Installation and User Manual (UM582140600), Revision A
Specification Number: 582140600
Model Number: 8100DB
Page 2
2
The information contained in this document is subject to change without
notice and may not be suitable for all applications. While every precaution
has been taken to ensure the accuracy and completeness of this
document, Vertiv Co. assumes no responsibility and disclaims all liability
for damages resulting from use of this information or for any errors or
omissions. Refer to other local practices or building codes as applicable
for the correct methods, tools, and materials to be used in performing
procedures not specifically described in this document.
The products covered by this instruction manual are manufactured and/or
sold by Vertiv Co. This document is the property of Vertiv Co. and
contains confidential and proprietary information owned by Vertiv Co. Any
copying, use or disclosure of it without the written permission of Vertiv Co.
is strictly prohibited.
Names of companies and products are trademarks or registered
trademarks of the respective companies. Any questions regarding usage
of trademark names should be directed to the original manufacturer.
Vertiv |NetSure 8100 Series Installation & User Manual (UM582140600)|Rev. A
Page 3
3
TABLE OF CONTENTS
Admonishments Used in this Document ............................................................ 5
Important Safety Instructions .............................................................................. 6
General Safety .......................................................................................................................................................... 6
DC Voltages ................................................................................................................................................................ 6
Personal Protective Equipment (PPE) .............................................................................................. 7
Physically Installing the System ......................................................................... 11
General Requirements ..................................................................................................................................... 11
Installing the Bays ................................................................................................................................................ 11
Installing Distribution Panel Paralleling Bars (if furnished) ....................................... 13
Installing the Internal Ground/Return Busbar Paralleling Bars List 39
(8-Panel Bay Only) (if furnished) ......................................................................................................... 14
Field Installing Bay Input Feed and Shunt Assembly List 43 .................................. 15
Making Switch and Jumper Settings ................................................................ 21
Circuit Cards with Jumpers and/or Switches Locations .............................................. 21
Switch Settings on IB2 Interface Board ........................................................................................ 22
Switch Settings on SM-DUE .................................................................................................................... 23
Jumper Settings on SM-DUE ................................................................................................................. 25
Analog Inputs AI1 to AI10 ................................................................................................................................... 25
Switch Settings on SM-DUH2 ................................................................................................................. 27
Making Electrical Connections .......................................................................... 29
Important Safety Instructions ................................................................................................................ 29
Input/Output Cable Routing and Cable Management ................................................... 41
Vertiv |NetSure 8100 Series Installation & User Manual (UM582140600)|Rev. A
Page 4
4
Load Distribution Connections ............................................................................................................. 45
DC Input Connections ................................................................................................................................... 53
Installing Circuit Breakers and Fuses .............................................................. 58
Initially Starting, Configuring, and Checking System Operation ............. 62
Important Safety Instructions ................................................................................................................ 62
Initially Starting the System ..................................................................................................................... 62
Monitor Unit Initialization ........................................................................................................................... 62
Verifying and Setting the Monitor Unit as Required for Your
Checking System Status ............................................................................................................................. 66
Final Steps ................................................................................................................................................................. 67
Operating the System .......................................................................................... 68
Monitor Unit ............................................................................................................................................................. 68
Local Controls and Indicators ................................................................................................................ 68
System Expansion .............................................................................................................................................. 72
Troubleshooting and Repair ................................................................................ 77
Important Safety Instructions ................................................................................................................. 77
Contact Information .......................................................................................................................................... 77
Monitor Unit .............................................................................................................................................................. 77
System Troubleshooting Information ............................................................................................. 77
Replacement Information ............................................................................................................................ 77
Replacing the Monitor Unit .............................................................................................................................. 77
Replacing a Distribution Device .................................................................................................................. 78
Replacing a Distribution Panel..................................................................................................................... 94
Replacing an Output Bar with Sensor in a List 15A or List 25A
Distribution Panel ..................................................................................................................................................... 96
Vertiv |NetSure 8100 Series Installation & User Manual (UM582140600)|Rev. A
Page 5
5
DAN
or serious injury if not avoided. (ANSI, OSHA)
WARNING!
in death or serious injury if not
pose a risk only to equipment, software, data, or service. (ANSI)
CAUTION!
in minor or moderate injury if not avoided. (
situations that pose a risk only to equipment, data, or service, even if such use appears to
be permitted in some of the applicable standards. (OSHA)
ALERT!
equipment, software, data, or service. (ISO)
ALERT!
equipment damage, software corruption, data loss, or service interruption. (ISO)
FIRE SAFETY!
policies, or of the locations of fire
SAFETY!
policies not related
ADMONISHMENTS USED IN THIS DOCUMENT
GER! Warns of a hazard the reader
Warns of a potential hazard the reader
avoided. This admonition is not used for situations that
Warns of a potential hazard the reader
Alerts the reader to an action that
Alerts the reader to an action that
will
be exposed to that will
may
be exposed to that
may
be exposed to that
ANSI, OSHA) This admonition is not used for
must be avoided
in order to protect
must be performed
likely
result in death
could
could
in order to prevent
result
result
Informs the reader of fire safety information, reminders, precautions, or
-fighting and fire-safety equipment. (ISO)
Informs the reader of general safety information, reminders, precautions, or
to a particular source of hazard or to fire safety. (ISO, ANSI, OSHA)
Vertiv |NetSure 8100 Series Installation & User Manual (UM582140600)|Rev. A
Page 6
6
IMPORTANT SAFETY INSTRUCTIONS
General Safety
DANGER! YOU MUST FOLLOW APPROVED SAFETY PROCEDURES.
Performing the following procedures may expose you to hazards. These procedures should be
performed by qualified technicians familiar with the hazards associated with this type of equipment.
These hazards may include shock, energy, and/or burns. To avoid these hazards:
a) The tasks should be performed in the order indicated.
b) Remove watches, rings, and other metal objects.
c) Prior to contacting any uninsulated surface or termination, use a voltmeter to verify that no voltage or
the expected voltage is present. Check for voltage with both AC and DC voltmeters prior to making
contact.
d) Wear eye protection.
e) Use certified and well maintained insulated tools. Use double insulated tools appropriately rated for the
work to be performed.
DC Voltages
DANGER! This system has DC voltage connected to it. Although the DC voltage is not hazardously
high, the associated rectifiers and/or battery can deliver large amounts of current. Exercise extreme
caution not to inadvertently contact or have any tool inadvertently contact an input or output terminal or
exposed wire connected to an input or output terminal. NEVER allow a metal object, such as a tool, to
contact more than one termination at a time, or to simultaneously contact a termination and a grounded
object. Even a momentary short circuit can cause sparking, explosion, and injury.
DANGER! Follow local lockout/tagout procedures to ensure DC branch circuit protection devices
remain de-energized during installation at loads, as required.
Vertiv |NetSure 8100 Series Installation & User Manual (UM582140600)|Rev. A
Page 7
7
Personal Protective Equipment (PPE)
DANGER! ARC FLASH AND SHOCK HAZARD.
Appropriate PPE and tools required when working on this equipment. An appropriate flash protection
boundary analysis should be done determine the “hazard/risk” category, and to select proper PPE.
This product is intended only for installation in a Restricted Access Location.
Only authorized and properly trained personnel should be allowed to install, inspect, operate, or maintain
the equipment.
Do not work on LIVE parts. If required to work or operate live parts, obtain appropriate Energized Work
Permits as required by the local authority, per NFPA 70E “Standard for Electrical Safety in the
Workplace”.
ALERT! Installation or removal of equipment containing static sensitive components requires careful
handling. Before handling any equipment containing static sensitive components, read and follow the
instructions contained on the Static Warning Page.
Maintenance and Replacement Procedures
CAUTION! When performing any step in procedures that requires removal or installation of hardware,
use caution to ensure no hardware is dropped and left inside the unit; otherwise service interruption or
equipment damage may occur.
NOTE!
When performing any step in procedures that requires removal of existing hardware, retain all
hardware for use in subsequent steps, unless otherwise directed.
Vertiv |NetSure 8100 Series Installation & User Manual (UM582140600)|Rev. A
Page 8
8
STATIC WARNING
This equipment contains static sensitive components. The warnings listed below must be observed to
prevent damage to these components. Disregarding any of these warnings may result in personal injury
or damage to the equipment.
1. Strictly adhere to the procedures provided in this document.
2. Before touching any equipment containing static sensitive components, discharge all static electricity
from yourself by wearing a wrist strap grounded through a one megohm resistor. Some wrist straps
have a built-in one megohm resistor; no external resistor is necessary. Read and follow wrist strap
manufacturer’s instructions outlining use of a specific wrist strap.
3. Do not touch traces or components on equipment containing static sensitive components. Handle
equipment containing static sensitive components only by the edges that do not have connector pads.
4. After removing equipment containing static sensitive components, place the equipment only on
conductive or anti-static material such as conductive foam, conductive plastic, or aluminum foil. Do not
use ordinary Styrofoam™ or ordinary plastic.
5. Store and ship equipment containing static sensitive components only in static shielding containers.
6. If necessary to repair equipment containing static sensitive components, wear an appropriately
grounded wrist strap, work on a conductive surface, use a grounded soldering iron, and use grounded
test equipment.
Vertiv |NetSure 8100 Series Installation & User Manual (UM582140600)|Rev. A
Page 9
9
CUSTOMER DOCUMENTATION PACKAGE
This document (UM582140600) provides Installation and User Instructions for NetSure™ -48 VDC Power
Distribution System Model 8100DB, Spec. No. 582140600.
The complete Customer Documentation Package consists of…
NetSure™ -48 VDC Power Distribution System Installation and User Manual
• Installation and User Instructions: UM582140600
• System Application Guide: SAG582140600
• Engineering Drawings
• Contact Information Page: Section 4154
NetSure™ Monitor Unit User Manual
• Monitor Unit User Instructions: UM1M832DNA
Configuration Drawing
• Available is a configuration drawing (C-drawing).
For factory settings of all configurable parameters, refer to the configuration drawing (C-drawing) supplied with
your system.
SYSTEM DESCRIPTION
-48 VDC Power Distribution System
The NetSure™ 8100DB DC Power Distribution System is a -48 VDC Battery Distribution Fuse / Circuit Breaker
Bay (BDF/CBB).
• The NetSure™ 8100
panels per side).
• Each distribution panel can be configured for separate inputs giving you an 8-load or 6-load bay, or the
panels per side can be paralleled to allow one to four feeds per side giving you a 2-load bay (may use
the optional internal ground/return bar). Other configurations include an 8-panel bay with 4-loads and
two loads, and a 6-panel bay with 4-loads (paralleling the top two panels or paralleling the bottom two
panels per side).
• Each bay can be equipped with an optional “full bay length” internal ground/return bar (per side).
Another option includes replacing one (8- and 6-panel bays) or two (8-panel bay only) distribution
panels per side with a “panel length” internal ground/return bar.
• Each bay can easily be configurable for top or bottom feed.
DB can be ordered as an 8-distribution panel or 6-distribution panel bay (4 or 3
• Each bay is equipped with a monitor unit. The monitor unit provides local and remote access to data
and alarms for the voltage, current, power, and energy delivered through the distribution bay. The
monitor unit contains a color TFT display and keypad for local access. The monitor unit provides an
Ethernet port and comes with comprehensive webpages for remote access. The monitor unit can also
be accessed via SNMP (v2 and v3), TL1 (over Ethernet), or MODBUS for remote system management.
The monitor unit supports software upgrade via its USB port. A machine-to-machine HTTP interface is
also available. Refer to the monitor unit instructions (UM1M832DNA) for more information.
Vertiv |NetSure 8100 Series Installation & User Manual (UM582140600)|Rev. A
Page 10
10
Each bay includes an SM-DUE. The SM-DUE sends information to the monitor unit and the monitor unit
monitors and displays load voltage, load current, and fuse alarm / circuit breaker alarm status of each
distribution panel in the bay.
The advanced distribution panels are equipped with an SM-DUH2. The SM-DUH2 sends information to
the monitor unit and the monitor unit additionally displays load voltage, load current, and fuse alarm /
circuit breaker alarm status of each distribution device in the advanced distribution panel.
Also provided in each bay is an IB2 (interface board) connected to the monitor unit. The IB2 board
provides four (4) programmable form C- relay outputs.
• Choices of distribution panels is a panel that accepts TPS / TLS and TPL-B fuses and a panel that
accepts bullet nose type circuit breakers and/or bullet nose type TPS / TLS fuseholders. The bullet
nose type distribution panel is available in a standard configuration or an advanced configuration. The
standard configuration allows for monitoring the panel as one unit. The advance configuration also
allows for monitoring each individual distribution device on the panel.
Refer to SAG582140600 (System Application Guide) for additional information.
INSTALLATION ACCEPTANCE CHECKLIST
Provided in this section is an Installation Acceptance Checklist. This checklist helps ensure proper installation
and initial operation of the system. As the procedures presented in this document are completed, check the
appropriate box on this list. If the procedure is not required to be performed for your installation site, also
check the box in this list to indicate that the procedure was read. When installation is done, ensure that each
block in this list has been checked. Some of these procedures may have been factory performed for you.
Physically Installing the System
Making Switch and Jumper Settings
NOTE!
NOTE!
Bay Mounted to the Floor
Distribution Panel Paralleling Bar(s) Installed (if required)
Internal Ground/Return Busbar Paralleling Bar Installed (if required)
Input Feed and Shunt Assembly Installed (if required)
Factory Switch Settings on IB2 Board Verified
The system is not powered up until the end of this checklist.
Some of these procedures may have been performed at the factory for you.
Factory Switch Settings on SM-DUE Board Verified
Factory Jumper Settings on SM-DUE Board Verified
Factory Switch Settings on SM-DUH2 Board Verified
Making Electrical Connections
Bay Frame Grounding Connection Made
External Alarm, Reference, Monitoring, and Control Connections Made
Vertiv |NetSure 8100 Series Installation & User Manual (UM582140600)|Rev. A
Page 11
11
Return Connected to RTN A and/or RTN B.
System Ethernet Connection Made
Optional Transient Voltage Surge Suppressor (TVSS) Device Installed and Wired
Load Distribution Connections Made
DC Input Connections Made
Installing Circuit Breakers and Fuses
Circuit Breakers and Fuses Installed
Initially Starting, Configuring, and Checking System Operation
System Started, Configured, and Checked
PHYSICALLY INSTALLING THE SYSTEM
General Requirements
• This product is intended only for installation in a restricted access location on or above a non-
combustible surface.
• This BDF/CBB uses natural convection. Equipment is designed for use in environmentally controlled
space.
• This product is intended for installation in network telecommunication facilities (CO, vault, hut, or other
• This product is intended to be connected to the common bonding network in a network
telecommunication facility (CO, vault, hut, or other environmentally controlled electronic equipment
enclosure).
• The installer should be familiar with the installation requirements and techniques to be used in securing
the bay to the floor.
• Typical industry standards recommend minimum aisle space clearance of 2'6" for the front of the bay
and 2' for the rear of the bay.
• Ventilating openings must not be blocked and temperature of air entering the bay must not exceed
rated operating ambient temperature range found in SAG582140600.
Installing the Bays
Ventilation Requirements
Refer to the “General Requirements” on page 11.
Placing and Securing the Bay to the Floor
Refer to the “General Requirements” on page 11.
Procedure
1. Locate where the bay is to be placed.
2. Drill mounting holes in the floor per site requirements. Refer to Figure 1 and Figure 2 for floor mounting
holes drilling dimensions.
3. Place the bay in position.
Vertiv |NetSure 8100 Series Installation & User Manual (UM582140600)|Rev. A
Page 12
12
4. Secure the bay to the floor by installing mounting hardware into floor per site requirements.
Figure 1:
List 01 and List 07 Floor Hole Drilling Pattern Dimensions
Figure 2:
List 03 and List 09 Floor Hole Drilling Pattern Dimensions
Vertiv |NetSure 8100 Series Installation & User Manual (UM582140600)|Rev. A
Page 13
13
Distribution Panel
(List 10, List 15 and
List 15A similar)
Distribution Panel
(List 10, List 15 and
List 15A similar)
Distribution Panel
(List 20, List 25 and
List 25A similar)
Distribution Panel
(List 20, List 25 and
List 25A similar)
Distribution Panel
Paralleling Bar
(List 31, includes
2 bars, 1 for each
side, only 1 shown)
Distribution Panel
Paralleling Bar
(List 30, includes
2 bars, 1 for each
side, only 1 shown)
Rear
Rear
Rear
Rear
Hardware Build-Up
3/8-16 x 1 Bolt
3/8 Belleville Lock Washer
3/8 Flat Washer
Torque to 180 in-lbs.
Hardware Build-Up
3/8-16 x 1 Bolt
3/8 Belleville Lock Washer
3/8 Flat Washer
Torque to 180 in-lbs.
Distribution Panel
(List 10, List 15 and
List 15A similar)
Distribution Panel
(List 20, List 25 and
List 25A similar)
Distribution Panel
(List 10, List 15 and
List 15A similar)
Distribution Panel
(List 20, List 25 and
List 25A similar)
Distribution Panel
Paralleling Bar
P/N 563497
Distribution Panel
Paralleling Bar
P/N 563497
Hardware Build-Up
3/8-16 x 1-1/4 Bolt
3/8 Belleville Lock Washer
3/8 Flat Washer
Torque to 180 in-lbs.
Hardware Build-Up
3/8-16 x 1-1/4 Bolt
3/8 Belleville Lock Washer
3/8 Flat Washer
Torque to 180 in-lbs.
Installing Distribution Panel Paralleling Bars (if furnished)
Procedure
1. If distribution panel paralleling bars (List 30, List 31, P/N 563497) are furnished, attach the paralleling
bars per Figure 3.
Figure 3:
Installing Distribution Panel Paralleling Bars (List 30, List 31, P/N 563497)
Vertiv |NetSure 8100 Series Installation & User Manual (UM582140600)|Rev. A
Page 14
14
Installing the Internal Ground/Return Busbar Paralleling Bars List 39 (8-Panel Bay Only)
(if furnished)
Procedure
1. If internal ground/return busbars (List 17) are furnished and the paralleling bars (List 39) are furnished,
attach the paralleling bars per Figure 4.
Figure 4:
Installing the Internal Ground/Return Busbar Paralleling Bars (List 39) (8-Panel Bay Only)
Vertiv |NetSure 8100 Series Installation & User Manual (UM582140600)|Rev. A
Page 15
15
Location and
Orientation View
List 43
(Top Feed)
List 43
Bottom Feed
Addtional input feed and shunt
assemblies are installed on any
distribution panel not paralleled
with a distribution panel that has
an input feed and shunt
assembly installed.
List 43
Input Feed and
Shunt Assembly
List 43
Input Feed and
Shunt Assembly
Rear View
8-Panel Bay
(6-Panel Bay Similar)
Portion of bay removed
in illustration for clarity.
Not to Scale
List 43
List 43
Field Installing Bay Input Feed and Shunt Assembly List 43
Procedure
1.Refer to Figure 5.
Figure 5:
Field Installing Bay Input Feed and Shunt Assembly (List 43) (cont’d on next page)
Vertiv |NetSure 8100 Series Installation & User Manual (UM582140600)|Rev. A
Page 16
16
Hardware Build-Up
and Torque Values
Apply anti-oxidation compound
to busbar mating surfaces.
4 Places (2 per side)
See Parts List
TORQUE TO 180 IN-LBS.
4 Places (2 per side)
See Parts List
TORQUE TO 180 IN-LBS.
Figure 5:
Field Installing Bay Input Feed and Shunt Assembly (List 43) (cont’d from previous page, cont’d on
next page)
Vertiv |NetSure 8100 Series Installation & User Manual (UM582140600)|Rev. A
Page 17
17
Shunt Lead Connections
8-Panel Bay, Top Feed
R
BK
R
BK
R
BK
R
BK
R
BK
R
BK
R
BK
R
BK
R
BK
R
BK
R
BK
R
BK
R
BK
R
BK
R
BK
R
BK
List 09
Bay
List 07
Bay
List 07
Bay
List 09
Bay
Note
All shunt leads not factory connected to shunts
are factory shorted together and insulated if no
panel is installed; otherwise, if a panel is
installed the leads are shorted together and
terminated on the bus.
Figure 5:
Field Installing Bay Input Feed and Shunt Assembly (List 43) (cont’d from previous page, cont’d on
next page)
Vertiv |NetSure 8100 Series Installation & User Manual (UM582140600)|Rev. A
Page 18
18
Shunt Lead Connections
8-Panel Bay, Bottom Feed
List 07
Bay
List 09
Bay
List 09
Bay
List 07
Bay
Note
All shunt leads not factory connected to shunts
are factory shorted together and insulated if no
panel is installed; otherwise, if a panel is
installed the leads are shorted together and
terminated on the bus.
R
BK
R
BK
R
BK
R
BK
R
BK
R
BK
R
BK
R
BK
R
BK
R
BK
R
BK
R
BK
R
BK
R
BK
R
BK
R
BK
Figure 5:
Field Installing Bay Input Feed and Shunt Assembly (List 43) (cont’d from previous page, cont’d on
next page)
Vertiv |NetSure 8100 Series Installation & User Manual (UM582140600)|Rev. A
Page 19
19
Shunt Lead Connections
6-Panel Bay, Top Feed
List 01
Bay
List 03
Bay
List 03
Bay
List 01
Bay
Note
All shunt leads not factory connected to shunts
are factory shorted together and insulated if no
panel is installed; otherwise, if a panel is
installed the leads are shorted together and
terminated on the bus.
R
BK
R
BK
R
BK
R
BK
R
BK
R
BK
R
BK
R
BK
R
BK
R
BK
R
BK
R
BK
Figure 5:
Field Installing Bay Input Feed and Shunt Assembly (List 43) (cont’d from previous page, cont’d on
next page)
Vertiv |NetSure 8100 Series Installation & User Manual (UM582140600)|Rev. A
Page 20
20
Shunt Lead Connections
6-Panel Bay, Bottom Feed
List 01
Bay
List 03
Bay
List 03
Bay
List 01
Bay
Note
All shunt leads not factory connected to shunts
are factory shorted together and insulated if no
panel is installed; otherwise, if a panel is
installed the leads are shorted together and
terminated on the bus.
R
BK
R
BK
R
BK
R
BK
R
BK
R
BK
R
BK
R
BK
R
BK
R
BK
R
BK
R
BK
Figure 5:
Field Installing Bay Input Feed and Shunt Assembly (List 43) (cont’d from previous page)
Vertiv |NetSure 8100 Series Installation & User Manual (UM582140600)|Rev. A
Page 21
21
Front
(panels removed for clarity only)
Components removed in
illustration for clarity only.
IB2
SM-DUE
SM-DUH2
List 15A Distribution Panel
(List 25A Similiar)
MAKING SWITCH AND JUMPER SETTINGS
Circuit Cards with Jumpers and/or Switches Locations
Refer to Figure 6.
Figure 6:
Circuit Cards with Jumpers and/or Switches Locations
Vertiv |NetSure 8100 Series Installation & User Manual (UM582140600)|Rev. A
Page 22
22
IB2
OFF
OFF
Setting
DIP Switch SW1
12
IB2OFFOFF
ONOFF
1
2
SW1
SW1
In this system, switch settings
must be in positions shown.
IB2 Interface Board
ON OFF
1
2
-
J12
SW1
7
J2
J11
531
Relay Out put Ter minal BlocksDigital Input Terminal Blocks
J9J8J7J6J5J4J3
+
NOCNC
NOCNC
531531531531
NOCNC
531
NOCNC
531
NOCNC
531
4 624 624 624 62
NOCNC
4 62
NOCNC
4 62
NOCNC
4 62
Relay
No.
Relay
No.
87654321
8642
87
6543
21
Input
No. (+)
Input
No. (
–
)
Switch SW1 is located in
this corner of the IB2 board.
Switch Settings on IB2 Interface Board
Dip switch SW1 on the IB2 board is used to set the communications address for this board. Refer to Table 1 for
SW1 settings. Refer to Figure 6 for circuit card location. Refer to Figure 7 for SW1 location.
Perform the following procedure to verify the factory settings. This procedure can also be used to make
adjustments on a replacement circuit card.
Procedure
1.Ensure SW1 is set per Table 1. Refer to Figure 7 for location.
Table 1:
Figure 7:
IB2 Interface Board Switch Settings
DIP Switch SW1
Setting
1 2
IB2 Interface Board Switch Location and Settings
Vertiv |NetSure 8100 Series Installation & User Manual (UM582140600)|Rev. A
Page 23
23
Communication Address
(Use Switch 1, 2, and 3 of SW1)
1 2 3
Off
Off
Off
Base Default
Off
Off
On
Base +1
Off
On
Off
Base +2
Off
On
On
Base +3
On
Off
Off
Base +4
On
Off
On
Base +5
On
On
Off
Base +6
On
On
On
Base +7
Baud Rate for Serial Port
(Use Switch 4 of SW1)
4
Off
19200 (Note 1)
On
9600
Parameter of Shunt Setting
(Use Switch 5 of SW1)
5
Off
Shunt parameter is set through software (Note 1).
On
Shunt parameter is set through DIP switch.
Switch Settings on SM-DUE
An SM-DUE is located in each bay. The SM-DUE is used to monitor individual distribution panels in the bay.
Dip switch SW1 on the SM-DUE board is used for parameter settings. Refer to Table 2 for SW1 settings. Refer
to Figure 6 for circuit card location. Refer to Figure 8 for SW1 location.
Perform the following procedure to verify the factory settings. This procedure can also be used to make
adjustments on a replacement circuit card.
Procedure
1.Ensure SW1 is set per Table 2. Refer to Figure 8 for location.
Table 2:
NOTE!
The permissible address range is 219 to 226. The default address of the board is 219.
SM-DUE Switch Settings (cont’d on next page)
Communication
Function Descriptions
Function Descriptions
Configured by Hardware or
Software
Vertiv |NetSure 8100 Series Installation & User Manual (UM582140600)|Rev. A
Function Descriptions
Page 24
24
Shunt Voltage
(Use Switch 6 of SW1)
6
Off
25 mV (Note 1)
On
50 mV
Shunt Current
(Use Switch 7 and 8 of SW1)
7
8
Off
Off
500 A (Note 1)
Off
On
1000 A
On
Off
1500 A
On
On
2000 A
ON
ON
OFF
OFF
18
18
SW1
SW1
Green LED
Red LED
Table 2:
SM-DUE Switch Settings (cont’d from previous page)
Note 1: Setting for this system.
Figure 8:
SM-DUE Switch Location
Function Descriptions
Function Descriptions
Vertiv |NetSure 8100 Series Installation & User Manual (UM582140600)|Rev. A
Page 25
25
Jumper Position
1-2
3-4
5-6
Measure General -Purpose
Transducer
0 mV DC to 50 mV
DC (Note 1)
Measure General-Purpose Transducer
0 mA to 20 mA
ON
ON
OFF
Measure Temperature Sensor
1 uA/K
ON
OFF
OFF
Jumper Settings on SM-DUE
An SM-DUE is located in each bay. The SM-DUE is used to monitor individual distribution panels in the bay.
There are thirty (30) 2-pin jumpers on the SM-DUE. Three (3) for each of the ten (10) SM-DUE’s analog inputs.
These jumpers must be set according to the type of analog signal that will be measured. Refer to Table 3 for
jumper settings. Refer to Figure 6 for circuit card location. Refer to Figure 9 for jumper locations.
Perform the following procedure to make the required setting per your site requirements.
This procedure can also be used to make adjustment on a replacement circuit card.
Analog Inputs AI1 to AI10
Procedure
1.Ensure the jumpers for each analog input are set per Table 3. Refer to Figure 9 for location.
Table 3:
SM-DUE Jumper Settings
Type of input Signal Range
Measure Shunt Current
Note 1: Setting for this system.
0 VDC to 10 VDC OFF OFF OFF
ON OFF ON
Vertiv |NetSure 8100 Series Installation & User Manual (UM582140600)|Rev. A
Page 26
26
ON
OFF
18
Channel 1
Jumpers
1 3 5
2 4 6
Jumpers
1 3 5
2 4 6
Jumpers
1 3 5
2 4 6
Jumpers
1 3 5
2 4 6
Jumpers
1 3 5
2 4 6
Jumpers
1 3 5
2 4 6
Jumpers
1 3 5
2 4 6
Jumpers
1 3 5
2 4 6
Jumpers
1 3 5
2 4 6
Jumpers
1 3 5
2 4 6
Channel 2Channel 3Channel 4Channel 5
Channel 6Channel 7Channel 8Channel 9Channel 10
SW1
Green LED
Red LED
Figure 9:
SM-DUE Jumper Location
Vertiv |NetSure 8100 Series Installation & User Manual (UM582140600)|Rev. A
Page 27
27
Off
Off
Off
Off
Off
Off
0
211
Off
On
Off
Off
Off
Off 2 213
Off
Off
On
Off
Off
Off 4 215
Off
On
On
Off
Off
Off 6 217
Communication Baud
Switch Settings on SM-DUH2
The SM-DUH2 is used in a List 15A and List 25A distribution panel to monitor individual distribution devices in
the distribution panel.
Dip switch SW1 on the SM-DUH2 board is used to set the communications address for this board and the
communications baud rate. Refer to Table 4 for SW1 settings. Refer to Figure 6 for circuit card location. Refer
to Figure 10 for SW1 location.
Perform the following procedure to verify the factory settings. This procedure can also be used to make
adjustments on a replacement circuit card.
Procedure
1.Ensure SW1 is set per Table 4. Refer to Figure 10 for location.
Table 4:
1 2 3 4 5 6 7 8
SM-DUH2 Switch Settings
SW1
Offset
Address
On Off Off Off Off Off 1 212
On On Off Off Off Off 3 214
NA
On Off On Off Off Off 5 216
On On On Off Off Off 7 218
NA OFF N/A
NA ON N/A
Rate: 19200 (Note 1)
Communication Baud
Rate: 9600
Note 1: Setting for this system.
Actual
Address
Vertiv |NetSure 8100 Series Installation & User Manual (UM582140600)|Rev. A
Page 28
28
Green LED
Red LED
ON (DOWN)
ON (DOWN)
ON is designated by shading.
OFF is designated by no shading.
18
18
SW1
SW1
Switch location
may vary.
Figure 10:
SM-DUH2 Switch Location
Vertiv |NetSure 8100 Series Installation & User Manual (UM582140600)|Rev. A
Page 29
29
Burndy:
Burndy:
Burndy:
T & B:
Burndy:
Burndy:
MAKING ELECTRICAL CONNECTIONS
Important Safety Instructions
DANGER! Adhere to the “Important Safety Instructions” presented at the front of this document.
Wiring Considerations
All wiring and branch circuit protection should follow the current edition of the American National Standards
Institute (ANSI) approved National Fire Protection Association's (NFPA) National Electrical Code (NEC), and
applicable local codes. For operation in countries where the NEC is not recognized, follow applicable codes.
For wire size, branch circuit protection, crimp lug, and general wiring recommendations; refer to System
Application Guide SAG582140600.
Lugs should be crimped per lug manufacturer’s specifications.
Refer to Table 5 for supplemental lug crimping information when using the special application crimp lug / strap
combination.
Table 5:
Supplemental Lug Crimping Information when Using the Special Application Crimp Lug / Strap
Combination
Crimp Tool Required1,
T&B Model TBM12 or TBM15 Hydraulic
Crimp Lug Part No.
Color Key
Heads
Die Index/
Code No.
Die Cat.
Number
245393500
245393600
245393700
245393800
514872
514873
1
The lugs should be crimped to the specifications given in the
manufacturer’s instructions furnished with the crimp tool or lug.
Burndy:
YA25L-4TCG1
YA26L-4TCG1
YA27L-4TCG1
YA28L-4TCG1
256-30695-1879
YA29L-4TCG1
T & B:
256-30695-
1880
YA31L-4TCG1
Pink 42H 15508
Black 45 15526
Orange 50 15530
Purple 54H 15511
Yellow 62 15510
Red 71 15514
Vertiv |NetSure 8100 Series Installation & User Manual (UM582140600)|Rev. A
Page 30
30
Bay Overall Connections Diagram
Figure 11:
Bay Overall Connections Diagram
Vertiv |NetSure 8100 Series Installation & User Manual (UM582140600)|Rev. A
Page 31
31
Bay Frame Grounding Connection
For bay grounding requirements, refer to the current edition of the American National Standards Institute
(ANSI) approved National Fire Protection Association's (NFPA) National Electrical Code (NEC), applicable local
codes, and your specific site requirements. For operation in countries where the NEC is not recognized, follow
applicable codes.
A customer's grounding network lead can be attached to the top of each bay. Provision is made for installing a
lead with a two-hole lug that has 1/4" bolt clearance holes on 5/8" centers. When using 1/4-inch hardware,
recommended torque is 84 in-lbs when a standard flat washer and lock washer are used. Refer to Figure 12 for
locations.
NOTE!
Figure 12:
REMOVE TAPE (IF PRESENT) FROM HOLE LOCATIONS BEFORE INSTALLING LUG.
Bay Frame Grounding Connection Points
Vertiv |NetSure 8100 Series Installation & User Manual (UM582140600)|Rev. A
Page 32
32
External Alarm, Reference, Monitoring, and Control Connections
Circuit Card locations
Refer to Figure 11.
IB2 (Interface Board) Connections
The IB2 (Interface Board) provides connection points for programmable relay outputs. The IB2 interface board
is mounted inside the bay. Refer to Figure 11 for location.
Programmable Relay Outputs - IB2
Relay output leads are connected to screw-type terminal blocks located on the IB2. Recommended torque for
these connections is 2.2 in-lbs. Refer to Figure 13 for terminal locations. Refer to Table 6 for pin-out
information.
The IB2 provides four (4) programmable alarm relays with dry Form-C contacts. Connect up to four (4) relay
outputs to relay 1 through 4 on the IB2. Refer to Figure 13 for terminal locations and Table 6 for pin-out
information.
Refer to the Monitor Unit Instructions (UM1M832DNA) for programming information.
Relay Ratings: Refer to the following.
a) 1 A Steady State @ 30 VDC.
a) 3 A Peak @ 30 VDC.
The relays may be preprogrammed for specific functions. Refer to the configuration drawing (C-drawing)
supplied with your system for your system’s specific configuration.
Vertiv |NetSure 8100 Series Installation & User Manual (UM582140600)|Rev. A
Page 33
33
* The relay assigned to “Critical Summary” alarm (relay 1 by default)
will operate in the “Fail Safe Mode”. “Fail Safe Mode” means Relay 1 is
de-energized during an alarm condition, opening the contacts between the
C and NO terminals, and closing the contacts between the C and NC terminals.
The remaining seven (7) relays energize during an alarm condition, closing the
contacts between the C and NO terminals, and opening the contacts between
the C and NC terminals.
Not all I/O points are available for customer connection (some are used for factory
system connections).
Vertiv |NetSure 8100 Series Installation & User Manual (UM582140600)|Rev. A
Page 34
34
NO
J6-5
COM
J6-3
NC
J6-1
NO
J6-6
COM
J6-4
NC
J6-2
NO
J7-5
COM
J7-3
NC
J7-1
NO
J7-6
COM
J7-4
NC
J7-2
NO
J8-5
COM
J8-3
NC
J8-1
NO
J8-6
COM
J8-4
NC
J8-2
NO
J9-5
COM
J9-3
NC
J9-1
NO
J9-6
COM
J9-4
NC
J9-2
Table 6:
Programmable Relay Outputs – IB2
NOTE!
The output relay configuration may not be set according to the factory default setting. Refer to
the configuration drawing (C-drawing) supplied with your system for your system’s specific
configuration.
Programmable
Relay Output
1
2
3
4
IB2
Pin No.
Alarms Assigned to this
Relay (Default)
Alarms Assigned to this
Relay (Custom)
5
6
Cannot be used in this system.
7
8
NOTE!
The relay assigned to “Critical Summary” alarm (relay 1 by default) will operate in the “Fail Safe
Mode”. “Fail Safe Mode” means Relay 1 is de-energized during an alarm condition, opening the contacts
between the C and NO terminals, and closing the contacts between the C and NC terminals.
The remaining seven (7) relays energize during an alarm condition, closing the contacts between the C
and NO terminals, and opening the contacts between the C and NC terminals.
Vertiv |NetSure 8100 Series Installation & User Manual (UM582140600)|Rev. A
Page 35
35
F1
Aux Load 1A (-48V)
TB3-2
F3
Aux Load 3B (-48V)
TB4-2
Auxiliary Fuse Board Connections
An auxiliary fuse circuit card is located behind the top right panel in each bay. This circuit card provides four
fuses for auxiliary equipment loads and two fuses for optional external (ABS) power to the system’s electronics.
All fuses are rated at 1-1/3A. Terminal blocks are provided on the circuit card for auxiliary load connections and
external (ABS) system electronics input power connections.
Refer to Figure 14 for connection details. Recommended torque for terminal block connections is shown in
Figure 14.
System’s Electronics External Input Connections
Refer to the following procedure and Figure 14.
1. Connect terminals 1 of TB1 and TB2 to an external “Ground/Return” point.
2. Connect an external “-48V Source” to terminal 2 of TB1. For an A and B input configuration, connect a
second “-48V Source” to terminal 2 of TB2.
Auxiliary Load Connections
Four circuits, each fused at 1-1/3A, are provided for connection of auxiliary loads. Refer to SAG582140600 for
recommended wire size. Refer to the following procedure and Figure 14.
WARNING! Load should not exceed 80% of device rating.
1. Connect load -48V leads as shown in Table 7.
2. Connect load Return leads to a system ground/return bar.
Table 7:
Auxiliary Load Connections
Fuse Circuit Name Terminal
F2 Aux Load 2A (-48V) TB3-1
F4 Aux Load 4B (-48V) TB4-1
Vertiv |NetSure 8100 Series Installation & User Manual (UM582140600)|Rev. A
Page 36
36
F1
F2
F3
F4
F5
F6
Auxiliary Fuse Card
Located Behind
Removable Panel
-48V
RTN
-48V
RTN
AB
1A (-48V)
2A (-48V)
3B (-48V)
4B (-48V)
Fused Aux.
Loads
See Note 2
ABS_A ABS_B
not
used
TB5TB1TB2TB3TB4
See Note 1
2121212121
FuseFunction
F1Aux Load 1A
F2Aux Load 2A
F3Aux Load 3B
F4Aux Load 4B
F5ABS Power A
F6
ABS Power B
All fuses 1-1/3A.
ABS and Aux. Supply Connections
NOTES:
1. For optional external (ABS)
power to the electronics, connect
source A to TB1 and source B to
TB2. Observe correct polarity as
shown.
2. Connect Return (+) leads for
Fused Auxiliary Loads to system
ground bar.
Figure 14:
Auxiliary Fuse Card Connections
Vertiv |NetSure 8100 Series Installation & User Manual (UM582140600)|Rev. A
Page 37
37
Rear View
+RTN A
10-32 threaded stud.
See Note 1.
+RTN B
10-32 threaded stud.
See Note 2.
Ground/Return Input Connections for
Auxiliary Fuse Card
NOTES:
1. Connect “+RTN A” to the system
Ground/Return busbar. If the bay is config ured for A/B operation, connect to the A side
system Ground/Return busbar.
2. If the bay is configured for A/B operation,
connect “+RTN B” to the B side system
Ground/Return busbar.
3. Torque to 24 in-lbs.
Ground/Return Input Connections for Auxiliary Fuse Card
System Ground/Return must be supplied to the auxiliary fuse card by the installer. Busbars located behind the
card and accessible through the back of the bay provide connection points for A side and B side connections.
Terminate each wire with a one-hole lug having a clearance hole for a 10-32 stud. Refer to Figure 15 for
connection location. Recommended torque for terminal block connections is shown in Figure 15.
1. Connect the lug-terminated end of a lead to the +RTN A busbar. Connect the remaining end of the lead
to the system Ground/Return busbar. If the bay is configured for A/B operation, connect lead to the A
side system Ground/Return busbar.
2. If the bay is configured for A/B operation, connect the lug-terminated end of a lead to the +RTN B
busbar. Connect the remaining end of the lead to the B side system Ground/Return busbar.
Vertiv |NetSure 8100 Series Installation & User Manual (UM582140600)|Rev. A
Page 38
38
System Ethernet Port Connections
The monitor unit provides a Web Interface via an Ethernet connection to a TCP/IP network. This interface can
be accessed locally on a computer and/or remotely through a network. The system has two Ethernet ports.
One located on the monitor unit top panel and the other located on the IB4 board. The function of these
Ethernet ports are as follows.
Monitor Unit Top Panel Ethernet Port
An RJ-45 10BaseT jack is provided on the top panel of the monitor unit for connecting a computer directly to
the monitor unit. This jack has a standard Ethernet pin configuration scheme, twisted pair. Refer to Figure 16
for location. Refer to the Monitor Unit Instructions (UM1M832DNA) for operational details.
NOTE!
Your system has an IB4 board, DO NOT connect your Local Area Network (LAN) to the monitor
unit’s top panel Ethernet port.
Default Monitor Unit Ethernet Port Parameters
Default IP address is 192.168.100.100.
IB4 Board Ethernet Port
An RJ-45 10BaseT jack is provided on the IB4 board for connection into a customer's network. Use this
Ethernet port to connect the monitor unit to your Local Area Network (LAN). This jack has a standard Ethernet
pin configuration scheme, twisted pair. Refer to Figure 11 for IB4 board location. Refer to Figure 16 for
Ethernet port location. Use shielded Ethernet cable (grounded at both ends). Note that the IB4 board’s RJ-45
jack is connected to chassis ground. Refer to the Monitor Unit Instructions (UM1M832DNA) for operational
details.
WARNING! The intra-building port(s) of the equipment or subassembly is suitable for connection to
intra-building or unexposed wiring or cabling only. The intra-building port(s) of the equipment or
subassembly MUST NOT be metallically connected to the interfaces that connect to the OSP or its
wiring. These interfaces are designed for use as intra-building interfaces only (Type 2 or Type 4 ports as
described in GR-1089-CORE, Issue 4) and require isolation from the exposed OSP cabling. The addition
of Primary Protectors is not sufficient protection in order to connect these interfaces metallically to OSP
wiring.
The intra-building port (RJ-45) of the equipment or subassembly must use shielded intra-building
cabling/wiring that is grounded at both ends.
Vertiv |NetSure 8100 Series Installation & User Manual (UM582140600)|Rev. A
Page 39
39
M832D
10/100M Ethernet Port (RJ-45)
(to connect a computer directly
to the Monitor Unit)
10M Ethernet
Port (RJ-45)
LAN Connection
USB-B Port
(factory
connected)
USB-A Port
(not used)
IB4 Board
Monitor Unit
Figure 16:
System Ethernet Ports
Installing and Wiring to an Optional Transient Voltage Surge Suppressor (TVSS) Device
Transient Voltage Surge Suppressor (TVSS) devices are installed in the 'distribution device' mounting positions
of a List 15, List 15A, List 25, and List 25A distribution panel only.
When required, all unparalleled distribution panels require a TVSS device. Only one (1) TVSS device is required
per paralleled groups of distribution panels.
Unless otherwise specified, install the TVSS device in the mounting position closest to the distribution panel’s
input busbar.
Refer to SAG582140600 for more information.
CAUTION! The TVSS device occupies two mounting positions. Leave an additional empty mounting
Procedure
position between the TVSS device and any overcurrent protective device.
1. Install the TVSS device(s) as required. Refer to Figure 17.
2. Connect a customer provided cable from the List 15, List 15A, List 25, or List 25A distribution panel lug
mounting busbar associated to the TVSS mounting position into a customer's grounding network. Refer
to Figure 17. Wire to be sized so that the maximum wire resistance is less than 0.550 milliohms.
NOTE!
recommended to use a Green cable and insulate the connection with shrink tubing to avoid incidental
The ground cable will be installed in a position normally used for -48V distribution. It is
contact.
Vertiv |NetSure 8100 Series Installation & User Manual (UM582140600)|Rev. A
Page 40
40
Shorter SideLonger Side
Longer SideShorter Side
Device’s Lead
Connections
Device’s Lead
Connections
List 15, List 15A, List 25,
and List 25A Distribution Panel
Front View
List 15
(Others Similiar)
List 15
(Others Similiar)
DANGER
Install TVSS Device so Shorter Side is Towards the Device's Lead Connection Points
Load Lead Connections (-48V) and
TVSS Lead Connections (+Ground)
1/4-20 Studs on 0.625 Centers
(Torque to 60 in-lbs)
Maximum Lug Width, 0.610 Inches
Ensure leads are connected to
proper polarity for the device
installed, either a distribution
device (load lead connection)
or a TVSS device (ground
connection).
Figure 17:
Installation and Wiring of Transient Voltage Surge Suppressor (TVSS) Devices
Vertiv |NetSure 8100 Series Installation & User Manual (UM582140600)|Rev. A
Page 41
41
Input/Output Cable Routing and Cable Management
Input/Output Cable Routing Diagram
Refer to Figure 18 for an input/output cable routing diagram.
Fuseholder and circuit breaker wiring should start with positions furthest from the point that distribution
cabling leaves the bay.
It is recommended to wire the loads for top feed arrangements starting with the bottom most distribution
position of the bottom most distribution panel and ending with the top most distribution position of the top
most distribution panel, and routing the wires starting from the back of the bay and ending with the front of the
bay (Bottom to Top, Rear to Front Wiring). For bottom feed bay arrangements, recommended wiring should
start with the top most distribution position of the top most distribution panel and ending with the bottom most
distribution position of the bottom most distribution panel, and routing the wires starting from the back of the
bay and ending with the front of the bay (Top to Bottom, Rear to Front Wiring). It is also recommended as you
run your wires to bundle about four wires together with cable lacing, and route each bundle up to the top (or
down to the bottom) of the bay, pressing each bundle towards the rear of the bay. When each bundle is
pressed as far back as it can go, secure the bundle to the cable dressing bars with cable lacing. Proceed with
the next bundle of wires until all distribution positions are wired.
Optional Cable Dressing Bar
Optional cable dressing bars are available. See SAG582140600. The dressing bars are adjustable and allow
customer to dress output load cables along the sides of the bay. See Figure 19.
Optional Load Distribution Cable Management Kit
An optional load distribution cable management kit is available. See SAG582140600. This kit provides twelve
(12) cable separators plus cable ties as a method to manage wiring. This kit cannot be used with the optional
cable dressing bars. See Figure 20.
Vertiv |NetSure 8100 Series Installation & User Manual (UM582140600)|Rev. A
Page 42
42
List 01, List 07
List 03, List 09
Load
Cables
Load
Cables
Input
Cables
Top View
Top Feed Installations
Bottom View
Top Feed Installations
Top View
Top Feed Installations
Bottom View
Top Feed Installations
Load
Cables
Load
Cables
Load
Cables
Load
Cables
Input
Cables
Input
Cables
Load
Cables
Load
Cables
Load
Cables
Load
Cables
Input
Power
Cables
Input
Return
Cables
Input
Power
Cables
Input
Return
Cables
Load
Cables
Load
Cables
Input
Cables
Figure 18:
Input/Output Cable Routing
Vertiv |NetSure 8100 Series Installation & User Manual (UM582140600)|Rev. A
Page 43
43
Cable Dressing Bars
Cable Dressing Bars
List 01, List 07
List 03, List 09
Figure 19:
Optional Cable Dressing Bars
Vertiv |NetSure 8100 Series Installation & User Manual (UM582140600)|Rev. A
Page 44
44
Cable Separators
Cable Separators
List 01, List 07
List 03, List 09
Figure 20:
Optional Load Distribution Cable Management Kit
Vertiv |NetSure 8100 Series Installation & User Manual (UM582140600)|Rev. A
Page 45
45
Load Distribution Connections
WARNING! Observe proper polarity when making load connections.
NOTE!
Refer to “Wiring Considerations” on page 29.
The rating of the distribution device determines the wire size requirements. Refer to the American National
Standards Institute (ANSI) approved National Fire Protection Association's (NFPA) National Electrical Code
(NEC) and applicable local codes.
To Distribution Panels
Load distribution (load side) leads terminated in the appropriate lug are connected to the “load side”
terminations provided on each distribution panel. See Figure 21. Torque connections as shown in Figure 21.
Load distribution (return side) leads terminated in the appropriate lug are connected to the “load return side”
terminations provided on the optional internal ground/return bars or to external ground/return bars. See
Figure 21. Torque connections as shown in Figure 21.
Vertiv |NetSure 8100 Series Installation & User Manual (UM582140600)|Rev. A
Page 46
46
Portion of bay removed
in illustration for clarity.
Optional Internal
Ground/Return Busbar
(Bay Length, shown)
or Optional Internal
Ground/Return Busbar
(Panel Length, see next pages)
or Optional External Busbar
Optional Internal
Ground/Return Busbar
(Bay Length, shown)
or Optional Internal
Ground/Return Busbar
(Panel Length, see next pages)
or Optional External Busbar
Load Distribution Connections
SEE NEXT PAGE IF
TVSS DEVICE IS
INSTALLED IN BULLET
DEVICE MOUNTING
BLOCK
-48V Load Connections
Load Return Connections
to Optional Internal
Ground/Return Busbar
or Optional External Busbar.
-48V Load Connections
Load Return Connections
to Optional Internal
Ground/Return Busbar
or Optional External Busbar.
SEE NEXT PAGE IF
TVSS DEVICE IS
INSTALLED IN BULLET
DEVICE MOUNTING
BLOCK
Rear View
8-Panel Bay
(6-Panel Bay Similar)
Figure 21:
Load Distribution Connections (cont’d on next page)
Vertiv |NetSure 8100 Series Installation & User Manual (UM582140600)|Rev. A
Page 47
47
Bullet Device Mounting Block
DANGER
TPL-B Fuseblock
5/16-18 swage studs
for installation of customer
provided single hole lugs.
(Torque to 132 in-lbs.)
(Maximum Lug Width is 1.800”.)
(Maximum Wire Size is 2/0 AWG.)
TLS/TPS Fuseblock
1/4-20 swage studs
for installation of customer
provided single hole lugs.
(Torque to 72 in-lbs.)
(Maximum Lug Width is 0.750”.)
(Maximum Wire Size is 2 AW G.)
-48V Load
Connections
-48V Load
Connections
1/4-20 studs on 5/8” centers
for installation of customer
provided two hole lugs.
(Torque to 72 in-lbs.)
(Maximum Lug Width is 0.610”.)
(Maximum Wire Size is 2 AW G.)
-48V Load
Connections*
or
TVSS
Connections
(+Ground)*
Ensure leads are connected to
proper polarity for the device
installed, either a Distribution
Device (load lead connection)
or a TVSS Device (ground
connection).
*
-48V Load
Connections*
or
TVSS
Connections
(+Ground)*
-48 VDC Load Connections and
TVSS Device Ground Connections to
List 15, List 15A, List 25, and List 25A Distribution Panel
-48 VDC Load Connections to
List 10 and List 20 Distribution Panel
Rear View
(wired from the rear of the bay)
Rear View
(wired from the rear of the bay)
List 15
(List 25 Similiar)
List 15A
(List 25A Similiar)
List 10
(List 20 Similiar)
List 10
(List 20 Similiar)
Figure 21:
Load Distribution Connections (cont’d from previous page, cont’d on next page)
Vertiv |NetSure 8100 Series Installation & User Manual (UM582140600)|Rev. A
Page 48
48
582140600 List 15582140600 List 15
P/N 556377
Right Angle
Lug Adapter Kit
P/N 556377
Right Angle
Lug Adapter Kit
P/N 556378
Right Angle
Lug Adapter Kit
P/N 556378
Right Angle
Lug Adapter Kit
RearRear
P/N 547991
3-Pole Lug
Adapter Kit
P/N 547991
3-Pole Lug
Adapter Kit
Figure 21:
Load Distribution Connections (cont’d from previous page, cont’d on next page)
Vertiv |NetSure 8100 Series Installation & User Manual (UM582140600)|Rev. A
Page 49
49
Figure 21:
Load Distribution Connections (cont’d from previous page, cont’d on next page)
Vertiv |NetSure 8100 Series Installation & User Manual (UM582140600)|Rev. A
Page 50
50
Optional Internal
Ground/Return Busbar
Connections
(Distribution Panel Length,
Replaces a Distribution Panel)
Optional List 27
Ground Bar Assembly
(Each List 27 provides
two [2] Ground Bar
Assemblies.)
Optional List 17
Ground Bar Assembly
(Each List 17 provides
two [2] Ground Bar
Assemblies.)
Optional List 17
Ground Bar Assembly
(Each List 17 provides
two [2] Ground Bar
Assemblies.)
List 39
Paralleling Bars
(behind center rail)
Top Feed Arrangement Shown
For Bottom Feed Arrangement,
Ground Bar Assemblies Are
Installed in Bottom Most
Mounting Positions
Front View
8-Panel Bay
Front View
6-Panel Bay
Figure 21:
Load Distribution Connections (cont’d from previous page, cont’d on next page)
Vertiv |NetSure 8100 Series Installation & User Manual (UM582140600)|Rev. A
Page 51
51
Load Return Connections
1/4” clearance holes/slots on 5/8” centers
for installation of customer
provided two hole lugs.
(Torque to 72 in-lbs.)
(Maximum Lug Width is 0.610”.)
(Maximum Wire Size is 2 AWG.)
Load Distribution Connections (cont’d from previous page, cont’d on next page)
Vertiv |NetSure 8100 Series Installation & User Manual (UM582140600)|Rev. A
Page 52
52
Figure 21:
Load Distribution Connections (cont’d from previous page)
Vertiv |NetSure 8100 Series Installation & User Manual (UM582140600)|Rev. A
Page 53
53
DC Input Connections
DANGER! Adhere to the “Important Safety Instructions” presented at the front of this document.
WARNING! Observe proper polarity when making battery connections.
NOTE!
Refer to “Wiring Considerations” on page 29.
DC input wire size varies depending on load. Refer to the American National Standards Institute (ANSI)
approved National Fire Protection Association's (NFPA) National Electrical Code (NEC) and applicable local
codes.
DC input (-48V) leads terminated in the appropriate lug are connected to the List 43 Input Feed and Shunt
Assembly. See Figure 22. Torque connections as shown in Figure 22.
DC input return leads terminated in the appropriate lug are connected to the optional internal ground/return
bars or to external ground/return bars. See Figure 22. Torque connections as shown in Figure 22.
Vertiv |NetSure 8100 Series Installation & User Manual (UM582140600)|Rev. A
Page 54
54
Addtional input feed and shunt
assemblies are installed on any
distribution panel not paralleled
with a distribution panel that has
an input feed and shunt
assembly installed.
List 43
Input Feed and
Shunt Assembly
List 43
Input Feed and
Shunt Assembly
Top Feed
DC Input Connections
(-48V Battery)
List 43
Bottom Feed
DC Input Connections
(-48V Battery)
List 43
Rear View
8-Panel Bay
(6-Panel Bay Similar)
Portion of bay removed
in illustration for clarity.
Not to Scale
List 43
List 43
3/8” clearance holes/slots
on 1.00” centers for
installation of customer
provided two hole lugs.
(Torque to 180 in-lbs)
(Max. lug width is 2.00”)
(Max. wire size is 750 kcmil)
Top and Bottom Feed
Figure 22:
DC Input Connections (cont’d on next page)
Vertiv |NetSure 8100 Series Installation & User Manual (UM582140600)|Rev. A
Page 55
55
Optional List 48 2400 A Ground/Return
Input Kit provides Additional DC Input
Connections (Battery Return Leads)
3/8” clearance holes on
1.00” centers for
installation of customer
provided two hole lugs.
(Torque to 180 in-lbs)
(Max. lug width is 2.00”)
(Max. wire size is 750 kcmil)
Top and Bottom Feed
3/8” clearance holes on
1.00” centers for
installation of customer
provided two hole lugs.
(Torque to 180 in-lbs)
(Max. lug width is 2.00”)
(Max. wire size is 750 kcmil)
List 48 Feed
Optional bonding strap
(P/O List 48) can be
removed if not required.
Optional bonding strap
(P/O List 48) can be
removed if not required.
Top Feed DC Input Connections
(Battery Return Leads)
Bottom Feed
DC Input Connections
(Battery Return Leads)
Optional List 48 2400 A Ground/Return
Input Kit provides Additional DC Input
Connections (Battery Return Leads)
Optional List 16 Internal
Ground/Return Busbar
Arranged for Top Feed
(List 26 similar)
Optional List 16 Internal
Ground/Return Busbar
Arranged for Bottom Feed
(List 26 similar)
Rear View
8-Panel Bay
(6-Panel Bay Similar)
Portion of bay removed
in illustration for clarity.
Figure 22:
DC Input Connections (cont’d from previous page, cont’d on next page)
Vertiv |NetSure 8100 Series Installation & User Manual (UM582140600)|Rev. A
Page 56
56
Top Feed
DC Input Connections
(Battery Return Leads)
Bottom Feed
DC Input Connections
(Battery Return Leads)
Optional List 17 Internal
Ground/Return Busbar
(List 27 similar)
Rear View
8-Panel Bay
(6-Panel Bay Similar)
Portion of bay removed
in illustration for clarity.
3/8” clearance holes on
1.00” centers for
installation of customer
provided two hole lugs.
(Torque to 180 in-lbs)
(Max. lug width is 2.00”)
(Max. wire size is 4/0 AWG)
Top and Bottom Feed
Figure 22:
DC Input Connections (cont’d from previous page, cont’d on next page)
Vertiv |NetSure 8100 Series Installation & User Manual (UM582140600)|Rev. A
Page 57
57
Figure 22:
DC Input Connections (cont’d from previous page)
Vertiv |NetSure 8100 Series Installation & User Manual (UM582140600)|Rev. A
Page 58
58
INSTALLING CIRCUIT BREAKERS AND FUSES
Circuit breakers and/or fuses may have been factory installed for you. If so, verify their positions and sizes.
Refer to SAG582140600 for any temperature, sizing, and spacing restrictions.
Installing TLS/TPS Fuses into Respective Fuseholders of a List 10 and List 20 Distribution Panel
Each fuse installs into a pre-mounted fuseholder.
Refer to the following procedure and install appropriately sized TLS/TPS fuses into the proper fuseholders in a
List 10 and List 20 distribution panel.
Procedure
Figure 23:
NOTE!
1. Remove the fuseholder portion from the mounted fuseholder body by pulling it straight out. Install the
TLS/TPS type fuse into the fuseholder. When done, push the fuseholder portion back into the mounted
fuseholder body.
2. Ensure an alarm fuse is installed in the GMT fuseholder provided on the mounted fuseholder body. The
alarm fuse should be a Bussmann GMT 18/100 ampere alarm fuse (P/N 248610301).
3. Ensure a safety fuse cover is install on the GMT alarm fuse.
4. A spare distribution fuse and alarm fuse may be placed inside the cavity provided on the front of the
pull-out fuseholder portion.
5. Record all fuse sizes installed.
Refer to
Installing TLS/TPS Fuses
Figure 23
as this procedure is performed.
Vertiv |NetSure 8100 Series Installation & User Manual (UM582140600)|Rev. A
Page 59
59
Installing TPL-B Fuses into Respective Fuseholders of a List 10 and List 20 Distribution Panel
Each fuse installs into a pre-mounted fuseholder.
Refer to the following procedure and install appropriately sized TPL-B fuses into the proper fuseholders in a
List 10 and List 20 distribution panel.
Procedure
NOTE!
Refer to
Figure 24
as this procedure is performed.
1. Remove the fuse case from the mounted fuse block by grasping its handle and pulling it straight out.
2. Verify that an 18/100 ampere alarm fuse is present in the GMT-type fuseholder located on the fuse
block and that a plastic safety cover is installed on this fuse.
3. Open the fuse case.
4. Install the TPL-B fuse into the fuse case.
5. Close the fuse case.
6. Firmly plug the fuse and fuse case into the fuse block.
7. Record all fuse sizes installed.
Figure 24:
Installing TPL Fuses
Vertiv |NetSure 8100 Series Installation & User Manual (UM582140600)|Rev. A
Page 60
60
Installing Bullet Nose-Type Fuseholders e/w TLS/TPS Fuses in a List 15, List 15A, List 25, and 25A Distribution
Panel
A single fuseholder provides for installation of a 3 to 70 ampere Bussmann TPS-type or a 3 to 125 ampere
Littelfuse TLS-type fuse. The fuseholder plugs into a single distribution device mounting position.
Refer to the following procedure and install bullet nose type fuseholders and appropriately sized TPS/TLS fuses
into a List 15, List 15A, List 25, and 25A distribution panel.
Procedure
NOTE!
Refer to
Figure 25
as this procedure is performed.
1. Orient the fuseholder as shown in Figure 25. Insert the terminals on the rear of the fuseholder into their
corresponding sockets on the distribution panel. Ensure the alarm contact on the back of the
fuseholder makes contact with the alarm terminal on the spring strip. Push fuseholder in firmly until fully
seated in the distribution panel.
2. When all fuseholders are installed, install an appropriately sized TPS/TLS fuse in each. To do this,
remove the fuse carrier from the mounted fuseholder body. Hold the fuseholder body while you pull the
fuse carrier from the body. Slide the fuse in place between the contacts of the fuse carrier. When done,
push the fuse carrier back into the fuseholder body. Note that a polarizing key on the bottom of the
carrier prevents the carrier from being inserted upside down.
3. Verify that an 18/100 ampere alarm fuse is present in each fuseholder and that a plastic safety cover is
installed on this fuse.
4. Record all fuse sizes installed.
Installing Bullet Nose Type Circuit Breakers in a List 15, List 15A, List 25, and 25A Distribution Panel
Each circuit breaker plugs into one, two, or three distribution device mounting position(s).
Refer to the following procedure and install bullet nose type circuit breakers into a List 15, List 15A, List 25, and
25A distribution panel.
Procedure
NOTE!
Refer to
Figure 25
as this procedure is performed.
1. Ensure that the circuit breaker is in the OFF position and is of the correct rating. Orient the circuit
breaker as shown in Figure 25. Insert the terminals on the rear of the circuit breaker into their
corresponding sockets on the distribution panel. Ensure the alarm contact on the back of the circuit
breaker makes contact with the alarm terminal on the spring strip. Push distribution device in firmly
until fully seated in the distribution panel.
2. Record all circuit breaker sizes installed.
Vertiv |NetSure 8100 Series Installation & User Manual (UM582140600)|Rev. A
Page 61
61
Shorter SideLonger SideShorter SideLonger Side
Install Fuseholder and/or
Breaker so Shorter Side is
Towards the Load Lead
Connections
Note: Line/Load Designa tions on Breaker may be
Different than Shown Here.
The Illustration Depicts the
Correct Orientation of the
Breaker for this System.
Load Lead
Connections
Load Lead
Connections
List 15, List 15A, List 25, and List 25A Distribution Panel
Front View
List 15
(Others Similiar)
List 15
(Others Similiar)
List 15, List 15A, List 25, List 25A
Bullet Nose-Type Distribution Devices
Fuse Carrier
Fuseholder Body
TPS/TLS Fuse
Polarizing Keyway
Matches Key on
Bottom of Fuse Carrier
Bullet Nose Fuseholder
Assembly Exploded View
Bullet nose fuseholder assembly (P/N
117201) includes fuseholder body, fuse
carrier, alarm fuse, and safety fuse cover.
Installation of Bullet Nose-Type Circuit Breakers and Fuseholders
Vertiv |NetSure 8100 Series Installation & User Manual (UM582140600)|Rev. A
Page 62
62
Menu Navigation Keys
M832D
Status
Indicator (Green)
Minor Alarm
Indicator (Yellow)
Critical or Major
Alarm Indicator (Red)
INITIALLY STARTING, CONFIGURING, AND CHECKING
SYSTEM OPERATION
Important Safety Instructions
CAUTION! Performing various steps in the following procedures may cause a service interruption
and/or result in the extension of alarms. Notify any appropriate personnel before starting these
procedures. Also, notify personnel when these procedures are completed.
Initial Startup Preparation
• Ensure that all blocks, except the last one, in the “Installation Acceptance Checklist” starting on page 10
have been checked.
• Install all distribution devices per “Installing Circuit Breakers and Fuses” starting on page 58. Verify all
circuit breakers are in the OFF (0) position.
• Refer to the configuration drawing (C-drawing) supplied with your power system documentation for
factory settings of adjustable parameters.
Initially Starting the System
Procedure
1. Close the external DC fuse or circuit breaker disconnect device(s) that supply DC input power to the
BDF/CBB.
2. Place each distribution circuit breaker (if furnished) to the ON position.
Monitor Unit Initialization
Refer to the Monitor Unit User Instructions (UM1M832DNA) for detailed instructions.
Refer to Figure 26 for locations of the monitor unit local indicators and navigation keys.
Figure 26:
Monitor Unit Local Indicators and Navigation Keys
Vertiv |NetSure 8100 Series Installation & User Manual (UM582140600)|Rev. A
Page 63
63
ENT
Press the UP and DOWN keys to highlight
the desired Menu graphic in the Main Menu.
Press the ENT key to enter the selected menu.
Date and time are
alternately displayed.
Green - No Alarm
Red - Alarm
09:22:58
Main Menu
GraphicsMenu NameDescription
Alarm
(Green - No Alarm)
(Red - Alarm)
View active alarms and
alarm history.
Settings
Gain access to the Monitor
Unit’s settings menus.
Bay CurrentView bay current graphs.
Input Feeds
Current and Voltage
View current and voltage
graphs for bay’s input feeds.
Distribution Panels
View selected distribution
panel status.
Bay Name
8 Feeds
Feeds
1080.0A
A
FA/CB
AB
C
D
EF
G
H
A
If any of the green fields are red in your
system, it indicates an alarm condition exists.
Procedure
NOTE!
The initialization routine takes several minutes. During that time various alarm indicators may
illuminate on the monitor unit front panel and an audible alarm may sound. Disregard all alarms. An
audible alarm can be silenced at any time by momentarily depressing the
key on the monitor unit.
1. After the monitor unit is powered on, the monitor unit initializes.
2. When initialization is complete, the language screen appears. Press the up or down arrow key to select
the desired language. Press the ENT key to confirm the selection.
3. The Main Menu displays. See Figure 27.
4. System information is displayed in multiple screens. If desired, press the ESC key to view other system
information. Press the down arrow key to view the next screen. Press the ESC key to return to the Main
Menu.
5. From the Main Menu (see Figure 27), press the UP and DOWN keys to highlight the desired Menu
graphic in the Main Menu. Press the ENT key to enter the selected menu.
NOTE!
Repeatedly press the “ESC” key to return in reverse order level by level from any submenu until
the Main Menu appears.
6. Refer to the following procedures to verify and set the monitor unit as required for your application.
Figure 27:
Monitor Unit Local Display Main Menu
Vertiv |NetSure 8100 Series Installation & User Manual (UM582140600)|Rev. A
Page 64
64
To Select a Sub-Menu:
To Select a User:
To Enter a Password:
To Change a Parameter:
Verifying and Setting the Monitor Unit as Required for Your Application
Refer to the Monitor Unit Instructions (UM1M832DNA) for additional information.
Note that you will have to program the monitor unit for any external inputs/outputs connected to the IB2
Interface Board.
Verifying the Configuration File
Your system was programmed with a configuration file that sets all adjustable parameters. The version number
of the configuration file can be found on the configuration drawing (C-drawing) that is supplied with your power
system documentation. You can verify that the correct configuration file has been loaded into your monitor
unit by performing the following procedure.
Procedure
1. With the Main Menu displayed, press ESC. A screen displays the monitor unit’s name, serial number, IP
number, software version, hardware version, and configuration version number.
2. Press ESC to return to the Main Menu.
Checking Basic System Settings
Navigate through the monitor unit menus and submenus to check system settings. You can adjust any
parameter as required. Note that these settings can also be checked (and changed if required) via the WEB
Interface.
NOTE!
Repeatedly press the “ESC” key to return in reverse order level by level from any submenu until
the Main Menu appears.
Procedure
1.
Press the UP and DOWN keys to highlight the desired sub-menu. Press the ENT key to enter the
selected sub-menu.
2.
To select a User, use the UP and DOWN keys to move the cursor to the Select User field. Press ENT.
Use the UP and DOWN keys to select a User previously programmed into the monitor unit. Press ENT
to select the User. Note that only Users programmed into the monitor unit are shown. Users are
programmed via the Web Interface. The default User is admin.
3.
If a password screen opens, a password must be entered to allow the User to make adjustments. To
enter a password, use the UP and DOWN keys to move the cursor to the Enter Password field. Press
ENT. Use the UP and DOWN keys to choose a character. Press ENT to accept and move to the next
character. Continue this process until all characters are entered. Press ENT again to accept the
password. The default password is 640275.
4.
Press the UP and DOWN keys to move up and down the list of parameters. Press ENT to select the
parameter. Press the UP and DOWN keys to change the parameter. Press ENT to make the change.
Press ESC to cancel the change.
5. Table 8 shows the menu navigation for some basic settings. Refer to the separate Monitor Unit Manual
(UM1M832DNA) supplied with your system for complete Local Display menus.
Vertiv |NetSure 8100 Series Installation & User Manual (UM582140600)|Rev. A
Page 65
65
Time
Main Menu / Settings Icon / Sys Settings / Time.
Table 8:
Monitor Unit Basic Settings Menu Navigation
Parameter Menu Navigation
Date Main Menu / Settings Icon / Sys Settings / Date.
IP Communications
Parameters (IP
address, subnet mask
Main Menu / Settings Icon / Comm Settings / enter parameters.
address, gateway
address)
Programming Channels for TVSS Devices
If a TVSS device is installed in an advance panel, program the panel as follows.
Procedure
1. Name the positions occupied by the TVSS device and mark the position as a two-pole device which is
not used.
Checking Circuit Breaker Alarm / Fuse Alarm
Perform the following procedure to verify the CBA/FA alarm is operational.
NOTE!
The following procedure applies only to circuit breakers that provide an alarm indication when
manually placed to the OFF (open) position. Electrical trip only circuit breakers cannot be easily tested
in the field. Electrical trip only circuit breakers have white handles and electrical/mechanical circuit
breakers have black handles.
1. On a distribution panel, remove an alarm-type fuse and replace it with a known open fuse or place a
circuit breaker to the OFF (0) position.
a) Requirement: The major alarm indicator on the monitor unit illuminates red. The monitor unit
displays a fuse alarm message with location. The STATUS indicator at the top of the bay
illuminates red. If connected and configured, remote CBA/FA alarms activate.
2. Replace the open fuse with a known good fuse or place the circuit breaker to the ON (1) position.
a) Requirement: The major alarm indicator on the monitor unit extinguishes. The monitor unit displays
“System OK”. STATUS indicator at the top of the bay illuminates green. If connected and
configured, remote CBA/FA alarms retire.
Vertiv |NetSure 8100 Series Installation & User Manual (UM582140600)|Rev. A
Page 66
66
3. Repeat steps 1) and 2) for each alarm-type fuse or circuit breaker on the distribution panel.
4. Repeat steps 1) through 3) for each distribution panel in the system.
5. If not already done, remove the access cover from the top of the bay front. Before removing, note the
location of any grounding washers used with the hardware securing the panel. This provides access to
the auxiliary fuse card. See Figure 14.
6. Remove an alarm-type fuse and replace it with a known open fuse.
a) Requirement: The major alarm indicator on the monitor unit illuminates red. The monitor unit
displays a fuse alarm message with location. STATUS indicator at the top of the bay illuminates
red. If connected and configured, remote CBA/FA alarms activate.
7. Replace the open fuse with a known good fuse.
a) Requirement: The major alarm indicator on the monitor unit extinguishes. The monitor unit
displays “System OK”. STATUS indicator at the top of the bay illuminates green. If connected and
configured, remote CBA/FA alarms retire.
8. Repeat steps 6 and 7 for each fuse on the circuit card.
Checking Monitor Unit Dual Power Source Check (if two power sources connected)
1. Remove fuse F5 from the auxiliary fuse card. See Figure 14 for location. Verify the monitor unit and
CBA/FA circuit are functional by performing the checkout procedure above.
2. Replace fuse F5.
3. Remove fuse F6. Verify the monitor unit and CBA/FA circuit are functional by performing the checkout
procedure above.
4. Replace fuse F6.
5. Install and secure the access cover over the auxiliary fuse card. Ensure ground washer are installed at
the locations noted earlier in the checkout procedure.
Checking System Status
Procedure
1. Observe the status of the indicators located on the monitor unit. If the system is operating normally, the
status of these is as shown in Table 9.
2. Verify that the STATUS indicator at the top of the bay is illuminated green.
3. Verify that all Power Status indicators located on the BDF/CBB’s front center channel (one for each
distribution panel) are illuminated green.
4. Verify that all FA/CBA alarm indicators located on the BDF/CBB’s front center channel (one for each
distribution panel) are off.
5. Verify there are no external alarms.
Vertiv |NetSure 8100 Series Installation & User Manual (UM582140600)|Rev. A
Page 67
67
Table 9:
Monitor Unit Status and Alarm Indicators
Indicator Normal State
Status (Green) On
Minor Alarm
(Yellow)
Critical or Major
Alarm (Red)
Off
Off
Final Steps
Procedure
1. If any monitor unit configuration settings were changed, refer to the Monitor Unit Instructions
(UM1M832DNA) and save a copy of the configuration file. This file can be used to restore the monitor
unit settings, if required, at a later date.
Vertiv |NetSure 8100 Series Installation & User Manual (UM582140600)|Rev. A
Page 68
68
OPERATING THE SYSTEM
Monitor Unit
For monitor unit operating instructions, refer to the Monitor Unit User Manual (UM1M832DNA).
NOTE!
The monitor unit’s default “User Name” is "admin" and the default “Password” is “640275”.
Local Controls and Indicators
Monitor Unit
Refer to the separate monitor unit instruction manual.
Bay’s Front Center Channel
The following indicators are located on the BDF/CBB’s front center channel. See Figure 28.
a) Bay Status Indicator: This indicator illuminates green when power is present and no alarms are active.
The indicator illuminates red for any alarm condition.
b) FA/CBA: This red indicator illuminates when a circuit breaker or fuse opens in the corresponding
distribution panel.
c) POWER STATUS: This green indicator illuminates when DC power is applied to the corresponding
distribution panel.
Transient Voltage Surge Suppressor Device (TVSS)
A TVSS contains an indicator which illuminates when the circuit activates to suppress voltages.
Vertiv |NetSure 8100 Series Installation & User Manual (UM582140600)|Rev. A
Page 69
69
Front View
8-Panel Bay
(6-Panel Bay Similar)
Bay Status Indicator
Green = Power is Present and No Alarms are Active
Red = Bay has an Alarm Condition
FA/CBA: This red indicator illuminates
when a circuit breaker or fuse opens in
the corresponding distribution panel.
POWER STATUS: This green indicator
illuminates when DC power is applied to
the corresponding distribution panel.
Figure 28:
Bay’s Indicators
Vertiv |NetSure 8100 Series Installation & User Manual (UM582140600)|Rev. A
Page 70
70
ON
OFF
18
SW1
Green LED
Red LED
SM-DUE Circuit Card Indicators
An SM-DUE is located in each bay. Refer to Figure 6 for location. The SM-DUE is used to monitor individual
distribution panels in the bay.
There are two (2) status and alarm indicators located on the SM-DUE. The functions of these indicators are as
shown in Table 10. Refer to Figure 29 for location.
Table 10:
SM-DUE Indicators
Indicator Normal State Fault State Description
On -- Unit is operating normally.
Operation
(Green)
Alarm
(Red)
-- Off Unit is non-operational.
Flashing --
Unit is communicating with the monitor
unit.
Off -- Normal State
-- On Unit has failed.
Figure 29:
SM-DUE Indicator Locations
Vertiv |NetSure 8100 Series Installation & User Manual (UM582140600)|Rev. A
Page 71
71
Green LED
SM-DUH2 Circuit Card Indicators
The SM-DUH2 is used in a List 15A and List 25A distribution panel to monitor individual distribution devices in
the distribution panel. Refer to Figure 6 for location.
There are two (2) status and alarm indicators located on the SM-DUH2. The functions of these indicators are
as shown in Table 11. Refer to Figure 30 for location.
Table 11:
SM-DUH2 Indicators
Indicator Normal State Fault State Fault Cause
On -- Unit is operating normally.
-- Off Unit is non-operational.
Operation
(Green)
Flashing --
-- Flashing
A 1 Hz flashing indicates the unit is
communicating with the monitor unit.
A 1/3 Hz flashing indicates a communication
failure.
Off -- Normal State
Alarm
(Red)
-- On
Alarm (hardware fault or bus voltage
sampling fault).
Figure 30:
SM-DUH2 Circuit Card Indicator Locations
SW1
ON (DOWN)
18
Red LED
Vertiv |NetSure 8100 Series Installation & User Manual (UM582140600)|Rev. A
Page 72
72
Procedure
Interval
Referenced In
Check ventilation
manuals, etc.
Inspect and tighten
connections.
“Making Electrical
on page 29.
“Checking Circuit
Alarm” on page 65.
MAINTENANCE
Important Safety Instructions
DANGER! Adhere to the “Important Safety Instructions” presented at the front of this document.
Routine Maintenance
The BDF/CBB requires minimal routine maintenance when installed correctly. The procedures listed in Table
12 may be performed at the recommended interval to provide a service record for the system. The table
references specific sections in this instruction manual which help in performing these procedures.
Table 12:
openings for
obstructions such as
dust, papers,
all installer's
Check Circuit
Breaker/Fuse Alarms
Procedures that May be Performed to Provide a Service Record for the System
1 year --
6 months
3 months
Connections” starting
Breaker Alarm / Fuse
System Expansion
Field Distribution Panel Installation
DANGER! Adhere to the “Important Safety Instructions” presented at the front of this document.
Perform the following procedure to add an additional distribution panel to the BDF/CBB.
Procedure
1. Remove blank cover panel(s) where new distribution panel(s) will be installed.
2. Place the new distribution panel into position on the front side of the BDF/CBB.
3. On the front of the BDF/CBB insert and tighten the four screws securing the new distribution panel to
Vertiv |NetSure 8100 Series Installation & User Manual (UM582140600)|Rev. A
NOTE!
the bay.
Refer to
Figure 31, Figure 32
, and
Figure 33
as this procedure is performed.
Page 73
73
4. Locate in the bay’s wiring harness near the new panel, the unconnected insulated quick connector for
the FA/CBA alarm circuits. Connect this to the tab located on the center alarm bus of the distribution
panel. Connect from the rear of the bay. Refer to Figure 33.
5. If the new distributing panel has a List 43, locate in the bay’s wiring harness near the new panel, the
unconnected connectors for the shunt leads. Connect these as shown in Figure 33. Otherwise
terminate to busbar.
6. Locate in the bay’s wiring harness near the new panel, the remaining unconnected connectors. Connect
these as shown in Figure 33.
7. Connect parallel bars as required to power the new panel per the appropriate section of this document.
8. Connect loads to the new panel per the appropriate section of this document.
9. Install distribution devices per the appropriate section of this document.
10. Install the new BDF/CBB front cover panel that was furnished with the new distribution panel.
11. Perform the “Initially Starting, Configuring, and Checking System Operation” procedure on page 62.
Vertiv |NetSure 8100 Series Installation & User Manual (UM582140600)|Rev. A
Page 74
74
Rear View
List 10 Distribution Panel
(List 20 Similar)
FA/CBA
Alarm Tab
10-32 x 1" Screw and Washer (4 places)
To secure distribution panel to
bay's inner support assemblies.
Torque to 20 in-lbs.
8-32 x 1/2" Screw (2 places)
#8 Ground Washer (1 place)
To secure distribution panel cover
to bay's center channel.
Torque to 20 in-lbs
Tabs
(Slide distribution panel cover at an angle so
tabs fit into slots on bay. Secure other side of
distribution panel cover with screws and
ground washer as shown.)
Figure 31:
Installing a List 10 or List 20 Distribution Panel
Vertiv |NetSure 8100 Series Installation & User Manual (UM582140600)|Rev. A
Page 75
75
Rear View
List 15 Distribution Panel
(List 15A, 25, 25A Similar)
FA/CBA
Alarm Tab
10-32 x 1" Screw and Washer (4 places)
To secure distribution panel to
bay's inner support assemblies.
Torque to 20 in-lbs.
8-32 x 1/2" Screw (2 places)
#8 Ground Washer (1 place)
To secure distribution panel cover
to bay's center channel.
Torque to 20 in-lbs
Tabs
(Slide distribution panel cover at an angle so
tabs fit into slots on bay. Secure other side of
distribution panel cover with screws and
ground washer as shown.)
Figure 32:
Installing a List 15, List 15A, List 25, or List 25A Distribution Panel
Vertiv |NetSure 8100 Series Installation & User Manual (UM582140600)|Rev. A
Page 76
76
To
SM-DUH2
CAN
To SM-DUH2 Power
To Shunt,
See Figure 5
To FA Tab
To Busbar
To Busbar
Figure 33:
Connecting the System Wire Harness to the Distribution Panel
Vertiv |NetSure 8100 Series Installation & User Manual (UM582140600)|Rev. A
Page 77
77
TROUBLESHOOTING AND REPAIR
Important Safety Instructions
DANGER! Adhere to the “Important Safety Instructions” presented at the front of this document.
Contact Information
Refer to Section 4154 (provided with your customer documentation) for support contact information.
Monitor Unit
General
For troubleshooting and repair instructions on the monitor unit, refer to the Monitor Unit User Instructions
(UM1M832DNA).
Monitor Unit Configuration
If any monitor unit configuration settings were changed, refer to the Monitor Unit Instructions (UM1M832DNA)
and save a copy of the configuration file. This file can be used to restore the monitor unit settings, if required,
at a later date.
System Troubleshooting Information
This system is designed for ease in troubleshooting and repair. The various indicators as described in “Local
Controls and Indicators” on page 68 and in the monitor unit instruction manual are designed to isolate failure to
a specific element. Once the faulty element has been identified, refer to “Replacement Information” on page 77
and “Replacement Procedures” on page 77.
Troubleshooting Alarm Conditions on the Monitor Unit
The monitor unit displays alarm conditions as listed in the “Resolving Alarms” section of the Monitor Unit
Instructions (UM1M832DNA). Programmable external alarm relays are also available. Refer to the configuration
drawing (C-drawing) supplied with your system documentation for your alarm relay configurations.
The monitor unit’s
the Monitor Unit Instructions (UM1M832DNA) to access these menus.
Active Alarm
and
Alarm History
submenus allow the User to view alarm details. Refer to
Replacement Information
User Replaceable Components
When a trouble symptom is localized to a faulty monitor unit or system circuit card; that particular device or
circuit card should be replaced in its entirety. No attempt should be made to troubleshoot or repair individual
components on any monitor unit or circuit card.
Refer to SAG582140600 (System Application Guide) for replacement part numbers.
Replacement Procedures
Replacing the Monitor Unit
Refer to the Monitor Unit Instructions (UM1M832DNA) for a replacement procedure.
Vertiv |NetSure 8100 Series Installation & User Manual (UM582140600)|Rev. A
DANGER! Adhere to the “Important Safety Instructions” presented at the front of this document.
Page 78
78
Safety Fuse Cover
P/N 248898700
(BUSSMANN GMT-X)
Safety Fuse Cover
P/N 102774
(BUSSMANN GMT-Y)
Replacing a Distribution Device
General
Replace distribution devices with the same type and rating. Refer to SAG582140600 (System Application
Guide) for part numbers.
Safety Fuse Covers
Safety fuse covers are provided for all alarm-type fuses installed in the system. These covers snap onto the
fuses and provide protection from exposed electrical terminations when a fuse opens. Ensure that the safety
fuse cover is installed after replacing a fuse. Refer to Figure 34 for installation details.
Figure 34:
Installation of Safety Fuse Covers
Replacing a Fuse on the Auxiliary Fuse Board
An auxiliary fuse board is located behind an access panel at the top right side of the bay. See Figure 35. This
circuit card provides four (4) fused auxiliary -48V power outputs (1-1/3A) and dual (A/B) system electronics
input fuses.
Procedure
1. Remove the access panel by removing the screws that secure it. Before removing, note the location of
any grounding washers used with the hardware securing the panel.
2. After fuse replacement is complete, re-install the access panel. Ensure grounding washers are replaced
in locations noted above.
Vertiv |NetSure 8100 Series Installation & User Manual (UM582140600)|Rev. A
Page 79
79
Front
(top cover panel removed for clarity only)
Auxiliary
Fuse Board
F1F2F3
F4F5F6
Auxiliary Fuse Board
FuseFunction
F1
Aux Load 1A
F2
Aux Load 2A
F3
Aux Load 3B
F4Aux Load 4B
F5
ABS Power A
F6
ABS Power B
All fuses 1-1/3A.
Figure 35:
Replacing a Fuse on the Auxiliary Fuse Board
Vertiv |NetSure 8100 Series Installation & User Manual (UM582140600)|Rev. A
Page 80
80
Distribution Fuse “Alarm Fuse” Replacement
If a distribution fuse opens, the associated alarm fuse opens. Replace the distribution fuse before replacing the
alarm fuse.
Procedure
1. An alarm fuse is removed by pulling it straight out of the fuseholder. If the alarm fuse is located in a
modular fuse carrier, hold the fuse carrier in place with your thumb while pulling on the alarm fuse to
prevent the entire carrier from inadvertently being pulled out.
Replacing List 10 and List 20 Distribution Panel TLS/TPS Fuses
Refer to “Installing TLS/TPS Fuses into Respective Fuseholders of a List 10 and List 20 Distribution Panel” on
page 58.
Replace the alarm fuse located to the side of the fuse case with a Bussmann GMT 18/100 A alarm fuse. Ensure
the alarm safety fuse cover is re-installed.
Replacing List 10 and List 20 Distribution Panel TPL-B Fuses
Refer to “Installing TPL-B Fuses into Respective Fuseholders of a List 10 and List 20 Distribution Panel” on
page 59.
Replace the alarm fuse located to the side of the fuse case with a Bussmann GMT 18/100 A alarm fuse. Ensure
the alarm safety fuse cover is re-installed.
Replacing List 15, List 15A, List 25, and List 25A Distribution Panel TLS/TPS Fuses and/or Fuseholders
Refer to the “Installing Bullet Nose-Type Fuseholders e/w TLS/TPS Fuses in a List 15, List 15A, List 25, and 25A
Distribution Panel” on page 60.
Replace the alarm fuse located on the fuse case with a Bussmann GMT 18/100 A alarm fuse. Ensure the alarm
safety fuse cover is re-installed.
Replacing List 15, List 15A, List 25, and List 25A Distribution Panel Circuit Breakers
Refer to the Installing Bullet Nose Type Circuit Breakers in a List 15, List 15A, List 25, and 25A Distribution
Panel” on page 60.
Replacing List 10 and List 20 Distribution Panel Fuseholders
For fuseholder replacement, refer to Figure 36.
Vertiv |NetSure 8100 Series Installation & User Manual (UM582140600)|Rev. A
Page 81
81
Fuseholder
P/N 248817100
Fuseholder
P/N 516241
6-32 x 3/4" TFMS Screw
#6 Lock Washer
#6 Flat Washer
(Torque to 11.0 in-lbs)
6-32 x 3/4" TFMS Screw
#6 Lock Washer
#6 Flat Washer
(Torque to 11.0 in-lbs)
List 10 Distribution Panel
(List 20 Distribution Panel Similar)
Front View
1/4" Pan Head SEMS Screw
(Torque to 72.0 in-lbs)
1/4" Pan Head SEMS Screw
(Torque to 72.0 in-lbs)
Apply Anti-Oxidation Compound to
Fuseholder and Busbar Contact Points
List 10 Distribution Panel
(List 20 Distribution Panel Similar)
Rear View
Figure 36:
List 10 and List 20 Distribution Panel Fuseholder Replacement
Vertiv |NetSure 8100 Series Installation & User Manual (UM582140600)|Rev. A
Page 82
82
IB4
Auxiliary
Fuse Board
Front
(panels removed for clarity only)
Components removed in
illustration for clarity only.
IB2
SM-DUE
SM-DUH2
List 15A Distribution Panel
(List 25A Similiar)
Circuit Card Replacement Procedures
DANGER! Adhere to the “Important Safety Instructions” presented at the front of this document.
WARNING! Circuit cards used in this system contain static-sensitive devices. Read the Static Warning
at the front of this document before performing any of the following procedures.
General
The following circuit card replacement procedures can be performed with the system operating.
Circuit Card Locations
Refer to Figure 37 for circuit card locations.
Figure 37:
Circuit Card Locations
Vertiv |NetSure 8100 Series Installation & User Manual (UM582140600)|Rev. A
Page 83
83
Replacing the Auxiliary Fuse Board
Procedure
NOTE!
Refer to
Figure 37
for circuit card location. Refer to
Figure 38
as this procedure is performed.
1. Performing this procedure may activate external alarms. Do one of the following. If possible, disable
these alarms. If these alarms cannot be easily disabled, notify the appropriate personnel to disregard
any future alarms associated with this system while the procedure is being performed.
DANGER! Performing the next steps exposes service personnel to battery potential. Exercise extreme
caution not to inadvertently contact or have any tool inadvertently contact any energized electrical
termination.
WARNING! Damage to the circuit card may result if the next step is not followed.
2. Connect an approved grounding strap to your wrist. Attach the other end to a suitable ground.
3. Remove the top front access panel from the bay. Before removing, note the location and orientation of
the grounding washers used with the hardware securing the panel.
4. Label all customer wires connected to the circuit card before removal in the next step. This will provide
better identification for reconnection later.
DANGER! Some customer wiring may be energized. In the next step, remove wires one at a time, and
isolate lead ends with tape or sleeving. Do not allow exposed lead ends to contact any other wires or
conductive surfaces.
5. Using a small flat blade screwdriver loosen the small screws securing the customer wires connected to
the connector. Remove all wires.
6. Unplug factory-connected wiring from the circuit card at the locations shown in the figure. Some plugs
are of the locking type. Hold the lock tab depressed and pull the plug from the mating connector.
7. Loosen and remove the four slotted screws securing the circuit card. Remove the circuit card.
8. Install the new circuit card and secure with four slotted screws.
9. Reconnect the previously-removed factory wiring. For locking type plugs, ensure the plug is fully
inserted and locked.
10. Reconnect customer wiring disconnected earlier. Torque specifications are 6.0 inch pounds for
customer connections.
11. Replace the top front access panel to the bay. Ensure grounding washers are used with each mounting
screw.
12. Remove the grounding wrist strap.
13. Enable the external alarms, or notify appropriate personnel that this procedure is finished.
14. Ensure that there are no local or remote alarms active on the system.
Vertiv |NetSure 8100 Series Installation & User Manual (UM582140600)|Rev. A
Page 84
84
Remove top cover panel.
Screw and grounding
washer 4-places.
Front
Remove auxiliary fuse board.
Customer
Connections
(torque 6.0 in-lbs)
Factory
Connections
(disconnect/reconnect
two wires)
Factory
Connections
(disconnect/reconnect
locking plug)
Figure 38:
Replacing the Auxiliary Fuse Board
Vertiv |NetSure 8100 Series Installation & User Manual (UM582140600)|Rev. A
Page 85
85
Replacing the IB2 (Interface Board)
Procedure
NOTE!
Refer to
Figure 37
for circuit card location. Refer to
Figure 39
as this procedure is performed.
1. Performing this procedure may activate external alarms. Do one of the following. If possible, disable
these alarms. If these alarms cannot be easily disabled, notify the appropriate personnel to disregard
any future alarms associated with this system while the procedure is being performed.
DANGER! Performing the next steps exposes service personnel to battery potential. Exercise extreme
caution not to inadvertently contact or have any tool inadvertently contact any energized electrical
termination.
WARNING! Damage to the circuit card may result if the next step is not followed.
2. Connect an approved grounding strap to your wrist. Attach the other end to a suitable ground.
3. Remove the top front access panel from the bay. Before removing, note the location and orientation of
the grounding washers used with the hardware securing the panel.
4. Carefully label the wires connected to the customer connection terminal blocks on the circuit card.
These wires must be connected to the same terminals on the replacement circuit card. Refer to Figure
39.
5. Carefully label the connectors plugged into the circuit card. These connectors must be plugged into the
same connectors on the replacement circuit card. Refer to Figure 39.
DANGER! In the next step, external alarm wiring may be energized from an external source. DO NOT
allow bare wire ends to contact any grounded or energized object.
6. Remove the external wiring from the customer connection terminal blocks. DO NOT allow the bare wire
end to contact any grounded or energized object. Isolate the wire end with electrical tape. Repeat for
each wire to be removed.
7. Unplug all connectors plugged into the circuit card.
8. Remove the circuit card (and shield) from the bay by removing the screws securing it. See Figure 39.
9. In this step, ensure you do not intermix the old and replacement circuit cards. Set the switch on the
replacement circuit card to the same setting as the old circuit card. See also “Switch Settings on IB2
Interface Board” on page 22.
10. Secure the replacement circuit card (and shield) to the bay. See Figure 39.
11. Plug all connectors removed from the old circuit card into the same position on the replacement circuit
card.
DANGER! In the next step, external alarm wiring may be energized from an external source. DO NOT
allow bare wire ends to contact any grounded or energized object.
12. Reconnect the external wiring to the correct terminals on the customer connection terminal block. First
remove the electrical tape that was applied to the bare wire end in a previous step. DO NOT allow the
Vertiv |NetSure 8100 Series Installation & User Manual (UM582140600)|Rev. A
Page 86
86
bare wire end to contact any grounded or energized object. After securing the wire, gently tug on the
wire to ensure that it cannot be pulled out of the terminal block. Repeat for each wire to be
reconnected. Recommended torque for these connections is 2.2 in-lbs.
13. Replace the top front access panel to the bay. Ensure grounding washers are used with each mounting
screw.
14. Remove the grounding wrist strap.
15. Enable the external alarms, or notify appropriate personnel that this procedure is finished.
16. Ensure that there are no local or remote alarms active on the system.
Vertiv |NetSure 8100 Series Installation & User Manual (UM582140600)|Rev. A
Note: Refer to MAKING
SWITCH AND JUMPER
SETTINGS section for switch
settings.
This side mounting
hardware between folds
in shield.
Figure 39:
Replacing the IB2 (Interface Board)
Vertiv |NetSure 8100 Series Installation & User Manual (UM582140600)|Rev. A
Page 88
88
Replacing the IB4 Board
Procedure
NOTE!
Refer to
Figure 37
for circuit card location. Refer to
Figure 40
as this procedure is performed.
1. Performing this procedure may activate external alarms. Do one of the following. If possible, disable
these alarms. If these alarms cannot be easily disabled, notify the appropriate personnel to disregard
any future alarms associated with this system while the procedure is being performed.
DANGER! Performing the next steps exposes service personnel to battery potential. Exercise extreme
caution not to inadvertently contact or have any tool inadvertently contact any energized electrical
termination.
WARNING! Damage to the circuit card may result if the next step is not followed.
2. Connect an approved grounding strap to your wrist. Attach the other end to a suitable ground.
3. Remove the top front access panel from the bay. Before removing, note the location and orientation of
the grounding washers used with the hardware securing the panel.
4. Unplug all connectors plugged into the circuit card.
5. Remove the circuit card from the bay by removing the screws securing. See Figure 40.
6. Secure the replacement circuit card to the bay. See Figure 40.
7. Plug all connectors removed from the old circuit card into the same position on the replacement circuit
card.
8. Replace the top front access panel to the bay. Ensure grounding washers are used with each mounting
screw.
9. Remove the grounding wrist strap.
10. Reboot the monitor unit.
Local Menu Navigation:
At the Main Screen, press ENT and ESC at the same time to reboot the monitor unit.
Web Menu Navigation:
Advance Settings Menu / SW Maintenance Tab / Reboot button.
11. Enable the external alarms, or notify appropriate personnel that this procedure is finished.
12. Ensure that there are no local or remote alarms active on the system.
Vertiv |NetSure 8100 Series Installation & User Manual (UM582140600)|Rev. A
Page 89
89
Remove top cover panel.
Front
Screw and grounding
washer 4-places.
Remove IB4 board.
IB4 Board
10M Ethernet
Port (RJ-45)
LAN Connection
USB-B Port
(Factory cable connected here.)
USB-A Port
(not used)
Figure 40:
Replacing the IB4 Board
Vertiv |NetSure 8100 Series Installation & User Manual (UM582140600)|Rev. A
Page 90
90
Replacing the SM-DUE Circuit Card
Procedure
NOTE!
Refer to
Figure 37
for circuit card location. Refer to
Figure 41
as this procedure is performed.
1. Performing this procedure may activate external alarms. Do one of the following. If possible, disable
these alarms. If these alarms cannot be easily disabled, notify the appropriate personnel to disregard
any future alarms associated with this system while the procedure is being performed.
DANGER! Performing the next steps exposes service personnel to battery potential. Exercise extreme
caution not to inadvertently contact or have any tool inadvertently contact any energized electrical
termination.
WARNING! Damage to the circuit card may result if the next step is not followed.
2. Connect an approved grounding strap to your wrist. Attach the other end to a suitable ground.
3. Remove the front center access panel from the bay. See Figure 41. Either slide the panel out of the way
to access the SM-DUE circuit card, or completely remove the panel by unplugging the connectors
connected to the circuit cards attached to the inside of the panel.
4. Carefully label the connectors plugged into the circuit card. These connectors must be plugged into the
same mating connector on the replacement circuit card. Refer to Figure 41.
5. Unplug all connectors plugged into the SM-DUE circuit card. REMOVE THE POWER CONNECTOR
FIRST.
6. Remove the circuit card from the bay by removing the screws securing. See Figure 41.
7. In this step, ensure you do not intermix the old and replacement circuit cards. Set the switches and
jumpers on the replacement circuit card to the same setting as the old circuit card. See also “Switch
Settings on SM-DUE” on page 23 and “Jumper Settings on SM-DUE” on page25.
8. Orient the replacement circuit card over its mounting position inside the bay, and secure with the
screws removed from the old circuit card.
9. Plug all connectors removed from the old circuit card into the same position on the replacement circuit
card. PLUG THE POWER CONNECTOR LAST.
10. Replace the front center access panel to the bay
11. Remove the grounding wrist strap.
12. Temporarily remove then re-insert the monitor unit. Wait for the monitor unit to initialize.
13. Enable the external alarms, or notify appropriate personnel that this procedure is finished.
14. Ensure that there are no local or remote alarms active on the system.
Vertiv |NetSure 8100 Series Installation & User Manual (UM582140600)|Rev. A
Page 91
91
Remove center panel.
Remove SM-DUE
circuit card.
Note: Refer to MAKING
SWITCH AND JUMPER
SETTINGS section for switch
and jumper settings.
ON
OFF
18
Channel 1
Jumpers
1 3 5
2 4 6
Jumpers
1 3 5
2 4 6
Jumpers
1 3 5
2 4 6
Jumpers
1 3 5
2 4 6
Jumpers
1 3 5
2 4 6
Jumpers
1 3 5
2 4 6
Jumpers
1 3 5
2 4 6
Jumpers
1 3 5
2 4 6
Jumpers
1 3 5
2 4 6
Jumpers
1 3 5
2 4 6
Channel 2Channel 3Channel 4Channel 5
Channel 6
5V for HallChannel 7Channel 8Channel 9
Channel 10
SW1
Green LED
Red LED
PowerCAN RS-485
Relay Output
SM-DUE
Figure 41:
Replacing the SM-DUE Circuit Card
Vertiv |NetSure 8100 Series Installation & User Manual (UM582140600)|Rev. A
Page 92
92
Replacing the SM-DUH2 Circuit Card
Procedure
NOTE!
Refer to
Figure 37
for circuit card locations. Refer to
Figure 42
as this procedure is performed.
1. Performing this procedure may activate external alarms. Do one of the following. If possible, disable
these alarms. If these alarms cannot be easily disabled, notify the appropriate personnel to disregard
any future alarms associated with this system while the procedure is being performed.
DANGER! Performing the next steps exposes service personnel to battery potential. Exercise extreme
caution not to inadvertently contact or have any tool inadvertently contact any energized electrical
termination.
WARNING! Damage to the circuit card may result if the next step is not followed.
2. Connect an approved grounding strap to your wrist. Attach the other end to a suitable ground.
3. Remove the distribution panel cover.
4. Carefully label the connectors plugged into the circuit card. These connectors must be plugged into the
same mating connector on the replacement circuit card. Refer to Figure 42.
5. Unplug all connectors plugged into the SM-DUH2 circuit card. REMOVE THE POWER CONNECTOR
FIRST (J1 and J4).
6. Remove the screws securing the circuit card and remove the circuit card from the distribution panel.
7. In this step, ensure you do not intermix the old and replacement circuit cards. Set the switches on the
replacement circuit card to the same setting as the old circuit card. See also “Switch Settings on SMDUH2” on page 27.
8. Orient the replacement circuit card over its mounting position on the distribution panel, and secure with
the screws removed from the old circuit card.
9. Plug all connectors removed from the old circuit card into the same position on the replacement circuit
card.. PLUG THE POWER CONNECTORS LAST (J1 and J4).
10. Reinstall the distribution panel cover.
11. Remove the grounding wrist strap.
12. Enable the external alarms, or notify appropriate personnel that this procedure is finished.
13. Ensure that there are no local or remote alarms active on the system.
Vertiv |NetSure 8100 Series Installation & User Manual (UM582140600)|Rev. A
Page 93
93
Green L ED
Red LED
ON (DOWN)
18
SW1
SM-DUH2
SM-DUH2
Note: Refer to MAKING
SWITCH AND JUMPER
SETTINGS section for switch
settings.
List 15 Distribution Panel
(List 15A, 25, 25A Similar)
J1
Power
J5
RS-232
J7
RS-485
J3
CAN
J4
5V Power
J2
Hall Connector
Figure 42:
Replacing the SM-DUH2 Circuit Card
Vertiv |NetSure 8100 Series Installation & User Manual (UM582140600)|Rev. A
Page 94
94
Replacing a Distribution Panel
DANGER! Adhere to the “Important Safety Instructions” presented at the front of this document.
DANGER! All sources of DC power must be completely disconnected from this system before
performing this procedure. Use a voltmeter to verify no DC voltage is present on the system busbars
before proceeding.
Procedure
NOTE!
Refer to
Figure 31, Figure 32
, and
Figure 33
as this procedure is performed.
Removing the Distribution Panel
1. Performing this procedure may activate external alarms. Do one of the following. If possible, disable
these alarms. If these alarms cannot be easily disabled, notify the appropriate personnel to disregard
any future alarms associated with this system while the procedure is being performed.
2. Remove the distribution panel cover.
3. Disconnect all system load and battery wiring from the distribution panel.
4. Disconnect the alarm wiring from the distribution panel.
5. Disconnect any input wiring to the distribution panel.
6. Remove any paralleling bars from the distribution panel.
7. Remove any input busbars from the distribution panel.
8. Disconnect the bay’s wire harness connectors from the distribution panel.
9. Remove the hardware securing the distribution panel to the bay. Remove the distribution panel from
the distribution cabinet
Installing the Distribution Panel
1. Orient the replacement distribution panel into bay. Secure the distribution panel to the bay with the
hardware removed from the old panel.
2. Reconnect the bay’s wire harness connectors to the distribution panel.
3. Replace any input busbars to the distribution panel.
4. Replace any paralleling bars to the distribution panel.
5. Reconnect any input wiring to the distribution panel.
6. Reconnect the alarm wiring to the distribution panel.
7. Reconnect the load distribution and battery wiring to the distribution panel.
8. Transfer the circuit breakers or fuses from the old distribution panel to the replacement distribution
panel.
9. Replace the distribution panel cover.
Vertiv |NetSure 8100 Series Installation & User Manual (UM582140600)|Rev. A
Page 95
95
Restarting the Power System
1. Reconnect the DC power sources to the system.
2. Start the system. Refer to “Initially Starting, Configuring, and Checking System Operation” on page 62.
3. Enable the external alarms, or notify appropriate personnel that this procedure is finished.
4. Ensure that there are no local or remote alarms active on the system.
Vertiv |NetSure 8100 Series Installation & User Manual (UM582140600)|Rev. A
Page 96
96
Replacing an Output Bar with Sensor in a List 15A or List 25A Distribution Panel
DANGER! Adhere to the “Important Safety Instructions” presented at the front of this document.
Procedure
NOTE!
Refer to
Figure 43
as this procedure is performed.
1. Performing this procedure may activate external alarms. Do one of the following. If possible, disable
these alarms. If these alarms cannot be easily disabled, notify the appropriate personnel to disregard
any future alarms associated with this system while the procedure is being performed.
2. Remove the front panel cover from the distribution panel.
3. Remove the covers from the rear of the bay to gain access to the rear of the distribution panel.
4. Disconnect the load cable from the output side of the output bar being replaced on the distribution
panel.
5. Remove the associated circuit breaker from the distribution panel.
6. Remove the clear protective cover from the front of the distribution panel by removing two (2) screws
(one on the top and one on the bottom).
7. Disconnect the flexible ribbon cable attached to the output bar being replaced from the SM-DUH2
circuit board by sliding the retainer back on the connector.
8. Remove the two (2) shoulder bolts securing the output bar being replaced from the rear of the
distribution panel.
9. Remove the output bar with sensor.
10. Install the replacement output bar with sensor and secure with the two (2) shoulder bolts previously
removed.
11. Connect the flexible ribbon cable attached to the replacement output bar to the SM-DUH2 circuit board.
12. Replace the clear protective cover to the front of the distribution panel and secure with the two (2)
screws previously removed (one on the top and one on the bottom).
13. Replace the associated circuit breaker onto the distribution panel.
14. Replace the load cable to the output side of the replacement output bar.
15. Replace the covers onto the rear of the bay
16. Replace the front panel cover over the distribution panel.
17. Enable the external alarms, or notify appropriate personnel that this procedure is finished.
18. Ensure that there are no local or remote alarms active on the system.
Vertiv |NetSure 8100 Series Installation & User Manual (UM582140600)|Rev. A
Page 97
97
Front
Front Panel Cover
Protective Cover
Flexible
Ribbon
Cable
List 15A, List 25A Similar
Rear
Output Bar
with Sensor
Shoulder Bolts
SM-DUH2
Circuit Card
Figure 43:
Replacing Output Bar / Sensor Assembly in a List 15A or List 25A Distribution Panel
Vertiv |NetSure 8100 Series Installation & User Manual (UM582140600)|Rev. A
Page 98
UM582140600 (RA 02/17)
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.