FireLock® Residential Zone Control Riser Module Assembly
SERIES 247
WARNING
• Read and understand all instructions before attempting to install any Victaulic products.
• Depressurize and drain the piping system before attempting to install, remove, adjust, or maintain
any Victaulic products.
• Wear safety glasses, hardhat, and foot protection when working with Victaulic piping products.
Failure to follow these instructions could result in serious personal injury and/or property damage.
I-247INSTALLATION INSTRUCTIONS
Waterow
Detector
Module Body
From Water
Supply
To Building Drain
Test/Drain Valve
1 - 2-inch/33.7 - 60.3-mm Sizes
INSTALLATION OF THE SERIES 247
The Series 247 FireLock Residential Zone Control Riser Module
includes the module body, a UL or ULC Listed and FM Approved
waterflow detector, a pressure gauge with shutoff valve (provision for
draining), and an alarm test module available with different orifice sizes
(K-factors). In addition, an optional pressure relief valve kit is available.
Refer to the “Installation of the Optional Pressure Relief Valve Kit”
section.
NOTE CONCERNING WATERFLOW DETECTOR INSTALLATION AND
MAINTENANCE INSTRUCTIONS VERSUS RISER MANIFOLDS, AS
STATED FROM THE WATERFLOW DETECTOR MANUFACTURER: “The
section ‘Installation Guidelines’ suggests mounting the detector at least
6 inches/152 mm from a fitting that changes the direction of water flow
and no less than 24 inches/610 mm from a valve or drain. This is a
general statement that is superseded when a riser manifold assembly
is listed or approved by agencies such as UL and/or FM. The agency
approval takes precedence because this configuration has been tested
and its operation validated.”
NOTICE
Pressure Gauge
Shuto Valve
Pressure
Gauge
To Sprinkler
Distribution
Shuto Valve
1. Install the Series 247 into the system using Victaulic couplings for
grooved-end pipe. Always refer to the instructions, supplied with
the coupling, for complete installation requirements.
2. For the NPT threaded drain outlet, follow standard piping practices
to make the threaded connection. NOTE: The nominal drain size is
1 inch/25 mm. The drawings, shown on page 2, provide examples
of alternative ways to make the threaded drain connection with
a street elbow to avoid interference with couplings on the water
supply side and sprinkler distribution side of the module body.
3. Apply thread sealant to the threads of the pressure gauge. Install
the pressure gauge into the module body, as shown in the drawing
above. Make sure the face of the gauge is visible.
4. Connect the water-flow detector to the alarm system in accordance
with the instructions supplied.
5. To install the optional pressure relief valve, follow the instructions
in the “Installation of the Optional Pressure Relief Valve Kit”
section.
6. Perform the system flow test, as outlined in the “System Flow
Test” section.
• The Series 247 can be installed in either the horizontal
(left-to-right or right-to-left flow) or vertical (up) position.
The flow direction arrow MUST point toward the
sprinkler distribution, as shown in the drawing above.
www.victaulic.com
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2012 VICTAULIC COMPANY. ALL RIGHTS RESERVED. PRINTED IN THE USA.
REV_C
I-2 47_1

INSTALLATION INSTRUCTIONS
I-247
FireLock® Residential Zone Control Riser Module Assembly
SERIES 247
EXAMPLES OF ALTERNATIVE WAYS TO MAKE THE THREADED DRAIN CONNECTION
The following drawings provide examples of alternative ways to make the threaded drain connection to avoid interference with couplings on the water
supply side and sprinkler distribution side of the module body. NOTE: These graphics show the Series 247 installed with the optional pressure relief
valve kit.
When installing a street elbow directly into the drain, the street elbow must be threaded into the drain
before the Series 247 is installed into the system with grooved pipe and grooved pipe couplings.
If the Series 247 was installed in the system before the connection to the drain was made,
install a close nipple and a straight coupling before installing the street elbow.
SYSTEM FLOW TEST
WARNING
• DO NOT operate the “Test/Drain Valve” under pressure.
Make sure the “Shutoff Valve” is in the “Closed”
position before operating the “Test/Drain Valve.”
Failure to follow these instructions could result in serious
personal injury and property damage.
Notify the authority having jurisdiction, remote station alarm monitors,
and anyone in the affected area that the system flow test is being
conducted.
1. Before performing the system flow test, confirm that all valves are
in their normal operating positions (“Shutoff Valve” in “Closed”
position, “Test/Drain Valve” in “Drain” position, and pressure
gauge shutoff valve in “Open” position).
2. Turn the thumb screw on the handle of the “Test/Drain Valve”
counterclockwise. Place the handle of the “Test/Drain Valve” in the
“Test” position.
3. Place the “Shutoff Valve” in the “Open” position.
4. Verify that the water-flow detector is operating properly and that
the alarms have sounded.
5. When the system flow test is complete, place the “Shutoff” valve in
the “Closed” position.
6. Place the “Test/Drain Valve” back to the “Drain” position. Handtighten the thumb screw on the handle.
www.victaulic.com
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2012 VICTAULIC COMPANY. ALL RIGHTS RESERVED. PRINTED IN THE USA.
I-2 47_ 2
REV_C