Viconics VT7300 Installation Guide

VT7300 Series
24 Vac Low Voltage Fan Coil Thermostats
Product overview
For Commercial and Lodging HVAC Applications
(Issue Date: August 10, 2007 – 028-0125 R6)
The VT7300 PI thermostat family is specifically designed for fan coil control. The product features a backlit LCD display with dedicated function menu buttons for simple operation. Accurate temperature control is achieved due to the product’s PI proportional control algorithm, which virtually eliminates temperature offset associated with traditional, differential-based thermostats.
Models are available for On/Off, 3 point floating and analog 0 to 10 Vdc control. All models contain can control three, two or single fan speed. 3 additional inputs are also
provided for various functions. All models feature configurable System and Fan button functions to meet all possible
applications. They all contain an SPST auxiliary switch that can be used to control lighting or auxiliary reheat.
The additional following documentation is available on www.viconics.com
Information on the LON models (VT73xxX1000E), is available on document ITG-VT7300-LON-Exx
Information on the BACnet models (VT73xxX1000B), is available on document ITG-VT7300-BAC-Exx
Models available
Viconics number
VT7300A1000
2 & 4
Application
RH sensor
Market Commercial / Institution Hotels / Lodging
Pipe
On/Off
No No Yes No No Yes No Yes No Yes
VT7300C1000
2 & 4 Pipe
Floating & On/Off
VT7350C1000
VT7305A1000
2 & 4
Pipe
On/Off
VT7305C1000
2 & 4 Pipe
Floating & On/Off
VT7355C1000
Commercial /
VT7300F1000
Institution
VT7350F1000
2 & 4 Pipe
Analog 0-10 Vdc
VT7305F1000
Hotels / Lodging
Features and benefits
Features Benefits
Models available with internal humidity sensing Increased occupant comfort through dehumidification
Advanced occupancy functions Through the network or smart local occupancy sensing
3 configurable inputs Adds functionality
Configurable sequences of operation Single model meets more applications
Configurable fan functions button Meets more applications with a single model
Unique configuration setup utility Minimizes parameter tampering
Multi level lockable keypad Tamper proof, no need for thermostat guards
Auto Fan speed mode Increased occupant comfort in cooling mode by reducing
humidity and offer less fan noise in all mode of operation
Available for 24 Vac On/Off, Floating or Analog control Meet advanced applications requirements
Auxiliary output Can be used for lighting or reheat
www.viconics.com
sales@viconics.com
VT7355F1000
Programmable BI/UI inputs overview
Binary input #1 can be configured for the following functions:
1. (None): No function will be associated with the input
2. (Rem NSB): remote NSB timer clock input. The
scheduling will now be set as per the binary input. It provides low cost setback operation via a dry contact
Contact opened = Occupied
Contact closed = Unoccupied
3. (Motion NO): remote NSB using a motion detector. The occupancy will now be set as per the binary input. Contact opened = Unoccupied. When the contact closes momentarily, the thermostat goes into occupied mode for the time specified by the ToccTime timer. The timer can reset at the end of its cycle if new movements are detected in the area.
4. (Motion NC): remote NSB using a motion detector. The occupancy will now be set as per the binary input. Contact closed = Unoccupied. When the contact opens momentarily, the thermostat goes into occupied mode for the time specified by the ToccTime timer. The timer can reset at the end of its cycle if new movements are detected in the area.
5. (Window) EMS: Forces the system to disable any current heating or cooling action by the thermostat. The mode stays the same and the current setpoints are the same Occupied setpoints. Only the outputs are disabled. There is a Door/Window alarm displayed on the thermostat to indicate to the local tenant that the door/window needs to be closed for cooling or heating to resume. Use NC contact.
Contact opened = System disabled with local
Window alarm
Contact closed = System enabled
Binary input #2 can be configured for the following functions:
1. (None): No function will be associated with the input
2. (Door Dry) Door contact & Motion detector:
This configuration is only functional if binary input #1 is set to Motion NO or Motion NC.
BI1 is connected to a motion detector & BI2 is connected to a door contact switch. With this sequence enabled, the occupancy is now dictated through those 2 inputs. Any motion detected will set the zone to occupied status. The zone will remain permanently in occupied mode until the door contact switch opens momentarily. The thermostat will then go in unoccupied mode. If more movements are detected, the occupied mode will resume. If the door stays open more than the time value specified by the doortime parameter, the zone will remain unoccupied. Use NC contact.
Contact opened = Door opened
Contact closed = Door closed
2
3. (RemOVR): temporary occupancy remote override contact. This function disables the central button override function on the thermostat. The override function is now controlled by a manual remote momentarily closed contact. When configured in this mode, the input operates in a toggle mode.
It is now possible to toggle between unoccupied & occupied setpoints for the amount of time set by parameter (TOccTime) temporary occupancy time.
4. (Filter): a backlit flashing Filter alarm will be displayed on the thermostat LCD screen when the input is energized. It can be tied to a differential pressure switch that monitor filters
Contact opened = No alarm
Contact closed = Alarm displayed
5. (Service): a backlit flashing Service alarm will be displayed on the thermostat LCD screen when the input is energized. It can be tied in to the AC unit control card, which provides an alarm in case of malfunction.
Contact opened = No alarm
Contact closed = Alarm displayed
Universal input #3 can be configured for the following functions:
1. (None): No function will be associated with the input
2. (COC/NH) Change over dry contact. Normally Heat: Used for hot / cold water change over switching in 2 pipe systems.
Contact closed = Cold water present
Contact opened = Hot water present
Only used and valid if system is setup as 2 pipes. Parameter ( Pipe No ) set as 2 pipes.
3. (COC/NC) Change over dry contact. Normally Cool: Used for hot / cold water or air change over switching in 2 pipe systems.
Contact closed = Hot water present
Contact opened = Cold water present
Only used and valid if system is setup as 2 pipes. Parameter ( Pipe No ) set as 2 pipes.
4. (COS) Change over analog sensor: Used for hot / cold water or air change over switching in 2 pipe systems. Only used and valid if system is setup as 2 pipes. Parameter ( Pipe No ) set as 2 pipes.
If water temperature is > 77 °F = Hot water present
If water temperature is < 75 °F = Cold water present
5. (SS) Supply air sensor monitoring: Used for supply air temperature monitoring. Only used for network reporting of the supply air temperature. Has no internal function in the thermostat.
.
Installation
Remove security screw on the bottom of thermostat cover.
Open up by pulling on the bottom side of thermostat.
Remove Assembly and remove wiring terminals from sticker. (Fig. 3)
A) Location: 1- Should not
be installed on an outside wall. 2- Must be installed away from any heat source. 3- Should not be installed near an air discharge grill. 4- Should not be affected by direct sun radiation. 5- Nothing must restrain vertical air circulation to the thermostat.
B) Installation: 1- Swing open the thermostat PCB to the left by pressing the PCB
locking tabs. (Fig. 4) 2- Pull out cables 6” out of the wall. 3- Wall surface must be flat and clean. 4- Insert cable in the central hole of the base. 5- Align the base and mark the location of the two mounting holes
on the wall. Install proper side of base up. 6- Install anchors in the wall. 7- Insert screws in mounting holes on each side of the base.
(Fig. 4) 8- Gently swing back the circuit board on the base and push on it
until the tabs lock it. 10- Strip each wire 1/4 inch. 11- Insert each wire according to wiring diagram. 13- Gently push back into hole excess wring (Fig. 5) 14- Re-Install wiring terminals in correct location. (Fig. 5) 15- Reinstall the cover (top side first) and gently push back extra
wire length into the hole in the wall. 16- Install security screw.
If replacing an old thermostat, label the wires before removal of the old thermostat.
Electronic controls are static sensitive devices. Discharge yourself properly before manipulation and installing the thermostat.
Short circuit or wrong wiring may permanently damage the thermostat or the equipment.
Anti-short cycling can be set to 0 minutes for equipment that posses their own anti cycling timer. Do not use that value unless the equipment is equipped with such internal timer. Failure to do so can damage the equipment.
All VT7000 series thermostats are to be used only as
operating controls. Whenever a control failure could lead to personal injury and/or loss of property, it becomes the responsibility of the user to add safety devices and/or alarm system to protect against such catastrophic failures.
Fig.3
Fig.5
3
Location of PCB retaining tabs
Fig.4
Re-install terminal blocks
Thermostat assembly
(VT7300F1000 shown)
Fig.6
Terminal identification
Vi con i cs num ber VT73xxA10x x VT73xxC10x x Vi con i cs num ber VT73xxF10xx Description / application 2 & 4 Pipe On/Off 2 & 4 Pipe Floating Description / application 2 & 4 Pipe Analog
2 & 4 Pip e On/ O ff
4
Internal temperature X X Internal temperature X Internal humidity
1- High Fan Speed 2- Medium Fan S pe ed 3- Low Fa n S pee d 4- 24 V~ Hot 5- 24 V~ Com
6- Aux BO 5 7- Aux BO 5 8- BO 3 Open Heat
9- BO 4 Close He at 10- BO 1 Ope n Coo l 11- BO 2 Close Cool 12- BI #1 13- RS 14- Scom 15- BI #2 16- UI #3 COS / COC / S S
Fan-H Fan-H Fan-M Fan-M Fan-L Fan-L
24 V~ Hot 24 V~ Hot
24 V~ Com 24 V~ Com
BO 5-Aux BO 5-Aux BO 5-Aux BO 5-Aux
BO 3 BO 3
BO 2 BO 2
BI 1 BI 1
RS RS
Scom Scom
BI 2 BI 2 UI 3 UI 3
Model dependent
BO 4
BO 1
Intern al humi d i ty
1- High Fan Spe ed 2- Medium Fan Spee d 3- Low Fan Spe e d 4- 24 V~ Hot 5- 24 V~ Com
6- Aux BO 5 7- Aux BO 5
9- AO 2 Heat 10- AO 1 Co o l Not use d Blank 12- BI #1 13- RS 14- Sco m 15- BI #2 16- UI #3 COS / COC /SS
Model dependent
Fan-H Fan-M Fan-L
24 V~ Hot
24 V~ Com
BO 5-Aux BO 5-Aux
AO 2 AO 1
Blank
BI 1
RS
Scom
BI 2 UI 3
Wiring
Power & Fan ( All models )
24 V~ transformer relay pack 3 speed 2 speed Single speed
Fan-H Fan-M Fan-L
High
Med
Low
High
Low
High
24 V~ Hot 24 V~ Com
Remote inputs ( All models )
BI 1 RS Scom
Remote wall sensor
- S3010W1000
- S3020W1000
BI 2 UI 3
Contact
- Door
- Remote Override
- Filter alarm
- service alarm
Contact
- Rem NSB
- Motion
- Window
SS ( supply sensor )
- S1010E1000
- S2000D1000
COS ( changeover sensor )
- S1010E1000
OR
COC/NH
- Normally heat
- Closed contact = cold water
COC/NC
- Normally cool
- Closed contact = heat water
Auxiliary output ( All models )
- Dry contact to end device 24 V~ maximum #4 24 V~ Hot
#5 24 V~ Com #6 #7
- 24 Vac power to relay #4 24 V~ Hot #5 24 V~ Com #6 #7
R
R
A
2
2
A
A
Main outputs wiring
VT7300A1000 & VT7305AC1000
24 V~ Hot 24 V~ Com
BO2
VT7300C1000, VT7305C1000, VT7350C1000 & VT7355C1000
24 V~ Hot 24 V~ Com
BO1 BO2
VT7300C1000, VT7305C1000, VT7350C1000 & VT7355C1000
24 V~ Hot 24 V~ Com
BO1 BO2
2 Pipe applications 4 Pipe applications
On-Off control
24 V~ Hot 24 V~ Com
24 Vac
N.C. Heating / Cooling valve
24 Vac
24 Vac Com
Com
BO3
BO2
24 Vac Com
Com
24 Vac
24 Vac Com
Com
24 V~ Hot 24 V~ Com BO3
if N.O.
OR
if N.C. if N.O. if N.C.
OR
OR
OR
if N.O. if N.C.
OR
Heating / Cooling valve
24 Vac Com
BO4 BO1 BO2
Floating control
24 V~ Hot 24 V~ Com BO3
Heating / Cooling valve
Open Com Close
BO4 BO1 BO2
Open Com Close
Open Com Close
N.O. Heating valve N.C. Cooling valve
24 Vac
24 Vac Com
Com
24 Vac
24 Vac Com
Com
Heating valve
Heating valve Cooling valve
Cooling valve
Heating valve
Cooling valve
5
Analog control
VT7300F1000, VT7305F1000, VT7350F1000 & VT7355F1000
24 V~ Hot 24 V~ Com
Heating / Cooling valve
Com 24 Vac
O 1
0-10 Vdc
4 V~ Hot 4 V~ Com
O 2 O 1
Com 24 Vac 0-10 Vdc
Com 24 Vac 0-10 Vdc
Heating valve Cooling valve
Typical applications
Schematic Wiring Settings
2 pipe system cooling and/or heating ( VT7300A1000, VT7300C1000 & VT7305C1000 ) On / Off N.C. actuator
Normally Closed On/Off
Valve Cooling and/or Heating
3 Speed fan
Room Temperature
Fan-H
Fan-M
Fan-L
UI3 COS
24 V~ Com
24 V~ Hot
BO2 N.C.
24 Vac f an relays
High
Med
Low
Control Thermostat
Mandatory
Pipe no = 2 pipes
CntrltTyp = On/Off
Fan Menu = 0 (L-M-H)
FL time = as per actuator
If cooling only set::
SeqOpera = 0 Cooling only If heating only set::
SeqOpera = 1 Heating only If heat / cool auto-changeover
with a local water temperature sensor set:
Optional supply water
temper at ure sensor
SeqOpera = 0 Cooling only
UI3 = COS
2 pipe system cooling and/or heating ( VT7300C1000 & VT7305C1000 ) Floating actuato r
Modulating Floating
Valve Cooling and/or Heating
3 Speed fan
Room Temperature Control Thermostat
Fan-H
Fan-M
Fan-L
UI3 COS
24 V~ Com
24 V~ Hot
BO1 Open
BO2 Close
24 Vac f an relays
High
Med
Low
Mandatory
Pipe no = 2 pipes
CntrltTyp = Floating
Fan Menu = 0 (L-M-H)
FL time = as per actuator
If cooling only set::
SeqOpera = 0 Cooling only If heating only set::
SeqOpera = 1 Heating only If heat / cool auto-changeover
with a local water temperature sensor set:
Optional supply water
temper at ure sensor
SeqOpera = 0 Cooling only
UI3 = COS
2 pipe system cooling and/or heating ( VT7300F1000 & VT7305F1000 ) Analog actuator
Modulating Analog
Valve Cooling and/or Heating
3 Speed fan
Room Temperature
Fan-H Fan-M
Fan-L
UI3 COS 0 V~ Com 24 V~ Hot
AO1
24 Vac f an relays
High
Med
Low
Control Thermostat
0 to 10
Vdc
Mandatory
Pipe no = 2 pipes
Fan Menu = 0 (L-M-H)
RA/DA = as per actuator
If cooling only set::
SeqOpera = 0 Cooling only If heating only set::
SeqOpera = 1 Heating only If heat / cool auto-changeover
with a local water temperature sensor set:
SeqOpera = 0 Cooling only
Optional supply water
temper at ure sensor
UI3 = COS
6
Loading...
+ 11 hidden pages