VICI ITC User Manual

Valco Instruments Co. Inc.
Instrumentation Temperature Controller Instruction Manual
P. O. Box 55603, Houston, TX 77255
(713) 688-9345
Sales toll-free (800) 367-8424
Fax (713) 688-8106
MAN-ITC
Rev. 8/96
Printed in USA
Table of Co ntents
1. GENERAL DE SCRIP TION. ...... .... .... ...... .... .... .... ...... .... .... ...... .... .... ...... .... .... ...1
1.1 Standard Features
1.11 Thermocouple Sensor
1.12 Proportional Heater Power Control
1.13 Power Attenuation
1.14 Zero Crossover Power Application
1.15 Digital Temperature Setting
1.16 Compact Rugged Construction and Functional Layout
1.2 Specific ations and Model Codes
1.3 Technical Description
1.31 Thermal System Overview
1.32 ITC Block Diagram by Function
1.321 Input Amplifier
1.322 Thumbwheel Switches and D/A Converter
1.323 Differential Comparator
1.324 Heater Power Switch
1.325 Thermocouple Break Detection
1.326 Proportional Power Control
1.327 Power Attenuation
1.33 Proportional Power Control
1.34 Power Attenuation
Pag e
2. OPERATION . .... .... .... .... .... .... .... .... .... .... .... .... .... .... .... .... .... .... .... .... .... .... .... .... .10
2.1 PHYSICAL LAYOUT OF THE ITC
2.2 Thermocouples
2.3 Setpoint (Set °C)
2.4 Propor tioning Bandwidth
2.41 Bandwidth Defined
2.5 Install ation
2.6 Troubleshooting and Schematic Di agram
2.61 Situation: PWR ON indicator fails to illuminate; instrument does nothing.
2.62 Situation: TCPL indicator ON continuously; no power applied to heater
2.63 Situation: No power being applied to heat er ; TCPL indicator OFF.
3. WARRANTY ............... .......... ........ ........ .......... ........ ........ .......... ........ ........ .....19
4. TECHNICAL DRAWINGS .................... .............. ................ .............. .............20
1. INTRODUCTION AND GENERAL DESCR IPTION
The Instrumentation Temperature Controller (ITC) is an isothermal temperature controller intended for broad spectrum usage in thermal systems common to modern analytical instrumentation. The instrument is designed to be a flexible building block with which the user can config ure a ther mal system to suit p art icular requi rements. Althoug h the contr oller is only a si ngle elemen t in such a sys tem, its flexibility and performance ultimately determine the stability, reproducibility, and accuracy of the enti re syst em.
Inasmu ch as we do no t attempt to prese nt a por tfolio o f specif ic appli cations, t his manual is m ore gener al th an sp ecif ic. Inst ead, we ar e att empti ng t o str ike a spar k of in tuitive understa nding a nd intere st for how the ITC functio ns. Th e ITC’s func­tion an d relat ionsh ip to therm al syst ems ar e the mos t valuable n otion s transm itte d by this manual. Just as there i s no appl icati on manua l for vice- grip pliers, there i s not an application manual for the ITC. Both are basic, extremely useful devices, whose rea l worth is det ermined by th e use r.
1.1 Standard Feat ures
1.11 Thermo couple Sen sors
The ITC utilizes thermocouple sensors fabricated from ordinary thermocouple wire. A variety of factor s lea d to th is b eing th e bes t choi ce of senso rs:
Sensor junctions of very low mass can be easily fabricated. Lower mass means quicker recognition of temperature changes.
Thermocouples are inherently rugged, requiring little in the way of special handling precautions.
Thermocouple wire is inexpensive and readily available.
In keeping with this choice of sensors, the instrument is appropriately equipped with:
Automatic reference junction compensation.
references to 0°C, regardless of ambient temperature.
Thermocouple break detection.
power circuitry will be disabled, and a front panel indicator illuminat ed.
High impedance differential input circuitry.
instrument to tolerate floating or grounded thermocouples, with high common-mode noise immunity.
The ea se o f fabr ic atio n for sens ors compa tible wit h th e IT C is suc h th at us ers can seriously consider making their own. (In many cases, all that is needed is a small torch, silver solder, and a roll of thermocouple wire.)
Should the ther mocouple break, the heater
Circuitry automatically
This circuitry allows the
1
1.12 Proportional Heater Power Control
The ITC utiliz es propor ti onal power applic ation t o minimiz e temper ature overs hoot, and improve temperature stability about the setpoint. Controls are accessible to the user, allowing the proportioning bandwidth (in
o
C) to be adjusted to meet
specific requirements.
1.13 Power Attenuation
Many te mperatu re co ntroll ers a re used in con junct ion wit h vari acs (var iable o utput transformers) in order to improve temperature stability. By reducing the maximum power available to the heater, the user is adjusting the heater "size" to suit his particular thermal system. This is a practical, flexible solution to the problem, but requi res two devi ces to con trol the t emperatu re, one of whi ch is heavy, ineffi cient, and expensive.
The ITC employs a pushbutton switch so the user can attenuate the total power available to the heater circuit. Attenuation is selectable from 0 to 90%, in incre­ments of 1 0% .
1.14 Zero Crossing Power Application
Power is applied to the load in increments of integral half cycles, only. This technique drastically reduces RFI/EMI normally associated with high current AC switching.
1.15 Digital Temp erature Setting
The ITC employs a bank of three digital thumbwheel switches for temperature setpoint selection. The setpoint is selecta ble in 1
o
increments. The most obvious
advanta ge t o thi s s che m e is 10 0% se tt i ng r epe at abi l ity.
1.16 Compact Rugged Cons tructio n and Func tional Layout
The ITC’s physical characteristics are strictly utilitarian. In all cases, rugged construction techniques are employed, insuring that the assembled instrument is not delivered by a freight company in kit form. The instrument is housed in an aluminum/cycolac enclosure measuring 2.4" x 8.3" x 5.9". The top of the enclo­sure c an b e qu ickl y r em oved, a l low ing ac ces s to al l f u ses, e lec tr on ic s, etc.
It is worthy of note that almost all electronic components are mounted on a single printed circuit board. This feature directly translates to simple troubleshooting methods and minimal spare parts inventory.
2
1.2 Product Numb ers and Spe cifications
Produc t Nu mbe rs: ITC 10 X
X corresponding to 399 for 0°C to 399°C range 999 for 0°C to 999°C range
Example: ITC103 99: ITC, 1000 watts m aximum he ate r power, 0°C to 399°C range
Sensor Requirem ent Thermocouple; Ty pe K Range 0° to 390°C, or 0° to 999°C, as ordered
Absolute Accurac y
±
.5% of full scale Repeatability .5°C at constant ambient Sensit i ti vi ty to Am bi en t Ch an ge s . 05° C per ° C c ha nge Operati n g A mbi en t 10° t o 5 0°C Switched AC Power 1000 watts;
zero-crossing erro r: 5V AC max.
Proportioni ng Ba ndwi dt h
±
3
°C
Proportioni ng Freque nc y 2 Hz Setpoint 1° C increments; push button selection Max. Power Input Requirement 10.0 amps at 117 VAC Power Attenu ati o n 0 to 90 % in 10% i ncr eme nt s Physical Dimensions 2.4" x 8.3" x 5.9"; weight 1 lb. 14.4 oz. Visual I ndi c at or s
Power On (PWR) - illuminated whenever the instrument is plugged into a source of 120V AC, and the PWR switch is in the ON position
Heater On (HTR) - illuminated whenever the controller applies power to the heater
Thermocouple Fault (TCPL) - illuminates whenever thermocouple sensor opens. (If a sensor failure is detected, heater power is automatically interrupted, and t he HTR i ndicator will remain O FF.)
3
1.3 Techn ical Description
A general knowledge of the ITC’s organization and operation is helpful to its successful implementation. To facilitate understanding, three questions are posed:
1. What position does the ITC occupy in a thermal system?
2. How is the ITC organized to accomplish its task?
3. What is the most important aspect of the ITC’s organization?
These ques t io ns ar e a nswere d by Se ct ion s 1 . 31, 1.3 2, and 1 . 33, re sp ect ive ly.
1.31 Thermal System Overview
Figure 1
depicts a generalized closed-loop control system. The system is termed closed-loop since the controller bases its corrective actions on the actual status of the controlled function. In an open-loop system, corrective actions are based on anticipated stat us. Closed-loop syste ms are defi nitel y pre ferable.
CONTROLLED
FUNCTION
SENSOR
CONTROLLER
CORRECTION
ELEMENT
Figure 1
The system is compr ised of:
Controlled Fu nction .
Sensor.
Controller.
Appropriate to the function; level sensor, pressure transducer, etc.
Determines when corrective action is necessary, based on
Water level, air pressure, etc.
information supplied by the sens or.
Correction Element.
Means of adding water, increasing pressure, etc.
With slight modification, the diagram becomes appropriate to a thermal system utili zing an ITC, as show n in
Figure 2
.
HEATED
ZONE
THERMOCOUPLE
INSTRUMENTATION
TEMPERATURE
CONTROLLER
(ITC)
HEATER
Figure 2
4
It is readily seen that the ITC is responsible for maintaining the temperature within the heated zone. However, proper selection and application of the thermocouple and heater are essential if the ITC is to perform its function. (Refer to Section
2.2.)
1.32 ITC Block Diagram by Function
Almost any electronic device can be described by a block diagram of its circuit elements, each element performing something essential to the function of the device. Indeed, such a diagram is typically the first state in its design. Further, devices of simi lar fu nction wil l have simila r block diagrams.
TCPL
BREAK DE-
TECTION
SENSOR
SET POIN T
SELECT
INPUT
AMP
D/A
CONVERTER
DIFFER E NT I AL
COMPARATOR
ZERO
CROSSING
SWITCH
POWER
ATTE NUATOR
HEATER POWER SWITCH
Are these blocks supposed to correlate to items in
PROPORTIONAL
POWER
CONTROL
1.321 and following? No­menclature needs to be consistent. RC
Figure 3
The function of the ITC is to control the temperature in a heated zone. A brief discussion of what is required to perform the function reveals the elements conta ine d i n i ts bl ock dia gra m,
Figure 3
.
1.321 Input Amplifier
The signal supplied by the thermocouple is too small to be recognized by the other circ uit el ement s (appr ox. 50 microvolts /
o
C). Therefore, t he si gn al m ust b e amp l ifi e d
to a us ef ul level .
1.322 Set Point Selectors and D/A Convert er
The th umbwheel sw itches provi de a means of repre senting th e desired t empera­ture within the heated zone. (This temperature is hereafter referred to as the
setpoint
.) The switches prov ide a digit al repres entation o f the setpoi nt, which i s then c onverted to a more useful s ignal by mea ns of a te n-bit D/A convert er. The D/A converter conforms to the same transfer function as the input amplifier; i.e., a representation of 100° C by the input amplifier is identical to the D/A converter’s repres ent a ti on of 10 0
o
C.
5
1.323 Differential Comparator
A dif ferential comparat or is u sed to co mpare the output o f the D/ A converte r with that of the inp ut ampl ifier. Subsequent ly, the com parator ’s output den otes whe ther the zo ne t emp era t ur e is hi gh er or l ower tha n the se t poin t .
1.324 Heater Power Switch
In accordance with the comparator’s decision, the power circuitry will apply power to the hea ter wh en t he zone temper atur e is below t he s etpoi nt a nd int err upt power when i t i s ab ove th e s etp oi nt .
In strictly theoretical terms, the above four elements are all that would be required to imp leme nt th e contr olle r’s fun ction . However, prac tical appl ica tion r equi res three additional elements:
1.325 Thermocouple Break Detection
The most common physical malfunction in thermocouples is a break, or open circuit. If a break occurs, the input amplifier can no longer report the zone temperature, and usually will report the ITC’s temperature, instead. From the preced ing d isc ussi on, one can de duce t hat t his i s a pot enti all y disa stro us s ituat ion. However, a separate circuit is employed specifically to detect a break condition. Its output will cause the Heater Power Switch to be disabled, and a front panel indicator to be illuminated whenever a break occurs.
1.326 Propor tional Power Control
To this point, power application to the heater has been described as simply "appl ied or inte rrupted ". In rea lity, this would be anal ogous to tr ying to m aintain a dragster’s speed at 30 mph using full throttle applications only. Obviously, power must be delivered according to the need. For this reason, the ITC employ s pro­portional power control, where net power is delivered to the heater according to the difference between the setpoint and zone temperature. The proportioning technique is discu ssed in Se ction 1.33 .
1.327 Power Attenuation
Effective heater size can be tailored to the application by proper adjustment of the power a ttenu atio n con tro l. Exce ssive h eat er rat ings ar e oft en t he ca use o f sys tem instability at near ambient temperatures. Proportional control and power attenuation work hand-in-hand to produce excellent temperature stability. (Refer to Section 2.3.)
1.328 Zero Crossing Switch
This allows the he ater to come on only if t he AC wavefor m is at zero to supp ress noise on th e p ower li ne.
1.33 Propor tional Power Control
Alth ough t he IT C’s inpu t amp lifi er a nd D/A ci rcui tr y are acc urate and predi cta ble in their temperature representations, they do not in themselves constitute a good temperature controller. In a control system, the essential factor is stability. A temperature controller is not doing its job if the zone temperature is allowed to oscil late about the setpoint to a degree which upsets the process. In shor t, the aim is to reduce a thermal system’s natural tendency to oscillate to a level where it is not significant.
6
If zone heat er p ower i s sim ply appli ed o r int err upted acc ordi ng to t he c ompara tor’s verdict (correction required/not required) the result is wholly unacceptable. To illustrate:
Assume that a zone is to be heated from room ambient to 75 power is applied until the temperature r eaches 75
o
, and then interrupted, the
temperature will overshoot. As the temperature settles back to 75
o
C. If 100%
o
, 100% power will again be appli ed in an effor t to prevent the temperature from falling below the setpoint. As a result, the temperature will overshoot again. In this manner, the temperature will continue to oscillate about the setpoint.
As can be seen, on/off, stop/go, etc. are corrective measures that would make the ITC unacceptable for all but the crudest applications.
The key to obtaining acceptable stability lies in applying heater power relative to the need. Using the above example, but employing proportional control, more reason abl e r esu l ts ar e ob t aine d:
o
While the temperature rises from ambient toward 75 continuously, just as before. However, at a poi nt just
o
, the power is reduced to 95%. As the temperature continues to rise,
70
C, power is applied
the setpoint, say
below
power is linearly reduced such that power will be applied 50% of the time when the temperature reaches the setpoint, and only 5% when it reaches
o
. When the temperature begins to settle, the process is reversed. Heater
80 power is gradually increased as the temperature declines toward the setpoint. As a result, the temperature will tend to stabilize at a point where the power application is sufficient to maintai n equilibrium.
In conclusi on, the syste m’s tendency to oscil late is greatl y reduced i f some form of proportional control is employed.
Commonly, two methods can be used to electronically control AC power: phase proportioning, and time proportioning. With phase proportioning, some percentage of eac h AC cyc le is appl ied to the l oad. While this method is ju st fine for power drills, it is not acceptable for instrument use. This is due to the fact that the power is not switched at zero-crossings. Therefore, large amounts of RFI/EMI can be generated. (If such elec trical "no ise" is generated, it may upset the operation of other instruments in the vicinity.) With time proportioning, the average power is contr oll ed by divi din g time int o sp ecif ied p eri ods. Duri ng ea ch pe rio d, t he pe rcent ­age of power ON versus OFF time is proportional to the difference between the setpoint and the controlled temperature. Power is switched only at AC voltage zero-c ros s ing s, avoidi ng RFI /E M I ge ne rati o n.
Figure 4
is a graphic represent ation of time pr oport ioning as it is implemen ted in the IT C. T he hear t of the p rocess is the propo rti oning waveform. Thi s sawtooth­shaped waveform defines three important parameters of operation: lower tempera­ture boundary, setpoint, and upper temperature boundary. The setpoint will always be situated in the exact center of the waveform. The
represents the point below which 100% power will be applied. The
ary temperature boundary
plie d. And, as sta ted ear li er, the
represents the point above which no power will be ap-
setpoint
denotes the point at which power will be
lower temperature bound-
upper
applied 50% of the time. Observe, also, that between the two boundary tempera­tures, the average applied power is linearly proportional to the difference between the s etp oi nt an d th e actu al t em per atu re wi th in th e h eat ed zon e.
7
1
PROPORTIONING
WAVEFORM
POWER
APPLICATIONS
CONTROLLED TEMPERATURE RISING FROM AMBIENT;
1
NOTICE POWER APPLICATION IS PROGRESSIVELY REDUCED AS T HE TEMPERATURE
RISES
OVERSHOOT; NO POWER APPLIED
2
EQUILIBRIUM;CONTROLLED TEMPERATURE HAS SETTLED AT APPROX. 40% POWER
3
TIME
2
3
102°
98°
Figure 4
The number of degrees between the upper and lower temperature boundaries is referred to as th e
proportioning bandwidth
. Proper adjustment of the bandwidth
will further enhance temperature stability within the heated zone. Some guidelines for adjust ment ar e found in S ectio n 2.4 .
1.34 Power Attenuation
In the precedi ng sect ion, pr opor tion al power co ntrol was desc ribed as the pro cess by which the ITC applies a percentage of power proportional to the difference between the setpoint and the controlled temperature. It is not unusual that this technique, alone, will not yield acceptable temperature stability. Commonly, this situation occurs when near ambient temperatures are desired of a thermal system orig inally de signed for h igher temp eratures. Cons equently, t he heater s ize (rated output) is much too large for system demand.
In compensating for such difficulties, laboratory personnel often employ variacs (variable output, s tep-down transformers) to attenuate the power delivered to the heater.
Power delivere d to the heate r can be atte nuated in incr ements of 10% by setting the ITC’s front panel mounted ATTN pushbutton switch. This control performs exactly the same function as the variac mentioned above. However, the method by which the ITC performs this function differs considerably from variac operation. Here’s how :
A variac provides a means of adjusting the voltage (and consequently, the power) applied to the heater. The ITC varies the number of half-cycles
to be delivered by its power circuitry. For example, 100% is available
able
avail -
when the ATTN control is set to 0. I f the attenuation is changed to 4 (40%), only six of every ten half-cycles are available for delivery to the heater. As a result, the heater output will be 60% of its full rating.
8
In summary, the proportioning circuitry determines the percentage of time during which power will be applied, while the attenuati on circuitry deter mines what per­centa ge o f power is t o be avai l able fo r d el ivery during t his t ime.
9
2.
In thi s sec t ion pr ac ti cal c on si der ati on s for th e IT C ’s usage a re di scu sse d.
OPERATION
2.1 Physical layout of the ITC
Following are illustrations of the var ious models of the Instrumentation Temperature Controller. the ITC. models. The numbers on the illustrations relate to the numbered parts below.
Figure 5
Figures 7
shows the front panel, and
and 8 show the back panels of the 110V AC and 220V AC
1
2
34
Figure 6
56
shows the top v iew of
A T T
5999
OPEN
TCPL
PWR
1
Power Switch PWR
Front mounted toggle switch controlling power to heater and power supply circuits.
2
Power On Indi cat or
Front mounted neon indicator; illuminated whenever the power switch is in the ON position and power supply fuse is intact.
3
Heater Power On
Front mounted neon indicator; illuminated whenever instrument applies power to heater; will not illuminate if heater is not connected, or if broken thermocouple is detected.
4
Thermocou ple Fault In dicator
Front mounted LED indicator; lights whenever thermocouple circuit is broken.
ON
Figure 5:
HTR
Front panel, model ITC10
N
S E
T
C
°
5
Heater Power Attenuation Switch
Front panel mounted bidirectional ATTN switch; denotes heater power attenuation in increments of 10 percent.
6
Setpoint Swi t ches
Front panel mounted switches; denote controlled temperature setpoint in
7
Calibr ation Adj ustment s
Printed circuit board mounted pots; DO NOT attempt adjustment.
10
o
C.
10
8
9
7 7
Top view, model ITC10
8
Thermocouple Connector
Figure 6:
Printed circuit board mounted connector; connect red lead of ther mocouple to Terminal R.
9
.5 Amp Fuse
Printed circuit board mounted; fuses power supply primary circuitr y.
10
10 Amp Fuse
Printed circuit board mounted; fuses heater power circuitry.
13 11
13
THERMOCOUPLE
Y R
Figure 7:
HEATER
POWER
Back panel, model ITC10 110V AC
120V AC
10A MAX
13 12 13
THERMOCOUPLE
Y R
Figure 8:
HEATER
POWER
Back panel, model ITC10 220V AC
220V AC
10A MAX
11
11
Heater Receptacle, 120V AC only
Rear panel mounted AC receptacle; two-wire plus ground; connects heater via standard 16 or 18 gauge three-wire power cord (not supplied).
12
Heater Receptacle, 220V AC only
Rear panel mounted AC receptacle; two-wire plus ground; connects heater via power cord (black and white to heater, green to ground). Power cord is not supplied.
13
Top Cover Reta ining Scr ews
Remove these screws to gain access to inter ior of ITC.
2.2 Thermoco uples
Thermocouples, when used properly, are a very expedient and reliable means of sensin g t empera ture. In t his sect ion, we wi ll a ttemp t to h elp the use r avoid cer tai n genera l and s pe ci f ic pit fal ls in t her m oc oup le u sag e wi t h t he IT C.
Ther mocoup le meas uri ng junc tions are fabr icate d by jo ining two di ssimi lar met als. A type K thermocouple is formed from chromel and alumel. In theory, the thermo­coupl e is func tio nal so l ong as th e t wo meta ls r emai n in c ont act. (Th is do es i mply that a measuring junction can be formed by twisting two wires together. We would point out that the junction will not be suitable for any real application, however.)
Maintaining the integrity of the measuring junction is of prime importance. This means th at for a given appl icatio n, thought mu st be given the junc tion’s maxim um attainable temperature, corrosion resistance to its environment, and mechanical strength.
Commercially available thermocouples are usually joined by welding. This produc es a juncti on in whi ch the max imum temperat ure and cor rosion resi stance properties are those of the metals themselves. For applications below 400 quite serviceable junction can be formed by twisting the bare ends of the wire toget her, and then sec uring wit h silver sold er. For applicat ions above 400
o
C, a
o
C, t he junction should be welded. In the case of silver soldered junctions, we would again point out that the environment and maximum temperature must not be harmful to the solder.
It is important to note that considerations pertaining to junction integrity are also applicable to the
insulation
around each wire. As sta ted earl ier, a new junctio n is formed each time the two thermocouple wires come into contact. Obviously, unplanned junctions are to be avoided.
In matters concerning the thermocouple, measuring junction mass, thermal conduc tivity of the contr olled mediu m and placem ent can grea tly affect con trolled tempe ratur e st abil ity. In Sect ion 1 .32 6, an examp le was give n ill ust rati ng te mpera­ture instability. It was pointed out that stability is obtained by supplying heater power proportional to the need. At this point, it is important to recall that the thermocouple is responsible for telling the controller what the need is. Most importantly, any change in temperature must be reported without appreciable delay. This causes instability, regardless of how craftily the correction is carried out. This notion of minimizing delay is carried to fact by observing two rules:
12
1. The meas uring junct ion sh ould be o f the l owest ma ss pra cticabl e for the a ppli­cation. Simply put, the higher the mass, the more time required for the junction to reach t h e t emp era t ure of i ts s ur ro undi n gs.
2. The measuring junction should be placed as close as possible (thermally) to the heater. Whenever there is doubt about proper location of a thermocouple, follow these suggestions:
a. Place the junction directly between the heater and the object to be heated, as close to the heater as possible.
b. In a stirred air or liquid bath, place the junction immediately downstream from the heater.
In addi tion to the mo re commo n cons iderati ons, t here are a few impor tant speci fic notions regarding thermocouples to be used with the ITC.
Electrical contact.
If the measuring junction is in electrical contact with an object, that object must be connected to AC ground. For example, this would require a heater block to be grounded unless the ther mocouple is electrically insulated from it. (The junction must float or be grounded.)
Thermocouple resistance.
The following data describes the thermocouples
normally shipped with the ITC: ITC-K: 10 ft., 28 gauge, 40 ohm , ANSI Type K
2.3 Setpoint (Set °C)
Loosely defined, the setpoint denotes the desired temperature within the heated zone. However, the user should be aware that the denoted setpoint is not neces­sarily the temperature at which the zone will stabilize.
To be more precis e, the setp oint denote s the tempera ture at whic h power will b e applied 50% of the time. It is entirely possible that the zone will require more or less t han 50% power to ma intain s tabilit y. As a cons equence, t he zone te mpera­ture will settle above the setpoint if less than 50% power is required, and below the s etp oi nt if mor e th an 50% powe r i s ne eded .
Essentially, this characteristic offset is brought about by the proportional power control method used in the ITC, coupled with the thermal characteristics of the user configured heated zone. Without prior knowledge of the zone’s heat input vs. heat l oss proper ties, the only certainty is that the zone temperature will stabilize
somewhere
settl es, can be op timized by adjustment of the propo rtion ing bandwidt h. (Refer to Section 2.4.)
within the proportioning bandwidth. Exactly
the temperature
where
13
2.4 Propor tioni ng Ban dwidth
Current models of the ITC may have fi xed valued resistors in the trim
Note:
pot location for the bandwidth calibration. If the ITC needs fur ther calibration they may be replaced with 10K trim pot and the following text will explain the band width adjustments.
Given that the controlled temperature is reasonably accurate, stability becomes a most important measure of system performance. Perfect stability is obtained by applying the exact amount of power required to offset a system’s demand. In addition, the power must be applied Think about thi s. Theor etical n otions l ike "exact" and "ins tantaneo us" soon reveal the me ani ng of t he term, "opti mum".
In attempting to achieve optimum stability, we assume that the user will experiment with t h e proport ion i ng ban dw id th ad jus tme nt po t . (Refer to Sec t ion 2. 1, i tem 7 . ) In keeping with this assumption, we offer the following explanation of bandwidth adjustment.
2.41 Bandwidth Defined
Rigorously defined, bandwidth is the peak to peak value of the proportioning wave­form, expres sed in degre es centigrade. The ba ndwidth pot con trols the heig ht of the wavefor m. More impor tantl y, t he heigh t deter mines the slope of the diagon al. In
Figure 9
6° bandwidth. In each case, the controlled temperature is depicted 1 below the peak height of the waveform. Notice that the resulting power applications are differen t. In fact, power is applied twice as l ong in the 3° example as in the 6° example. This is due to the slope of the diagonal, and, as we shall see, is a very usefu l t hi ng t o re memb er.
, two waveforms are shown: one with 3° bandwidth, and the other with
instantaneously whenever a d emand occ urs.
The important thing to notice in changes within the bandwidth, the resulting change in heater power is dependent on the slope of the diagonal. More specifically, the power is controlled by the slope of the diagonal.
If, in each case, the temperature falls 1° (1° excursion), the resulting changes in applied power are dramatically different. In the 3° example, ap plication ch anges from 33- 1/3% to 66- 2/3%. The same 1 excursion in a 6° bandwidth causes application to change from 16- 2/3% to 33- 1/3% per degree and 16- 2/3% per degree, respectively. By observation, increasing the bandwidth decreases the amount of ch an ge i n averag e ap pl i ed pow er for a g iven cha ng e in t em per atu re.
How does all this relate to stability improvement? Well, assuming that a stability problem ex ist s, it may be attr ibutabl e to excessi ve heater power. By this, we mea n that the heater is simply too powerful for the application. The situation usually results from designing the system to heat quickly and operate over a broad tempe rature range. The pr oblem is chara cterized by the contro lled temper ature’s tendency to spend most of the time above the bandwidth, occasionally falling into its upper reaches. The temperature will not stay within the bandwidth because
14
Figure 9
is that as the controlled temperature
rate of change
in applied
POWER AP PLI CATIONS
3
°
TIME
6
°
CONTROLLED TEMP
1° EXCURSION
POWER AP PLI CATIONS
CONTROLLED TEMP 1° EXCURSION
CONTROLLED TEMP EXCURSION TEMP
Figure 9
power is i nc rease d too ab rupt ly, quickly dr ivi ng th e temper ature up, out of re ach. If the heater size cannot be reduced, the bandwidth must be increased. Doing so will decrease the rate of change in applied power, hopefully increasing stability. Always allow ten to fifteen minutes after making each adjustment before making another. This will allow the system enough time to reveal whether or not further adjustment is required.
As a consequence of increasing the bandwidth, the user should be aware that the controlled temperature is usually shifted upward, as well. This notion is most eas­ily understood by noting the position of the 1% power point before and after adjust­ment. Remember that the system will still require the same average power to maint ain a given temp erat ure. There fore, as t he bandwi dth is i ncre ased, the given power point shifts upward, carrying with it, the controlled temperature.
Note that the controlled temperature shifts upward only if it was originally trying to stabilize above the setpoint (50% power point). There usually is no stability problem when the temperature is settling below the setpoint. However, we will point out that in this situation, the temperature will shift downward when bandwidth is increased.
The valu e of th e ba ndwi dt h ( i n ° C) ca n be de termined by t h e fol low ing met h od:
1. Reduce the setpoint temperature until the HTR indicator is OFF continu­ously. Make note of this temperature.
2. Increase the setpoint until t he HTR indicator is ON continuously. Make note of this temperature.
3. Determine the difference between the two temperatures. This value is the bandwidth.
15
2.5 Installation
The following discussion is intended to assist you in the initial installation of an ITC. It is assumed that you have read the foregoing portions of this manual.
Check the instrument for shipping damages. Open the instrument and check for loose components. There shouldn’t be any. In the event that damage is noted, notif y th e carr ier imme diate ly. Valco a ssumes no r espo nsib ilit y for dam age in cur red in shipment.
Assuming no damage is seen, perform the following checkout. You will need an ordinary incandescent light or other resistive load that provides indication of when power is applied.
1. Connect the load to the ITC. In 110V models, a receptacle (labeled P1) is provided which accepts ordinary three-wire appliance plugs. The 220V uses a cinch socket.
2. Connect t h e in st r ume nt t o a su it abl e s our ce of 12 0V AC.
3. Set the set poin t and at tenuati on switc hes to 0 . Swi tch th e instr ument o n. The TCPL indicator should illuminate momentarily. (The instrument is determining whether or not its thermocouple is OK.) The HTR indicator should be OFF.
4. After allowing the instrument to warm up for a few minutes, increase the setpoint until the HTR indicator flashed with a 50/50 duty cycle. The setpoint shoul d a ppr oxima te t he am b ien t temp era t ur e.
5. Hold the thermocouple’s measuring junction firmly in one hand. Since your skin temperature is usually 10° above ambient (and subsequently, the setpoint), the HT R i ndi c at or sho ul d c eas e f l as hing .
6. Increase the setpoint until the HTR indicator is ON continuously. (Try 50°.) Change the power attenuation switch to 9. The HTR indicator should flicker faintly. Progressively decrease the ATTN setting, noting that the HTR indicator "bright­ness" increases at each position. When the ATTN switch is at zero, the HTR indi­cator should be ON continuously, with no visible flickering.
Regarding the zone heater specifications, care should be taken to avoid exceeding the ITC’s specifications for switched power. The ITC10 will switch loads up to 1000 watts. If you attempt to exceed this rating, the instrument will probably sacri­fice its f uses and/or p ower tr iac.
The present ITC power circuitry is intended to switch resistive loads only. This means that inductive loads, such as electric motors, solenoids, and especially variacs cannot be switched successfully.
Damage may result if inductive loads are used.
Always use three-wire power connections for the instrument, as well as heater connection. (Ref. Section 2.2.) It is important that the heater block, etc. be
16
connec t ed t o AC gr ou nd . Failure t o d o so may c aus e a s ho ck haz ar d, or co ntr ol le r malfu nctio n, or bo th.
Locate the ITC where it will not be subjected to abrupt changes in ambient tempe ratu re. This w i ll im pr ove the c ont r ol led t emp era tur e s tab i lit y.
When installing the thermocouple, be sure to observe electrical restrictions noted in Sect ion 2.2 .
Actual installation consists of, first, thinking about what must be done, then connec ting the heater, and finally inserting the ther mocouple. After this is done, turn it ON and play with the system. Notice whether or not corrections need to be made in such areas as thermocouple location, bandwidth adjustment, etc. Enjoy! (If you’re not enjoying yourself, cal l us. We’ll try t o help in any way we can.)
2.6 Troubleshooting and Schematic Diagram
Troubleshooting the ITC is straightforward, in most cases. The device can be though t of as being di vided in to two sections ; ins trumenta tion an d power cir cuitr y. Problems with the power circuitry are the most easily identified, and can be handled with a minimum of electronics experience. Isolation and repair of mal­functi ons in th e instrum entation circuitr y require sophistic ated test equipment an d extensi ve el ec t ron ic s expertise. For this r eas on, i t i s rec omm e nded t hat th e fa ctory be con sul te d w he n t he foll owi ng pr oc edur es ar e of no he l p.
2.61 Situation: PWR ON indicator fails to illuminate; instrument does
nothing.
A 1/2 amp fu se i s em ployed t o fuse th e ins trum ent’s DC p ower s uppl y. If this fus e is blown, the PWR ON indicator will not illuminate, and the instrument will not perfor m any fun cti ons. The f use is l ocate d at the le ft re ar c or ner of t he en clos ure. (Refer to fact ory.
2.62 Situat ion : TCPL ind icat or ON con ti nuously; no p ower appl ied to
heater
When t he TC PL in dica tor is O N con tinuo usly, the in str ument thi nks an ope n cir cui t has developed in the thermocouple. As a consequence, the ITC will refuse to apply power to the heat er. The t hermo couple is co nnected t o the i nstru ment by a barrier strip, designated B1. (Refer to tions are snug. As a second consideration, be cer tain that proper connection to AC ground is made in any case where the thermocouple measuring junction contacts metal. If this is not done, the TCPL circuit can sometimes be fooled into beli eving there is a malf unction. As a fin al considera tion, dis connect the th ermo­coupl e, and check i t for elect rical c ontinui ty. If the problem is not locat ed, consul t the fact ory.
Figure 6
, Item 10.) If the ITC persists in blowing this fuse, consult the
Figure 6
, Ite m 9.) Be cer t ai n t he se co nnec -
17
2.63 Situation: No power being applied to heater; TCPL indicator OFF.
In this situation, the HTR indicator remains OFF. The power triac is protected against continuous current overload with a 10 amp fuse. (Refer to
11.) If this fuse is blown, no power is available to the heater circuitry. In addition to replacing a blown fuse, consider what may have caused the overload. The heater and/or power triac may have developed a short circuit. This sort of occur­rence i s us ual ly acc ompan ied by bu rn ed wi rin g. Be cer ta in tha t the heate r doe sn’ t exceed the power rating for the ITC (1000 watts).
It is the case that the situation described above can occur without blowing the fuse. If this occurs, consid er whet her or not the load i s induct ive. Rememb er that such loads cannot be switched with the ITC’s present circuitry.
The appropriate schematic diagram is supplied in this section. Should you require any explan at io n o f th e c ir cui try, p l ea se con tac t the fac tory.
Figure 6
, Item
18
3.
WARRANTY
This L imited Warran ty gives the Bu yer speci fic legal rights, and a Buyer may a lso have othe r r i gh ts t h at var y form state t o s ta t e.
For a period of 365 calendar days from the date of shipment, Valco Instruments Company, Inc. (hereinafter Seller) warrants the goods to be free from defect in mater ial and w orkmanshi p to the o riginal purchaser. During the warrant y period, Seller agrees to repair of replace defective and/or nonconfor ming goods or parts without charge for material or labor OR at seller’s option demand return of the goods and tender repayment of the price. Buyer’s exclusive remedy is repair or replacement of defective and nonconforming goods OR at Seller’s option repay­ment o f t he p r ic e.
SELLER EXCLUDES AND DISCLAIMS ANY LIABILITY FOR LOST PROFITS, PERSONAL INJURY, INTERRUPTION OF SERVICE, OR FOR CONSEQUEN­TIAL INCIDENTAL OR SPECIAL DAMAGES ARISING OUT OF, RESULTING FROM, OR RELATING I N ANY MANNER TO THESE GOODS.
The Limited Warranty dose not cover defects, damage or nonconformity resulting from abuse, misuse, neglect, lack of reasonable care, modification or the attach­ment of improper devices to the goods. This Limited Warranty does not cover expendabl e items. This warr anty is VOID w hen repai rs are perfor med by a non ­author ized ser vice cent er or rep resentati ve. If you have any problem loc ating an authorized service center or representative, please call or write Customer Repairs, (713) 688-9345, Valco Instruments Company, Inc., P.O. Box 55603, Houston, Texas
77255. At Seller’s option, repairs or replacements will be made on site or at the
factor y. If repairs or re plac ement s are t o be made at the fact or y, Buyer s hall r etur n the goods prepaid and bear all the risks of loss until delivered to the factory. If Seller returns the goods, they will be delivered prepaid and Seller will bear all risks of loss until delivery to Buyer. Buyer and Seller agree that this Limited Warranty shall be governed by and construed in accordance with the laws of the State of Texas.
THE WARRANTIES CONTAINED IN THIS AGREEMENT ARE IN LIEU OF ALL OTHER WARRANTIES EXPRESSED OR IMPLIED, INCLUDING THE WARRAN­TIES OF MERCHAN TABILITY AND FITNESS FOR A PARTICULAR PUR POSE.
This Limited Warranty supercedes all prior proposals or representations oral or written and constitutes the entire understanding regarding the warranties made by the Seller to Buyer. This Limited Warranty may not be expanded or modified except i n wr it in g s ign ed by t he p arties h ere t o.
19
4.
Assembly Drawing..... .............. .............. .............. .............. ............ ....... Drawing 21556 Page 21
Assembly Broad Drawing ............ .............. .............. .............. .............. . Drawing 22218 Page 22
Schematic – ITC Board ............. .............. .............. ............ .............. ..... Drawing 22219 Page 23
Board Conversion.... ............ .............. .............. .............. ............ ........... Drawing 21647 Page 24
TECHNICAL DRAWINGS
20
110V VERSION
4 3
(ON BOTTOM)
1A
220V VERSION ONLY
*
3 4
9
18
4
7
8
13
*
17
(FROM BOTTOM
12
OF ENCLOSURE)
16
5
15
BLACK
GREEN
14
GREEN
WHITE
BLACK
WHITE
9
(GREEN/YELLOW 220V)
(BLUE 220V)
(BROWN 220V)
1
Valco Instruments Co., Inc.
INSTRUMENTATION TEMPERATURE CONTROLLER
PWR
ON HTR
11
LTR DESCRIPTION
A
ITC BD. ASSY. REV. M,N
B
19
2
4
YELLOW RED
34
OPEN TCPL
6
-
A T T
0
N
+
10
+
++
993
---
S E T
C
18
20
Instrumentation Temperature Controller Instruction Manual
Valco Instruments Co. Inc.
18
SEE NOTE 2
NOTE: FOR 220V MODEL.
*
ITEM
1 2 PCB ASSY: ITC 10 AMP 3 4 5 6 7
*
8 9 10 11 12 13 14 15 16 17 18 19 20
21 22 23 24 25 REF
*
REMOVE ITEM 13 AND DRILL MOUNTING HOLES USING DRILL TEMPLATE A-21819. INSTALL CINCH SOCKET #S304-AB WITH COVER PLATE ITEM 20 (A-21820).
WIRE SCHEDULE
WIRE (PCB)
TERMINAL (SOCKET) BLACK (HOT) WHITE (NEUT.) GREEN (GND)
MODIFY PCB PER DRAWING A-21647 INCLUDE I-T304PCCT PLUG
ENCLOSURE C-21527 REV. G
C
ECN #2050 CLARIFY DWG
D
ECN #4668 CLARIFY 220V VERSION
ENCLOSURE: ITC, 10 AMP.
STANDOFF: 4-40*1/4, THREADED, NYLON SCREW,PLMS: 4-40*1/4 lg,PANHD,PH,SS STANDOFF: 4-40*1/4 SWAGE THREADED SWITCH ASSY: ITC TEMP.CTRL. (399 DEG.C) POWER-CORD: GREY 6' 18/3 SVT STRAIN-RELIEF: SRR-10, HEYCO#: 5P-4 1147 LUG: FEMALE SLIP-ON, 16-14 AWG THERMOCOUPLE-ASSY: 10'2 (ITC) K TYP FEET: RUBBER STICK-ON NUT, HEX: #4-40 UNC, STAINLESS RECEPTACLE: POWER OUTLET BLACK WIRE: 14 AWG TEFLON BLACK CSA SPEC WIRE: 14 AWG TEFLON GREEN CSA SPEC WIRE: 14 AWG TEFLON WHITE CSA SPEC TUBING: HEAT SHRINK 1/4" ID. SCREW,SMS : #4*3/8 LG, PL, SS TAG: SERIAL, ALL ELEC. DEVICES MANUAL: OPERATION, ITC
PLATE, ADAPTER 220V ITC PLUG SCREW,PLMS: 6-32 X 3/8 LG NUT, KEP: #6-32 PLUG: 4 PIN CABLE SOCKET-MOUNT: 4 PIN PANEL POWER CORD: "SCHUKO" PLUG
DESCRIPTION
1 2 3
REVISIONS
PARTS LIST
POWER CORD 220V
I-W-17800
BRN
HOT
BLU
NEUT
YEL/GRNGND
23
25
4
ENCLOSURE
DATE APPROVED
20FEB89 22FEB89 8AUG94 22MAR99
VALCO # I-21527 I-22218 HWSO-4050 HWSC-PL4-4 HWSO-1650-2 I-21280-02 I-W-CS-21 HWSRR-10 HWLUG-4218B I-21014-01 HW-1658 HWNUT-HEX#4 HW-OUTLET I-W-14-BLACK I-W-14-GREEN I-W-14-WHITE I-STUBE.250 HWSC-SM4-6 I-21988 MANUAL:ITC
I-21820 HWSC-PL6-6 HWNUT-KEP#6 I-T304PCCT I-T304SAB I-W-17800
J DURR J DURR
QTY
.333 .333 .333 .125
1 1 3 9 3 1 1 1 6 1 4 1 1
4" 4" 4"
6 1 1
1 2 2 1 1 1
24
21
21
I
N
V
S
a
T
lc
R
o
In
U
M
s
tr
E
u
N
m
T
e
n
A
t
s
T
C
IO
o
N
.
, In
T
c
E
.
M
P
E
R
A
T
U
R
E
C
O
N
T
R
O
L
L
E
R
NOTE 2 ADJUST HEIGHT OF COVER BY TURNING SCREW
1B
22
FINAL ASSY
THIS DOCUMENT AND THE INFORMATION WHICH IT CONTAINS SHALL NOT BE USED, EXPLOITED OR SOLD, AND SHALL NOT BE REVEALED OR DISCLOSED TO OTHERS WITHOUT THE EXPRESSED WRITTEN PERMISSION OF VALCO. THIS DOCUMENT SHALL REMAIN THE PROPERTY OF VALCO AND SHALL BE RETURNED UPON DEMAND.
TOLERANCES UNLESS OTHERWISE SPECIFIED FRACTIONS DEC. ANGLES
1/64"
APPROVED
DRAWN
R.B.D. / M.C.
DESIGNED
CHECKED
FILE NAME
21556
.XX.01
.XXX.005
63
.X.1
1
ITC ASSY. 10 AMP
DATE
2/20/94
REV. M,N,P
2/20/89
SUB-DIR
\ITC\
USA PROJECTION
1
432
Valco Instruments Co., Inc.
ITC10399-220
SIZE DRAWING NO.SCALE
C
ITC10399
21556---
SHEET
OF
22
* * *
ITEM
PCB T1 F1 F2 TP1-10 CO1 CO2 C03,4 CO5,6 Z1 Z2-4 Z5 Z6 Z7 S1,5 S2-4 S6 S7 TR1 C1,2 C3,4,14
C5,6,8-10, 15,16
C7 C11 C12,13 RN1 RN2,3 Q1 Q2,3 SW1 L1,2 L3 BR1 VR1 VR2 D1 R1 R2 R3 R4 R5,7 R6 R8A R8B R9,R10 R11 R12 MT1-6 SC1-6 KN1-6 FC1-4
R13-14
PCB ASSY: ITC 10 AMP TRANSFORMER 115/230V DSC4-24 FUSE: 10AMP 3AG FUSE: 3AG SLO BLO 1/2 AMP (TYPE 313.5) TERMINAL: HOLLOW USECO CONN: 20 PIN HEADER, ANSLEY CONN: 2 POSITION BLOCK CONN: 2 PIN MOLEX CONN: DIALIGHT IC: K TYPE THERMOCOUPLE CONDITIONER IC: COMPARATOR ( DUAL ) IC: DUAL TYPE D FLIP-FLOP IC: DECIMAL CTR/DIVIDER. RCA OR MOT IC: OPTO-TRIAC MOC3011 SOCKET: DIP, 14 PIN LOW PROFILE SOCKET: DIP, 8 PIN, LOW PROFILE SOCKET: DIP, 16 PIN, LOW PROFILE SOCKET: DIP, 6 PIN, LOW PROFILE TRIAC: T0220, 400V 15AMP CAP: ELECT, 220uF 35V, AXIAL LEAD CAP: TANTAL, 4.7MF 35V CAP: CERAMIC, .022uF 50V, .250 LEADS CAP: CERAMIC, 27 PF 50V CAP: MONO CERAMIC, .22 uF 50V, .2"LEADS CAP: TANTAL, 1MF 35V RES NET: 10 K, 16 PIN DIP, DISCRETE RES NET: 100 K, 16 PIN DIP, DISCRETE TRANSISTOR: NPN, T093, DARLINGTON TRANSISTOR: PNP, TO93, DARLINGTON SWITCH: TOGGLE DPDT-RPC-N-P-S LAMP: NEON, RED (9001-52-C-03-2RN) LED: RED, WITH MOUNT (9001-52-C-03-2RN) RECTIFIER BRIDGE IC: VOLTAGE REGULATOR, -12V TO220 IC: VOLTAGE REGULATOR, 12V, TO220 DIODE: SILICON SIGNAL RES: 100, 5%, 1/2W RES: 1.27 K, 1%, 1/4W RES: 2.2 MEG, 5%, 1/4W RES: 10, 1%, 1/4W RES: 10 K, 5%, 1/4W RES: 953, 1%, 1/4W RES: 10.0 K, 1%, 1/4W RES: 715, 1%, 1/4W POT: 10 K, TRIM, SHORT CT9W RES: 100 K, 5%, 1/4W RES: 1 K, 5%, 1/4W MALE TABS SCREW,PLMS: 6-32 X 1/4 LG, SS NUT, KEP: #6-32 UNC FUSE CLIP: PCB MOUNT (102080) FOR 110V MODELS-WIRE:BUSS, UNINSULATED,.025 DIA,22 AWG FOR 220V MODLES - RES, 237 K, 1%, 1/4W
DESCRIPTION
* R6,R8A,R8B MAY BE SUBSTITUTED BY TRIM POTS.
VALCO # I-PCB22217 I-X-DSC4-24 HWFUSE-10A HWFUSE-.5A HW-2010B I-T6092027 I-T4888-6 I-T09641021 I-TCM21-3 I-ICAD595AQ I-ICLM358 I-IC4013 I-IC4017 I-IC3011 I-TDS-14-LP I-TDS-8-LP I-TDS-16-LP I-TDS-6-LP I-Q4015L5 I-CE227-35AL I-CT475-35 I-CC223-50 I-CC270-50 I-CC224-50 I-CT105-35 I-RN761-3-10K I-RN761-3-100K I-QMPSA13 I-QMPSA65 I-SW-MTM206 I-LAMP-R I-LED550-01 I-D-VE28 I-IC7912 I-IC7812 I-D1N914 I-R521000 I-R111271 I-R512204 I-R1110R0 I-R511002 I-R119530 I-R111002 I-R117150 I-RTP103 I-R511003 I-R511001 HW-607 HWSC-PL6-4 HWNUT-KEP#6 HWFUSECLIP-1 I-W-BUSS-1
I-R112373
1 EA 1 EA 1 EA 1 EA 10 EA 1 EA 1 EA 2 EA 2 EA 1 EA 3 EA 1 EA 1 EA 1 EA 2 EA 3 EA 1 EA 1 EA 1 EA 2 EA 3 EA 7 EA 1 EA 1 EA 2 EA 1 EA 2 EA 1 EA 2 EA 1 EA 2 EA 1 EA 1 EA 1 EA 1 EA 1 EA 1 EA 1 EA 1 EA 1 EA 2 EA 1 EA 1 EA 1 EA 2 EA 1 EA 1 EA 6 EA 6 EA 6 EA 4 EA
.75" EA
QTY
2 EA
NOTE: INSTALL TR1 AS SHOWN
.15
.35
.35"
FC1
FC3
MT3 SC3 KN3
F1
F2
MT4 SC4 KN4
MT5 SC5 KN5
MT6 SC6 KN6
CO3
CO5 CO6
SW 1
LTR
A B C
TR1
MT1
MT2
SC1
SC2
N1
KN2
FC2
FC4
Z7 S7
+
+
CO4
R13 R14
L1
L2
INSTALL JUMPERS FOR R13 & R14 (110V MODELS) INSTALL R13 & R14 ON 220V MODELS
REFER TO DWG 21647
NEXT ASSY
21556
REVISIONS
SHEET
INITIATED
J DURR
I-22218
J DURR
REPLACE R9A,R9B FOR TRIM POT 10K (R9)
DESCRIPTION
ECN #1805 UPDATE PER REV. P BOARDS ECN #2145 CHG R2 TO 1.27K WAS 2.2K
Z5 S5
THIS DOCUMENT AND THE INFORMATION WHICH IT CONTAINS SHALL NOT BE USED, EXPLOITED OR SOLD, AND SHALL NOT BE REVEALED OR DISCLOSED TO OTHERS WITHOUT THE EXPRESSED WRITTEN PERMISSION OF VALCO. THIS DOCUMENT SHALL REMAIN THE PROPERTY OF VALCO AND SHALL BE RETURNED UPON DEMAND.
TOLERANCES UNLESS OTHERWISE SPECIFIED FRACTIONS DEC. ANGLES
.X.1
1/64"
.XX.01
.XXX.005
APPROVED
DRAWN
M.CHIU 1/11/89
DESIGNED
CHECKED
FILE NAME SUB-DIR
22218 \ITC\
DATE
Z1
TP10
S1
Z2 S2
C12
C14
+
+
+
C13
R 8 B
Z4 S4
A
R9
Z6
R10
S6
63
1
PCB ASSY: ITC
REV M,N,P
DO NOT SCALE DRAWING
SCALE
USA PROJECTION
Z3 S3
C
1 6
R N 3
Valco Instruments Co., Inc.
SIZE DRAWING NO.
B
DATE
2/28/89 4/5/94 22SEP94
REV P BOARDS ONLY DRILL FEEDTHRUS OUT AT THIS LOCATION. JUMPER LAND ON BOTTOM OF BOARD TO BRIDGE HOLE.
22218---
OF
CO2 R
Y
+12V
C9 .022uf
953
FRONT END
R6
BANDWIDTH ADJ.
98
11
-12V
RN3 100K
3
+
Z3
1
2
358
6
/
-
2
RN2
100K
8
+
C14
4.7uf
-12V
RN2
100K
10
1
9
RN3 100K
10
R12 1K
RN3
100K
7
+12V
.022uf
C8
R7 10K
-12V
C10 .022uf
TCPL TEMP.
- 100V
TP1
Z1
R5 10K
13
14
-ALM
-IN
7
+IN
-V
1 2
5
AD
6
3
595
10
4
COUNT
8
11
FB
+V
9
12
V0
+ALM
THERMOCOUPLE FAULT
L3
16 1
RN1
Q3
10K
A65
215
Q2
RN1 10K
A65
Q1 A13
+12V
R2 2.2K
Z7
R1
1
MOC
2
3011
3
100
4
5
6
VOLT. READING
+5V
-5V
TP2
REF.
RN3
100K
.22uf
C11
6 2 5 1 73
4
16 1
215
3
COMPARE
RN2
100K
13
RN2
100K
1
100K
6
-
8
Z3
1
/
358 +
4
5
-12V
-12V
RN3
2
+12V
RN2
100K
15
6
­1
/
Z2
+
5
+
C12
1MF
16
7
7
+
C13 1MF
-12V
6
11
R8A
RN2
10K
100K
R8B
715
-12V
RN3
100K
14
(NOT INSTALLED)
10 8
9 4
LTR DESCRIPTION DATE
A REPLACE R9A,B FOR TRIM POT 10K(R9) 3/1/89
ECN #2050 UPDATE DRAFTING STANDARDSB 4AUG94 ECN #3334 CORRECT SCHEMATICC
2
2
358
7
14
3
RN2
100K
TP4
TP5
10.00V DC
REFERENCE VOLTAGE
+12V
R10 10K
REVISIONS
7AUG96
R3
2.2Meg
+12V
R4
10
3
2
27pF
-
Z2
1
/ +
-12V
TP3
8
2
358
4
C7
HEAT
1
D1
1N914
18 19 20
J DURR J DURR
FRONT PANEL
CONTROLS
TEMPERATURE SELECTOR
10K
INITIATED
23
.022uf
C15
RN3
100K
413
+12V
-
8
Z4
1
2
358
220V
+
/
1
+
324
VR2
7812
+
C2
C6
.022uF
VR1
.022uF
7912
C5
C1 220V
R11
100K
+-
BR1
ZERO CROSSING
100K
RN3
125
+12V
10K
TP9
+12V
+
C4
4.7MF
TP8
C3
+
4.7MF
9
R
6
-
Z4
1
2
358
/ +
5
T1 DSC4-24
5 6 7 8
-12V
7
1
2
3
4
TP6
7.21V DC
R13
*
*
CUT
*
JUMP
*
CUT & JUMP FOR
*
220V MODLES
POWER SUPPLY
** R13, R14 - 220V
MODLES ONLY
JUMP FOR 110V MODELS
F2 .5A
SW1
F1 10A
L1
TO LOAD
HEAT
TP7
+12V
RN1
.022uf
10K
MT6
MT5
MT4
C16
HOT BLACK
NEUTR. WHITE
GND GREEN
314
Q4015L
R14
**
MT2
B
H
G
L
O
N
A
T
D
C K
TR1
L2
MT3
MT1
N
W
G
E
H
R
U
I
E
T
T
E
RE
N
Z6
4017
4
7
Q3
Q2 Q0
3
1
Q4 Q5
5
16
+12
Q6
Q7
12
NC
10
Q7
CK
9
14
Q8
6
8
Q9
11
13
EN
15
2
RES
Q1
ATTENUATOR
Z5
6
S
RES
2
C
Q D
5
4013
14 13 12
1
C
Q
P O W E R
I N
12
4
11 10 9 8 7
3
5
RN1 10K
413
RN1 10K
512
RN2
100K
THIS DOCUMENT AND THE INFORMATION WHICH IT CONTAINS SHALL NOT BE USED, EXPLOITED OR SOLD, AND SHALL NOT BE REVEALED OR DISCLOSED TO OTHERS WITHOUT THE EXPRESSED WRITTEN PERMISSION OF VALCO. THIS DOCUMENT SHALL REMAIN THE PROPERTY OF VALCO AND SHALL BE RETURNED UPON DEMAND.
TOLERANCES UNLESS OTHERWISE SPECIFIED FRACTIONS
1/64"
APPROVED
DRAWN
M.CHIU
DESIGNED
CHECKED
FILE NAME
22219
.XX.01
.XXX.005
63
ANGLES
DEC.
.X.1
1
DATE
1/16/89
SUB-DIR
\ITC\
10
2 3 5 6 4 8 7 9
11 12 13 14 15 16 17
1
CO1
BOARD ASSY. I-22218
Valco Instruments Co., Inc.
SCHEMATIC
ITC REV P
USA PROJECTION
SIZE DRAWING NO.SCALE
1
ATTENUATOR
9
SELECTOR
8 6 5 7
C
3 4 2
N/C
22219---
C
SHEET
OF
ADD JUMPER
LTR DESCRIPTION
A
ITC BD. REV M,N
ECN #1808 NEW DWG
B C
ECN #2050 SHOW NEW VER. W/R13 & R14
ASSY-22218 SCH-22219 BD-22217 AW-160 REV-N
CUT
DATE APPROVED
21FEB89
15APR94
8AUG94
J DURR J DURR
COMPONENT SIDE
MT6 SC6 KN6
SW 1
CO3
CO5
R13
L1
CO4
CO6
R14
L2
COMPONENT SIDE
NOTE: INSTALL R13 AND R14 ON BOARD FOR 220V VERSION.
(237K 1% 1/4W I-R112373)
THIS DOCUMENT AND THE INFORMATION WHICH IT CONTAINS SHALL NOT BE USED, EXPLOITED OR SOLD, AND SHALL NOT BE REVEALED OR DISCLOSED TO OTHERS WITHOUT THE EXPRESSED WRITTEN PERMISSION OF VALCO. THIS DOCUMENT SHALL REMAIN THE PROPERTY OF VALCO AND SHALL BE RETURNED UPON DEMAND.
USA FILE NAME
SUB-DIR
\ITC\
SCALE
SHEET OF
APPROVED DATE
DRAWN
R.B.D.
DESIGNED
---
8/22/9021647
DRAWING NO.
A
TOLERANCES UNLESS OTHERWISE SPECIFIED
+-1/64"
21647
DEC.FRACTIONS
.X.1
.XX.01
.XXX.005
63
ANGLES
+- 1
Valco Instruments Co., Inc.
O
PCB CONVERSION, ITC
110V TO 220V
24
Loading...