Analog Input Process Meter
Instruction Manual
Viatran DL Series Analog Input Process Meter Instruction Manual
2
Disclaimer
The information contained in this document is subject to change without notice. Viatran makes no representations or warranties with respect to the contents hereof and specifically disclaims any implied warranties of merchantability or fitness for a particular purpose.
CAUTION: Read complete instructions prior to installation and operation of the meter.
WARNING: Risk of electric shock or personal injury.
Warning!
This product is not recommended for life support applications or applications where malfunctioning could result in personal injury or property loss. Anyone using this product for such applications does so at his/her own risk. Viatran Corporation shall not be held liable for damages resulting from such improper use.
Limited Warranty
Viatran warrants this product against defects in material or workmanship for the specified period under “Specifications” from the date of shipment from the factory. Viatran’s liability under this limited warranty shall not exceed the purchase value, repair, or replacement of the defective unit.
Registered Trademarks
All trademarks mentioned in this document are the property of their respective owners.
© 2016-2018 Viatran Corporation. All rights reserved.
www.viatran.com
!
Viatran DL Series Analog Input Process Meter Instruction Manual
3
Table of Contents
ABOUT VIATRAN ---------------------------------------------------------- 6 INTRODUCTION ------------------------------------------------------------ 6 ORDERING INFORMATION --------------------------------------------- 7 SPECIFICATIONS ---------------------------------------------------------- 8
General ------------------------------------------------------------------------------- 8 Process Input -------------------------------------------------------------------- 10 Relays ------------------------------------------------------------------------------ 11 Isolated 4-20 mA Transmitter Output ------------------------------------ 12 Modbus® RTU Serial Communications ---------------------------------- 12 COMPLIANCE INFORMATION ---------------------------------------------- 13 Safety ------------------------------------------------------------------------------- 13 Electromagnetic Compatibility --------------------------------------------- 13
SAFETY INFORMATION ------------------------------------------------ 14 INSTALLATION ------------------------------------------------------------ 14
Unpacking ------------------------------------------------------------------------- 14 Panel Mounting Instructions ------------------------------------------------ 15
Mounting Dimensions ------------------------------------------------------- 16
Configuration for 12 or 24 VDC Power Option ------------------------ 17 Transmitter Supply Voltage Selection (P+, P-) ----------------------- 18 Connections ---------------------------------------------------------------------- 18
Connectors Labeling --------------------------------------------------------- 19 Power Connections ---------------------------------------------------------- 19 Signal Connections ---------------------------------------------------------- 20 Modbus RTU Serial Communications ----------------------------------- 21 Relay Connections ----------------------------------------------------------- 21 Switching Inductive Loads -------------------------------------------------- 22 F4 Digital Input Connections ----------------------------------------------- 23 4-20 mA Output Connections ---------------------------------------------- 23 Analog Output Transmitter Power Supply ------------------------------ 23 External Relays & Digital I/O Connections ----------------------------- 24 Interlock Relay Feature ----------------------------------------------------- 25
SETUP AND PROGRAMMING ---------------------------------------- 26
Front Panel Buttons and Status LED Indicators --------------------- 27 Display Functions & Messages -------------------------------------------- 28 Main Menu ------------------------------------------------------------------------ 31 Setting Numeric Values ------------------------------------------------------ 32 Setting Up the Meter (setup) ------------------------------------------------ 33
Viatran DL Series Analog Input Process Meter Instruction Manual
4
Setting the Input Signal (Input) ------------------------------------------ 34 Setting the Input Units or Custom Tags (units) ---------------------- 35 Setting the Decimal Point (dEc pt) -------------------------------------- 36 Programming the Meter (prog) ------------------------------------------- 37
Program Menu for Single Scale Process --------------------------- 37 Program Menu for Dual-Scale Level Applications ---------------- 37 Multi-Point Calibration & Scaling -------------------------------------- 38 MeterView® Pro Software ----------------------------------------------- 38 Scaling the Meter (SCALE) ---------------------------------------------- 38 Dual-Scale for Level Application -------------------------------------- 39
Calibrating the Meter with External Source (Cal) ----------------- 41 Setting the Display Parameter & Intensity (dsplay) ----------------- 42 Display Setup Menu --------------------------------------------------------- 43
Setting the Relay Operation (relay) ------------------------------------- 44
Setting the Relay Action ---------------------------------------------------- 45 Programming Set and Reset Points ------------------------------------- 46 Setting Fail-Safe Operation ------------------------------------------------ 46 Programming Time Delay -------------------------------------------------- 46 Relay Action for Loss of 4-20 mA Input (Loop Break) --------------- 46
Relay and Alarm Operation Diagrams ----------------------------------- 47
High Alarm Operation (Set > Reset) ------------------------------------- 47 Low Alarm Operation (Set < Reset) -------------------------------------- 48 High Alarm with Fail-Safe Operation (Set > Reset) ------------------ 49 Low Alarm with Fail-Safe Operation (Set < Reset) ------------------- 50 Pump Alternation Control Operation ------------------------------------- 51 Relay Sampling Operation ------------------------------------------------- 52 Signal Loss or Loop Break Relay Operation --------------------------- 53 Time Delay Operation ------------------------------------------------------- 54
Relay Operation Details ------------------------------------------------------ 55
Overview ------------------------------------------------------------------------ 55 Relays Auto Initialization ---------------------------------------------------- 55 Fail-Safe Operation ---------------------------------------------------------- 55 Front Panel LEDs ------------------------------------------------------------- 56 Latching and Non-Latching Relay Operation -------------------------- 56 Non-Latching Relay (Auto) ------------------------------------------------- 57 Non-Latching Relay (A-man) -------------------------------------------- 57 Latching Relay (LatcH) ----------------------------------------------------- 57 Latching Relay (Lt-Clr) ---------------------------------------------------- 58 Acknowledging Relays ------------------------------------------------------ 58 Pump Alternation Control Applications (Altern) --------------------- 59 Setting Up the Interlock Relay (Force On) Feature ------------------ 62
Scaling the 4-20 mA Analog Output (Aout) ---------------------------- 63
Viatran DL Series Analog Input Process Meter Instruction Manual
5
Reset Menu (reset) ------------------------------------------------------------ 64 Control Menu (Contrl) -------------------------------------------------------- 64 Setting Up the Password (pass) ------------------------------------------- 65
Protecting or Locking the Meter ------------------------------------------- 65 Making Changes to a Password Protected Meter -------------------- 66 Disabling Password Protection -------------------------------------------- 66
Advanced Features Menu ---------------------------------------------------- 67
Advanced Features Menu & Display Messages ---------------------- 68 Noise Filter (filter) -------------------------------------------------------- 71 Noise Filter Bypass (bypass) ---------------------------------------------- 71 Rounding Feature (round) ------------------------------------------------- 71 Modbus RTU Serial Communications (serial) ---------------------- 72 Select Menu (SElect) ------------------------------------------------------- 73 Signal Input Conditioning (Functn) -------------------------------------- 73 Low-Flow Cutoff (CutofF) -------------------------------------------------- 76 Analog Output Programming (AoutPr) ---------------------------------- 76 Programmable Function Keys User Menu (user) -------------------- 77 Tare (tare) --------------------------------------------------------------------- 78 Internal Source Calibration (ICAL) --------------------------------------- 78
METER OPERATION ----------------------------------------------------- 81
Front Panel Buttons Operation -------------------------------------------- 81 Function Keys Operation ---------------------------------------------------- 81 F4 Operation --------------------------------------------------------------------- 82 Maximum/Minimum Readings ---------------------------------------------- 82
TROUBLESHOOTING ---------------------------------------------------- 83
Diagnostics Menu (diag) ----------------------------------------------------- 83
Determining Software Version -------------------------------------------- 83
Reset Meter to Factory Defaults ------------------------------------------- 84
Factory Defaults & User Settings ----------------------------------------- 85
Troubleshooting Tips --------------------------------------------------------- 88
Table of Figures
Figure 1. 1/8 DIN Panel Cutout Dimensions ..................................... 15
Figure 2. Panel Mounting Details ...................................................... 15
Figure 3. Meter Dimensions - Side View ........................................... 16
Figure 4. Meter Dimensions - Top View ............................................ 16
Figure 5. Jumper Configuration for 12/24 VDC Power .................... 17
Figure 6. Transmitter Supply Voltage Selection .............................. 18
Figure 7. Connector Labeling for Fully Loaded Meter ..................... 19
Figure 8. Power Connections ............................................................ 19
Viatran DL Series Analog Input Process Meter Instruction Manual
6
Figure 9. Transmitters Powered by Internal Supply ........................ 20
Figure 10. Transmitter Powered by Ext. Supply or Self-Powered .. 20
Figure 11. Voltage Input Connections .............................................. 21
Figure 12. Relay Connections ........................................................... 21
Figure 13. AC and DC Loads Protection ........................................... 22
Figure 14. Low Voltage DC Loads Protection .................................. 22
Figure 15. F4 Digital Input Connections ........................................... 23
Figure 16. 4-20 mA Output Connections .......................................... 23
Figure 17. Expansion Modules & DIN Rail Mounting Kit ................. 24
Figure 18. External Relays Module Connections ............................. 24
Figure 19. Digital I/O Module Connections ....................................... 25
Figure 20. Interlock Connections ...................................................... 25
Figure 21. Acknowledge Relays w/Function Key or Digital Input .. 58
Figure 22. 1/8 DIN Panel Cutout Template ........................................ 89
ABOUT VIATRAN
Established in 1965, Viatran has over 50 years of experience in providing solutions for pressure and level measurement. Based in Wheatfield, NY, the company is a worldwide leading supplier of pressure transducers and transmitters in a wide range of industries, including automotive, oil and gas as well as the test stand, fluid power, food and beverage industries. For more information about Viatran, visit our Web site at www.viatran.com.
INTRODUCTION
The DL series analog input process meter is a multi-purpose, easy-to-use digital process meter ideal for level, flow rate, temperature, or pressure transmitter applications. It accepts current and voltage signals (e.g. 4-20 mA, 0-10 V). Three of the front panel buttons can be custom-programmed for a specific operation. The analog input can be scaled to display the process in two different scales; for example, the main display could indicate level in feet and the second display could indicate the volume in gallons.
The basic model includes an isolated 24 VDC transmitter power supply that can be used to power the input transmitter or other devices. An additional isolated 24 VDC power supply is included with the 4-20 mA output option. A digital input is standard.
A fully loaded meter has the following: four SPDT relays, 4-20 mA output, and two 24 VDC power supplies. Its capabilities may be enhanced by adding the following external expansion modules: four SPST relays (creating an eight-relay process meter), two digital I/O modules with four inputs and four outputs each, and USB, RS-232 or RS-485 communication adapters.
The eight relays can be used for alarm indication or process control applications such as pump alternation control. The 4-20 mA isolated output, Modbus RTU serial communications, and digital I/O options make it an excellent addition to any system.
Viatran DL Series Analog Input Process Meter Instruction Manual
7
ORDERING INFORMATION
Standard Models
85-265 VAC Model
12/24 VDC Model
Options Installed
DL-ACS0N DL-DCS0N No options DL-ACS2N DL-DCS2N 2 relays DL-ACS0R DL-DCS0R 4-20 mA output DL-ACS4N DL-DCS4N 4 relays DL-ACS2R DL-DCS2R 2 relays & 4-20 mA output DL-ACS4R DL-DCS4R 4 relays & 4-20 mA output
Sunlight Readable Display Models
85-265 VAC Model
12/24 VDC Model
Options Installed
DL-ACB0N DL-DCB0N No options DL-ACB2N DL-DCB2N 2 relays DL-ACB0R DL-DCB0R 4-20 mA output DL-ACB4N DL-DCB4N 4 relays DL-ACB2R DL-DCB2R 2 relays & 4-20 mA output DL-ACB4R DL-DCB4R 4 relays & 4-20 mA output
Accessories
Model Description
350PDA1002 DIN rail mounting kit for two expansion modules 350PDA1004 4 SPST (Form A) relays 350PDA1044 4 digital inputs & 4 digital outputs (2 may be connected) 350PDA1232 RS-232 serial adapter 350PDA1485 RS-485 serial adapter 350PDA7485-I RS-232 to RS-422/485 isolated converter 350PDA7485-N RS-232 to RS-422/485 non-isolated converter 350PDA8008 USB serial adapter 350PDA8232-N USB to RS-232 non-isolated converter 350PDA8485-I USB to RS-422/485 isolated converter 350PDA8485-N USB to RS-422/485 non-isolated converter 350PDX6901
Suppressor (snubber): 0.01 µF/470 Ω, 250 VAC
Enclosures
Model Description
350PDA2811 1 Meter Plastic NEMA 4X Enclosure 350PDA2812 2 Meter Plastic NEMA 4X Enclosure
Viatran DL Series Analog Input Process Meter Instruction Manual
8
SPECIFICATIONS
Except where noted all specifications apply to operation at +25°C.
General
DISPLAY Main display: 0.60" (15 mm) high, red LEDs
Second display: 0.46" (12 mm) high, red LEDs 6 digits each (-99999 to 999999), with lead zero blanking
DISPLAY INTENSITY
Eight user selectable intensity levels
DISPLAY UPDATE RATE
5/second (200 ms)
OVERRANGE
Display flashes
999999
UNDERRANGE
Display flashes
-99999
DISPLAY ASSIGNMENT
The main (Big) and small (Little) displays may be assigned to PV1, PV2, PCT, d r-u, d gross, d nt-g, max/min, max & min, set points, units (small display only), or Modbus input.
PROGRAMMING METHODS
Four front panel buttons, digital inputs, PC and MeterView Pro software, or Modbus registers.
NOISE FILTER Programmable from 2 to 199 (0 will disable filter)
FILTER BYPASS Programmable from 0.1 to 99.9% of calibrated span
RECALIBRATION All ranges are calibrated at the factory. Recalibration is
recommended at least every 12 months.
MAX/MIN DISPLAY
Max/min readings reached by the process are stored until reset by the user or until power to the meter is turned off.
PASSWORD
Three programmable passwords restrict modification of programmed settings.
Pass 1: Allows use of function keys and digital inputs Pass 2: Allows use of function keys, digital inputs and editing set/reset points Pass 3: Restricts all programming, function keys, and digital inputs.
POWER OPTIONS
85-265 VAC 50/60 Hz, 90-265 VDC, 20 W max or jumper selectable 12/24 VDC ± 10%, 15 W max
ISOLATED TRANSMITTER POWER SUPPLY
Terminals P+ & P-: 24 VDC ± 10%. 12/24 VDC powered models selectable for 24, 10, or 5 VDC supply (internal jumper J4). 85-265 VAC models rated @ 200 mA max, 12/24 VDC powered models rated @ 100 mA max, @ 50 mA max for 5 or 10 VDC supply.
NON-VOLATILE MEMORY
All programmed settings are stored in non-volatile memory for a minimum of ten years if power is lost.
FUSE Required external fuse: UL Recognized, 5 A max, slow
blow; up to 6 meters may share one 5 A fuse
Viatran DL Series Analog Input Process Meter Instruction Manual
9
NORMAL MODE REJECTION
Greater than 60 dB at 50/60 Hz
ISOLATION 4 kV input/output-to-power line
500 V input-to-output or output-to-P+ supply
OVERVOLTAGE CATEGORY
Installation Overvoltage Category II: Local level with smaller transient overvoltages than Installation Overvoltage Category III.
ENVIRONMENTAL Operating temperature range: -40 to 65°C
Storage temperature range: -40 to 85°C Relative humidity: 0 to 90% non-condensing
CONNECTIONS Removable screw terminal blocks accept 12 to 22 AWG
wire, RJ45 for external relays, digital I/O, and serial communication adapters.
ENCLOSURE 1/8 DIN, high impact plastic, UL 94V-0, color: black
MOUNTING 1/8 DIN panel cutout required:
3.622" x 1.772" (92 mm x 45 mm) Two panel mounting bracket assemblies are provided.
TIGHTENING TORQUE
Screw terminal connectors: 5 lb-in (0.56 Nm)
OVERALL DIMENSIONS
4.68" x 2.45" x 5.64" (119 mm x 62 mm x 143 mm) (W x H x D)
WEIGHT 9.5 oz (269 g)
WARRANTY 3 years parts & labor
Viatran DL Series Analog Input Process Meter Instruction Manual
10
Process Input
INPUTS Field selectable:
0-20, 4-20 mA, ±10 V (0-5, 1-5, 0-10 V), Modbus PV (Slave)
ACCURACY ±0.03% of calibrated span ±1 count,
square root & programmable exponent accuracy range: 10-100% of calibrated span
TEMPERATURE DRIFT
0.005% of calibrated span/°C max from 0 to 65°C ambient,
0.01% of calibrated span/°C max from -40 to 0°C ambient
SIGNAL INPUT CONDITIONING
Linear, square root, programmable exponent, or round horizontal tank volume calculation
MULTI-POINT LINEARIZATION
2 to 32 points for PV or PV1 2 to 8 points for PV2 (Dual-scale Level feature)
PROGRAMMA­BLE EXPONENT
1.0001 to 2.9999
ROUND H TANK Diameter & Length: 999.999 inch or cm calculates volume
in gallons or liters respectively.
LOW-FLOW CUTOFF
0-999999 (0 disables cutoff function)
DECIMAL POINT Up to five decimal places or none:
d.ddddd, d.dddd, d.ddd, d.dd, d.d, or dddddd
CALIBRATION RANGE Input Range
Minimum Span Input 1 & Input 2
4-20 mA 0.15 mA ±10 V 0.01 V
An error message will appear if the input 1 and input 2 signals are too close together.
INPUT IMPEDANCE
Voltage ranges: greater than 500 kΩ Current ranges: 50 - 100 Ω
(depending on resettable fuse impedance)
INPUT OVERLOAD
Current input protected by resettable fuse, 30 VDC max. Fuse resets automatically after fault is removed.
F4 DIGITAL INPUT CONTACTS
3.3 VDC on contact. Connect normally open contacts across F4 to COM.
F4 DIGITAL INPUT LOGIC LEVELS
Logic High: 3 to 5 VDC Logic Low: 0 to 1.25 VDC
Viatran DL Series Analog Input Process Meter Instruction Manual
11
Relays
RATING 2 or 4 SPDT (Form C) internal and/or 4 SPST (Form A)
external; rated 3 A @ 30 VDC and 125/250 VAC resistive load; 1/14 HP ( 50 W) @ 125/250 VAC for inductive loads
NOISE SUPPRESSION
Noise suppression is recommended for each relay contact switching inductive loads; see page 22 for details.
DEADBAND 0-100% of span, user programmable
HIGH OR LOW ALARM
User may program any alarm for high or low trip point. Unused alarm LEDs and relays may be disabled (turn off).
RELAY OPERATION
Automatic (non-latching) and/or manual reset Latching (requires manual acknowledge) with/without clear Pump alternation control (2 to 8 relays) Sampling (based on time) Off (disable unused relays and enable Interlock feature) Manual on/off control mode
TIME DELAY
0 to 999.9 seconds, on & off relay time delays Programmable and independent for each relay
AUTO INITIALIZATION
When power is applied to the meter, relays will reflect the state of the input to the meter.
RELAY RESET User selectable via front panel buttons or digital inputs
1. Automatic reset only (non-latching), when the input passes the reset point.
2. Automatic + manual reset at any time (non-latching)
3. Manual reset only, at any time (latching)
4. Manual reset only after alarm condition has cleared (latching)
Note: Front panel button or digital input may be assigned to
acknowledge relays programmed for manual reset.
FAIL-SAFE OPERATION
Programmable and independent for each relay.
Note: Relay coil is energized in non-alarm condition.
In case of power failure, relay will go to alarm state.
Viatran DL Series Analog Input Process Meter Instruction Manual
12
Isolated 4-20 mA Transmitter Output
OUTPUT SOURCE
Process variable (PV), max, min, set points 1-8, Modbus input, or manual control mode
SCALING RANGE 1.000 to 23.000 mA for any display range
CALIBRATION Factory calibrated: 4.000 to 20.000 = 4-20 mA output
ANALOG OUT PROGRAMMING
23.000 mA maximum for all parameters:
Overrange, underrange, max, min, and break
ACCURACY ± 0.1% of span ± 0.004 mA
TEMPERATURE DRIFT
0.4 µA/°C max from 0 to 65°C ambient,
0.8 µA/°C max from -40 to 0°C ambient
Note: Analog output drift is separate from input drift.
ISOLATED TRANSMITTER POWER SUPPLY
Terminals I+ & R: 24 VDC ± 10%. May be used to power the 4-20 mA output or other devices. Refer to Figure 5 on page 17 and Figure 16 on page 23.
All models rated @ 40 mA max.
EXTERNAL LOOP POWER SUPPLY
35 VDC maximum
OUTPUT LOOP RESISTANCE
Power supply Minimum Maximum
24 VDC 10 Ω 700 Ω
35 VDC (external) 100 Ω 1200 Ω
Modbus® RTU Serial Communications
SLAVE ID 1 – 247 (Meter address)
BAUD RATE 300 – 19,200 bps
TRANSMIT TIME DELAY
Programmable between 0 and 199 ms
DATA 8 bit (1 start bit, 1 or 2 stop bits)
PARITY Even, Odd, or None with 1 or 2 stop bits
BYTE-TO-BYTE TIMEOUT
0.01 – 2.54 second
TURN AROUND DELAY
Less than 2 ms (fixed)
Note: Refer to the Modbus Register Tables located at www.viatran.com for details.
Viatran DL Series Analog Input Process Meter Instruction Manual
13
COMPLIANCE INFORMATION Safety
UL & c-UL LISTED USA & Canada
UL 508 Industrial Control Equipment
UL FILE NUMBER E160849
FRONT PANEL UL Type 4X, NEMA 4X, IP65; panel gasket provided
LOW VOLTAGE DIRECTIVE
EN 61010-1:2010 Safety requirements for measurement, control, and laboratory use
Electromagnetic Compatibility
EMISSIONS
EN 55022:2010 Class A ITE emissions requirements
Radiated Emissions
Class A
AC Mains Conducted Emissions
Class A
IMMUNITY
EN 61326-1:2013 Measurement, control, and laboratory equipment
EN 61000-6-2:2005 EMC heavy industrial generic immunity standard
RFI - Amplitude Modulated
80 -1000 MHz 10 V/m 80% AM (1 kHz)
1.4 - 2.0 GHz 3 V/m 80% AM (1 kHz)
2.0 - 2.7 GHz 1 V/m 80% AM (1 kHz)
Electrical Fast Transients
±2kV AC mains, ±1kV other
Electrostatic Discharge
±4kV contact, ±8kV air
RFI - Conducted
10V, 0.15-80 MHz, 1kHz 80% AM
AC Surge
±2kV Common, ±1kV Differential
Surge
1KV (CM)
Power-Frequency Magnetic Field
30 A/m 70%V for 0.5 period
Voltage Dips
40%V for 5 & 50 periods 70%V for 25 periods
Voltage Interruptions
<5%V for 250 periods
Viatran DL Series Analog Input Process Meter Instruction Manual
14
Note:
Testing was conducted on DL series meters installed through the covers of grounded metal enclosures with cable shields grounded at the point of entry representing installations designed to optimize EMC performance.
Declaration of Conformity available at www.viatran.com
SAFETY INFORMATION
CAUTION: Read complete
instructions prior to installation and operation of the meter.
WARNING: Risk of electric shock or personal injury.
Warning!
Hazardous voltages exist within enclosure. Installation and service should be performed only by trained service personnel.
INSTALLATION
There is no need to remove the meter from its case to complete the installation, wiring, and setup of the meter for most applications.
Instructions are provided for setting up a 12/24 VDC powered meter to operate from 12 VDC and for changing the transmitter power supply to output 5 or 10 VDC instead of 24 VDC, see page 17.
Unpacking
Remove the meter from box. Inspect the packaging and contents for damage. Report damages, if any, to the carrier.
If any part is missing or the meter malfunctions, please contact your supplier or the factory for assistance.
!
Viatran DL Series Analog Input Process Meter Instruction Manual
15
Panel Mounting Instructions
Prepare a standard 1/8 DIN panel cutout – 3.622" x 1.772" (92 mm x 45 mm). Refer to Figure 1 below, for more details.
Clearance: allow at least 6.0" (152 mm) behind the panel for wiring.
Panel thickness: 0.04" - 0.25" (1.0 mm - 6.4 mm).
Recommended minimum panel thickness to maintain Type 4X rating: 0.06" (1.5 mm) steel panel, 0.16" (4.1 mm) plastic panel.
Remove the two mounting brackets provided with the meter (back-off the two screws so that there is ¼" (6.4 mm) or less through the bracket. Slide the bracket toward the front of the case and remove).
Insert meter into the panel cutout.
Install mounting brackets and tighten the screws against the panel. To
achieve a proper seal, tighten the mounting bracket screws evenly until meter is snug to the panel along its short side. DO NOT OVER TIGHTEN, as the rear of the panel may be damaged.
Figure 1. 1/8 DIN Panel Cutout Dimensions
Figure 2. Panel Mounting Details
Panel
Gasket
Mounting
Bracket
Mounting
Screw
Removable Connectors
3.622" (92 mm)
1.772"
(45mm)
Panel Cutout to DIN 43700
Square Corners to 0.060"
(1.5mm) Max Radius
A
B
Tolerances:
A
: +0.032 (+0.8mm)
-0.000 (-0.0mm)
B: +0.024 (+0.6mm)
-0.000 (-0.0mm)
Refer to page 16 for mounting dimensions
Viatran DL Series Analog Input Process Meter Instruction Manual
16
Mounting Dimensions
Figure 3. Meter Dimensions - Side View
Figure 4. Meter Dimensions - Top View
N
O
N
C
N
C
C
N
O
C
N
O
N
C
N
C
C
N
O
C
+
-
R
Viatran DL Series Analog Input Process Meter Instruction Manual
17
Configuration for 12 or 24 VDC Power Option
Warning!
Do not exceed voltage rating of the selected configuration.
Meters equipped with the 12/24 VDC power option are shipped from the factory ready to operate from 24 VDC.
To configure the meter for 12 VDC power:
1. Remove all the connectors.
2. Unscrew the back cover.
3. Slide the back cover about 1 inch.
4. Configure the J9 jumper, located behind the power connector, for 12 V as shown below.
Figure 5. Jumper Configuration for 12/24 VDC Power
MAIN BOARD
24 VDC 12 VDC POWER
J9
12 V
24 V
J9 CONFIGURATION
Factory Default
M-LINK
+ _
Viatran DL Series Analog Input Process Meter Instruction Manual
18
Transmitter Supply Voltage Selection (P+, P-)
All meters, including models equipped with the 12/24 VDC power option, are shipped from the factory configured to provide 24 VDC power for the transmitter or sensor.
If the transmitter requires 5 or 10 VDC excitation, the internal jumper J4 must be configured accordingly.
To access the voltage selection jumper:
1. Remove all the wiring connectors.
2. Unscrew the back cover.
3. Slide out the back cover by about 1 inch.
4. Configure the J4 jumper, located behind the input signal connector, for the desired excitation voltage as shown.
Figure 6. Transmitter Supply Voltage Selection
Connections
All connections are made to removable screw terminal connectors located at the rear of the meter.
Use copper wire with 60°C or 60/75°C insulation for all line voltage connections. Observe all safety regulations. Electrical wiring should be performed in accordance with all applicable national, state, and local codes to prevent damage to the meter and ensure personnel safety.
Viatran DL Series Analog Input Process Meter Instruction Manual
19
Connectors Labeling
The connectors’ label, affixed to the meter, shows the location of all connectors available with requested configuration.
Warning!
Do not connect any equipment other than Viatran’s expansion modules, cables, or meters to the RJ45 M-LINK connector. Otherwise damage will occur to the equipment and the meter.
Figure 7. Connector Labeling for Fully Loaded Meter
Power Connections
Power connections are made to a two-terminal connector labeled POWER on Figure 7 on page 19. The meter will operate regardless of DC polarity connection. The + and - symbols are only a suggested wiring convention.
Figure 8. Power Connections
AC or DC
POWER
Required External Fuse:
5 A max, 250 V Slow Blow
POWER
+
-
Viatran DL Series Analog Input Process Meter Instruction Manual
20
Signal Connections
Signal connections are made to a six-terminal connector labeled SIGNAL on Figure 7. The COM (common) terminal is the return for the
4-20 mA and the ±10 V input signals.
Current and Voltage Connections
The following figures show examples of current and voltage connections. There are no switches or jumpers to set up for current and voltage inputs.
Setup and programming is performed through the front panel buttons.
Figure 9. Transmitters Powered by Internal Supply
Figure 10. Transmitter Powered by Ext. Supply or Self-Powered
The current input is protected against current overload by a resettable fuse. The display may or may not show a fault condition depending on the nature of the overload.
The fuse limits the current to a safe level when it detects a fault condition, and automatically resets itself when the fault condition is removed.
Viatran DL Series Analog Input Process Meter Instruction Manual
21
Figure 11. Voltage Input Connections
The meter is capable of accepting any voltage from -10 VDC to +10 VDC.
Modbus RTU Serial Communications
Serial communications connection is made to an RJ45 connector labeled M-LINK on Figure 7. For interfacing to the meter, use the 350PDA1232 for RS-232, the 350PDA1485 for RS-485, or the 350PDA8008 for USB. The same port is used for interfacing with all expansion modules (e.g. external relays, digital I/O).
Relay Connections
Relay connections are made to two six-terminal connectors labeled RELAY1 – RELAY4 on Figure 7. Each relay’s C terminal is common only to the normally open (NO) and normally closed (NC) contacts of the corresponding relay. The relays’ C terminals should not be confused with the COM (common) terminal of the INPUT SIGNAL connector.
Figure 12. Relay Connections
CNONO NC NC C
RELAY4 RELAY3
4365 21
CNONO NC NC C
RELAY2 RELAY1
4365 21
Viatran DL Series Analog Input Process Meter Instruction Manual
22
Switching Inductive Loads
The use of suppressors (snubbers) is strongly recommended when switching inductive loads to prevent disrupting the microprocessor’s operation. The suppressors also prolong the life of the relay contacts. Suppression can be obtained with resistor-capacitor (RC) networks assembled by the user or purchased as complete assemblies. Refer to the following circuits for RC network assembly and installation:
Figure 13. AC and DC Loads Protection
Choose R and C as follows: R: 0.5 to 1 for each volt across the contacts C: 0.5 to 1 µF for each amp through closed contacts
Notes:
1. Use capacitors rated for 250 VAC.
2. RC networks may affect load release time of solenoid loads. Check to confirm proper operation.
3. Install the RC network at the meter's relay screw terminals. An RC network may also be installed across the load. Experiment for best results.
Figure 14. Low Voltage DC Loads Protection
RC Networks Available from Viatran
RC networks are available from Viatran and should be applied to each relay contact switching an inductive load. Part number: PDX6901.
Note:
Relays are de-rated to 1/14th HP (50 watts) with an inductive load.
C
R
C
R
Use a diode with a reverse breakdown voltage two to three times the circuit voltage and forward current at least as large as the load current.
Viatran DL Series Analog Input Process Meter Instruction Manual
23
F4 Digital Input Connections
A digital input, F4, is standard on the meter. This digital input is connected with a normally open contact across F4 and COM, or with an active low signal applied to F4.
Figure 15. F4 Digital Input Connections
4-20 mA Output Connections
Connections for the 4-20 mA transmitter output are made to the connector terminals labeled MA OUT. The 4-20 mA output may be powered internally or from an external power supply.
Figure 16. 4-20 mA Output Connections
Analog Output Transmitter Power Supply
The internal 24 VDC power supply powering the analog output may be used to power other devices, if the analog output is not used. The I+ terminal is the +24 V and the R terminal is the return.
12-35 VDC
Power Supply
+
4-20 mA
Input Meter
-
+
RI- I+
132
RELAY1
321
24 V
-
4-20 mA Input
Remote Display,
Chart Recorder, Etc.
-
+
RI- I+
MA OUT
132
RELAY1
321
24 V
MA OUT
Viatran DL Series Analog Input Process Meter Instruction Manual
24
External Relays & Digital I/O Connections
The relay and the digital I/O expansion modules 350PDA1004 & 350PDA1044 are connected to the meter using a CAT5 cable provided with each module. The two RJ45 connectors on the expansion modules are identical and interchangeable; they are used to connect additional modules to the system.
Note: The jumper located between the RJ45 connectors of the
350PDA1044 must be removed on the second digital I/O module in order for the system to recognize it as module #2.
Warning!
Do not connect or disconnect the expansion modules with the power on!
More detailed instructions are provided with each optional expansion module.
Figure 17. Expansion Modules & DIN Rail Mounting Kit
Figure 18. External Relays Module Connections
12
RLY5 RLY6 RLY7 RLY8
345 678
NO C NO C NO C NO C
Viatran DL Series Analog Input Process Meter Instruction Manual
25
Figure 19. Digital I/O Module Connections
Interlock Relay Feature
As the name implies, the interlock relay feature reassigns one, or more, alarm/control relays for use as interlock relay(s). Interlock contact(s) are wired to digital input(s) and trigger the interlock relay. This feature is enabled by configuring the relay, and relative digital input(s) (see page
62). In one example, dry interlock contacts are connected in series to
one digital input which will be used to force on (energize) the assigned interlock power relay when all interlock contacts are closed (safe). The interlock relay front panel LED flashes when locked out. The interlock relay would be wired in-series with the load (N/O contact). See below.
Figure 20. Interlock Connections
123456
+5 I1 I2 I3 I4 O1
78
O2 O3
910
O4 G
DI 1-4 DO 1-4
5 VDC GND
Viatran DL Series Analog Input Process Meter Instruction Manual
26
SETUP AND PROGRAMMING
The meter is factory calibrated prior to shipment to read in milliamps and volts depending on the input selection. The calibration equipment is certified to NIST standards.
Overview
There are no jumpers to set for the meter input selection. Setup and programming is done through the front panel buttons. After power and input signal connections have been completed and
verified, apply power to the meter.
Viatran DL Series Analog Input Process Meter Instruction Manual
27
Front Panel Buttons and Status LED Indicators
Press the Menu button to enter or exit the Programming Mode at any time.
Press the Right arrow button to move to the next digit during digit or decimal point programming.
Press or hold the Up arrow button to scroll through the menus, decimal point, or to increment the value of a digit.
Press the Enter button to access a menu or to accept a setting.
Press and hold the Menu button for three seconds to access the
advanced features of the meter.
Button Symbol
Description LED Status
Menu
1-8 Alarm 1-8 indicator
Right arrow/F1
1-8 M
Flashing: Relay in manual control mode
Up arrow/F2
T Flashing: Tare
Enter/F3
1-8
Flashing: Relay interlock switch open
Note: F4 is a digital input. Alarms 5-8
are enabled when relay expansion module is installed.
Note: LEDs for relays in manual mode
flash with the “M” LED every 10 seconds. “M” flashing by itself indicates Aout – manual control is used.
Viatran DL Series Analog Input Process Meter Instruction Manual
28
Display Functions & Messages
The meter displays various functions and messages during setup, programming, and operation. The following table shows the main menu functions and messages in the order they appear in the menu.
Display Parameter Action/Setting Description
setup
Setup
Enter Setup menu
Input
Input
Enter Input selection menu
mA
4-20 mA
Set meter for 4-20 mA input
volt
0-10 VDC
Set meter for ±10 VDC input
d-SCAL
Dual-scale
Press Enter to select dual-scale display for some level applications (Select Yes or No)
units
Units
Select the display units/tags
Dec pt
Decimal point
Set decimal point
Pv 1
PV1
PV1 decimal point (Level)
Pv 2
PV2
PV2 decimal point (Level)
prog
Program
Enter the Program menu
SCALE
Scale
Enter the Scale menu
SCAL 1
Scale 1
Enter the Scale menu for PV1
SCAL 2
Scale 2
Enter the Scale menu for PV2
Cal
Calibrate
Enter the Calibration menu
Inp 1
Input 1
Calibrate input 1 signal or program input 1 value
Dis 1
Display 1
Program display 1 value
Inp 2
Input 2
Calibrate input 2 signal or program input 2 value (up to 32 points)
Dis 2
Display 2
Program display 2 value (up to 32 points)
Error
Error
Error, calibration not successful, check signal or programmed value
dsplay
Display
Enter the Display menu
big
Big display
Press Enter to assign the Main display parameter (default: PV)
Little
Little display
Press Enter to assign the small display parameter (default: engineering units)