REMOVING THE SYSTEM FROM SERVICE
1. Notif y the authority having jurisdiction, remote station alarm
monitors, and those in the affected area that the system is being
taken out of service.
2. Close the water supply main control valve to take the system out of
service.
3. Open the system main drain valve, and allow the system to drain
completely. NOTE: It may be necessary to open the remote system
test valve (inspector’s test connection) and any auxiliary drains in
order to drain the system completely.
INSTALLATION OF THE AUXILIARY WATER MOTOR ALARM
TEST VALVE KIT
WARNING
• Make sure the valve is depressurized and
drained before attempting to remove any
trim from the valve.
Failure to follow this instruction could result
in serious personal injury and/or property
damage.
1. Make sure the valve is completely depressurized and drained.
2. Remove the trim at the locations designated in the exploded view
drawing on page 1.
3. Apply a small amount of pipe joint compound or Teflon* tape to
the external threads of all threaded pipe connections contained in
the kit. DO NOT get any tape, compound, or other foreign material
into the pipe connections.
4. Install the kit components, as shown in the exploded view drawing
on page 1.
5. Place the system back in service by following the “Placing
the System in Service” section of the I-751.VDS Installation,
Maintenance, and Testing Manual.
6. Check the connections for any leaks. If any leaks are present,
depressurize and drain the system and repair any leaks.
* Teflon is a registered trademark of the DuPont Company
I-751.VDS/KIT_2
Series 751 FireLock European Alarm Check Valve Stations
AUXILIARY WATER MOTOR ALARM TEST VALVE KIT
I-751.VDS/KIT
KIT INSTALLATION INSTRUCTIONS
www.victaulic.com
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2009 VICTAULIC COMPANY. ALL RIGHTS RESERVED. PRINTED IN THE USA.
REV_A