VICI DVI User Manual

Page 1
Technical Note 411
Valco Instruments Co. Inc.
Implementation of the Digital Valve Interface (DVI)
NOTE: This technical note replaces the DVI man ual, and includes all the information except a schematic drawing. Call Valco if a copy of the schematic is required.
The V alco Digital V alv e Interface (D VI) is an electronic controller which uses CMOS integ rated circuitry to convert low power logic level signals or contact closures into pneumatic pulses for the operation of Valco two position air actuated valves. The DVI has two solenoids which correspond to the two posi­tions of the actuator, with the output air supplied through the one which is activ ated. The input signal determining which solenoid is activated may be sent manually with the toggle switch on the front panel, or the DVI can be connected to a data system’s timed outputs for automated valve switching.
The input signal to the D VI causes the interface circuitry to provide a two second pulse to the designated solenoid, driving the air actuator and valve to the indicated position. Upon removal of the first signal and application of a second, a two second pulse from the other solenoid drives the actuator to the other position. The result is that air pressure is applied to the actuator only during switching, eliminating the possibility of side-loading, misalignment, or other problems which can arise when torque is continu­ously applied to the valve. This “pulsed operation” procedure mimics valve switching by hand while providing the advantages of powered, automated operation.
The D VI also has leads to connect a remote LED position readout, for situations in which its o wn LEDs are out of sight inside an instrument or in a different building. In addition, two contact closures are provided for signalling the time of sample injections or for starting other devices, such as a gradient programmer or data system.
Installation
The Digital Valve Interface can be easily installed by the user with the following items supplied:
1. One plug-in transformer
2. One remote 10 pin flat cable (5 feet long) for interfacing with a data system
3. 5 feet of 1/8" plastic tubing for the air supply
4. The necessary fittings for air line installation
Mounting
Mounting dimensions are shown in Figure 1. The D VI f eatures a two-sided f ace/mounting plate which is factory-installed for mounting on the left side of the instrument panel. Howe ver , its design allows the option of removing four screws and the hex nut on the switch and re-installing the plate for mounting on the right side.
Page 2
1.75”
BLACK
LOAD RELAY
1.8” 3” 4”
2”
RED
BLUE
1.35”
2.75”
Figure 1: Mounting dimensions
Figure 2: Relay connections
INJECT RELAY
Basic Connections
1. Connect the air lines betw een the DVI and the air actuator as shown in Figure 3 on the back page.
2. Connect the air supply line to a regulated source of compressed air or nitrogen. (60-80 psi recom­mended, 100 psi maximum)
3. Connect the tr ansformer to the DVI as indicated, and plug it in.
Manual Operation
No additional installation is required for use of the three position switch on the front panel of the DVI. The manual switch will override automatic operation unless the operation is controlled by a single double throw relay.
Automatic Operation
The D VI can be controlled b y one doub le throw relay, two single throw relays, or remote negative true logic. The input signals to the DVI can be continuous or as short as fifty milliseconds. Any unused wires should be taped or tied out of the way.
One relay operation (double throw)
1. Connect the BLACK (LOAD) wire from the DVI to the Normally Closed (N.C.) relay contact.
2. Connect the RED (ground) wire to the Common (Com/Grnd) relay contact.
3. Connect the BLUE (INJECT) wire to the Normally Open (N.O.) relay contact.
Two relay operation
1. Connect the RED (ground) wire from the DVI to the common of both relays.
2. Connect the BLACK (LOAD) wire to the Normally Open (N.O.) contact of the relay designated for the LOAD position.
3. Connect the BLUE (INJECT) wire to the Normally Open (N.O.) contact of the relay designated for the INJECT position.
Page 3
Operation by Remote Negative True Logic
1. Connect the RED (logic g round) wire from the DVI to the logic ground of the timing device . (Consult its manual as necessary.)
2. Connect the BLACK (LOAD) wire from the DVI to the output chosen for the LOAD position.
3. Connect the BLUE (INJECT) wire from the DVI to the output chosen for the INJECT position.
Use of Remote LEDs
1.Connect the positive (+) leg of the LEDs to the grey wire of the interface cable.
2. Connect the other legs from the LEDs to the VIOLET wire for the LO AD indicator and to the GREEN wire for the INJECT indicator.
INPUT (LOAD)
CONTACT CLOSURE 2
LED DRIVE +
LED 2 (LOAD)
INPUT (INJECT)
LED 1 (INJECT)
CONTACT CLOSURE 1 CONTACT CLOSURE 2
LOGIC GROUND
CONTACT CLOSURE 1
BLACK WHITE
GREY VIOLET BLUE
GREEN YELLOW ORANGE RED BROWN
NOTE:
ALL INPUTS ARE 5 VOLT NEGATIVE TRUE LOGIC
1. INPUTS REQUIRE .5 MILLIAMPERES DRIVE
2. INPUTS MUST HAVE A CLOSURE TO LOGIC GROUND - (RED) TO ACTUATE
3.
DIGIT AL V AL VE
INTERF ACE (D VI)
CONNECTION FOR
LOAD POSITION
VALCO TWO POSITION
AIR ACTUATOR
CONNECTION FOR INJECT POSITION
POWER SUPPLY TRANSFORMER
Figure 3: D VI connections
North America, South America, and Australia/Oceania contact: Europe, Asia, and Africa contact:
®
Valco Instruments Co. Inc.
P. O. Box 55603 Houston, TX 77255 Sales toll-free (800) 367-8424 Technical help Fax (713) 688-8106
(713) 688-9345
valco@vici.com
®
VICI AG International
Parkstrasse 2 CH-6214 Schenkon Switzerland Phone (Int + 41 + 41) 925-6200
Cheminert® and VICI® are registered trademarks of Valco Instruments Co . Inc. and VICI AG
Fax (Int + 41 + 41) 925-6201 info@vici.ch
AIR IN (100 psi MAX)
TN-411 8/04
Loading...