VICOR VI-RC6WXX-XXXX, VI-RC6VXX-XXXX, VI-RC6TXX-XXXX, VI-RC6RXX-XXXX, VI-RC6PXX-XXXX Datasheet

...
Total Power Part No. Dimensions
Single Outputs: 50-200W VI-LC
8.6" x 2.5" x 0.99" (218,4 x 63,5 x 25,2mm)
100-400W VI-MC
8.6" x 4.9" x 0.99" (218,4 x 124,5 x 25,2mm)
300-600W VI-NC
8.6" x 7.3" x 0.99" (218,4 x 185,4 x 25,2mm)
8.6" x 4.9" x 0.99" (218,4 x 124,5 x 25,2mm)
150-600W VI-QC
8.6" x 7.3" x 0.99" (218,4 x 185,4 x 25,2mm)
Triple Outputs: 150-600W VI-RC
8.6" x 7.3" x 0.99" (218,4 x 185,4 x 25,2mm)
Product Highlights
ComPAC delivers up to 600W from one, two, or three outputs in a package just 0.99” (25,2mm) in height with the field proven performance, high efficiency and high reliability inherent in Vicor ’s component level power converters. ComPAC meets British Telecom and European norms for input surge withstand and meets conducted emissions of EN55022 Class B. ComPAC is offered with input voltage ranges optimized for industrial and telecommunication applications and provides extended input overvoltage capability, input reverse polarity protection, undervoltage lockout, and master disable.
Features
Inputs 24, 48, and 300VdcAny output: 1 to 95VdcInput surge withstand:
British Telecom BTR 2511, EN-61000-4-5
Meets British Telecom BTR 2511,
EN55022 Class B conducted emissions
UL, CSA, TÜV (IEC 950)
CE marked80-90% efficiencyUp to 10W/cubic inchReverse polarity protectedMaster disableOvervoltage shutdown
DC-DC Switchers 50 to 600W 1-3 Outputs
Input Voltage
Nominal Range
1 = 24V 21 - 32V (1) W = 24V 18 - 36V (1) 3 = 48V 42 - 60V (2) N = 48V 36 - 76V (2) 6 = 300V 200 - 400V (2)
Output Voltage
Z 2V M 10V K 40V Y 3.3V 1 12V 4 48V 0 5V P 13.8V H 52V X 5.2V 2 15V F 72V W 5.5V N 18.5V D 85V V 5.8V 3 24V B 95V T 6.5V L 28V R 7.5V J 36V
Output Power/Current
V
out
5V V
out
< 5V W = 100W 20A V = 150W 30A U = 200W 40A S = 300W 60A Q = 400W 80A
Output Power/Current
V
out
5V V
out
< 5V S = 300W 60A P = 450W 90A M = 600W 120A
Product Grade
E = -10°C to +85°C C = -25°C to +85°C I = -40°C to +85°C M = -55°C to +85°C
Output Power/Current
V
out
5V V
out
< 5V Y = 50W 10A X = 75W 15A W = 100W 20A V = 150W 30A U = 200W 40A
ComPAC Configuration Chart
Use the configuration chart at the right to define your Vicor part number(s).
ComPAC
Max 5V <5V output for Outputs Outputs
(1) 150W 30A (2) 200W 40A
Conduction Cooled Models Available
Add "-CC" to the end of the part number.
(Consult factory for details.)
Long Term Safe Operating Area Curves (1% duty cycle max. Z
s
=0.5Ω; for short duration transient capability refer to page 3.)
0.1 1 10ms 100 1000
800V
Normal Operating Area
I.S.W.
Full Load
300V Input
S.D.
R.E.
500V 400V
200V
500ms
276V
Normal Operating Area
I.S.W.
Full Load
0.1 1 10ms 100 1000
48V Wide Range Input
R.E.
76V
125V
36V
S.D.
S.D.
100V
500ms
0.1 1 10ms 100 1000
100V
Normal Operating Area
I.S.W.
Full Load
100V
Standard Wide Range
24V Inputs
R.E.
32V
21V
36V
18V
S.D.
160V
0.1 1 10ms 100 1000
Normal Operating Area
I.S.W.
Full Load
48V Input
R.E.
S.D.
60V
100V
42V
I.S.W.: Input surge withstand, no degradation of performance. R.E.: Ratings Exceeded S.D.: Shutdown
ComPAC 10/02 1 of 4
ComPAC Specifications
(Typical at 25°C, nominal line and 75% load, unless otherwise specified)
E-GRADE C-, I-, M-GRADE
PARAMETER MIN TYP MAX MIN TYP MAX BROWNOUT* TRANSIENT** UNITS NOTES
Input Characteristics
24V 21 24 32 21 24 32 18 36 Vdc See Fusing Information below 24V Wide 18 24 36 18 24 36 n/a n/a Vdc See Fusing Information below 48V 42 48 60 42 48 60 36 72 Vdc See Fusing Information below 48V Wide 36 48 76 36 48 76 n/a n/a Vdc See Fusing Information below 300V 200 300 400 200 300 400 170 425 Vdc See Fusing Information below No load power dissipation
3
1.35 2 1.35 2 Watts
Master disable input current
3
4 4 mA Sink or source into disable (Absolute max., 20 mA) optocoupler Quiescent Input current
logic disable
3
7 10 7 10 mA Current drawn from source
when disabled
Reverse polarity protection No damage to unit with
external fuse
Output Characteristics (applies to each output individually)
Setpoint accuracy 1% 2% 0.5% 1% V
NOM
Load/line regulation 0.5% 0.05% 0.2% V
NOM
LL to HL, 10% to full load
Load/line regulation 1% 0.2% 0.5% V
NOM
LL to HL, no load to full load Output temperature drift 0.02 0.01 0.02 %/°C Over rated temperature Long term drift 0.02 0.02 %/1k hours Output ripple
2V, 3.3V 150mV 60mV 100mV Vp-p 20 MHz bandwidth 5V 5% 2% 3% Vp-p 20 MHz bandwidth 10-48V 3% 0.75% 1.5% Vp-p 20 MHz bandwidth
Output voltage trimming
1
50% 110% 50% 110%
Total remote sense
compensation
1
0.5 0.5 Volts 0.25V max. neg. leg
OVP set point 125% 115% 125% 135%
V
NOM
Recycle power Current limit 105% 135% 105% 125%
I
NOM
Automatic restart Short circuit current
2
20% 140% 20% 130%
I
NOM
Thermal Characteristics
Efficiency 78-88% 80-90% @5V and higher Shutdown temp. — case 90 95 105 90 95 105 °C Cool and recycle power to restart Operating temp. case 85 85 °C See Thermal Curves
Isolation Characteristics
Isolation
Input to output 4,242 4,242
Vdc
Output to case 707 707
Vdc
Input to case 2,121 2,121
Vdc
Mechanical Specifications
Weight
3
19.2 (544) 19.2 (544) Ounces (Grams)
Fusing Information Input voltage 24V 48V 300V
LC series (200W) 10A 7A 2A MC, PC series (400W) 20A 15A 4A NC, QC, RC series (600W) 35A 25A 6A
Safety Agency Approvals
UL, CSA, TÜV, VDE, IEC950, CE Marked
Environmental Characteristics/Product Grade Designators (Temperatures apply to product case.)
E-Grade C-Grade I-Grade M-Grade
Storage temperature -20°C to +100°C -40°C to +100°C -55°C to +100°C -65°C to +100°C Operating temperature -10°C to +85°C -25°C to +85°C -40°C to +85°C -55°C to +85°C
EMI/EMC Characteristics (Performed on selected samples representative of the ComPac product family.)
Input surge withstand (Up to 200 mS, Z
s
= .5, no interruption of performance, see: Long Term Safe Operating Area Curves, pg.2)
IEC 61000-4-5 level 2
Conducted Emissions British Telecom BTR 2511, Issue 2
EN 55022, class B
ESD IEC 61000-4-2 level 4
*Brownout 75% of rated load. **Transient voltage for one second.
1
10V, 12V and 15V outputs, trim range ± 10%. Consult factory for wider trim range.
2
Output voltages of 5V or less incorporate foldback current limiting, outputs greater than 5V incorporate straight line current limiting.
3
For MC, PC series, multiply by 2;for NC, QC, RC series, multiply by 3.
ComPAC 10/02 2 of 4
Loading...
+ 2 hidden pages