Viconics VT7300F Installation Guide

CONTENTS
Installation 2
Location 2 Installation 2 Features overview 3
Configurable BI/UI inputs overview 4 Model Selection 6 Terminal, Identification and Function 6
Wiring 7 Screw terminal arrangement 8 Main outputs wiring 8 Remote sensor accessories 9
Configuring and Status Display Instructions 11
Status display 11
User Interface 12
Local keypad interface 13 Dual occupied setpoints adjustment 13 Single occupied setpoints adjustment 14 Unoccupied and stand-by setpoints adjustments 14 Mode button menu sequence 14 Sequence of operations 14
Installer Configuration Parameter Menu 15 Specifications 25 Drawing & Dimensions 26
1 | PIR Ready VT7300-2572 Series
INSTALLATION
Remove the security screw on the bottom of
Terminal Equipment Controller cover.
Open unit by pulling on the bottom
side of Terminal Equipment Controller (fig. 1).
Remove wiring terminals from sticker. Please read the FCC ID and IC label
installed in the cover upon removal of cover for the wireless products.
Location
1. Should not be installed on an outside wall.
2. Must be installed away from any direct heat source.
3. Should not be installed near an air discharge grill.
4. Should not be affected by direct sun radiation.
5. Nothing should restrict vertical air circulation to the Terminal Equipment Controller.
Installation
1. Swing open the Terminal Equipment Controller PCB to the left by pressing the PCB locking tabs (fig. 2).
2. Pull out cables 6” out from the wall.
3. Wall surface must be flat and clean.
4. Insert cable in the central hole of the base.
5. Align the base and mark the location of the two mounting holes on the wall. Install base in proper orientation. Arrow on base should be facing up.
6. Install anchors in the wall.
7. Insert screws in mounting holes on each side of the base (fig. 2).
8. Gently swing back the circuit board on the base and push on it until the tabs lock it.
9. Strip each wire 1/4 inch from end.
2 | PIR Ready VT7300-2572 Series
10. Insert each wire according to wiring diagram.
When replacing an existing Terminal Equipment Controller, label the
wires before removal of the Terminal Equipment Controller.
Electronic controls are static sensitive devices. Discharge yourself
properly before manipulating and installing the Terminal Equipment Controller.
A short circuit or wrong wiring may permanently damage the Terminal
Equipment Controller or the equipment.
All VT7000 series Terminal Equipment Controllers are designed for use
as operating controls only and are not safety devices. These instruments have undergone rigorous tests and verification prior to shipping to ensure proper and reliable operation in the field. Whenever a control failure could lead to personal injury and or loss of property, it becomes the responsibility of the user / installer / electrical system designer to incorporate safety devices (such as relays, flow switch, thermal protections, etc…) and or an alarm system to protect the entire system against such catastrophic failures. Tampering with the devices or unintended application of the devices will result in a void of warranty.
11. Gently push excess wiring back into hole (fig. 3).
12. Re-Install wiring terminals in their correct locations (fig. 3).
13. Re-install the cover (top side first) and gently push extra wire length back into the hole in the wall.
14. Install security screw.
Features overview
System modes lock out.  System efficiency feedback.
Lockable keypads for tamper proofing. No need for Terminal Equipment Controller guards.  PIR- ready.  Advanced occupancy functions.  Configurable fan functions.  Auto fan speed mode.  Auxiliary output.  Unique configuration setup utility.  Three configurable inputs.
.
3 | PIR Ready VT7300-2572 Series
CONFIGURABLE BI/UI INPUTS OVERVIEW
Binary input #1 can be configured for the following functions:
1. (None): No function will be associated with the input
2. (Rem NSB): remote NSB timer clock input. The scheduling will now be set as
per the binary input. It provides low cost setback operation via a dry contact Contact opened = Occupied Contact closed = Unoccupied
3. (Motion NO) and (Motion NC): Advanced PIR occupancy functions using a normally open (NO) or normally closed (NC) remote PIR motion sensor. Occupancy mode is now set as per applied PIR function and configuration. Application information and examples are available on document: APP-PIR- Guide-Exx. This document will provide the installers and system designers with detailed examples on applications, parameter configuration information, sequence of operation, troubleshooting and diagnostic help required for the proper usage of the PIR accessory covers
4. (Window) EMS: Forces the system to disable any current heating or cooling action by the Terminal Equipment Controller. The mode stays the same and the current setpoints are the same occupied setpoints. Only the outputs are disabled. There is a Door/Window alarm displayed on the Terminal Equipment Controller to indicate to the local tenant that the door/window needs to be closed for cooling or heating to resume. Use NC contact.
Contact opened = System disabled with local Window alarm Contact closed = System enabled
Binary input #2 can be configured for the following functions:
1. (None): No function will be associated with the input
2. (Door Dry) Door contact & Motion detector: This configuration is only functional if binary input #1 is set to Motion NO or Motion NC or a PIR accessory cover is used. With this sequence enabled, the occupancy is now dictated through those 2 inputs. Any motion detected will set the zone to occupied status. The zone will remain permanently in occupied mode until the door contact switch opens momentarily. The Terminal Equipment Controller will then go in stand-by mode. If more movements are detected, the occupied mode will resume. While the door is opened, any movements detected by the remote PIR sensor or the PIR accessory cover will be ignored. Use a Normally Closed contact switching device.
Contact opened = Door opened Contact closed = Door closed
3. (RemOVR): temporary occupancy remote override contact. This function disables the central button override function on the Terminal Equipment Controller. The override function is now controlled by a manual remote momentarily closed contact. When configured in this mode, the input operates in a toggle mode. It is now possible to toggle between unoccupied & occupied setpoints for the amount of time set by parameter (TOccTime) temporary occupancy time.
4. (Filter): a backlit flashing Filter alarm will be displayed on the Terminal Equipment Controller LCD screen when the input is energized. It can be tied to a differential pressure switch that monitor filters
Contact opened = No alarm
4 | PIR Ready VT7300-2572 Series
Contact closed = Alarm displayed
5. (Service): a backlit flashing Service alarm will be displayed on the Terminal Equipment Controller LCD screen when the input is energized. It can be tied in to the AC unit control card, which provides an alarm in case of malfunction.
Contact opened = No alarm Contact closed = Alarm displayed
Universal input #3 can be configured for the following functions:
1. (None): No function will be associated with the input
2. (COC/NH) Change over dry contact. Normally Heat: Used for hot / cold air / water change over switching in 2 pipe systems.
Contact closed = Cold air / water present Contact opened = Hot air / water present
Only used and valid if system is setup as 2.0. Parameter (Out1Conf) set as 2.0.
3. (COC/NC) Change over dry contact. Normally Cool: Used for hot / cold air / water change over switching in 2 pipe systems.
Contact closed = Hot air / water present Contact opened = Cold air / water present
Only used and valid if system is setup as 2.0. Parameter (Out1Conf) set as 2.0.
4. (COS) Change over analog sensor: Used for hot / cold air / water change over switching in 2 pipe systems.
Only used and valid if system is setup as 2.0. Parameter (Out1Conf) set as 2.0.
If temperature is > 77 °F = Hot air / water present If temperature is < 75 °F = Cold air / water present
5. (SS) Supply air sensor monitoring: Used for supply air temperature monitoring.
Only used for network reporting of the supply air temperature. Has no internal function in the Terminal Equipment Controller.
5 | PIR Ready VT7300-2572 Series
MODEL SELECTION
Part number
Description
Communication
Options
VT7300F5X00-2572
Commercial Applications with Override
Communication Ready
VT7300F5X00B-2572
Commercial Applications with Override
BACnet MS/TP
VT7305F5X00-2572
°C/°F Hotel/Lodging Applications
Communication Ready
VT7305F5X00B-2572
°C/°F Hotel/Lodging Applications
BACnet MS/TP
1- Not used Fan H
2- Not used Fan M
3- Fan Enable/disable
Fan L
4- 24 V~ Hot 24 V~ Hot
5- 24 V~ Com 24 V~ Com
6- Aux BO 5 BO 5-Aux
7- Aux BO 5 BO 5-Aux
8- Blank Blank
9- ECM Output AO 2
10-Valve Output AO 1
11- Not used Blank
12- BI #1 BI 1
13- RS
RS
14- Scom Scom
15- BI #2 BI 2
16- UI #3 COS / COC /SS
UI 3
- Controllers can be ordered with a factory installed PIR cover. Please use (5500) extension instead of the (5000) only extension. Ex. VT7300F5500B-2572.
- Controllers ordered without a PIR cover can be retrofitted with a separate PIR accessory cover afterwards when required
TERMINAL, IDENTIFICATION AND FUNCTION
6 | PIR Ready VT7300-2572 Series
16
15141312109
76
54
BO5
BO5
Ui3
Bi2
Scom
RS
Bi1
AO1
AO2
24V-Com
24V-Hot
321
Fan-L
Fan-M
Fan-H
24
Vac
0-10
Vdc
FAN
24
Vac
2-10
Vdc
On/
Off
Water Detector
(NO contact)
(Valve Open Position Detector) NO contact
Water
Supply
Sensor
24Vac
Transformer
Hot/Cold
Water Coil
Wiring
7 | PIR Ready VT7300-2572 Series
Screw terminal arrangement
AO2
AO1
BI1
RS
Scom
BI2
UI3
Fan H Fan M
Fan L
24V~Hot
BO5
BO5
5 pole left top connector
3 pole left top connector
8 pole bottom connector
24V-Com
Main outputs wiring
Wiring notes: Note 1: Electromechanical contacts are to be used with the digital inputs. Electronic triacs
cannot be used as mean of switching for the input. The switched leg to the input for the input to activate is terminal C (common).
Note 2: The transformer of the unit provides power to the t Terminal Equipment Controller
and the additional loads that will be wired to the Terminal Equipment Controller.
8 | PIR Ready VT7300-2572 Series
Loading...
+ 18 hidden pages