Victaulic KOIL-KIT 799 Series, KOIL-KIT 79V Series, KOIL-KIT 79B Series, KOIL-KIT 79A Series Installation And Maintenance Instructions Manual

Page 1
I-KOIL.KITINSTALLATION AND MAINTENANCE INSTRUCTIONS
KOIL-KIT™ Coil Pack – Series 799, Series 79V with ATC Valve, Series 79B with Bypass, and Series 79A with Bypass and ATC Valve
WARNING
• Depressurize and drain the piping system before attempting to install, remove, adjust, or maintain any Victaulic piping products.
• Wear safety glasses, hardhat, and foot protection.
Failure to follow these instructions could result in death or serious personal injury and property damage.
RECEIVING THE SHIPMENT
Victaulic® KO IL-K I T™ Coil Packs are a pre-packaged and labeled system designed to improve efficiency of hooking up HVAC coils. Upon receipt of the shipment, ensure that the kit is the correct one for the coil being installed. If any components are damaged or missing, contact Victaulic.
Union Port Fitting with Air Vent
The Series 78U Union Port Fitting with Air Vent can be supplied to accommodate up to a three­size reduction. Connections can be configured, as listed below:
• Sweat x Sweat Union (Two Size Reductions)
• Sweat x Female Thread Union (Two Size Reductions)
• Sweat x Male Thread Union (Three Size Reductions)
• Female Thread x Sweat Union (Two Size Reductions)
• Female Thread x Female Thread Union (Two Size Reductions)
• Female Thread x Male Thread Union (Three Size Reductions)
“Y” Strainer/Ball Valve Combination or “T” Ball Valve
SERIES 78Y SERIES 78T
The Series 78Y Strainer/Ball Valve Combination or Series 78T Ball Valve can accommodate up to a two-size reduction from inlet to outlet. Connections can be configured, as listed below:
• Sweat x Sweat Union (Two Size Reductions)
• Sweat x Female Thread Union (Two Size Reductions)
• Sweat x Male Thread Union (Three Size Reductions)
• Female Thread x Sweat Union (Two Size Reductions)
• Female Thread x Female Thread Union (Two Size Reductions)
• Female Thread x Male Thread Union (Three Size Reductions)
Bypass Tee Option
The Bypass Tee option connects to the Series 78Y Strainer/Ball Valve Combination or Series 78T Ball Valve for hookup of the Series 79B KOIL-KIT™ Coil Pack with Bypass or Series 79A KOIL-KIT™ Coil Pack with Bypass and ATC Valve.
Balancing Valves
Series 78 6 Balancing Valve
(Submittal D ocument 0 8.16)
Series 78 K Balancing Valve
(Submittal D ocument 0 8.16)
Series 76K Au tomatic Balan cing Valve
(Submittal D ocument 0 8.34)
Series 76 V Automatic Bal ancing Valve
(Submittal D ocument 0 8.34)
Series 7FP Pressure-Indep endent Combined Balancing and Control Valve with Independent EQM (Equal Percent age Value) Characteristics
(Submittal D ocument 0 8.53)
Series TCP Pressure-Independent
Balancing and Control Valve
(Submittal D ocument 0 8.39)
Series 787 B alancing Valve
(Submittal D ocument 0 8.16)
Series 76B Au tomatic Balan cing Valve
(Submittal D ocument 0 8.34)
Series 76T Automatic Bal ancing Valve
(Submittal D ocument 0 8.34)
Series 7FC C ombined Balancing and Contro l
Valve with Indep endent EQM
(Equal Percentage Value) Characteristics
(Submittal D ocument 0 8.52)
Series TC /TCM TBV Terminal Balancing
and Control Valves
(Submittal D ocument 0 8.38)
Manual or Automatic Air Bleed Valve
The manual or automatic air bleed valve is rated to 250 psi/17 Bar and provides a means of bleeding off trapped air when used with the Series 78U Union Port Fitting, Series 78Y Strainer/Ball Valve Combination, Series 78T Ball Valve, or Series 78K Balancing Valve.
Coil Hoses
Coil hoses are available in 1-foot/0.3-meter, 2-foot/0.6-meter, or 3-foot/0.9-meter lengths for connecting to the inlet and outlet of the coil and are available with the following union ends:
Male Coupling x Female Union End
Male Coupling x Male Swivel Union
Male Coupling x Female Union End with Adapter
REV_F
I-KOIL.KIT_1
Page 2
I-KOIL.KIT / KO I L-K IT™ Coil Pack / Installation and Maintenance Instructions
EXAMPLE COIL COMPONENT ASSEMBLY DRAWING
NOTE: THE FIGURES SHOWN BELOW ARE FOR REFERENCE ONLY AND ILLUSTRATE T YPICAL 2-WAY AND 3-WAY CONFIGURATIONS.
(By Others)
(By Others)
Hose (Optional)
Series 78U
Series 78K
Hose (Optional)
SUPPLY
Series 78Y
RETURN
SWEAT CONNECTIONS
CAUTION
• Valves must be in the fully-open position before attempting to solder the ends.
Soldering a valve in the closed or partially-open position may cause damage to internal components, resulting in valve leakage and property damage.
Make sure the valve is installed in the correct direction of flow (refer to applicable flow direction arrow on the valve body) and that the valve is in the fully-open position before attempting to solder the ends. Connections must be soft soldered with 95/5 (95% tin, 5% antimony) type solder. The valve body must be heat sinked with a wet cloth or putty at the closest joint to protect internal components, and the flame must be directed away from the center of the valve body. DO NOT exceed the temperature rating of the valve (250°F/121°C). Valve bodies must be allowed to cool to room temperature before attempting operation.
THREADED CONNECTIONS
Make sure all threaded connections are clean and free of any burrs. Apply PTFE thread sealant tape or pipe dope to the external threads of all threaded pipe connections. DO NOT use a combination of PTFE thread sealant tape and pipe dope. DO NOT get any tape, dope, or other foreign material into the flow path. NOTE FOR CONNECTING TO FEMALE NPSM SWIVEL ENDS OF COIL HOSES: DO NOT use PTFE thread sealant tape or pipe dope on any NPT threads connecting into the female NPSM swivel end. Tape or dope may prevent proper tightening of the threaded connection, reducing gasket compression.
UNION-TYPE ADAPTERS/CONNECTIONS
The o-rings in union-type adapters/connections must be lubricated with Victaulic Lubricant or silicone to prevent the o-ring from pinching or tearing during installation. Tighten union-type adapters/connections hand-tight, then apply an additional quarter turn. DO NOT over-tighten the connection.
Hose (Optional)
Hose (Optional)
Series 78U
Hose
(Optional)
Bypass
Valve
(Optional)
Series 78T with Bypass Tee Option
Series 787
RETURN
SUPPLY
COIL COMPONENT INSTALLATION
1. Connect the supply side of the Series 78Y Strainer/Ball Valve Combination or Series 78T Ball Valve to the feed pipe via standard threading or sweating practices, as described previously. Make sure the applicable flow direction arrow on the valve body is facing the direction of flow and that the valve body is rotated to the desired position. NOTE: For effective operation, air vents must be positioned at the highest possible location and must point upward.
2. If using coil hoses, make the connection to the coil first. Connect the coil hose to the Series 78Y or Series 78T outlet union joint. Ensure the o-ring is in place on the Series 78Y or Series 78T body. Apply a thin coat of Victaulic Lubricant or silicone to the o-ring. Refer to the “Coil Hose Installation” section for details on bend radius specifications and additional installation requirements.
3. Connect the outlet of the balancing valve to the return pipe via standard threading or sweating practices. NOTE: In order to obtain accurate differential pressure measurements, turbulence should be minimized. Refer to the installation instructions supplied with the applicable valve.
4. Connect the coil hose (if applicable) to the inlet of the Series 78U Union Port Fitting.
NOTICE
• Generally, between the male union outlet of the Series 78U and the inlet of the balancing valve, there is a customer-specified Automatic Temperature Control (ATC) Valve.
• Ensure that the ATC valve contains the correct inlet and outlet sizes. Cutout lengths, etc. will need to be determined on a case-by-case basis, depending on the type of ATC valve being installed.
• If ATC valves are sent to Victaulic for inclusion in kits, verify that the appropriate ATC valve is installed for the particular hook-up to ensure proper design flows and performance.
• Refer to the instructions supplied with the ATC valve for complete installation and maintenance requirements.
I-KOIL.KIT_ 2
REV_F
Page 3
I-KOIL.KIT / KO I L-K IT™ Coil Pack / Installation and Maintenance Instructions
NPT Male
COIL HOSE INSTALLATION
CAUTION
• DO NOT introduce chemicals into the system without verifying compatibility with the EPDM material of the coil hoses.
Failure to follow this instruction could cause damage to the coil hose, resulting in property damage.
Straight Pipe
NPSM Female
Swivel End
Compression
Gasket
Ferrule
Size Inlet Options – inches
Female
NPSM
Nominal ID
inches
Male End
Thread
Swivel
Union inches/mm psi/Bar
½ x ½NPT ½
¾ x ¾ NPT ¾
1 x 1 NPT 1
x 1 ¼ NPT 1 ¼
x 1 ½ NPT 1 ½
2 x 2 NPT 2
The minimum temperature rating for coil hoses is 5°F/-15°C. The maximum temperature rating for coil hoses is 230°F/110°C. Contac t Victaulic if
higher temperature ratings are required. Coil hoses are intended for liquid applications only. DO NOT attempt to use coil
hoses in gas/air applications.
Coil hoses can change in length approximately 4% when pressurized. Allowance must be given to accommodate for this change in length; therefore, coil hoses must not be stretched tightly between the coil and mating component. Refer to the graphics below for examples of correct and incorrect bend configurations.
INCORRECT INCORRECT INCORRECT INCORRECT
Stainless Steel
Braided Hose
Minimum
Bend
Radius
2⁄ 375
67 26
300 114 21
300
140 21
225
172 16
8⁄ 150
213 10 11¼ 150
286 10
Ferrule
End
Maximum
Working
Pressure
The following table contains the minimum distance requirement from each ferrule to the start of the bend. This table must be referenced to prevent the coil hose from being bent too close to the ferrules.
Size
Nominal ID inches
½
¾
1
2
Minimum Distance from Each Ferrule to
Start of Bend inches/mm
1
25
38
2
51
64
3
76
4
102
If male threaded connections have sharp burrs, a thin wall, or rough or uneven edges, Victaulic recommends the use of the female x male coil hose adapter (refer to table below for part codes).
Coil Hose Adapter Size
inches Part Code
½ P- 004-799-ADP
¾ P- 006-799-ADP
1 P- 010-799-A DP
1 ¼ P- 012-799 -ADP
1 ½ P-014 -799 -ADP
2 P-020-799-ADP
If the female swivel connector is being used with the female x male coil hose adapter, apply PTFE thread sealant tape or pipe dope to the male threads that connect into the female swivel connector. DO NOT apply PTFE thread sealant tape or pipe dope to the male threaded end of the coil hose adapter. Tape or pipe dope on the male threaded end of the coil hose adapter may prevent proper tightening of the threaded connection, reducing gasket compression.
To prevent damage to the connections, torque during assembly must not exceed hand-tight plus a quarter turn. The wrench must engage only the hex portion of the coil hose ends. NOTE: Over-tightening of the threaded connection may cause cuts in the compression gasket, resulting in leakage past the compression gasket.
After the system is pressurized, check the coil hoses for leaks or discoloration on the stainless steel braided section or connections. If leaks are present, replace the affected coil hose(s). DO NOT attempt to repair coil hoses.
Tight
CORRECT
+4% Minimum
CORRECT CORRECT
If the minimum bend radius, specified in the table above, falls below the dimension listed for the applicable coil hose size, an angle adapter must be used to avoid sharp bends. NOTE: Failure to follow the minimum bend radius requirements can cause increased pressure drop and damage to the coil hose. If coil hoses are stored or installed at temperatures of 40°F/4°C or lower, the bend radius should be increased by 50%. Use caution to prevent the coil hose from collapsing.
REV_F
MAINTENANCE
WARNING
• Depressurize and drain the piping system before attempting to perform any maintenance on Victaulic products.
Failure to follow this instruction could result in serious personal injury and/or property damage.
A 20-mesh stainless steel strainer basket is included in the body of the Series 78Y Strainer/Ball Valve Combination and must be
20-Mesh Stainless
Steel Strainer Basket
in pressure drop, the 20-mesh stainless steel strainer basket may need to be cleaned. To access the strainer basket, remove the drain valve adapter from the valve body. Clean out the strainer basket and reinstall it into the valve body in the same orientation. Replace the strainer basket or o-ring of the drain valve adapter with new, Victaulic-supplied components if damage is present.
inspected and cleaned after system startup.
Victaulic recommends blowing down the valve every 6 months. If there is an increase
I-KOIL.KIT_ 3
Page 4
I-KOIL.KITINSTALLATION AND MAINTENANCE INSTRUCTIONS
KOIL-KIT™ Coil Pack – Series 799, Series 79V with ATC Valve, Series 79B with Bypass, and Series 79A with Bypass and ATC Valve
INSTALLING THE BALANCING VALVE DRAIN KIT
NOTICE
• System depressurization is not required for drain kit installation; however, caution must be taken to ensure that the long pressure/ temperature (PT) port is not loosened prematurely.
FLOW
Drainage
Nipple
Gasket*
Gasket*
Nut
Cover
The drain kit (part number K-000-786-CBV) for Series 786, 787, and 78K Balancing Valves is sold separately through Victaulic and comes with two new gaskets, a drainage nipple, and a nut.
1. Remove the components from the long pressure/temperature (PT) port, shown in the assembly drawings above. NOTE: The cover with red holder will be re-used when the drain kit is installed.
2. Install the drain kit components, as shown in the drawing above. The new gaskets (provided in the kit) must be installed to prevent leakage from the port. Re-install the cover with red holder onto the nut.
3. Locate the recess under the cover. Insert a 5-mm allen key, and apply 8 - 14 counterclockwise turns to drain from the PT port.
*NOTE: New gaskets must be used.
PRE-SETTING, BALANCING, AND MEASURING
Refer to the applicable installation and setting instructions for the valve supplied with the KOIL-KIT™ Coil Pack.
REPLACEMENT PART INFORMATION
WARNING
PT Ports for Series 78Y Strainer/Ball Valve Combination, Series 78T Ball Valve, Series 78U Union Port Fitting with Air Bleed, or Series 786/787/78K Balancing Valves (Part Number P-002-78Y-PTP for 78Y/78T/78U or K-000-740-003 for 786/787/78K)
The PT ports are field-replaceable. Remove the existing PT port(s), and thread the new port(s) into the valve body. For Series 78Y/78T/78U: Use PTFE thread sealant tape or pipe dope on the threads. For Series 786/787/78K: DO NOT use PTFE thread sealant tape or pipe dope on the threads.
Air Vent for Series 78Y Strainer/Ball Valve Combination, Series 78T Ball Valve, Series 78U Union Port Fitting with Air Bleed (Part Number P-002-78U-MAV)
The air vents are field-replaceable. Remove the existing air vent, and thread the new air vent into the valve body. Use PTFE thread sealant tape or pipe dope on the threads.
Port Extender for Series 78Y Strainer/Ball Valve Combination, Series 78T Ball Valve, or Series 78U Union Port Fitting with Air Bleed
2-inch/51-mm Length (Part Number P-000-78Y-2XT) 4-inch/102-mm Length (Part Number P-000-78Y-4XT)
In applications where KOIL-KIT™ Coil Pack components will be insulated, port extenders are available to extend the PT ports of the Series 78Y or 78T or the air vent of the Series 78U to provide clearance for 2 inches/51 mm or 4 inches/102 mm of insulation. Thread the port extender into the existing PT ports or the existing air vent. Use PTFE thread sealant tape or pipe dope on the threads. NOTE: Depending on the configuration ordered, some KOIL-KIT™ Coil Packs may be supplied with this option factory installed.
Handle Extension for Series 78Y Strainer/Ball
Handle Extension
Valve Combination or Series 78T Ball Valve
• Depressurize and drain the piping system before attempting to perform any maintenance or replace any components.
Failure to follow this instruction could result in serious personal injury and/or property damage.
The following parts are sold separately through Victaulic for KOIL-KIT™ Coil Packs. Contact Victaulic with any order requests or questions regarding these par ts.
Hose-End Drain Assembly for Series 78Y Strainer/ Ball Valve Combination or Series 78T Ball Valve (Part Number P-002-78Y-DRN for ¼-inch NPT or P-004-78Y-DRN for ½-inch NPT)
The hose-end drain assembly is field-replaceable. Remove the existing hose-end drain assembly from the drain valve adapter, and thread the new assembly into the adapter. Use PTFE thread sealant tape or pipe dope on the male threads that connect to the Series 78Y or 78T.
For complete contact information, visit victaulic.com
I-KOIL.KIT 2954 REV F UPDATED 07/2014 Z004799001
VICTAULIC AND KOIL-KIT ARE TRADEMARKS OR REGISTERED TRADEMARKS OF VICTAULIC COMPANY AND/OR ITS AFFILIATED ENTITIES IN THE UNITED STATES AND/OR OTHER COUNTRIES. © 2014 VICTAULIC COMPANY. ALL RIGHTS RESERVED.
In applications where KOIL-KIT™ Coil Pack components will be insulated, the handle extension is available to extend the handle of the Series 78Y or Series 78T valves to provide clearance for 2 inches/51 mm or 4 inches/102 mm of insulation. Remove the hex washer-head screw from the handle assembly. Remove the handle assembly and install the handle extension. Re-install the handle assembly onto the handle extension by using the hex washer-head screw. NOTE: Depending on the configuration ordered, some KOIL-KIT™ Coil Packs may be supplied with this option factory-installed.
78Y
78T
Valve Inlet Size
inches
½ - 1 P- 004 -78Y-2HL P- 004 -78Y-4 HL
1 ¼ - 1 ½ P-012-78Y-2H L P- 012-78Y-4HL
2 P- 020-78Y-2HL P- 020-78Y-4HL
½ - ¾ P- 004 -78Y-2HL P- 004 -78Y-4 HL
1 - 1 ½ P- 012-78Y-2HL P - 012-78 Y-4HL
2 P- 020-78Y-2HL P- 020-78Y-4HL
Part Code for
2-inch/51-mm
Handle Extension
Part Code for
4- inch/102-m m
Handle Extension
Loading...