Vertiv PSI5-800RT120, PSI5-5000RT208, PSI5-1100RT120, PSI5-2200RT120, PSI5-1500RT120 User Manual

...
LIEBERT PSI5™ UPS
Quick Installation User Guide
I M P O RTANT: Before installing, connecting to supply or operating your Liebert PSI5TM UPS, please review the Safety and Regulatory Statements sheet. For detailed installation, operating, maintenance and troubleshooting information refer to the PSI5TM User Guide available at www.VertivCo.com.
INSTALLATIO N
1. Inspecting the UPS
Inspect the UPS for any signs of obvious damage. If damage is visible, do not proceed and call our warranty support line for assistance at 1-800-222-5877 menu option 3, or email at microups.warranty@vertivco.com.
2. Choosing a location
Install the PSI5TM UPS in a temperature-controlled environment that is free of corrosive and conductive contaminants. Avoid locations near heat or water sources and exposed to direct sunlight. For proper ventilation, leave four inches clearance on all sides of the UPS.
The input outlet should be nearby and easily accessible.
3. Installing the UPS
The PSI5TM UPS and optional PSI5TM UPS External Battery Cabinets may be installed in either a tower or rack configuration. For tower installation, assemble and attach the tower support stands. For rack installation, attach the brackets to the UPS, install the rail kit in the rack if needed, and install the UPS in the rack.
NOTE :
computer room as defined in the standard for the protection of electronic computer/data processing equipment of ANSI/ NFPA 75.
This UPS is not for use in a
MODEL DESIGN CONFIGURATIONS
PSI5-800/1100/1500RT120
PSI5-2200RT120
PSI5-3000RT120
PSI5-5000RT208
# Description
1 Grounding screw
2 Network/Fax/Modem surge protection input/output
3 External battery connector
4 USB communication port
5 Programmable receptacles
6 Non-programmable receptacles
7 SNMP IntelliSlot port
8 Emergency Power O (EPO) connector
9 Input circuit breaker
10 AC input
11 Output circuit breaker
590-1817-501C/SL-23316_REV2_3-18 1
LIEBERT PSI5™ UPS
Quick Installation User Guide
PSI5TM UPS to External Battery Cabinet Connections
EBC port
PSI5-2200RT120 Shown
Single/First EBC
Second EBC
CONNECTIONS
1. Connecting Loads
The UPS has non-programmable and programmable rear outlets. Plug your critical equipment (such as computer, monitors, etc.) into the non-programmable outlets and equipment (such as printers and other less-often used peripherals) into the programmable outlets.
your less-critical
2. Connecting for Network Protection (Optional)
Connect a network, fax, or modem to the network/fax/ modem surge-protection ports on the rear panel for protection from electrical surges to your computer or telephone network.
3. USB Communication Connection (Optional)
Connect the PSI5TM through the rear panel USB Type-B port to a computer via USB to allow unattended, controlled­shutdown of your computer in case of UPS input power failure.
The UPS works with the computer running software built-in within the Microsoft® Windows® operating system or the Liebert Multilink™ Shutdown software located at www.VertivCo.com.
4. Emergency Power­o (EPO) Connection (Optional)
To comply with national and local wiring codes and regulations, the EPO connector internally disconnects all power sources to the UPS and connected equipment. To use this feature remove the factory­installed jumper on the rear­panel EPO connector and connect to active-open contacts that are normally closed but open during an emergency power o event. Operating logic may be reversed in the Settings menu. If you do not use the EPO connector, leave the factory­installed jumper in place and the default (active open) EPO setting in the Settings Menu.
5. External Battery Cabinet Connection (Optional)
External battery cabinets provide longer battery run-time for connected devices. Refer to PSI5TM User Guide, to select the appropriate model and quantity for your PSI5TM model and applications. You can connect up to 6 battery cabinets to the PSI5.
1. Turn o the UPS utility input.
2. Open the front left cover on the UPS and the External Battery Cabinet (EBC) and disconnect the internal batteries.
3. Remove the EBC terminal covers from the UPS and the EBC. Connect one end of the external battery cable to the UPS and one end to the battery cabinet. If connecting more than one external battery, connect one end of the external battery cable to the second connector on the battery cabinet, then connect the other end to the next battery cabinet.
2 590-1817-501C/SL-23316_REV2_3-18