Victaulic VS1 Series, VicFlex I-VICFLEX.VS1 Installation Instructions Manual

I-VICFLEX.VS1INSTALLATION INSTRUCTIONS
Victaulic® VicFlex™ Style VS1 Dry Sprinkler
I-VICFLEX.VS1_1
Flexible Hose Bend Characteristics:
NOTE: For out-of-plane (three-dimensional) bends, care shall be taken
to avoid imparting torque on the flexible hose.
90°
OR
OR
Minimum
Bend Radius
Minimum
Bend Radius
Minimum
Bend Radius
Minimum
Bend Radius
Minimum
Bend Radius
Minimum
Bend Radius
Minimum
Bend Radius
2X
Minimum
Bend
Radius
2X
Minimum
Bend
Radius
WARNING
• Read and understand all instructions before attempting to install any Victaulic® VicFlex™ products.
• Wear safety glasses, hardhat, and foot protection.
• These installation instructions are intended for an experienced, trained installer.
• The installer shall understand the use of this product and why it was specified for the particular application.
• The installer shall understand common industry safety standards and potential consequences of improper product installation.
• It is the system designer’s responsibility to verify suitability of stainless steel flexible hose for use with the intended fluid media within the piping system and external environment.
• The material specifier shall evaluate the effect of chemical composition, pH level, operating temperature, chloride level, oxygen level, and flow rate on stainless steel components to confirm system life will be acceptable for the intended service.
Failure to follow these instructions could cause improper sprinkler operation and product failure, resulting in death or serious personal injury and property damage.
The following table is used when the ambient temperature is maintained between 40° F/4° C and 60°F/16°C around the wet piping system.
Ambient
Temperature
Exposed to
Discharge End
of Sprinkler
°F/°C
Exposed Minimum Barrel Length “Y” inches/mm
40°F
4°C
50°F 10°C
60°F 16°C
40 0 0 0
4 0 0 0
30 0 0 0
-1 0 0 0
20 4 0 0
-7 100 0 0
10 8 1 0
-12 200 25 0 0 12 3 0
-18 300 75 0
-10 14 4 1
-23 350 100 25
-20 14 6 3
-29 350 150 75
-30 16 8 4
-34 400 200 100
-40 18 8 4
-40 450 200 100
-50 20 10 6
-46 500 250 150
-60 20 10 6
-51 500 250 150
NOTE: Expo sed minimum bar rel lengths are inclusive u p to 30-mph/48-kp h wind velocit ies
SIDEWALL
Y
Exterior
Heated
Space
Unheated
Space
Face of Fitting
PENDENT
Y
Exterior
Face of Fitting
Heated
Space
Unheated
Space
Maximum Working Pressure Rating:
175 psi/12 Bar/1207 kPa
Connection to Branch Line (Inlet):
1 inch/25 mm NPT or BSPT
Minimum Bend Radius: 2 inch/50 mm (UL) 7 inch/178 mm (FM)
K-Factor of Sprinkler:
5.6 US/80 metric
Maximum Number of 90° Bends: 4 Bends (UL) – All Hose Lengths 2 Bends (FM) – 38-inch/965-mm Hose Length 3 Bends (FM) – 50-inch/1270-mm Hose Length 4 Bends (FM) – 58-inch/1475-mm Hose Length
I-VICFLEX.VS1_2
REV_D
I-VICFLEX.VS1 / Victaulic® VicFlex™ Style VS1 Dry Sprinkler / Installation Instructions
IMPORTANT INSTALLATION INFORMATION
• Victaulic® VicFlex™ Style VS1 Dry Sprinklers shall be installed according to current, applicable National Fire Protection Association (NFPA 13, 13D, 13R, etc.) standards or equivalent standards. Style VS1 Dry Sprinklers are intended to be installed in wet, dry, or preaction actuated systems. Deviations from these standards or alterations to Style VS1 Dry Sprinklers will void any Victaulic warranty and will impact system integrity. Installations shall meet the provisions of the local authorit y having jurisdiction and local codes, as applicable.
• Victaulic® VicFlex™ Sprinkler Fittings shall not be intermixed with other manufacturer’s flexible sprinkler products.
Transport and store Style VS1 Dry Sprinklers in a cool, dry environment in their original packaging.
Refer to the specific Victaulic product submittal for applications
and listing information. Submittals can be downloaded at victaulic.com.
Size the piping system to provide the minimum operating pressure of 7 psi/0.5 Bar/48 kPa.
Per NFPA requirements, flush the system to remove foreign material. Continue to flush the system until water runs clear.
DO NOT install sprinkler system piping through heating ducts.
DO NOT connect sprinkler system piping to domestic hot water systems.
DO NOT install Style VS1 Dry Sprinklers where they will be exposed to temperatures that exceed the maximum ambient temperature rating for the sprinkler and sprinkler fittings.
Style VS1 Dry Sprinklers have limited flexibility* and are
intended only to be installed with bends not less than their respective minimum bend radii. DO NOT install flexible hose in a straight configuration.
Protect wet piping systems from freezing temperatures.
If construction is altered, the building owner or their representative is responsible for referencing applicable standards to determine if additional Style VS1 Dry Sprinklers or other system adjustments are required.
DO NOT install Style VS1 Dry Sprinklers that have been dropped or struck by another object, even if they do not appear damaged. Never install glass bulb sprinklers if the bulb is cracked or if there is a loss of liquid from the bulb. Discard and replace any Style VS1 Dry Sprinklers that are damaged or show signs of corrosion.
Before installation, verify that the St yle VS1 Dry Sprinkler is the proper style, orifice size, and temperature rating for the intended service.
VICTAULIC® VICFLEX™ STYLE VB2 BRACKET ASSEMBLIES
SHALL BE USED ONLY WITH STYLE VS1 RECESSED PENDENT SPRINKLERS.
VICTAULIC® VICFLEX™ STYLE VB3 BRACKET ASSEMBLIES SHALL BE USED ONLY WITH STYLE VS1 CONCEALED PENDENT SPRINKLERS.
DO NOT paint, coat, plate, or alter Style VS1 Dry Sprinklers. Style VS1 Dry Sprinklers that have been altered from their manufactured condition may not function properly and will void any agency listings and/or approvals.
DO NOT test Style VS1 Dry Sprinklers with a heat source. The glass bulb can weaken or shatter if exposed to a heat source during testing.
Style VS1 Dry Sprinklers that have operated cannot be reassembled or reused, per NFPA requirements. When replacing sprinklers, use new sprinklers of the same type, orifice, temperature, and response.
DO NOT clean St yle VS1 Dry Sprinklers with soapy water, detergents, ammonia, cleaning fluids, or other chemicals. Remove any dust, lint, etc. with a soft, dry cloth.
Inspect Style VS1 Dry Sprinklers on a regular basis for corrosion, mechanical damage, obstructions, etc. The frequency of inspections may vary due to corrosive atmospheres/water supplies and activities around the sprinklers.
DO NOT hang anything from or at tach anything to Style VS1 Dry Sprinklers. Obstructing the discharge pattern will prevent the sprinkler from operating properly.
The owner is responsible for maintaining the fire protection system in proper operating condition.
For minimum maintenance and inspection requirements, refer to NFPA 25 and any other applicable NFPA standards that describe the care and maintenance of sprinkler systems. In addition, the authority having jurisdiction may have additional maintenance, testing, and inspection requirements that shall be followed.
WARNING
• Replacement/relocation of this Victaulic® VicFlex™ Style VS1 Dry Sprinkler SHALL be performed by qualified personnel familiar with the system’s original design criteria, sprinkler listings/ approvals, and state and local codes (including NFPA 13 standards).
Failure to replace/relocate a Style VS1 Dry Sprinkler properly could affect its performance during a fire, resulting in serious personal injury and property damage.
* Reference UL 2443: Section 25.1
STYLE VS1 SPRINKLER ASSEMBLY DRAWING
3
2
1
Recessed Pendent Shown Above
Item Description
1 Swivel Hex Nut
2 Weld Fitting
3 Inlet
I-VICFLEX.VS1_3
I-VICFLEX.VS1 / Victaulic® VicFlex™ Style VS1 Dry Sprinkler / Installation Instructions
STYLE VB1 BRACKET ASSEMBLY DRAWING
2
1
3
STYLE VB2 BRACKET ASSEMBLY DRAWING
2
3
1
4
5
3
5
STYLE VB3 BRACKET ASSEMBLY DRAWING
2
3
1
4
5
3
5
Item Description
1 Style VB1 Bracket
2 Hex Cap Screw
3 Relocation Warning Label
Item Description
1 24-inch/610-mm or 48-inch/1219-mm Square Bar*
2 Center Gate Assembly with Wing Nut
3 Style VB2 End Bracket with Tapping Screw
4 Relocation Warning Label
5 Wing Screw
* Reference submittal document 10.91 for listing information. Square bar length is in reference to nominal ceiling grid spacing.
NOTICE
• VICTAULIC® VICFLEX™ STYLE VB2 BRACKET ASSEMBLIES SHALL BE USED ONLY WITH STYLE VS1 RECESSED PENDENT SPRINKLERS.
Item Description
1 24-inch/610-mm or 48-inch/1219-mm Square Bar*
2 Center Gate Assembly with Wing Nut
3 Style VB3 End Bracket with Tapping Screw
4 Relocation Warning Label
5 Wing Screw
* Reference submittal document 10.91 for listing information. Square bar length is in reference to nominal ceiling grid spacing.
NOTICE
• VICTAULIC® VICFLEX™ STYLE VB3 BRACKET ASSEMBLIES SHALL BE USED ONLY WITH STYLE VS1 CONCEALED PENDENT SPRINKLERS.
Loading...
+ 5 hidden pages