VICOR V375A2C160A Technical data

Vicor Corp. Tel: 800-735-6200, 978-470-2900 Fax: 978-475-6715 V375A2C160A DC-DC Converter Rev. 5.2 Page 1 of 8
Set your site on VICOR at www.vicorpower.com
Shown actual size:
4.6 x 2.2 x 0.5 in
117 x 56 x 12,7 mm
45
Absolute Maximum Ratings
Parameter Min Typ Max Unit
Thermal Resistance and Capacity
375Vin / 2V out / 160Watts
DC-DC Converter Module
Model Number V375A2C160A
*
See part numbering chart on this page for other product grades.
V375 A 5 C 400 A
Input Voltage
24=24Vin
48=48Vin 300=300Vin 375=375Vin
A = Maxi
B = Mini
C = Micro
Output
Voltage
Product Grade Temperatures (°C)
Grade Storage Operating
C =
-
40 to +125-20 to +100
T = -40 to +125-40 to +100
H =
-
55 to +125-40 to +100
M = -65 to +125-55 to +100
Pin
Style
Base-
plate
Output
Power
Features
DC input range: 250 - 425V
Input surge withstand: 500Vfor 100ms
DC output: 2V
Programmable output: 10 to 110%
Regulation: ±0.2% no load to full load
Efficiency: 74.5%
Maximum operating temperature:
100°C at full load
Power density: 32W/cubic inch
Height above board: 0.43 in. (10,9 mm)
Parallelable, with N+M fault tolerance
Low noise ZCS/ZVS architecture
Typical Applications: distributed power; off-line systems using power PFC front-ends; electric vehicles
Product Overview
This DC-DC converter module uses 2nd Generation power processing, control and packaging technologies to provide the performance, flexibility and cost effectiveness expected of a mature power component. For example, a plated-cavity core transformer couples widely separated primary and secondary windings, resulting in low in-to­out parasitic capacitance and noise. High frequency ZCS/ZVS switching, advanced power semiconductor packaging and thermal management provide high power density with low temperature gradients. Extensive use of silicon integration results in 1/3 the part count of a 1st Generation converter.
*
Part Numbering
For pin styles see page 6. Slotted baseplate (style 1) requires no designator. For threaded baseplate add a “2” to the end of the part number. For thru-hole, add a “3”.
See page 7 for dimensions.
Parameter Rating Unit Notes
+In to –In voltage -0.5 to +425.0 Vdc +In to –In voltage 500 Vdc <100ms PC to –In voltage -0.5 to +7.0 Vdc PR to –In voltage -0.5 to +7.0 Vdc +Out to –Out voltage -0.5 to +3.1 Vdc +Sense to –Out voltage -0.5 to +3.1 Vdc –Sense to –Out voltage 1.0 Vdc SC to –Out voltage -0.5 to +1.5 Vdc Isolation voltage (in to out) 3000 Vrms Isolation voltage (in to base) 1550 Vrms Isolation voltage (out to base) 500 Vrms Storage temperature (C–Grade) -40 to +125 °C Operating temperature (C–Grade) -20 to +100 °C Baseplate Pin soldering temperature 500 (260) °F (°C) <5 sec; wav e solder Pin soldering temperature 750 (390) °F (°C) <7 sec; hand solder Mounting torque 5 (0.57) in-lbs (N-m) 6 each, # 4-40 or M3
查询V375A2C160A供应商查询V375A2C160A供应商
Vicor Corp. Tel: 800-735-6200, 978-470-2900 Fax: 978-475-6715 V375A2C160A DC-DC Converter Rev. 5.2 Page 2 of 8
Set your site on VICOR at www.vicorpower.com
Parameter Min Typ Max Unit Notes
Operating input voltage 250 375 425 Vdc Input surge withstand 500 Vdc <100ms Output voltage setpoint 1.98 2.00 2.02 Vdc Nominal input; full load; 25°C Output OVP setpoint 2.7 2.8 2.9 Vdc 25°C;recycle input voltage to restart ( 1 minute off ) Output power 160 Watts At 100°C baseplate temperature Efficiency 73.5 74.5 % Nominal input; 75% of full load;25°C
Parameter Min Typ Max Unit Notes
Line regulation ±0.02 ±0.20 % Low line to high line; full load Load regulation ±0.06 ±0.20 % No load to full load; nominal input Temperature regulation ±0.002 ±0.005 % / °C Over operating temperature range Ripple and noise, p-p 70 88 mV Nominal input, full load; 25°C;20MHz bandwidth Current limit 81.6 92.0 104.0 Amps Output voltage 95% of nominal Short circuit current 56 92 104 Amps Output voltage <250mV Power sharing accuracy ±2 ±5 % 10 to 100% of full load
Programming range 10 110 %
Of nominal output voltage.For trimming below 90% of nominal, a minimum load of 10% of maximum rated power may be required.
Parameter Min Typ Max Unit Notes
Undervoltage turn-on 242.5 247.5 Vdc Undervoltage turn-off 204.7 212.2 Vdc Overvoltage turn-off/on 429.2 446.3 467.6 Vdc Dissipation, standby 5.0 7.5 Watts No load
MODULE OPERATING SPECIFICATIONS
MODULE INPUT SPECIFICATIONS
MODULE OUTPUT SPECIFICATIONS
ELECTRICAL CHARACTERISTICS
Electrical characteristics apply over the full operating range of input voltage, output load (resistive) and baseplate temperature, unless otherwise specified. All temperatures refer to the operating temperature at the center of the baseplate.
Baseplate Slotted (Style 1)
Slotted baseplate (style 1) requires no designator. For threaded baseplate add a "2" to the end of the
part number. For thru-hole add a "3".
Pin style Short (Style 1)
For long pin configuration add “L”to the end of the part number.See page 7 for pin dimensions.
MODULE MECHANICAL SPECIFICATIONS
Note: For important information relative to applications where the converter modules are subject to continuous dynamic loading,
contact Vicor applications engineering at 800-927-9474.
Vicor Corp. Tel: 800-735-6200, 978-470-2900 Fax: 978-475-6715 V375A2C160A DC-DC Converter Rev. 5.2 Page 3 of 8
Set your site on VICOR at www.vicorpower.com
Parameter Min Typ Max Unit Notes
PRIMARY SIDE
(PC = Primary Control; PR = Parallel)
PC bias voltage 5.50 5.75 6.10 Vdc PC current = 1.0 mA
current limit 1.5 2.1 3.0 mA PC voltage = 5.5V PC module disable 2.3 2.6 2.9 Vdc Must be able to sink 4 mA.See Fig.1 PC module enable delay 4 7 ms PC module alarm 0.5 Vavg UV, OV, OT, module fault.See Figs.2 and 4 PR emitter amplitude 5.7 5.9 6.1 Volts PR load >30 ohms, < 30 pF PR emitter current 150 mA PR receiver impedance 375 500 625 ohms 25°C PR receiver threshold 2.4 2.5 2.6 Volts Minimum pulse width: 20ns PR drive capability 12 modules Without PR buffer amplifier
SECONDARY SIDE
(SC = Secondary Control)
SC bandgap voltage 1.21 1.23 1.25 Vdc Referenced to –Sense SC resistance 990 1000 1010 ohms SC capacitance 0.033 µF SC module alarm 0 Vdc With open trim;referenced to –Sense. See Fig.6
Parameter Min Typ Max Unit Notes
Remote sense (total drop) 0.5 Vdc 0.25V per leg (senses must be closed) Isolation voltage (in to out) 3000 Vrms Complies with reinforced insulation requirements Isolation voltage (in to base) 1550 Vrms Complies with basic insulation requirements Isolation voltage (out to base) 500 Vrms Complies with operational insulation requirements
Isolation resistance (in to out) 10 megohms Weight 7.3 (210) 8 (227) ounces (grams) Temperature limiting 100 115 °C See Figs. 2 and 4
Agency approvals UL, CSA, TÜV, BABT, CE, VDE
UL1950, CSA950, EN60950, VDE0805, BS7002, IEC 60950.With a fuse in series with the +Input
MODULE CONTROL SPECIFICATIONS
MODULE GENERAL SPECIFICATIONS
ELECTRICAL CHARACTERISTICS, continued
Loading...
+ 5 hidden pages