Victaulic FireLock I-800 Installation Manual

I-800
Victaulic FireLock® CPVC
Sprinkler System Products
DESIGN AND
INSTALLATION MANUAL
DESIGN AND INSTALLATION MANUAL
If you need additional copies of any instructions, or if you have
questions about the safe and proper installation of Victaulic products,
contact Victaulic.
For the most up-to-date information on Victaulic products, visit:
www.victaulic.com
I-800_1
FIRELOCK CPVC SPRINKLER SYSTEM PRODUCTS REV_J
QUICK REFERENCE
Frequently Referenced Sections Page(s)
Handling and Storage of CPVC Pipe and Fittings ............... 7
Chemical Compatibility with CPVC Pipe and Fittings ............. 8
Use with Other Manufacturers’ Pipes, Fittings,
and Solvent Cements:................................. 20
Set and Cure Times ................................ 26 – 27
Painting Pipe and Fittings ............................... 35
Hanger/Support Spacing ............................ 44 – 46
I-800_2
FIRELOCK CPVC SPRINKLER
SYSTEM PRODUCTS REV_J
TABLE OF CONTENTS
Purpose of This Manual .................................................3
Hazard Identification ...................................................3
Installer Safety Instructions ..............................................4
Introduction ..........................................................5
Helpful Information – English and Metric Conversion Chart .....................6
Handling and Storage of CPVC Pipe and Fittings..............................7
Chemical Compatibility with CPVC Pipe and Fittings...........................8
Handling and Storage of One-Step Solvent Cement............................9
System Approvals, Listings, Usage, and Standards ...........................10
Light Hazard Occupancies:............................................10
Residential Occupancies: .............................................10
Concealed Installations: ..............................................10
Ordinary Hazard Installations: ..........................................11
Exposed Installations: ................................................11
Extended Coverage Sprinklers: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Return Air Plenums Installations: .......................................12
Combustible Attic Installations with Specific-Application Sprinklers: .............12
Multi-Purpose Systems: ..............................................12
Combustible Concealed Installations with Specific-Application Sprinklers: ........13
Unfinished Basements with Exposed, Solid-Wood Joist Installations: ............13
System Risers (Protected and Exposed):..................................15
Garage Installations: .................................................17
High Temperature Areas: .............................................17
Cold Temperature Areas: .............................................18
Underground Fire Service: ............................................19
Factory Mutual:.....................................................19
NSF
®
International: ..................................................19
Penetrating Fire-Rated Walls and Partitions: ...............................20
Heat Sources and Open Ceiling Areas: ...................................20
Use with Other Manufacturers’ Pipes, Fittings, and Solvent Cements: ...........20
Installation & Joining Section............................................21
Cutting the Pipe ....................................................21
Deburring and Beveling...............................................22
Fitting Preparation ..................................................22
Solvent Cement Application ...........................................23
Assembly .........................................................26
Set and Cure Times .................................................26
Threaded Connections ...............................................28
Transition to Other Materials ...........................................30
Flange Connections .................................................30
Grooved Connections ................................................32
System Acceptance Testing (Hydrostatic Pressure Test) .......................34
Painting Pipe and Fittings ..............................................35
Cut-In Procedures for System Modification or Repair .........................36
Accessories..........................................................38
Adjustable Sprinkler Adapter Installation Instructions .........................42
Engineering Data Section ...............................................43
Pipe and Fitting Specifications .........................................43
Hydraulic Design....................................................43
Hanger/Support Spacing................................................44
Riser Supports .......................................................47
Exposed Installations ................................................47
Earthquake Bracing .................................................47
Tre nc hing ...........................................................48
Snaking/Deflection of Pipe..............................................49
Backfilling...........................................................51
Appendix A – Design Criteria for Combustible Concealed Installations
Incorporating Victaulic FireLock CPVC Sprinkler System Products and Victaulic
Model V2502 or Viking Coin™ (VK900) Specific Application Sprinklers ........52
Appendix B – Design Criteria for Combustible Concealed Installations
Involving Victaulic FireLock CPVC Sprinkler System Products and
Tyco Fire Products Model CC1 Combustible Concealed Sprinklers .............57
Material Properties ....................................................58
Expansion and Contraction..............................................59
Style #899 FireLock CPVC One-Step Solvent Cement MSDS Sheet ..............62
Warranty ............................................................64
Facilities ...........................................................B/C
I-800_3
FIRELOCK CPVC SPRINKLER SYSTEM PRODUCTS REV_J
PURPOSE OF THIS MANUAL
This manual is intended for use by specifiers, installers, and users in the selection, design, installation, and inspection of Victaulic FireLock CPVC Piping Systems for Fire Protection Service. Due to the critical safety and loss prevention uses of such systems, all information contained herein is considered vital to obtain proper system performance and must be read and understood carefully before starting the installation. If you have any questions, or if you need additional copies of this manual, contact Victaulic at (800) PICK VIC or (800) 742-5842.
HAZARD IDENTIFICATION
Definitions for identifying the various hazard levels are provided below.
This safety alert symbol indicates important safety messages. When you see this symbol, be alert to the possibility of personal injury. Carefully read and fully understand the message that follows.
DANGER
The use of the word “DANGER” • identifies an immediate hazard with a likelihood of death or serious personal injury if instructions, including recommended precautions, are not followed.
WARNING
The use of the word “WARNING” • identifies the presence of hazards or unsafe practices that could result in death or serious personal injury if instructions, including recommended precautions, are not followed.
CAUTION
The use of the word “CAUTION” • identifies possible hazards or unsafe practices that could result in personal injury and product or property damage if instructions, including recommended precautions, are not followed.
NOTICE
The use of the word “NOTICE” • identifies special instructions that are important but not related to hazards.
I-800_4
FIRELOCK CPVC SPRINKLER
SYSTEM PRODUCTS REV_J
INSTALLER SAFETY INSTRUCTIONS
Read and understand this manual before proceeding with the installation 1.
and testing of the Victaulic FireLock CPVC System. Education and a complete
understanding of the instructions provided are requirements for the installer of the Victaulic FireLock CPVC System. These instructions contain important information. If you need additional copies, or if you have any questions about the safe installation and use of this system, contact Victaulic Company, P.O. Box 31, Easton, PA 1804 4-0 031 USA, Telephone 800-PICK-VIC or 800-742-58 42.
Use only recommended accessories.
2. Use of improper accessories or unapproved
system components in conjunction with the Victaulic FireLock CPVC System will void the warranty and may result in improper operation of the system.
Avoid dangerous environments.
3. If utilizing electrically powered tools for installation,
be sure that the area is free of moisture or wetness that could create an unsafe condition. Keep work area well illuminated. Allow sufficient space for measuring and system dry fit to accommodate proper installation.
Prevent back injury.
4. Always practice safe lifting and installation techniques.
Use only tools specifically designed for plastic pipe and fittings.
5.
Inspect the products.6. Be sure that all parts are included and that you have all
necessary tools available to properly install the system.
Wear safety glasses, hardhat, and safety footwear.
7. Always practice safety first.
When solvent-cementing, always work in a well-ventilated area.
8.
Wear protective gloves.9. PVA-coated protective gloves are recommended for use
while solvent cementing. If hands come in contact with solvent cement, use a waterless, abrasive soap.
When solvent-cementing, avoid sources of heat or open flames. DO NOT smoke.
10.
Keep work area clean.11. Cluttered areas and slippery floors invite accidents.
Wear ear protection.
12. Protect your hearing if you are exposed to long periods of very
noisy job-site operations.
Keep visitors away.
13. All visitors should be kept a safe distance away from the work
area.
I-800_5
FIRELOCK CPVC SPRINKLER SYSTEM PRODUCTS REV_J
INTRODUCTION
Victaulic FireLock CPVC Sprinkler System Products are manufactured from high-quality, Post-Chlorinated Polyvinyl Chloride (CPVC), a specialty thermoplastic material. Victaulic FireLock CPVC Sprinkler System Products are designed specifically for fire sprinkler systems. They provide unique advantages over traditional sprinkler piping systems through superior hydraulics, ease of installation and handling, and quick assembly using readily available, inexpensive tools. In addition, Victaulic Style #899 FireLock CPVC One-Step Solvent Cement eliminates the need for primers that are typical in two-step cementing processes. The one-step process simplifies installation and reduces labor time.
DANGER
Victaulic FireLock CPVC Sprinkler System Products must be used in wet systems • only. A wet piping system contains water and is connected to a water supply system so that the water will discharge immediately when the sprinkler activates.
Victaulic FireLock CPVC Sprinkler System Products must never be used in a • system that uses compressed air or other gases.
Failure to follow these instructions could result in severe personal injury, significant property damage, and product damage.
CAUTION
DO NOT use Victaulic FireLock CPVC Sprinkler System Products in outdoor • applications. These products are not Listed for outdoor applications.
Failure to follow this instruction could result in product failure and property damage and will not be covered under the Victaulic CPVC warranty.
I-800_6
FIRELOCK CPVC SPRINKLER
SYSTEM PRODUCTS REV_J
HELPFUL INFORMATION – ENGLISH AND METRIC CONVERSION CHART
The following chart is a guideline for converting English and metric measurements. The English measurements, given throughout this manual, are the actual values. It is important that accurate metric conversions are made to ensure proper installation of Victaulic FireLock CPVC Sprinkler System Products.
Convert Imperial (U.S.) to Metric
Convert Metric to Imperial (U.S.)
25.4 ×
Inches
(In.)
Millimeters
(mm)
× 0.03937
0.3048 ×
Feet
(Ft.)
Meters
(m)
× 3.281
0.4536 ×
Pounds
(Lbs.)
Kilograms
(kg)
× 2.205
28.35 ×
Ounces
(Oz.)
Grams
(g)
× 0.03527
6.894 ×
Pressure
(psi)
Kilopascals
(kPa)
× 0.145
.069 × Pressure
Bar × 14.5
4.45 ×
End Load
(Lbs.)
Newtons
(N)
× 0.2248
1.356 ×
Torque
(Lb. Ft.)
Newton Meters
(N•m)
× 0.738
F – 32 ÷ 1.8
Temp.
(°F)
Celsius
(°C)
C + 17.78 × 1.8
745.7 ×
Horsepower
(hp)
Watts
(w)
× 1.341 × 10
-3
3.785 ×
Gal. per Min.
(GPM)
Liters per min.
(L/M)
× 0.2642
3.7865 ×
10
-3
Gal. per Min.
(GPM)
Cubic Meters per min.
(m3/m)
× 264.2
I-800_7
FIRELOCK CPVC SPRINKLER SYSTEM PRODUCTS REV_J
HANDLING AND STORAGE OF CPVC PIPE AND FITTINGS
Victaulic FireLock CPVC Sprinkler System pipe and fittings should be stored at normal ambient temperatures, which must not exceed the maximum installation temperature of 1 50 °F.
Victaulic recommends storing FireLock CPVC Sprinkler System Products indoors where the product will not be exposed to heat-producing sources or sunlight. For extended indoor storage, the area must be well ventilated so that the ambient temperature does not exceed 150ºF.
If stored outdoors, Victaulic FireLock CPVC Sprinkler System Products must be covered with a non-transparent material to reduce the risk of extended exposure to sunlight and heat absorption, which could cause discoloration and weakening of CPVC material. Victaulic FireLock CPVC Sprinkler System Fittings must be stored in their original containers to prevent dirt accumulation and to help reduce the possibility of damage.
Excessive loading (i.e. stacking, point loading, etc.) or excessive strapping or banding must be avoided to prevent CPVC material from warping. DO NOT drop CPVC products or allow anything to drop on them.
Before installation, CPVC products must be inspected for any scratches, splits, gouges, or warping that may have occurred from improper handling or storage. Damaged sections of CPVC pipe must be cut out and discarded. Any damaged fittings must be discarded.
WARNING
Victaulic FireLock CPVC Sprinkler System pipe and fittings MUST NOT be • subjected to prolonged sunlight exposure.
The ambient storage temperature MUST NOT exceed 150ºF.•
If stored outdoors, fittings must be stored in the original shipping containers, • and pipe must be covered with a non-transparent material.
DO NOT install Victaulic FireLock CPVC Sprinkler System pipe and fittings that • have been damaged during handling or storage.
Failure to follow these instructions could cause system failure, resulting in property damage and personal injury due to leaks.
I-800_8
FIRELOCK CPVC SPRINKLER
SYSTEM PRODUCTS REV_J
CHEMICAL COMPATIBILITY WITH CPVC PIPE AND FITTINGS
When combining steel with Victaulic FireLock CPVC products in a system, all steel components must be degreased then flushed thoroughly to remove internal and external oils before assembly.
FireLock CPVC products may be damaged by chemicals that are not corrosive to metallic piping. These damaging chemicals can be found in common substances used in construction and residential settings. Specific chemicals or chemical vapors that contact CPVC can weaken or severely damage the material.
DO NOT expose product to edible oils, cooking oils, esters, ketones, or glycol-based anti­freeze fluids.
DO NOT expose product to petroleum-based substances, such as cutting oils, packing oils, traditional pipe thread paste and dope, termiticides, insecticides, surfactants, plasticizers, and building caulks.
To avoid contamination with hydrocarbons, DO NOT store CPVC fittings in bins with metal fittings or handle CPVC products with oil-contaminated hands or gloves.
Refer to the following:
“Threaded Connections” section for compatible thread sealants
“Grooved Connections” section for compatible lubricants
“Penetrating Fire-Rated Walls and Partitions” section for compatible fire-stopping products
WARNING
CPVC piping components, including Victaulic FireLock CPVC Sprinkler System • Products, may be damaged by chemicals that are not corrosive to metallic piping. These damaging chemicals can be found in common substances used in construction and residential settings.
DO NOT expose CPVC products to edible oils, cooking oils, esters, ketones, or • glycol-based anti-freeze fluids.
DO NOT expose CPVC products to petroleum-based substances, such as • cutting oils, packing oils, traditional pipe thread paste and dope, termiticides, insecticides, surfactants, plasticizers, and building caulks.
When combining steel with CPVC products in a system, all steel components • must be degreased then flushed thoroughly to remove internal and external oils before assembly.
To avoid contamination with hydrocarbons, do not store CPVC products in • containers with metal fittings.
Handle CPVC products with clean hands and gloves only.•
Failure to follow these instructions may cause cracks or fractures in CPVC products, resulting in property damage and personal injury due to leaks or flooding. Alternatively, partial or full system replacement may be required due to the presence of visible cracks.
For questions regarding chemical compatibility with CPVC products, contact Victaulic at 1-800-554-4434 or by e-mail at engserv@victaulic.com.
I-800_9
FIRELOCK CPVC SPRINKLER SYSTEM PRODUCTS REV_J
HANDLING AND STORAGE OF ONE-STEP SOLVENT CEMENT
Victaulic Style #899 FireLock CPVC One-Step Solvent Cement must be stored out of direct sunlight in ambient temperatures between 40°F and 110°F. The solvent cement may be used for a period of two years from the date stamped on the container. Expired solvent cement must be discarded in an environmentally friendly fashion, in accordance with local regulations. To prolong the life of the cement, the containers must be kept tightly closed when not in use and covered as much as possible during use. Refer to the “Solvent Cementing Procedures” section for more information.
DANGER
Before using Victaulic Style #899 FireLock CPVC One-Step Solvent Cement, • refer to ASTM-F402-05, “Standard Practice for Safe Handling of Solvent Cements, Primers, and Cleaners Used for Joining Thermoplastic Pipe and Fittings.” In addition, refer to the solvent cement Material Safety Data Sheet (MSDS) and the solvent cement can label for important information.
Victaulic Style #899 FireLock One-Step Solvent Cement is highly flammable. • Make sure all ignition sources are eliminated before use.
Avoid breathing solvent cement vapors, and use solvent cement only in well-• ventilated areas. Explosion-proof, general mechanical ventilation or local exhaust is recommended to maintain vapor concentrations below recommended exposure limits. In confined or partially enclosed areas, a NIOSH-approved, organic-vapor cartridge respirator with a full-face piece is recommended.
Avoid frequent contact with skin. PVA coated gloves and an impervious apron • are recommended.
Avoid contact with eyes. Splash-proof chemical goggles are recommended.•
Failure to follow these instructions could result in serious personal injury.
WARNING
Follow all instructions contained in this manual when solvent cementing • Victaulic FireLock CPVC Sprinkler System products.
Avoid puddling solvent cement on or within the fitting or pipe.•
DO NOT allow solvent cement to run into the inside or on the outside of the pipe • or fitting.
Failure to follow these instructions could cause the pipe or fitting to fracture, resulting in serious personal injury and/or significant property damage.
I- 80 0_10
FIRELOCK CPVC SPRINKLER
SYSTEM PRODUCTS REV_J
SYSTEM APPROVALS, LISTINGS, USAGE, AND STANDARDS
Victaulic FireLock CPVC Sprinkler System Products are Underwriters Laboratories Inc. (UL) Listed and Factory Mutual (FM) Approved for use in wet-pipe sprinkler systems. In addition, these products are approved by NSF
®
International for use in potable water systems (refer to page 19 for more information). Victaulic Style #899 FireLock CPVC One-Step Solvent Cement meets ASTM-F493 and NSF International requirements.
National Fire Protection Association (NFPA) Standards 13, 13R, and 13D must be referenced for design and installation requirements in addition to this manual.
The following section summarizes the agency approvals, listings, usage, and standards that Victaulic FireLock CPVC Sprinkler System Products meet. For more specific listing information concerning FM or NSF International, contact Victaulic.
Light Hazard Occupancies:
Victaulic FireLock CPVC Sprinkler System Products are UL Listed for use in Light Hazard Occupancies, as defined in NFPA 13, “Standard for the Installation of Sprinkler Systems.”
Residential Occupancies:
Victaulic FireLock CPVC Sprinkler System Products are UL Listed for use in:
Residential occupancies, as defined in NFPA 13R, “Standard for the Installation
1.
of Sprinkler Systems in Residential Occupancies up to and Including Four Stories in Height.”
Residential occupancies, as defined in NFPA 13D, “Standard for the Installation of
2.
Sprinkler Systems in One- and Two-Family Dwellings and Manufactured Homes.”
Residential occupancies, as defined in NFPA 13, “Automatic Sprinkler Systems
3.
Handbook 2007 Edition”
Concealed Installations:
Victaulic FireLock CPVC Sprinkler System Products are UL Listed for use in concealed installations with the following provisions.
The minimum protection shall consist of one layer of •
⁄-inch gypsum wallboard,
½-inch plywood soffits, or a suspended membrane ceiling with lay-in panels or
tiles having a weight of not less than .35 lbs/ft
2
when installed with metallic support
grids.
The minimum protection for residential occupancies, defined in NFPA 13D and 13R, • may consist of one layer of
½-inch plywood.
Victaulic FireLock CPVC Sprinkler System Products must be used in sprinkler • systems employing sprinklers rated at 225°F or lower.
NOTICE
Victaulic FireLock CPVC Sprinkler System Products CANNOT be installed in • spaces defined by NFPA 13 as combustible, concealed spaces that require sprinklers, unless the space is protected by sprinklers that are specifically Listed for the application.
NFPA 13D and NFPA 13R permit the omission of sprinklers in combustible, • concealed spaces. Victaulic FireLock CPVC Sprinkler System Products can be installed in these areas when sprinkling residential occupancies in accordance with these standards.
I-8 00_11
FIRELOCK CPVC SPRINKLER SYSTEM PRODUCTS REV_J
Ordinary Hazard Installations:
In accordance with NFPA 13 (2007 Edition), paragraph 6.3.6.2, “Pipe or tube listed • for light hazard occupancies shall be permitted to be installed in ordinary hazard rooms of otherwise light hazard occupancies where the room does not exceed 400 ft
2
.” Follow all instructions contained in this manual for proper installation of
Victaulic FireLock CPVC pipe and fittings.
Exposed Installations:
Victaulic FireLock CPVC Sprinkler System Products are UL Listed for use in installations without protection (exposed), with the following restrictions:
Exposed CPVC Fire Sprinkler piping is installed below a smooth, flat, horizontal • ceiling construction utilizing UL Listed support devices.
Listed, Quick-Response, ordinary temperature-rated pendent sprinklers having • deflectors installed within 8 inches from the ceiling. Listed, Residential, ordinary temperature-rated, pendent sprinklers located in accordance with their Listing. The maximum distance between sprinklers must not exceed 15 feet. The piping must be mounted directly to the ceiling.
Listed, Quick-Response, ordinary-temperature-rated horizontal sidewall sprinklers • having deflectors installed within 6 inches from the ceiling and within 6 inches from the sidewall. Listed, Residential, ordinary temperature-rated horizontal sidewall sprinklers located in accordance with their Listing. The maximum distance between sprinklers must not exceed 14 feet. Piping must be mounted directly to the sidewall.
Listed, Quick-Response, upright sprinklers having a maximum temperature rating • of 155°F must be installed so that the deflectors are a maximum of 4 inches from the ceiling. The maximum distance from the ceiling to the centerline of the main run of pipe must be 7
½ inches. The maximum distance between sprinklers must not
exceed 15 feet. The distance from the centerline of a sprinkler to a hanger must be 3 inches. Rigid pipe hangers secured to the ceiling must be used.
Extended Coverage Sprinklers:
Victaulic FireLock CPVC Sprinkler System Products are UL Listed for installations without protection (exposed) when installed with extended coverage sprinklers with the following provisions.
Exposed piping must be installed below a smooth, flat, horizontal ceiling • construction.
Listed pendent, light-hazard, quick-response, extended-coverage sprinklers with • a maximum temperature rating of 155°F must be installed within 8 inches from the ceiling. The distance between sprinklers must not exceed 20 feet, and the application density must be at least 0.10 gpm/ft
2
. Piping must be mounted directly
to the ceiling.
Listed pendent, residential sprinklers with a maximum temperature rating of 155ºF • must be installed within 8 inches from the ceiling. The distance between sprinklers must not exceed 20 feet, and the application density must be at least 0.10 gpm/ft
2
.
Piping must be mounted directly to the ceiling.
Listed horizontal sidewall, light-hazard, quick-response, extended coverage • sprinklers with a maximum temperature rating of 165ºF must be installed within 12 inches from the ceiling and within 6 inches from the sidewall. The distance between sprinklers must not exceed 18 feet, and the application density must be at least 0.10 gpm/ft
2
.
Listed, Quick-Response, (200°F maximum temperature-rated) horizontal sidewall • sprinklers having deflectors installed within 12 inches from the ceiling and within 6 inches from the sidewall. Listed, Residential, ordinary temperature-rated horizontal sidewall sprinklers located in accordance with their Listing. The maximum distance between sprinklers must not exceed 14 feet. Piping must be mounted directly to the sidewall.
I-800_12
FIRELOCK CPVC SPRINKLER
SYSTEM PRODUCTS REV_J
Listed horizontal sidewall, light-hazard, quick-response, extended coverage • sprinklers with a maximum temperature rating of 175°F must be installed with the deflectors within 12 inches from the ceiling and within 6 inches from the sidewall. The distance between sprinklers must not exceed 16 feet, and the application density must be at least 0.10 gpm/ft
2
.
Listed horizontal sidewall, light-hazard, quick-response, extended coverage • sprinklers manufactured by Reliable Automatic Sprinkler Co. (SIN RA0362) with a maximum temperature rating of 155°F must be installed with the deflectors within 12 inches from the ceiling and within 6 inches from the sidewall. The distance between sprinklers must not exceed 24 feet, and the flow must not be less than 40 gpm per sprinkler.
Listed horizontal sidewall, residential sprinklers with a maximum temperature rating • of 165ºF must be installed within 12 inches from the ceiling and within 6 inches from the sidewall. The distance between sprinklers must not exceed 18 feet, and the application density must be at lest 0.10 gpm/ft
2
.
These installations require the use of Schedule 80 fittings in sizes 1 •
½ inches and
larger.
The piping for horizontal sidewall sprinklers shall be mounted directly to the sidewall.•
The end-use application is limited to unobstructed construction only.•
Solvent cemented joints may be made with Victaulic Style #899 FireLock CPVC One-• Step Solvent Cement or any of the solvent cement products listed in this manual.
Return Air Plenums Installations:
Victaulic FireLock CPVC Sprinkler System Products meet the combustibility requirements for thermoplastic sprinkler pipe, as described in the Standard for Installation of Air Conditioning and Ventilating Systems, NFPA 90A.
Victaulic FireLock CPVC Sprinkler System Products must be installed in the plenum • space adjacent to, but not over, an opening in the ceiling, such as a ventilation grill.
Combustible Attic Installations with Specific-Application Sprinklers:
Specific Application Attic Sprinklers are designed to provide protection of specific, light­hazard combustible and non-combustible attic spaces that require sprinkler protection. The sprinklers must be installed in accordance with Tyco Fire Products’ Technical Data Sheets TFP610 for Specific Application Attic Sprinklers. Victaulic FireLock CPVC Sprinkler System Products can be installed within an attic space, provided that the attic space is protected with UL Listed Tyco Fire Products Specific Application Attic Sprinklers, and the CPVC pipe and fittings are used only to feed the wet sprinkler system below the ceiling.
According to the guidelines found in TFP610, Victaulic FireLock CPVC pipe must be covered by 6 inches minimum of non-combustible insulation that extends 12 inches on each side of the pipe centerline (when protected above with Specific Application Attic Sprinklers). If the pipe is installed between the ceiling joists, and the area above is protected by Specific Application Attic Sprinklers, the joist channel must be covered or filled with 6 inches of non-combustible insulation on top of the pipe. NOTE: Insulation is for fire protection purposes only; it is not intended for freeze protection.
Multi-Purpose Systems:
Multi-purpose systems are defined as a piping system designed to serve both domestic and fire protection needs in a residential occupancy. Victaulic FireLock CPVC Sprinkler System Products are UL Listed for use in multi-purpose systems, as defined in NFPA 13R and NFPA 13D, where there are no provisions to prevent domestic water flow upon activation of the sprinkler system. Design and installation of these types of systems shall be in accordance with Chapter 6 of the 2002 edition of NFPA 13R and NFPA 13D.
I-800_13
FIRELOCK CPVC SPRINKLER SYSTEM PRODUCTS REV_J
Combustible Concealed Installations with Specific-Application Sprinklers:
In accordance with the UL Listing, Victaulic FireLock CPVC Sprinkler System Products can be used in specific light-hazard, combustible concealed and non-combustible concealed spaces that require sprinkler protection when installed with UL Listed Victaulic Model V2502, Viking Coin (VK900), or Tyco Fire Products Model CC1 specific-application sprinklers. The system must be installed in accordance with the information contained in Appendix A or Appendix B. For the Victaulic Model V2502, additional reference should be made to Submittal 40.09. For the Viking Coin (VK900), additional reference should be made to the “Technical Data” sheet (Form No. F_110503 or Form No. F_110603). For the Tyco Fire Products Model CC1 sprinkler, refer to the “Model CC1 Combustible Concealed Space Sprinkler Technical Data Sheet” (TFP630).
NOTICE
When installing Victaulic FireLock CPVC Sprinkler System Products in • combustible concealed areas that require sprinkler protection, the Victaulic Model V2502, Viking Coin (VK900), or Tyco Fire Products Model CC1 Sprinkler must be used in accordance with the UL Listing. Contact the local authority having jurisdiction with questions concerning code requirements.
Unfinished Basements with Exposed, Solid-Wood Joist Installations:
NOTICE
Use of Victaulic FireLock CPVC Sprinkler System Products is limited to • basements where the quantity and combustibility of contents is low and fires with relatively low rates of heat release are expected.
Refer to NFPA 13D, “Standard for the Installation of Sprinkler Systems in • One-and Two-Family Dwellings and Manufactured Homes” for more information regarding installations in unfinished basements with exposed, solid-wood joists.
Victaulic FireLock CPVC Sprinkler System Products can be installed in unfinished basements with exposed, solid-wood joists with the following limitations:
The ceiling must be horizontal and must be constructed of nominal 2-inch x 10-inch • solid wood joists on 16-inch centers.
– OR –
The ceiling must be horizontal and must be constructed of nominal 2-inch x 12-inch • solid wood joists on 16-inch centers. When Victaulic FireLock CPVC Sprinkler System Products are used in constructions with 2-inch x 12-inch solid wood joists, the maximum system working pressure under flowing conditions must not exceed 100 psi. The maximum system working pressure under non-flowing conditions must not exceed 175 psi. Refer to Figure “A” on page 16.
For installations involving 2-inch x 10-inch solid wood joists or 2-inch x 12-inch
1.
solid wood joists, all solvent cement joints must be made by using Victaulic Style #899 FireLock CPVC One-Step Solvent Cement or any of the solvent cement products listed in this manual.
Schedule 80 fittings are required for installations involving 1
2. ½-inch through 2-inch
piping.
The distance from the floor to the bottom of the solid wood joists must be between
3.
7 feet and 8 feet.
I-800_14
FIRELOCK CPVC SPRINKLER
SYSTEM PRODUCTS REV_J
All system mains must run perpendicular to the joists, and all branch lines must run 4.
parallel to the joists.
CEILING
BLOCKING
16
inches
2 x 10 or 2 x 12
Solid Wood
Joists (Typical)
When the total protected area exceeds 1,000 square feet, blocking must be used 5.
in-between the joists to divide the area into sections; these sections must not exceed 1,000 square feet. Refer to the drawing above.
The maximum length along the joist must not exceed 32 feet. If the length exceeds
6.
32 feet, blocking must be used. The blocking must be constructed of minimum ½-inch plywood and must be equal to the full depth of the wood joists.
Listed, residential-pendent sprinklers with a maximum temperature rating of 155°F
7.
and a minimum K-factor of 3.0 must be used for this type of installation. NOTE: The maximum sprinkler spacing must not exceed 12 feet.
The system must be designed to UL Listed flows for the sprinkler being used.
8.
However, the flow must not be less than 11 gpm per sprinkler. Sprinklers must be installed with the deflectors below the solid wood joists for future installation of a finished ceiling. However, deflector placement must not exceed 1
¾ inches below the solid wood
joist in anticipation of a future finished ceiling installation (refer to Figures “B” and “C” below). For more information, refer to NFPA 13D, “Standard for the Installation of Sprinkler Systems in One-and Two-Family Dwellings and Manufactured Homes.”
Branches Supported with Blocking Branches Supported with Hangers
½ Joist
Depth Max.
1¾" Max.
FIGURE “B”
½ Joist
Depth Max.
1¾" Max.
FIGURE “C”
When installing Victaulic FireLock CPVC Sprinkler System Products perpendicular
9.
(system mains) to solid wood joists, UL Listed support devices must be used to mount the piping directly to the bottom of the solid wood joists. In addition, it is acceptable to cut holes in the solid wood joists at or below the center depth of the solid wood joist for support. Holes must be oversized to allow for movement and must be located in an area that will not compromise joist integrity. Contact the local authority having jurisdiction for information regarding structural integrity.
I-800_15
FIRELOCK CPVC SPRINKLER SYSTEM PRODUCTS REV_J
When installing Victaulic FireLock CPVC Sprinkler System Products parallel (branch 10.
lines) to solid wood joists, the pipe and fittings must be installed in the cavity below the bottom of the ceiling and above the bottom of the joist. Branch lines must be located at or below the center depth of the solid wood joist. UL Listed support devices must be used to mount the piping directly to nominal 2-inch wood blocking. In addition, UL Listed support devices can be used that offset the pipe a nominal distance of 1
½ inches from
the solid wood joists.
System Risers (Protected and Exposed):
Victaulic FireLock CPVC Sprinkler System Products are UL Listed for use as system risers in accordance with NFPA 13R and NFPA 13D with the following limitations.
A. CPVC risers must be installed in accordance with NFPA 13, “Support of Risers.”
B. When the system riser is installed protected (concealed), the minimum protection
must consist of one layer of
⁄-inch gypsum wallboard or ½-inch plywood. Refer to the
“Hanger/Support Spacing” section for detailed installation instructions for riser supports.
C. When the system riser is installed without protection (exposed), the following limitations apply. NOTE: Only NFPA 13R and NFPA 13D applications can be installed exposed.
The riser must be installed below a smooth, flat, horizontal ceiling construction. • A UL Listed, residential-pendent sprinkler must be located in accordance with its Listing and must be installed at a maximum horizontal distance of 12 inches from the centerline of the riser. Refer to Figure “A” on page 16.
– OR –
The riser must be installed below a horizontal, unfinished basement ceiling in • accordance with NFPA 13D. The unfinished basement ceiling must be constructed of nominal 2-inch x 10-inch or 2-inch x 12-inch exposed solid wood joists on 16-inch centers. Refer to Figure “A” on page 16.
When installing Victaulic FireLock CPVC Sprinkler System Products in constructions
1.
with 2-inch x 12-inch solid wood joists, the maximum system working pressure under flowing conditions must not exceed 100 psi. The maximum system working pressure under static (non-flowing) conditions must not exceed 175 psi.
A UL Listed residential-pendent sprinkler with a maximum temperature rating of
2.
155ºF and a minimum K-factor of 3.0 is required at a maximum horizontal distance of 12 inches from the centerline of the riser. The deflector must be a maximum of 1
¾ inches
below the bottom of the solid wood joist; this is in anticipation of a future finished ceiling. The system must be designed to UL Listed flows for the sprinkler being used. However, the flow must not be less than 11 gpm per sprinkler.
The riser must be supported vertically within 2 feet from the ceiling or bottom of the
3.
joist.
UL Listed riser pipe sizes must be between 1 inch and 2 inches inclusive.
4.
The maximum distance between the walls and the outside surface of the riser pipe 5.
must be 1 ½ inches. Refer to Figure “A” on page 16.
Solvent cemented joints may be made with Victaulic Style #899 FireLock CPVC
6.
One-Step Solvent Cement or any of the solvent cement products listed in this manual.
These installations require the use of Schedule 80 fittings for risers that are 1
7. ½
inches and larger.
I- 80 0_16
FIRELOCK CPVC SPRINKLER
SYSTEM PRODUCTS REV_J
32 feet Maximum to Wall or Blocking
1½ inches Maximum from
Wall to Edge of Riser
2 feet Maximum
to Support
12 inches Maximum to Center of Riser
12 feet Maximum
6 feet Maximum
6 feet Maximum
2 x 10 or 2 x 12
16-inch centers
1¾ inches Max.
Branch
Main
Riser
Figure “A”
I- 800_17
FIRELOCK CPVC SPRINKLER SYSTEM PRODUCTS REV_J
Garage Installations:
Victaulic FireLock CPVC Sprinkler System Products are suitable for use in garages requiring sprinklers, as defined in NFPA 13R, with the following requirements:
Minimum protection consisting of either one layer of
1. ⁄-inch thick gypsum or ½-inch thick plywood must be provided.
Listed pendent or sidewall sprinklers with a maximum temperature rating of 225°F
2.
must be used.
All sprinklers must be installed per the manufacturer’s published installation
3.
instructions.
The system must be installed per the requirements of NFPA 13R and these
4.
installation instructions.
High Temperature Areas:
Victaulic FireLock CPVC Sprinkler System Products are suitable for use in areas • where ambient temperatures are within the range of 35°F to 150°F.
Victaulic FireLock CPVC Sprinkler System Products can be installed in areas, such • as an attic, where the ambient temperature exceeds 150°F if ventilation is provided or if insulation is used around the product to maintain a cooler environment.
WARNING
DO NOT install Victaulic FireLock CPVC Sprinkler System Products in an area • where the ambient temperature will exceed 150°F, unless ventilation is provided or insulation is used around the product.
Failure to follow this instruction could result in significant property damage and product damage.
I-800_18
FIRELOCK CPVC SPRINKLER
SYSTEM PRODUCTS REV_J
Cold Temperature Areas:
Victaulic FireLock CPVC Sprinkler System Products can be used if the ambient • temperature remains above 35°F.
In addition, these products can be used if the installation is in an area subject • to freezing temperatures; however, the sprinkler system must be protected from freezing. Many standard cold weather piping design and installation practices can be used to protect the system from freezing, including, but not limited to, the use of glycerin, insulation installation techniques, and pipe insulation. Contact Victaulic with questions concerning compatibility. NOTE: Attention must be given to local insulating techniques and codes that require a particular method.
Antifreeze solutions of water and USP or CP grade GLYCERIN are acceptable for use • with Victaulic FireLock CPVC Sprinkler System Products. Refer to NFPA 13, NFPA 13R, and NFPA 13D.
WARNING
DO NOT allow a sprinkler system to freeze. A frozen system will deactivate, and • the pressure can damage pipe or cause sprinklers to open.
DO NOT use glycol-based antifreeze solutions. Glycol solutions are not • chemically compatible with the CPVC material and can cause damage to the Victaulic FireLock CPVC Sprinkler System.
Failure to follow this instruction can result in serious personal injury, property damage, and product damage.
Consult the local authority having jurisdiction before using glycerin solutions in fire sprinkler applications. Since very cold weather will make Victaulic FireLock CPVC
Sprinkler System Products more susceptible to damage, extra care should be taken to avoid rough handling or impact to these products.
The following information can be used to determine the quantity of an antifreeze solution needed to protect the piping system.
Pipe Size
Gallons of Water/Foot
Nominal
Diameter
inches/mm
Actual Outside
Diameter
inches/mm
¾ 1.050
.0311
20 26.9
1 1.315
.0494
25 33.7
1 ¼ 1.660
.0792
32 42.4
1 ½ 1.900
.1042
40 48.3
2 2.375
.1636
50 60.3
* Note: The gallons per foot column can be used for calculations when adding GLYCERIN to the piping system for freeze protection. All fire protection systems winterized with glycerin solutions must conform to local, state, and NFPA requirements. Glycerin based solutions are the only antifreeze solutions recommended for use. Glycol solutions are not chemically compatible with the CPVC material, and their use may result in damage to the Victaulic FireLock CPVC Sprinkler System.
I-800_19
FIRELOCK CPVC SPRINKLER SYSTEM PRODUCTS REV_J
Underground Fire Service:
Victaulic FireLock CPVC Sprinkler System Products are UL Listed for use in underground water service when installation is in accordance with:
ASTM-D2774, “Standard Recommended Practice for Underground Installation of • Thermoplastic Pressure Piping”
ASTM-F645, “Standard Guide for Selection, Design and Installation of Thermoplastic • Water Pressure Piping Systems”
NFPA 24, “Standard for the Installation of Private Fire Service Mains and Their • Appurtenances”
The installation procedures detailed in this manual apply to Victaulic FireLock CPVC Sprinkler System Products with solvent cemented joints in sizes
¾ inch through 2 inches.
Factory Mutual:
Victaulic FireLock CPVC Sprinkler System Products are FM Approved for use only in wet pipe systems, as defined in:
Light Hazard occupancies, as defined in NFPA 13, “Standard for the Installation of • Sprinkler Systems”
Residential occupancies, as defined in NFPA 13R, “Standard for the Installation of • Sprinkler Systems in Residential Occupancies Up to and Including Four Stories in Height”
Residential occupancies, as defined in NFPA 13D, “Standard for the Installation of • Sprinkler Systems in One and Two-Family Dwellings and Manufactured Homes”
Underground fire service systems, as defined in NFPA 24, “Standard for the • Installation of Private Fire Service Mains and Their Appurtenances”
Concealed Installations
Minimum protection shall be a permanently installed, non-combustible barrier • that cannot be removed without substantial cosmetic damage. Drop-in ceiling tiles used in suspended ceilings are not to be considered permanently installed for the purposes of this definition.
Victaulic FireLock CPVC Sprinkler System Products are FM Approved for use with • Fire Resistant Barriers for CPVC Pipe and Fittings in Light Hazard Occupancies under FM Approval of the Soffi-Steel™ System manufactured by Grice Engineering, Inc. Installation is to be made in accordance with the FM Approval requirements for the Soffi-Steel™ System.
Exposed Installations
Victaulic FireLock CPVC Sprinkler System Products are FM Approved for exposed • environments in Light Hazard Occupancies.
Where piping is installed above drop-in ceiling tiles, it shall be considered exposed.•
Piping may be installed under combustible or non-permanently installed smooth, • flat, horizontal ceilings.
Piping shall be installed according to the information in this manual, and the • sprinklers shall be FM Approved.
NSF® International:
Victaulic FireLock CPVC Sprinkler System Products are approved by NSF International for potable water applications. These products meet all applicable performance standards for a pressure rated application, as required in ANSI/NSF Standard 14, and they comply with ANSI/NSF Standard 61 for health effects. Victaulic FireLock CPVC Sprinkler System Products carry the NSF-pw end-use marking. Victaulic FireLock CPVC pipe and fittings conform to ASTM-F438 and ASTM-F442 requirements. In addition, Victaulic Style #899 FireLock CPVC One-Step Solvent Cement meets ASTM-F493 and NSF International requirements.
Loading...
+ 47 hidden pages