Vertiv SmartRow DCR Installer/user Manual

Page 1
SmartRow™ DCR
3to6 Rack20-kW (N/(N+1) and5to10Rack36-kW(N)CoolingUnits, 60Hz
Installer/User Guide
Page 2
Technical Support Site
If you encounter any installation or operational issues with your product, check the pertinent section of this manual to see if the issue can be resolved by following outlined procedures. For additional assistance, visit https://www.VertivCo.com/en-us/support/
Page 3
1 Important Safety Instructions 7
2 Introduction 9
2.1 Operational Overview 9
2.2 DCR Control Panel andFire-suppressionSystemCommissioningandTraining 9
2.3 SmartRow DCR Components 10
2.4 Liebert PDX/PCW Notes 11
3 Preparation 13
3.1 Clearance Requirements 13
3.2 Inspection 13
3.3 Unloading the SmartRow DCR 13
3.4 Required Set-up Tools and Equipment 14
3.5 Heat Load Guidelines 14
4 Installation 15
4.1 Assembly Sequence Overview 15
4.1.1 SmartRow DCR withSingleLiebertPDX/PCW(20-kW(N)Configuration) 15
4.1.2 Configuring theSmartRowDCRforLeft-to-Right Assembly 16
4.1.3 SmartRow DCR with Two Liebert PDX/PCW Units—20-kW(N+1)/36-kW(N) Configurations 18
4.2 Install the DCR Base Plenum-PDX/PCW First 18
4.3 Assemble the DCR Base Plenums-Rack 19
4.4 Set the PDX/PCW on the Base Plenum-PDX/PCW andInstallCondensatePumpandLiqui-tectSensor 21
4.5 Set the DCR Control Panel andFireSuppressionSystemonthe Base Plenum 28
4.6 Install the DCR Racks on the Base Plenums 29
4.7 Install the Top Plenum-PDX/PCW 33
4.8 Mounting the Top Plenums-Rack 33
4.9 Installing a Second PDX/PCW (20-kW(N+1)/36-kW(N)Configuration) 36
4.10 Installing and Wiring Sensors 38
4.10.1 Connect Return-temperature Thermostat, theL5-20ReceptacleandtheSmokeDetector 38
4.10.2 Connecting the Secondary Return-temperature Thermostat(P3R) for 20-kW (N+1)/36-kW (N) Configurations 39
4.10.3 Connecting the Secondary PDX/PCW Smoke Detector tothePrimaryPDX/PCWSmokeDetector 40
4.10.4 Install Supply Air Temperature Sensor 40
4.10.5 Install and Wire 2T Sensors 40
4.10.6 Locate and Install 4-pin HVAC Fault/Emergency Fan Control, Thermal-unitShutdownConnectorCable(P2) 41
4.10.7 Connecting Secondary, 4-pin HVAC Fault/ Emergency Fan Control, Thermal-UnitShutdownConnectorCable (P2R) for20-kW(N+1)/36-kW (N) Configurations 42
4.11 Adjusting Air-flow Adjustment Dampers 42
4.12 Install Emergency-fan Assemblies 44
Vertiv | SmartRow DCR Installer/User Guide | 3
Page 4
4.13 Air/Ventilation Management 46
4.13.1 Ventilation Requirements 46
4.13.2 Emergency-fan Notes 46
4.14 Cable Management 46
4.14.1 Prepare for Cable Management 46
4.14.2 Routing Power Whips 47
4.14.3 Routing Network Cables—Ethernet and Fiber-optic 48
5 Power Connections 53
5.1 Power Connections to Liebert PDX/PCW 53
5.2 Input Power Wiring Alternatives to DCR Control Panel andFireSuppression System and Rack Equipment 53
5.2.1 Single Bus—SmartRow DCR Load Supplied by a Single UPS 54
5.2.2 Single Bus—SmartRow DCR Load SuppliedbyRack-mountedUPS 54
5.2.3 Dual Bus—SmartRow DCR Load SuppliedbyTwo Central UPSs 54
6 Liebert iCOM™ Controls Set-up 55
6.1 iCOM Installation Prerequisites 55
6.2 Liebert iCOM Setup for all SmartRow DCR Types 55
6.2.1 Set Fixed Fan Speed to Factory-approved Level 56
6.2.2 Prevent False High- and Low-Temperature Alarms 56
6.2.3 Prevent Emergency Fan Activation by Warnings 56
6.2.4 Control Cooling Calculation byRemote2TRackTemperatureSensor Readings 56
6.2.5 Additional Liebert iCOM Settings andAdjustmentsforSmartRowDCR Operation 57
6.3 Additional Settings for20-kW, 3-to6-rackSystems—NCooling(1PDX/PCW-one cooling unit on) 58
6.4 Additional Settings for 20-kW, 3-to6-rackSystems—N+1cooling Only (2PDX/PCWs-onecoolinguniton,oneinstandby) 58
6.4.1 Prevent High-temperature Threshold fromStartingAllLiebertPDX/PCWs 59
6.4.2 Prevent False High-humidity Alarms 59
6.5 Additional Settings for 36-kW, 5-to10-rackSystems—NCooling Only (2PDX/PCWs - both units on) 59
6.5.1 Ensure Even Airflow to all Racks During Low Heat Load 59
7 DCR Control Panel and Fire Suppression System 61
7.1 DCR Control Panel andFireSuppressionSystemComponentLocations 61
7.1.1 Control Panel andFireSuppressionSystemComponentsOperation 62
7.2 Recovering from EPO Circuit Activation 64
7.3 Recovering from a Fire Suppression System Activation 65
8 Installation Checklist 67
8.1 Cooling and Power Component Installation Checklist 67
8.2 Fire Suppression System Installation Checklist 68
8.2.1 DCRFireSuppressionCommissioning Procedure 69
9 Start-up 71
9.1 System Start-up and Commissioning 71
9.2 System Start-up and Activation 71
Vertiv | SmartRow DCR Installer/User Guide | 4
Page 5
10 Troubleshooting 73
11 Maintenance 77
11.1 Liebert PDX/PCW Maintenance 77
11.2 Fire Detection and Suppression System Maintenance 77
11.3 UPSs and Rack PDUs Maintenance 77
12 Technical Data 78
12.1 Unit Dimensions, Weights, and Wiring Tables 78
12.2 Technical-installation Illustrations 81
Vertiv | SmartRow DCR Installer/User Guide | 5
Page 6
Vertiv | SmartRow DCR Installer/User Guide | 6
Page 7

1 IMPORTANT SAFETY INSTRUCTIONS

Save These Instructions
This manual contains important instructions that must be closely followed during installation of this unit to maintain compliance with agency listings. Read all safety and operating instructions before attempting to operate the SmartRow DCR. Adhere to all warnings on the unit and in this manual. Follow all operating and user instructions.
This product is designed for commercial / industrial use only. This product is not intended for use with life support or other U.S. FDA designated “critical” devices. Maximum loads must not exceed those specified in this manual.
Install in a clean environment, free from moisture, flammable liquids, gases and corrosive substances. Operate this product in an indoor environment at an ambient temperature between 35°F and 85°F (1.6°C to 29°C). Additionally, units using a remote condenser must be operated at outdoor ambient temperatures of:
MC condensers—above 0°F (18°C)
Liebert Lee-Temp™condensers—above -20°F (-29°C)
This product must be connected to and powered by suitable AC supplies, rated in accordance with the unit’s serial tag. It must be properly grounded and protected by circuit breakers or fuses.
The SmartRowDCR must be installed on a flat, level surface for proper assembly and operation.
We recommend using shielded cables for all external communication interfaces.
Ensure that the SmartRow DCR has proper ventilation. Never block or insert objects into the ventilation holes or other openings. Maintain minimum clearances as specified in this manual (see Clearance
Requirements on page13 and Unit Dimensions, Weights, and Wiring Tables on page78).
WARNING! Risk of handling heavy unit. Can cause equipment damage, injury or death. Read all instruction before beginning.
WARNING! Risk of top-heavy unit falling over. Improper handling can cause equipment damage, injury or death. Only properly trained and qualified personnel wearing appropriate safety headgear, gloves, shoes and glasses should attempt to move, lift, remove packaging from or prepare unit for installation. Read all instructions before attempting to move, lift, remove packaging from or preparing unit for installation.
Vertiv | SmartRow DCR Installer/User Guide | 7
Page 8
Table 1.1 Glossary of Symbols
SYMBOL DESCRIPTION
Hazardous voltage present
Indicates c aution f ollowed by important instructions
Requests t he user to consult the manual
Indicates weight
Equipment grounding conductor
Bonded t o ground
Alternating-current (AC) voltage
Vertiv | SmartRow DCR Installer/User Guide | 8
Page 9

2 INTRODUCTION

The SmartRow DCR is an integrated component of the SmartRow™offering from Vertiv™. The system includes a closed-loop, integrated cooling system and fire suppression. Assembly is a matter of connecting the plenums and cabinets, then making electrical and piping connections.
The SmartRow DCR is available in three basic cooling configurations:
20-kW (N) Configuration—3- to 6-rack system capable of removing up to 20kW of heat (single LiebertPDX/PCW).
20-kW (N+1) Configuration—3- to 6-rack system capable of removing up to 20kW of heat (redundant LiebertPDX/PCW).
36-kW (N) Configuration—5- to 10-rack system capable of removing up to 36kW of heat (dual LiebertPDX/PCWs).
Each configuration has different requirements and recommendations for setup and operation. Those requirements are integral to effective operation of a SmartRow DCR.
The SmartRow DCR must be installed in an indoor, climate-controlled environment. The unit will not protect electronic equipment if it is installed in an environment subject to extreme temperatures or humidity.
This manual is to be used in conjunction with existing Vertiv™ product manuals for each component and site-specific documentation and drawings. User and installation manuals ship with the equipment and are also available at http://www.VertivCo.com/en-us/support/.

2.1 Operational Overview

The SmartRow DCR is an enclosed system to house and cool electronic equipment. The DCR racks house the critical IT equipment, optional Rack PDUs and optional rack-mounted UPS units.
Cooling air is supplied by an integral Liebert PDX/PCW and conveyed to the racks with bottom plenums. Heated exhaust air from the racks returns to the Liebert PDX/PCW through the top plenums. An emergency fan system is included to exhaust air in the event of excessive internal temperature or a primary cooling failure.
The DCR Control Panel and Fire Suppression System module contains the fire detection and suppression system, fire strobe light and audible horn, the power/fire control interface, fire-suppression-system abort and manual-release switches, emergency fan-reset controls, and the load-distribution center. The fire-detection system uses a smoke detector to monitor the air in the SmartRow DCR for evidence of combustion. If the smoke detector mounted in the return air plenum senses combustion products, the system control activates audible and visual alarms and releases a fire-suppression agent (see Figure 7.1 on page61). The load-distribution center distributes power to powered loads inside the SmartRow DCR.
2.2 DCR Control Panel andFire-suppressionSystemCommissioningandTraining
A local qualified service representative will commission and arm the DCR Control Panel and Fire Suppression System after the SmartRow DCR is fully installed and operational. The representative will conduct training on the system during the same visit. The commissioning, arming and training cannot be performed before all items in Cooling and Power Component Installation Checklist on page67, and Fire
Suppression System Installation Checklist on page68, have been completed.
Vertiv | SmartRow DCR Installer/User Guide | 9
Page 10

2.3 SmartRow DCR Components

Required components differ based on whether the SmartRow DCR employs a single Liebert PDX/PCW or two Liebert PDX/PCWs.
DCR Base Plenum-Rack (with Manual Air-flow Adjustment Damper)—one for each DCR rack
DCR Top Plenum-Rack (with Emergency Fan)—one for each DCR Rack
DCR Base Plenum-PDX/PCW (with Back-draft Dampers)—installs under each Liebert PDX/PCW and DCR Control Panel and Fire Suppression System
DCR Top Plenum-PDX/PCW—installs on each Liebert PDX/PCW and DCR Control Panel and Fire Suppression System
DCR Control Panel and Fire Suppression System—consists of the fire detection panel, fire­suppression system, override timers, load-distribution center, fire strobe/horn and the power/fire control interface
Liebert PDX/PCW—5-ton downflow unit specially configured for use in the SmartRow DCR
DCR Rack—Plexiglas® front door, split solid rear door, sealed rack design; number varies. Standard configuration includes 1 networking rack, 800-mm wide, and the remaining quantity are server racks, 700-mm wide. See DCR 700-mm wide cabinet and DCR 800-mm wide cabinet in Technical-installation Illustrations on page81.
Redundant DCR Control Shell—attaches to the second Liebert PDX/PCW; houses the optional redundant load-distribution center
Vertiv | SmartRow DCR Installer/User Guide | 10
Page 11
Figure 2.1 SmartRow DCR components
Table 2.1 SmartRow DCR Components
NO. DESCRIPTION NO. DESCRIPTION
1 Emergency Fans 5
2 DCR Top Plenum-PDX/PCW 6 4-rack 20kW (N) SmartRow DCR shown
DCR Control Panel
3
and Fire-suppression System, PDX/PCW
4 DCR Base Plenum-PDX/PCW 8 DCR Top Plenum(s)-Rack

2.4 Liebert PDX/PCW Notes

Specially configured for SmartRow DCR applications
Does not include reheat or humidifier
Includes a condensate pump field-installed.
Liebert PDX/PCW can be factory-configured for either top feed or bottom feed for piping/electrical feeds; this must be specified at time of order
5 ton, digital scroll, downflow unit
Factory-installed, field-mounted leak detection
Large Liebert iCOM with monochrome display
Liebert PDX/PCW cooling unit (a s econd cooling unit att aches at opposite end for20-kW (N+1) and 36-kW configurations)
7 DCR Base Plenum(s)-Rack
Vertiv | SmartRow DCR Installer/User Guide | 11
Page 12
This page intentionally left blank.
Vertiv | SmartRow DCR Installer/User Guide | 12
Page 13

3 PREPARATION

The application and installation location should be determined and prepared before the SmartRow DCR is delivered. Proper planning will permit installing the required power and coolant connections and ensuring proper clearances. The installation location must have:
An indoor, climate-controlled environment free from moisture, flammable liquids, gases, and corrosive substances.
An environment that is maintained year-round at an ambient temperature between 35°F and 85°F (1.6°C to 29°C) and a relative humidity between 50°F and 85°F dry bulb and less than 60°F dew point.
Sufficient height and clearance from ceilings, walls, fixtures and overhead sprinkler nozzles for the SmartRow DCR, including its emergency fans
NOTE: The SmartRow DCR must be installed on a flat, level surface to maintain proper spacing and provide tight seals. Leaving gaps in the field-applied gaskets will reduce cooling efficiency, increase energy use and adversely affect fire-suppression system operation.
Heat rejection coolant supply for the Liebert PDX/PCW
Input power sufficient for:
Each Liebert PDX/PCW—one or two units; each requires a separate input power feed.
DCR Control Panel and Fire Suppression System, Emergency Fans and powered equipment installed in the DCR racks
For details about any component’s requirements, refer to that unit’s user manual. The Liebert PDX/PCW installation manual is SL-19800; Liebert iCOM™ user manual is SL-18835. These are delivered with the unit and are available at http://www.VertivCo.com/en-us/support/.

3.1 Clearance Requirements

See SmartRow DCR dimension details in Technical Data on page78.
Table 3.1 SmartRow DCR system clearances—Single or Dual Liebert PDX/PCWs
DCR COMPONENT MINIMUM CL EARANCE REQUIRE MENT, IN.(MM)
DCR Control Panel & Fire Suppression Sys tem
PDX/PCW CoolingUnit 36 (914) front
Any DCR surface and the nearest building fire-suppression sprinkler head. 18 (457) per NFPA 13
DCR Emergency Fan discharge and nearest surface 16 (406) air-flow clearance
36 (914) front

3.2 Inspection

Upon receiving a SmartRow DCR, examine the packaging for any signs of mishandling or damage. If any damage is noted, notify your local Vertiv™ representative and the carrier immediately.

3.3 Unloading the SmartRow DCR

Before unloading the SmartRow DCR, refer to the manual for each component, particularly the Liebert PDX/PCW and DCR Racks. These manuals are shipped with the SmartRow DCR and are available at http://www.VertivCo.com/en-us/support/.
Vertiv | SmartRow DCR Installer/User Guide | 13
Page 14
Read these manuals thoroughly. They include handling instructions and safety notices that must be followed when unpacking, installing, operating and maintaining the SmartRow DCR.
Adhere to all warnings, cautions and installation, operating and safety instructions on the units and in their manuals. Only properly trained and qualified personnel should move, install, operate or service this equipment.

3.4 Required Set-up Tools and Equipment

The following tools are needed to set up a SmartRow DCR:
3/4-in. (19-mm) open end wrench or socket
Ratchet to fit sockets
Phillips-head screwdriver
Flat-blade screwdriver
Forklift or pallet jacks
Scissors or knife
Carpenter’s level, 3-ft long or longer

3.5 Heat Load Guidelines

Notice
Risk of exceeding cooling capability. Can cause equipment damage.
A SmartRow DCR 20-kW (N) configuration (one PDX/PCW cooling unit) or 20-kW (N+1) configuration (two PDX/PCW cooling units) is capable of removing 20 kW of heat. A SmartRow DCR 36-kW (N) configuration (two PDX/PCW cooling units) can remove 36kW of heat. Exceeding that heat load limit, such as by overloading the DCR racks, can cause equipment in the cabinets to overheat, resulting in equipment damage and voiding warranties.
Refer to the values in Table 3.2 below. The total system capacity and heat loads per cabinet must fall withing these ranges. We recommend that higher-density loads be located in the center of the SmartRow configuration. This avoids the need to manually adjust the air dampers when thermal-management units switch in 2-unit configurations.
Table 3.2 Average heat load per cabinet
20-KW (N/N + 1 ) CONFIGURATION HEAT L OAD PER CABINET 36 -KW (N) CONFIGURATION HEAT LOA D PE R CABINET
NUMBER OF
CABI NETS
3 1.2 6 5 1.4 7
4 0.9 5 6 1.2 6
5 0.7 4 7 1.0 5
6 0.6 3 8 0.9 5
9 0.8 4
10 0.7 4
MINIMUM, KW MAXIMUM, KW
NUMBER OF
CABI NETS
MINIMUM, KW MAXIMUM, KW
Vertiv | SmartRow DCR Installer/User Guide | 14
Page 15

4 INSTALLATION

4.1 Assembly Sequence Overview

Typical SmartRow DCR assemblies with a single thermal-management unit are configured with the Control Panel and Fire Suppression system and the thermal-management unit on the right-hand side. To configure your assembly with the panel and unit on the left-hand side, start with Configuring
theSmartRowDCRforLeft-to-Right Assembly on the next page, then continue with the subsequent
instructions.
4.1.1 SmartRow DCR withSingleLiebertPDX/PCW(20-kW(N)Configuration)
Refer to Figure 4.1 below components and follow the procedures in the subsequent sections to assemble theSmartRow DCR.
Figure 4.1 Components of single Liebert PDX/PCW system installation
NO. DESCRIPTION NO. DESCRIPTION
1 Emergency Ventilation Fans 5
2 DCR Top Plenum-PDX/PCW 6 DCR network rack
DCR Control Panel
3
and Fire-suppression System
4 DCR Base Plenum-PDX/PCW 8 DCR Top Plenum(s)-Rack
Vertiv | SmartRow DCR Installer/User Guide | 15
Liebert PDX/PCW sect ion (cooling unit behind control panel/fire­suppression syst em.)
7 DCR server racks
Page 16
4.1.2 Configuring theSmartRowDCRforLeft-to-Right Assembly
These steps are only needed if you have a single thermal-management-unit configuration and you want to mount the unit and the Control Panel and Fire Suppression system on the left-hand side of the SmartRow assembly. You are modifying the base and top plenums for the control panel/thermal­management unit for installation on the opposite end of the SmartRow.
1. Modify the Base Plenum-PDX/PCW (DCR-A-300 PDX):
a. Remove the cover plate on the right-hand side of the Base Plenum-PDX/PCW, and set it
aside tobe installed on the base plenum of the final rack on the opposite end of the row.
b. Move the (2) Back-draft Dampers on the left-hand side of the plenum to the right-hand
side of the plenum as shown Figure 4.2 below.
c. Move the (4) Hex stand-offs from the left-hand side of one of the Base Plenums-Rack
(DCR-A-101) and install them on the right-hand side of the Base Plenum-PDX/PCW (DCR-A-300PDX), see Figure 4.2 below. The Base Plenum-Rack without the stand-offs is now the base plenum that will be positioned on the opposite end of the row with the cover plate installed on its right-hand side.
Figure 4.2 Modifying Base Plenum-PDX/PCW for installation on left-hand side of SmartRow
NO. DESCRIPTION NO. DESCRIPTION
1 Cover plate 4 Base plenum-PDX/PCW after modification
2 Back-draft dampers 5 Base plenum-PDX/PCW before modification
3 Hex stand-off hardware (4 places)
Vertiv | SmartRow DCR Installer/User Guide | 16
Page 17
2. Modify the Top Plenum PDX/PCW (DCR-A-400PDX):
a. Remove the cover plate on the right-hand side of the Top Plenum-PDX/PCW, Figure 4.3
below, andsetit aside to be installed on the top plenum of the final rack on the opposite end of the row.
b. Move (4) Hex Standoffs from the left-hand side of one of the Top Plenums-Rack
(DCR-A-200) andinstall them on the right-hand side of the Top Plenum-PDW/PCW (DCR-A-400PDX), seeFigure 4.3 below. This Top Plenum-Rack without the stand-offs is now the top plenum that will be positioned on the opposite end of the row with the cover plate installed on its right-hand side.
3. Continue with the installation procedures, starting with Install the DCR Base Plenum-PDX/PCW
First on the next page.
Figure 4.3 Modifying Top Plenum-PDX/PCW for installation on left-hand side of SmartRow
NO. DESCRIPTION NO. DESCRIPTION
1 Cover plate 3 Top plenum-PDX/PCW after modification
2 Hex stand-off hardware (4 places) 4 Top plenum-PDX/PCW before modification
Vertiv | SmartRow DCR Installer/User Guide | 17
Page 18
4.1.3 SmartRow DCR with Two Liebert PDX/PCW Units—20-kW(N+1)/36-kW(N) Configurations
Refer to Figure 4.4 below components and starting with Install the DCR Base Plenum-PDX/PCW First below, follow the procedures in the subsequent sections to assemble the SmartRow DCR.
Figure 4.4 Componentsof two Liebert PDX/PCW installation
NO. DESCRIPTION NO. DESCRIPTION
1 DCR Top Plenum(s)-Rack 6
2 Emergency Ventilation Fans 7 DCR network rack
3 DCR Top Plenum(s)-PDX/PCW 8 DCR server racks
DCR Control Panel
4
and Fire-suppression System
5 DCR Base Plenum-PDX/PCW
PDX/PCW sections (thermal-management unit behindControl Panel and F ire-suppression system/DCR Control-panelshell)
9 DCR Control-panel Shell

4.2 Install the DCR Base Plenum-PDX/PCW First

NOTE: This Base Plenum for the PDX/PCW must be installed first and positioning is critical to the remaining installation.
1. Position the DCR Base Plenum-PDX/PCW where the power and refrigerant connections can be made easily.
Connections will be made either through the DCR Top Plenum-PDX/PCW or the DCR Base Plenum-PDX/PCW, depending on the Liebert PDX/PCW system selected. This selection correlates with the selection of a top-fed unit/bottom-fed unit. (The top and base plenums for the Liebert PDX/PCW and DCR Control Panel and Fire Suppression System module are wider than the plenums for the DCR racks (DCR Base Plenum-PDX/PCW or DCR Top Plenum-PDX/PCW).
Vertiv | SmartRow DCR Installer/User Guide | 18
Page 19
2. Check the DCR Base Plenum-PDX/PCW installation position to ensure that it meets the required clearances; refer to Clearance Requirements on page13.
NOTICE
Risk of severe cabinet and system stress. Can cause equipment damage and improper operation.
Do not move the SmartRow DCR after assembly. This unit is not designed to be moved after assembly. Movement without properly disassembling the SmartRow DCR can damage internal components, reduce unit stability and void the warranty.
Floor anchoring, if required, should not be performed until after the entire base plenum assembly has been completely assembled and leveled.
3. Remove the plenum side plate cover attached on the interior of the Primary DCR BasePlenum-PDX/PCW (DCR-A-300PDX). This will be installed on the last base plenum in the row.

4.3 Assemble the DCR Base Plenums-Rack

The base plenum-rack assembly supports the SmartRow DCR and distributes supply air to the DCR Racks.
1. Apply the factory-supplied, D-shaped gasket material to the side of the DCR Base Plenum­Rack that faces the DCR Base Plenum-PDX/PCW as shown in Figure 4.5 below.
The gaskets are cut to the correct length at the factory.
The gasket must be applied continuously along the profile edge of the plenum frame.
Apply pressure to the gasket to make sure it adheres to the frame.
2. At each corner, form a 1-in. to 1.5-in. radius, Figure 4.5 below.
3. When you reach the starting point, form a sealed joint by butting the start and finish edges together, Figure 4.5 below.
Figure 4.5 Gasket applied to side of base plenum
NO. DESCRIPTION
1 Gasket 1-in. to 1.5-in. corner radius
2 Gasket start and finish
Vertiv | SmartRow DCR Installer/User Guide | 19
Page 20
4. Place the first DCR Base Plenum-Rack beside the DCR Base Plenum-PDX/PCW. Ensure that gasket side of the DCR Base Plenum-Rack faces theDCRBasePlenum-PDX/PCW,Figure 4.6 below:
The front of each DCR Base Plenum-Rack must be oriented with the rack placement inmind.
The front of the DCR Base Plenum-Rack has louvers.
The front of the DCR Racks have a door with a transparent acrylic sheet.
Figure 4.6 Correct orientation of base plenum sections and required side gaskets
NO. DESCRIPTION
1 Gasket
2 DCR base plenum
3 Rack base plenums
4 Side plate cover (shippedloose)
5. Attach the DCR Base Plenum-Rack to the DCR Base Plenum-PDX/PCW with (4) 9-mm long spacers that are factory-installed on the right-hand side of each rack plenum.
6. Using the factory-supplied Nylock nut and washer, secure the plenum faces together but do not tighten them at this time.
IMPORTANT! Do not tighten any Nylock nuts at this time. The Nylock nuts must remain loose to permit additional assembly steps.
7. Apply gaskets to the remaining DCR Base Plenums-Rack, referring to Figure 4.6 above, then attach each plenum to the adjacent plenum assembly with the factory-installed spacers and factory-supplied Nylock nuts and washers.
8. If installing system with a single PDX/PCW unit, attach the shipped-loose, side plate cover to the outside of the final base plenum (see Figure 4.6 above).
– or –
If installing a second PDX/PCW unit, do not install the side plate cover until instructed to do so in section Installing a Second PDX/PCW (20-kW(N+1)/36-kW(N)Configuration) on page36.
9. Use a 3/4-in. (19-mm) wrench to adjust the leveling feet so that the assembled base plenum is level. Use a carpenter’s level to make sure the plenum assembly is completely level both front­to-rear and side-to-side, Figure 4.7 on the facing page.
Vertiv | SmartRow DCR Installer/User Guide | 20
Page 21
10. When the complete base plenum assembly is level, use the 3/4” (19-mm) wrench to tighten the jam nuts against the bottom of the plenum assembly to secure the leveling feet, Figure 4.7 below.
Figure 4.7 Level plenum using carpenter’s level and wrench to adjust and lock feet
NO. DESCRIPTION
1 Carpenter’s level
2 Jam nut
3 Height-adjustment nut
11. Tighten all internal plenum Nylock nuts installed in step 5 using an M10 socket.
NOTE: Floor anchoring, if required, should not be done until after all steps above have been completed. Floor anchoring is optional. Hardware for this step is not included. For further information, contact your local Vertiv™ representative.
4.4 Set the PDX/PCW on the Base Plenum-PDX/PCW andInstallCondensatePumpandLiqui-tectSensor
There is factory-installed gasketing around the perimeter of the top face of the DCR Base Plenum­PDX/PCW. The PDX/PCW will rest on the area highlighted in Figure 4.8 on the next page. The Liebert iCOM screen must face the opposite side of where the DCR Control Panel and Fire Suppression System will sit, see Figure 4.8 on the next page.
NOTE: Take care not to damage the gasket when setting the PDX/PCW and the Control Panel and Fire Suppression System on the Base Plenum.
Vertiv | SmartRow DCR Installer/User Guide | 21
Page 22
Figure 4.8 Equipment locations on the Base Plenum-PDX/PXW
NO. DESCRIPTION
1 PDX/PCW location
2 DCR control panel and fire-suppression syst em location
To install the unit and pump:
1. Ensure the front, left, and right sides of the PDX/PCW are accessible by removing the panels oftheunit.
2. Remove the Condensate Pump Box and the Pump components boxes located in the rear of the unit.
Vertiv | SmartRow DCR Installer/User Guide | 22
Page 23
3. Verify that the condensate pump components box contains the items shown in Figure 4.9 below and listed in Table 4.1 below.
Figure 4.9 Condensate Pump Components Box
Table 4.1 Pump Components
ITEM NO. DESCRI PTION QTY.
17 Clamp hose wire 1
105 Ell 90 compression x compression 1/2” x 1/2” 1
106 1/2” tube form 1
107 Bracket, condensate pump 2
108 Screw self-driller 8-18 x 1/2” 6
109 Bag plastic zip-lock 1
110 Corrugated box 1
113 Instruction/Installation drawing 1
Vertiv | SmartRow DCR Installer/User Guide | 23
Page 24
4. Remove one of the Condensate Brackets (107) and two of the Self-Driller 8-18x1/2” screws (108) from the box.
5. Use the two self driller screws to screw the bracket in to Position 1, Figure 4.10 below. The hole positions are labeled on the foam with silver markings.
Figure 4.10 Condensate-pump brackets and Liqui-tect sensor installation locations
NO. DESCRIPTION
1 Position 1
2 Position 2
3 Position 3
6. Remove the condensate pump with the wire harness from the box.
7. Position the pump with the electric-box side of the condensate pump facing towards the bracket in Position 1.
NOTE: Lay the pump on its side so that the pump does not get damaged when installing the PDX/PCW unit on top of the Base Plenum.
Vertiv | SmartRow DCR Installer/User Guide | 24
Page 25
8. Use pallet jacks or a similar lifting device to place the PDX/PCW on the Base Plenum-PDX/PCW so that the iCOM display is facing 180 degrees from where the DCR Control Panel and Fire Suppression system will sit (See Components of single Liebert PDX/PCW system installation on page15).
The PDX/PCW must be aligned with the back of the base plenum that supports it. The PDX/PCW also should be flush with the side of the DCR Base Plenum-PDX/PCW.
WARNING! Risk of personal injury. Can cause equipment damage, injury or death. The Liebert PDX/PCW weighs more than 600lb. (272kg). If a lifting device is used to move the PDX/PCW, ensure that it is rated to handle its weight. If personnel willmove the unit manually, ensure that an adequate number of properly trained and qualified personnel are used. Read all instructions before beginning.
WARNING! Make sure that the Condensate Pump is laying on its side to ensure that the pump does not get cracked or damaged during the installation of the PDX/PCW unit.
WARNING! Risk of top-heavy unit falling over. Improper handling can cause equipment damage, injury or death. Only properly trained and qualified personnel wearing appropriate safety headgear, gloves, shoes and glasses should attempt to move, lift, remove packaging from or prepare unit for installation. Read all instructions before attempting to move, lift, remove packaging from or preparing unit for installation.
9. Locate the hole(s), shown in Figure 4.11 below, in the bottom of PDX/PCW, and insert the four supplied carriage bolts (3/8”-16x1-1/2”). Then from underneath the base-plenum, install andtightenthehexnuts and washers.
Figure 4.11 Secure the Liebert PDX/PCW to the DCR Base Plenum-PDX/PCW
NO. DESCRIPTION
1 Hole (in each corner)
Vertiv | SmartRow DCR Installer/User Guide | 25
Page 26
10. Remove the panel on the rear of the Base plenum–PDX/PCW.
11. Locate the Liqui-tect Sensor cable tied to the PDX/PCW EC-motor impeller wheel, cut the cable ties, and place the Liquitect 410 sensor in Position 2 (shown in Figure 4.10 on page24).
12. Remove 2 of the 8-18 x ½” self-driller screws from the pump components box, and screw the LT410sensor into Position 2.
13. Re-position the condensate pump right-side up and place it against the condensate-pump bracket in Position 1 (installed in step 5 and shown in Figure 4.10 on page24).
14. On the left-hand side of the PDX/PCW, un-clamp the rubber drain line from the drain-line bracket.
15. Remove the clamp-hose wire from the pump-components box, slip it onto the drain line, and insert the rubber drain line on to the barbed end connection of the condensate pump. (See Figure 4.12 on the facing page for proper positioning.)
16. Re-clamp the drain line to the drain-line bracket referenced in step 14.
17. Remove the 90° compression fitting elbow (105) from the pump components box and install it onto the ½-in. Copper drain line that routes to the top of the unit. (See Figure 4.12 on the facing page for proper positioning.)
18. Remove the ½” tube form (106) from the pump components box. Install the tube form into the 90compression fitting on the condensate pump. (See Figure 4.12 on the facing page for proper positioning)
19. Remove the remaining condensate-pump bracket (107) and two 8-18x1/2” self driller screws (108) from the pump-components box, position the bracket against the condensate pump, and screw the bracket into Position 3 (shown in Figure 4.10 on page24) using the self-driller screws.
Vertiv | SmartRow DCR Installer/User Guide | 26
Page 27
20. Refer to Figure 4.12 below as a final check of your condensate pump installation.
21. Route the wire harness from the condensate pump to the electric box, and connect it to the condensate-pump fuse block.
Figure 4.12 Condensate-pump installation
NO. DESCRIPTION NO. DESCRIPTION
1 1/2-in. copper drain line 4 Rubber drain line
2 Condensate pump wire harness 5 Right s ide
3 1/2-in. copper drain line 6 Front of unit
Vertiv | SmartRow DCR Installer/User Guide | 27
Page 28
4.5 Set the DCR Control Panel andFireSuppressionSystemonthe Base Plenum
WARNING! Risk of personal injury. Can cause equipment damage, injury or death. The DCR Control Panel and Fire Suppression System weighs more than 413lb. (187kg). If a lifting device is used to move the DCR Control Panel and Fire Suppression System, ensure that it is rated to handle its weight. If personnel will move the unit manually, ensure that an adequate number of personnel are used. Only properly trained and qualified personnel wearing appropriate safety headgear, gloves, shoes and glasses should attempt to move, lift, remove packaging from or prepare the unit for installation. Read all instructions before attempting to move, lift, remove packaging from or prepare unit for installation.
WARNING! Risk of top-heavy unit falling over. Improper handling can cause equipment damage, injury or death. Only properly trained and qualified personnel wearing appropriate safety headgear, gloves, shoes and glasses should attempt to move, lift, remove packaging from or prepare unit for installation. Read all instructions before attempting to move, lift, remove packaging from or preparing unit for installation.
1. Apply gasket (1/2-in. thick x 2-in. wide; factory-supplied, Part # 8694K89) along the outside edge of the Liebert PDX/PCW that the DCR Control Panel and Fire Suppression System will rest against (see Figure 4.13 on the facing page). Use a lifting device to place the DCR Control Panel and Fire Suppression System onto the DCR Base Plenum-PDX/PCW.
The DCR Control Panel and Fire Suppression System must be aligned with the front of the DCR Base Plenum-PDX/PCW.
The fire-suppression section will be flush against the Liebert PDX/PCW and the end of the DCR Base Plenum-PDX/PCW.
2. Bolt the DCR Control Panel and Fire Suppression System to the base plenum with the (6)factory-supplied 1/4-in. - 20 x 1-in. Hex Head Cap screws and washers.
Vertiv | SmartRow DCR Installer/User Guide | 28
Page 29
Figure 4.13 Gasket application between PDX/PCW and DCR Control Panel/Fire-suppression System
NO. DESCRIPTION
1 Control panel and f ire-suppression sy stem
2 PDX/PCW
3 Gasket

4.6 Install the DCR Racks on the Base Plenums

The SmartRow DCR Network rack, 800-mm wide, and one of the server racks, 700-mm wide, ship with both solid and cable-pass-through split-side panels. The remaining DCR server racks ship with cable­pass-through split-side panels on both sides. When you choose rack orientation, make sure that the solid split-side panels are on the ends of the rows. The figures in this manual are shown with the Network Rack, 800-mm wide, next to the primary PDX/PCW system.
Vertiv | SmartRow DCR Installer/User Guide | 29
Page 30
Figure 4.14 Panel and Gasket placement—one PDX/PCW (20-kW(N)Configuration
NO. DESCRIPTION NO. DESCRIPTION
1 Solid split-side panel 4 Gasket, field-installed
2 Cable-pass-throughsplit-side panel 5 PDX/PCW, Control Panel andFire-suppression System
3 Cable-pass-throughsplit-side panels onboth sides of rack 6 Gasket, factory-installed aroundeachbaseplenum
Vertiv | SmartRow DCR Installer/User Guide | 30
Page 31
Figure 4.15 Panel and Gasket placement—two PDX/PCW units (20-kW(N+1)/36-kW (N))Configuration
NO. DESCRIPTION NO. DESCRIPTION
1 Solid split-side panel 5 PDX/PCW, Control Panel andFire-suppression System
2 Cable-pass-throughsplit-side panel 6 Gasket, fact ory-installed aroundeachbaseplenum
3 Cable-pass-throughsplit-side panels onboth sides of rack 7 PDX/PCW and Control-panel shell
4 Gasket, field-installed
To install the racks:
1. Find the DCR rack that has the two solid split-side panels on one side and cable-pass-through panels on the other to place next to the PDX/PCW and Control Panel/Fire-suppression System (shown in Figure 4.14 on the previous page or Figure 4.15 above).
2. Apply the supplied gasketing to the rack's frame profile edge as shown Figure 4.16 on the next page:
Start the gasket strip at the base of the rack, directly in the middle of the rack.
Using pressure to make sure it adheres to the frame, apply the gasket continuously following the profile edge of the rack’s frame.
At each corner, make a 1-in. to 1.5-in. radius.
Create a sealed joint by butting the start and finish edges together.
NOTE: Tags have been provided in each rack that illustrate these instructions as well. Do not remove these tags until the SmartRow assembly is completed.
Vertiv | SmartRow DCR Installer/User Guide | 31
Page 32
Figure 4.16 Applying gasket to profile edge on side of the rack
NO. DESCRIPTION
1 Gasket 1-in. to 1.5-in. corner radius
2 Gasket start and finish
3. Use an adequate number of personnel to install that rack on the Base Plenum that is adjacent to the Liebert PDX/PCW and DCR Control Panel & Fire Suppression System.
NOTE: The side panels are interchangeable among the racks. Make sure that the rack that will be next to the PDX/PCW and Control Panel has the solid split-side panels on one side, as described in step 1.
NOTE: Removing the rack’s front and rear doors will lighten the unit, making it easier to maneuver.
When setting DCR Racks on the base plenum, be sure to:
a. Align the front frame of the rack to the control-panel frame.
b. Space the DCR Racks evenly and square with the side of each DCR Base Plenum-
Rack.
NOTE: Take care not to damage the gasket when applying it and when setting the DCR Racks on the base plenum. If the gasket is damaged, the rack must be removed and the gasket replaced. A damaged gasket will permit cooling air to escape, which will reduce cooling efficiency, increase energy use and adversely affect fire-suppression system operation.
4. Repeat steps 2 and 3 for each rack with cable-pass-through split-side panels on both sides of the rack (Figure 4.14 on page30 or Figure 4.15 on the previous page).
5. Repeat steps 2 and3 for the rack with left-side solid split-side panels (Figure 4.14 on page30 or Figure 4.15 on the previous page).
6. Bay each adjacent rack with supplied baying plate and hardware, (2) plates front and back.
Vertiv | SmartRow DCR Installer/User Guide | 32
Page 33

4.7 Install the Top Plenum-PDX/PCW

1. Remove the plenum side plate cover attached on the interior of the Primary DCRTopPlenum-PDX/PCW (DCR-A-400PDX). This side plate cover will be installed on side of the last top plenum intherow.
2. Set the DCR Top Plenum-PDX/PCW on the top of the PDX/PCW and DCR Control Panel andFireSuppression System.
NOTE: Take care not to damage the gasket when setting the DCR Top Plenum-PDX/PCW on the top of the Liebert PDX/PCW and DCR Control Panel and Fire Suppression System. If the gasket is damaged, the plenum must be removed and the gasket replaced. A damaged gasket will permit cooling air to escape, which will reduce cooling efficiency, increase energy use and adversely affect fire-suppression system operation.
3. Secure the plenum to the Control Panel and Fire Suppression system using the factory­supplied (6)1/4-in.–20screws, nuts and washers through the top plenum and into the (6) factory-installed nutinserts in the Control Panel and Fire Suppression system.
4. Secure the rear of the plenum to the PDX/PCW using the factory-supplied carriage bolts.

4.8 Mounting the Top Plenums-Rack

1. Referring to Figure 4.17 below, start at the center, bottom and apply D-shaped gasket material to the side ofthe DCRTopPlenum-Rack that faces the DCR Top Plenum-PDX/PCW (shown in Figure 4.19 on page35):
The gaskets are cut to the correct length at the factory.
Apply the gasket continuously along the profile edge of the plenum frame.
Apply pressure to the gasket to make sure it adheres to the frame.
2. At each corner, make a 1-in. to 1.5-in. radius, Figure 4.17 below.
3. When you reach the starting point, form a sealed joint by butting the start and finish edges together asshown in Figure 4.17 below.
Figure 4.17 Gasket applied to face of top plenums
NO. DESCRIPTION
1 Gasket 1-in. to 1.5-in. corner radius
2 Gasket start and finish
Vertiv | SmartRow DCR Installer/User Guide | 33
Page 34
4. Install edge guard on the bottom edge of the two openings in the top plenum by pressing the guard onto the edge as shown in Figure 4.18 below.
Figure 4.18 Edge guard installation
NO. DESCRIPTION
1 Edge guard
Vertiv | SmartRow DCR Installer/User Guide | 34
Page 35
5. Place the first DCR Top Plenum-Rack beside the DCR Top Plenum-PDX/PCW, and ensure that gasket side of the Top Plenum-Rack faces the Top Plenum-PDX/PCW, Figure 4.19 below.
Figure 4.19 Correct orientation of top plenum sections and required side gaskets
NO. DESCRIPTION
1 Side plate cover (shippedloose)
2 Rack top plenums
3 Gasket
4 PDX/PCW t op plenum
Vertiv | SmartRow DCR Installer/User Guide | 35
Page 36
6. Attach the Top Plenum-Rack to the DCR Rack:
Position the top plenum over the 4 attachment points on the top of the rack, see Figure
4.20 below.
Secure the plenum with the factory-supplied washers and hex nuts.
Figure 4.20 Plenum attachment point example on top of rack
NO. DESCRIPTION
1 Attachment point
7. Attach the plenums together:
Use the (4) 9-mm long spacers that are factory-installed on the left-hand side of each plenum
Use factory-supplied locknut and washer to secure the plenum faces together.
8. Repeat steps 6 to 7 for each of the remaining top plenums. There is one DCR Top Plenum-Rack for each DCR Rack.
9. Attach the shipped-loose, side plate cover to the outside of the final top plenum in the row (see Figure 4.19 on the previous page).
4.9 Installing a Second PDX/PCW (20-kW(N+1)/36-kW(N)Configuration)
To install a second Liebert PDX/PCW:
1. On the secondary DCR Base Plenum-PDX/PCW (DCR-A-301PDX), apply D-shaped gasket to the side that faces the adjacent DCR rack.
The gaskets are cut to the correct length at the factory.
Apply the gasket continuously along the profile edge of the plenum frame.
Apply pressure to the gasket to make sure it adheres to the frame.
At each corner, form a 1-in. to 1.5-in. radius.
When you reach the starting point, form a sealed joint by butting the start and finish edges together.
Vertiv | SmartRow DCR Installer/User Guide | 36
Page 37
2. Attach the secondary Base Plenum-PDX/PCW to the adjacent Base Plenum-Rack with the 4 factory-supplied Nylock nuts.
NOTE: Take care not to damage the gasket when setting the Liebert PDX/PCW on the DCR Base Plenum-PDX/PCW. If the gasket is damaged, the cooling unit must be removed and the gasket replaced. A damaged gasket will permit cooling air to escape, which will reduce cooling efficiency, increase energy use and adversely affect fire-suppression system operation.
3. Attach the shipped-loose side plate cover to the outside of the secondary Base Plenum­PDX/PCW.
4. Level the secondary Base Plenum-PDX/PCW with other base plenums.
5. Apply D-shaped gasketing to the side of the DCR rack that is adjacent to the second PDX/PCW, if you have not already done so.
6. Use pallet jacks or similar lifting devices to place the second PDX/PCW on the secondary Base Plenum-PDX/PCW.
The PDX/PCW must be aligned with the back and outer edges of the base plenum that supports it.
Figure 4.21 20-kW (N+1)/36-kW (N) Liebert PDX/PCW option arrangement
NO. DESCRIPTION NO. DESCRI PTION
1 Gasket 3 Base plenum-PDX/PCW
Control panel and F ire-suppression system. PDX/PCW is installed behind
2
panel.
Control-panel s hell. Second PDX/PCW installed behind
4
shell.
7. Secure the PDX/PCW using the four factory-supplied carriage bolts, see Figure 4.11 on page25.
8. Apply supplied gasket material to the side of the PDX/PCW that the DCR Control Panel will rest against, see Figure 4.13 on page29.
Vertiv | SmartRow DCR Installer/User Guide | 37
Page 38
9. Use a pallet jack or an adequate number of qualified personnel to lift the DCR Control Panel Shell onto the secondary Base Plenum-PDX/PCW.
The DCR Control Panel Shell must be aligned with the front of the base plenum and will be flush with the end of the base plenum.
10. Bolt the DCR Control Panel Shell to the base plenum with the 6 factory-supplied 1/4-20x3/4bolts.
11. Apply D-shaped gasket to the side of the secondary Top Plenum-PDX/PCW facing adjacent DCR rack.
12. Install edge guard on the bottom half of the two openings on the secondary Top Plenum­PDX/PCW.
13. Set the secondary DCR Top Plenum-PDX/PCW on the top of the PDX/PCW and DCR Control Panel Shell, and secure it with 6 1/4-20x3/4 bolts.
NOTE: Take care not to damage the gasket when applying it and when setting the DCR Top Plenum-PDX/PCW on the top of the Liebert PDX/PCW and Redundant Control Shell. If the gasket is damaged, the cooling unit must be removed and the gasket replaced. A damaged gasket will permit cooling air to escape, which will reduce cooling efficiency, increase energy use and adversely affect fire-suppression system operation.

4.10 Installing and Wiring Sensors

DCR Return Temperature Thermostat—Activates emergency fans
Supply Air Temperature Sensor—For supply air temperature control
2T Sensor—Sense temperature of each rack; for load balancing
Smoke Detector—Senses combustion products in the return air to activate fire suppression
HVAC Fault/Emergency Fan Control, Thermal unit Shutdown
See Table 11.4 on page80 for SmartRow DCR field-wiring guidelines
4.10.1 Connect Return-temperature Thermostat, theL5-20ReceptacleandtheSmokeDetector
The DCR Return Temperature Thermostat and smoke detector are factory-installed in the DCR Top Plenum PDX/PCW. The L5-20 receptacle, which supplies power for the emergency fans, is factory­installed on the exterior of the DCR Top Plenum-PDX/PCW.
Wiring for the DCR Return-temperature thermostat, smoke detector, and supply power for the Emergency Fan's receptacle must be connected for these items to function properly. To facilitate this connection, a factory-supplied harness is located in the Control Panel and Fire Suppression cabinet. The wiring harness consists of three connector cables:
4-pin Smoke Detector connector cable
3-pin Emergency Fan supply-power connector (P1)
3-pin DCR Return Temperature thermostat connector (P3)
NOTE: The DCR Return Temperature Thermostat is used to activate the emergency fans in the event of a high return air temperature (98°F [37°C]).
The wiring harness is located in the control panel.
Vertiv | SmartRow DCR Installer/User Guide | 38
Page 39
To install and connect the wiring:
1. Locate the wiring harness in the DCR Control Panel and Fire Suppression System, and feed it through the rubber grommet into the DCR Top Plenum-PDX/PCW as shown in Figure 4.22 below.
2. Connect the wires to the appropriate connection points on the smoke-detector assembly as shown in Figure 4.22 below.
When connecting the Emergency Fan supply-power connector (P1) to its receptacle, it is easier to remove the top plate of the DCR Top Plenum-PDX/PCW, turn it upside down exposing the receptacle points, and making the connections.
Once the connections are made, return the top plate to its original position.
Figure 4.22 Wire connection points in the Top Plenum-PDX/PCW
NO. DESCRIPTION NO. DESCRIPTION
1 4-pin smoke-detector connector cable 6 4-pinsmoke-detector connector receptacle
2 3-pin emergency-fan supply-power c onnector cable (P1) 7 Rubber grommet
3 3-pin return-temperature thermostat connector cable (P3) 8 L5-20 receptacle
4 Smoke detector 9
5 3-pin return-temperature thermostat connector receptacle
3-pin emergency-fan supply-power c onnector receptacle (from top plate of DCR Top Plenum-PDX/PCW)
4.10.2 Connecting the Secondary Return-temperature Thermostat(P3R) for 20-kW (N+1)/36-kW (N) Configurations
1. Locate the wire harness with the secondary, 3-Pin return-temperature thermostat connector (P3R) in the Control Panel and Fire Suppression cabinet, and route the wire harness through the rubber grommet as shown in Figure 4.22 above.
2. In the Secondary Top Plenum-PDX/PCW, locate the 30-ft extension cable with the 3-pinconnector for the return temperature thermostat.
3. Connect one side of the extension cable to the 3-pin connector cable in the secondary Top Plenum-PDX/PCW.
4. Route the extension, through the Top Plenum-Rack(s) to the Primary Top Plenum-PDX/PCW, and connect this end of the extension to the 3-pin connector for the return-temperature thermostat.
Vertiv | SmartRow DCR Installer/User Guide | 39
Page 40
4.10.3 Connecting the Secondary PDX/PCW Smoke Detector tothePrimaryPDX/PCWSmokeDetector
1. In the secondary Top Plenum-PDX/PCW, locate the 30-ft extension cable with the black, 4-pin connector for the secondary PDX/PCW Smoke Detector.
2. Connect one end of the extension cable to the Smoke Detector connection point in the secondary Top Plenum-PDX/PCW.
3. Route the other end through the Top Plenum-Rack(s) to the primary Top Plenum-PDX/PCW, and connect this end of the cable to the smoke-detector connection point on TB2.

4.10.4 Install Supply Air Temperature Sensor

1. Locate the supply air-temperature sensor in the bottom, right-hand corner of the front of the PDX/PCW unit, and cut the wire ties securing it there. (The Supply Air Temperature Sensor is wired to the Liebert iCOM™ at the factory.)
2. Route the wiring into the middle of the second rack base plenum from the PDX/PCW, Figure
4.23 below.
3. Repeat steps 1 and 2 for a secondary PDX/PCW unit, if applicable.
Figure 4.23 Supply Air Temperature Sensor wiring routed through base plenum
NO. DESCRIPTION
1 Supply-air s ensor

4.10.5 Install and Wire 2T Sensors

2T sensors are factory-installed in the top, front of each rack.
1. Route the wire for both sensors in the front of the racks as shown in Figure 4.24 on the facing page:
Install one sensor probe in the middle of the rack.
Install one sensor probe near the top of the rack.
Vertiv | SmartRow DCR Installer/User Guide | 40
Page 41
2. Locate the coiled CAN cable on top of the PDX/PCW.
3. Uncoil the cable, route it to 2T sensor on the adjacent rack and connect it to the 2T sensor.
4. Connect all adjacent 2T sensors with supplied CAN cable.
Figure 4.24 2T sensor and probe placement
NO. DESCRIPTION NO. DESCRIPTION
1 2T sensors 6 Control panel and F ire-suppression system
2 Top plenum-rack 7 Base plenum-rack
3 Top plenum-PDX/PCW 8 2T-sensor probes
4 PDX/PCW cooling unit 9
5 Base plenum-PDX/PCW
DCR rack (st andard doors; panels andpartitions removed for clarity)
4.10.6 Locate and Install 4-pin HVAC Fault/Emergency Fan Control, Thermal-unitShutdownConnectorCable(P2)
The wires may be identified by their color:
Orange wires are HVAC fault/Run Emergency Fans
Yellow wires are thermal-unit shutdown.
1. Locate this cable (with the 4-pin connector) in the bottom of the DCR control panel.
2. Referring to Figure 4.25 on the next page, route the cable out of the grommet in the top, right-hand corner of the Control Panel and Fire Suppression module.
Vertiv | SmartRow DCR Installer/User Guide | 41
Page 42
3. Again referring to Figure 4.25 below, route the cable along the right-hand side of the top plenum and connect to the mated low-voltage connector of the PDX/PCW.
Figure 4.25 HVAC fault/Emergency Fan control/Thermal-unit Shutdown cable routing path
NO. DESCRIPTION
1 4-pin connector
2 Rubber grommet
3 Cable path
4.10.7 Connecting Secondary, 4-pin HVAC Fault/ Emergency Fan Control, Thermal-UnitShutdownConnectorCable (P2R) for20-kW(N+1)/36-kW (N) Configurations
1. Locate the wire harness with the secondary, 4-pin connector (P2R) in the Control Panel and Fire Suppression cabinet, and route the wire harness through the rubber grommet as shown in Figure 4.25 above.
2. In the secondary DCR Top Plenum-PDX/PCW (DCR-A-401PDX) locate the 30-ft extension cable with the 4-pin connector.
3. Connect one end of the extension cable to the low-voltage connector attached to the secondary PDX/PCW unit, referring to Figure 4.25 above for routing the cable.
4. Route the opposite end of the extension cable through the Top Plenum-Rack(s) to the primary Top Plenum-PDX/PCW, and connect this end to the 4-pin connector of the DCR Control Panel and Fire Suppression module.

4.11 Adjusting Air-flow Adjustment Dampers

To make sure that the air-flow adjustment dampers stay in place during cooling-unit operation, (2)damper-security push pins are factory-installed in each of the damper assemblies.
1. Refer to Figure 4.26 on the facing page, and locate the pins in the front of the air-supply opening on the damper.
Vertiv | SmartRow DCR Installer/User Guide | 42
Page 43
2. Insert the pins in each of the pin openings located directly below the front of the dampers as shown in Figure 4.26 below.
Figure 4.26 Securing the air-flow adjustment damper
NO. DESCRIPTION
1 Damper-security push pin
2 Pin opening
3 Damper-security pins inst alled
3. Repeat steps 1and 2 for the remaining dampers.
4. The damper slides must be opened varying amounts to provide adequate cooling for each DCR Rack:
NOTE: The cooling air flow required by the equipment in a DCR Rack will vary according to several factors, especially the distance from the Liebert PDX/PCW and each rack’s heat load. Do not obstruct back draft dampers in the bottom plenum. We recommend running all rack PDU cables through the top plenum.
a. After the SmartRow DCR is operational and the heat loads have time to equalize, check
the temperature in each DCR Rack with the racks’ doors closed via the 2Tsensors connected to the CANbus port on the Liebert iCOM.
If the 2T sensor reading of a rack is lower than the average leaving air temperature of the other racks, close the inlet damper slightly to reduce cooling air flow.
If the 2T sensor reading of a rack is higher than the average leaving air temperature of the other racks, open the inlet damper slightly to increase cooling air flow.
b. Reposition the air-flow adjustment dampers to equalize the cooling in each rack as
needed, referring to Figure 4.27 on the next page:
Loosen the wing nuts.
Move the damper to the position you want.
Tighten the wing nuts to make sure the damper doesn’t move during operation.
c. Repeat steps a and b until the system is equalized.
Vertiv | SmartRow DCR Installer/User Guide | 43
Page 44
Figure 4.27 Adjusting the air-flow dampers
NO. DESCRIPTION
1 Wing nuts

4.12 Install Emergency-fan Assemblies

Fans can be positioned front-to-back or side-to-side depending on the application. Orientation must be consistent with plenum opening.
1. Install the emergency-fan assembly on the rack top plenums:
a. Determine the orientation, and position the cover plates on the top of plenum as shown in
Figure 4.28 on the facing page.
b. Refer to Figure 4.28 on the facing page, and set the emergency-fan assemblies onto the
cover plates and bolt each into place with 5/16-in., self-tapping, sheet-metal screws.
2. Repeat step 1 for each remaining DCR rack.
Vertiv | SmartRow DCR Installer/User Guide | 44
Page 45
Figure 4.28 Adjust cover plates, place and attach emergency-fan assembly
NO. DESCRIPTION
1 Cover plates
2 Cover plates wit h holes for screws
3. Plug the emergency fans into outlets on the adjacent Emergency-fan housing as shown in Figure 4.29 below. Ensure that all fans are daisy-chained to each other.
4. Plug the emergency fan on the rack next to the PDX/PCW into the receptacle ontopoftheTopPlenum-PDX/PCW, Figure 4.29.
Figure 4.29 Connect Emergency Fans
NO. DESCRIPTION
1 Power connection foradjacentemergencyfan
2 Power cord
3 Power connection ontopplenumofPDX/PCW
Vertiv | SmartRow DCR Installer/User Guide | 45
Page 46

4.13 Air/Ventilation Management

Free rack space in the DCR racks must be blocked with blanking panels. Blocking the open space helps optimize system cooling performance by minimizing short cycling of conditioned air.
Heat loads should be balanced as well as possible among the cabinets. This can be done by distributing equipment evenly among the cabinets to avoid excessive heat concentration. Refer to Table 3.2 on page14 for details.

4.13.1 Ventilation Requirements

The maximum room temperature for a SmartRow DCR is 85°F (29°C).
The air-supply inlet temperature to the room should match the output capacity of the emergency fans.
If the room is sealed, the air inlet opening size from the building should be 1.5 ft2(0.14m2) per rack.
If the ceiling space is not open to the rest of the building, a damper or grille of 1.5 ft2 (0.14m2) per rack will be required.

4.13.2 Emergency-fan Notes

The emergency-fan assembly for each rack will move nominally 1160cfm (548 l/s) of air and are powered from the Control Panel and Fire Suppression System through a factory-installed L5-20 receptacle on top of the Top Plenum-PDX/PCW.
If the SmartRow DCR is installed in a dedicated room and airflow inlet and outlet openings to the room are not provided, the emergency fans will remove cabinet heat for only a short time.

4.14 Cable Management

The SmartRow DCR includes factory-suppled cable-management accessories throughout the system, taking advantage of industry best practices. Follow these cable-management guidelines to help ensure optimal performance of your system.

4.14.1 Prepare for Cable Management

1. On Top Plenum(s)-Rack, remove the access panel from the front and rear of the plenum and locate the two rectangular cutouts on each side, shown in Figure 4.30 on the facing page.
Vertiv | SmartRow DCR Installer/User Guide | 46
Page 47
2. Install the factory-supplied lobster claws in the rectangular cutouts, 1 on each side of the plenum (2 in the front and 2 in the rear of the plenum).
3. Repeat steps 1 and 2 for each Top Plenum-Rack in your system.
NOTE: Run High-voltage power whips in the front of the row. Run Ethernet and other network cabling in the rear of the row.
Figure 4.30 Lobster-claw installation (power whips not shown)
NO. DESCRIPTION
1 PDU plug
Rectangular cutouts
2
(2 in front and 2 in rear of plenum, 4 t otal)
3 Lobster claw installed

4.14.2 Routing Power Whips

Route power whips on the front of the row.
1. Locate the Rack/PDU Circuit breaker in the Load distribution center, Figure 4.31 on the next page.
2. Identify the field-supplied power-cable whip and refer to Figure 4.31 on the next page:
a. At the start or end of the DCR row, connect the whip to the PDU plug (shown in Figure
4.30 above).
b. Route the whip through the (2) front-side lobster claws of each of the Top Plenums-Rack.
c. Punch-out the knockouts in the top of the Control Panel & Fire Suppression system.
d. Attach whip to he Rack/PDU Circuit breaker in the Load distribution center in the
Control Panel & Fire Suppression system.
Vertiv | SmartRow DCR Installer/User Guide | 47
Page 48
3. Repeat steps 1 and 2 for each power whip until complete.
Figure 4.31 Power whip routing, knockouts, and circuit-breaker connection
NO. DESCRIPTION
1 Circuit breakers in load-distribution center
2 Whips routed in f ront of plenum
3 Knockouts in top of Control panel/Fire-suppression system

4.14.3 Routing Network Cables—Ethernet and Fiber-optic

NOTE: Follow best practices for cable routing and management. Refer to SL-11364 for further details.
Route the network cables on the rear of the row.
1. Route the cables into the DCR using the sealed cable-entrance kit, Figure 4.32 on the facing page.
You can use the kit in each rack or you can group all cables into a “main trunk” that enters through the Network rack.
Vertiv | SmartRow DCR Installer/User Guide | 48
Page 49
Figure 4.32 Rear of Top Plenums and sealed cable entrance example
NO. DESCRIPTION
1 Cable-pass-throughside panels
2 PDU/Cable-management brackets
3 Sealed cable entrance
2. Once inside the rack, route the cables through the top plenums or through the cable-pass­through side panels:
a. Route the cabling down through the cable-entrance openings in the rack Top Panel,
Figure 4.33 on the next page.
b. Then, route the cables to the front of the racks where you can use the factory-supplied
cable management fingers, Figure 4.34 on page51, and the field-supplied cable­management tools you choose.
NOTE: Inter-cabinet routing can be completed using a variety of DCEcable-management accessories.
Vertiv | SmartRow DCR Installer/User Guide | 49
Page 50
3. Once all cable-routing is complete, attach the shipped-loose side plate cover (from the primary Top Plenum-PDX/PCW) to the outside of the top plenum at the end of the row.
Figure 4.33 Cable entrances in Top rack plenum, looking down through the top surface-rear door
NO. DESCRIPTION
1 Cable entrances
Vertiv | SmartRow DCR Installer/User Guide | 50
Page 51
Figure 4.34 Factory-suppliedcable-managementfingers, shown in the front of networkrack
NO. DESCRIPTION
1 Cable-management fingers
Vertiv | SmartRow DCR Installer/User Guide | 51
Page 52
This page intentionally left blank.
Vertiv | SmartRow DCR Installer/User Guide | 52
Page 53

5 POWER CONNECTIONS

5.1 Power Connections to Liebert PDX/PCW

Provide input power to the Liebert PDX/PCW on its own dedicated circuit based on the specific Liebert PDX/PCW configuration requirements. Input power to the Liebert PDX/PCW must not be connected through the 225A 3PH or 125A 1PH load center in the DCR Control Panel and Fire Suppression System. Refer to the Liebert PDX/PCW user manual that shipped with the unit and is available at http://www.VertivCo.com/en-us/support/.
For electrical and piping connections, the Liebert PDX/PCW can be top-fed, bottom-fed or a combination of the two. Connections are made through the knockouts in the bottom of the Liebert PDX/PCW electrical panel/box. For top access, power wiring is routed through the Liebert PDX/PCW top piping chase.
NOTICE
Risk of improper power input. Can cause equipment damage or degraded cooling.
The Liebert PDX/PCW must be powered separately by a dedicated circuit. Power must not be supplied from the 225A 3PH or 125A 1PH panel, in part because of potential electrical noise problems.
5.2 Input Power Wiring Alternatives to DCR Control Panel andFireSuppression System and Rack Equipment
The load-distribution center located inside the DCR Control Panel and Fire Suppression System requires connection to either a 120/208VAC, 3-phase, 5-wire connection, or a 120/208VAC, 1-Phase, 4-wire connection depending on the phase of the load-distribution center selected.
Two 120VAC, 15A branch breakers are supplied for:
DCR Control Logic/Emergency Ventilation Fans
Fire Suppression System
The user must supply branch breakers, whips and wiring for all rack equipment, including optional rack PDUs, rack UPSs and general connectivity.
The SmartRow DCR Fire Suppression system and the Control-logic/Emergency-fan circuits must be connected to an on-line, double-conversion UPS power source to ensure that the Fire-Suppression system, Control Logic and Emergency ventilation fans do not lose power in the event of any type of power interruption. The remote emergency-power-off (REPO) switch for the UPS may be a normally-open (N/O) or normally-closed (N/C).
NOTE: The connection requirements to the SmartRow DCR for each system is different. UPS systems with a N/O REPO switch must tie-in to terminals 25 & 26A, and the jumper between terminals 21 and 22 must be removed. UPS systems with a N/C REPO switch must tie in to terminals 25 & 26 (See the figure "SmartRow DCR control logic" in Technical-installation Illustrations on page81). It is criticalthat this UPS is connected to the system correctly.
Vertiv | SmartRow DCR Installer/User Guide | 53
Page 54
The remaining UPS systems that are connected to loads within the SmartRow DCR system must be N/C systems. Please refer to the figure "SmartRow DCR control logic" in Technical-installation Illustrations on page81,” for further details.
NOTE: To determine if an electrical disconnect is required to be installed in conjunction with the use of the SmartRow DCR, consult local codes and agency requirements.

5.2.1 Single Bus—SmartRow DCR Load Supplied by a Single UPS

1. Connect the UPS to the load-distribution center located in the SmartRow DCR Control Panel and Fire Suppression System.
2. Use customer-supplied whips to route power from the load-distribution center to the individual racks as required.
3. Once power is routed to the racks, optional Rack PDUs can be installed and plugged in to distribute power to the rack equipment.
4. Connect emergency fans.
5.2.2 Single Bus—SmartRow DCR Load SuppliedbyRack-mountedUPS
1. Connect utility input power to the load-distribution center in the DCR Control Panel and Fire Suppression System.
2. Use customer-supplied whips to route input power from the load-distribution center to each rack UPS as required.
3. Once power is routed to the rack UPSs, Rack PDUs can be installed and plugged in to distribute power to the rack equipment.
4. Connect emergency fans to the UPS(s) in the rack or to Rack PDUs connected to the UPS in the rack.
5. Connect the DCR Control Logic and Fire Suppression system circuits to a rack-mount UPS (See the figure, "SmartRow DCR with rack-mounted UPS systems" in Technical-installation
Illustrations on page81).
NOTICE
Risk of improper electrical connections. Can cause equipment damage.
5.2.3 Dual Bus—SmartRow DCR Load SuppliedbyTwo Central UPSs
1. Connect UPS A to the load-distribution center in the DCR Control Panel and Fire Suppression System.
2. Connect UPS B to the Redundant Load Distribution Center.
3. Connect equipment on Circuit A to output power from the load-distribution center.
4. Connect equipment on Circuit B to output power from the redundant load-distribution center.
5. Connect emergency fans in a daisy chain to the connection on top of the DCR Top Plenum­PDX/PCW (L5-20R).
6. Wire Circuit A and Circuit B (See the figure, "SmartRow DCR with rack-mounted UPS systems" in Technical-installation Illustrations on page81).
Vertiv | SmartRow DCR Installer/User Guide | 54
Page 55

6 LIEBERT ICOM™ CONTROLS SET-UP

The Liebert iCOM provides control of the Liebert PDX/PCW and monitoring of conditions in the DCR racks. If more than one SmartRow DCR is installed, the Liebert iCOM’s may be networked so that each can be monitored or controlled from a single location.
Field-wiring is required for the Liebert iCOM, even if it is part of a stand-alone unit, as in a single SmartRow DCR. Refer to the Liebert PDX/PCW installation manual, SL-19800, or to the Liebert iCOM user manual, SL-18835. The manuals are available at http://www.VertivCo.com/en-us/support/.
The Liebert PDX/PCW with Liebert iCOM has Liebert IntelliSlot™ slots for use with optional communication card:
IntelliSlot UNITY-DP card
Each card employs the Vertiv™ Protocol to monitor and manage a wide range of operating parameters, alarms, and notifications. The cards communicate with Vertiv™ software tools & services, including Trellis®, Liebert SiteScan Web™ and Liebert Nform®. Visit www.VertivCo.com for the latest supported protocols.
The Liebert iCOM must be configured as stated in this section for the SmartRow DCR to operate properly. These instructions are applicable to SmartRow DCR systems with one or two Liebert PDX/PCW units and all cooling-system types (air-cooled, water/glycol and chilled water). These configurations must be made on each cooling unit, even if the units are networked, because not all settings are shared. These Settings are factory set, but the this documentation illustrates how to set them if anything were changed or was malfunctioning for some reason.

6.1 iCOM Installation Prerequisites

System fully assembled according to this document.
2T temperature sensors installed on the front (cold side) of each rack and the supply air temperature sensor(s) properly located in the supply air stream.
If the SmartRow DCR has two Liebert PDX/PCW cooling units, verify that they are connected and communicating to each other via an Ethernet switch.

6.2 Liebert iCOM Setup for all SmartRow DCR Types

You will need to enter the Level 2 iCOM control password, 5010, to change parameters.
Make these settings in the Liebert iCOM Service Menu > Setpoints:
S102 Temperature Control Sensor: Remote Sensor
S103 Temperature Setpoint Act / Set: 65°F (this can be adjusted per customer preference)
S104 Temperature Control Type: PI
S106 Temp Proportional / Integral: 25°F/ 5 min.
NOTE: After the IT equipment is loaded and operational, if the SmartRow DCR system cooling capacity is responding too slowly to heat load changes, decrease the Integral time, which dampens Liebert iCOM’s rate of change). We recommend that you adjust the Integral time before adjusting the Proportional setting.
S108 AutoSet Enable: No
S109 Temperature Deadband: 2°F
S110 Supply Limit Enabled/Setpoint: No
Vertiv | SmartRow DCR Installer/User Guide | 55
Page 56

6.2.1 Set Fixed Fan Speed to Factory-approved Level

To set the fan control to a fixed fan speed at the factory-approved level, select Service Menu > Fanspeed Control >
S146 Fan Control Sensor: Manual
S153 - Fanspeed Dehum/No Power: 100/100

6.2.2 Prevent False High- and Low-Temperature Alarms

The Liebert iCOM is set at the factory for open rooms. The high number of air exchanges in the SmartRow DCR may cause false alarms. These may be prevented by delaying the sensor triggers.
To delay the sensor triggers, make these settings in the iCOM Service Menu > Set Alarms:
S219 REM Sensor Alarms / Init Delay: Com Set: 180sec (Com Set means “common setpoint” for delaying all sensors.)
S220 High and Low Remote Temperature Setpoints: 90°F / 55°F (for remote 2T rack sensors)
NOTE: The system must use V4 IS cards (Unity) to report temperature alarms remotely.

6.2.3 Prevent Emergency Fan Activation by Warnings

To prevent warnings from activating the emergency fans, make this setting in the iCOM Service Menu > Set Alarms:
S232: Warning Activates Alarm Relay: NO
Once the critical threshold is surpassed, the iCOM would generate an alarm and activate the emergency fans.
NOTE: If a Warning occurs, it is recorded in the Event Log.
6.2.4 Control Cooling Calculation byRemote2TRackTemperatureSensor Readings
The Liebert iCOM automatically reverts to using the supply air temperature sensor in the base plenum if it loses communication with the remote rack sensors. The return air temperature sensor should never be used as a controlling sensor in the SmartRow DCR.
Make these settings in the iCOM Service Menu > Remote Sensors:
Remote Sensors: Verify that all remote sensors installed on the front (cold) side of the racks are set to “Control” not “Reference.”
SB02: Max (This takes the average or maximum of the two temperature probes per 2T).
SB03: Max (This takes the average or maximum of all the 2T sensor readings).
NOTE: Verify that the 2T temperature sensors are in an active air stream. Do not place the probes in front of blanking plates. Additional 2T temperature sensors can be installed in the SmartRow DCR for monitoring, such as determining the temperature in the rear of the racks. These sensors must be setup as “Reference.”
Vertiv | SmartRow DCR Installer/User Guide | 56
Page 57
6.2.5 Additional Liebert iCOM Settings andAdjustmentsforSmartRowDCR Operation
These changes to the Liebert iCOM settings are also required for proper operation of the SmartRowDCR.
Table 6.1 Liebert iCOM setting changes
APPLICA BLE TO:
All Units
Air-Cooled and
Water/Glycol
(compressorized)
Configurations
Only; Not Applicable
to Chilled Water
All Units
LIE BERT ICOM CONTROL KEY
S202 Return Sensor Alarms Enable
S203 High Return Temperature 80°F 87°F
S232
S232B
S239 EC Fan Fault Enable Alarm
S237 Loss of Airflow Enable Alarm
S238 Clogged Filters Enable Warning Message
S239 High Room Temp Disable Enable Warning
S249 Comp 1 Overload Enable Alarm Warning
S251 Comp 1 High Pressure Enable Alarm Warning
S253 Comp 1 Low Pressure Enable Alarm Warning
S257 Dig Scroll 1 High Temp Enable Alarm Warning
S262 Working Hrs Exceeded Enable Disable Warning
S264 Water Under Floor Enable Alarm Warning
S265 Con Pump—High Water Enable Alarm Warning
S266 Loss of Flow Enable Alarm Warning
PARAMETER DEFAULT CHANGE TO: ALARM TYPE CHANGE TO:
Warning Activates
Alarm Relay
Water Alarm Shuts Unit
Down
Yes No
No
Water/Glycol
Units Only
All Units
S267 Stby Glycol Pump On Enable Alarm Warning
S268 Standby Unit On Enable Alarm Warning
S275 Customer Input 1 Enable Alarm Warning
S276 Customer Input 2 Enable Alarm Warning
S277 Customer Input 3 Enable Alarm Warning
S278 Customer Input 4 Enable Alarm Warning
S279 Call Service Enable Alarm Warning
S280 High Temperature Enable Alarm Warning
Vertiv | SmartRow DCR Installer/User Guide | 57
Page 58
6.3 Additional Settings for20-kW, 3-to6-rackSystems—NCooling (1PDX/PCW-one cooling unit on)
Before making these changes, complete the adjustments in Liebert iCOM Setup for all SmartRow DCR
Types on page55.
Make these settings in the iCOM Service menu:
System / Network Setup > S803 Teamwork Mode: 0 - No
Standby Settings / Lead-Lag > S515 Cascade: No
Standby Settings / Lead-Lag > S503 Rotation Frequency: No
6.4 Additional Settings for 20-kW, 3-to6-rackSystems—N+1cooling Only (2PDX/PCWs-onecoolinguniton,oneinstandby)
These settings apply to a SmartRow DCR that has two Liebert PDX/PCWs, one operating and one in standby mode.
Before making these changes, complete the adjustments in Liebert iCOM Setup for all SmartRow DCR
Types on page55.
These settings allow the cooling units to share the remote 2T temperature sensor data when the cooling units are operating or on standby. This ensures that the temperature readings from all racks are factored into the cooling capacity calculation (CFC: Call for Cooling). Additionally, if the heat load temporarily exceeds the capacity of the SmartRow DCR’s operating cooling unit, the standby unit will be automatically started to assist. When one cooling unit can again maintain the load the second unit will return to standby mode (cooling and fans Off).
1. Make these settings in the iCOM Service Menu > System / Network Setup:
S803 Teamwork Mode: 1
S804 Teamwork is based on: Maximum
NOTE: The controlling temperature sensor (S102) must be properly selected (see Liebert iCOM Setup
for all SmartRow DCR Types on page55) before setting the Teamwork Mode, followed by setting
Standby and Cascade modes.
2. Make these settings in the iCOM Service Menu > Standby Settings / Lead-Lag:
S502 Number of Standby Units: 1
S503 Rotation Frequency: Every WED (schedule for convenient day)
S504 Rotate at: 09:00 (schedule at convenient time)
S505 Rotate by: 1
NOTE: We recommend scheduling the cooling system rotation to occur at a time the person in charge of the SmartRow DCR operation is present.
S515 Cascade Units: Cooling
S516 Cascaded Units Delay: 3 min
S517 Cascaded Units Quick Start: 0 min
S518 Cascaded Units Control Delay: [blank]
S520 Cascaded Units Min Run: 5 minutes
Vertiv | SmartRow DCR Installer/User Guide | 58
Page 59
6.4.1 Prevent High-temperature Threshold fromStartingAllLiebertPDX/PCWs
The high-temperature threshold, when enabled, will prompt the Liebert iCOM to start all cooling units. The function is intended to prevent high temperatures in the SmartRow DCR. However, when the second Liebert PDX/PCWis activated by this parameter, the cooling unit will remain On until you manually acknowledge it’s activation by pressing the horn button on the Liebert iCOM or over remote monitoring.
To prevent the high-temperature threshold from starting the second Liebert PDX/PCW, go to the Service Menu > Standby Lead-Lag > S513: Start all Standby units by HT. Change the setting to “NO.”
NOTE: While this setting is disabled, the combination of Teamwork Mode and Cascade settings will achieve the same result (see Additional Settings for 20-kW, 3-to6-rackSystems—N+1cooling Only
(2PDX/PCWs-onecoolinguniton,oneinstandby) on the previous page). During thermal overload
scenarios the redundant Liebert PDX/PCW will be activated to provide supplemental cooling and automatically reset when no longer needed.
NOTE: The default high temperature threshold is 80°F. The user may reset this threshold once the temperature drops 4°F below the setpoint. This threshold operates only off the return air temperature sensor.

6.4.2 Prevent False High-humidity Alarms

Delaying the humidity alarm will prevent false high-humidity alarms during a rotation of cooling units. The humidity sensor in the standby Liebert PDX/PCW will report a false high humidity reading because it is briefly not in an active air stream.
To delay the alarm, make this setting change in Service Menu > Set Alarms (Page 4) > S241 High humidity: 120 second
The default delay is 30 seconds. The maximum is 9,999 seconds.
6.5 Additional Settings for 36-kW, 5-to10-rackSystems—NCooling Only (2PDX/PCWs - both units on)
These settings apply to a SmartRow DCR that has two Liebert PDX/PCWs operating at a time. The system’s cooling capacity is 36 kW.
Before making these changes, complete the adjustments in Liebert iCOM Setup for all SmartRow DCR
Types on page55.

6.5.1 Ensure Even Airflow to all Racks During Low Heat Load

The compressor in the secondary Liebert PDX/PCW may shut off if the heat load is low. The intent of the setting is to avoid over-cooling and undesired dehumidification. This change rotates the designation of “primary cooling unit” between the cooling units to help balance compressor run hours. If the fan in the secondary PDX/PCW unit were to shut-off, some racks would experience hot spots. These settings also ensure that the temperature readings from all racks are factored into the cooling capacity calculation
Vertiv | SmartRow DCR Installer/User Guide | 59
Page 60
To enable this function:
1. Enter these changes in the iCOM Service Menu > System / Network Setup:
S803 Teamwork Mode:1
S804 Teamwork is based on: Maximum
NOTE: The controlling temperature sensor (S102) must be properly selected (see Liebert iCOM Setup
for all SmartRow DCR Types on page55) prior to setting the Teamwork Mode, followed by setting
Standby and Cascade modes.
2. Enter these changes in the iCOM Service Menu > Standby Settings / Lead-Lag:
S502 Number of Standby Units: 0 (the fans in both Liebert PDX/PCWs are always running)
S503 Rotation Frequency: Every WED (schedule at a convenient time; see the Note that follows)
S504 Rotate at: 09:00 (schedule at a convenient time; the Note that follows)
S505 Rotate by: 1
S515 Cascade Units: No (Teamwork Mode 1 will allow the cooling capacity to Cascade while keeping the fans On constantly. Enabling Cascade would force the fans to turn Off, which would prevent even distribution of cooling air.)
NOTE: We recommend scheduling the cooling system rotation to occur at a time the person in charge of the SmartRow DCR operation is present.
Vertiv | SmartRow DCR Installer/User Guide | 60
Page 61

7 DCR CONTROL PANEL AND FIRE SUPPRESSION SYSTEM

The SmartRow DCR must be installed in compliance with all applicable national, state and local fire codes. An emergency power off (EPO) switch is provided as one means of meeting regulations. Additional field­supplied connections to the system may be required, depending on the applicable regulations, the equipment configuration and the user’s operational preference.
The DCR Control Panel and Fire Suppression System has been fully tested and certified at the factory.
The DCR Control Panel and Fire Suppression System is shipped with wiring that, if required by local fire code, must be field-connected to the shutdown circuits of the Liebert PDX/PCW and any connected UPS systems.
Under NFPA regulations, systems protected by a clean fire-suppression agent can be left with the UPS and HVAC systems operational at the discretion of the owner and local fire officials.
The DCR Control Panel and Fire Suppression System should be field-connected as a separate zone to the building fire detection and alarm system.
If the SmartRow DCR is installed in a dedicated room, an additional strobe and horn may be installed at the entrance to the room. Contact your local authorized service representative if required.
7.1 DCR Control Panel andFireSuppressionSystemComponentLocations
Figure 7.1 DCR Control Panel and Fire Suppression System, exterior features
NO. DESCRIPTION NO. DESCRIPTION
1 Control-power available light 4 Manualfire-suppression release button (key-opened)
2 Fire-suppression-system abort button 5 Viewing window (for fire-system status LEDs)
3 Emergency power-off button 6 Horn and st robe
Vertiv | SmartRow DCR Installer/User Guide | 61
Page 62
Figure 7.2 DCR Control Panel and Fire Suppression System internal features
NO. DESCRIPTION NO. DESCRIPTION
1 Load-distribution c enter 5 Fire-suppression tank
2A Control-logic c ircuit breakers in "Off"position 6 Fire-syst em st atus LEDs
2B Control-logic c ircuit breakers in "On" position 7 High-temp reset butt on
3 Fire-suppression-control bypass timer 8 Emergency power-off override timer
4 Fire-suppression tank gauge
7.1.1 Control Panel andFireSuppressionSystemComponentsOperation
Table 7.1 on the facing page, shows each component, describes what each one does, and how to use it.
Vertiv | SmartRow DCR Installer/User Guide | 62
Page 63
Table 7.1 Component operation for the DCR Control Panel and Fire Suppression System
COMPONENT ACTION OPERATION
Emergency power-off
(Non-latching button)
Press the EPO button on the front door of t he Control Panel and Fire Suppression System.
Press the Remote EPO (REPO) button(s) if they are connected to t he system.
Note: Systems manufact ured and shipped before August 26, 2016 have the non-latching EPO butt on.
Emergency power-off
(Latching butt on)
Press the EPO button on the front door of t he Control Panel and Fire Suppression System.
Press the Remote EPO (REPO) button(s) if they are connected to t he system
Note: Systems manufact ured and shipped after August 26, 2016 have the latchingEPO butt on.
The EPO button is a spring loaded, non-latching butt on.
To engage the EPO: Press t he button once and the system shuts down.
To disengage the EPO: Press t he EPO button once more.
When engaged, all coolingunits, UPS(s)(if wired into EPO circuit), Firesuppression and emergency ventilation fans (if running) power down. There are multiple ways to configure the EPO circuit per the electrical schematic to comply with local codes, so y our operation may vary. However, all equipment c an be wired to shutdown.
If equipped, the Shunt trip breaker in t he load panel c an be wired to open as well.
The EPO button is a latching button.
To engage the EPO: Press t he button until it latches and the sy stem shuts down.
To disengage the EPO: Pull-out t he EPO button.
When engaged, all coolingunits, UPS(s)(if wired into EPO circuit), Firesuppression and emergency ventilation fans (if running) power down. There are multiple ways to configure the EPO circuit per the electrical schematic to comply with local codes, so y our operation may vary. However, all equipment c an be wired to shutdown.
If equipped, the Shunt trip breaker in t he load panel c an be wired to open as well.
Resetting emergency v entilation f ans
Push t he High Temp Reset button after an event in which the fans have activated and lowered t he return air temperature t o 89°F ±3°F or lower.
Turning the fire-suppression-control bypass timer
Turn the timer past the 1-hour position.
Turning the DCR emergency power-off override timer
Turn the timer past the 1-hour position.
Turning the key to activate the manual fire-suppression release
Deactivates the emergency v entilation f ans aft er the safe temperature is reached.
Allows cooling unit to reactivate when possible (Ut ility power rest ored, alarm cleared, etc.).
Resets the control logic for t he Emergency Ventilation Fans for future activation.
Note: Do not reset emergency ventilation fans f or at least 2minutes after they activate to ensure that the thermal unit’s 2-minute rest art delay has expired.
Suspend the fire-detection so that maintenance can be performed on the system.
The timer provides a normally-closed circuit bypassing the internal, normally-closed relays in t he fire-suppression panel.
Once t he timer expires, the circuit is returned to its normal setting (Off ).
Note: You can turn t he timer up to a maximum of two hours if necessary to perform maintenance.
To continue the bypass operation, just turn the t imer again when time gets low
Temporarily bypass the EPO circuit. This allows manual rest art of the UPS after an EPO event.
Note: You can turn t he timer up to a maximum of two hours if necessary to perform maintenance.
To continue the bypass operation, just turn the t imer again when time gets low.
If you see smoke and/or fire in the DCR sy stem, but the smoke detector is malfunctioning, you can manually discharge the fire suppression material into the DCR system.
Vertiv | SmartRow DCR Installer/User Guide | 63
Page 64
Table 7.1 Component operation for the DCR Control Panel and Fire Suppression System (continued)
COMPONENT ACTION OPERATION
Fire-suppression sy stem abort Prevents the fire-suppression system from dumping due to a false alarm.
Control Power Available lightilluminated (green)
Control system is powered via T B1positions (1 & 2) or (3 &4).
Control Power Available lightisNOTilluminated
Main Circuit Breaker with Shunt Trip Assembly (If applicable)
To enablepower f low to the control panel, flip the breaker s witc h to the UP position (On/Closed)
To disable power flow to the control panel, flip the breaker s witc h to the DOWN position (Off/Open)
No power going to t he control panel
Eliminates power t o all loads connected t o and downstream of the load distribution center both locally and remotely.
IMPORTANT! The shunt trip assembly r equires a d edicated, field-supp lied s ource of 120-V power to TB1 p ins 9 & 10.
If the breaker is tripped (EPO activation), you must reset the breaker before beginningthe restart protocols. See Recovering from EPO Circuit Activation below,f or details.

7.2 Recovering from EPO Circuit Activation

In the event that the EPO circuit is activated by the local EPO button on the SmartRow DCR or by a field­supplied REPO button and the system is shut down, the following steps must be taken to recover:
1. If a Shunt-Trip Main Circuit Breaker is being used, reset the Shunt-Trip Main Circuit Breaker.
2. Disengage the EPO circuit:
NOTE: You must reset the EPO or REPO button that activated the circuit to reset the circuit. Pressing a button that did not originally trigger the circuit will not reset the circuit.
a. If the local EPO button on the DCR activated the circuit:
For a Non-latching EPO button on the DCR: Push the EPO button to disengage the circuit.
For a Latching EPO button on the DCR: Pull the button back to disengage the circuit.
b. If a remote EPO (REPO) button activated the circuit, reset the REPO button that
activated the circuit using the reset function of the field-supplied button.
Once cleared, the thermal-management units in the SmartRow DCR automatically start via their dedicated power supply.
3. Turn the Local Emergency Power Off Override Timer past the 1/2-hour position.
NOTE: If needed, you may turn the timer to a maximum of 2 hours. If time is running low, turn the timer past the 1/2-hour mark again to continue the bypass.
Vertiv | SmartRow DCR Installer/User Guide | 64
Page 65
4. Reset the UPS that powers the SmartRow DCR control circuit and fire-suppression control circuit.
a. If the SmartRow DCR is powered by a stand-alone Liebert UPS, refer to the corresponding
procedure in the manual for the UPS to start-up the UPS. If it will not restart, put the UPS in bypass and restart the remaining equipment. For assistance putting a Liebert 3-phase UPS in bypass and for service support, call 800-543-2378. For a Liebert single-phase UPS, call 800-222-5877, option #1.
b. If the SmartRow DCR controls, and emergency fans are connected to rack-mounted
UPSs, you must manually restart the UPS(s). Refer to the corresponding procedure in the manual for the UPS to start-up the UPS.
The Fire-suppression System is protected from commercial power failures by an integrated battery and battery charger. In the event of a commercial power failure, the fire-suppression system continues to operate in idle mode from this battery for up to 48 hours. Upon restoration of commercial power, the battery charger automatically recharges the battery to float state.

7.3 Recovering from a Fire Suppression System Activation

In the event of a fire suppression system activation, contact your local fire-suppression representative for proper guidance on bringing your system back on-line.
Vertiv | SmartRow DCR Installer/User Guide | 65
Page 66
This page intentionally left blank.
Vertiv | SmartRow DCR Installer/User Guide | 66
Page 67

8 INSTALLATION CHECKLIST

8.1 Cooling and Power Component Installation Checklist

1. All cabinets and plenums have been installed.
2. All gaskets and edge guards are installed.
3. All electrical and piping connections have been made.
4. All cabinet doors seal and close securely.
5. All Emergency Power Off interlocks to the UPSs and to the Liebert PDX/PCW (P2 4-pin Connector) are connected.
6. All external Emergency Power Off and fire detection connections have been made, if applicable.
7. All Rack PDUs are installed and connected to the load-distribution center for external UPS configurations and to UPS outputs for internal UPS configurations, if applicable.
8. Fire-suppression control panel (CB-4) and the SmartRow DCR control logic circuit (CB-2) connected to a centralized or rack-mounted, online, double-conversion UPS.
9. Liebert PDX/PCW has been started-up and factory-commissioned.
10. UPSs have been installed and are operational.
11. If applicable:
a. Are all power-supply systems that are required to be shut-down by the EPO button
properly tied-in to the shutdown terminals?
b. Are the Liebert PDX/PCW units connected to the SmartRow DCR Thermal Unit
Shutdown circuit? (P2 and, if applicable, P2R)
c. Is there 120-V power supplied to your shunt-trip assembly (if applicable)?
d. When the local EPO button is pushed:
1. Does the power supply for the DCR (Load Distribution Center or UPS systems) Shutdown?
2. Does the Liebert PDX/PCW unit(s) shutdown?
12. Bypass timer for emergency power override works. To test the timer:
a. Turn the EPO bypass timer of an operational SmartRow DCR system past the 1-hour
position.
b. Push the EPO button and check to see if your components that are tied-in to the circuit
are still operational
c. Once confirmed, disengage the EPO button.
13. All external cable and piping entrances are properly sealed.
14. All rack supply air dampers have been adjusted to distribute the air based on the heat load in each cabinet.
15. 2T temperature sensor nodes are installed in the DCR racks, and are routed correctly in each rack
16. Supply Air Temperature Sensor is installed in the DCR Base Plenum-Rack.
17. The Liebert iCOM displays the system supply-air temperature.
18. All monitoring points are communicating to the Network Management System.
Vertiv | SmartRow DCR Installer/User Guide | 67
Page 68
19. Power and temperature monitoring are fully operational.
20. Perform all installation checks as stated in manuals for SmartRow DCR components:
Liebert PDX/PCW, Liebert iCOM, UPSs and Rack PDUs. Each UPS and Liebert PDX/PCW must be started before the fire-suppression system can be activated.

8.2 Fire Suppression System Installation Checklist

1. Is permanent 120VAC power available and on?
2. Is the Building Fire Alarm tied in? Place a check mark next to each, depending on your application.
a. Alarm ______
b. Trouble ______
c. Supervisory ______
3. Is the separately-shipped box (see Figure 8.1 on the facing page) that contains the following items on site?
a. One (1) Fire-suppression tank
b. One (1) Black Pipe Assembly
c. One (1) Aluminum Fike Nozzle
d. Two (2) Power Sonic Batteries (12V 12AH)
*Note: The local Fire Rep will install these items.
4. Is the Liebert PDX/PCW EPO tied-in?
5. Is the EPO override timer working correctly?
6. Perform EPO test to verify function (application-specific).
7. Is the SmartRow DCR installation complete and the SmartRow DCR operational?
Vertiv | SmartRow DCR Installer/User Guide | 68
Page 69
Figure 8.1 Separately-shipped Fire-suppression kit
8.2.1 DCRFireSuppressionCommissioning Procedure
Do not call to have the Fire Suppression system commissioned until all of the items in Cooling and Power
Component Installation Checklist on page67, and Fire Suppression System Installation Checklist on the
previous page, have been completed.
The local company arming the fire-suppression system cannot turn the system On until all the items above have been completed, and the "Fire Suppression System Installation Checklist" has been signed by the representative and the customer. Scheduling the local distributor prior to these items being completed may result in additional charges.
After the tasks have been completed, a local qualified service representative will conduct final fire­suppression system commissioning and arming.
1. Reach out to Flagship Fire inc. at 941-723-7320 and request help to arrange a day and time for a local fire rep. to come out to charge, start up and commission the fire-suppression system. The representative will also walk through any special jurisdictional requirements for the project that may require additional paperwork and possibly fees.
2. When the local agent arrives on site, the dry agent tank will be charged and the system will be started and commissioned.
3. If you want the system to be put through any specific testing, a Vertiv™ technician is required to be on-site to oversee the cooling unit, UPS and other Vertiv™ equipment. This is explained during the initial phone call referenced in step 1.
Vertiv | SmartRow DCR Installer/User Guide | 69
Page 70
This page intentionally left blank.
Vertiv | SmartRow DCR Installer/User Guide | 70
Page 71

9 START-UP

9.1 System Start-up and Commissioning

The Thermal Management components will be started-up by Vertiv™ personnel. Authorized Fire Suppression Personnel will contact the user to schedule start-up and commissioning. Optional UPSs will be started-up and commissioned by authorized service personnel if the UPS start-up option is purchased by the user.
The initial start-up should be scheduled after all installation steps have been completed.
NOTE: The DCR Control Panel and Fire Suppression System is shipped from the factory with the solenoid activator disconnected and without the nozzle placed in the supply air stream. The fire­suppression system should be commissioned after the UPSs, Rack PDUs and Liebert PDX/PCW have been commissioned and are fully operational.

9.2 System Start-up and Activation

The SmartRow DCR is configured to start-up when power is connected. The user must connect the emergency fans and the SmartRow DCR Control Logic to an on-line double-conversion UPS power source.
We recommend that the DCR Fire-suppression Controls and the DCR Control Circuit are supported by an on-line double-conversion UPS. When power is fed to the SmartRow DCR, the Control Power available light should be illuminated (green) on the front door (See Table 7.1 on page63).
Vertiv | SmartRow DCR Installer/User Guide | 71
Page 72
This page intentionally left blank.
Vertiv | SmartRow DCR Installer/User Guide | 72
Page 73

10 TROUBLESHOOTING

Table 10.1 on the next page, lists possible issues you could encounter when operating the SmartRow DCR, and steps for resolution of the issues
Vertiv | SmartRow DCR Installer/User Guide | 73
Page 74
Table 10.1 Troubleshooting
ISSUE RESOLU TION
Make sure the control panel logic is fed from a double-conversion UPS power source. If
When t here is a power outage, myentire SmartRow shuts down.
The cooling unit(s), UPS(s), andtheControl Panel & Fire Suppression system will not turn on.
The fire suppression panel is alarming.
When t he EPO is pressed thecoolingunits do not shutdown.
When a cooling unit shuts off andtheEmergency Ventilation Fans donot activate.
The UPS(s) connected to the s ystem may give indications of an EPO being pressed,
Call 800-222-5877, option #1.
Make sure that t he CB1 and CB2 in t he top, right-hand corner of the Control Panel and Fire
Ensure that the two 15-A breakers supplied in the Load Distribution center are closed (ON)
Turn EPO Override timer beyond the ½-hour position and rest art t he UPS.
If t he SmartRow DCR is powered by a stand-alone, 3-phase Liebert U PS and will not
Call 800-543-2738 for assistance in putting the UPS in bypass and for service support.
Reference t he Troubleshooting sect ion 6.3 of the
Call your local Fike fire-suppression representative with the details regarding the event for
Make sure that t he 4-pin HVAC f ault / Emergency Ventilation Fan Control, Thermal-unit
Make sure that t he 4-pin HVAC f ault / Emergency Ventilation Fan Control, Thermal-unit
Check to see if the load-distribution-center breaker that feeds the emergency-fan c ircuit is
Check to make sure that the return-air-temperature sensor is properly connected as
Validate that the SmartRow DCR iCOM-control settings are entered as inst ructed for t he
the control logic looses power, it will appear as if an EPO is pressed.
which also indicates a loss in control-logic power and improper connection to the system.
Suppression module are closed (ON). See Figure 7.2 on page62, for t he locations. These provide power to the control-logic circuitry.
as they provide power to the fire suppression panel and t he emergency ventilation fans
restart, put the UPS in bypass and restart t he remainingequipment.
the type of event t riggering t he alarm.
Fike SHP Pro Product Manual
propersupport of your syst em.
Shutdown Connector Cable (P2) is connected t o its low -voltage PDX/PCW receptacle.
See Locate and Install 4-pin HVAC Fault/ Emergency Fan Control,
Thermal-unitShutdownConnectorCable(P2) on page41for additional details.
Shutdown Connector Cable (P2) is connected t o its low -voltage PDX/PCW receptacle.
See Locate and Install 4-pin HVAC Fault/ Emergency Fan Control,
Thermal-unitShutdownConnectorCable(P2) on page41for additional details.
closed (ON).
documented in Connect Return-temperature Thermostat,
theL5-20ReceptacleandtheSmokeDetector on page38.
SmartRow DCR.
See Liebert iCOM™ Controls Set-up on page55for additional details.
to identify
Vertiv | SmartRow DCR Installer/User Guide | 74
Page 75
Table 10.1 Troubleshooting (continued)
ISSUE RESOLU TION
The Emergency Ventilation Fans activate for no apparent reason.
The temperature in one of the racks istoo warm/cold.
The cooling unit is short cycling (turningon and off frequently).
Validate that the SmartRow DCR iCOM-control settings are entered as inst ructed for t he SmartRow DCR.
See Liebert iCOM™ Controls Set-up on page55for additional details.
Adjust t he damper in the bott om of the rack until the desired t emperature is achieved. You may need to adjust t he damper in neighboring racks slightly to help balance the airflow in the system.
See Adjusting Air-flow Adjustment Dampers on page42for additional details.
Do not exceed 6kW of heat load in a given rack.
Ensure that the heat load is reasonably distributed across all of t he racks.
Validate that the SmartRow DCR iCOM-control settings are entered as inst ructed in the SmartRow DCR.
See Liebert iCOM™ Controls Set-up on page55in for additional details.
Close the air damper in racks that have no I T equipment.
Ensure blanking panels are inst alled in any empty U-space to prevent cold air supply bypassing directly into t he return air stream.
Make sure that t here is at least 4kW of heat load in the 20-kW SmartRow, 8kW inthe 36-kW system.
Do not exceed 6kW of heat in a s ingle rack.
If using a 20-kW(N+1) or 36-kW (N) configuration, the iCOM controls of the thermal­management units must be set f or Teamwork mode.
Vertiv | SmartRow DCR Installer/User Guide | 75
Page 76
This page intentionally left blank.
Vertiv | SmartRow DCR Installer/User Guide | 76
Page 77

11 MAINTENANCE

11.1 Liebert PDX/PCW Maintenance

Proper application and maintenance of the entire DCR-integrated PDX/PCW is critical to the life and reliability of the system. See appropriate sections for maintenance in the Liebert PDX and PCW Thermal Management Systems User Manual for recommended procedures and timing of Preventative maintenance on your thermal-management units.

11.2 Fire Detection and Suppression System Maintenance

Periodic maintenance, replacement and testing shall be, as a minimum, performed per NFPA 72. Maintenance shall be performed by a trained or authorized Fike representative.
Make sure that you consistently check the cylinder to ensure it remains properly charged. The cylinder gauge must be in the green area. If it is not, be sure to contact your local trained or authorized Fike representative.
See section 6.0 in the SHP Pro Product Manual that comes with your system for further detail on proper Fire Suppression System Maintenance.

11.3 UPSs and Rack PDUs Maintenance

Refer to your system’s UPS manual for recommended maintenance procedures and timing. Contact Vertiv™ at 800-543-2378 for information about availability of optional preventative-maintenance plans.
Vertiv | SmartRow DCR Installer/User Guide | 77
Page 78

12 TECHNICAL DATA

12.1 Unit Dimensions, Weights, and Wiring Tables

Table 11.1 SmartRowDCR with a Single PDX/PCW
COMPONENT REFERENCE DIMENSIONS, MM (IN.)
EMPTY RACKS MAX RACK CAPAC ITY
3 rack system width 3099 (122) 1454 (3232) 5504 (12231.5)
4 rack system width 3805 (149.8) 1727 (3838) 7127 (15838)
5 rack system width 4511 (177.6) 2000 (4444) 8750 (19444)
6 rack system width 5217 (205.4) 2273 (5050) 10373(23050)
Leveling feet at minimum adjustable to 1in. (25 mm).
Rack mounting rails must be positioned 9in. (229mm) from the front of the rack frame for cooling airflow.
Table 11.2 SmartRow DCR with a Second PDX/PCW
COMPONENT REFERENCE DIMENS IONS , MM (IN.)
EMPTY RACKS MAX RACK CAPAC ITY
W3 (3 RACK) 3983 (156.8) 1980(4400) 6030 (13400)
W4 (4 RACK) 4689 (184.6) 2253(5006) 7653 (17006)
W5 (5 RACK) 5395 (212.4) 2525(5612) 9275 (20612)
W6 (6 RACK) 6101 (240.2) 2798(6218) 10898(24218)
W7 (7 RACK) 6807 (268) 3071 (6825) 12521 (27825)
W8 (8 RACK) 7514 (295.8) 3444(7431) 14144(31431)
W9 (9 RACK) 8220 (323.6) 3617(8037) 15767(35037)
W10 (10 RACK) 8926(351.4) 3890 (8644) 17390 (38644)
Leveling feet at minimum adjustable to 0.75in. (19mm).
Rack mounting rails must be positioned 9in. (229mm) from the front of the rack frame for cooling airflow.
TOTAL SYSTEM WEIGHT, KG (LB)
TOTAL SYSTEM WEIGHT, KG (LB)
Vertiv | SmartRow DCR Installer/User Guide | 78
Page 79
Table 11.3 SmartRow DCR Part Dimensions
COMPONENT
PART NO.
DCR-A-101
DCR-A-104
DCR-A-200
DCR-A-204
DCR-A-300
DCR-A-301
DCR-A-400
DCR-A-401
DCR-A-500
DCR-A-600
Control enclosure is shipped laying down (the dimension scheme references it as st anding).
DIMENSIONS,
(D X W X H) IN. (MM.)
46.62 (1184.3) x 27.56 (700.1) x 10.50 (266.7)
46.62 (1184.3) x 31.50 (800.1) x 10.5 (266.7)
46.62 (1184.3) x 27.56 (700.1) x 8.75 (222.3)
46.62 (1184.3) x 31.50 (800.1) x 8.75 (222.3)
46.62 (1184.3) x 34.93 (887.4) x 10.5 (266.7)
46.62 (1184.3) x 34.50 (876.3) x 10.5
(266.7)
46.62 (1184.3) x 34.93 (887.4) x 8.75 (222.3)
46.62 (1184.3) x 34.50 (876.3) x 8.75 (222.3)
13.50 (342.9) x 34.50 (876.3) x 77.56
(1970.1)
13.50 (342.9) x 34.50 (876.3) x 77.56
(1970.1)
SHIPPING MATERIAL
DIMENSIONS,
(D X W X H) IN. (MM.)
47.50 (1206.5) x 32.50 (825.5) x
10.75 (273.1)
47.50 (1206.5) x 32.50 (825.5) x
10.75 (273.1)
47.50 (1206.5) x 32.50 (825.5) x
10.75 (273.1)
47.50 (1206.5) x 32.50 (825.5) x
10.75 (273.1)
47.50 (1206.5) x 35.50 (901.7) x
10.75 (273.1)
47.50 (1206.5) x 35.50 (901.7) x
10.75 (273.1)
47.50 (1206.5) x 35.50 (901.7) x
10.75 (273.1)
47.50 (1206.5) x 35.50 (901.7) x
10.75 (273.1)
16.50(273.1) x 34.75(882.7) x
77.75 (1974.9)
16.50(273.1) x 34.75(882.7) x
77.75 (1974.9)
SKID DIMENSIONS,
(D X W)IN. (MM.)
43 (1092) x 51 (1295.4) (4) Unit Max
43 (1092) x 51 (1295.4) (4) Unit Max
43 (1092) x 51 (1295.4) (4) Unit Max
43 (1092) x 51 (1295.4) (4) Unit Max
43 (1092) x 51 (1295.4) (4) Unit Max
43 (1092) x 51 (1295.4) (4) Unit Max
43 (1092) x 51 (1295.4) (4) Unit Max
43 (1092) x 51 (1295.4) (4) Unit Max
36 (914.4) x 79 (2006.6) (2) U nit Max
36 (914.4) x 79 (2006.6) (2) U nit Max
Vertiv | SmartRow DCR Installer/User Guide | 79
Page 80
Table 11.4 DCR field-wiring list
BUNDL E FROM TO
PRIMARY PDX/PCW & CONTROL PANEL (All Configurations)
1 Fire Control Panel Smoke Detect or FACTORY
2 TB1(P1- 3pin connector, Positions 7, 8, and GND )
3 TB2 (P2 - 4pin c onnector, Positions 3,4,23, and 24)
4 TB2 (P3 - 3pin c onnector, Positions 5 and 6)
5 Supply Air Temp Sensor PDX/PCW iCOM board FACTORY
6 2T Sensor Adjacent 2T Sensor FACTORY
7 Rack Temp Sensor to PDX / PCW Sensor PDX / PCW Return Air Sensor FACTORY
8 Emergency Fan Adjacent Emergency Fan FACTORY
9 Load-center AC Power I nput Load center FIELD
10 PDX AC Power I nput PDX FIELD
11 MC Condenser AC Power Input MC Condenser FIELD
12 PDX / MC Piping MC Condenser FIELD
13 PDX Condensate Piping Drain FIELD
14 Fire Control Panel Building F ire System FIELD
15 PDU Power Input Load center FIELD
16 EPO UPS or UTI LITY F EED FIELD
SECONDARY PDX/PCW (Redundant / Higher Capacity Configurations) & OPTIONAL LOAD CENTER
1 Secondary PDX / PCW (P2R - 4pin connector) TB2 (P2R - 4pin connector) FACTORY
2 Secondary Top Plenum - Thermostat (P3R - 3pin connector) TB2 (P3R - 3pin connector) FACTORY
3 Supply Air Temp Sensor PDX/PCW iCOM board FACTORY
4
5 Rack Temp Sensor to PDX / PCW Sensor PDX / PCW Return Air Sensor FACTORY
6 Optional Secondary Load-center AC Power Input Load center FIELD
7 Secondary PDX AC Power Input PDX FIELD
8 Secondary MC Condenser AC Power Input MC Condenser FI ELD
9 Secondary PDX / MC Piping MC Condenser FIELD
10 Secondary PDX Condensate Piping Drain FIELD
11 vNSA AC Power Load center FIELD
12 vNSA Network PDX FIELD
Secondary [[[Undefined variable ctrl_panel_fire_ suppress.PComponent4]]] Smoke Detector t o Primary Smoke Detector
PDX Top Plenum (P1- 3pin connector)
PDX / PCW (P2 - 4pin connector, Positions75, 76, 37,and38)
PDX Top Plenum Thermostat (P3 ­3pin connector, Positions 5 and 6)
Smoke Detect or FACTORY
FACTORY/FIELD-SUPPLIED
WIRING
FACTORY
FACTORY
FACTORY
Vertiv | SmartRow DCR Installer/User Guide | 80
Page 81

12.2 Technical-installation Illustrations

The technical illustrations are included in the order listed. Reference the document number to find the title you need..
Table 11.5 Technical illustrations
DOCUMENT NUMBER TITLE
DCR3RACK20 pg. 1 SmartRow DCR component arrangement
DCR3RACK20 pg. 2 SmartRow DCR dimensions and weights—20-kW (N) configuration
DCR6RACK20P136 SmartRow DCR dimensions and weights—20-kW (N+1)/36-kW (N) configuration
DCR-CP-3 DCR Control Panel and Fire Suppression Syst em components
DCR-RACK-700 DCR 700-mm wide cabinet
DCR-RACK-800 DCR 800-mm wide cabinet
DCR-PD-3 SmartRow DCR power distribution 3PH
DCR-PD-3MBS SmartRow DCR power distribution 3PH with main circuit breaker and shunt-trip assembly
DCR-PD-1 SmartRow DCR power distribution 1PH
DCR-PD-1MBS SmartRow DCR power distribution 1PH with main circuit breaker and shunt-trip assembly
1196888-E03 SmartRow DCR control logic
1196888-E04 SmartRow DCR control logic (continued)
1196888-E06 SmartRow DCR terminal block layout
DCRELECBD pg. 2 SmartRowDCR with rack-mounted UPS systems
DCRELECBD pg. 3 SmartRow DCR with Central UPS System
DCRELECBD pg. 4 SmartRow DCR with A-B UPS and load centers
Vertiv | SmartRow DCR Installer/User Guide | 81
Page 82
This page intentionally left blank.
Vertiv | SmartRow DCR Installer/User Guide | 82
Page 83
NOTES:
1. SOME PARTS NOT SHOWN FOR C L ARITY.
SMARTROW DCR RACK TOP PLENUM WITH EMERGENCY FAN
SMARTROW DCR RACK 42U x 700W x 1200D (x2)
SMARTROW DCR RACK BASE PLENUM
SUPPLY AIRFLOW MANUAL ADJUSTMENT DAMPER
SMARTROW DCR RACK 42U x 800W x 1200D (x1)
SMARTROW DCR PDX TOP PLENUM
LIEBERT PDX
FRONT ISOMETRIC VIEW
DRAWN BY:
JST
CHECKED BY:
BLR
REFERENCE DRAWING:
FORM NO.DPN001230 REV 4
SHEET NUMBER:
1 OF 3
ECN NUMBER:
QUOTE NUM B E R:
SMARTROW DCR CONTROL PANEL & FIRE SUPPRESSION SYSTEM.
TITLE / DESCRIPTION
SMARTROW DCR
MAJOR COMPONENTS
DRAWING NUMBER:
DCR3RACK20
CUSTOMER / JOB
3 RACK 20kW(N)
DATE:
3/13/2017
SMARTROW DCR PDX BASE PLENUM
REV#:
1050 DEARBORN DRIVE
P.O BOX 29186
1
COLUMB US, OHIO 43229
Page 84
NOTES:
2. ALL DIMENSIONS ARE IN mm (INCHES)
u1.5mm (u0.06")
3. LEVELING FEET SHOWN FULLY RECESSED. LEVELING FEET ARE ADJUYSTABLE UP TO +25mm (1.0")
4. TOTAL WEIGHT OF SYSTEM SHOWN: EMP T Y RACKS = 1454 KG [323 2 L B] MAX RACK CAPACITY = 5504 KG [12231.5 LB]
1231
48.5
3099
122.0
311
12.3
DRAWN BY:
JST
CHECKED BY:
BLR
REFERENCE DRAWING:
SHEET NUMBER:
2 OF 3
ECN NUMBER:
QUOTE NUM B E R:
213
8.4
TITLE / DESCRIPTION
SMARTROW DCR
DIMENSION & WEIGHTS
2763
108.8
DRAWING NUMBER:
DCR3RACK20
413
16.3
CUSTOMER / JOB
3 RACK 20kW(N)
DATE:
3/13/2017
REV#:
1
1050 DEARBORN DRIVE
P.O BOX 29186
COLUMB US, OHIO 43229
FORM NO.DPN001230 REV 4
Page 85
NOTES:
1. SOME PARTS NOT SHOWN FOR C L ARITY.
SMARTROW DCR RACK 42U x 700W x 1200D (x5)
LIEBERT PDX W/ REDUNDANT CONTROL PANEL
FRONT ISOMETRIC VIEW
SMARTROW DCR RACK BASE PLENUM
SUPPLY AIRFLOW MANUAL ADJUSTMENT DAMPER
SMARTROW DCR CONTROL PANEL & FIRE SUPPRESSION SYSTEM
SMARTROW DCR RACK TOP PLENUM WITH EMERGENCY FAN
SMARTROW DCR RACK 42U x 800W x 1200D (x1)
SMARTROW DCR PDX TOP PLENUM
LIEBERT PDX
SMARTROW DCR PDX BASE PLENUM
DRAWN BY:
JST
CHECKED BY:
BLR
REFERENCE DRAWING:
FORM NO.DPN001230 REV 4
SHEET NUMBER:
1 OF 3
ECN NUMBER:
QUOTE NUM B E R:
TITLE / DESCRIPTION
SMARTROW DCR
MAJOR COMPONENTS
DRAWING NUMBER:
DCR6RACK20P136
CUSTOMER / JOB
6 RACK 20kW (N+1) / 36kW (N)
DATE:
3/13/2017
REV#:
1
1050 DEARBORN DRIVE
P.O BOX 29186
COLUMB US, OHIO 43229
Page 86
NOTES:
2. ALL DIME NSIONS ARE IN mm (INCHES)
u1.5mm (u0.06")
3. LEVELING SHOWN FULLY RECESSED. LEVELING FEET ARE ADJUSTABLE UP TO +25mm (1.0”).
4. TOTAL WEIGHT OF SYSTEM SHOWN: EMP T Y RA CKS = 2798 KG [621 8 L B] MAX RACK CAPACITY = 10898 KG [24218 LB]
6101
240.2
311
12.3
213
8.4
1231
48.5
413
16.3
DRAWN BY:
JST
CHECKED BY:
BLR
REFERENCE DRAWING:
FORM NO.DPN001230 REV 4
SHEET NUMBER:
2 OF 3
ECN NUMBER:
QUOTE NUM B E R:
TITLE / DESCRIPTION
SMARTROW DCR
DIMENSION & WEIGHTS
DRAWING NUMBER:
DCR6RACK20P136
2763
108.8
CUSTOMER / JOB
6 RACK 20kW (N+1) / 36kW (N)
DATE:
3/13/2017
REV#:
1
1050 DEARBORN DRIVE
P.O BOX 29186
COLUMB US, OHIO 43229
Page 87
NOTES:
5. 3 RACK PRIMARY & REDUNDANT COOLING CONFIGURATION SHOWN FOR REFERENCE ONLY
EMERGENCY FAN POSITIONING ORIENTATION PLATES
NETWORK CABLE ENTRANCE KOs LOCATED ON TOP OF PLENUM. TYPICAL FRONT AND REAR.
RACK TOP PLENUM ACCESS COVERS FRONT & REAR
EMERGENCY FAN INPUT DAISY CHAIN
EMERGENCY FAN MAIN INPUT
PDX PIPE CHASE-TOP ENTRY ONLY REFER TO PDX DOCUMENTATION FOR PIPE SIZES.
PDX TOP PLENUM ACCESS COVERS FRONT, SIDE AND REAR
DRAWN BY:
JST
CHECKED BY:
BLR
REFERENCE DRAWING:
FORM NO.DPN001230 REV 4
SHEET NUMBER:
3 OF 3
ECN NUMBER:
QUOTE NUM B E R:
EMERGENCY FAN INPUT AIR ACCESS / DAMPER
ACCESS & CONNECTIONS
TITLE / DESCRIPTION
SMARTROW DCR
DRAWING NUMBER:
DCR6RACK20P136
CUSTOMER / JOB
6 RACK 20kW (N+1) / 36kW (N)
DATE:
3/13/2017
PDX BASE PLENUM ACCESS COVERS FRONT, SIDE AND REAR
REV#:
1050 DEARBORN DRIVE
P.O BOX 29186
1
COLUMB US, OHIO 43229
Page 88
LOAD DISTRIBUTION CENTER
-LOAD CENTER CONSISTS OF A 3PH, 5-WIRE, 30-POLE RATED AT 120/208VAC & 225A OR 1PH, 4-WIRE, 30-POLE RATED AT 120/208VAC & 225A
-LOAD CENTER IS FACTORY SUPPLIED WITH (2) 120 VAC 15A CIRCUIT BREAKERS.
CONTROL TERMINAL STRIPS
SMARTROW DCR EMERGENCY POWER OFF OVERRIDE TIMER (MANUAL/120 MINUTE) & HIGH TEMPERATURE RESET BUTTON
DE TAIL A
SMARTROW DCR
FIRE SUPPRESSION SYSTEM AND
EPO CONTROLS
FIRE STROBE/HORN
SEE DETAIL A
DRAWN BY:
JST
CHECKED BY:
BLR
REFERENCE DRAWING:
N/A
FORM NO.DPN001230 REV 3
FIRE SUPPRESSION SYSTEM STATUS VISUAL INSPECTION
FIRE SUPPRESSION SYSTEM
CONTROL PANEL
SHEET NUMBER:
1 OF 1
ECN NUMBER:
N/A
QUOTE NUM B E R:
N/A
CONTROL PANEL & FIRE SUPPRESSION
FIRE SUPPRESSION
GAS CYLINDER
(SHIP SEPERATE)
TITLE / DESCRIPTION
SMARTROW DCR
DRAWING NUMBER:
SMARTROW DCR
DCR-CP-3
FIRE SUPPRESSION SYSTEM GAS CYLINDER VISUAL INSPECTION
CUSTOMER / JOB
DATE:
4/29/2016
REV#:
0
1050 DEARBORN DRIVE
P.O. BOX 29186
COLUMB US, OHIO 43229
Page 89
208/120VAC
60Hz
3
L1 L2 L3
N G
3PH Load Distribution Center
3Ø PANELBOARD
15A/1P
1
3
2
15A/1P
4
REMOVE WIRES IF USING UPS OPTION
TB1
CONTROL PANEL
1
2
CHASSIS GROUND
NOTE: CONTROL LOGIC MUST BE BACKED BY
ON-LINE DOUBLE CONVERSION UPS-SOURCE
RACK #1 POWER
120VAC 1 PHASE
RACK #3 POWER
120VAC 1 PHASE
RACK #5 POWER
120VAC 1 PHASE
RACK #1 POWER
208 1 PHASE
RACK #3 POWER
208 1 PHASE
RACK #5 POWER
208 1 PHASE
RACK #1 POWER
208/120VAC
3 PHASE
RACK #3 POWER
208/120VAC
3 PHASE
RACK #5 POWER
208/120VAC
3 PHASE
FORM NO. DPN001231 REV 4
CUSTOMER PROVIDED
120V 1 PHASE RACK CONNECTION
H
N
H
N
H
N
208V 1 PHASE RACK CONNECTION
L2
L3
L1
L2
L3
L1
208V 3 PHASE RACK CONNECTION
L1
L2
L3
N
L1
L2
L3
N
L1
L2
L3
N
OPTION
20A/1P
34
5
78
6
OPTION
20A/1P
34
20A/1P
20A/1P
5
7
9
9
11
11
13
13
6
8
10
10
12
12
14
14
OPTION
20A/1P
7
9
11
20A/1P
13
15
17
20A/1P
19
21
23 24
8
10
12
14
16
18
20
22
10A/1P
20A/1P20A/1P
20A/1P20A/1P
20A/1P
20A/1P
20A/1P
20A/1P
20A/1P
20A/1P
H
RACK #2 POWER 120VAC 1 PHASE
N
H
RACK #4 POWER 120VAC 1 PHASE
N
H
RACK #6 POWER 120VAC 1 PHASE
N
L2
RACK #2 POWER
208 1 PHASE
L3
L1
RACK #4 POWER
208 1 PHASE
L2
L3
RACK #6 POWER
208 1 PHASE
L1
L1
RACK #2 POWER
L2
L3
N
L1
RACK #4 POWER
L2
L3
N
L1
RACK #6 POWER
L2
L3
N
208/120VAC
3 PHASE
208/120VAC
3 PHASE
208/120VAC
3 PHASE
OPTION 42P
5
7
9
11
13
15
17
19
21
23
25
27
29
31
33
35
37
39
41
DRAWN BY:
BLR
CHECKED BY:
SK
REFERENCE DRAWING:
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
40
42
6
8
SHEET NUMBER:
1 OF 1
ECN NUMBER:
QUOTE NUMBER:
FIRE SUPPRESSION
H1
CONTROL SYSTEM
(INTERNAL BATTERY BACK-UP)
H2 CHASSIS GROUND
208,240, OR 460VAC
TITLE / DESCRIPTION
CONTROL PANEL & FIRE SUPPRESSION
POWER DISTRIBUTION
LIEBERT COOLING POWER
CONNECTIONS
3
L2L1
L1
60Hz
L3 G
L3
L2
LIEBERT
HVAC UNIT
DRAWING NUMBER:
G
DCR-PD-3
208,240, OR 460VAC
3
L2L1
L1
L2
LIEBERT
OPTIONAL REDUNDANT HVAC UNIT
CUSTOMER / JOB SMARTROW DCR
REV#:
DATE:
04/17/17
1
60Hz
L3 G
L3
1050 DEARBORN DRIVE
P.O. BOX 29186
COLUMBUS, OHIO 43229
G
Page 90
3PH Load Distribution Center with Main Breaker & Shunt-Trip Assembly
RACK #1 POWER
120VAC 1 PHASE
RACK #3 POWER
120VAC 1 PHASE
RACK #5 POWER
120VAC 1 PHASE
RACK #1 POWER
208 1 PHASE
RACK #3 POWER
208 1 PHASE
RACK #5 POWER
208 1 PHASE
RACK #1 POWER
208/120VAC
3 PHASE
RACK #3 POWER
208/120VAC
3 PHASE
RACK #5 POWER
208/120VAC
3 PHASE
FORM NO. DPN001231 REV 4
208/120VAC
60Hz
3
CUSTOMER PROVIDED
120V 1 PHASE RACK CONNECTION
H
N
H
N
H
N
208V 1 PHASE RACK CONNECTION
L2
L3
L1
L2
L3
L1
208V 3 PHASE RACK CONNECTION
L1
L2
L3
N
L1
L2
L3
N
L1
L2
L3
N
OPTION
20A/1P
34
5
78
6
OPTION
20A/1P
34
20A/1P
20A/1P
5
7
9
9
11
11
13
13
6
8
10
10
12
12
14
14
OPTION
20A/1P
7
9
11
20A/1P
13
15
17
20A/1P
19
21
23 24
8
10
12
14
16
18
20
22
10A/1P
20A/1P20A/1P
20A/1P20A/1P
20A/1P
20A/1P
20A/1P
20A/1P
20A/1P
20A/1P
H
RACK #2 POWER 120VAC 1 PHASE
N
H
RACK #4 POWER 120VAC 1 PHASE
N
H
RACK #6 POWER 120VAC 1 PHASE
N
L2
RACK #2 POWER
208 1 PHASE
L3
L1
RACK #4 POWER
208 1 PHASE
L2
L3
RACK #6 POWER
208 1 PHASE
L1
L1
RACK #2 POWER
L2
L3
N
L1
RACK #4 POWER
L2
L3
N
L1
RACK #6 POWER
L2
L3
N
208/120VAC
3 PHASE
208/120VAC
3 PHASE
208/120VAC
3 PHASE
L1 L2 L3
N G
CBM
OPTION 42P
225A
SHUNT TRIP
TB1
9
NOTE: REQUIRES A 120V DEDICATED SOURCE TO POWER
2
4
6
8
15A/1P
15A/1P
SHEET NUMBER:
1 OF 1
ECN NUMBER:
QUOTE NUMBER:
10
(FIELD SUPPLIED)
REMOVE WIRES IF USING UPS OPTION
TB1
CONTROL PANEL
1
2
CHASSIS GROUND
FIRE SUPPRESSION
H1
CONTROL SYSTEM
(INTERNAL BATTERY BACK-UP)
H2 CHASSIS GROUND
NOTE: CONTROL LOGIC MUST BE BACKED BY
ON-LINE DOUBLE CONVERSION UPS-SOURCE
208,240, OR 460VAC
TITLE / DESCRIPTION
CONTROL PANEL & FIRE SUPPRESSION
POWER DISTRIBUTION
LIEBERT COOLING POWER
CONNECTIONS
3
L2L1
L1
60Hz
L3 G
L3
L2
LIEBERT
HVAC UNIT
DRAWING NUMBER:
G
DCR-PD-3MBS
208,240, OR 460VAC
3
L2L1
L1
L2
LIEBERT
OPTIONAL REDUNDANT HVAC UNIT
CUSTOMER / JOB SMARTROW DCR
REV#:
DATE:
04/17/17
1
60Hz
L3 G
L3
1050 DEARBORN DRIVE
P.O. BOX 29186
COLUMBUS, OHIO 43229
G
ST
3Ø PANELBOARD
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
31
33
35
37
39
41
DRAWN BY:
BLR
CHECKED BY:
SK
REFERENCE DRAWING:
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
40
42
Page 91
1PH Load Distribution Center
L1
CUSTOMER PROVIDED
RACK #1 POWER
120VAC 1 PHASE
RACK #3 POWER
120VAC 1 PHASE
RACK #5 POWER
120VAC 1 PHASE
RACK #1 POWER
240 1 PHASE
RACK #3 POWER
240 1 PHASE
RACK #5 POWER
240 1 PHASE
120V 1 PHASE RACK CONNECTION
H
N
H
N
H
N
240V 1 PHASE RACK CONNECTION
L2
L3
L1
L2
L3
L1
OPTION
20A/1P
34
5
78
OPTION
20A/2P
34
5
20A/2P
7
9
9
20A/2P
11
11
13
13
240/120VAC
60Hz
1
125a
L2 N
G
REMOVE WIRES IF USING UPS OPTION
1Ø PANELBOARD
1
3
5
7
9
11
13
15
17
10A/1P
20A/1P20A/1P
6
20A/1P20A/1P
H
RACK #2 POWER 120VAC 1 PHASE
N
H
RACK #4 POWER 120VAC 1 PHASE
N
H
RACK #6 POWER 120VAC 1 PHASE
N
19
21
23
25
27
20A/2P
L2
RACK #2 POWER
6
20A/2P
8
10
10
20A/2P
12
12
14
14
240 1 PHASE
L3
L1
RACK #4 POWER
240 1 PHASE
L2
L3
RACK #6 POWER
240 1 PHASE
L1
29
15A/1P
2
15A/1P
4
6
8
10
12
14
16
18
20
22
24
26
28
30
TB1
CONTROL PANEL
1
2
H1
FIRE SUPPRESSION
H2
CONTROL SYSTEM
(INTERNAL BATTERY BACK-UP)
CHASSIS GROUND
CHASSIS GROUND
FORM NO. DPN001231 REV 3
FORM NO. DPN001231 REV 4
DRAWN BY:
DRAWN BY:
BLR
CHECKED BY:
CHECKED BY:
SK
REFERENCE DRAWING:
REFERENCE DRAWING:
SHEET NUMBER:
SHEET NUMBER:
1 OF 1
1 OF 1
ECN NUMBER:
ECN NUMBER:
QUOTE NUMBER:
QUOTE NUMBER:
TITLE / DESCRIPTION
TITLE / DESCRIPTION
CONTROL PANEL & FIRE SUPPRESSION
POWER DISTRIBUTION
DRAWING NUMBER:
DRAWING NUMBER:
DCR-PD-1
CUSTOMER / JOB
CUSTOMER / JOB SMARTROW DCR
DATE:
DATE:
05/26/17
REV#:
REV#:
1
1050 DEARBORN DRIVE
1050 DEARBORN DRIVE
P.O. BOX 29186
P.O. BOX 29186
COLUMBUS, OHIO 43229
COLUMBUS, OHIO 43229
Page 92
1PH Load Distribution Center with Main Breaker & Shunt-Trip Assembly
CUSTOMER PROVIDED
RACK #1 POWER
120VAC 1 PHASE
RACK #3 POWER
120VAC 1 PHASE
RACK #5 POWER
120VAC 1 PHASE
RACK #1 POWER
240 1 PHASE
RACK #3 POWER
240 1 PHASE
RACK #5 POWER
240 1 PHASE
120V 1 PHASE RACK CONNECTION
H
N
H
N
H
N
240V 1 PHASE RACK CONNECTION
L2
L3
L1
L2
L3
L1
OPTION
20A/1P
34
5
78
OPTION
20A/2P
34
5
20A/2P
7
9
9
20A/2P
11
11
13
13
CBM
L1
240/120VAC
60Hz
1
L2
125a
N G
1
3
5
7
9
11
13
15
17
10A/1P
20A/1P20A/1P
6
20A/1P20A/1P
6
8
10
10
12
12
14
14
20A/2P
20A/2P
20A/2P
H
RACK #2 POWER 120VAC 1 PHASE
N
H
RACK #4 POWER 120VAC 1 PHASE
N
H
RACK #6 POWER 120VAC 1 PHASE
N
L2
RACK #2 POWER
240 1 PHASE
L3
L1
RACK #4 POWER
240 1 PHASE
L2
L3
RACK #6 POWER
240 1 PHASE
L1
19
21
23
25
27
29
TB1
ST
LOCATED IN MAIN CONTROL PANEL
1Ø PANELBOARD
15A/1P
2
15A/1P
4
6
8
10
12
14
16
18
20
22
24
26
28
30
9
120VAC BREAKER
10
SHUNT TRIP
REMOVE WIRES IF USING UPS OPTION
TB1
CONTROL PANEL
1
2
H1
FIRE SUPPRESSION
H2
CONTROL SYSTEM
(INTERNAL BATTERY BACK-UP)
TB1
1
120VAC BREAKER
2
SHUNT TRIP
LOCATED UNDER PANELBOARD
CHASSIS GROUND
CHASSIS GROUND
FORM NO. DPN001231 REV 3
FORM NO. DPN001231 REV 4
DRAWN BY:
DRAWN BY:
BLR
CHECKED BY:
CHECKED BY:
SK
REFERENCE DRAWING:
REFERENCE DRAWING:
SHEET NUMBER:
SHEET NUMBER:
1 OF 1
1 OF 1
ECN NUMBER:
ECN NUMBER:
QUOTE NUMBER:
QUOTE NUMBER:
TITLE / DESCRIPTION
TITLE / DESCRIPTION
CONTROL PANEL & FIRE SUPPRESSION
POWER DISTRIBUTION
DRAWING NUMBER:
DRAWING NUMBER:
DCR-PD-1MBS
CUSTOMER / JOB
CUSTOMER / JOB SMARTROW DCR
DATE:
DATE:
05/26/17
REV#:
REV#:
1
1050 DEARBORN DRIVE
1050 DEARBORN DRIVE
P.O. BOX 29186
P.O. BOX 29186
COLUMBUS, OHIO 43229
COLUMBUS, OHIO 43229
Page 93
CUTOUT SHOWN FOR CLARITY
PDU POWER CABLE SECURED
TO TOP PANEL WITH (2) VELCRO
SEALED FRONT PLEXIGLASS DOOR
RACK ID TAG,
ROWLINE-UP LOCATION
(LEFT ROW END,
CENTER OF ROW,
OR RIGHT ROW END)
CABLE MANAGEMENT
TOP PANEL PASSTHROUGH
WITH EDGE GUARD PROTECTION
SADDLES.
SEALED REAR SOLID SPLIT DOORS
TOP PANEL EXHAUST OPENING
CABLE PASS-THRU PANELS (2 PER SIDE) SHOWN (FOR RACKS LOCATED IN -BETWEEN ROW)
SOLID PANELS USED IN RIGHT SIDE WHEN RACK LOCATED AT RIGHT ROW END.
SOLID PANELS USED ON LEFT SIDE WHEN RACK DEPLOYED AT LEFT ROW END.
NOTES:
1.ALL DIMENSIONS ARE IN MM (INCHES)
2.
UNIT WEIGH T: 184.1 KG [405 LB
]
u 1.5mm(u 0.06")
3. WEIGHT CAPACITY: 1361 KG [3000 LB] STATIC LOA D PACKAGE
4.
DRAWN BY:
JST
CHECKED BY:
BLR
REFERENCE DRAWING:
N/A
OF QTY (50) M6 SCREWS AND M6 CAGE NUTS INCLUDED.
SHEET NUMBER:
1 OF 2
ECN NUMBER:
N/A
QUOTE NUM B E R:
N/A
RACK, SERVER CABINET (700W)
TITLE / DESCRIPTION
DRAWING NUMBER:
DCR-RACK-700
CUSTOMER / JOB
SMARTROW DCR
DATE:
4/25/2016
REV#:
1
1050 DEARBORN DRIVE
P.O. BOX 29186
COLUMB US, OHIO 43229
Page 94
CABLE MANAGEMENT
TOP PANEL PASSTHROUGH
WITH EDGE GUARD PROTECTION
SEALED REAR SOLID SPLIT DOORS
PDU POWER CABLE SECURED
TO TOP PANEL WITH (2) VELCRO
SEALED FRONT PLEXIGLASS DOOR
RACK ID TAG,
ROWLINE-UP LOCATION
(LEFT ROW END,
CENTER OF ROW,
OR RIGHT ROW END)
TOP PANEL EXHAUST OPENING
SADDLES.
CABLE PASS-THRU PANELS (2 PER SIDE) SHOWN (FOR RACKS LOCATED IN -BETWEEN ROW)
SOLID PANELS USED IN RIGHT SIDE WHEN RACK LOCATED AT RIGHT ROW END.
SOLID PANELS USED ON LEFT SIDE WHEN RACK DEPLOYED AT LEFT ROW END.
NOTES:
1.ALL DIMENSIONS ARE IN MM (INCHES)
2.
UNIT WEIGH T: 195.9 KG [431 LB
3.W
EIGHT CAPACITY: 1361 KG [3000 LB] STATIC LOAD
PACKAGE
4.
DRAWN BY:
JST
CHECKED BY:
BLR
REFERENCE DRAWING:
N/A
OF QTY (50) M6 SCREWS AND M6 CAGE NUTS INCLUDED.
SHEET NUMBER:
1 OF 2
ECN NUMBER:
N/A
QUOTE NUM B E R:
N/A
]
u 1.5mm(u 0.06")
RACK, NETWORK CABINET (800W)
TITLE / DESCRIPTION
DRAWING NUMBER:
DCR-RACK-800
CUSTOMER / JOB
SMARTROW DCR
DATE:
5/2/2016
REV#:
1
1050 DEARBORN DRIVE
P.O. BOX 29186
COLUMB US, OHIO 43229
Page 95
3
(H2)
BLK 14AWG
(42, LVTB-76) SEE NOTE 11
P2
2
P2R
2
P3
2
P3R
2
CONTROL CHARACTERISTICS
MATERIAL:
FINISH:
MATERIAL NOTE: FABRICATE FROM THE MATERIAL SPECIFIED IN ACCORDANCE WITH THE CURRENT APPLICABLE LIEBERT ENGINEERING SPECIFICATION OR AS
DIMENSIONAL TOLERANCES
UNLESS OTHERWISE SPECIFIED
MM (PRIMARY)
X .X
.XX
ANGULAR
1
DRAWN:
CHECKED:
ENGR:
H2
H1
H3 H4
X1
X2
24V
(24AC1)
13
ORN
(38)
L1
ORN
(40)
13
ORN
(42)
CR2
RESET
± .03
± .015
(42A)
± .1
13
ORN
(46A)
13
ORN
13
M H
THIRD ANGLE PROJECTION
CORPORATE CAGE CODE:
55455
4
91
ORN
HIGH TEMP
(46) HIGH TEMP FAULT
6
ORN
10
SYMBOL LEGEND
OTHERWISE SPECIFIED ON THIS DRAWING.
INCHES (
SECONDARY)
± 2
(.X)
(.XX)
± .8
(.XXX)
± .38
± 2°
RH NA RH
3
(N)
WHT 14AWG
50VA T2
SOURCE A AVAILABLE
14
CR1
E2-5,E2
POWER AVAILABLE
G
SHUT DOWN BACKUP FANS
14
CR2
E2
RUN BACKUP FANS
14
CR3
E2-6
14
CR7
E2-41, E3 E3-89
HIGH TEMP FAULT SEAL
14
CR7A
E2-49
24ACN
DESIGN MAJOR HIGHLIGHTED
1050 DEARBORN DRIVE
P.O. BOX 29186
COLUMBUS, OHIO 43229
DATE:
15DEC15
DATE:
-
DATE:
15DEC15
-7,E2-38,E2-40
-42
-78,E3-87,
PART NUMBER
EMERSON NETWORK POWER - CONFIDENTIAL
©
AND PROPRIETARY - ALL RIGHTS RESERVED THIS DOCUMENT (AND THE INFORMATION IT
CONTAINS) ARE THE PROPERTY OF EMERSON
NETWORK POWER. BY ACCEPTING IT INTO
YOUR POSSESSION, YOU AGREE THAT YOU
WILL KEEP THIS DOCUMENT, AND ALL INFORMATION CONTAINED HEREIN, IN
STRICTEST CONFIDENCE, AND WILL NOT COPY, RETRANSMIT, USE (EXCEPT SOLELY FOR THE BENEFIT OF EMERSON NETWORK
POWER), SELL, LEND OR OTHERWISE DISPOSE
OF THE SAME, DIRECTLY OR INDIRECTLY,
WITHOUT THE EXPRESS WRITTEN PERMISSIO N
OF EMERSON NETWORK POWER, AND THIS
DOCUMENT SHALL BE RETURNED TO
EMERSON NETWORK POWER IMMEDIATELY
UPON REQUEST.
TITLE:
SIZE
B
1196888-E03
2
DESCRIPTION
LIEBERT DCR
CONTROL LOGIC
DRAWING NUMBER SHEET
12
D
C
B
A
REV.
3/6
2
1
N
2
N
WHT 14AWG
5
1H1 N1H2
26
FU1
27
G
P1
FNQ-R-2
28
(H1)
29
BLK
30
14AWG
31
32
33
(24AC1) (24ACN)
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
24AC1
24AC2
FAN1
FAN2
FAN1
FAN2
6
N
(N)(5)
RACK#1
RACK#2
8
H
1
1
2
3
14AWG
4
D
5
6
(1H1)
7
8
9
10
11
12
C
13
14
15
16
17
18
19
20
B
21
22
23
24
25
H
3 4
CB1
CB2
15A
BLK
BLK 14AWG
(1H2)
15A
CR1
59
CR1
19
400 UNIT
BACKUP FAN BOX
BACKUP FAN BOX
(ADAPTER MODULE REQUIRED FOR RACK 8 TO 10
1H1
1H2
7
120VAC
60Hz
120VAC
60Hz
1
CR3
95
BLK
14AWG
(5A)
7 8
12 3
P1
L5-20R L5-20P
L5-20R L5-20P
L5-20R
CONNECTION TO RACK#3 THRU #7
DAISY CHAIN
SEE DRAWING 1176575)
TO THIS SHEET
ROW 26
A
RED DENOTES RED WIRE
ALL WIRE 16AWG UNLESS NOTED
NOTES:
1.1.
BLK DENOTES BLACK WIRE
2.
BLU DENOTES BLUE WIRE
3.3.
BLU/WHT DENOTES BLUE WIRE WITH WHITE TRACER
4.
ORN DENOTES ORANGE WIRE
5.
ORN/WHT DENOTES ORANGE WIRE WITH WHITE TRACER
6.
8
7.7.
TB1 TERMINAL BLOCK
8.8.
TB2 TERMINAL BLOCK
9.
10.
FACTORY SUPPLIED WIRING. LENGTH 9 FEET FROM
11.
TOP OF TB1. MARKED AS INDICATED: ##, &&&&&&& WERE ## IS WIRE NUMBER, &&&&&&& IS TERMIANL LOCATION IN HVAC UNIT.
7
LIEBERT DCR CONTROL PANEL & FIRE SUPPRESSION POWER CONNECTIONS
6
5
FRONT VIEW Plug/socket
1-350346-0
4
FROM THIS SHEET
WHT 14AWG
ROW 25
FU2 FNQ-R-2
H2
H1
H3 H4
50VA
(24AC2)
T1
X2
ORN
X1
24V
ORN ORN/WHT
CR1
812
CR1
412
(38)
P2/P2R
NOT USED IN 500B AND 500BMB UNITS
FIRE CONTROL PANEL (FC)
AUX RELAY #2
CNO
1 2
[2] [6]
(38, LVTB-75)
SEE NOTE 11
P2
LVTB-75 LVTB-76
1
3
P2R
LVTB-75 LVTB-76
1
7 8
TOP PLENUM THERMOSTAT
P3
1
5
TOP PLENUM THERMOSTAT
P3R
1
9
TO 1196888-E04
ROW 51
[ARM1]
59
LIEBERT (HVAC)
FAULT
REDUNDANT
LIEBERT (HVAC)
FAULT
REDUNDANT
59
[522CAS]
CR7
CR7A
P3/P3R
1
1
FRONT VIEW Plug/socket
1-480702-0
FRONT VIEW Plug/socket
1-480700-0
4
Page 96
24AC1 24ACN
(24VAC1)
ORN
24AC2
(24VAC2)
11 12
ORN
EMERGENCY POWER OFF
EPO
TT LEFT
REMOVE JUMPER IF REMOTE EPO IS USED
(54)
13
ORN
FROM 1196888-E03
ROW 50
OPTIONAL REMOTE EPO
14
(54A) (54B)
CR6
19
ORN ORN
51
52
53
54
55
56
57
58
59
15 16
TT
RIGHT
60
61
62
FIRE CONTROL PANEL (FC)
AUX RELAY
#3
63
64
65
66
67
68
DETECT #1
69
70
71
(58)
17
ORN
REMOVE JUMPER IF REMOTE EPO IS USED
TM1
P4-3
P4-2
P3-2
P3-1
C
+
-
+
-
120MIN FC
BYPASS TIMER
LINE2
MANUAL
SPRING OPERATED
(68)
(69)
(70)
(71)
4.3K
LOAD2
2
1
4
3
EOL
(65)
19 20CR6
BLU
SMOKE DETECTOR
9
10
4
ALARM
5
14
SUPERVISORY
3
NO 4P-2
24VDC
13
(58A) (58B)
18
412
ORN ORN
FIRE CONTROL PANEL (FC)
14
BLU
BLU (65B)
(68)
2
(69)
1
(70)
4
(71)
3
CR6
-24 DC
MEDIA RELEASE
-54, E3-58
E3
SMOKE DETECTOR
(68A)*
9
10
(69A)*
(70A)*
4
ALARM
5
(71A)*
14
SUPERVISORY
3
72
73
REDUNDANT SYSTEM WIRING
74
75
(76)
(77) (77A)
CR4
76
77
(24VACN)
CR4
CR4A
CR5
EPO-PRIMARY POWER
14
E3-76,E3-77,E3-77 E3-82
14
E3-82,E3-82,E3-87,E3-87
ORN/WHT
EPO-PRIMARY POWER
14
E3-77,E3-78,E3-78 E3-83
13
13
13
78
79
(77, LVTB-37)
SEE NOTE 13
80
LIEBERT (HVAC)
81
82
83
84
13
CR5A
14
E3-83,E3-83,E3-88,E3-88
(REFER TO SHEET 5 FOR 522CAS)
85
86
87
88
REDUNDANT SMOKE DETECTOR
9
2
2
10
1
1
4
4
4
3
4.3K
(74)*(70) (70)
3
EOL
5
14
3
ALARM
SUPERVISORY
89
90
91
92
93
94
P2/P2R
95
96
59
CR5
59
YEL
23 24
P2
3
LVTB-37
HVAC SHUTDOWN *
(82F) (82G)
YEL YEL
27 28
UPS RACK2 SHUTDOWN
(87) (87A) (87B) (87C)
YEL YEL YE L YEL
YEL
(79, LVTB-38)
SEE NOTE 13
4
LVTB-38
CR4
11 7
CR5
11 7
N.C. CONTACT *
CR4A
711 610
CR5A CR5A
711 610
35 36
UPS RACK6 SHUTDOWN *
AND OPEN FOR POWER DOWN EXCEPT TERMINAL 25 TO 26A AND 27 TO 28A.
*** TERMINAL 27 TO 28A IS OPEN UNDER NORMAL OPERATION
YEL
(77B) (77C)
210
YEL
CR7
(79)
P2
CR4
6
10
CR5
6
10
YEL
LINE1
25 26 26A
N.C. CONTACT *
UPS SHUTDOWN CENTRAL OR RACK#1
YEL
CR4
311
REMOVE JUMPER IF NOT USING SOURCE B POWER
CR5
28B 28C
311
(84) YEL
(83)
YEL
YEL
28A
N.O. CONTACT ***
CR4A
(87B, LVTB-37)
SEE NOTE 13
37 38
(90, LVTB-38)
SEE NOTE 13
P2R P2R
34 LIEBERT (HVAC)
LVTB-37
REDUNDANT HVAC
SHUTDOWN *
* ALL CONTACTS ARE CLOSED UNDER NORMAL OPERATION
** TERMINAL 25 TO 26A IS OPEN UNDER NORMAL OPERATION
AND CLOSES FOR POWER DOWN AND CLOSES FOR POWER DOWN
CR4
210
CR5
210
(77D)
120MIN SYSTEM RESTART TIMER MANUAL - SPRING OPERATED
LOAD1
TM2
N.O. CONTACT **
UPS RACK3 SHUTDOWN * UPS RACK4 SHUTDOWN * UPS RACK5 SHUTDOWN *
311
CR7
YEL
(90)
LVTB-38
YEL
REMOVE JUMPER IF NOT USING SOURCE B POWER
21 22
YEL
YEL
LINE2
TM2
LOAD2
(79A)(77B) (77C)
(82) (82A) (82B) (82C) (82D) (82E)
CR4
812 59 812
CR5 CR5A CR5A
812 9 812
YELYELYELYELYELYEL
29 30
(87D) (87E)
CR7
812
YEL YEL
CR4A
5
31 32
CR4A
33 34
39 40 HIGH TEMP FAULT *
97
98
99
100
FRONT VIEW Plug/socket
1-480702-0
1
ALL WIRE 16AWG UNLESS NOTED
NOTES:
1.1.
BLK DENOTES BLACK WIRE
2.
BLU DENOTES BLUE WIRE
3.3.
BLU/WHT DENOTES BLUE WIRE WITH WHITE TRACER
4.
ORN DENOTES ORANGE WIRE
5.
ORN/WHT DENOTES ORANGE WIRE WITH WHITE TRACER
6.
RED DENOTES RED WIRE
7.7.
YEL DENOTES YELLOW WIRE
8.8.
TB1 TERMINAL BLOCK
9.
TB2 TERMINAL BLOCK
10.
11.
* - DENOTES USER ON-SITE SUPPLIED WIRING
12.
FACTORY SUPPLIED WIRING. LENGTH 9 FEET FROM
13.
TOP OF TB1. MARKED AS INDICATED: ##, &&&&&&& WERE ## IS WIRE NUMBER, &&&&&&& IS TERMIANL LOCATION IN HVAC UNIT.
SMART ROW DCR CONTROL PANEL & FIRE SUPPRESSION POWER CONNECTIONS
Page 97
101
102
103
104
105
106
107
108
109
110
111
112
113
114
115
116
117
118
119
120
121
122
123
124
125
1 2 3 4 5 6 7 8 9
10
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16 17 18
TB1 120VAC TERMINAL LAYOUT
H
CONTROL POWER INPUT FROM SOURCE "A" 120VAC
N
FROM PANELBOARD CB1(UPS SUPPLIED)
H
CONTROL POWER INPUT FROM SOURCE "B" 120VAC*
N
FROM SECONDARY PANELBOARD CB1(UPS SUPPLIED)
H
FAN POWER 120VAC OUT
N
H
120VAC MAIN BREAKER SHUNT TRIP (IF SUPPLIED)
N
TB2 24V TERMINAL LAYOUT
FIRE CONTROLLER AUX RELAY#2 (NOT USED IN 500B AND 500BMB UNITS)
HVAC FAULT INPUT
PLENUM THERMOSTAT
REDUNDANT HVAC FAULT INPUT* REDUNDANT PLENUM THERMOSTAT*
LOCAL EPO CONTACT #1 (PUSHBUTTON)
REMOTE EPO CONTACT #1* (REMOVE JUMPER IF USED)
LOCAL EPO CONTACT #2 (PUSHBUTTON)
REMOTE EPO CONTACT #2* (REMOVE JUMPER IF USED)
126
127
128
129
130
131
132
133
134
135
136
137
138
139
140
141
142
143
144
145
146
147
148
149
150
TB2 24V TERMINAL LAYOUT (CONTINUED)
19
FC AUX RELAY #3 AND BYPASS TIMER (24VDC FC POWER SOURCE)
20
FC 24VDC COMMON
21
CENTRAL OR RACK#1 UPS SHUTDOWN N.O. JUMPER REMOVE IF NOT USING SOURCE B (N.O. CONTACT ONLY)
22 23
HVAC SHUTDOWN
24 25
COM
26
26A
27
28 28A 28B 28C
29
30
31
32
33
34
35
36
37
38
39
40
RACK#1 UPS SHUTDOWN*
N.C. N.O. COM
RACK#2 UPS SHUTDOWN*
N.C. N.O.
RACK#2 UPS SHUTDOWN N.O. JUMPER REMOVE IF NOT USING SOURCE B (N.O. CONTACT ONLY)
RACK#3 UPS SHUTDOWN*
RACK#4 UPS SHUTDOWN*
RACK#5 UPS SHUTDOWN*
RACK#6 UPS SHUTDOWN*
REDUNDANT HVAC SHUTDOWN*
HIGH TEMPERATURE FAULT
SMOKE DETECTOR - TOP PLENUM
3 4 5
9 10 14
EOL
4.3K
TO P3-2 FC TO P3-1 FC TO P4-3 FC TO P4-2 FC
ALL WIRE 16AWG UNLESS NOTED
NOTES:
1.1.
BLK DENOTES BLACK WIRE
2.
BLU DENOTES BLUE WIRE
3.3.
BLU/WHT DENOTES BLUE WIRE WITH WHITE TRACER
4.
ORN DENOTES ORANGE WIRE
5.
ORN/WHT DENOTES ORANGE WIRE WITH WHITE TRACER
6.
RED DENOTES RED WIRE
7.
TB1 TERMINAL BLOCK
8.8.
TB2 TERMINAL BLOCK
9.
10.
11.
SMOKE DETECTOR TERMINAL BLOCK
* - DENOTES USER ON-SITE SUPPLIED WIRING
12.
FC = FIRE CONTROL PANEL
13.
SMART ROW DCR CONTROL PANEL & FIRE SUPPRESSION POWER CONNECTIONS
Page 98
ENP Supplied and installed Wiring
Field Supplied Power Wiring
Field Supplied Control Wiring
Optional
Rack
Mount
UPS #1 Optional
Rack
Mount
UPS #2
Optional
Rack
Mount
UPS #X
(See Note 2)
SmartRow DCR
Control Panel and
Fire Suppression
System
(See Note 1)
L1 L2 L3 N GND
Main 225A
CB w/
Shunt Trip
(Optional)
Fire
Control
Panel
15A /120V
FIELD
SUPPLIED
FIELD
SUPPLIED
FIELD
SUPPLIED
Utility Feed
15A /120V
(See Note 4)
Optional Remote
EPO
SmartRow DCR
Control Interface
1 2
3 4
27 28
TB1-Control Power
TB2-System EPO
13 14
25
26
1
Source A
2 3
Source B(Optional)
4
11 12
Local EPO
15 16 13
Remote EPO Contact #1*
14 17
Optional Remote EPO
18
25
UPS 1 Shut Down
26 27
UPS 2 Shut Down
28 29
UPS X Shut Down
30
Optional
Contact #2
*Remove Jumper If
Used
Note 1: SmartRow DCR Control Panel Load Center - 3 PH – 5 Wire 208/120VAC 225A – 30 Pole. Optional 1PH 4 wire 208/120 VAC not shown for clarity. Note 2: For additional component installations please refer to Wiring Section of the SmartRow DCR Installation Manual. Note 3: Must be wired in accordance with national and local wiring codes and regulations. Note 4: Disconnect the wires from this breaker to TB1 in this configuration
DRAWN BY
RAY SHARP
CHK BY
REF. DWG.
SHEET
ECN NO.
ORD-DOT
1
CONFIGURATION
#2: DCR WITH
RACK-MOUNTED
UPS SYSTEM(s)
OPTIONAL
DCRELECBD
DATE
5/2/2017
REV. #DWG. NO.
4
1050 DEARBORN DRIVE
P.O. BOX 29186
COLUMBUS, OHIO 43229
Page 99
ENP Supplied and installed Wiring
Field Supplied Power Wiring
Field Supplied Control Wiring
Optional
Rack
PDU #1
Optional
Rack
PDU #2
SmartRow DCR
Control Panel and
Fire Suppression
System
(See Note 1)
Main 225A
CB w/ Shunt Trip (Optional)
Fire
Control
Panel
15A /120V
FIELD
SUPPLIED
FIELD
SUPPLIED
Central UPS
L1 L2 L3 N GND
15A /120V
Optional Remote
SmartRow DCR
Control Interface
TB1-Control Power
1 2
TB2-System EPO
13 14
25 26
EPO
1
Source A
2 3
Source B(Optional)
4
11 12
Local EPO
15 16
Optional Remote
13
EPO Contact #1*
14
Optional Remote
17
EPO Contact #2
18 25
UPS A Shut Down
26
Optional
Rack
PDU #X
FIELD
SUPPLIED
*Remove Jumper If Used
Note 1: SmartRow DCR Control Panel Load Center - 3 PH – 5 Wire 208/120VAC 225A – 30 Pole. Optional 1PH 4 wire 208/120 VAC not shown for clarity. Note 2: For additional component installations please refer to Wiring Section of the SmartRow DCR Installation Manual. Note 3: Must be wired in accordance with national and local wiring codes and regulations.
DRAWN BY
RAY SHARP
CHK BY
REF. DWG.
SHEET
ECN NO.
ORD-DOT
2
OPTIONAL
CONFIGURATION
#3: DCR WITH
CENTRAL UPS
DATE
5/2/2017
4DCRELECBD
1050 DEARBORN DRIVE
P.O. BOX 29186
COLUMBUS, OHIO 43229
REV. #DWG. NO.
Page 100
ENP Supplied and installed Wiring
Field Supplied Power Wiring
Optional
Rack
PDU (B)
#1
Optional
Rack
PDU (B)
#2
Optional
Rack
PDU (B)
#X
(See Note 2)
Redundant / B Feed
SmartRow DCR
Load Center
(See Note 1)
Main 225A
CB w/ Shunt
Trip
(Optional)
15A / 120V
SUPPLIED
SUPPLIED
SUPPLIED
UPS (B)
L1 L2 L3 N GND
FIELD
FIELD
FIELD
15A / 120V
Optional
Rack
PDU (A)
#1
Optional
Rack
PDU (A)
#2
Optional
Rack
PDU (A)
#X
(See Note 2)
SmartRow DCR
Control Panel and
Fire Suppression
System
(See Note 1)
Main 225A
CB w/ Shunt
Trip
Fire
Control
Panel
(Optional)
15A / 120V
Field Supplied Control Wiring
UPS (A)
L1 L2 L3 N GND
FIELD
SUPPLIED
FIELD
SUPPLIED
FIELD
SUPPLIED
15A / 120V
1 2 3 4
25 26
27 28
Optional
Remote EPO
Liebert DCR
Control Interface
1 2 3 4
11 12 15
13 14
16 13 14 17 18 25 26 27 28
Source A
Source B(Optional)
Local EPO
Optional Remote EPO Contact #1*
Optional
Remote EPO
Contact #2
UPS A Shut Down
UPS B Shut Down
Note 1: SmartRow DCR Control Panel Load Center - 3 PH – 5 Wire 208/120VAC 225A – 30 Pole.Optional 1PH 4 wire 208/120 VAC not shown for clarity. Note 2: For additional component installations please refer to Wiring Section of the SmartRow DCR Installation Manual. Note 3: Must be wired in accordance with national and local wiring codes and regulations.
DRAWN BY
RAY SHARP
CHK BY
REF.DWG
SHEET
ECN NO.
ORD-DOT
3
OPTIONAL CONFIGURATION #4
DCR WITH A – B UPS
AND LOAD CENTERS
DATE
5/2/2017
REV. #DWG. NO.
4DCRELECBD
1050 DEARBORN DRIVE
P.O. BOX 29186
COLUMBUS, OHIO 43229
Loading...