VICI DVSP User Manual

Valco Instruments Co. Inc.
Digital Valve Sequence Programmer Instruction Manual
P. O. Box 55603, Houston, TX 77255
(713) 688-9345
Sales toll-free (800) 367-8424
Fax (713) 688-8106
MAN-DVSP
Rev. 1/93
Printed in USA
Table of Co ntents
1. GENERAL DESCRIPTION............................................................................... 1
2. IMPLEMENTATION...... .... .... ...... .... .... ...... .... .... ...... .... .... ...... .... .... ...... .... .... ...... .2
2.1 Solenoid Valves
2.11 110 VAC
2.12 12 VDC
2.13 Valco MSVA
2.14 Pulsed Operation of Solenoids
2.2 Valco Electric Actuators
2.21 Multiposition
2.22 Two position
2.3 Valco Digital Valve Interface (DVI)
3. SWITCH AND DISPLAY FUNCTIONS ................. .............. ................ .............7
3.1 Operating the DVSP by Remote Contact Closure
4. DEMONS TRATION SEQUENCE ...... .... .. .. .... .. .. .... .. .. .... .. .. .... .. .. .... .. .. .... .. .. .. .... .8
5. TECHNICAL DRAWINGS.................... .. .. .. .. .. .. .. .. .. .. .. .. .. .... .. .. .. .. .. .. .. .. .. .. .. .. .. .. .11
6. WARRANTY......... .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .... .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .... .. .. .. .. .. .. .. .. .. .23
1. GENERAL DESCRIPTION
The Digital Valve Sequence Programmer (DVSP) is an add-on or stand-alone timer /programmer ava ilable with ei ther 2 or 4 int ervals, se ttable in rang es of 0-99 seconds, 0-9.9 minutes, or 0-99 minutes. The DVSP is most commonly used for remote operation of electrical devices such as solenoid valves, Valco two position or multiposition electric actuators, and the Valco Digital Valve Interface (DVI), which converts contact closures into pneumatic pulses for switching Valco two position air actuators.
The DVSP has two operational modes: in the AUTO mode, the DVSP will return to the first interval and begin another sequence after the last interval is completed, and i n the SING LE CYCLE m ode it s tops aft er one sequ ence. During a c ycle or sequence, simple controls allow the user to stop the cycle, reset it to Interval 1, switch to the AUTO mode, or advance to the next interval. The DVSP can also be wired for remote operation by contact closure from a data system or other control device.
Each interval has one DPDT (double pole, double throw) relay, which provides two sets of contacts with no connection from one side to the other. This means that a single interval can be used to perform two separate functions requiring differing voltage requirements. For example, one side of relay A (Interval 1) can be used to switch an electr ic actuator (contact closure) while the other si de is connected to 110 VAC and switch es a 11 0 VAC sole noid valve
actuator.
second contac t. When solenoid valves are wired in serie s with this rel ay the result is "pulsed operation" of the air actuator, which avoids the potential valve and ac­tuato r p robl ems as s oc iat ed wit h co nti nu ou sl y-a pp lie d ai r p re ssu re.
In ad dition , Relay E (f unctiona l only i n the AUTO mode) s upplies a two
at the same time as the electric
Both 12 VDC and 110 VAC power s upplies are inclu ded withi n the DVSP, but the relays may be supplied from any external power source. For example, 24 VDC solenoid valves can be switched by the DVSP relays if the 24 volts is supplied to the re lays f r om a n external 24 V DC power su pply.
SPECIFICATIONS General
3-wire power cord (2 meters) Externally access ible 2A fuse 95-1 30 VAC, 25-60 H z 2 or 4 intervals; settable from 0 - 99 seconds, 0 - 0.9 minutes, or 0 - 99 minutes DPDT relay con tacts rate d at 3 am ps @1 20 VAC resistive load Elapsed time display
Dimensions
30 cm (11. 8") x 15 cm ( 6") x 6 c m (2. 4") Weight: 2 Kgm (4 lbs)
Accuracy
2.16 seconds/day maximum error
Temperature range
0 - 70°C
Power Consumption
110 VAC @ 50 mA 12 VDC @ 200 mA
1
2. IMPLEMENTATION
Before rem ovi ng the to p cov er of th e DVSP, make ce r t ain th a t th e p ower cord is unplugged.
Remove the two screws on the upper rear panel which secure the top cover. Look at
Figure 1
large printed circuit board. The terminals are grouped beside letters denoting re­lays A, B, C, and D, and are marked C for Common, NO for Normally Open, and
for Normally Closed . For convenience, the power lin e (fus ed and swi tched) is
NC
connec ted to two of the ter minals on the DVS P mother boa rd, label led
NEUT
to loc ate the two ba rrier t ermina l strips located ne ar the cent er of the
.
is the high side of the line and
HOT
is the low side.
NEUT
HOT
and
PIN FOR RE-
MOTE "RUN"
PIN FOR
REMOTE "STOP"
LOGIC
BOARD
PIN FO R REMOTE "GROUND"
PIN FO R REMOTE "+12"
Figure 1:
TERMINAL STRIPS
View of DVSP with cover removed
GRND
+12
HOLE FOR WIRING
NEUT HOT
For operat io n of devic es re qui rin g line vo ltage (1 am p max), one si de of t he devic e is conn ected direc tly to t he
ter minal and the
NEUT
is switch ed by the o utput
HOT
relays. For devices which operate on 12 VDC (300 mA max), voltage can be suppl ie d t o any of the r elay s w it h a si mp le j ump er co nn ect i on b et wee n t he t er m inal marked
and the Common te rmin al of the ta rget rel ay. (
12
Figure 2
) Any external power source can be connected to a Common in the same manner, with a hole provided in the rear panel to allow a passage for all the external wiring.
TERMINALS FOR ADDITIONAL RELAY WITH TWO SECOND CONTACT
The DVSP output relays are double pole, d ouble throw (D PDT), meanin g that they have two separate sets of contacts with no connection from one set to the other. One contact of each set is the common (C), which is connected to the normally
not
closed (NC) contact when the DVSP is
in the interval corresponding to that relay. As the DVSP enters each interval, the corresponding relay switches and connects the common (C) terminal to the normally open (NO) terminal, sending the current to the external device.
2
The tabl e below indica tes whic h grou p of ter minal s appl ies to each in ter val for the various DVSP models. In the drawings which illustrate the different wiring options, the terminal groupings are chosen purely for convenience: there is no intent in these drawings to convey any information about specific intervals.
2.1 Solenoid V alves
2.11 110 VA C
DVSP-2 Interval 1 Relay A
Interval 2 Relay C
DVSP-4 Interval 1 Relay A
Interval 2 Relay B Interval 3 Relay C Interval 4 Relay D
The steps described below are illustrated in
1. Supply 110 VAC by connecting the
Figure 2.
terminal to C of the appropriate
HOT
relay.
2. Connect one wire of the solenoid to the
NEUT
terminal.
3. Connect the other wire of the solenoi d to the normally open (NO) terminal of the relay which corresponds to the C of Step 1.
2.12 12 VDC
The steps described below are illustrated in
Figure 2.
12 VDC SOLE-
NOID
110 VAC SOLE-
NOID
1. Supply 12 VDC by connecting the
terminal to C of the ap-
+12
propriate relay.
2. Connect one wire of the sole­noid to the
GRND
terminal.
3. Connect the other wire of the solenoid to the normally open (NO) terminal of the relay which corresponds to the C of Step 1.
Figure 2:
12 VDC and 110 VAC solenoids
3
2.13 Valco MSVA
The MSVA is used wi th a two pos ition air actuator, whic h require s one interval to switch to the inject position and another to switch to the load position. The steps described below are illustrated in
Figure 3
.
1. Supply the proper voltage (110 VAC in this example) by connecting the
terminal to C of the one of the groups of
HOT
terminals to be used, and jumping it to C of the other.
2. Connect one wire of each solenoid to the
NEUT
terminal.
3. Connect the other wire of each solenoid to the NOs which correspond to the Cs of Step 1, according to the desired switching sequence.
Figure 3:
110 VAC Valco MSVA
2.14 Pulsed Operation of Solenoids
The first three procedures demonstrate the simplest uses of the DVSP. This example w ill illu strate th e use of the pulsed relay in conjunct ion with t wo devices on the same DPDT relay. The steps described below are illustrated in
1. Connect the two wires of the 12 VDC
12 VDC SOLE-
NOID
Figure 4.
solenoid as descri bed i n Sec tion 2. 12.
2. Connect one wire of the 110 VAC sole­noid to
as described in Section
NEUT
2.11, but connect the other wire to the
second
NO terminal of the
same
relay to which the 12 VDC solenoid is con­nected.
3. Supply 12 VDC by connecting the
+12
terminal to one of the NO terminals on the pulsed relay (
Figure 1
) and connecting that NO’s related Common to the Common of the NO which has the 12 VDC solenoid connected to it.
110 VAC SOLE-
NOID
4. Likewise, supply 110 VAC by connecting the
terminal to the remaining
HOT
NO
terminal on the pulsed relay and connecting that NO’s related Common to the Common of the NO which has the 110 VAC solenoid connected to it .
4
Figure 4:
two events on one relay
Use of the pulsed relay and
TERM IN AL S F OR EXTRA RELAY WITH TWO SEC­OND PULSE
2.2 Valco Electric Actuators
Multiposition actuators require only one event to step the valve/actuator to its next position. However, the two position actuator requires two intervals: one to switch the two position valve to its inject position and another to switch it to its load position.
2.21 Multiposition
GREY WIRE
WHITE WIRE
Figure 5 :
Valco multiposition electric actuator
BLACK WIRE
GREEN WIRE
RED WIRE
Figure 6:
Valco two position electric actuator
The steps below are illustrated in
Figure 5
.
1. Locate the two pairs of adjacent grey and white wires in t he interface cable supplied with the actuator. The relevant pair for this applica­tion is the one near the center of the ribbon cable.
2. Connect the grey (STEP) wire to the
NO
terminal of the appropriat e relay.
3. Connect the white (GRND) wire to C or the same relay.
2.22 Two position
The steps below are illustrated in
Figure 6
.
1. Locate the black, red, and green wires in the remote switching cable extending from the cover of the actuator.
2. Connect the black (INJECT) wire to the
NO
terminal of the appropriate relay for the de­sired interval.
3. Connect the red (LOAD) wire to the
NO
terminal of the relay corresponding to the interval where sample is to be loaded.
4. Connect the green (GRND) wire to the
ommon of one of the relays and use a
C
jumper to connect it to the Common of the other relay.
5
2.3 Valco Digital Valve Interf ace (DVI)
Two inter vals are req uire d with the DVI: one to signal it to move the valve to the inject position, and one to signal it to retu rn t o the l oad pos ition. The s teps des cribe d below are illustrated in
Figure 7
1. Connect the air actuator to the DVI as described in the DVI liter atur e.
2. Locate the blue, black, and red wires in the interface cable supplied with the DVI.
3. Connect the blue (INJECT) wire to the NO terminal of the appropriate relay for the desired interval.
4. Connect the black (LOAD) wire to the NO terminal of the relay corresponding to the interval where sample is to be loaded.
5. Connect the red (GRND) wire to the Common of one of the NOs used in Steps 3 and 4, and use a jumper to connect it to the Common of the other
.
NO
In routine operation the DVSP will control the switching of the valves, so manual control through the DVI will not be an issue. However, it is possible to allow the option of manually overriding the posi­tioning of valves switched by the DVI. To do this, the DVSP signal must be removed from the DVI remote cable by routing the DVI common (RED) through the pulsed relay, E. The signal from the DVSP is ap­plied for only two seconds and then removed, per­mitting subsequent manual valve positioning with the switch on the front of the DVI.
.
Figure 7:
DIGITAL VALVE
INTERFACE
BLUE WIRE
RED WIRE
BLACK WIRE
Valco Digital Valve Interface
6
Loading...
+ 17 hidden pages