Victaulic 751 Series Installation Instructions Manual

WARNING
• Read and understand all instructions before attempting to install any Victaulic piping products.
• Depressurize and drain the piping system before attempting to install, remove, adjust, or perform maintenance on any Victaulic products.
• Wear safety glasses, hardhat, and foot protection when working with Victaulic piping products.
• Any activities that require taking the valve out of service may eliminate the fire protection provided by the system. Before removing the valve from service, notify the authority having jurisdiction. Consideration of a fire patrol should be given for the affected areas.
Failure to follow these instructions could result in serious personal injury and/or property damage.
4
TO SYSTEM
WATER
SUPPLY
TO WATER
MOTOR ALARM
TO
DRAIN
NORMALLY
CLOSED
(LOCKABLE)
3
4
4
3
1
2
Bill of Materials 1 Auxiliary Water Motor Alarm Test Ball Valve
(Normally Closed - Lockable) 2 Flexible Stainless Steel Braided Hose 3 Female Tee 4 Close Nipple
I-751.VDS/KIT_1
Series 751 FireLock European Alarm Check Valve Stations
AUXILIARY WATER MOTOR ALARM TEST VALVE KIT
I-751.VDS/KITKIT INSTALLATION INSTRUCTIONS
www.victaulic.com
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2009 VICTAULIC COMPANY. ALL RIGHTS RESERVED. PRINTED IN THE USA.
REV_A
REMOVING THE SYSTEM FROM SERVICE
1. Notif y the authority having jurisdiction, remote station alarm monitors, and those in the affected area that the system is being taken out of service.
2. Close the water supply main control valve to take the system out of service.
3. Open the system main drain valve, and allow the system to drain completely. NOTE: It may be necessary to open the remote system test valve (inspector’s test connection) and any auxiliary drains in order to drain the system completely.
INSTALLATION OF THE AUXILIARY WATER MOTOR ALARM TEST VALVE KIT
WARNING
• Make sure the valve is depressurized and drained before attempting to remove any trim from the valve.
Failure to follow this instruction could result in serious personal injury and/or property damage.
1. Make sure the valve is completely depressurized and drained.
2. Remove the trim at the locations designated in the exploded view drawing on page 1.
3. Apply a small amount of pipe joint compound or Teflon* tape to the external threads of all threaded pipe connections contained in the kit. DO NOT get any tape, compound, or other foreign material into the pipe connections.
4. Install the kit components, as shown in the exploded view drawing on page 1.
5. Place the system back in service by following the “Placing the System in Service” section of the I-751.VDS Installation, Maintenance, and Testing Manual.
6. Check the connections for any leaks. If any leaks are present, depressurize and drain the system and repair any leaks.
* Teflon is a registered trademark of the DuPont Company
I-751.VDS/KIT_2
Series 751 FireLock European Alarm Check Valve Stations
AUXILIARY WATER MOTOR ALARM TEST VALVE KIT
I-751.VDS/KIT
KIT INSTALLATION INSTRUCTIONS
www.victaulic.com
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2009 VICTAULIC COMPANY. ALL RIGHTS RESERVED. PRINTED IN THE USA.
REV_A
Loading...
+ 2 hidden pages