by using the (optional) VE.Direct non inverting remote on/off cable.
3.13. WireBox
The optional MPPT WireBox is a plastic cover that can be attached to the bottom of the solar charger. It covers the battery and
solar terminals, preventing accidental or inquisitive contact with the battery and PV terminals. It provides an extra level of safety,
and is particularly useful if the solar charger is installed in a general access area.
For more information and to find the right MPPT WireBox for your solar charger see the MPPT WireBox product page:
• MPPT WireBox-MC4
• MPPT WireBox-Tr
Example of a solar charger with MPPT WireBox
Page 8Features
MPPT solar charger manual
4. Installation
The DC (PV) input is not isolated from the battery circuit. Therefore the PV, battery and control circuit are
considered hazardous and should not be user accessible.
For proper temperature compensated battery charging the ambient temperature of the solar charger and the
battery must be within 5°C (9°F).
The battery and PV connections must be guarded against inadvertent contact. Install the solar charger in an
enclosure or install the optional WireBox [8].
4.1. Mounting
Mount the solar charger vertically on a non-flammable substrate, with the electrical terminals facing downwards.
The Dimension drawings [61] chapter of this manual contains the dimension drawing of the solar charger, this drawing also
indicates the mounting holes.
Observe a minimum clearance of 10cm under and above the solar charger for optimal cooling.
Mount the solar charger close to the battery, but never directly above the battery. This is to prevent damage due to gassing of the
battery.
Avoid ambient temperature differences of more than 5°C between the solar charger and the battery. These
temperature differences can lead to incorrect temperature compensated charging, which can reduce the
battery lifetime.
If large temperature differences or extreme ambient temperature conditions are expected, use a direct battery
temperature sense source like the Smart Battery Sense or a BMV or SmartShunt equipped with a temperature
sensor.
If the optional MPPT WireBox is used:
• For solar chargers with screw PV terminal use the MPPT WireBox TR.
• For solar chargers with MC4 PV terminals use the MPPT WireBox MC4.
• Affix the steel WireBox base to the solar charger before the solar charger is mounted into its final position.
• For full mounting instructions, see the MPPT WireBox TR or MPPT WireBox MC4 quick installation guide.
4.2. Battery
The battery supply must be protected by a fuse as per the below table.
Solar charger typeMinimum battery fuse ratingMaximum battery fuse rating
MPPT 150/60 and 250/6070A80A
MPPT 150/70 and 250/7080A100A
For Canada the battery fuse must comply with the C22.2 standards.
The battery installation must be done in accordance with the local storage battery rules. For Canada this is the
Canadian Electrical Code, Part I.
Use flexible multi stranded copper cable for the battery connections Also see chapter Wiring safety
precautions [1].
4.3. PV array
The solar charger can be used with a PV configuration that satisfies both these two conditions:
Page 9Installation
MPPT solar charger manual
• The maximum open circuit PV voltage can not exceed 150V.
• The nominal PV voltage should be at least 5V higher than the battery voltage.
The PV array can consist of mono- or poly-crystalline panels.
The solar panels are connected in series, in parallel or in series/parallel. See below figure for examples of these configurations.
120 W
12 V
To help calculate the size of the PV array configuration use the MPPT sizing calculator. Alternatively, use one of these PV array
configurations:
PV array example 24V battery with 150V solar charger:
• Minimum number of cells in series: 72 (2x 12V panel in series or 1x 24V panel).
• Recommended number of cells for highest controller efficiency: 144 cells (4x 12V panel or 2x 24V panel in series).
240 W
24 V
10 A
120 W
12 V
120 W
12 V
Examples of series, parallel and series/parallel solar arrays.
240 W
12 V
20 A
120 W
12 V
120 W
12 V
120 W
12 V
480 W
24 V
20 A
120 W
12 V
120 W
12 V
• Maximum: 216 cells (6x 12V or 3x 24V panel in series).
PV array example 48V battery with 150V solar charger:
• Minimum number of cells in series: 144 (4x 12V panel or 2x 24V panel in series).
• Maximum: 216 cells (6x 12V or 3x 24V panel in series).
• Provide a means to disconnect all current-carrying conductors of a photo-voltaic power source from all other
conductors in a building or other structure.
• Careful: when calculating the number of panels that can be used in series, make sure to take both its Open
circuit voltage (Voc) and its Temperature coefficient into account. At ambient temperatures below 25°C, the
Voc will be higher.
• A switch, circuit breaker, or other device, either AC or DC, shall not be installed in a grounded conductor if
operation of that switch, circuit breaker, or other device leaves the grounded conductor in an un-grounded
state while the system remains energized.
• Do not use solar panels with optimizers. In worst case, the use of optimizers will cause irreparable damage
to the solar charger.
• Use flexible multi stranded copper cable for the screw connections (Tr model). See chapter Wiring safety
precautions [1].
• For MC4 models: several of the solar charger's MC4 pairs may be needed to parallel solar panel strings. Be
aware that the maximum current through a MC4 connection cannot exceed 30A.
4.4. Grounding
Battery grounding
The solar charger can be installed in a positive or in a negative grounded system.
Page 10Installation
MPPT solar charger manual
Apply a single ground connection, preferably close to the battery, to prevent system issues or ground loops.
PV array grounding
The positive and negative of the PV array should not be grounded.
Ground the frame of the PV panels to reduce the impact of lightning.
Do not connect the solar charger to a grounded PV array. Only one ground connection is allowed, and this should be near the
battery.
Ground fault detection
The solar charger does not have internal ground fault protection.
The USA National Electrical Code (NEC) requires the use of an external ground fault protection device (GFPD).
The system electrical negative should be bonded through a GFPD to earth ground at one (and only one) location.
When a ground fault is indicated, battery terminals and connected circuits may be un-grounded and
hazardous.
4.5. Connection overview
IDDescription
AGround screw.
BRotary switch.
CLEDs.
DVE.Direct socket.
EBattery screw terminals.
FPV screw terminals.
GRelay screw terminals.
HRemote on/off terminals.
TR Model.
MC4 model.
4.6. Electrical connections
WARNING: Check the polarity before connecting the battery and PV voltage.
WARNING: Follow the correct installation procedure described in this chapter.
IMPORTANT: Torque the battery and PV connections at 2.4Nm.
Page 11Installation
MPPT solar charger manual
Connection order electrical connections:
1. Connect the battery: allow the solar charger to automatically recognise the system voltage (wait 10 seconds).
2. It is recommended to verify system voltage: use VictronConnect or an external control display.
3. Connect the PV.
4. Connect the applicable other connections: such as the remote on/off connector, the programmable relay connectoror the
VE.Direct port.
The correct connection order is necessary to allow the automatic system voltage detection to setup properly. It is only allowed to
connect PV first when the system voltage is manually set before connecting the battery. Not following the correct procedures can
disable or damage the charger and/or the installation.
See the below figure on how the basic electrical connections are made:
IDDescription
ASolar charger, on the left the Tr model and on the right the MC4 model.
BBattery or battery bank, lead acid or lithium.
CSolar panel or solar panel array.
DDC loads.
DC fuse.
4.7. Connect the MPPT Control display
Connect the (optional) MPPT Control display to the VE.Direct port of the solar charger using a VE.Direct cable.
The VE.Direct cable is available in a variety of lengths and is not included with the MPPT control display. Note that it is not
possible to extend the VE.Direct cable, the maximum length can not exceed 10 meters.
For more information, see the MPPT Control manual.
Page 12Installation
MPPT solar charger manual
Connect the display to the solar charger via a VE.Direct cable
Page 13Installation
MPPT solar charger manual
5. Configuration and settings
The solar charger settings can be configured so it can be taylored specifically for the system it is used in.
Do not change solar charger settings unless you know what they are and what the effect of changing these
settings is going to be.
Incorrect settings may cause system problems including damage to batteries. When in doubt, seek advice
from an experienced Victron Energy installer, dealer or distributor.
5.1. How to change settings
There are several methods that can be used to change these settings. Some of these allow all settings to be configured, but
others might have limitations:
• The VictronConnect app - All settings can be changed and the firmware can be updated.
• The rotary switch - The charge algorithm for a number of pre-set battery types can be selected.
• The MPPT Control display (optional) - Most settings can be changed.
Do not change solar charger settings unless you know what they are and what the effect of changing these
settings can be. Incorrect settings may cause system problems including damage to batteries. When in doubt,
seek advice from an experienced Victron Energy installer, dealer or distributor.
5.1.1. Settings via the VictronConnect app
The VictronConnect app can be used to change all solar charger settings and can be used to update the firmware.
See the VictronConnect app [4] chapter for an overview of the different ways the VictronConnect app can connect to the solar
charger.
This manual only covers the VictronConnect app solar charger-specific items. For more general information on the
VictronConnect app, like how to use it or how to connect, see the VictronConnect manual.
To access the solar charger settings, navigate to the settings page. Do this by clicking on the cog icon at the top right of the
home screen.
The settings page provides access to view and/or to change the solar charger settings.
For information about each setting and how to update firmware see the Updating firmware [28] chapter.
5.1.2. Settings via the rotary switch
The rotary switch can be used to select eight pre-programmed battery charge algorithms.
Page 14Configuration and settings
MPPT solar charger manual
Use a small flathead screwdriver to turn the rotary switch. The arrow indicates which setting number has been selected.
The table below indicates the charge algorithm and charge settings for each rotary switch position.
Rotary switch set to position 2
Turning the rotary switch will override the charge settings including settings that were made with the
VictronConnect app or with the display. Likewise, if charge settings are changed with the VictronConnect
app or the display, this will override the rotary switch setting.
Switch
position
0
1
2
3
4
5
Suggested
battery type
Gel long life
(OPzV)
Gel Exide A600
(OPzV)
Gel MK
Gel Victron
deep discharge
Gel Exide A200
AGM Victron
deep discharge
Stationary
tubular plate
(OPzS)
Default setting
Gel Victron
deep discharge
Gel Exide A200
AGM Victron
deep discharge
Stationary
tubular plate
(OPzS)
AGM spiral cell
Stationary
tubular plate
(OPzS)
Rolls AGM
PzS tubular
plate traction
batteries or
OPzS batteries
PzS tubular
plate traction
batteries or
OPzS batteries
* The top value is for 12V systems, the middle for 24V systems and the bottom for 48V systems.
** Equalize is by default disabled. To enable see chapter Battery settings [17]
Absorption
voltage* (V)
14.1
28.2
56.4
14.3
28.6
57.2
14.4
28.8
57.6
14.7
29.4
58.8
14.9
29.8
59.6
15.1
30.2
60.4
Float
voltage*
(V)
13.8
27.6
55.2
13.8
27.6
55.2
13.8
27.6
55.2
13.8
27.6
55.2
13.8
27.6
55.2
13.8
27.6
55.2
Equalize**
voltage* (V)
15.9
31.8
63.6
16.1
32.2
64.4
16.2
32.4
64.8
16.5
33.0
66.0
16.7
33.4
66.8
16.9
33.8
67.6
Equalize**
nominal
current
percentage
8%
8%
8%
8%
25%
25%
factor* (mV/°C)
Temperature
compensation
-16
-32
-64
-16
-32
-64
-16
-32
-64
-16
-32
-64
-16
-32
-64
-16
-32
-64
Page 15Configuration and settings
MPPT solar charger manual
Switch
position
6
7
A binary LED code helps determining the position of the rotary switch. After changing the position of the rotary switch, the LEDs
will blink during 4 seconds as indicated in below table. Thereafter, normal indication resumes, as described in the LEDs section.
Switch positionBulk LEDAbsorption LEDFloat LEDBlinking frequency
Suggested
battery type
PzS tubular
plate traction
batteries or
OPzS batteries
Lithium Iron
Phosphate
(LiFePo4)
batteries
* The top value is for 12V systems, the middle for 24V systems and the bottom for 48V systems.
** Equalize is by default disabled. To enable see chapter Battery settings [17]
0111Fast
1001Slow
2010Slow
3011Slow
4100Slow
5101Slow
6110Slow
7111Slow
Absorption
voltage* (V)
15.3
30.6
61.2
14.2
28.4
56.8
Float
voltage*
(V)
13.8
27.6
55.2
13.5
27.0
54
Equalize**
voltage* (V)
17.1
34.2
68.4
n/an/a
Equalize**
nominal
current
percentage
25%
Temperature
compensation
factor* (mV/°C)
-16
-32
-64
0
0
0
5.1.3. Settings via MPPT Control display
The optional MPPT Control display can be used to configure solar charger settings, with the exception of advanced settings such
as RX and TX port settings. For information on how to do this see the MPPT Control manual.
The MPPT Control
Although the MPPT Control can connect to the solar charger, consider using a SmartSolar control display
instead.
5.2. All settings explained
This chapter lists all solar charger settings that are user-configurable and also explains how to update firmware of the solar
charger.
Do not change settings unless you know what they are and what the effect of changing these settings will
be. Incorrect settings may cause system problems including damage to batteries. When in doubt, seek advice
from an experienced Victron Energy installer, dealer or distributor.
Page 16Configuration and settings
5.2.1. Battery settings
MPPT solar charger manual
Battery voltage
The battery voltage is automatically detected at the very first power-up of the solar charger and the battery voltage is set
accordingly. Further automatic detection is disabled. To make sure that a stable measurement is used, the charger first waits 10
seconds, and thereafter takes an averaged measurement. Note that the solar charger will remain off during this time.
In case the solar charger does not measure a battery voltage, it will default to 12V and store that. This will happen if the solar
charger is powered via its PV terminals, while not connected to a battery.
Note that the solar charger will not automatically detect a 36V battery. This will need to be set manually.
After automatic detection has taken place, the battery voltage can be changed and set to 12, 24, 36 or 48V, if so required .
Tip:
If the firmware of the solar charger needs to be updated, while keeping the automatic voltage detection active,
for example before shipping the unit to an end-user, do the following:
• Update the firmware.
• Once the firmware update is complete, go to the settings page in the VictronConnect app.
• On the settings page, click on the three vertical dots in the upper right corner and select "Reset to defaults”
from the drop-down menu.
• Un-power the solar charger within 10 seconds.
The next time that the unit is powered up, it will perform the initial automatic voltage detection.
Max charge current
This setting sets the maximum battery charge current. It is by default set to the maximum solar charge current.
Use this setting to reduce the charge current, for example, when a smaller battery bank is used that requires a lower charge
current.
Charger enabled
This setting enables or disables the battery charger. It is by default set to "enabled".
This setting can be used when work needs to be carried out on the installation. When this setting is disabled, the batteries will not
be charged.
Battery preset
This setting sets the battery charge algorithm. It is by default set to "rotary switch".
A selection can be made between:
Page 17Configuration and settings
MPPT solar charger manual
• The rotary switch position.
• Pre-defined factory battery presets.
• User-defined battery presets.
• Create, modify or delete a user-defined preset.
This setting uses factory pre-defined presets for a large variety of battery types. These pre-defined charge algorithms are suitable
for almost all installations.
It is possible to also create user-defined battery presets. The chapter Customize battery charge algorithm [18] explains how to
do this. These user-defined presets are stored in the VictronConnect app library. This is helpful in case multiple solar chargers
need to be configured, eliminating the need to define the entire charge algorithm each time a new solar charger is configured.
Expert mode
This setting enables or disables expert mode. It is by default set to "disabled".
The default charge algorithms work well for almost all installations. Only enable expert settings if your
equipment has special requirements.
When this setting is enabled the following parameters can be configured:
• Charger voltages: bulk, absorption and float.
• Bulk: re-bulk voltage offset.
• Absorption: duration, time and tail current.
• Equalization: current, interval, stop mode and duration.
• Temperature voltage compensation.
• Low temperature cut off.
For the meaning of these parameters see chapter Battery charge algorithm settings [20].
Equalization
Equalization can cause damage to the battery if the battery is not suitable for an equalization charge. Always
check with the battery manufacturer prior to enabling equalization.
This setting can be used to disable or enable automatic equalization. When enabled, the number of days can be selected when
equalization should repeat.
A manual equalization can be initiated by pressing the "START NOW" button. Use the manual equalize option only during
absorption and float charge stages, and when there is sufficient sunlight. The current and voltage limits are identical to the
automatic equalize function. The manual equalization stage lasts 1 hour and can be stopped at any time by the Stop Equalize.
The equalization setting might not be active, this can be the case if the battery preset does not support an
equalization charge which is the case with lithium batteries.
Customize battery charge algorithm
This chapter explains how to modify a battery charge algorithm or to create, modify and delete user defined battery presets. See
the Battery charge algorithm settings [20] chapter for the meaning of all charge algorithm parameters.
Page 18Configuration and settings
MPPT solar charger manual
Only experienced users should configure or edit user defined battery charge algorithms. A wrongly defined
battery charge algorithm can lead to battery damage or create unsafe situations.
To Modify a basic battery charge algorithm:
• Select a preset battery type that is the best match to your battery type.
• Change one of the basic charge parameters that are listed on the settings screen.
• Configure the required parameters.
• The battery preset is now set to "user defined".
To Modify an expert battery charge algorithm
• Enable "Expert" mode.
• The basic and additional charge parameters are now listed on the screen.
• Configure the required parameters.
• The battery preset is now set to "user defined".
To create and save a custom battery type:
• Select a preset battery type that is the best match to your battery type.
• Change the charge parameters so they match your battery. This can be done either in normal mode or in expert mode.
• The battery preset is now set to "user defined".
• Select in the "Battery preset" menu "Create preset".
• Give the preset battery a name.
To load a custom battery type:
• Select in the "Battery preset" menu "Select preset".
• The menu lists all factory preset and custom battery types that were previously added (if any).
• Select the battery type of your choice.
To modify (or delete) a custom battery type:
• Select in the "Battery preset" menu "Edit presets"
• Navigate to the battery you want to modify. It is not possible to modify a factory preset, only custom types can be modified (or
deleted).
• Modify the charge parameters.
Page 19Configuration and settings
MPPT solar charger manual
• To save the settings press the "SAVE CHANGES" button at the bottom of the page.
• To delete the battery, press the "REMOVE PRESET" button.
Battery charge algorithm settings
This chapter explains all parameters that are used in "Expert" mode and the settings that are used when programming a custom
battery type via the battery preset menu.
Absorption voltage
This setting sets the absorption voltage.
Adaptive absorption time
This setting enables or disables the adaptive absorption time.
• When disabled: The length of the absorption stage is the same each day, the length is determined by the "Maximum
absorption time" setting, provided there is enough solar power.
Be aware that this option can potentially result in overcharging your batteries, especially for lead batteries and if only shallow
daily discharges take place. Check with the battery manufacturer for the recommended maximum absorption time.
The only condition that can end the absorption time before the maximum time has been reached, is the "tail current" setting. If
the absorption time always needs to be the same length, then disable the "Tail current" setting. See more information on the tail
current setting further down in this chapter.
• When enabled: The length of the absorption stage is different each day, it adapts itself to the state of charge of the battery in
the morning at the beginning of the charge cycle.
The maximum "adaptive" absorption time for the day is determined by the battery voltage as measured just before the solar
charger begins operation each morning.
Multiplierx 1x 2/3x 1/3x 1/6
Adaptive absorption
time *
12V systemVbatt < 11.9V
24V systemVbatt < 23.823.8 < Vbatt < 24.2V
48V systemVbatt < 47.6
*) The adaptive absorption time is calculated by the multiplier times the "Maximum absorption time" setting. The adaptive
absorption times in this table are based on the 6 hour default "Maximum absorption time" setting.
6:00 hours4:00 hours2:00 hours1:00 hour
11.9V < Vbatt <
12.2V
47.6V < Vbatt <
48.8V
12.2V < Vbatt <
12.6V
24.2V < Vbatt <
25.2V
48.8V < Vbatt <
50.4V
Vbatt > 12.6V
Vbatt > 25.2V
Vbatt > 50.4
Maximum absorption time
This setting sets the absorption time limit. This setting is only available when programming a custom charge profile.
Page 20Configuration and settings
MPPT solar charger manual
Enter the maximum time in hours and minutes (hh:mm) the solar charger is allowed to spend in the absorption stage. The
maximum time that can be set is 12 hours and 59 minutes.
Float voltage
This setting sets the float voltage.
Re-bulk voltage offset
This setting sets the re-bulk voltage offset. This offset voltage is used to determine when a charge stage stops and the bulk stage
starts again, i.e. the charge cycle resets and starts at the first charge stage again.
The re-bulk voltage is calculated by adding the re-bulk voltage offset to the lowest voltage setting (normally this is the float stage).
An example: If the re-bulk offset is set at 0.1V and the float voltage at 13.8V, the charge cycle will restart once the battery voltage
drops below 13.7V (13.8 minus 0.1) for one minute.
Equalization voltage
This setting set the equalization voltage.
Equalization current percentage
This setting sets the percentage of the "maximum charge current" setting that will be used to calculate the equalization charge
current.
For example: If the "maximum charge current" setting is set at 10A and the "Equalization current percentage" setting is set to
10%, the Equalization current will be 1A (10% of 10A).
Automatic equalization
This setting sets the repeat interval when the equalization stage should take place. This can be set between 1 and 250 days.
Setting to 1 means a daily equalization, 2 means every other day and so on.
An equalization stage is typically used to balance the cells and also to prevent stratification of the electrolyte in flooded lead-acid
batteries. If equalization is needed or not depends on the type of battery if (automatic) equalization is needed and under what
conditions. Check with the battery supplier to find out if equalization is needed for the battery.
During the equalization stage, the charge voltage increases up to the set "Equalization voltage". This is maintained as long as the
charge current stays below the "equalization current percentage" setting of the "Maximum current" setting.
Duration of the Automatic equalization cycle:
• For all VRLA battery presets and for some flooded battery presets, the automatic equalization stage ends when the voltage limit
(maxV) has been reached.
• For the lithium battery preset, equalization is not available.
• When an automatic equalization stage has not been completed within one day, it will not resume the next day. The next
equalization surge will take place according to the interval as set in the "Auto Equalization" setting.
Equalisation stop mode
This setting determines when the equalisation stage should end:
• Automatic: Equalization stops if the battery voltage has reached the equalisation voltage.
• Fixed time: Equalization stops when the time has reached the time as set in the "Maximum equalization duration" setting.
Maximum equalization duration
This setting sets the maximum time that the equalization stage will last.
Manual equalization
Use this to perform a "once-off" equalization. Once the "start now" button is pressed, a one-hour equalization cycle will be
performed, alternatively, the equalization stage can be stopped manually.
Tail current
This setting sets the current threshold to end the absorption stage before the maximum absorption time has been reached. If the
charge current drops below the set tail current, for one minute, the absorption stage will end and the float stage will start. This
setting can be disabled by setting it to zero.
Temperature compensation
This setting sets the temperature compensation coefficient that is needed for temperature compensated charging.
Many battery types require a lower charge voltage in warm operating conditions and a higher charge voltage in cold operating
conditions. The configured coefficient is in mV per degree Celsius for the whole battery bank, not per cell. The base temperature
for the compensation is 25°C (77°F).
Page 21Configuration and settings
MPPT solar charger manual
The chart below indicates the absorption and float charge voltage behaviour at different temperatures. The graph displays the
temperature compensation for a 12V system and uses a -16mV/°C temperature compensation coefficient. For a 48V system
multiply by 4.
Temperature compensated charge graph
By default, the solar charger uses its internal temperature for battery temperature compensated charging. An internal temperature
reading is taken in the morning and then again when the e solar charger has been idle for at least one hour, for example when the
charger is not actively charging a battery or supplying a load.
When the solar charger is part of VE.Smart Networking and receives a battery temperature reading from a Battery Sense or a
battery monitor with a temperature sensor, the actual battery temperature will be used for temperature compensated charging
throughout the day.
Low temperature cut-off
This setting is used to prevent damage to a lithium battery by disabling charging at low temperatures.
The "Low temperature cut-off" feature is only active when the solar charger is part of a VE.Smart network and
is receiving a battery temperature reading from a Battery Sense or a battery monitor with temperature sensor.
The "low temperature cut-off" setting is by default disabled. When enabled, a low cut off temperature can be set. The default
temperature is 5°C, this is a suitable temperature setting for lithium iron phosphate (LFP) batteries. However, always check with
the lithium battery supplier to find out what this temperature should be set at.
The "low temperature cut-off" mechanism will stop battery charging when the battery temperature has dropped below the low
temperature cut-off setting. Battery charging will resume once the battery temperature has risen 0.5°C above the low temperature
cut-off setting.
Note that setting "low temperature cut-off" is not needed for Victron Lithium Smart batteries or for Victron Super Pack batteries
with serial number HQ2040 and above. This setting is only needed for lithim batteries that are unable to block charging when the
temperature drops too low.
5.2.2. Load output settings
The load output settings used to control the VE.Direct TX port [26] or the , enabling it to operate a BatteryProtect, a relay or
another load-shedding device. For more information, see the chapter TX port settings [26].
Page 22Configuration and settings
MPPT solar charger manual
The available operation modes are:
• BatteryLife (default setting):
This algorithm is self-adapting and aims to maximise the battery's lifespan. For a detailed explanation of its functionality, please
refer to the BatteryLife [6] chapter for a description of its functionality.
• Conventional algorithm 1:
12V system: OFF when Vbatt < 11.1V, ON when Vbatt > 13.1V.
24V system: OFF when Vbatt < 22.2V, ON when Vbatt > 26.2V.
48V system: OFF when Vbatt < 44.4V, ON when Vbatt > 52.4V.
• Conventional algorithm 2:
12V system: OFF when Vbatt < 11.8V, ON when Vbatt > 14.0V.
24V system: OFF when Vbatt < 23.6V, ON when Vbatt > 28.0V.
48V system: OFF when Vbatt < 47.4V, ON when Vbatt > 56.0V.
• Always off:
The load output is always OFF.
• Always on:
The load output is always ON.
• User defined algorithm 1:
OFF when Vbatt < Vlow.
ON when Vbatt > Vhigh.
• User defined algorithm 2:
OFF when Vbatt < Vlow or Vbatt > Vhigh.
ON when Vbatt is between Vlow and Vhigh.
The "always off" and the "always on" modes will respond immediately. The other modes have a 2-minute delay before the load
output changes. This is so that the solar charger does not respond too quickly when, for example, an inrush current briefly lowers
the battery voltage below the threshold.
The load output settings also control the streetlight [23] algorithm. Both work together to protect the battery from being too
deeply drained. The streetlight settings are overridden should the battery voltage falls below the load disconnect voltage. When
the battery voltage increases to the load reconnect voltage, the streetlight function will resume.
5.2.3. Streetlight settings
The streetlight function enables the solar charger to automatically control night lighting. It will automatically determine when the
light should be on or off and can control the light intensity.
Page 23Configuration and settings
MPPT solar charger manual
When the streetlight function is enabled a timer program can be created whereby Sunset, Sunrise as well as Midnight can be
used as anchor points for the timer program. These anchor points will automatically adjust depending on length of the night as
this changes with the seasons.
Streetlight control
The solar charger controls the streetlight:
• Via the TX port together with a VE.Direct TX digital output cable. Also see the TX port settings [26] chapter for more details.
• Via the programmable relay. Also see the ??? chapter for details.
The streetlight algorithm is always applied in conjunction with the settings as configured in the Load output
menu:
• If the streetlight is disabled, then the (virtual) load output is controlled only by the configuration as made in
the load output menu.
• If streetlight is enabled, then it's an AND function: the load output will be on when both the conditions made
in the Load output menu are satisfied as well as the streetlight settings. Otherwise, it's off.
Make sure that load output setting is set to "Always on" or to "BatteryLife". Do not set it to "Always off" as this
will result in the light being always off.
For more configurable voltage levels to force the light off, the other load output options can also be used.
Setting the Sunset action
At sunset you can choose any of the following actions:
• Keep the lights off
• Switch on for a fixed time:
This option will turn the light on at sunset, and then off again after a configurable interval. When the dimming feature is
enabled1 (1), two dim-levels can be entered: one for the “on” period; and a second for the “off” period. A typical use case for
these options is to get a strong light during high traffic hours (right after sunset), and lower intensity during the low hours, to
save the battery. Set the second dim level to 0% to switch the light completely off during that second section.
• Switch on till midnight:
This option turns the light on at sunset, and then off again at midnight. When the dimming feature is enabled1, two dim-levels
can be entered: one for the “on” period (up to midnight) and a second dim-level for the “off” period after midnight. Set the
second dim level to 0% to switch the light completely off during that second section.
• Switch on till sunrise:
This options turns the light on at sunset, and then off again at sunrise. When this option is selected; there is no need to also
select an action at sunrise, so the sunrise control option is not needed. When the dimming feature is enabled1, only one dim
level can be configured, the dim level at sunset.
Page 24Configuration and settings
MPPT solar charger manual
1)
The dimming feature requires the TX Port function to be configured to one of the "Light dimming" settings. This so the TX port
outputs a PWM signal that can be used to dim the light. If the TX port function has not been set to one of the "Light dimming"
settings, the dimming options will not appear in the sunset settings menu. Also see the TX port settings [26] chapter.
Setting the Sunrise action
At sunrise you can choose to:
• Switch off:
Turns the light off at sunrise.
• Switch on before sunrise:
This option switches the light on at a configurable time interval before sunrise, and then switches the light off at sunrise.
In case the dimming feature is enabled1 an interval of more intense light can be configured during early morning rush hour.
Together with the Sunset action, you can now configure three dim levels: one for the sunset rush hours, one during the low
traffic hours, and the third for the early morning rush hours.
Midnight
The charger has no real time clock, and therefore does not know when it is 12 o'clock at night. All references to midnight refer to
what we call solar midnight, this is the mid-point between sunset and sunrise.
Midnight and Sunrise synchronisation
The solar charger needs to have its internal clock synchronised with the solar cycle so it can set the solar midnight and sunrise
anchor points in the timer program.
After the streetlight settings have been programmed and the solar charger is powered up, the solar charger will start
unsynchronised. It will first assume that midnight is 6 hours after sunset, and that the full night last for 12 hours.
Once in operation, the solar charger will check the time between each detected sunrise. After three full day/night cycles, where
the detected time is approximately 24 hours (one hour of deviation is allowed), it will start using its internal clock, instead of the
fixed 6 and 12 hour timing.
A loss of power (no battery power together with no PV power) will cause the solar charger to loose its
synchronisation. It will take 5 days before it is re-synchronised. Note that the streetlight configuration settings
and all other settings will never be lost, they are stored in a non-volatile memory.
Sunset and sunrise detection
The sunset and sunrise detection voltage settings can be used to adjust the detection to match the panel configuration. The
sunrise detection voltage must be 0.5V higher than the sunset detection level. The lowest detectable voltage is 11.4V. Set this
option to 0 to use the built-in defaults, which are:
• Sunset = Vpanel < 11.4V.
• Sunrise = Vpanel > 11.9V.
The default setting is 0, which uses built-in default voltages.
Use the "Delay" periods to avoid the system making an accidental switch when clouds pass over the panels. The valid range is
between 0 and 60 minutes. The "Delays" are disabled by default (0).
Gradual dimming speed
The gradual dimming option can be used to slow down the response of the timer program. This is useful when multiple
streetlights are used in a row. This helps to mask the fact that each timer uses its own detection and will have a transition moment
which will vary from unit to unit.
The dimming settings can be adjusted. You can input the number of seconds required to achieve each percentage-point of
change (x seconds/per 1% of dimming). A number from 0 to 100 can be entered. Two examples:
A setting of 0 will achieve an immediate response, this effective means that the gradual dimming option is disabled.
• 9 = dim from 0 to 100% in 15 minutes:
Setting the dimming speed to 9, for example, slows down the dimming speed to 15 minutes (9 seconds for each percentage
point of dimming x 100 percentage points = 900 seconds = 15 minutes.
Make sure that the TX port function is set to "Light dimming" mode (as described in point 1 at the beginning of
this chapter) and connect a VE.Direct TX digital output cable to the PWM dim input of your LED driver.
Mid-point shift
Page 25Configuration and settings
MPPT solar charger manual
The time of midnight is estimated based on solar activity, and depends on your geographical location. Daylight saving times can
cause a further deviation between the "solar" and the "clock" midnight. The Mid-point shift function will compensate for these
differences. Use 0 to disable the shift (default).
The Mid-point shift setting is only relevant when your streetlight setting program uses "Midnight" as a
switching moment.
Calculation Example:
For calculation we use a day of 1440 minutes, where Sunset is at 19:00 (1140 minutes) and Sunrise is at 6:25 (385 minutes):
• The night duration in minutes is: 1440m
• The degree of shift = time of sunset
(minutes)
(min/day)
-1140m(time to sunset) + 385m
+ half the duration of night
(minutes)
(time to sunrise)
- length of day
= 685m.
(minutes)
= 1140m + 342m - 1440m =
42 minutes.
Example configuration
The selections which have been made on above screen image results in this program:
• At sunset - the light will be switched on for a fixed time.
• Dim level at sunset - at Full brightness (100%).
• Keep lights on during - the duration has been set to 1h 0m.
• Dim level at end - at the end of one hour the brilliance will be reduced to half (50%).
Also:
• At sunrise - the lighting will be adjusted before sunrise.
• Time before sunrise - at 1h 0m before sunrise, the following adjustment will be made:
• Dim level - full brilliance will be restored (100%).
5.2.4. TX port settings
The VE.Direct-TX port can be used to send a signal to an external device. For example, to send a PWM signal to dim a
streetlight.
To use the TX port, a VE.Direct TX digital output cable is needed.
Page 26Configuration and settings
The functionality of the TX port can be set at:
MPPT solar charger manual
• Normal communication:
This is the default setting. Use this function when connecting to a GX device, a VE.Direct Bluetooth Smart dongle, or any other
device that needs to communicate with the solar charger via the VE.Direct port.
• Pulse every 0.01 kWh:
Use this function in combination with an energy meter.
The TX port will emit a pulse each time an additional 0.01kWh of energy has been harvested. The TX port is normally high and
will be driven low for approximately 250ms for every 0.01kWh harvested.
• Light dimming (PWM normal):
Use this function in combination with the "Streetlight" setting.
The TX port PWM* signal will be at 100% duty cycle when full light intensity is required.
• Light dimming (PWM inverted):
Use this function in combination with the "Streetlight" setting.
The TX port PWM* signal will be at 0% duty cycle when full light intensity is required.
• Virtual load output:
Use this function to create a virtual load output if the solar charger does not have a physical load output.
The TX port will switch using the same conditions as set in the load output settings.
Connect the VE.Direct TX digital output cable to a BatteryProtect module, a relay or directly to the remote on/off connector of
the load**.
*) The PWM signal is 5V, 160Hz.
**) The TX port is a logic 5V signal. It can drive a maximum of a 22kOhm impedance load, where the output voltage is dropped to
3.3V. Make sure that the connected load is within this specification.
Note that these functionalities (other than the first functionality) do not disable the ability of the unit to communicate. What
happens is that the unit will automatically detect incoming data, and while data is being received, it will resume normal
communication. Once the data reception has been completed, it will automatically return to its configured TX function.
For more in-depth "developer style" information on the VE.Direct port see the Data communication with Victron Energy products
document.
5.2.5. RX port settings
The VE.Direct-RX port can be used to receive a signal from an external device. For example to switch the solar charger on (or off)
from a signal sent by a battery management system (BMS).
To use the RX port for remote on/off control a VE.Direct non inverting remote on/off cable is needed.
Page 27Configuration and settings
The functionality of the RX port can be set at:
MPPT solar charger manual
• Remote on/off:
This is the default setting. This functionality will switch the solar charger on or off via the RX pin.
- RX pin to GND will switch the solar charger off.
- RX pin floating or to battery positive will switch the solar charger on.
• Load output on/off inverted:
This setting reverses the load output on/off control:
- RX pin 0V will switch load output on.
- RX pin +5V will switch load output off.
• Load output on/off normal:
This setting allows load output on/off control:
- RX pin 0V will switch the load output off.
- RX pin +5V will switch load output on.
For more in depth "developer style" information on the VE.Direct port see the Data communication with Victron Energy products
Whitepaper.
5.3. Updating firmware
The firmware can be checked and updated with the VictronConnect app.
The VictronConnect app might ask on the first connection to update the firmware. If this is the case, let it perform a firmware
update.
If it did not automatically update, check if the firmware is already up to date using the following procedure:
• Connect to the solar charger.
• Click on the settings symbol
• Click the options symbol .
• Go to product info.
• Check if you are running the latest firmware and look for the text: “This is the latest version”.
• If the solar charger does not have the most up-to-date firmware, perform a firmware update.
Page 28Configuration and settings
.
5.4. VE.Smart Networking
MPPT solar charger manual
VE.Smart Networking allows a variety of products connected to the same network to share data via Bluetooth and is specially
designed for smaller systems that do not have a GX device installed.
When this product is part of a VE.Smart Network, it can receive data or communicate with the following devices:
• All SmartSolar solar chargers.
• All BlueSolar solar chargers connected to a VE.Direct Bluetooth Smart dongle.
• The Smart Battery Sense.
• A BMV or SmartShunt battery monitor equipped with Bluetooth (or VE.Direct Bluetooth Smart dongle) and an optional BMV
temperature sensor.
• Certain Smart AC chargers.
• The SUN inverter.
For the product compatibility list see the VE.Smart manual located on the VictronConnect app product page.
VE.Smart Networking can be used for:
• Temperature sensing - the measured battery temperature is used by the chargers in the network for temperature compensated
charging and in case of lithium battery for the low temperature cut off.
• Battery voltage sensing - the measured battery voltage is used by the chargers in the network to to compensate the charge
voltage should there be a voltage drop over the battery cables.
• Current sensing - The measured battery current is used by the charger so it knows the exact tail current at which the absorption
stage should end and the float (or equalisation) stage should start. To measure the charge current all charge currents from all
chargers are combined, or if a battery monitor is part of the network the actual battery current will be used.
• Synchronised charging - All chargers in the network will act as they were one large charger. One of the chargers in the network
will assume a master role and the master will dictate the charge algorithm the other chargers will be using. All chargers will
follow the same charge algorithm and charge stages. The master is selected randomly (not user settable) so it is important
that all chargers use the same charge settings. During synchronised charging each charger will charge up to its own maximum
charge current setting (it is not possible to set a maximum current for the whole network). For more information see the
VE.Smart manual located on the VictronConnect app product page.
This video introduces the Smart Battery Sense and some features of VE.Smart Networking:
https://www.youtube.com/embed/v62wCfXaWXY
5.4.1. VE.Smart Networking setup
VE.Smart Networking design notes:
Page 29Configuration and settings
MPPT solar charger manual
There can only be one product in the network that transmits battery voltage and/or battery temperature. It is not possible to use a
battery monitor together with a Smart Battery Sense, or multiple of these devices.
For the network to be operational all networked devices must be within Bluetooth transmission distance of each other.
A maximum of 10 devices can be joined into a VE.Smart Network.
Some older devices might not support VE.Smart Networking. for more information see the Limitations chapter in the VE.Smart
Networking manual.
Setting up the network
When setting up the network, first set up the Smart Battery Sense or battery monitor, and then add one or more solar chargers or
AC chargers to the network.
All solar chargers and AC chargers need to have the same charge settings. The easiest way to do this is to use a preset battery
type or a saved used defined battery type. A warning #66 message will be shown if there is a difference between the devices
charge settings.
To set up a new network:
• Open the VictronConnect app.
• Select one of the devices that needs to become part of the new VE.Smart network.
• Navigate to the settings page by clicking the gear symbol.
• click on "VE.Smart networking".
• Click on "create network".
• Enter a name for the new network.
• Click "save".
• Wait for confirmation that the network has been set up and click "OK".
• If more devices need to be added to this network go to next paragraph and join multiple devices to the network.
To join another device to an existing network:
• Open the VictronConnect app. Select a device that needs to become part of a VE.Direct network.
• Navigate to the settings page by clicking the gear
• Click on "VE.Smart Networking".
• Click on "join existing".
• Select the network the device needs to be joined to.
• Wait for confirmation that the network has been set up and click "OK".
• Repeat above steps if more devices need to be added to the network.
To leave a network:
• Open the VictronConnect app.
• Select a device that needs to be removed from the VE.Direct network.
symbol.
• Navigate to the settings page by clicking the gear
• Click on "VE.Smart Networking".
• Click on "leave network".
Check the network
Once the network has been set up all devices communicate with each other. The active LED on each connected device will now
blink every 4 seconds. This is an indication that the device is actively communicating with the network.
To check if an individual device is communicating with the network, click on the VE.Smart symbol
the solar dail. A pop-up window will open showing the connection status and the shared parameters.
Page 30Configuration and settings
symbol.
in the main screen next to
MPPT solar charger manual
VE.Smart Networking pop-up
To check if all devices are actively communicating with the same VE.Smart Networking, navigate to the settings page of one of
the networked devices and click on "VE.Smart Networking". A screen will be shown containing which device parameters of this
device are shared and all the other devices that are connected to the same network are shown.
Example of a VE.Smart Network
More information
For more information see the VE.Smart Networking manual.
Page 31Configuration and settings
MPPT solar charger manual
6. Operation
6.1. Start up
The solar charger will power up as soon as it has been connected to a battery and/or to a solar panel. As soon as the solar
charger has been powered up, it can communicate via the VE.Direct port . The solar charger's data can be read out and setting
configurations can be made using the VictronConnect or the optional display.
The solar charger will commence battery charging as soon as the PV voltage is 5V higher than the battery voltage. For charging
to continue, the PV voltage must remain at least 1V higher than the battery voltage.
6.2. Battery charging
The charge controller will start a new charge cycle every morning, when the sun starts shining and when the PV voltage is 5V
higher than the battery voltage.
Default method to determine length and end of absorption for Lead-acid batteries
The charging algorithm behaviour of solar chargers differ from AC connected battery chargers. Please read this section of
the manual carefully to understand the solar charging behaviour, and always follow the recommendations of your battery
manufacturer.
The voltage values mentioned in this chapter are for 12V systems, for 24V systems multiply by 2 and for 48V
systems multiply by 4.
By default, the absorption time is determined on idle battery voltage at the start of each day based on the following table:
Battery voltage at start upMultiplierMaximum absorption time
< 11.9Vx 16h
11.9V - 12.2Vx 0.664h
12.2V - 12.6Vx 0.332h
> 12.6Vx 0.161h
The default absorption voltage is 14.4V and the default float voltage is 13.8V.
The absorption time counter starts once switched from bulk to absorption.
The MPPT solar chargers will also end absorption and switch to float when the battery current drops below a low current
threshold limit, the "tail current". The default tail current value is 2A.
The default settings (voltages, absorption time multiplier and tail current) can be modified with the VictronConnect app.
There are two exceptions to normal operation:
• When used in an ESS system; the solar charger algorithm is disabled; and instead it follows the curve as mandated by the
inverter/charger.
• For CAN-bus Lithium batteries, like BYD, the battery tells the system, including the solar charger, what charge voltage to use.
This Charge Voltage Limit (CVL) is for some batteries even dynamic; changes over time; based on for example maximum cell
voltage in the pack and other parameters.
Variations to the expected charging behaviour
Pausing of the absorption time counter:
•
The absorption time counter starts when the configured absorption voltage is reached and pauses when the output voltage is
below the configured absorption voltage. An example of when this voltage drop could occur is when PV power (due to clouds,
trees, buildings) is insufficient to charge the battery and to power the loads.
Restarting the charge process:
•
The charging algorithm will reset if charging has stopped for an hour. This may occur when the PV voltage drops below the
battery voltage due to bad weather, shade or similar.
• Battery being charged or discharged before solar charging begins:
The automatic absorption time is based on the start-up battery voltage (see table). This absorption time estimation can be
incorrect if there is an additional charge source (eg alternator) or load on the batteries. This is an inherent issue in the default
algorithm. However, in most cases it is still better than a fixed absorption time regardless of other charge sources or battery
state. It is possible to override the default absorption time algorithm by setting a fixed absorption time when programming
Page 32Operation
MPPT solar charger manual
the solar charge controller. Be aware this can result in overcharging your batteries. Please see your battery manufacturer for
recommended settings.
• Absorption time determined by tail current:
In some applications it may be preferable to terminate absorption time based on tail current only. This can be achieved by
increasing the default absorption time multiplier (warning: the tail current of lead-acid batteries does not decrease to zero when
the batteries are fully charged, and this “remaining” tail current can increase substantially when the batteries age).
Default settings for LiFePO4 batteries
The default absorption voltage is to 14.2V (28.4V, 56.8V) and the absorption time is fixed and set to 2 hours. The float voltage
is set at 13.5V (27V, 54V). Equalization is disabled. The tail current is set to 0A, this so that the full absorption time is available
for cell balancing. The temperature compensation is disabled and the low temperature cut off is set to 5. These settings are
the recommended settings for LiFePO4 batteries, but they can be adjusted if the battery manufacturer specifications advise
otherwise.
Reset of the charge algorithm:
The default setting for restarting the charge cycle is Vbat < (Vfloat – 0.4 V) for lead-acid, and Vbat (Vfloat – 0.1 V) for LiFePO4
batteries, during 1 minute. These values are for 12 V batteries, multiply by two for 24V and by four for 48V.
6.3. Automatic equalization
Do not equalize charge Gel, AGM, VRLA or lithium batteries.
Equalization can cause damage to the battery if the battery is not suitable for an equalization charge. Always
check with the battery manufacturer prior to enabling equalization.
Automatic equalization is by default disabled. When enabled, it can be configured with a number between 1 (every day) and 250
(once every 250 days).
When automatic equalization is active, the absorption charge will be followed by a voltage limited constant current period. The
current is by default limited to 8% of the bulk current and can be adjusted between 0% and 100%. The bulk current is set by
default to the maximum charge current the solar charger is capable of, unless a lower charge current has been chosen.
The maximum equalization duration is set by default to 1 hour and can be configured between 0 minutes and 24 hours. The
automatic equalization will end when the voltage limit has been reached or when the set maximum equalization duration has been
reached, whichever comes first.
When automatic equalization has not finished within a day, it will not resume the next day. The next equalization session will take
place as determined by the day interval.
6.4. Lithium batteries
Lithium Iron Phosphate (LiFePo4) batteries do not need to be fully charged to prevent premature failure. The default lithium (and
recommended) settings are:
SettingAbsorption voltageAbsorption timeFloat voltage
12V system14.2V2h13.2V
24V system28.4V2h26.4V
48V system56.8V2h52.8V
These settings are adjustable.
6.5. Shutdown and restart procedure
The solar charger is always active when the PV and/or the battery terminals are powered. The solar charger does not have an
on/off switch.
To shut down the solar charger, perform these steps in the prescribed order:
1. Disconnect the PV supply to the solar charger by switching the PV supply off or by removing the external fuse(s) or circuit
breaker(s).
2. Disconnect the battery supply to the solar charger by switching the battery supply off or by removing the exterenal fuse(s) or
circuit breaker(s).
To restart the solar charger after it was shutdown, perform these steps in the prescribed order:
1. Connect the battery supply to the solar charger by switching the battery supply on or by inserting the external fuse(s) or
circuit breaker(s).
Page 33Operation
MPPT solar charger manual
2. Reconnect the PV supply to the solar charger by switching the PV supply on or by inserting the external fuse(s) or circuit
breakers(s).
6.6. Maintenance procedure
The solar charger does not need regular maintenance.
Page 34Operation
MPPT solar charger manual
7. Monitoring
This chapter describes all various monitoring methods and for each method how to access live data, historic data and errors.
7.1. LED indications
The solar charger has three LEDs to indicate operational status, a blue, green and a yellow LED. These LEDs respectively
indicate the charge stages bulk, absorption and float, but are also used to indicate other charge situations and fault situations.
Errors are indicated via a combination of LEDs that are on, off, or are blinking. Each LED combination has a meaning, indicating
either a normal operation mode, or indicating an error.
SymbolMeaning
Permanent on
Blinking
Off
Overview of LED indications:
Operation modeBulk LEDAbsorption LEDFloat LED
Not charging
1
Bulk
Absorption
Manual equalisation (alternating
blinking)
Automatic equalisation
Float
1
2
2
2
2
1. The bulk LED will blink briefly every 3 seconds when the system is powered but there is insufficient power to start charging.
2. The LED(s) might blink every 4 seconds indicating that the charger is receiving data from another device, this can be a GX
device (ESS) or a VE.Smart Network link via Bluetooth
Fault modeBulk LEDAbsorption LEDFloat LED
Charger temperature too high
Charger over-current
Charger or panel over-voltage
VE.Smart networking or BMS
issue
Internal error, calibration issue,
settings data lost or current
sensor issue.
For the latest and most up-to-date information about the LED blink codes, refer to the Victron Toolkit app. The app is available for
Apple and Android. The app can be downloaded from the respective app stores or alternatively follow the download links on our
software downloads page.
Page 35Monitoring
MPPT solar charger manual
7.2. Error codes
In case of an error, an error code will be displayed in the following ways:
• Via its LEDs.
• Via the VictronConnect app while it is connected to the solar charger.
• Via an optional MPPT control or SmartSolar Control display.
• Via an optional GX device or GlobalLink 520 and the VRM Portal.
For the meaning of blinking LED codes, see the previous chapter or the Victron Toolkit app.
For a full list of error codes and their meaning see the Error code overview chapter.
7.3. Monitoring via the VictronConnect app
The VictronConnect app can be used to monitor the solar charger, see its historical values and if there are operational warnings
or errors.
This chapter explains the solar charger-specific VictronConnect app usage. Refer to the general VictronConnect app manual for
information about the VictronConnect app itself, such as: how to install the app, how to connect to the solar charger, how to
update firmware and more.
Where battery voltage is referred in this chapter, a 12V battery is assumed.
To arrive at values for 24V, 36V or 48V batteries, multiply the 12V values by a factor of 2, 3 or 4 respectively.
7.3.1. VictronConnect app status screen
The status screen displays the solar charger model name together with the live solar charger information.
VE Smart Networking
• The presence of the VE.Smart Networking symbol indicates that the solar charger is configured for VE.Smart Networking
and is receiving battery temperature and/or battery voltage data from the VE.Smart Network.
Solar
• The solar gauge shows the solar output in relation to the maximum output power that the solar charger can generate at the set
battery voltage and displays the dynamic real-time value of the solar array output power.
• The solar voltage measured at the solar terminals of the solar charger.
• The solar current flowing from the PV array into the solar charger.
Battery
Page 36Monitoring
MPPT solar charger manual
• The battery voltage measured at the battery terminals of the solar charger.
• The current flowing from the solar charger into the battery.
• The battery state indicates the battery charge stage or if external control is active. These are the possible states:
Bulk
During this stage the solar charger delivers as much charge current as possible to rapidly charge the batteries. When the
battery voltage reaches the absorption voltage setting, the solar charger activates the absorption stage.
Absorption
During this stage the solar charger switches to the constant voltage mode, where a pre-set absorption voltage is applied. When
the charge current decreases below 2A or if the pre-set absorption time has elapsed, the battery is fully charged and the solar
charger will enter the Float stage. Note that when an automatic equalisation is being performed this will also be reported as
absorption.
Float
During this stage the float voltage is applied to the battery to maintain a fully-charged state. When the battery voltage drops
below float voltage during at least 1 minute, a new charge cycle will be triggered.
External control
This will be displayed when another device is controlling the charge behaviour of the solar charger, bypassing its normal charge
algorithm. Examples are when the solar charger is controlled by an ESS system or a managed battery.
• In case the charger is not charging a "Why is the charger off?" message will display. When clicking on this message, a new
window will open with more information as to why the solar charger is not charging.
Virtual load output
• The state of the virtual load output, being switched on or switched off.
Relay
• The state of the relay, being open or closed.
7.3.2. VictronConnect app history screen
The history screen shows a summary of the data collected over the previous 30 days. Swipe the screen to the right or left to show
any of the 30 days.
To switch between portrait or landscape screen presentation click the fragmented square icon, or , at the top left of the
screen.
The daily log shows:
• Solar yield: The energy (Wh) converted for that day.
• Solar Pmax: The maximum power (W) recorded during the day.
Page 37Monitoring
MPPT solar charger manual
• Solar Vmax: The highest voltage (V) from the PV array during the day.
• Battery max and min: The first figure shows the maximum battery voltage (Vmax) for the day. The figure below is the minimum
battery voltage(Vmin) for the day.
• Errors: This shows the daily number of errors, if any. To get more information about the error(s), click the orange dot. You may
need to slide the display on your device up to see the errors.)
• Lifetime total: This shows the total energy converted by the installation (W and is not re-settable).
• Since reset: This shows how much energy has been converted by the installation since the last reset.
Clicking on any bar (day) in the graph will expand the information. It will show the time and percentage of the total charge time
that the solar charger has spent in each Bulk, Absorption and Float charge stage.
You can use the charge times to see if the PV array is properly sized for your requirements. A system that
never reaches the float stage may need more panels. Or perhaps the load should be reduced?
The history can be exported as a comma-separated file (CSV) by clicking the three connected dots symbol or the save symbol
at the top right of the history screen. The symbol varies, depending on what platform VictronConnect is used.
The history can be reset by clicking the clock with an arrow symbol at the top right of the history screen.
7.3.3. VictronConnect app error reporting
The VictronConnect app will indicate active errors while the app is actively connected to the solar charger. The error will show up
in a pop-up window on the status screen together with the error number, name and a short error description.
The VictronConnect app also displays historical errors. To see these errors, navigate to the “History” tab and look at the bottom of
each day column. An orange dot will indicate an error on that day.
An active error and a historical error.
7.4. Monitoring via a GX device and VRM
If the solar charger is connected to a GX device, all its data can be accessed via the GX device. The GX device will also notify in
case of solar charger alarms or faults.
For more information see the GX device manual.
GX device showing alarm notification and historic errors.
Page 38Monitoring
MPPT solar charger manual
If the GX device is connected to Victron Remote Monitoring (VRM) portal, the solar charger can be monitored remotely via the
internet.
All solar charger data, alarms and errors can be accessed via the VRM portal and solar charger settings can be remotely
changed via the VRM portal with the VictronConnect app.
Solar charger alarm logging via VRM
Page 39Monitoring
MPPT solar charger manual
8. Troubleshooting
Refer to this chapter for addressing any unforeseen behaviour of the solar charger. Start by reviewing the common issues listed
here during troubleshooting.
If the problem persists or requires technical assistance, contact the point of purchase – the Victron Energy dealer or distributor. If
unsure whom to reach or unaware of the point of purchase, visit the Victron Energy Support webpage for guidance.
8.1. Solar charger is damaged
Before proceeding with troubleshooting, it is important to inspect the solar charger for any visible damage. Please note that
damage to the solar charger is typically not covered by warranty.
By conducting this initial visual inspection, you can identify any visible damage that may impact the functionality of the solar
charger:
Visual inspection
Step 1
Step 2
Step 3
Examine the solar charger for any signs of mechanical damage to the housing or electrical terminals. Please be
aware that this type of damage is not covered by warranty.
Inspect the electrical terminals of the solar charger for signs of burning or melting. This type of damage is often
caused by loose electrical connections, the use of rigid core cables, or exceeding the MC4 terminal current
ratings. Please be aware that this damage is not covered by warranty. Refer to chapter PV connections burned
or melted [54] for more information.
Look for any indications of water damage or corrosion on the solar charger, especially around the electrical
connection area. It is important to note that such damage is not covered by warranty.
8.2. Solar charger is unresponsive
If the solar charger is unresponsive, it means that none of its LEDs will illuminate or blink, there is no charging activity, and it is
unable to establish communication with the VictronConnect app through the VE.Direct port.
Conversely, if the solar charger is active, you will notice its LEDs are either illuminated or blinking, and it can successfully
communicate with the VictronConnect app via the VE.Direct port.
The solar charger should activate as soon it receives power from the battery, the PV supply, or both. Note that the solar charger
does not have an on/off switch.
To troubleshoot, verify that the solar charger is receiving either battery or PV power, using the below procedure.
Unresponsive solar charger troubleshooting procedure
Step 1Set a multimeter to DC voltage mode.
• Measure the voltage between the positive and negative battery terminals of the solar charger.
• Measure the voltage between the positive and negative PV terminals of the solar charger.
Step 2
WARNING: Certain solar charger models may have PV voltages up to 250Vdc. Voltages
exceeding 50V are generally considered dangerous. Only a qualified technician should
handle dangerous voltages.
Page 40Troubleshooting
MPPT solar charger manual
Unresponsive solar charger troubleshooting procedure
If the battery or PV voltage is below the minimum voltage, check the following:
• Check the continuity of the battery and PV supply cables.
• Inspect the fuses and circuit breakers in the battery and PV supply cables.
Step 3
Step 4
• Ensure that all cable connections are sufficiently tightened.
• Verify if the battery voltage is sufficiently high. If not, charge the battery using an auxiliary charger.
• Confirm if the PV voltage is sufficiently high. Check for any issues with the PV array, such as wiring mistakes,
damaged panels, cloudy weather, nighttime conditions, etc.
If, even after confirming sufficient battery or PV voltage, the solar charger remains unresponsive, consider the
solar charger to be faulty.
8.3. Solar charger is off
When the solar charger is off, the VictronConnect app shows this on the status screen. Click the "Why is the charger off?" text for
a pop-up window with an explanation and possible remedies.
The reasons why the solar charger is off:
• There is insufficient PV power. Refer to the PV voltage too low [41] subchapter.
• The settings are being edited on an external display. Refer to the Settings being edited on an external display [42] subchapter.
• The charger is disabled in the settings. Refer to the Disabled in the settings [43] subchapter.
• The charger is disabled by remote or BMS. Refer to the Disabled by remote or BMS [43] subchapter.
• Low lithium battery temperature. Refer to the Low lithium battery temperature [43] subchapter.
VictronConnect app – Why is the charger off?
8.3.1. PV voltage too low
The solar charger starts charging when the PV voltage is 5V above the battery voltage. Charging continues if the PV voltage
remains 1V higher than the battery voltage.
To troubleshoot if a low PV voltage is the reason the solar charger is not charging, use the below procedure.
Page 41Troubleshooting
PV and battery voltage check
Use the VictronConnect app, a solar charger display or a GX device to check the battery and PV voltage.
Step 1
If the above step is impossible, use a multimeter in DC mode to measure the battery and PV voltages at the
solar charger terminals.
Step 2
MPPT solar charger manual
WARNING: Certain solar charger models may have PV voltages up to 250Vdc. Voltages
exceeding 50V are generally considered dangerous. Only a qualified technician should
handle dangerous voltages.
Step 3
Possible reasons why the solar voltage might be too low:
• Insufficient solar irradiance is reaching the solar panels:
• It is night.
• There is cloudy or bad weather.
• There is shade from nearby objects. See this shading blog story for more information.
• The panels are dirty.
• There are seasonal differences. The sun angle is lower in winter.
• The panels have an incorrect panel orientation or inclination.
•
There are issues with a solar panel or the solar panel wiring:
• There is a mechanical or electrical issue with an individual panel (or multiple panels).
• Wiring problems, like loose wires, loose connections or incorrect crimped MC4 connectors.
• Blown fuses.
• Open or faulty circuit breakers.
Compare both voltages. Remember that the PV voltage needs to be 5V higher than the battery voltage for
charging to commence.
• Issues with splitters, combiners or incorrect usage of these components.
Incorrect PV array design or configuration:
•
• The PV array is misconfigured. For example, there are an insufficient number of panels in a series string.
• Reverse PV polarity:
• The positive and negative PV wires have been mistakenly swapped when connected to the solar charger. For more
information, see the Reverse battery polarity [46] chapter.
8.3.2. Settings being edited on an external display
Charging is disabled when a MPPT Control external display is used to make configuration changes. And this is likewise the case
if a SmartSolar Control display is used.
Page 42Troubleshooting
MPPT solar charger manual
Once the settings menu is closed on the display, charging will resume.
8.3.3. Disabled in the settings
The charger has been disabled in the settings.
Check the VictronConnect app battery settings page to ensure that the charger has been enabled.
VictronConnect app charger enable/disable setting
8.3.4. Disabled by remote or BMS
The charger has been switched off via its remote on/off terminal or VE.Direct port.
Note that in systems with lithium batteries together with an external BMS, it is typical for the solar charger to be switched on or
off as needed. This happens when the BMS turns off the charger due to full batteries or low temperatures (below ~5°C). Charging
automatically resumes when the batteries are discharged or have warmed up.
If the solar charger has unexpectedly been switched off, check the following:
Remote terminal check
Typically, both the remote connector and the wire loop must be present for the solar charger to function correctly. In more
advanced systems, the remote on/off terminal might be connected to an external device, such as a switch, relay, or battery
BMS system for external control.
Step 1Verify that the connector block with the wire loop is present.
Step 2Verify that the connector block has been inserted all the way in.
Step 3
Step 4
VE.Direct RX port functionality check
The VE.Direct port can be used to switch the solar charger on or off by utilising its RX functionality in combination with, for
example, a VE.Direct non-inverting remote on/off cable.
Step 1
Step 2If a VE.Direct non-inverting remote on/off cable) is used, check if it is in good working order.
Step 3
Verify that the wire loop is making electrical contact with the connector
block.
Remote connector with the wire
loop.
Take note of the various methods the solar charger can be activated via the remote terminal:
• ON when the L and H terminals are interconnected via a switch or a relay contact.
• ON when the L terminal is pulled to battery minus (VL< 3.5V).
• ON when the H terminal is high (2.9V<VH<Vbat).
check if the RX port has been configured correctly. For more information, see the RX port settings [27] chapter
and the VE.direct protocol documentation.
If a non-Victron cable is used, check if it is configured correctly. For more information see the VE.direct protocol
documentation.
8.3.5. Low lithium battery temperature
Charging may be suspended if the battery temperature is low, as a part of the battery protection mechanism, without necessarily
indicating a problem. The rationale behind this precaution is that lithium batteries are prone to damage when charged in
temperatures below °5C.
If this protection is triggered unnecessarily, please reach out to your installer to adjust the related settings.
8.4. Solar charger is externally controlled
Managed batteries or an inverter/charger with an external control system (e.g., ESS system) can govern the solar charger via a
GX device. The external system determines charging permissions and sets the charge voltage and currents.
Page 43Troubleshooting
MPPT solar charger manual
When external control is active, it is visible on both the VictronConnect app and the GX device. This is normal behaviour and is
not a fault.
The VictronConnect app indicates that the charger is externally controlled.
8.5. Batteries are not charged
This chapter explains scenarios where the charger is active, but the batteries are not charging. In such cases, the VictronConnect
app will show the charger as active with the correct charge voltage, but the charge current will be at zero or very close to zero.
There are several reasons why this can happen, namely:
• The battery is fully charged, and no further current is required. This is normal behaviour and is not a fault. Refer to the Battery
is full [44] chapter for more details.
• Reverse PV polarity. Refer to the Reverse PV polarity [47] subchapter for more details.
• PV voltage is too high. Refer to the PV voltage too high [47] subchapter for more details.
• Reverse battery polarity. Refer to the Reverse battery polarity [46] subchapter for more details.
• The solar charger is disconnected from the battery, possibly due to cable, fuse, or circuit breaker issues. Refer to the Battery
not connected [45] subchapter for more details.
• Incorrect charger configuration, e.g., low charge voltage or current setting. Refer to the Battery settings too low [46]
subchapter for more details.
• The charger is externally controlled (ESS or DVCC), which is normal and not a fault. Refer to the Solar charger externally
controlled chapter for more details.
• The temperature-compensated charging feature is active, and the battery temperature is too high, or the feature is
misconfigured. Refer to the Wrong temperature compensation setting chapter for more details.
The VictronConnect app shows a close to zero charge current.
8.5.1. Battery is full
Once the battery is full, the solar charger will stop or significantly reduce its charge current. This is especially evident when DC
loads are not drawing power from the battery. It is important to note that this behaviour is normal and not a fault.
Page 44Troubleshooting
MPPT solar charger manual
To determine the battery's state of charge (SoC), check the battery monitor (if available) or inspect the charge stage indicated by
the solar charger. During the daily charge cycle, the solar cycle progresses through the following stages:
1. Bulk stage: 0-80% SoC.
2. Absorption stage 80-100% SoC.
3. Float stage: 100% SoC.
Be aware that the solar charger may detect the battery as fully charged when it's not. This happens if the charge voltages are set
too low, causing the charger to switch from absorption to float stage prematurely. Refer to the Battery settings too low chapter.
8.5.2. Battery not connected
To ensure proper battery charging, a correct connection to the battery is crucial.
Be aware that that if the solar charger operates without a battery, it may seem connected, showing battery voltage and charge
stage in the VictronConnect app, but the charge current will be negligible or zero.
Potential reasons for a disconnected battery:
• Loose or missing battery cables.
• Loose cable connections.
• Poorly crimped cable terminals.
• A blown (or missing) fuse in the battery supply cable.
• Open (or faulty) circuit breaker in the battery supply cable.
• Incorrectly wired battery cables.
Battery voltage check
Use the VictronConnect app, a connected display or a GX device to read the solar charger battery voltage.
Alternatively, use a multimeter to measure the battery voltage at the terminals of the solar charger.
Step 1
Use a multimeter to measure the voltage at the battery terminals.
Step 2
Step 3Compare the two voltages.
Page 45Troubleshooting
Battery voltage check
In case of a voltage difference, investigate the reason behind it by tracing the path from the solar charger to the
battery to identify the cause.
• Check and confirm that all cabling is accurately connected and that there are no wiring errors.
• Inspect the cable connections for tightness while keeping the maximum torque levels in mind.
MPPT solar charger manual
Step 4
• Verify the correct crimping of all cable lugs or terminals.
• Check the fuses and circuit breakers.
Should you come across a blown fuse, make sure to check the correct wiring of the battery
polarity before replacing it. Refer to the Reverse battery polarity [46] chapter.
8.5.3. Reverse battery polarity
Reverse polarity occurs when the positive and negative battery cables are accidentally swapped. This means the negative battery
terminal connects to the positive solar charger terminal, and the positive battery terminal connects to the negative solar charger
terminal.
Examples of correct and incorrect (reverse) battery polarity.
Be aware that a red or positively labelled cable may not necessarily indicate the cable is positive. A wiring or
labelling mistake during the solar charger installation is possible.
Always double-check the battery polarity before reconnecting the battery wires to the solar charger.
Reverse battery polarity can potentially damage the solar charger, causing its internal fuse to blow for fail-safe protection. This
fuse might blow before the external fuse in the battery cable. However, please note that the internal fuse is situated in a
non-serviceable area, and it cannot be replaced or repaired. If this happens, the solar charger should be considered faulty.
The solar charger is not protected against reverse battery polarity, and any resulting damage is not covered under warranty.
8.5.4. Battery settings too low
If the solar charger's charge voltage and current are well below the manufacturer's recommended levels, the battery charging
process may become inadequate or excessively slow. Incorrect configuration can be a contributing factor, including:
• Setting the "Battery voltage" parameter too low.
• Setting the ''Absorption voltage" and "Float voltage" parameters too low.
• Setting the "Max charge current" parameter to zero or an excessively low value.
Page 46Troubleshooting
MPPT solar charger manual
VictronConnect app, showing battery (system) voltage, charge current and charge voltages settings.
8.5.5. PV voltage too high
The PV voltage should always stay within the maximum rated limit of the solar charger, as indicated in its product name, type
plate and Technical specifications [60]. The solar charger can sustain damage based on the extent of the PV voltage height, and
it's important to note that such damage is not covered by warranty.
Should the PV voltage exceed the maximum rated PV voltage, the solar charger will cease charging, showing an overvoltage
error #33 with rapid blinking of the absorption and float LEDs. Charging resumes only when the PV voltage drops 5V below the
rated maximum voltage.
During investigations into high voltage issues, it's essential to review the VictronConnect app, solar charger display, or GX device
history. Check for the highest PV voltage recorded each day (Vmax) and past overvoltage warnings.
To avoid issues, check the open circuit voltage (Voc) rating of the PV array and ensure it is lower than the solar charger's
maximum rated voltage. Use the MPPT sizing calculator on the solar charger product page. For PV arrays in cold climates or with
night temperatures nearing or below 10°C, it's essential to consider possible increased output (more than its rated Voc). As a rule
of thumb, maintain an additional 10% safety margin.
VictronConnect app error #33 indication on the status screen and history screen.
8.5.6. Reverse PV polarity
When the solar charger is installed within the published specifications, internal protection guards the PV input against reverse PV
polarity, and no error is displayed in such cases.
Page 47Troubleshooting
MPPT solar charger manual
To identify reverse PV voltage, watch for these indicators:
• Absence of battery charging with the charge current remaining at zero.
• Excessive heat generated by the solar charger.
• PV voltage reading zero or close to zero.
To verify, use a multimeter to ensure that the positive PV cable is correctly connected to the positive PV terminal and the negative
cable is connected to the negative PV terminal.
WARNING: Certain solar charger models may have PV voltages up to 250Vdc. Voltages exceeding 50V are
generally considered dangerous. Only a qualified technician should handle dangerous voltages.
8.6. Batteries are undercharged
This chapter addresses the issue of undercharged batteries. It explores possible reasons why the solar charger might not be
adequately charging the batteries and provides steps to check or resolve the situation.
Some signs of undercharged batteries include:
• Batteries taking too long to charge.
• Batteries not being fully charged by the end of the day.
• Charge current is less than expected.
Several factors can cause this, such as:
• Insufficient solar supply. Refer to the Insufficient solar supply [48] subchapter.
• High DC load. Refer to the DC load too high [49] subchapter.
• Voltage drop in battery cables. Refer to the Battery cable voltage drop [49] subchapter.
• Incorrect temperature compensation setting. Refer to the Temperature compensation setting incorrect [50] subchapter.
• Temperature difference between the solar charger and battery. Refer to the Temperature difference between solar charger and
battery [50] subchapter.
• Battery charge voltages or current settings are too low. Refer to the Battery settings too low [46] chapter.
8.6.1. Insufficient solar supply
Check if the solar charger reaches the float charge stage each day.
To investigate, check if the solar charger reaches the float charge stage each day. Utilise the VictronConnect app's history tab,
where a histogram displays the daily charging durations in the Bulk, Absorption, and Float stages for the last 30 days. Clicking on
a histogram column provides a breakdown of the charge stages.
You can use the charge times to assess whether the PV array is appropriately sized for your needs.
Reasons for the solar charger not reaching the float stage include:
• An inadequate number of solar panels.
• Excessive DC load.
• PV array issues causing reduced power output.
• Solar charger is unable to reach full output. Refer to the Solar charger not achieving full output [52] chapter.
Page 48Troubleshooting
MPPT solar charger manual
Please note that this information does not apply to an ESS system. An ESS system will continuously be in the bulk charge stage
while connected to the grid.
Left: Example of a system that is spending all its time in the bulk stage. Right: Breakdown of the charge stages - The system
spends time in bulk and in the absorption stage.
8.6.2. DC load too high
The solar charger not only charges the batteries but also supplies power for the system's DC loads, such as lights, refrigerators,
inverters, inverter/chargers and more.
Battery charging occurs only when the power generated by the PV panels exceeds the power consumed by the system's DC
loads.
To check the PV array's power generation and load power usage:
To check the PV array's power generation and load power usage:
• If the system includes a properly installed and configured battery monitor, you can monitor the current flowing in (or out) of the
battery, while the solar charger indicates the current generated by the solar array.
• Use a current clamp and compare the current flowing from the solar charger into the battery and the current flowing from the
battery into the DC system.
• A positive sign alongside the current reading indicates current flowing into the battery, whereas a negative sign suggests
current being drawn from the battery.
8.6.3. Battery cable voltage drop
If the battery cables experience a voltage drop, the solar charger will produce the correct voltage, but the batteries will receive a
lower voltage, potentially leading to undercharged batteries. An excessive voltage drop of more than 2.5% is unacceptable.
The voltage drop can result in the following:
• Longer battery charging times.
• Battery receiving a charge voltage that is too low.
• Loss of charge power.
• Increased heat in the battery cables.
The voltage drop can be caused by:
• Battery cables with insufficient cross-sectional area.
• Poorly crimped cable lugs or terminals.
• Loose terminal connections.
• Faulty or loose fuse(s).
For more information on cabling issues and voltage drop, refer to the Wiring Unlimited Book.
Battery cable voltage drop check
Step 1
Page 49Troubleshooting
Make sure that the charger is charging with the full current, preferably in the morning. Use the VictronConnect
app to confirm the output current.
Battery cable voltage drop check
Using the VictronConnect app or a multimeter, measure the voltage on the battery terminals of the solar
charger.
Step 2
Measure the battery voltage on the terminals of the battery using a multimeter.
Step 3
MPPT solar charger manual
Step 4Compare the two voltages to identify any voltage difference.
VE.Smart Networking can assist in mitigating a small cable voltage drop. However, for a substantial voltage drop, there may be
an issue with the wiring between the solar charger and the battery, which requires rectification before proceeding.
In a VE.Smart Network a Smart Battery Sense or battery monitor measures the battery terminal voltage and transmits this via
VE.Smart Networking to the solar charger. If the battery voltage is less than the solar charge voltage, the solar charger will
increase its charge voltage to compensate for (small) voltage losses.
8.6.4. Temperature compensation setting incorrect
Improperly configuring the temperature compensation coefficient can lead to either undercharged or overcharged batteries.
Note that temperature compensation is typically applicable only to lead-acid batteries.
To determine the correct temperature compensation coefficient for your battery, consult the battery documentation. If uncertain,
use the default value of -64.80mV/°C for lead-acid batteries, and for lithium batteries, disable the temperature compensation
setting.
8.6.5. Temperature difference between solar charger and battery
For proper operation, it is crucial that the ambient temperatures of both the battery and the solar charger are equal, especially if
the solar charger is not receiving battery temperature data.
Note that this chapter does not apply if the solar charger is connected to a VE.Smart Network with a battery
temperature measurement or is equipped with a temperature sensor.
At the beginning of the day, as soon as power is generated by the solar array, the solar charger will measure the ambient
temperature and use it to temperature-compensate the charge voltage.
During the float stage, the solar charger will re-measure the ambient temperature and adjust the voltages accordingly.
Large differences in ambient temperature between the solar charger and the battery can lead to improper charging voltages for
the battery.
For instance, if the solar charger is placed near a sunlit window while the batteries are located on a cold concrete floor in the
shade, this temperature discrepancy can affect the charging process.
To ensure optimal performance, always ensure that the ambient conditions are equal for both the solar charger and the battery.
Page 50Troubleshooting
MPPT solar charger manual
8.7. Batteries are overcharged
WARNING: Overcharging batteries can be extremely dangerous! There is a significant risk of battery
explosion, fire, or acid leakage. To prevent accidents, do not smoke, create sparks, or have open flames
in the same room where the batteries are located.
Overcharging batteries can lead to severe battery damage and may be caused by the following factors:
• Incorrect charge voltage settings. Refer to the Battery charge voltage settings too high [51] subchapter.
• Battery voltage setting too high. Refer to the Battery voltage setting too high [51] subchapter.
• Applying equalisation while the battery is not suitable for it. Refer to the Battery unable to deal with equalisation [51]
subchapter.
• The battery is too small, old, has been mistreated in the past or is faulty. Refer to the Battery old, faulty or undersized [51]
subchapter.
8.7.1. Battery voltage setting too high
If the "battery voltage" setting in the VictronConnect app is configured to a voltage higher than the actual system voltage, it will
result in overcharging the battery.
The solar charger automatically detects the battery voltage on the first install, and afterwards, the self-detection is disabled.
However, if the solar charger is moved from a 24V system to a 12V system, it may not recognise the system change.
Consequently, it will continue charging with 24V battery charge voltages, while the connected battery is a 12V battery, leading to
overcharging of the 12V battery.
To verify the "battery voltage" setting, use the VictronConnect app or a connected display. If the setting is incorrect, make sure to
adjust it to the correct battery voltage.
8.7.2. Battery charge voltage settings too high
Batteries can be overcharged if the battery charge voltages are set too high.
Verify that all the battery charge voltages (absorption and float) are correctly configured to match the recommended voltages
specified in the battery manufacturer's documentation.
8.7.3. Battery unable to deal with equalisation
When equalisation occurs, the battery charge voltage will be considerably high, and if the battery is unsuitable for equalisation, it
may be overcharged.
It's essential to note that not all batteries can handle equalisation voltages. Check with the battery manufacturer to determine if
the battery you are using requires a periodic equalising charge.
In general, sealed batteries and lithium batteries do not require equalisation and should not undergo the equalisation process.
8.7.4. Battery old, faulty or undersized
A battery that has reached the end of its service life or has been damaged due to improper use may be susceptible to
overcharging.
A battery is comprised of multiple cells connected in series. In the case of an old or damaged battery, it's possible that one of
these cells is no longer operational. During charging, the faulty cells will not accept charge, and the remaining cells will receive
the broken cell's charge voltage, resulting in overcharging.
To address this issue, replace the battery. If the system includes multiple batteries, it's recommended to replace the entire battery
bank rather than mixing batteries of different ages in one bank.
Determining the exact history of a battery during its lifetime can be challenging. The solar charger retains 30 days of battery
voltage history. If the system has a battery monitor or is connected to the VRM portal, the battery voltages and cycle history can
be accessed to assess the battery's overall health and whether it is nearing the end of its service life or has been misused.
Similar issues can arise if the battery is too small and charged with a significantly high current. The small battery will not be able
to accept the total charge and will end up being overcharged.
Page 51Troubleshooting
MPPT solar charger manual
Battery health check using battery monitor history data
Step 1
Step 2
Step 2Determine the average discharge or cumulative energy drawn.
Step 3
Step 4
Step 5
In the VictronConnect app, navigate to the battery monitor history
screen. Or (if applicable) access the battery history via the VRM portal.
Determine the number of charge cycles and synchronisations. Both
indicate how many charge cycles the battery underwent.
Refer to the battery data sheet to find out how many cycles at what
average discharge the battery is capable of. Compare this with the
battery history and determine if the battery is approaching the end of
its service life.
Check if the battery has been completely discharged at any point. Total
and very deep discharges can damage a battery. Examine the deepest
discharge, the lowest battery voltage and the number of full discharges.
Check if the battery has been charged with a too-high voltage. A very
high charge voltage can damage the battery. Review the maximum
battery voltage and the high voltage alarms. Verify that the measured
maximum voltage has not exceeded the battery manufacturer's
recommendations.
VictronConnect app showing
battery monitor history
8.8. Solar charger not achieving full output
In addition to potential issues with the PV array, several other reasons can hinder the solar charger from reaching its full-rated
output.
Reasons for the solar charger not reaching its full output:
• The PV array is too small. If the PV array's power rating is less than the solar charger's nominal power rating, the solar charger
cannot output more power than the connected solar array can provide.
• The PV array is not reaching its maximum power rating. Refer to the PV yield lower than expected [52] subchapter.
• The PV array is a mix of different PV panel types or models. Only use solar panels that are of the same brand, type and model.
• Do not use optimisers. Nearly all optimisers contain an MPPT or other tracking mechanisms, which will interfere with the MPPT
algorithm in the solar charger.
• The PV array is wrongly configured. For a detailed explanation of how to configure PV arrays and properly use MC4 splitters
and MC4 combiners, see the "Solar panel" chapter in the Wiring Unlimited Book.
• The solar charger's maximum PV output power is related to the battery voltage. Refer to the Maximum output power relates to
battery voltage [53] subchapter.
• The solar charger's PV electric connections are burned or melted, or MC4 connectors have been insufficiently crimped. Refer to
the PV connections burned or melted [54] subchapter.
• The solar charger temperature is above 40°C. Refer to the Temperature above 40°C [54] subchapter.
• The batteries are either full or nearly full, causing no further power to flow into them.
• There may be an issue with the battery. Refer to the Batteries are not charged [44] and Batteries are undercharged [48]
chapters.
8.8.1. PV yield lower than expected
If the PV yield is not meeting expectations, start by checking the solar charger history in the VictronConnect app. Verify the total
maximum power (Pmax) for each day and compare it with the array power.
To determine the potential solar yield per day for a specific PV array size in a particular geographical location, utilise the MPPT
sizing calculator on the solar charger product page.
List of reasons why the PV array may generate less power than expected:
• Low sun angle (morning or evening) or seasonal differences.
• Cloud cover or adverse weather conditions.
• Shading from trees or buildings.
Page 52Troubleshooting
MPPT solar charger manual
• Dirty solar panels.
• Incorrect orientation or inclination of the solar panels.
• Broken or faulty solar panels.
• Issues with wiring, fuses, circuit breakers, or there is a cable voltage drop.
• Incorrect usage or malfunctioning splitters or combiners.
• Part of the PV array is not functioning correctly.
• The PV array is too small for the desired output.
• Mistakes in solar array configuration.
• The batteries may be too small or aging, resulting in a reduced capacity.
VictronConnect app history Pmax reading.
8.8.2. Maximum output power relates to battery voltage
The solar charger's output current is limited to its rated current, resulting in varying output power depending on the battery's
voltage.
For instance:
In a 75/15 solar charger with a 15A output current rating, the power going into the battery will differ for a 12V battery and a 24V
battery.
• For a 12V battery, this is 15A x 12V = 180W.
• For a 24V battery, this is 15A x 24V = 360W.
Thus, even though a 360W panel is connected to the solar charger, the output power into a 12V battery will be less than when
connected to a 24V battery.
Page 53Troubleshooting
MPPT solar charger manual
Example of differences in output power at different battery voltages
8.8.3. Temperature above 40°C
The solar charger operates up to 60°C, with full-rated output maintained up to 40°C. Above 40°C, the output will derate, reducing
output power.
For efficient performance, consider the solar charger's mounting arrangement. Mount it vertically with terminals facing downwards
to dissipate heat effectively. In closed enclosures, like cabinets, ensure proper airflow with mounted vents to allow cold air in
and hot air out. In extremely high-temperature environments, mechanical air extraction or air conditioning may be necessary to
maintain optimal performance.
8.8.4. PV connections burned or melted
Burned or melted PV cables or connections are not covered under warranty. This can occur due to the following reasons:
• Loose screw connections.
• Using cables with rigid core wire or rigid strands.
• Soldering the core wire ends of the cables.
• Using thin cables may result in higher currents when the PV voltage is lower. Refer to the Wiring Unlimited book for more
information.
• Inserting cable insulation too deeply into the connector.
• Exceeding 30A per MC4 connector pair.
• Incorrectly crimping MC4 connectors.
• Using low-quality MC4 connectors.
8.9. Communication Issues
In this chapter, we address potential problems that may occur when connecting the solar charger to the VictronConnect app, other
Victron devices, or third-party devices.
8.9.1. Bluetooth
Please note that Bluetooth interface issues are highly unlikely. If you encounter problems, they are probably caused by other
factors. Use this chapter to quickly identify common causes of Bluetooth issues.
For a comprehensive troubleshooting guide, refer to the VictronConnect manual.
Bluetooth check
Check if the solar charger is powered up:
• Observe the LEDs: If any LEDs are on, blinking, or pulsing with a few seconds interval, the unit is powered
Step 1
Page 54Troubleshooting
up, and Bluetooth should be functional.
• f all LEDs are off, the unit is not powered up, and Bluetooth is inactive. Refer to the Solar charger is
unresponsive [40] chapter to troubleshoot.
Bluetooth check
Check if the solar charger is equipped with Bluetooth:
Step 2
Step 3
Step 4
• Only SmartSolar models have built-in Bluetooth; BlueSolar models do not.
• To add Bluetooth capability to a BlueSolar solar charger, use a VE.Direct Bluetooth Smart dongle. VE.Direct
Bluetooth Smart dongle.
Check that Bluetooth is in range:
• Bluetooth's maximum distance in open space is about 20 meters, but it may be lower inside buildings or
vehicles.
The Windows version of the VictronConnect app does not support Bluetooth:
• Use an Android, iOS, or macOS device or connect using a VE.Direct to USB interface.
The solar charger is missing from the VictronConnect app device list:
• Press the orange refresh button at the bottom of the device list.
MPPT solar charger manual
Step 5
Step 6
Step 7
• Ensure no other devices are connected to the solar charger simultaneously.
• Try connecting to another Victron product to rule out device-specific issues.
• If still unresolved, refer to the VictronConnect app manual.
Lost PIN code:
• Navigate to the VictronConnect app device list.
• Click on the options symbol (3 dots) next to the solar charger listing.
• Enter the solar charger's unique PUK code as printed on its product information sticker.
• Reset the PIN code.
Communication without Bluetooth:
• If Bluetooth is unavailable, the VictronConnect app can still communicate via the unit’s VE.Direct port or via
the VRM portal (if connected to a GX device). Refer to the VictronConnect app [4] chapter.
8.9.2. VE.Direct port
Problems with the VE.Direct port are uncommon, but if encountered, they are likely due to the following issues:
Physical cable connector or data port issue
• Try using a different VE.Direct cable to check if communication is established.
• Ensure the connector is inserted properly and fully into the port.
• Inspect the VE.Direct port for bent pins. If found, power the unit off by disconnecting it from the battery and the PV, and
straighten the pins using long-nose pliers.
VE.Direct communication issues
• Connect the solar charger to a GX device to verify VE.Direct communication.
• Check if the solar charger appears in the GX device list.
• If it does not show up in the list, set the TX port function in VictronConnect to "Normal communication."
VE.Direct TX port issues
• Verify the "TX port function" setting in VictronConnect matches the intended application.
• Test the TX port's functionality using a TX digital output cable.
VE.Direct RX Port issues
• Confirm the "RX port function" setting in VictronConnect aligns with the intended application.
• Test the RX port's functionality using a VE.Direct non-inverting remote on/off cable.
8.9.3. VE.Smart Networking
A VE.Smart Network is a wireless communication network that connects multiple Victron products using Bluetooth. If you
encounter any problems with a VE.Smart Network, please refer to VE.Smart Networking manual.
Page 55Troubleshooting
MPPT solar charger manual
8.10. Miscellaneous issues
This chapter describes issues that were not covered in the previous troubleshooting chapter.
8.10.1. Unable to operate as a DC-DC charger or power supply
Avoid using the solar charger as a DC-DC charger (e.g., to charge a 12V battery from a 24V battery bank). Connecting a battery
to the PV terminals under certain operational conditions can damage the solar charger, which is not covered by the warranty.
Instead, use a dedicated DC-DC charger or converter. Check our DC-DC converter product page for a complete product range.
Also, refrain from using the solar charger as a power supply without batteries connected. Although this operation won't harm the
solar charger, it might not support all types of loads. Some loads may function, while others may not, particularly at low load
power, where the solar charger's response might be too slow to maintain a constant voltage. Please note that support is not
provided for such situations.
8.10.2. Interrupted firmware update
An interrupted firmware update is recoverable and there is no need to worry. Simply attempt to update the firmware once more.
8.10.3. Ground current
If a ground current is detected in the system during normal operation, take the following steps:
• First, thoroughly inspect all the equipment connected to the system and check for any ground faults.
• Next, verify the number of connections to ground in the system. Ideally, there should be only one point in the system connected
to the ground, which should be at the battery.
• For more information on system grounding, see the "System grounding" chapter in the Wiring Unlimited book.
Note that the solar charger is non-isolated and the minus of the PV input is at the same potential as the minus of the battery
output.
Page 56Troubleshooting
MPPT solar charger manual
8.11. Error code overview
The error codes in the following subchapters are potentially displayed in the VictronConnect app, on a remote display or a
connected GX device. For the most up-to-date error overview, see this link: https://www.victronenergy.com/live/mppt-error-codes.
Furthermore, the solar charger utilises specific LED indications to signal particular errors. For an overview of these LED codes,
please refer to the Victron Toolkit app.
8.11.1. Error 1 - Battery temperature too high
This error will auto-reset after the battery temperature has dropped. The solar charger will stop charging to prevent damaging the
battery. The battery temperature can be received by an external sensor (like Smart Battery Sense or BMV) or measured by the
charger when this feature is available.
8.11.2. Error 2 - Battery voltage too high
This error will auto-reset after the battery voltage has dropped. This error can be due to other charging equipment connected to
the battery or a fault in the solar charger.
This error can also occur if the battery voltage (12, 24, 48V) is set to a lower voltage than the connected battery.
8.11.3. Error 17 - Solar charger overheated despite reduced output current
This error will auto-reset after the solar charger has cooled down. Check the ambient temperature and check for obstructions near
the heat sink.
8.11.4. Error 18 - Solar charger over-current
This error will auto-reset. If the error does not auto-reset, disconnect the solar charger from all power sources, wait 3 minutes,
and reconnect so it will power up again.
Possible causes for an over-current on the battery terminals:
• Switching on/off a very large load on the battery side.
• Sudden change in irradiance is causing a temporary over-power in the solar charger.
• Overload of the inverter ac output.
Possible solutions:
• If possible, provide adequate cooling for the unit. A cooler unit can handle more current.
• Reduce the load on the inverter.
• Charge the battery before using the inverter. At higher battery voltages, the same amount of power requires less current.
8.11.5. Error 20 - Maximum bulk time exceeded
The maximum bulk time protection was a feature when the solar chargers were newly released in 2015 (or prior). This feature has
now been removed.
If you see this error, update the solar charger to the latest firmware. If, after the update, you still see this error, then perform a
"reset to factory defaults" and then reconfigure the solar charger.
8.11.6. Error 21 - Current sensor issue
If you see this error, update the solar charger to the latest firmware. If, after the update, you still see this error, then perform a
"reset to factory defaults" and then reconfigure the solar charger.
Disconnect all wires and then reconnect all wires to force the solar charger to restart. Also, make sure the minus on the solar
charger (PV negative and battery negative) is not bypassing the solar charger.
This error will not auto-reset.
If the error remains, please contact your dealer or distributor, as there might be a hardware defect.
8.11.7. Error 26 - Terminal overheated
Power terminals overheated, check the wiring, including the wiring type and type of strands, and/or fasten bolts if possible.
This error will auto-reset.
Page 57Troubleshooting
MPPT solar charger manual
8.11.8. Error 28 - Power stage issue
This error will not auto-reset.
Disconnect all wires, and then reconnect all wires. If the error persists, the charger is probably faulty.
Note that this error was introduced in v1.36. So when doing an update, it might look like the firmware update caused this issue;
but it doesn't. The solar charger was then already not performing 100% before the update; updating to v1.36 or later merely made
the issue more visible. The unit needs to be replaced.
8.11.9. Error 33 - PV over voltage
This error will auto-reset after the PV voltage has dropped to a safe limit.
This error is an indication that the PV array configuration with regard to open-circuit voltage is critical for this charger. Check
configuration, and if required, re-organise panels.
For more information, refer to the PV voltage too high [47] chapter.
8.11.10. Error 38, 39 - PV Input shutdown
When these errors show, the PV Input is internally shorted to protect the battery from overcharging. Prior to any other
troubleshooting, make sure to update to the latest firmware version.
Possible reasons for this error to occur:
• The "Battery voltage" parameter (12/24/36/48V) is set incorrectly. Use the VictronConnect app to set the correct "Battery
voltage" parameter.
• Another device is connected to the battery, configured to a higher voltage. For example, an inverter/charger is configured to
equalise at 17 Volts, while this is not configured in the solar charger.
Error recovery:
Error 38: First, disconnect the solar panels and then disconnect the battery. Wait for 3 minutes, then first reconnect the battery
•
and then the panels.
• Error 39: The charger will automatically resume operation once the battery voltage drops below its maximum voltage setting
(normally Equalisation or Absorption voltages). It can also take a minute to reset the fault.
• If the error persists, the solar charger is probably faulty.
8.11.11. Error 40 - PV Input failed to shutdown
If the solar charger is unable to turn off the PV input, it will go into a safe mode in order to protect the battery from over-charging
or having a high voltage on the battery terminals. In order to do that, the solar charger will stop charging and disconnect its own
output. The solar charger will become faulty.
8.11.12. Error 80 to 88 - PV Input shutdown
When these errors show, the PV Input is internally shorted in order to protect the battery from over-charging.
Prior to any other troubleshooting, make sure to update to the latest firmware version.
Possible reasons for this error to occur:
• The "Battery voltage" (12, 24, 36 or 48V) parameter is set incorrectly. Use the VictronConnect app to set it to the correct battery
voltage.
• Another device is connected to the battery with a higher charge voltage configuration. For instance, a MultiPlus is configured to
equalise at 17V, while the solar charger has not been configured for equalise charging.
Error recovery:
• Ensure that the solar charger is running the latest firmware.
Errors 80 to 83: First, disconnect the solar panels, then disconnect the battery and then follow the procedure as described in
•
the ??? chapter.
• Errors 84 to 87: First, disconnect the solar panels and disconnect the battery. Wait for 3 minutes, then first reconnect the battery
and then reconnect the panels.
• If the error persists, the solar charger is probably faulty.
8.11.13. Error 116 - Calibration data lost
If the unit does not work and error 116 pops up as the active error, the unit is faulty. Contact your dealer for a replacement.
Page 58Troubleshooting
MPPT solar charger manual
If the error is only present in the history data and the unit operates normally this error can be ignored safely. Explanation: when
the units power up for the very first time in the factory, it does not have calibration data and an error 116 is logged. Obviously, this
should have been cleared, but in the beginning, units left the factory with this message still in the history data.
SmartSolar models (not the BlueSolar models): upgrading to v1.4x firmware is a one-way trip, you cannot go back to an older
firmware version once you upgrade to v1.4x. Reverting to older firmware gives error 116 (calibration data lost), this can be fixed
by re-installing the v1.4x firmware.
8.11.14. Error 117 - Incompatible firmware
This error indicates that a firmware update did not complete, so the device is only partially updated. Possible causes are: the
device was out of range when updating over the air, a cable got disconnected or power was lost during the update session.
To fix this the update needs to be retried, download the correct firmware for your device from the Victron Professional Portal
When your GX device is connected to VRM, you can do a remote firmware update using this firmware file. You can do this via the
VRM website or using the VRM tab in VictronConnect. VictronConnect can also be used together with the firmware file to update
using a Bluetooth connection.
The procedure to add the file to VictronConnect and start the update is described here: 9. Firmware updates
8.11.15. Error 119 - Settings data lost
The charger cannot read its configuration and has stopped. This error will not auto-reset.
Perform the below procedure to get it working again:
Error recovery:
• First, restore it to factory defaults. (top right in Victron Connect, click on the three dots).
• Disconnect the solar charger from all power sources.
• Wait 3 minutes, and power up again.
• Reconfigure the charger.
• Report this to your Victron dealer and ask for it to be escalated to Victron; as this error should never happen. Preferably include
firmware version and any other specifics (VRM URL, VictronConnect screenshots or similar).
Page 59Troubleshooting
MPPT solar charger manual
9. Technical specifications
9.1. Specifications 150/60 and 150/70
MPPT 150/60MPPT 150/70
Battery voltage12/24/48V Auto select, 36V: manual select
Maximum battery current60A70A
Nominal PV power, 12V
Nominal PV power, 24V
Nominal PV power, 36V
Nominal PV power, 48V
Max. PV short circuit current
Maximum PV open circuit voltage150V absolute maximum coldest conditions
Peak efficiency98%
Self-consumption12V: less than 35mA / 48V: less than 20mA
1a) The solar charger will limit input power if more PV power is connected.
1b) The PV voltage must exceed Vbat + 5V for the controller to start. Thereafter the minimum PV voltage is Vbat + 1V.
2) A higher short circuit current may damage the solar charger in case of reverse polarity connection of the PV array.
3) Equalization is by default disabled.
4) For more information on data communication see the data communication paper in the Technical information section on
our website.
5) MC4 models: several splitter pairs may be needed to parallel the strings of solar panels. Maximum current per MC4
connector is 30A. The MC4 connectors are internally parallel connected to a single MPPT tracker.
9.2. Dimension drawings
9.2.1. Dimensions 60A-MC4 and 70A-MC4 BlueSolar
Page 61Technical specifications
80.7
233.5
45
45
5.3
A
248.5
91
4
182.4 170.7
7.5
8
R4
DETAIL
A
4x
SCALE 1 : 1
Rev00
Dimensions in mm
Dimension Drawing - BlueSolar MPPT Tr
SCC010045200
BlueSolar MPPT 150/45-Tr
SCC010060200
BlueSolar MPPT 150/60-Tr
SCC010070200
BlueSolar MPPT 150/70-Tr
D
E
F
C
1
2
3
4
B
A
3
2
1
5
C
D
4
6
7
8
A
B
8
7
6
5
F
E
MPPT solar charger manual