Vertiv VP7557 User Manual

Instruction
Manual
VertivCo.com/geist
Basic Rack PDU VP7557 Instruction Manual Page 2
Contents
1. Specifications ........................................................................................................................................................ 3
1.1. Overview ........................................................................................................................................................ 3
1.2. Environmental ................................................................................................................................................ 3
1.2.1. Temperature ........................................................................................................................................ 3
1.2.2. Humidity .............................................................................................................................................. 3
1.2.3. Elevation .............................................................................................................................................. 3
1.3. Electrical ......................................................................................................................................................... 3
1.4. Receptacle Ratings ......................................................................................................................................... 3
2. Installation ............................................................................................................................................................. 5
2.1. Instructions .................................................................................................................................................... 5
2.2. Guidelines....................................................................................................................................................... 5
3. Mounting ................................................................................................................................................................ 6
4. Service/Tech Support ........................................................................................................................................... 10
4.1. Service and Maintenance ............................................................................................................................. 10
4.2. More Technical Support ............................................................................................................................... 10
5. Revision ................................................................................................................................................................ 10
Basic Rack PDU VP7557 Instruction Manual Page 3
1. SPECIFICATIONS
1.1. OVERVIEW
The VP7557 is a Power Distribution Units (PDU) intended for connection to a 16 Amp AC Mains cir­cuit. The PDUs are designed to be powered by a three phase WYE 230/400 Volt AC input circuit. 230 Volt AC (Line-Neutral) single phase output power is distributed through the output receptacles to connected equipment.
1.2. ENVIRONMENTAL
1.2.1. TEMPERATURE
Operating: 10°C (50°F) min 45°C (113°F) max Storage: -25°C (-13°F) min 65°C (149°F) max
1.2.2. HUMIDITY
Operating: 5% min 95% max (non-condensing) Storage: 5% min 95% max (non-condensing)
1.2.3. ELEVATION
Operating: 0 m (0 ft) min 2000 m (6561 ft) max Storage: 0 m (0 ft) min 15240 m (50000 ft) max
1.3. ELECTRICAL
See nameplate for unit ratings.
1.4. RECEPTACLE RATINGS
IEC-320 C13 125/250 Volt, 10 Amp (per Receptacle Bank) IEC-320 C19 125/250 Volt, 16 Amp
Basic Rack PDU VP7557 Instruction Manual Page 4
** Receptacle ratings give nameplate component voltage and current ratings. All Y Series PDUs have
output receptacles wired for 230 Vac, Line-Neutral Output
Loading...