SAVE THIS BOOK
This book is valuable. In addition to instructing you
on how to install and maintain your appliance, it also
contains information that will enable you to obtain replacement parts or accessory items when needed. Keep
it with your other important papers.
This fireplace is approved for use as a wood burning fireplace or for use with a vented gas log approved to ANS
Z21.60 or Z21.84 standards or for use with a vent-free gas
log heater approved to ANS Z21.1 1.2 standard. A hood must
be installed when using a vent-free log heater (see , page
18).
This wood burning fireplace complies with UL127-
CAN/ULS-S610-M87 standard as a FACTORY BUILT
APPLIANCE.
FOR CANADA: The authority having jurisdiction (such
as the municipal building department, fire department,
etc.) should be contacted before installation to determine the need to obtain a permit.
INSTALLER: Leave this manual with the appliance.
CONSUMER: Retain this manual for future reference.
WARNING: Improper installation, adjustment, alteration,
service or maintenance can
cause injury, property damage or
loss of life. Refer to this manual
for assistance or additional information. Consult a qualified
installer or local distributor.
IMPORT ANT : Check local codes
before installing this fireplace.
Before beginning installation of this fireplace,
read these instructions through completely.
• This Style Crest, Inc fireplace and its components are safe when installed according
to this installation manual. Unless you use
Style Crest, Inc components, which have
been designed and tested for the fireplace
system, you may cause a fire hazard.
• The Style Crest, Inc warranty will be voided
by and Style Crest, Inc disclaims any responsibility for the following actions.
a. Modification of the fireplace, com-
ponents, doors, air inlet system and
damper control.
b. Use of any component part not manu-
factured or approved by Style Crest, Inc
in combination with a Style Crest, Inc
fireplace system.
Proper installation is the most important step
in ensuring safe and continuous operation of
fireplace. Consult the local building codes as
to the particular requirements concerned with
the installation of all factory built fireplaces.
WARNING: Do not install a
fireplace insert in this box unless
the manufacturer's instructions
with the insert specifically state
this fireplace has been tested for
use with this insert.
FOR YOUR SAFETY
• Do not store or use gasoline
or any other flammable vapors
or liquids in the vicinity of this
or any other appliance.
• Due to high temperatures, the
appliance should be located
out of traffic and away from
furniture and draperies.
• Do not place clothing or other
flammable materials on or near
the appliance.
• Never leave children unat-
tended when a fire is burning
in the fireplace.
WARNING: Use solid wood
or processed solid fuel fire logs
only. When processed wood
fuel fire logs are used, do not
poke or stir the logs while they
are burning. Use only fire logs
that have been evaluated for
the application in fireplace and
refer to fire log warnings and
caution markings on packaging
prior to use.
This fireplace is not intended to
be used as a substitute for a furnace to heat an entire home. Use
for supplemental heat only.
www.fmiproducts.com
108919-01H2
SPECIFICATIONS
1" AIRSPACE
TO COMBUSTIBLE
MATERIAL
0" TO
TOP SPACERS
3/4" AIR
SPACE
BACK
AND
SIDES
OUTSIDE AIR
(LEFT SIDE
ONLY)
0" TO
BOTTOM
21.125"
0.625"
12"
EACH SIDE
28.5"
44"
NO COMBUSTIBLE
MATERIAL ON FACE
HEARTH
EXTENSION
66" X 20"
14"
GAS LINE
KNOCK OUTS
COMBUSTIBLE
WALL BOARD
NOT LESS
THAN 14" TO
PERPENDICULAR
SIDEWALL
AIR KIT
KNOCK OUT
10.375"
25.375"
38.85"
RIGHT SIDE
KNOCK OUTS
LEFT SIDE
8.25"
7"
GAS LINE
8.25"
7"
13"
14.438"
1.375"
ROUND TOP TERMINATION
1"
37.5"
33"
6.5"
42"
1"
108919-01H3
44"
www.fmiproducts.com
21.5"
32"
1.75"
SQUARE CHASE-TOP
TERMINATION
FIREPLACE INSTALLATION
SELECTING LOCATION
T o determine safest and most efficient location
for fireplace, you must take into consideration
the following guidelines:
1. Location must allow for proper clearances
(see Figures 1 and 2).
2. Consider a location where fireplace will
not be affected by drafts, air conditioning
ducts, windows or doors.
3. A location that avoids cutting of joists or
roof rafters will make installation easier.
4. An outside air kit is available with this
fireplace (see Optional Outside Air Kit on
page 7).
MINIMUM CLEARANCE TO
COMBUSTIBLES
Back and sides of fireplace 3/4" minimum*
Floor** 0" minimum
Perpendicular wall to opening 12" minimum
Top spacers 0" minimum
Mantel clearances see Mantels, page 6
Chimney outer pipe surface 1" minimum
* Not required at nailing flanges
** See step 2 of Framing
WARNING: Do not pack required air spaces with insulation
or other materials.
Minimum/Maximum Chimney Height
Minimum height of chimney, measured from
base of fireplace to flue gas outlet of termination, is 11.5 feet for straight flue or a flue with
one elbow set. Maximum distance between
elbows is 2 feet. For systems with two elbow
sets, minimum height is 22 feet. Maximum
height of any system is 28 feet. This measurement includes fireplace, chimney sections and
height of termination assembly at level of flue
gas outlet (see Figure 18, page 11).
FRAMING
1. Frame opening for fireplace using dimensions shown in Figures 1 and 2.
2. If fireplace is to be installed directly on
carpeting, tile (other than ceramic) or any
combustible material other than wood
flooring, fireplace must be installed upon
a metal or wood panel extending full width
and depth of fireplace.
3. Set fireplace directly in front of this open-
ing and slide unit back until nailing flanges
touch side framing.
4. Check level of fireplace and shim with
sheet metal if necessary.
5. Before securing fireplace to prepared
framing, ember protector must be placed
between hearth extension (not included)
and under bottom front edge of fireplace
to protect against glowing embers falling
through. If fireplace is to be installed on
a raised platform, a Z-type ember protector (not included) must be fabricated to
fit your required platform height. Ember
protector should extend under fireplace a
minimum of 1
1
/2". Ember protector should
be made of galvanized sheet metal (28
gauge minimum) to prevent corrosion.
6. Using screws or nails, secure fireplace to
framing through flanges located on sides
of fireplace.
37.625"
44.25"
22"
Figure 1 - Framing Dimensions
Maintain 3/4"
Clearance at
7
Sides and
/8"
15
Back of
22
52 1/2"
1
/2"
3/4" Clearance Not
Required at Nailing Flanges
72
7
/8"
Fireplace
Figure 2 - Corner Installation
www.fmiproducts.com
108919-01H4
FIREPLACE INSTALLA TION
Continued
HEARTH EXTENSION
A hearth extension projecting a minimum of
20" in front of and a minimum of 12" beyond
each side of fireplace opening is required to
protect combustible floor construction in front
of fireplace. Fabricate a hearth extension
using a material which meets the following
specifications: a layer of noncombustible,
inorganic material having a thermal conductivity of K=0.84 BTU IN/FT , HR. F (or less) at 1"
thick. For example, if material selected has
a K factor of 0.25, such as glass fiber, the
following formula would apply:
0.25 x 1.0" = 0.30" thickness required
0.84
Thermal conductivity "K" of materials can be
obtained from manufacturer or supplier of
noncombustible material. If hearth extension
is to be covered, use noncombustible material such as tile, slate, brick, concrete, metal,
glass, marble, stone, etc. Provide a means
to prevent hearth extension from shifting and
seal gap between fireplace frame and hearth
extension with a noncombustible material
(see Figure 3).
WARNING: Hearth extension
is to be installed only as shown
in Figure 3.
Fireplace Front
Ember Protector
Seal Gap
NO
Do Not Block Louver
Extension
Fireplace Front
Elevated
Ember Protector
Hearth Extension, Circulating Modes
Fireplace Front
Ember Protector
Fireplace Front
Raised Hearth
Ember Protector
Fireplace Front
Elevated
Seal Gap
Seal Gap
Extension
Seal Gap
Hearth
Hearth
Ember Protector
Hearth Extension, Noncirculating Models
Figure 3 - Hearth Extension
108919-01H5
www.fmiproducts.com
FIREPLACE INSTALLA TION
Continued
MANTELS
A mantel may be installed if desired (see
Figure 4). Woodwork such as wood trims,
mantels or any other combustible material
projecting from front face must not be placed
within 12" of fireplace opening (and within 9"
of top louver opening). Combustible materials above 12" and projecting more than 1
from fireplace must not be placed less than
12" from top opening of fireplace (NFPA STD
211, Sec. 7-3.3.3).
Mantels or any other combustible material
may come up to side edge of black metal face
of fireplace if projection from front face falls
within limits shown in Figure 5.
1
/2"
FAN/BLOWER KIT ASSEMBLY
Fan or blower kit is optional with this fireplace
(for circulating models only). Use of blowers
or fans other than those manufactured by
Style Crest, Inc voids warranty. Fan is operated by pressing rocker switch (see Figure 6)
in lower right hand corner of fireplace face.
Blower is operated by turning control knob
(not shown).
Fan/blower kit electrical connections are
made through electrical cover plate on side
of fireplace a shown in Figure 6.
Sheet
Metal
Screws
12 1/4" Ref.
6"
Ref.
33°
3" Nom.
15"
Min.
Min.
12"
Min.
Fireplace Opening
1
/2"
1
Max.
9"
Top of
Louvered
Opening
Figure 4 - Mantel Clearances to
Combustible Material
Top View of Fireplace
SAFE ZONE
8"
33°
1"
Min. 12" from
Perpendicular Side Wall
Figure 5 - Side Mantel Clearance
Combustible
Material
Safe Zone For
Projection of
Combustible
Materials
*Note: Drawing
Not To Scale
Upper Section
of Circulating
Fireplace
FIREBOX
0.625" Max.
Rocker
Switch
Electrical
Housing
Electrical
Bushing
Wire Nut (3x)
(Not Supplied)
Electrical
Cover
Plate
Outer Wrapper
of Fireplace
Power Source Wiring
(Not Supplied)
To Power
Source
Electrical Cover
Receptacle
(Supplied)
Prewired Receptacle
and Ground
Plate and
Electrical Bushing
Fireplace Chassis
Ground
Figure 6 - Fan Switch-Electrical Bushing
Wiring Instructions
1. Remove electrical cover plate with bushing from fireplace by removing 2 sheet
metal screws as shown in Figure 6.
2. Slide power source wiring through electrical bushing opening and electrical cover
plate and make all necessary connections.
3. Slide all wiring connections in electrical
housing as shown in Figure 6.
4. Secure electrical cover plate with screws
previously removed.
Note: Electrical housing and cover plate have
sharp edges. Wear protective gloves.
www.fmiproducts.com
108919-01H6
VENTING INSTALLATION
OPTIONAL OUTSIDE AIR KIT
(MODEL AK4/AK4F)
Installation of outside air kit should be performed during rough framing of fireplace due
to the nature of it's location. Outside combustion air is accessed through a vented crawl
space (AK4F) or through a sidewall (AK4).
See Figure 24 on page 15 for instruction of
operating air kit.
CAUTION: Combustion air
inlet ducts shall not terminate
in attic space.
The maximum height for the
air vent can not exceed 3 feet
below the flue gas outlet of the
termination.
Secure to Collars with Metal Tape, Screws
or Straps (Min. of 1/4" x 20" in size)
Air Inlet
Location
Must Allow
For Bushes
or Snow
Air Inlet
Vented Crawl Space
(Check Local Codes
Before Installing in a
Vented Crawl Space)
Figure 7 - Outside Air Kit
CHIMNEY PIPE
Style Crest, Inc chimney system consists of
12", 18", 24", 36" and 48" snap-lock, doublewall pipe segments, planned for maximum
adaptability to individual site requirements.
Actual lengths gained after fitting overlaps
must be taken into consideration (lineal
gain) and are given in lineal gain chart (see
Figure 8).
Lineal gain is actual measurable length of a
part after two or more parts are connected.
Eyebrow
Vent Hood
Required for
Wall Installation
WARNING: The opening in
collar around chimney at top of
fireplace must not be obstructed.
Never use blown insulation to fill
chimney enclosure.
* The lineal gain for the terminations is
measured to the flue gas outlet height.
Figure 8 - Lineal Gain
End
5
5
5
5
5
7
/8"*
3
/4"*
7
/8" to
6
23 1/8"*
8 1/2" to
21 1/2"*
12"*
7" to 15"*
12" to
1
25
/8"
/8"
/8"
/8"
/8"
/2"*
108919-01H7
www.fmiproducts.com
VENTING INSTALLATION
Continued
ASSEMBLY AND INSTALLATION OF
DOUBLE WALL CHIMNEY SYSTEM
Each double wall chimney section consists
of a galvanized outer pipe, a stainless steel
inner flue pipe and a wire spacer. Pipe sections must be assembled independently as
chimney is installed. When connecting chimney directly to fireplace, inner flue pipe section must be installed first with lanced side
up. Outer pipe section can then be installed
over flue pipe section with hemmed end up.
Press down on each pipe section until lances
securely engage hem on fireplace starter.
Wire will assure proper spacing between
inner and outer pipe sections.
Note: For Canada, use chimney parts designated HT.
WARNING: Opening in collar
around chimney at top of fire-
place must not be obstructed.
Never use blown insulation to
fill chimney enclosure.
Continue to assemble chimney sections as
outlined, making sure that both inner and
outer pipe sections are locked together. When
installing double wall snap-lock chimney together, it is important to assure joint between
chimney sections is locked. Check by pulling
chimney upward after locking. Chimney will
not come apart if properly locked. It is not
necessary to add screws to keep chimney together (exception - see Figure 11, page 9).
USING ELBOW OFFSETS (30E-8DM)
1. To achieve desired offset, you may install
combinations of 12", 18", 24", 36" and
48" length of double wall pipe (see offset
chart, page 7, and Figure 9).
Note: For systems with 2 elbow sets, mini-
mum height is 22 feet. Maximum height
for any system is 50 feet.
2. Chimney weight above offset rests on
return elbow. Straps must be securely
nailed to rafters or joists (see Figure 10,
details A and B, page 9).
3. Maximum length of pipe between supports
(return elbow or 12S-8DM) is 6' of angle
run. Maximum of two 6' angle run sections
per chimney system (see Figure 9).
4. All pipe connections between offset and
return must be secured with two screws
on outer pipe only (see Figure 11, page
Firestop spacers are required at each point
where chimney penetrates a floor space.
Their purpose is to establish and maintain
required clearance between chimney and
combustible materials. When pipe passes
through a framed opening into a living space
above, firestop must be placed onto ceiling
from below as shown in Figure 12.
They also provide complete separation from
one floor space to another or attic space as
required by most codes. When double wall
pipe passes through a framed opening into
an attic space, firestop must be placed into
an attic floor as shown in Figure 13.
If area above is a living space, install
firestop below framed hole.
4. Remove shingles around opening measured. Cut out this section.
5. Add next sections of pipe until end
penetrates roof line. Check to see that
proper clearances are maintained. Extend
chimney by adding sections of double wall
pipe until pipe is minimum of 30" above
highest point of roof cutout. Termination
and chimney must extend a minimum of
36" above highest point where it passes
through roof.
Minimum Measurements
14 3/8"
(36.5 cm)
1"
(2.5
cm)
1"
(2.5
cm)
30"
(76.2 cm
1"
(2.5 cm)
Figure 12 - Firestop Spacer with Living
Space Above Ceiling
If area above is an attic or insulated area,
install firestop above framed hole.
Figure 13 - Firestop Spacer with Attic
Space Above Ceiling
PENETRATING ROOF
T o maintain a 2" clearance to pipe on a roof with
a pitch, a rectangular opening must be cut.
1. Determine center point where pipe will
penetrate the roof.
2. Determine center point of the roof. Pitch
is the distance the roof drops over a given
span, usually 12". A 6/12 pitch means that
the roof drops 6" for each 12" measure
horizontally down from roof rafters.
3. Use roof opening chart (Figure 14) to
determine correct opening length and
flashing required.
www.fmiproducts.com
Opening "A"
PitchSlope Opening
"A" Max.
Flat0°15"V6F-8DM
0-6/1226.6°16
6/12- 12/12 45.0°20
Used Flashing
Model No.
1
/8"V6F-8DM
3
/8"V12F-8DM
Figure 14 - Roof Opening Measurements
FLASHING INSTALLATION (V6F-8DM
OR V12F-8DM)
Determine flashing to be used with roof opening chart. Slide flashing over pipe until base is
flat against roof. Replace as many shingles as
needed to cover exposed area and flashing
base. Secure in position by nailing through
shingles (see Figure 15, page 11). DO NOT
NAIL THROUGH FLASHING CONE.
Installing Flashing on a Metal Roof
When installing flashing on a metal roof, it
is required that putty tape be used between
flashing and roof. Flashing must be secured
to roof using #8 x 3/4" screws and then sealed
with roof coating to prevent leakage through
screw holes. A roof coating must also be applied around perimeter of flashing to provide
a proper seal.
108919-01H10
VENTING INSTALLATION
.
Continued
Storm Collar
Flashing
Cone
Nail Only
Outer
Perimeter
of Flashing
Underlap Shingles
at Bottom
Figure 15 - Flashing Installation
Storm Collar Installation (SC1 or SC2)
Place storm collar over pipe and slide down
until it is snug against open edge of flashing
(see Figure 16). Use SC1 for all round terminations and SC2 for all terminations with
slip sections. Apply waterproof caulk around
perimeter of collar to provide a proper seal.
Chimney
Pipe
Storm
Collar
Figure 16 - Storm Collar
Terminations/Spark Arrestor
Fireplace system must be terminated with
listed round top or chase terminations. In any
case, refer to installation instructions supplied
with termination. Terminations approved for
this fireplace are RT -8DM and R TL-8DM that
can be used for flashing or chase and ET8DM, ETO-8DM, ETL-8DM and ETLO-8DM
for chase style termination only. Figure 17
shows an RTL-8DM round top termination.
Overlap
Shingles Top
and Sides Only
Waterproof
Caulk
Flashing
Terminations with 16" slip pipe sections are
available. RTT-8DM and RTTL-8DM are
approved for flashing installations. When
needed, these adjustable terminations may
be used in combination with pipe assembly
to achieve correct chimney height.
Note: In the rare instance there is a problem
with side driven rain or wind or chimney is
not drafting properly, an ADS-8DM (Anti-Draft
Shield) can be used with round terminations.
Attach Bracket
Tabs to
Outer Pipe
(3 Places)
Secure with
Screws
Overlap
Shingles Top
and Sides
RTL-8DM
Figure 17 - Termination
Level of Flue
Gas Outlet
Flue Pipe of
RTL-8DM
Inside Inner
Pipe of
Chimney
Caulk
Collar
Flashing
Underlap Shingles
Bottom Only
CHASE INSTALLATIONS
Instructions for chase installations are included with chase style termination chosen. In a
multiple chase installation, be sure to provide
adequate distance between terminations to
prevent smoke spillage from one termination
to another. We suggest that terminations be
separated at least 24", center to center and
stacked at a vertical height difference of 18"
(see Figure 18).
Note: If a decorative shroud is to be installed,
contact manufacturer for specifications.
CAUTION: Do not seal openings on the rooftop flashing. Follow the installation instructions
provided with the termination
being used.
108919-01H11
www.fmiproducts.com
24" MIN.
24" MIN.
Figure 18 - Multiple Chase Installation
18" MIN. TYP
VENTING INSTALLATION
Continued
10 FOOT RULE
All flue gas outlet chimney terminations must
extend a minimum of 3 feet in height above
highest point where it passes through roof and
must be at least 2 feet above highest point of
the roof that is within a horizontal distance of
10 feet (see Figure 19).
10'
2' Min.
Level of
Flue Gas
Outlet
10'
3' Min.
FINISHING FIREPLACE
Combustible materials, such as wallboard,
gypsum board, sheet rock, drywall, plywood,
etc., may make direct contact with sides and
top around fireplace face. It is important that
combustible materials do not overlap face
itself. Brick, glass, tile or other noncombustible
materials may overlap front face provided
they do not obstruct essential openings such
as louvered slots. When overlapping with
a noncombustible facing material, use only
noncombustible mortar or adhesive.
Figure 19 - 10 Foot Rule
EFFECTIVE HEIGHT
OF TERMINATION CAP
11.5 FT.
MINIMUM
HEIGHT
2' Min.
EFFECTIVE HEIGHT
OF TERMINATION CAP
11.5 FT.
MINIMUM
HEIGHT
UP TO
6FT. MAX.
3' Min.
EFFECTIVE HEIGHT
OF TERMINATION CAP
MAX. HEIGHT
50 FT.
(ANY SYSTEM)
UP TO
6FT. MAX.
30E-8DM
EFFECTIVE HEIGHT
OF TERMINATION CAP
MIN. HEIGHT
OF 22 FT. (WITH
2 ELBOW SETS)
MAX. HEIGHT OF
50 FT.
30E-8DM
Figure 20 - Typical Residential Installations
www.fmiproducts.com
108919-01H12
OPTIONAL GAS LINE INSTALLATION
Gas line hook up should be done by your
supplier or a qualified service person.
Note: Before you proceed, make sure your
gas supply is turned off.
Use only a 1/2" black iron pipe and appropriate fittings.
1. Remove knockout indentation on refractory or firebrick wall located above refractory
hearth floor. Knockout indentation must
be firmly tapped with any solid object,
such as a 1/2" dowel, until it is released.
Remove fragmented portions of refractory
(see Figure 21).
2. Remove gas line cover plate located on
either side of fireplace and pull out insulation from gas line conduit sleeve. Save
insulation for reuse.
3. Run a 1/2" black iron gas line into fire-
place through rear at gas line conduit
sleeve (if using a raised platform, add
height). Provide sufficient gas line into
fireplace chamber for fitting connection
(see Figure 22).
Note: Secure incoming gas line to wood
framing to provide rigidity for threaded
end.
4. Repack insulation around gas line and into
sleeve opening. Seal any gaps between
gas line and refractory knockout hole with
refractory cement or commercial furnace
cement. Install gas appliance or cap off
gas line if desired.
CAUTION: All gas piping and
connections must be tested for
leaks after installation is completed. After ensuring that gas
valve is on, apply soap and water
solution to all connections and
joints. Bubbles forming show a
leak. Correct all leaks at once.
DO NOT USE AN OPEN FLAME
FOR LEAK TESTING AND DO
NOT OPERATE ANY APPLIANCE
IF A LEAK IS DETECTED. LEAK
TESTING SHOULD BE DONE
BY A QUALIFIED SERVICE
PERSON.
Note: A Style Crest, Inc hood must be installed
when using an unvented gas log set (see Accessories on page 18).
WARNING: Do not operate an
unvented gas log set in this fire-
place with chimney removed.
If you install a decorative gas appliance
(vented gas log), decorative gas appliance
must comply with the Standard for Decorative
Gas Appliance for Installation in Solid Fuel
Burning Fireplaces, ANS Z21.60 or Z21.84
and shall also be installed in accordance with
the National Fuel Gas Code, ANSI 7223NFP A 54 latest edition.
WARNING: To avoid the risk
of damaging fireplace materials and increasing the risk of
spreading a fire, do not use fire-
place to cook or warm food.
Outside of
Fireplace
Gas Line
Conduit
Insulation
Gas
Conduit
Cover
Figure 21 - Gas Line Knockout
Outside of
Fireplace
Gas
Line
Conduit
Repack
Insulation
Figure 22 - Gas Line Installation
Incoming
1/2" Black
Iron Pipe
Seal
Opening
with
Refractory
Cement
Provide Enough Threaded
End for Fitting Connection
Side
Firebrick
Finished
Side
1/2" Dowel
Refractory
Knockout
Plug
Side
Firebrick
Finished
Side
108919-01H13
www.fmiproducts.com
OPTIONAL GAS LINE INSTALLATION
Continued
WARNING: If the fireplace
has been used for wood burning, firebox and chimney must
be cleaned of soot, creosote and
ashes be a qualified chimney
cleaner. Creosote will ignite if
heavily heated.
OPERATION AND MAINTENANCE
GLASS DOORS
Glass doors are standard with this fireplace.
When fireplace is in operation, doors must be
fully opened or fully closed position only or a
fire hazard may be created (see Figure 23).
A fireplace equipped with glass doors operates much differently than a fireplace with an
open front. A fireplace with glass doors has a
limited amount of air for combustion. Excessive heat within fireplace can result if too large
a fire is built or if combustion air gate is not
completely open.
The following tips should be used to assure
that both fireplace and glass door retain
their beauty and function properly. Both the
flue damper and glass doors must be fully
opened before starting a fire. This will provide
sufficient combustion air and maintain safe
temperatures in firebox.
IMPORTANT: The glass must be allowed
to warm slowly and evenly. Tempered glass
will withstand a gradual temperature rise to
550° F, which is more than a normal fire will
generate. Such materials as pitch/wax laden
logs, very dry mill end lumber and large
amounts of paper or cardboard boxes can
create an excessively hot fire and should not
be burned in this fireplace. Always keep fire
back from doors and never allow flames to
contact glass.
WARNING: Fireplaces
equipped with glass doors
should be operated only with
doors fully opened or doors fully
closed. Doors, if left partly open,
may draw gas and flame out of
the fireplace opening creating
risks of both fire and smoke.
WARNING: When using
a decorative vented gas log,
damper must be removed or
permanently locked in fully open
position and glass doors must
be in fully open position.
Doors Fully Closed
Fireplace Front
Doors Fully Opened
Fireplace Front
Figure 23 - Glass Doors
Cleaning Glass
Clean glass with any commercial glass
cleaner or soap and water. Do not use any
abrasive material to clean the glass. Do not
clean glass with any cool water if glass is still
hot from fire and smoke.
A gas line or gas log lighter may be installed
for the purpose of installing a vented or ventfree decorative gas appliance incorporating an
automatic shutoff device and complying with
the Standard for Decorative Gas Appliances
for Installation in Vented Fireplaces, ANSI
Z21.60 or American Gas Association draft
requirements for Gas Fired Log Lighters for
Wood Burning Fireplaces, Draft NO. 4 dated
August, 1993.
If you wish to install an unvented (vent-free)
gas log set, only unvented gas log sets which
have been found to comply with the standard
for unvented room heaters, ANSI Z21.1 1.2 are
to be installed in this fireplace.
www.fmiproducts.com
108919-01H14
OPERATION AND MAINTENANCE
Continued
DAMPER HANDLE OPERATION
Damper handle, which opens and closes
damper blade, is located inside firebox at
center towards back wall (see Figure 24).
Pushing handle back into keyway slot will
free damper blade to automatically open.
To close, push handle back into keyhole slot
then pull down and forward to lock it in place
(see Figure 25).
WARNING: Risk of fire! Replace grate with Style Crest, Inc
model 107001-02 only. This grate
has been designed to keep the
operation of your fireplace safe
and efficient.
For further operating guidelines, instructions and warranty information, please refer to your homeowner's guide or contact
your authorized dealer.
Damper
Handle
Figure 24 - Damper Handle Location
Damper
Weight
2
1
3
To Close DamperTo Open Damper
Figure 25 - Damper Rod
1
3
2
TECHNICAL SERVICE
You may have further questions about installation, operation, or troubleshooting. If so, contact
Style Crest, Inc. at 1-800-231-4822 or write to:
Style Crest Service
P. O. Box 191 10
Wichita, KS. 67204.
When calling or writing, please have your model and serial numbers of your heater ready.
108919-01H15
www.fmiproducts.com
PARTS
WOOD BURNING FIREPLACE MODEL C42MW
20
5
1
2
18
3
4
17
25
11
10
14
24
22
15
21
19
28
12
26
13
16
29
6
7
8
30
9
23
27
www.fmiproducts.com
108919-01H16
PARTS
WOOD BURNING FIREPLACE MODEL C42MW
This list contains replaceable parts used in your fireplace. When ordering parts, see Replacement Parts on page 18 of this manual.
KEY
NO. PART NO.DESCRIPTIONQTY.
1**Insulation Pan1
2**Air Separator1
3**Firebox Top1
4108302-01 Air Deflector1
5**Wrapper T op1
6**Firebox Wrapper1
7**Outer Wrapper/Insulation Assembly1
8**Firebox Floor1
9**Wrapper Bottom1
10**Front Face Weldment, Smooth1
11