Vertiv VP9571A, VP7553, VP7541 User Manual

Instruction
Manual
Basic Rack PDU
VP7541, VP9571A
and VP7553
VertivCo.com/geist
Table of Contents
Specifications .............................................................................................................. 3
Overview .........................................................................................................................................................3
Environmental.................................................................................................................................................3
Temperature ...................................................................................................................................................3
Humidity..........................................................................................................................................................3
Elevation .........................................................................................................................................................3
Electrical..........................................................................................................................................................3
Receptacle Ratings .......................................................................................................................................... 3
EMC Verification ............................................................................................................................................. 3
Installation .................................................................................................................. 4
Instructions .....................................................................................................................................................4
Guidelines .......................................................................................................................................................4
Mounting .................................................................................................................... 5
Optional Local Monitoring ........................................................................................ 12
Power Meter .................................................................................................................................................12
Current Meter ...............................................................................................................................................12
Service/Tech Support................................................................................................ 13
Service and Maintenance..............................................................................................................................13
More Technical Support................................................................................................................................13
BASIC RACK PDU
3
Specifications
Overview
The Vertiv Basic Rack PDU products are Power Distribution units (PDU) intended for connection to a 30 Amp AC Mains circuit. The PDUs are designed to be powered by a single phase AC input circuit. The Vertiv Basic Rack PDUs covered by this manual are available in vertical or horizontal configurations rated 208-240V and can be optionally configured with a Vertiv Power Meter that provides local monitoring and display of Current, Voltage, Wattage, and Power Factor.
Environmental Temperature
Operating:
10°C (50°F) min
45°C (113°F) max
Storage:
-25°C (-13°F) min
65°C (149°F) max
Humidity
Operating:
5% min 95% max
(non-condensing)
Storage:
5% min 95% max
(non-condensing)
Elevation
Operating:
0 m (0 ft) min
2000 m (6561 ft) max
Storage:
0 m (0 ft) min
15240 m (50000 ft) max
Electrical
See nameplate for unit ratings.
Receptacle Ratings
NEMA 5-15R or L5-15R
125 Volts, 12 Amp
NEMA 5-20R or L5-20R
125
Volts, 16
Amp
NEMA 6-20R or L6-20R
250
Volts,
16
Amp
IEC-320 C13
125/250 Volt,
12
Amp
(per
Receptacle
Bank)
IEC-320 C19
125/250 Volt, 16
Amp
EMC Verification
This Class A device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.
This Class A digital apparatus complies with Canadian ICES-003.
Cet appareil numérique de la classe A est conforme à la norme NMB-003 du Canada.
Warning: Changes or modifications to this unit not expressly approved by the party responsible for compliance could void the user’s authority to operate this equipment.
BASIC RACK PDU
4
Installation
Instructions
1. Using appropriate hardware, mount PDU to rack (see Mounting section for additional instructions.
2. Plug PDU into de-energized 30 Amp branch circuit receptacle.**
3. Connect devices into PDUs output receptacles. It is recommended that the devices are turned off until all devices are connected to PDU
4. Turn on branch circuit to energize PDU.
5. Power on devices. Sequential power up is recommended to avoid high inrush current.
**Branch Circuit should be sized based on the PDU’s nameplate electrical rating. A 24 Amp
rated PDU is intended for use on a 30 Amp Branch Circuit. For Global Units a 32 Amp rated PDU is intended for use on a 32 Amp Branch Circuit.
Guidelines
If the PDU is installed in a cabinet the ambient temperature of the rack should be no greater
than 45C.
Install the PDU such that the amount of airflow required for safe operation of equipment is not
compromised.
Mount the PDU so that a hazardous condition is not achieved due to uneven mechanical
loading.
Follow nameplate ratings when connecting equipment to the branch circuit. Take into
consideration the effect that overloading of the circuits might have on over-current protection
and supply wiring.
The PDU relies on the building installation for protection from over-current conditions. A
certified overcurrent protection device is required in the building installation. The overcurrent protection device should be sized according to the PDUs nameplate ratings and local/national
electrical codes.
Reliable earthing of rack-mount equipment should be maintained. Particular attention should
be given to supply connections other than direct connections to the branch circuit. The PDU
must be connected to an earthed socket-outlet.***
The PDU is intended for Restricted Access Locations only and only qualified service
personnel should install and access the PDU.
For pluggable equipment, install the PDU so that the input plug or appliance coupler may be
disconnected for service.
Sequential power-up of devices powered by the PDU is recommended to avoid high inrush
current.
Caution: Disconnect all power cords before servicing.
The PDU is intended for use with TN, TT, or IT power supply systems
***XP Series PDUs may optionally be configured as Isolated Ground units. All Isolated
Ground units will be shipped with an enclosure grounding cable. This cable must be connected between the enclosure and a reliable safety ground.
BASIC RACK PDU
5
Mounting
Full Length Bracket
Using the full length bracket, mount PDU to rack as shown
Mini "L" Brackets (SLB-4)
Loading...