Note 1: Click on the step above to jump to that page.
Note 2: To return to the Table of Contents, click on the header of any page.
Vertiv™ XTE PTS enclosures are co-located with active
electronic enclosures in wireless networks to provide
AC power transfer, surge protection, distribution, and T1
terminations for cellular, PCS, and all wireless markets.
Description
Application
The Vertiv XTE PTS Series is a full service
power transfer switch designed to provide
main service disconnect, AC surge
protection, AC distribution and generator
connection in a single environmentally
protected enclosure.
Vertiv | XTE PTS Power Transfer Switches | Ordering Guide (R01/20)2
The Vertiv XTE PTS Series of cabinets is
co-located with active electronic
enclosures in wireless and wireline
telecommunication networks. PTS
enclosures provide.
This ordering guide is a sample of our
most common configurations. Custom
options are available. Just ask.
Page 3
Overview
PE15/PE24 Model
PESB ModelGESB ModelAC ModelA8 ModelComb o Cab ModelATS M ode l
Model Comparison
Model
PTS (Generator Power up to 100A)
PE1560-100A30-100AHubbell
PE2460-100A30-100A
PTS (Generator Power up to 200A)
PESB100-200A30-200A
GESB
(Galvanized
Steel)
CAC100-200A30-200A
PTS (Generator Power, 200A)
Commercial
Power
100-200A30-200A
Generator
Power
Gen Inlet
Options
Hubbell
Appleton
Crouse-Hinds
Hubbell
Appleton
Crouse-Hinds
Hubbell
Appleton
Appleton
Hubbell
AIC Rating
10kAIC
22kAIC
42kAIC
10kAIC
22kAIC
42kAIC
10kAIC
22kAIC
42kAIC
10kAIC
22kAIC
42kAIC
10kAIC
65kAIC
Surge
Arrestor
AC Data12 posOptionalOff-White
AC Data8-12 posNone
AC Data
Edco
ASCO
AC Data
Edco
ASCO
ASCO24-30 posNoneOff-WhiteNone
Load
Center
8-32 posOptional
8-32 posOptional
GFI
Color
Options
Off-White
Green
Off-White
Green
Off-White
Green
Meter Options
None
Hub and
Backplate
Hub and
backplate
Cutler Hammer
None
Milbank
Durham
Siemens
Cutler Hammer
None
Milbank
Durham
Siemens
Cutler Hammer
AC Model200A200A
PTS with Telco Compartment (Generator Power up to 200A)
GESBTEMPF1004492Galvanized pad-mounting template (see drawing)
Custom configurations available. Call 800-800-1280 or emailAccountManagement.ESNA@Vertiv.com for more information.
8Vertiv | XTE PTS Power Transfer Switches | Ordering Guide (R01/20)
Page 9
CAC
CAC Model
y Telco demarcation with optional
telco cabinet.
y Mechanical interlock prevents
simultaneous use of utility and
generator power.
y Brute force metal oxide varistor surge
suppression with easy to read LED
and remote status indication.
y 3-point door closure with continuous
hinge and heavy duty door gasket.
y UL891 listed rain/drip hood provides
protection against the elements.
Technical Specifications
Cabinet Dimensions39.00" H x 20.00" W x 10.00" D
Exterior MaterialPowder-coated aluminum
MountingWall, pole, or pad mount
Cabinet Enclosure TypeNEMA 3R
Operating Voltage120/240 VAC, single phase, 3 wire and ground
Service
DisconnectSlide bar mechanical interlock
AIC Rating
Load Center
Standby Power Receptacle
TVSS with Indicator LightsMetal oxide Varistors (MOV) (160kA/Phase)
Security (padlockable)3-point door closure with 1/4 turn handle
Safety ComplianceUL 891, dead front switchboards
100A
200A
10kAIC
22kAIC
65kAIC
12-position
24-position
100A
200A
CAC Model
Catalog Number
CAC-A22204090100A slide bar transfer device, 24-position load center, ADR1044RS,
CAC-A45201090200A slide bar transfer device, 24-position load center, AR2044RS, MOV
CAC-A45201190
CAC-A75201090200A slide bar transfer device, 30-position load center, AR20044RS
Part
Number
Description
MOV
200A slide bar transfer device, 24-position load center, AR20044RS with
45 degree angle adapter, MOV
Custom configurations available. Call 800-800-1280 or
emailAccountManagement.ESNA@Vertiv.com for more information.
9Vertiv | XTE PTS Power Transfer Switches | Ordering Guide (R01/20)
Page 10
XTE PTS Ordering Guide
PTS (Generator Power, 200A)
AC Model
y Manual transfer switch.
y Transient Voltage Surge
Suppression (TVSS).
y Generator receptacle.
y Load center.
y Neutral-ground bonding point.
y Optional telco cabinet.
Technical Specifications
Cabinet Dimensions59.00" H x 24.00" W x 10.00" D
Exterior MaterialPowder-coated aluminum
MountingWall or pad mount
Cabinet Enclosure TypeNEMA 3R
Operating Voltage120/240 VAC, single phase, 3 wire and ground
Service200A
100A
DisconnectInterlock toggle switch
AIC Rating10kAIC
22kAIC
Load Center12-position
24-position
Standby Power Receptacle100A
TVSS with Indicator LightsASCO 4M120V
Security (padlockable)3-point door closure with 1/4 turn handle
Safety ComplianceUL 891, dead front switchboards
Front door closed (left), interior deadfront panel open (middle)
and deadfront panel closed (right)
Catalog NumberPart NumberDescription
BN232W000F1009598200A mechanical transfer device, 24-position load center, SAD/MOV
BS2S2W000F1009593200A mechanical transfer device, 24-position load center, AR20044RS, SAD/MOV
Custom configurations available. Call 800-800-1280 or emailAccountManagement.ESNA@Vertiv.com for more information.
10Vertiv | XTE PTS Power Transfer Switches | Ordering Guide (R01/20)
Page 11
PTS With Telco Compartment (Generator Power up to 200A)
A8 Model
y Designed specifically for
wireless applications.
y Underneath telco section allows for
T1 demarcation.
y Compact design maximizes area
on site.
A8 Model
Telco Model
Technical Specifications
Cabinet Dimensions48"H x 30"W x 13.5"D
Exterior MaterialPowder-coated aluminum
MountingPad mount
Cabinet Enclosure TypeNEMA 3R
Operating Voltage120/240 VAC, single phase, 3 wire and ground
Service100A, 200A
DisconnectSlide bar
AIC Rating10kAIC, 22kAIC, 42kAIC, 65kAIC
Load Center12-position
Standby Power Receptacle100A, 200A
TVSS with Indicator LightsAC Data, Atlantic Scientific
Security (padlockable)3-point door closure with 1/4 turn handle
Safety ComplianceUL 891, dead front switchboards
Catalog
Number
ESBA8ADTZN7F1004100A8, 10,000 AIC, ESB, 26-in. power compartment, 10-in. telco
ESBA8BBHFN7F1004085A8, 10,000 AIC, ESB, 26-in. power compartment, 10-in. telco
ESBA8CLTZN7F1009643A8, 10,000 AIC, ESB, 26-in. power compartment, 10-in. telco
Part
Number
Description
compartment, 200/200, AR20034RS (Appleton 200amp), off white
compartment, 200/100, 4100B12W (Hubbell 100amp), off white
compartment, 100/100, ADR1034RS (Appleton 100amp), off white
Accessories
A8EXTF1003921Extender and template for pad mounting
y Wall-mount or grade Level.
y Transient voltage surge suppressor for
telco T1 service optional.
y Terminal block with remote indication.
y Plywood back board.
y Cooling fan with thermostat.
y Metal mesh electrostatic air filter.
y NEMA 3R rainproof.
Technical Specifications
Cabinet Dimensions59.00"H x 24.00"W x 20.00"D
Exterior MaterialPowder-coated aluminum
MountingWall or pad mount
Cabinet Enclosure TypeNEMA 3R
Remote Indication (optional) 8-position terminal block with wire harness
Grounding12 position, double lug master ground bar
Security (padlockable)3- point latching handle
Safety ComplianceNEMA 3R
*Install neoprene base gasket when pad mounting.
**Fan leads must be connected to power using the wire harness provided, 120 VAC, 10A breaker.
***All penetrations of the cabinet must utilize NEMA 3R rated components to maintain the cabinet rating.
Catalog NumberDescription
TNN00W20120" telco cabinet with TCS-T1DS
TNN00W23820" telco cabinet (no TCS-T1DS)
TNN00W27020" telco cabinet with 2000048 multi T1, isolated ground (no terminal block)
TNN00W10110" telco cabinet with TCS-T1DS
Custom configurations available. Call 800-800-1280 or
emailAccountManagement.ESNA@Vertiv.com for more information.
11Vertiv | XTE PTS Power Transfer Switches | Ordering Guide (R01/20)
Page 12
XTE PTS Ordering Guide
Side-by-Side Model
y AC and telco demarcation together.
y Manual transfer switch.
y Transient Voltage Surge
Suppression (TVSS).
y Generator receptacle.
y Load center.
y Neutral-ground bonding point.
NOTE: For cabinet specifications, refer to the
AC and Telco Models on the following pages.
Technical Specifications
Cabinet Dimensions48"H x 30"W x 13.5"D
Exterior MaterialPowder-coated aluminum
MountingWall or pad mount
Cabinet Enclosure TypeNEMA 3R
Operating Voltage120/240 VAC, single phase, 3 wire and ground
Service
DisconnectInterlock toggle switch
AIC Rating
Load Center
Standby Power Receptacle100A
TVSS with Indicator LightsASCO 4M120V
Security (padlockable)3-point door closure with 1/4 turn handle
Safety ComplianceUL 891, dead front switchboards
200A
100A
10kAIC
22kAIC
12-position
24-position
Side-by-Side Model
Catalog NumberDescription
NS2S2-W201
NS2S1-W203
NS2S1-W101
LS2S1-W201
200A mechanical transfer device, 24-position load center, AR20044RS, SAD/
MOV with 20" telco cabinet (no TCS-T1DS)
200A mechanical transfer device, 24-position load center, AR20033RS with 45
degree angle adapter, SAD/MOV with 20" telco cabinet, fire retardant plywood
backboard
200A mechanical transfer device, 24-position load center, AR20044RS, SAD/
MOV with 10" telco cabinet
100A mechanical transfer device, 12-position load center, PM4100B12W, SAD/
MOV with 20" telco cabinet
Custom configurations available. Call 800-800-1280 or
emailAccountManagement.ESNA@Vertiv.com for more information.
12Vertiv | XTE PTS Power Transfer Switches | Ordering Guide (R01/20)
Page 13
Combo Cab Model
y Designed specifically for
wireless applications.
y Underneath telco section allows for
T1 demarcation.
y Compact design maximizes area
on site.
Technical Specifications
Cabinet Dimensions
Exterior MaterialPowder-coated aluminum
MountingWall, H-frame, bracket, or pad mount
Cabinet Enclosure TypeNEMA 3R
Operating Voltage120/240 VAC, single phase, 3 wire and ground
Service200A
DisconnectSlide bar
AIC Rating65kAIC
Load Center24-position
Standby Power Receptacle200A
TVSS with Indicator LightsASCO 4M120V
Security (padlockable)3- point latching handle
Safety ComplianceUL 891 dead front switchboards
66"H x 30"W x 10"D
60"H x 25"W x 10"D
Catalog NumberPart NumberDescription
CS2S2-W736-
CS7S2-W836F1009123
200A slide bar transfer device, 24-position load center,
AR20044RS SAD/MOV, over/under
200A slide bar transfer device, 24-position load center,
AR20044RS MOV, over/under
Combo Cab Model
Catalog Number Definition
Cabinet Configuration C=200A (65kAIC with slide bar)
Generator ReceptableS=AR20044RS (Appleton 200A)
TVSS Level7=MOV only (1 - 6M120V/phase) 200kA/Phase
TVSS ConnectionS=Standard (breaker)
Load Center2=24 position
Mounting OptionsW=Wall / in-line cabinets
Dimensions (H x W x D)
Auxiliary Options36=Left side (when facing cabinet)
7
8
= =66" x 30" x 10" (30" high for AC; 36" high for telco)
60" x 25" x 10" (30" high for AC; 30" high for telco)
Custom configurations available. Call 800-800-1280 or
email AccountManagement.ESNA@Vertiv.com for more information.
13Vertiv | XTE PTS Power Transfer Switches | Ordering Guide (R01/20)
Page 14
XTE PTS Ordering Guide
aTS (Generator Power, up to 200A)
ATS Model
y ASCO 300 Series switch.
y Hinged deadfront panel with
wind latch.
y 200A main breaker for normal power.
y ATS controller.
y Isolated neutral assembly.
y ATS contactor.
y Ground bar.
y Conduit access panel.
y 11BG engine exerciser.
Technical Specifications
Cabinet Dimensions43.2"H x 18.0"W x 9.0"D
Exterior MaterialPowder-coated aluminum
MountingWall or pad mounted
Cabinet Enclosure TypeNEMA 3R
Operating Voltage120/240 VAC, single phase, 3 wire and ground
Service
DisconnectASCO 300 Series automatic transfer switch
AIC Rating
Load CenterNone
Standby Power ReceptacleNone
Security (padlockable)3- point latching handle
Safety ComplianceUL 891
100A
200A
Catalog NumberPart NumberDescription
A100CF1007034100Amp ATS stand alone module (remote mount)
A200CF1007035200Amp ATS stand alone module (remote mount)
ATSTEMPF1007036
ATSXIF1007484Bottom for ATS when wall mounting
Pad mounting template for ATS modules
ATS Model
Custom configurations available. Call 800-800-1280 or
emailAccountManagement.ESNA@Vertiv.com for more information.
14Vertiv | XTE PTS Power Transfer Switches | Ordering Guide (R01/20)
Page 15
Dimensions
16.75"H x 18.75"W x 11"D
Figure 1 - 16.75"H x 18.75"W x 11"D
PE15 Model
Figure 2 - 24"H x 19.09"W x 11.16"D
24"H x 19.09"W x 11.16"D
PE24MC Model
(22,000 AIC)
Figure 3 - 30"H x 18.8"W x 10.8"D
30"H x 18.8"W x 10.8"D
PE24ME Model
(42,000 AIC)
15Vertiv | XTE PTS Power Transfer Switches | Ordering Guide (R01/20)
Page 16
XTE PTS Ordering Guide
Dimensions
43.13"H x 21.98"W x 7.41"D
Figure 4 - 43.13"H x 21.98"W x 7.41"D
PESB Model
43.13"H x 24"W x 8.5"D
Figure 5 - 43.13"H x 24"W x 8.5"D
GESB Model
39.00" H x 20.00" W x 10.00" D
Figure 6 - 39.00" H x 20.00" W x 10.00" D
CAC Model
16Vertiv | XTE PTS Power Transfer Switches | Ordering Guide (R01/20)
Page 17
Dimensions
59.00" H x 24.00" W x 10.00" D
Figure 7 - 59.00" H x 24.00" W x 10.00" D
AC Model (BN2S2W000)
Figure 8 - 59.00" H x 24.00" W x 10.00" D
59.00" H x 24.00" W x 10.00" D
AC Model (BS2S2W000)
48"H x 30"W x 13.5"D
Figure 9 - 48"H x 30"W x 13.5"D
A8 Model
17Vertiv | XTE PTS Power Transfer Switches | Ordering Guide (R01/20)
Page 18
XTE PTS Ordering Guide
30
66
10
D
C
B
A
8
7
6
5
4
3
2
1
DIMENSIONS ARE IN INCHESTOLERANCES:FRACTIONALANGULAR: MACH
BEND TWO PLACE DECIMAL THREE PLACE DECIMAL
DRAWN
CHECKED
ENG APPR.
DATE
NAME
TITLE:
UNLESS OTHERWISE SPECIFIED:
J.GESSELE
4/10/2013
10
D
C
B
4
3
2
1
D
C
B
1
Dimensions
48"H x 30"W x 13.5"D
Figure 10 - 48"H x 30"W x 13.5"D
Side-by-Side Model (NS2S2-W201)
66"H x 30"W x 10"D
Figure 11 - 66"H x 30"W x 10"D
Combo Cab Model (CS2S2-W736)
TELCO
FAN/FILTER PACK
90
DOOR OPENING
WITH DOOR STOP
GROUND BAR
200A/200A MAIN BREAKERS
MTS MECHANICAL INTERLOCK
24-POSITION LOAD CENTER
EXTERNAL GFI RECEPTACLE
INTERNAL GFI RECEPTACLE
TELCO COMPARTMENT
TELCO GROUND BAR
66
30
10
18Vertiv | XTE PTS Power Transfer Switches | Ordering Guide (R01/20)
Page 19
Dimensions
60"H x 25"W x 10"D
Figure 12 - 60"H x 25"W x 10"D
Combo Cab Model (CS2S2-W836)
59.00"H x 24.00"W x 20.00"D
Figure 13 - 59.00"H x 24.00"W x 20.00"D
Telco Model (TNN00W201)
19Vertiv | XTE PTS Power Transfer Switches | Ordering Guide (R01/20)
Page 20
XTE PTS Ordering Guide
Dimensions
Figure 14 - 59"H x 24"W x 10"D
Telco Model (TNN00W101)
43.2"H x 18.0"W x 9.0"D
Figure 15 - 43.2"H x 18.0"W x 9.0"D
ATS Model
20Vertiv | XTE PTS Power Transfer Switches | Ordering Guide (R01/20)
Page 21
Pad-Mounting Templates
Aluminum pad-mounting template, J-bolts and hardware (see drawing)
PESB / GESB Pad Mounting Template
PEILRPEILTEMP
PE24MC Pad Mounting Template
PE24MC Pad Mounting Template
PE 24TE MP
GESBTEMP
PE24ME Pad Mounting Template
PE24ME pad mounting template
PE24METEMP
21Vertiv | XTE PTS Power Transfer Switches | Ordering Guide (R01/20)
Page 22
XTE PTS Ordering Guide
DRAWING NOTES:
D1)REVISIONS CHANGES ARE INDICATED BY CIRCLED LETTERS.
D2)ORTHOGRAPHIC PROJECTIONS ARE THIRD ANGLE.
D3)DO NOT SCALE DRAWING.
D4)PRIMARY DIMENSIONS ARE STATEDIN INCHES, AND SECONDARY DIMENSIONS IN [] ARE MM UNLESS OTHERWISESPECIFIED.
D5)THIS DOCUMENT IS THE PROPERTY OF EMERSON NETWORKPOWER,ENERGYSYSTEMSNORTHAMERICA, INC. AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OWNED BY EMERSON NETWORKPOWER,ENERGYSYSTEMSNORTHAMERICA, INC. ANY COPYING USE OR DISCLOSUREOF IT WITHOUT WRITTEN PERMISSION OF EMERSON NETWORK POWER, ENERGY SYSTEMS, NORTHAMERICA, INC. IS STRICTLY PROHIBITED.
D6)TOLERANCES&LIMITSAPPLYOVERADDITIVEFINISH.
DRAWING NOTES:
D1)REVISIONS CHANGES ARE INDICATED BY CIRCLED LETTERS.
D2)ORTHOGRAPHIC PROJECTIONS ARE THIRD ANGLE.
D3)DO NOT SCALE DRAWING.
D4)PRIMARY DIMENSIONS ARE STATEDIN INCHES, AND SECONDARY DIMENSIONS IN [] ARE MM UNLESS OTHERWISESPECIFIED.
D5)THIS DOCUMENT IS THE PROPERTY OF EMERSON NETWORKPOWER,ENERGYSYSTEMSNORTHAMERICA, INC. AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OWNED BY EMERSON NETWORKPOWER,ENERGYSYSTEMSNORTHAMERICA, INC. ANY COPYING USE OR DISCLOSUREOF IT WITHOUT WRITTEN PERMISSION OF EMERSON NETWORK POWER, ENERGY SYSTEMS, NORTHAMERICA, INC. IS STRICTLY PROHIBITED.
D6)TOLERANCES&LIMITSAPPLYOVERADDITIVEFINISH.
Pad-Mounting Templates
A8 Pad Mounting Template
A8EXT
Pad mounting template for ATS modules
Pad mounting template for ATS modules
ATS Pad Mounting Template
ATST E M P
22Vertiv | XTE PTS Power Transfer Switches | Ordering Guide (R01/20)
Page 23
Accessories for All Models
Catalog NumberPart NumberDescription
Meter Housings
10056471005647200 amp Durham meter housing
U7040XLTGKKE74116200 amp Milbank meter housing, ringless, horn type (M2)
U7018XLTGKKE74125200 amp Milbank meter housing, ringless
U2964XTLU2964XTL100 amp Milbank meter housing, test by-pass
U2974XTLU2974XTL200 amp Milbank meter housing, test by-pass
U9551-RXLU9551-RXL200 amp Milbank meter housing (M9)
Generator Power Cords
11680Hubbell 100 amp generator connector 4100C12W
11680-11681-2525-ft. 100/100 amp cord set e/w Hubbell 4100C12 connector to Hubbell 4100P12 plug
11680-11681-5050-ft. 100 amp cord set e/w Hubbell 4100C12 connector to Hubbell 4100P12 plug
11680-11720-2525-ft. 100/30 amp cord set e/w Hubbell 4100C12W connector to Hubbell #2711 plug
11680-11720-5050-ft. 100/30 amp cord set e/w Hubbell 4100C12W connector to Hubbell #2711 plug
NOTE: Circuit breakers available, please call customer service at 1-800-800-1280.
Services
A complete life-cycle approach to service,
from project launch to ongoing maintenance
and performance optimization
Project
When launching new
facilities or powering up new
equipment, you want to do it
right – right from the start
y Plan
y Design
y Engineer
y Integrate
y Commission
y Project management
We strive to keep your network infrastructure highly available, eicient and
adaptable, so you can:
y Increase mean time between failure
y Decrease operating cost
y Implement future technologies while maximizing your resources
Maintenance
Services to ensure that your
business-critical
infrastructure operates
reliably, safely and eiciently
y Preventive and corrective
maintenance
y Remote services and
monitoring
y Cap / fan / battery
replacements
y Repair
y Spare parts
Performance
Full range of services designed
to optimize infrastructure
performance and
reduce complexity
y Assess
y Audit
y Model
y Configure
y Upgrade
y Tr ai n
23Vertiv | XTE PTS Power Transfer Switches | Ordering Guide (R01/20)