Vertiv NetSure 801DB NVGB System Application Manual

Page 1
SYSTEM OVERVIEW
Home
General Specifications
The NetSure™ 801DB NVGB DC Power Distribution is a -48V Battery Distribution Fuse / Circuit Breaker Bay
(BDF/CBB).
The NetSure™ 801DB
Each distribution panel can be configured for separate inputs giving you an 8-load or 6-load bay (must
Each bay can be equipped with an optional “full bay length” internal ground/return bar (per side)
Each bay can easily be configurable for top or bottom feed.
Each bay is equipped with a digital meter assembly. The List 105 and 107 bays provide a basic digital
SAG582120600
System Application Guide
Spec. No. 582120600 (Model 801DB
Revision BK, September 27, 2017
NVGB can be ordered as an 8-distribution panel or 6-distribution panel bay (4 or
3 panels per side).
use an external ground/return bar), or the panels per side can be paralleled to allow one feed per side giving you a 2-load bay (may use the optional internal ground/return bar). Other configurations include an 8-panel bay with 4-loads and two loads, and a 6-panel bay with 4-loads (paralleling the top two panels
paralleling the bottom two panels per side).
(configuration restrictions apply). Another option includes replacing one (8- and 6-panel bays) or two (8-panel bay only) distribution panels per side with a “panel length” internal ground/return bar.
meter, which is capable of displaying system load voltage and current on each Distribution Panel. An advanced Digital Meter/Alarm Panel is provided in the List 106 and 108 bays. In addition to the basic metering functions, this panel provides Low Voltage, Power Lost, Over-current and Fuse/Circuit Breaker alarms for each panel in the bay. Also provided are four (4) external alarm relay circuits, to which any combination of alarms can be mapped. This Meter Panel comes with a comprehensive Web page capability for remote system management.
NVGB)
See detailed specifications on page 66.
Family: NetSure™
Spec. No.: 582120600
Model: 801DB
NVGB
Output Voltage: -48 Volts DC
Output Capacity: 640A continuous per Distribution Panel
8-Panel Bay; 2400A Maximum per Side, 4800A Maximum per Bay
6-Panel Bay; 1800A Maximum per Side, 3600A Maximum per Bay
Agency Approval: UL Listed ("cULus"), NEBS
Framework Type: Seismic Rated (Zone 4) Box Framework
6-Panel Sizes: 84”H x 26“W x 16“D
84”H x 30“W x 24“D
8-Panel Sizes: 84”H x 26“W x 16“D
84”H x 30“W x 24“D
Access: Front and Rear for Installation, Front for Operation and Maintenance
Color: Textured Gray (M500-147)
Environment: 0°C to +40°C (+32°F to +104°F)
Page 1 of 75
Page 2
SAG582120600 System Application Guide
Home
Revision BK, September 27, 2017 Spec. No. 582120600 (Model 801DB NVGB)
Page 2 of 75
Page 3
System Application Guide SAG582120600 Spec. No. 582120600 (Model 801DB NVGB) Revision BK, September 27, 2017
TABLE OF CONTENTS
SYSTEM OVERVIEW ............................................................................................................................................................................................................. 1
MAIN COMPONENTS ILLUSTRATIONS .......................................................................................................................................................................... 5
Eight Panel Bay ............................................................................................................................................................................................................... 5
Six Panel Bay.................................................................................................................................................................................................................... 7
LIST DESCRIPTIONS ............................................................................................................................................................................................................9
List Numbers ....................................................................................................................................................................................................................9
List 106: Common Equipment, 6-Panel Bay, w/ Advanced Metering .............................................................................................................................. 9
List 206: Common Equipment, 6-Panel Bay, w/ Advanced Metering ...........................................................................................................................10
List 108: Common Equipment, 8-Panel Bay, w/ Advanced Metering ............................................................................................................................. 11
List 208: Common Equipment, 8-Panel Bay, w/ Advanced Metering ........................................................................................................................... 12
List 110: Distribution Panel, 8-Panel Bay .......................................................................................................................................................................................... 13
List 115: Distribution Panel, 8-Panel Bay .......................................................................................................................................................................................... 13
List 116: Optional Internal Ground/Return Bar, 8-Panel Bay (Full Bay Length) ...................................................................................................... 14
List 117: Optional Internal Ground/Return Bar, 8-Panel Bay (Panel Length) ............................................................................................................ 14
List 118: Blank Distribution Panel Cover, 8-Panel Bay ............................................................................................................................................................. 15
List 120: Distribution Panel, 6-Panel Bay ......................................................................................................................................................................................... 15
List 125: Distribution Panel, 6-Panel Bay ......................................................................................................................................................................................... 16
List 126: Optional Internal Ground/Return Bar, 6-Panel Bay (Full Bay Length) ..................................................................................................... 16
List 127: Optional Internal Ground/Return Bar, 6-Panel Bay (Panel Length) ........................................................................................................... 17
List 128: Blank Distributional Panel Cover, 6-Panel Bay ........................................................................................................................................................ 17
List 130: Distribution Panel Paralleling Bar .................................................................................................................................................................................... 17
List 139: Optional Internal Ground/Return Bar Paralleling Kit, 8-Panel Bay (Panel Length) .......................................................................... 18
List 143: Bay Input Feed and Shunt Assembly (4 Cables, 25 mV. Shunts) ................................................................................................................ 18
List 144: Bay Input Feed and Shunt Assembly (2 Cables, 25 mV. Shunts) ................................................................................................................ 18
List 145: Bay Input Feed and Shunt Assembly (2 Cables, 50 mV. Shunts) ................................................................................................................ 19
List 147: Bay Input Feed and Shunt Assembly (4 Cables, 50 mV. Shunts) ................................................................................................................ 19
List 148: 2400A Ground/Return Input Assembly, with Optional Bonding Strap ................................................................................................... 20
List 150: Optional Capacitor Precharge Assembly ................................................................................................................................................................... 20
List 151: Dressing Bar .................................................................................................................................................................................................................................... 21
List 251: Dressing Bar ................................................................................................................................................................................................................................... 21
List 153: Load Distribution Cable Management Kit................................................................................................................................................................... 21
List 253: Load Distribution Cable Management Kit ................................................................................................................................................................. 22
List 166: Meter Panel Field Upgrade Retrofit Kit ....................................................................................................................................................................... 22
List 167: Pre-Installed Load Lug-Mounting Hardware ........................................................................................................................................................... 22
List 168: Meter Panel Field Upgrade Retrofit Kit ....................................................................................................................................................................... 23
List 170: Assembly, Ethernet .................................................................................................................................................................................................................. 23
For Manufactured Discontinued Bays (Model 1293V3) ..................................................................................................................................... 24
ACCESSORY DESCRIPTIONS ......................................................................................................................................................................................... 26
Load Lug Hardware Kits ............................................................................................................................................................................................ 26
Side by Side Busbar Link Kit for Use with List 110 and List 120, P/N 556103 .............................................................................................. 26
Side by Side Busbar Link Kit for Use with List 115 and List 125, P/N 557256 .............................................................................................. 26
Right Angle Lug Adaptor Kits, P/Ns 556377 and 556378 ................................................................................................................................. 28
External Return/Ground Bar Assemblies .............................................................................................................................................................. 29
Seismic Anchor Kit, P/N 545387 .............................................................................................................................................................................. 30
Transient Voltage Surge Suppressor (TVSS) Device ........................................................................................................................................ 30
Distribution Devices and Lug Selection.................................................................................................................................................................. 31
TLS/TPS Fuses/Fuseblocks, TPL Fuses/Fuseblocks, and Lug Selection for Lists 110 and 120 .................................................................... 31
Bullet Nose-Type Circuit Breakers, Bullet Nose-Type Fuseblocks e/w TLS/TPS Fuses, and Lug Selection for Lists
115 and 125 ........................................................................................................................................................................................................................................................... 35
Box Framework Extensions ........................................................................................................................................................................................ 41
One (1) Foot Box Framework Extension ............................................................................................................................................................................................ 41
Two (2) Foot Box Framework Extension........................................................................................................................................................................................... 41
Four and One-Half (4-1/2) Foot Box Framework Extension ................................................................................................................................................. 41
Wiring Notes ................................................................................................................................................................................................................. 42
Bay Frame Grounding Wire Sizes and Lugs Selection ............................................................................................................................................................ 42
External Alarm Wiring—List 105 and 107 Bays ............................................................................................................................................................................ 42
Page 3 of 75
Page 4
SAG582120600 System Application Guide Revision BK, September 27, 2017 Spec. No. 582120600 (Model 801DB NVGB)
External Alarm and Control Wiring—List 106, 206, 108 and 208 Bays ......................................................................................................................... 42
Load Distribution Wire Sizes Selection ............................................................................................................................................................................................. 43
DC Input Cable Sizes and Lugs Selection ....................................................................................................................................................................................... 47
Wiring Illustrations ...................................................................................................................................................................................................... 48
Overall Installer’s Connections ............................................................................................................................................................................................................... 48
Bay Frame Grounding Connection ...................................................................................................................................................................................................... 49
External Alarm and Meter/Alarm Card Input Connections .................................................................................................................................................. 50
Load Distribution Connections—Lists 106, 108, 206, 208 .................................................................................................................................................... 55
DC Input Connections ................................................................................................................................................................................................................................... 61
Replacement Alarm, Reference, and Control Fuses, List 105 and 107 Bays ................................................................................................. 64
Fuseblock Located in Bay’s Top Center .......................................................................................................................................................................................... 64
Replacement Alarm, Reference, and Control Fuses, List 106 and 108 Bays ................................................................................................. 64
Fuses Located on Auxiliary Fuse Card at Top of Bay ............................................................................................................................................................. 64
Replacement Circuit Cards, List 105 and 107 Bays ............................................................................................................................................. 65
Replacement Circuit Cards, List 106, 108, 206, and 208 Bays ......................................................................................................................... 65
SPECIFICATIONS ................................................................................................................................................................................................................ 66
1.1 DC Operating Voltage .......................................................................................................................................................................................... 66
1.2 Environmental Ratings ......................................................................................................................................................................................... 66
1.3 Compliance Information ....................................................................................................................................................................................... 66
1.4 Output Ratings ....................................................................................................................................................................................................... 66
1.5 Standard Features—Lists 106 and 108 ............................................................................................................................................................ 66
MECHANICAL SPECIFICATIONS (LIST 106 AND 108) ............................................................................................................................................ 68
Floor Hole Drilling Pattern Dimensions .................................................................................................................................................................. 68
MECHANICAL SPECIFICATIONS (LIST 206 AND 208) ........................................................................................................................................... 69
Floor Hole Drilling Pattern Dimensions .................................................................................................................................................................. 69
Dimensions, List 108: 8-Bus Bay .............................................................................................................................................................................. 70
Dimensions, List 208: 8-Bus Bay ............................................................................................................................................................................... 71
Dimensions, List 106: 6-Bus Bay .............................................................................................................................................................................. 72
Dimensions, List 206: 6-Bus Bay ............................................................................................................................................................................. 73
RELATED DOCUMENTATION ........................................................................................................................................................................................ 74
REVISION RECORD ............................................................................................................................................................................................................ 75
Page 4 of 75
Page 5
System Application Guide SAG582120600
Front View
Eight Panel Bay
Digital Meter Assembly
Distribution Panel (B) Box Framework Extension (1’,
Distribution Panel (G)
Distribution Panel (H)
Distribution Panel (A)
Paralleling Bar
Paralleling Bar
Paralleling Bar
Paralleling Bar
Distribution Panel (C)
Distribution Panel (D)
Distribution Panel (E)
Distribution Panel (F) Paralleling Bar
Paralleling Bar
Home
Spec. No. 582120600 (Model 801DB NVGB) Revision BK, September 27, 2017
MAIN COMPONENTS ILLUSTRATIONS
Eight Panel Bay
List 108 or 208 (Common Equipment)
List 116 (Optional Internal ‘Full Bay
Length’ Ground/Return Bar)
List 143, 144, 145, 147 (Bay Input Feed and Shunt Assembly)
2’, or 4.5’)
P/O List 108 or 208 (shown)
(List 110 or 115) or
Blank Panel (List 118)
(List 130)
(List 110 or 115) or
Blank Panel (List 118)
(List 130)
(List 110 or 115) or
Blank Panel (List 118)
(List 130)
(List 110 or 115) or Blank Panel (List 118)
(List 130)
(List 110 or 115) or Blank Panel (List 118)
(List 130)
(List 110 or 115) or Blank Panel (List 118)
(List 130)
(List 110 or 115) or
Blank Panel (List 118)
(List 110 or 115) or Blank Panel (List 118)
Page 5 of 75
Page 6
SAG582120600 System Application Guide
OTHER OPTIONS
Home
Revision BK, September 27, 2017 Spec. No. 582120600 (Model 801DB NVGB)
List 117 (Optional Internal
‘Panel Length’ Ground/Return Bar)
List 139 (Optional Internal ‘Panel Length’
Ground/Return Bar Paralleling Kit)
List 148 (2400A Ground/Return Input Assembly,
with Optional Bonding Strap for List 116 Ground/Return Bar)
List 150 (Optional Capacitor
Precharge Assembly)
List 151 (Dressing Bar)
List 153 (Load Distribution
Cable Management Kit)
List 156 (Meter and Alarm Card
Internal Power In-Line Fuse Kit, for List 105 bay)
List 167 (Pre-Installed Load Lug Hardware)
List 168 (Field Installable Advanced Meter Panel for
older 8-Panel BDFBs)
Page 6 of 75
Page 7
System Application Guide SAG582120600
Front View
Six Panel Bay
Digital Meter Assembly P/O List 106 (shown) or 206
Distribution Panel (B) Box Framework Extension (1’,
Distribution Panel (D)
Distribution Panel (E)
Distribution Panel (F)
Distribution Panel (C)
Distribution Panel (A)
Paralleling Bar
Paralleling Bar
Paralleling Bar
Paralleling Bar
Home
Spec. No. 582120600 (Model 801DB NVGB) Revision BK, September 27, 2017
Six Panel Bay
List 106 or 206 (Common Equipment)
List 126 (Optional Internal ‘Full Bay
Length’ Ground/Return Bar)
List 143, 144, 145, 147 (Bay Input Feed and Shunt Assembly)
2’, or 4.5’)
(List 120 or 125) or
Blank Panel (List 128)
(List 130)
(List 120 or 125) or
Blank Panel (List 128)
(List 130)
(List 120 or 125) or
Blank Panel (List 128)
(List 120 or 125) or Blank Panel (List 128)
(List 130)
(List 120 or 125) or Blank Panel (List 128)
(List 130)
(List 120 or 125) or Blank Panel (List 128)
Page 7 of 75
Page 8
SAG582120600 System Application Guide
OTHER OPTIONS
Home
Revision BK, September 27, 2017 Spec. No. 582120600 (Model 801DB NVGB)
List 127 (Optional Internal
‘Panel Length’ Ground/Return Bar)
List 148 (2400A Ground/Return Input Assembly,
with Optional Bonding Strap for List 126 Ground/Return Bar)
List 150 (Optional Capacitor
Precharge Assembly)
List 151 (Dressing Bar)
List 153 (Load Distribution
Cable Management Kit)
List 156 (Meter and Alarm Card
Internal Power In-Line Fuse Kit, for List 107 bay)
List 167 (Pre-Installed Load Lug Hardware)
List 166 (Field Installable Advanced Meter Panel for
older 6-Panel BDFBs)
Page 8 of 75
Page 9
System Application Guide SAG582120600
Home
Spec. No. 582120600 (Model 801DB NVGB) Revision BK, September 27, 2017
LIST DESCRIPTIONS
List Numbers
List 106: Common Equipment, 6-Panel Bay, w/ Advanced Metering
Features
List 106 provides the common equipment for a 6-Distribution Panel BDF/CBB (Battery Distribution Fuse/Circuit Breaker
Bay) with advanced metering.
♦ Configurable for top or bottom feed.
Consists of a 7’H x 26”W x 15”D welded box framework (seismic, zone 4 earthquake compliant).
Includes an Advanced Meter/Alarm Panel that provides the following functions for each panel in the bay: voltage and
current metering and Low Voltage, Power Lost, Overcurrent, and Fuse/Circuit Breaker alarms. Also provided are four (4) external alarm relay circuits, to which any combination of alarms can be mapped.
Provides four (4) fused auxiliary -48V power outputs (1-1/3A), fused remote (A/B) meter panel inputs, internal/external
sense option, and an Ethernet connection (requires List 170 Ethernet option).
Restrictions
None.
Ordering Notes
1) Order up to six (6) Lists 120 and/or List 125 Distribution Panels per bay.
2) If List 120 is ordered, order a List 150 Capacitor Precharge Assembly, if required.
3) For any open Distribution Panel position, order a List 128 Blank Panel.
4) Order List 143 or 144 Input Feed and Shunt Assembly as required. Each List 143 or 144 provides input terminations and
shunts for both sides.
For top and bottom feed 2-load applications, order one (1) List 143 or 144 and specify top or bottom feed.
For top and bottom feed multi-load applications, order three (3) List 143 or 144 for each Side A/Side B load and specify top or bottom feed.
List 120 Only: For 3-load side by side applications, order three (3) List 143 or 144, and order three (3) 556103.
List 125 Only: For 3-load side by side applications, order three (3) List 143 or 144, and order three (3) 557256.
5) If Distribution Panels (per side) are to be paralleled, order a List 130 Distribution Panel Paralleling Bar. Each List 130
includes two (2) Paralleling Bars (one per side).
6) Order List 126 or List 127 Internal Ground Bars as required, or External Ground Bars (see ACCESSORY DESCRIPTIONS
section) as required.
7) List 126 provides input lug landing points at the top or bottom (as specified) of the full bay length ground/return busbars.
List 126 internal return bars are rated for 1200 Amps. List 148 is available to increase that capacity to 2400 Amps and provide additional cable landing points. Each bay can accommodate (1) List 148. List 148 offers cable termination at the rear of the bay and the option of a bonding strap.
8) Order List 151 Cable Dressing Bars as required.
9) Order a 1’, 2’, or 4-1/2’ Box Framework Extension as required.
10) Order distribution fuses, circuit breakers, and load lugs as required per Distribution Devices and Lug Selection in
ACCESSORY DESCRIPTIONS.
11) For Load and Load Return lug-mounting hardware, order Load Lug Hardware Kits (ship-loose) as required, or order List
167 (pre-installed).
12) Order TVSS Device(s) as required per Transient Voltage Surge Suppressor (TVSS) Device in ACCESSORY
DESCRIPTIONS.
13) Order DC input lugs as required per DC Input Cable Sizes and Lugs Selection under Wiring Notes in ACCESSORY
DESCRIPTIONS.
14) Order bay frame grounding lugs as required per Bay Frame Grounding Wire Sizes and Lugs Selection under Wiring Notes
in ACCESSORY DESCRIPTIONS.
15) For remote access capability, order one (1) List 170 Ethernet option.
Page 9 of 75
Page 10
SAG582120600 System Application Guide
Home
Revision BK, September 27, 2017 Spec. No. 582120600 (Model 801DB NVGB)
List 206: Common Equipment, 6-Panel Bay, w/ Advanced Metering
Features
List 206 provides the common equipment for a 6-Distribution Panel BDF/CBB (Battery Distribution Fuse/Circuit Breaker
Bay) with advanced metering.
♦ Configurable for top or bottom feed.
Consists of a 84”H x 30”W x 24”D welded box framework (seismic, zone 4 earthquake compliant).
Includes an Advanced Meter/Alarm Panel that provides the following functions for each panel in the bay: voltage and
current metering and Low Voltage, Power Lost, Overcurrent, and Fuse/Circuit Breaker alarms. Also provided are four (4) external alarm relay circuits, to which any combination of alarms can be mapped.
Provides four (4) fused auxiliary -48V power outputs (1-1/3A), fused remote (A/B) meter panel inputs, internal/external
sense option, and an Ethernet connection (requires List 170 Ethernet option).
Restrictions
None.
Ordering Notes
1) Order up to six (6) Lists 120 and/or List 125 Distribution Panels per bay.
2) If List 120 is ordered, order a List 150 Capacitor Precharge Assembly, if required.
3) For any open Distribution Panel position, order a List 128 Blank Panel.
4) Order List 143 or 144 Input Feed and Shunt Assembly as required. Each List 143 or 144 provides input terminations and
shunts for both sides.
For top and bottom feed 2-load applications, order one (1) List 143 or 144 and specify top or bottom feed.
For top and bottom feed multi-load applications, order three (3) List 143 or 144 for each Side A/Side B load and specify top or bottom feed.
List 120 Only: For 3-load side by side applications, order three (3) List 143 or 144, and order three (3) 556103.
List 125 Only: For 3-load side by side applications, order three (3) List 143 or 144, and order three (3) 557256.
5) If Distribution Panels (per side) are to be paralleled, order a List 130 Distribution Panel Paralleling Bar. Each List 130
includes two (2) Paralleling Bars (one per side).
6) Order List 126 or List 127 Internal Ground Bars as required, or External Ground Bars (see ACCESSORY DESCRIPTIONS
section) as required.
7) List 126 provides input lug landing points at the top or bottom (as specified) of the full bay length ground/return busbars.
List 126 internal return bars are rated for 1200 Amps. List 148 is available to increase that capacity to 2400 Amps and provide additional cable landing points. Each bay can accommodate (1) List 148. List 148 offers cable termination at the rear of the bay and the option of a bonding strap.
8) Order List 251 Cable Dressing Bars as required.
9) Order distribution fuses, circuit breakers, and load lugs as required per Distribution Devices and Lug Selection in
ACCESSORY DESCRIPTIONS.
10) For Load and Load Return lug-mounting hardware, order Load Lug Hardware Kits (ship-loose) as required, or order List
167 (pre-installed).
11) Order TVSS Device(s) as required per Transient Voltage Surge Suppressor (TVSS) Device in ACCESSORY
DESCRIPTIONS.
12) Order DC input lugs as required per DC Input Cable Sizes and Lugs Selection under Wiring Notes in ACCESSORY
DESCRIPTIONS.
13) Order bay frame grounding lugs as required per Bay Frame Grounding Wire Sizes and Lugs Selection under Wiring Notes
in ACCESSORY DESCRIPTIONS.
14) For remote access capability, order one (1) List 170 Ethernet option.
Page 10 of 75
Page 11
System Application Guide SAG582120600
Home
Spec. No. 582120600 (Model 801DB NVGB) Revision BK, September 27, 2017
List 108: Common Equipment, 8-Panel Bay, w/ Advanced Metering
Features
List 108 provides the common equipment for an 8-Distribution Panel BDF/CBB (Battery Distribution Fuse/Circuit Breaker
Bay) with advanced metering.
♦ Configurable for top or bottom feed.
Consists of a 84”H x 26”W x 15”D welded box framework (seismic, zone 4 earthquake compliant).
Includes an Advanced Meter/Alarm Panel that provides the following functions for each panel in the bay: voltage and
current metering and Low Voltage, Power Lost, Overcurrent, and Fuse/Circuit Breaker alarms. Also provided are four (4) external alarm relay circuits, to which any combination of alarms can be mapped.
Provides four (4) fused auxiliary -48V power outputs (1-1/3A), fused remote (A/B) meter panel inputs, internal/external
sense option, and an Ethernet connection (requires List 170 Ethernet option).
Restrictions
None.
Ordering Notes
1) Order up to eight (8) Lists 110 and/or List 115 Distribution Panels per bay.
2) If List 110 is ordered, order a List 150 Capacitor Precharge Assembly, if required.
3) For any open Distribution Panel position, order a List 118 Blank Panel.
4) Order List 143 or 144 Input Feed and Shunt Assembly as required. See Restrictions above. Each List 143 or 144 provides
input terminations and shunts for both sides.
For top and bottom feed 2-load applications, order one (1) List 143 or 144 and specify top or bottom feed.
For top and bottom feed multi-load applications, order two (2) or four (4) List 143 or 144 for each Side A/Side B load and specify top or bottom feed. Order List 130 as required.
List 110 Only: For 4-load side by side applications, order four (4) List 143 or 144, and order four (4) 556103. For top and bottom feed 2-load side by side applications, order two (2) List 143 or 144, two (2) 556103, and two (2) List 130.
List 115 Only: For 4-load side by side applications, order four (4) List 143 or 144, and order four (4) 557256. For top and bottom feed 2-load side by side applications, order two (2) List 143 or 144, two (2) 557256, and two (2) List 130.
5) If Distribution Panels (per side) are to be paralleled, order a List 130 Distribution Panel Paralleling Bar. Each List 130
includes two (2) Paralleling Bars (one per side).
6) Order List 116 or List 117 Internal Ground Bars as required, or External Ground Bars (see ACCESSORY DESCRIPTIONS
section) as required.
7) List 116 provides input lug landing points at the top or bottom (as specified) of the full bay length ground/return busbars.
List 116 internal return bars are rated for 1200 Amps. List 148 is available to increase that capacity to 2400 Amps and provide additional cable landing points. Each bay can accommodate (1) List 148. List 148 offers cable termination at the rear of the bay and the option of a bonding strap.
8) Order List 151 Cable Dressing Bars as required.
9) Order a 1’, 2’, or 4-1/2’ Box Framework Extension as required.
10) Order distribution fuses, circuit breakers, and load lugs as required per Distribution Devices and Lug Selection in
ACCESSORY DESCRIPTIONS.
11) For Load and Load Return lug-mounting hardware, order Load Lug Hardware Kits (ship-loose) as required, or order List
167 (pre-installed).
12) Order TVSS Device(s) as required per Transient Voltage Surge Suppressor (TVSS) Device in ACCESSORY
DESCRIPTIONS.
13) Order DC input lugs as required per DC Input Cable Sizes and Lugs Selection under Wiring Notes in ACCESSORY
DESCRIPTIONS.
14) Order bay frame grounding lugs as required per Bay Frame Grounding Wire Sizes and Lugs Selection under Wiring Notes
in ACCESSORY DESCRIPTIONS.
15) For remote access capability, order one (1) List 170 Ethernet option.
Page 11 of 75
Page 12
SAG582120600 System Application Guide
Home
Revision BK, September 27, 2017 Spec. No. 582120600 (Model 801DB NVGB)
List 208: Common Equipment, 8-Panel Bay, w/ Advanced Metering
List 208 provides the common equipment for an 8-Distribution Panel BDF/CBB (Battery Distribution Fuse/Circuit Breaker
Bay) with advanced metering.
♦ Configurable for top or bottom feed.
Consists of a 84”H x 30”W x 24”D welded box framework (seismic, zone 4 earthquake compliant).
Includes an Advanced Meter/Alarm Panel that provides the following functions for each panel in the bay: voltage and
current metering and Low Voltage, Power Lost, Overcurrent, and Fuse/Circuit Breaker alarms. Also provided are four (4) external alarm relay circuits, to which any combination of alarms can be mapped.
Provides four (4) fused auxiliary -48V power outputs (1-1/3A), fused remote (A/B) meter panel inputs, internal/external
sense option, and an Ethernet connection (requires List 170 Ethernet option).
Restrictions
None.
Ordering Notes
1) Order up to eight (8) Lists 110 and/or List 115 Distribution Panels per bay.
2) If List 110 is ordered, order a List 150 Capacitor Precharge Assembly, if required.
3) For any open Distribution Panel position, order a List 118 Blank Panel.
4) Order List 143 or 144 Input Feed and Shunt Assembly as required. See Restrictions above. Each List 143 or 144 provides
input terminations and shunts for both sides.
For top and bottom feed 2-load applications, order one (1) List 143 or 144 and specify top or bottom feed.
For top and bottom feed multi-load applications, order two (2) or four (4) List 143 or 144 for each Side A/Side B load and specify top or bottom feed. Order List 130 as required.
List 110 Only: For 4-load side by side applications, order four (4) List 143 or 144, and order four (4) 556103. For top and bottom feed 2-load side by side applications, order two (2) List 143 or 144, two (2) 556103, and two (2) List 130.
List 115 Only: For 4-load side by side applications, order four (4) List 143 or 144, and order four (4) 557256. For top and bottom feed 2-load side by side applications, order two (2) List 143 or 144, two (2) 557256, and two (2) List 130.
5) If Distribution Panels (per side) are to be paralleled, order a List 130 Distribution Panel Paralleling Bar. Each List 130
includes two (2) Paralleling Bars (one per side).
6) Order List 116 or List 117 Internal Ground Bars as required, or External Ground Bars (see ACCESSORY DESCRIPTIONS
section) as required.
7) List 116 provides input lug landing points at the top or bottom (as specified) of the full bay length ground/return busbars.
List 116 internal return bars are rated for 1200 Amps. List 148 is available to increase that capacity to 2400 Amps and provide additional cable landing points. Each bay can accommodate (1) List 148. List 148 offers cable termination at the rear of the bay and the option of a bonding strap.
8) Order List 251 Cable Dressing Bars as required.
9) Order distribution fuses, circuit breakers, and load lugs as required per Distribution Devices and Lug Selection in
ACCESSORY DESCRIPTIONS.
10) For Load and Load Return lug-mounting hardware, order Load Lug Hardware Kits (ship-loose) as required, or order List
167 (pre-installed).
11) Order TVSS Device(s) as required per Transient Voltage Surge Suppressor (TVSS) Device in ACCESSORY
DESCRIPTIONS.
12) Order DC input lugs as required per DC Input Cable Sizes and Lugs Selection under Wiring Notes in ACCESSORY
DESCRIPTIONS.
13) Order bay frame grounding lugs as required per Bay Frame Grounding Wire Sizes and Lugs Selection under Wiring Notes
in ACCESSORY DESCRIPTIONS.
14) For remote access capability, order one (1) List 170 Ethernet option.
Page 12 of 75
Page 13
System Application Guide SAG582120600
Home
Spec. No. 582120600 (Model 801DB NVGB) Revision BK, September 27, 2017
List 110: Distribution Panel, 8-Panel Bay
Features
Twelve (12) TLS/TPS fuse positions, or six (6) TPL fuse positions, or a combination of TLS/TPS and TPL fuse positions.
Includes (12) TLS/TPS Fuseholders P/N 248817100. For panels
bay, each TPL Fuseholder P/N 516241 ordered replaces (2) P/N 248817100 Fuseholders.
See Load Distribution Connections under Wiring Illustrations in ACCESSORY
DESCRIPTIONS for load termination specifications.
Restrictions
640A maximum continuous.
For use in List 108 or 208.
Ordering Notes
1) Order as required.
2) Specify up to twelve (12) TLS/TPS fuseholders, or up to six (6) TPL fuseholders, or a
combination per Distribution Panel (all positions MUST be filled). This instructs the factory how to configure the Distribution Panel. Also specify mounting location for each configured Distribution Panel per bay. This instructs the factory where to mount each configured Distribution Panel per bay.
3) Order distribution fuses and load lugs as required per Distribution Devices and Lug
Selection in ACCESSORY DESCRIPTIONS.
4) Replacement panels will be equipped with 12 TLS/TPS Fuseholders. TPL fuseholders (P/N 516241) may be ordered to
field modify the distribution panel. One TPL fuseholder takes the space of two TLS/TPS fuseholders.
List 115: Distribution Panel, 8-Panel Bay
Features
Sixteen (16) bullet nose circuit breaker and/or TLS/TPS Fuse (with bullet nose fuseholder) positions.
♦ See Load Distribution Connections under Wiring Illustrations in ACCESSORY DESCRIPTIONS for load termination
specifications.
Restrictions
640A maximum continuous.
For use in List 108 or 208.
configured in a
Ordering Notes
1) Order as required.
2) Specify mounting location for each Distribution Panel per bay. This instructs the factory
where to mount each Distribution Panel when the bay is populated with different types of Distribution Panels.
3) Order distribution fuses, fuseholders, circuit breakers, and load lugs as required per
Distribution Devices and Lug Selection in ACCESSORY DESCRIPTIONS.
4) Order TVSS Device(s) as required per Transient Voltage Surge Suppressor (TVSS)
Device in ACCESSORY DESCRIPTIONS.
Page 13 of 75
Page 14
SAG582120600 System Application Guide
Home
Revision BK, September 27, 2017 Spec. No. 582120600 (Model 801DB NVGB)
List 116: Optional Internal Ground/Return Bar, 8-Panel Bay (Full Bay Length)
Features
Provides two full bay length internal ground/return bars (one per side).
See Load Distribution Connections under Wiring Illustrations in ACCESSORY DESCRIPTIONS for load
termination specifications.
Includes two (2) Input Lug Landing Plate Assemblies (one per side).
♦ Can be configured for top or bottom feed.
Restrictions
For use in List 105 or List 208 only.
Ordering Notes
1) Order as required.
2) Specify mounting location of included Input Lug Landing Plate Assemblies: top for top-feed or bottom
for bottom feed.
3) List 116 internal ground/return bars are rated for 1200 Amps. List 148 is available to increase that
capacity to 2400 Amps and provide additional cable landing points. Each bay can accommodate (1) List
148. List 148 offers cable termination at the rear of the bay and the option of a bonding strap. Mounting location (top or bottom) of List 148 will be opposite that specified for the Input Lug Landing Plate Assemblies of List 116.
4) Order load lugs as required per Distribution Devices and Lug Selection in ACCESSORY DESCRIPTIONS.
List 117: Optional Internal Ground/Return Bar, 8-Panel Bay (Panel Length)
Features
Replaces a Distribution Panel on the left and right side with a panel length internal
ground/return bar.
Consists of two (2) ground/return bar assemblies and two (2) blank cover panels.
For installation in top feed or bottom feed arrangements. When used in top feed
arrangements, ground bar assemblies are installed in top most left and right Distribution Panel mounting positions (appropriate blank cover panels are also installed in these positions). When used in bottom feed arrangements, ground bar assemblies are installed in bottom most left and right Distribution Panel mounting positions (appropriate blank cover panels are also installed in these positions). When an additional List 117 is ordered, these additional ground bar assemblies are installed in the adjacent Distribution Panel mounting positions (appropriate blank cover panels are supplied and installed in these positions).
See Load Distribution Connections under Wiring Illustrations in ACCESSORY
DESCRIPTIONS for load termination specifications.
See List 139 for a paralleling kit when two (2) List 117 are ordered for the same bay.
Restrictions
For use in List 108 or 208.
Ordering Notes
1) Order as required. Order two (2) List 117 for a fully configured bay. Also order one (1) List 139 Paralleling Kit if two (2)
List 117 are ordered.
2) Specify top feed or bottom feed to instruct the factory to mount the Internal Ground/Return Bars at the top or bottom of
the bay.
3) Order load lugs as required per Distribution Devices and Lug Selection in ACCESSORY DESCRIPTIONS.
Page 14 of 75
Page 15
System Application Guide SAG582120600
Home Home
Spec. No. 582120600 (Model 801DB NVGB) Revision BK, September 27, 2017
List 118: Blank Distribution Panel Cover, 8-Panel Bay
Features
Covers an unused Distribution Panel position.
Restrictions
For use in List 108 or 208.
Ordering Notes
1) Order one (1) List 118 for each position in the bay that is NOT populated with a Distribution Panel.
List 120: Distribution Panel, 6-Panel Bay
Features
Twenty (20) TLS/TPS fuse positions, or ten (10) TPL fuse positions, or a combination of
TLS/TPS and TPL fuse positions.
Includes (20) TLS/TPS Fuseholders P/N 248817100. For panels
each TPL Fuseholder P/N 516241 ordered replaces (2) P/N 248817100 Fuseholders.
See Load Distribution Connections under Wiring Illustrations in ACCESSORY DESCRIPTIONS
for load termination specifications.
Restrictions
640A maximum continuous.
For use in List 106 or List 206 only.
Ordering Notes
1) Order as required.
2) Specify twenty (20) TLS/TPS fuseholders, or up to ten (10) TPL fuseholders, or a combination
per distribution panel (all positions MUST be filled). This instructs the factory how to configure the Distribution Panel. Also specify mounting location for each configured Distribution Panel per bay. This instructs the factory where to mount each configured Distribution Panel per bay.
3) Order distribution fuses and load lugs as required per Distribution Devices and Lug Selection in
ACCESSORY DESCRIPTIONS.
4) Replacement panels will be equipped with 20 TLS/TPS Fuseholders. TPL fuseholders (P/N
516241) may be ordered to field modify the distribution panel. One TPL fuseholder takes the space of two TLS/TPS fuseholders.
configured in a bay,
Page 15 of 75
Page 16
SAG582120600 System Application Guide
Home
Revision BK, September 27, 2017 Spec. No. 582120600 (Model 801DB NVGB)
List 125: Distribution Panel, 6-Panel Bay
Features
Twenty-Eight (28) bullet nose circuit breaker and/or TLS/TPS fuse (with bullet nose
fuseholder) positions.
See Load Distribution Connections under Wiring Illustrations in ACCESSORY DESCRIPTIONS
for load termination specifications.
Restrictions
640A maximum continuous.
For use in List 106 or List 206 only.
Ordering Notes
1) Order as required.
2) Specify mounting location for each Distribution Panel per bay. This instructs the factory
where to mount each Distribution Panel when the bay is populated with different types of Distribution Panels.
3) Order distribution fuses, fuseholders, circuit breakers, and load lugs as required per
Distribution Devices and Lug Selection in ACCESSORY DESCRIPTIONS.
4) Order TVSS Device(s) as required per Transient Voltage Surge Suppressor (TVSS) Device in ACCESSORY
DESCRIPTIONS.
List 126: Optional Internal Ground/Return Bar, 6-Panel Bay (Full Bay Length)
Features
Provides two full bay length internal ground/return bars (one per side).
See Load Distribution Connections under Wiring Illustrations in ACCESSORY DESCRIPTIONS for load
termination specifications.
Includes two (2) Input Lug Landing Plate Assemblies (one per side).
♦ Can be configured for top or bottom feed.
Restrictions
For use in List 106 or List 206 only.
Ordering Notes
1) Order as required.
2) Specify mounting location of included Input Lug Landing Plate Assemblies: top for top-feed or bottom
for bottom feed.
3) List 126 internal ground/return bars are rated for 1200 Amps. List 148 is available to increase that
capacity to 2400 Amps and provide additional cable landing points. Each bay can accommodate (1) list
148. List 148 offers cable termination at the rear of the bay and the option of a bonding strap. Mounting location (top or bottom) of List 148 will be opposite that specified for the Input Lug Landing Plate Assemblies of List 126.
4) Order load lugs as required per Distribution Devices and Lug Selection in ACCESSORY DESCRIPTIONS.
Page 16 of 75
Page 17
System Application Guide SAG582120600
Home
Spec. No. 582120600 (Model 801DB NVGB) Revision BK, September 27, 2017
List 127: Optional Internal Ground/Return Bar, 6-Panel Bay (Panel Length)
Features
Replaces a Distribution Panel on the left and right side with a panel length internal
ground/return bar.
Consists of two (2) ground/return bar assemblies and two (2) blank cover panels.
For installation in top feed or bottom feed arrangements. When used in top feed
arrangements, ground bar assemblies are installed in top most left and right Distribution Panel mounting positions (appropriate blank cover panels are also installed in these positions). When used in bottom feed arrangements, ground bar assemblies are installed in bottom most left and right Distribution Panel mounting positions (appropriate blank cover panels are also installed in these positions).
See Load Distribution Connections under Wiring Illustrations in ACCESSORY
DESCRIPTIONS for load termination specifications.
Restrictions
For use in List 106 or List 206 only.
Ordering Notes
1) Order as required. Order one (1) List 127 for a fully configured bay.
2) Specify top feed or bottom feed to instruct the factory to mount the Internal Ground/Return Bars at the top or bottom of
the bay.
3) Order load lugs as required per Distribution Devices and Lug Selection in ACCESSORY DESCRIPTIONS.
List 128: Blank Distributional Panel Cover, 6-Panel Bay
Features
Covers an unused Distribution Panel position.
Restrictions
For use in List 106 or List 206 only.
Ordering Notes
1) Order one (1) List 128 for each position in the bay that is NOT populated with a Distribution Panel.
List 130: Distribution Panel Paralleling Bar
Features
Parallels two Distribution Panels mounted one above the other.
Each List 130 includes two (2) Paralleling Bars (one per side).
Restrictions
For use in Lists 106, 108, 206 and 208.
Ordering Notes
1) Order as required.
Page 17 of 75
Page 18
SAG582120600 System Application Guide
Home
Revision BK, September 27, 2017 Spec. No. 582120600 (Model 801DB NVGB)
List 139: Optional Internal Ground/Return Bar Paralleling Kit, 8-Panel Bay (Panel Length)
Features
Parallels the List 117 Internal Ground/Return Bars.
Each List 139 consists of two (2) Paralleling Bars for two sides.
Restrictions
For use with List 117 only.
Ordering Notes
1) Order one (1) List 139 if two (2) List 117 ordered for the same bay.
List 143: Bay Input Feed and Shunt Assembly (4 Cables, 25 mV. Shunts)
Provides landing points for four (4) input leads (on each side).
♦ Provides an 800A, 25mV shunt (one per side).
Can be rotated for top or bottom feed configurations.
See DC Input Connections under Wiring Illustrations in ACCESSORY DESCRIPTIONS for
input termination specifications.
Restrictions
For use in Lists 106, 108, 206 and 208.
Ordering Notes
1) Order as required. Each List 143 provides input terminations and shunts for both sides.
For top and bottom feed 2-load applications, order one (1) List 143 and specify top or bottom feed.
For top and bottom feed multi-load applications, order one (1) List 143 for each Side A/Side B load and specify top or bottom feed.
2) Order input lugs as required per DC Input Cable Sizes and Lugs Selection under Wiring
Notes in ACCESSORY DESCRIPTIONS.
List 144: Bay Input Feed and Shunt Assembly (2 Cables, 25 mV. Shunts)
Provides landing points for two (2) input leads (on each side).
♦ Provides an 800A, 25mV shunt (both sides).
Can be rotated for top or bottom feed configurations.
See DC Input Connections under Wiring Illustrations in ACCESSORY DESCRIPTIONS for
input termination specifications.
Restrictions
For use in Lists 106, 108, 206 and 208.
Ordering Notes
1) Order as required. Each List 144 provides input terminations and shunts for both sides.
For top and bottom feed 2-load applications, order one (1) List 144 and specify top or bottom feed.
For top and bottom feed multi-load applications, order one (1) List 144 for each Side A/Side B load and specify top or bottom feed.
2) Order input lugs as required per DC Input Cable Sizes and Lugs Selection under Wiring
Notes in ACCESSORY DESCRIPTIONS.
Page 18 of 75
Page 19
System Application Guide SAG582120600
Home
Spec. No. 582120600 (Model 801DB NVGB) Revision BK, September 27, 2017
List 145: Bay Input Feed and Shunt Assembly (2 Cables, 50 mV. Shunts)
Features
Provides landing points for two (2) input leads (on each side).
Provides an 800A, 50mV shunt (both sides).
Can be rotated for top or bottom feed configurations.
See DC Input Connections under Wiring Illustrations in ACCESSORY DESCRIPTIONS for
input termination specifications.
Restrictions
For use in Lists 105 and 107 only.
Ordering Notes
1) Order as required. Each List 145 provides input terminations and shunts for both sides.
For top and bottom feed 2-load applications, order one (1) List 145 and specify top or bottom feed.
For top and bottom feed multi-load applications, order one (1) List 145 for each Side A/Side B load and specify top or bottom feed.
2) Order input lugs as required per DC Input Cable Sizes and Lugs Selection under Wiring
Notes in ACCESSORY DESCRIPTIONS.
List 147: Bay Input Feed and Shunt Assembly (4 Cables, 50 mV. Shunts)
Provides landing points for four (4) input leads (on each side).
Provides an 800A, 50mV shunt (one per side).
Can be rotated for top or bottom feed configurations.
See DC Input Connections under Wiring Illustrations in ACCESSORY DESCRIPTIONS for
input termination specifications.
Restrictions
For use in Lists 105 and 107 only.
Ordering Notes
1) Order as required. Each List 147 provides input terminations and shunts for both sides.
For top and bottom feed 2-load applications, order one (1) List 147 and specify top or bottom feed.
For top and bottom feed multi-load applications, order one (1) List 147 for each Side A/Side B load and specify top or bottom feed.
2) Order input lugs as required per DC Input Cable Sizes and Lugs Selection under Wiring
Notes in ACCESSORY DESCRIPTIONS.
Page 19 of 75
Page 20
SAG582120600 System Application Guide
J1
J1
Adapter supplied with panels E/W TPL fuses
Home
Revision BK, September 27, 2017 Spec. No. 582120600 (Model 801DB NVGB)
List 148: 2400A Ground/Return Input Assembly, with Optional Bonding Strap
Features
Provides additional landing points for ground/return input
leads (both sides) to the optional List 116 or 126 Internal Ground/Return Bar.
Increases Ground/Return Bar rating from 1200A to 2400A.
Each List 148 provides two (2) Input Lug Landing Plate
Assemblies (one per side).
Included is an optional bonding strap for connecting both
Ground/Return Bars together for any current requirement up to 2400A.
Restrictions
For use with List 116 and 126 Internal Ground/Return Bars only.
Ordering Notes
1) List 116 and 126 internal return bars are rated for 1200 Amps. List 148 is available to increase that capacity to 2400 Amps
and provide additional cable landing points. Each bay can accommodate (1) List 148. List 148 offers cable termination at the rear of the bay and the option of a bonding strap. Mounting location (top or bottom) of List 148 will be opposite that specified for the Input Lug Landing Plate Assemblies of List 116 or 126.
2) Order input lugs as required per DC Input Cable Sizes and Lugs Selection under Wiring Notes in ACCESSORY
DESCRIPTIONS.
List 150: Optional Capacitor Precharge Assembly
Features
Portable hand-held unit.
Allows capacitors of a DC load to be initially
charged before a TLS/TPS or TPL distribution fuse is inserted. This prevents the fuse from possibly blowing open as it is inserted due to high capacitor charging current.
Designed to plug directly into a TLS/TPS
type fuseholder case. An adapter is supplied which plugs directly into a TPL type fuseholder case.
Restrictions
For Use with Lists 110 and 120 only.
Ordering Notes
1) Order as required.
Page 20 of 75
Page 21
System Application Guide SAG582120600
Home
Spec. No. 582120600 (Model 801DB NVGB) Revision BK, September 27, 2017
List 151: Dressing Bar
Features
Provides adjustable grooming bar to allow customer to dress output load
cables along the sides of the bay.
Restrictions
For use in Lists 106 and 108.
Ordering Notes
1) Order dressing bars as required.
2) Maximum of eight (8) dressing bars to be ordered for an eight (8) panel bay
(List 105 or 108).
3) Maximum of six (6) dressing bars to be ordered for a six (6) panel bay (List
106 and 107).
4) Additional dressing bars may be ordered when using boxframe extensions.
Maximum of four (4) additional dressing bars to be ordered when using the two foot (2’) extension.
Maximum of six (6) additional dressing bars to be ordered when using the four and one-half foot (4-1/2’) extension.
List 251: Dressing Bar
Features
Provides adjustable grooming bar to allow customer to dress output load
cables along the sides of the bay.
Restrictions
For use in Lists 206 and 208.
Ordering Notes
1) Order dressing bars as required.
2) Maximum of eight (8) dressing bars to be ordered for an eight (8) panel
bay (List 208).
3) Maximum of six (6) dressing bars to be ordered for a six (6) panel bay
(List 206).
List 153: Load Distribution Cable Management Kit
Features
Provides Twelve (12) Cable Separators (P/N 541543) plus cable ties as a ‘Method to
Manage Wiring’.
Restrictions
Not for use with List 151.
Ordering Notes
1) Order one (1) kit per bay. Order an additional kit if Box Framework Extensions are
ordered.
Page 21 of 75
Page 22
SAG582120600 System Application Guide
ESC ENT
SYSTEM OK
52.09V
1492A
A 52.09V 210A B 52.9V
Home
Home
Revision BK, September 27, 2017 Spec. No. 582120600 (Model 801DB NVGB)
List 253: Load Distribution Cable Management Kit
Features
Provides Twelve (12) Cable Separators (P/N 559799) plus cable ties as a ‘Method
to Manage Wiring’.
Restrictions
Not for use with List 251.
List 166: Meter Panel Field Upgrade Retrofit Kit
Features
Provides components to replace the standard meter panel in a List 107 bay with the
Advanced Meter/Alarm Panel.
Includes an Advanced Meter/Alarm Panel that provides the following functions for
each panel in the bay: voltage and current metering and Low Voltage, Power Lost, Overcurrent, and Fuse/Circuit Breaker alarms. Also provided are four (4) external alarm relay circuits, to which any combination of alarms can be mapped.
Provides four (4) fused auxiliary -48V power outputs (1-1/3A), fused remote (A/B)
meter panel inputs, internal/external sense option, and an Ethernet connection (requires List 170 Ethernet option).
Restrictions
Upgrades List 107 only.
Original 50mV load shunts must be replaced with 25mV shunts. Six (6) 25mV shunts (P/N 545619) are included in List 166.
Ordering Notes
1) Order one (1) List 166 to upgrade one (1) List 107.
2) For remote access capability, order one (1) List 170 Ethernet option.
3) For installation, contact Vertiv at 800-800-1280.
List 167: Pre-Installed Load Lug-Mounting Hardware
Features
Provides all required 1/4” flat washers, 1/4” lock washers and 1/4-20 hex nuts for connecting customer-
furnished lugs to all Load distribution positions in a bay.
If internal full-length ground/return bars (List 116 or 126) are ordered, List 167 will also include all required
¼” lug-mounting hardware for all Load Return positions.
Hardware is pre-installed on lug-landing studs.
Restrictions
Does
provide input lug hardware.
Does
provide lug hardware for panel length ground/return bars (List 117, 127).
Ordering Notes
1) Order one (1) List 167 to provide pre-installed hardware on all load distribution lug positions and all full-length
ground/return bar lug positions present in the bay you are ordering.
Page 22 of 75
Page 23
System Application Guide SAG582120600
ESC ENT
SYSTEM OK
52.09V
1492A
A 52.09V 210A B 52.9V
Home
Spec. No. 582120600 (Model 801DB NVGB) Revision BK, September 27, 2017
List 168: Meter Panel Field Upgrade Retrofit Kit
Features
Provides components to replace the standard meter panel in a List 105 bay with the
Advanced Meter/Alarm Panel.
Includes an Advanced Meter/Alarm Panel that provides the following functions for
each panel in the bay: voltage and current metering and Low Voltage, Power Lost, Overcurrent, and Fuse/Circuit Breaker alarms. Also provided are four (4) external alarm relay circuits, to which any combination of alarms can be mapped.
Provides four (4) fused auxiliary -48V power outputs (1-1/3A), fused remote (A/B)
meter panel inputs, internal/external sense option, and an Ethernet connection (requires List 170 Ethernet option).
Restrictions
Upgrades List 105 only.
Original 50mV load shunts must be replaced with 25mV shunts. Eight (8) 25mV shunts (P/N 545619) are included in List 168.
Ordering Notes
1) Order one (1) List 168 to upgrade one (1) List 105.
2) For remote access capability, order one (1) List 170 Ethernet option.
3) For installation, contact Vertiv at 800-800-1280.
List 170: Assembly, Ethernet
Features
Provides comprehensive remote monitoring, control, and data processing functions for a
BDFB equipped with the Advanced Meter/Alarm Panel via an Ethernet port.
Access is by means of a Web Interface.
Requires a PC equipped with an Ethernet card and Internet Explorer.
Restrictions
For use only with List 106 or 108 bays, or bays retrofitted with List 166 or 168.
Ordering Notes
1) Order as required.
Page 23 of 75
Page 24
SAG582120600 System Application Guide
Notes:
Home Home
Revision BK, September 27, 2017 Spec. No. 582120600 (Model 801DB NVGB)
For Manufactured Discontinued Bays (Model 1293V3)
FOR MANUFACTURER DISCONTINUED BAYS (MODEL 1293V3)
Distribution Bus Modules
List
Number
-- -- 8 Panel Bay
20G 58212060020G 6 Panel Bay
15 58212060015
25 58212060025 6 Panel Bay
10 58212060010
20 See Notes 6 Panel Bay
Remove the ground bar from a List 20G for a List 20 replacement.
A List 150 can be used to replace a List 50.
A List 156 can be used to replace a List 56.
Part
Number
TLS/TPS-Type Fuseholders (3-70A) e/w Internal Grounding.
8 Panel Bay Bullet Nose-Type Circuit Breakers or Bullet Nose-Type TLS/TPS
Fuseholders (1-100A), or a combination of both.
(Snap-In Blank Distribution Position Cover: P/N 387454200.)
8 Panel Bay
TLS/TPS-Type Fuseholders (3-70A)
Description
Page 24 of 75
Page 25
System Application Guide SAG582120600
To Parallel This List
W
I
T
H
This List
Order
Paralleling
Option List
Purchased
Before 6/30/00
Purchased
After 6/30/00
Purchased
Before 6/30/00
Purchased
After 6/30/00
Home
Spec. No. 582120600 (Model 801DB NVGB) Revision BK, September 27, 2017
FOR MANUFACTURER DISCONTINUED BAYS (MODEL 1293V3)
Distribution Bus Module Paralleling Options
10, 11, 12, or 14 -- 10, 11, 12, or 14 -- 30, 35
20, 21, 22, or 24 -- 20, 21, 22, or 24 -- 31, 36
15 -- 15 -- 35 or 37
25 -- 25 -- 36 or 38
-- 10, 11, 12, 14, or 15 -- 10, 11, 12, 14, or 15 35 or 37
-- 13 -- 13 35 or 37
--
-- 23 -- 23 36 or 38
15 -- -- 10, 11, 12, 14, or 15 35 or 37
25 -- --
10, 11, 12,
or 14
20, 21, 22,
or 24
10, 11, 12, or 14 -- 15 -- NONE
20, 21, 22, or 24 -- 25 -- NONE
10, 11, 12, or 14 -- -- 15 NONE
20, 21, 22, or 24 -- -- 25 NONE
20, 20G, 21, 22, 24, or
25
-- --
-- --
--
20, 20G, 21, 22, 24, or
25
20, 20G, 21, 22, 24, or
25
10, 11, 12,
or 14
20, 20G, 21, 22,
or 24
36 or 38
36 or 38
30*, 35
31*, 36
Total load for all paralleled distribution bus modules is limited to 640 amperes, maximum.
List 35 and 36 provide multiple load shunts. List 30, 31, 37, and 38 provide a single load shunt.
* Requires additional components, see Lists 30 and 31 Ordering Notes in Issue AR SAG582120600.
Page 25 of 75
Page 26
SAG582120600 System Application Guide
For
Each
of the
Following List
Numbers Ordered
Order This Kit Quantity
Kit P/N 547682
Kit P/N 547683
Home
Revision BK, September 27, 2017 Spec. No. 582120600 (Model 801DB NVGB)
ACCESSORY DESCRIPTIONS
Load Lug Hardware Kits
Features
These kits provide hardware for connecting customer-furnished Load and Load Return (internal full-length ground bar
only) lugs.
Part No. 547682 kit provides (35) each of 1/4” flat washers, 1/4” lock washers and 1/4-20 hex nuts.
Part No. 547683 kit provides (60) each of 1/4” flat washers, 1/4” lock washers and 1/4-20 hex nuts.
All hardware is shipped loose in bags.
Restrictions
Does
provide input lug hardware.
Does
Ordering Notes
1) Order as required. The table shows the quantity required for each assembly.
provide lug hardware for panel length ground/return bars (List 117, 127).
110 0 N/A
115 1 N/A
116 8 N/A
120 N/A 0
125 N/A 1
126 N/A 6
Side by Side Busbar Link Kit for Use with List 110 and List 120, P/N 556103
Features
Connects each side of a List 143 or List 144 together, side by side, in a List 106 or List 108 bay using List 120 or List 110
distribution panels. Provides two positions to terminate up to four (4) 750 MCM cables.
Restrictions
For use with List 106 with List 120 and List 108 with List 110.
Ordering Notes
1) Order P/N 556103 for List 143 or List 144 as required (see restrictions above and illustration on next page).
Side by Side Busbar Link Kit for Use with List 115 and List 125, P/N 557256
Features
Connects each side of a List 143 or List 144 together, side by side, in a List 106 or List 108 bay using List 125 or List 115
distribution panels. Provides two positions to terminate up to four (4) 750 MCM cables.
Restrictions
For use with List 106 with List 125 and List 108 with List 115.
Ordering Notes
1) Order P/N 557256 for List 143 or List 144 as required (see restrictions above and illustration on next page).
Page 26 of 75
Page 27
System Application Guide SAG582120600
Home
582120600 List 144
(List 143 Similar)
when used with List 110 and List 120
556103
582120600 List 144
(List 143 Similar)
when used with List
1
15 and List 125
557256
Hardware Build Up 3/8-16 x 1-1/4” Bolt 3/8” Flat Washer Busbar Link 3/8” Flat Washer 3/8” Lock
Washer
3/8-16 Nut
Hardware Build Up 3/8-16 x 1-1/2” Bolt 3/8” Flat W
asher Busbar Link Spacer Busbar Link 3/8” Flat W
asher 3/8” Belleville Lock Washer 3/8-16 Nut
556103
557256
Spec. No. 582120600 (Model 801DB NVGB) Revision BK, September 27, 2017
Page 27 of 75
Page 28
SAG582120600 System Application Guide
Home
5821206
00 List 115
(som
e components
not shown for c
larity only)
5821206
00 List 115
P/N 55
637
7
Righ
t Angle
Lug
Adap
ter Ki
t
P
/N 55
6377 Right Angle Lug Adapter Kit
P/N 55637
8
Righ
t Ang
le
Lug Adapter Kit
P
/N 55
6378 Right Angle L
ug A
dapte
r Kit
re
ar rear
Revision BK, September 27, 2017 Spec. No. 582120600 (Model 801DB NVGB)
Right Angle Lug Adaptor Kits, P/Ns 556377 and 556378
Features
These kits allow for load connections to the List 115, 116, 125, and 126 panels at right angle to the standard connection
and also allows for use of up to 4/0 AWG wire. The lug adapters are designed for use with 2-hole lugs with 3/8” clearance holes on 1” centers. The lug adapters permit installation of cables back to back.
Part No. 556377 provides one (1) busbar P/N 555918, six (6) 1/4” flat washers P/N 214110100, six (6) 1/4” split lock
washers P/N 215111100, and six (6) 1/4-20 hex nuts P/N 228557100.
Part No.556378 provides one (1) busbar P/N 555919, six (6) 1/4” flat washers P/N 214110100, six (6) 1/4” split lock washers
P/N 215111100, and six (6) 1/4-20 hex nuts P/N 228557100.
Restrictions
For use with lists 115,116,125 and 126.
For use with three-pole circuit breaker or 3-pole ground/return only.
Ordering Notes
1) Order as required. Refer to the following table.
Application for
Right Angle Adaptors
Left Side
(viewed from rear)
Right Side
(viewed from rear)
Top Feed Application P/N 556378 P/N 556377
Bottom Feed Application P/N 556377 P/N 556378
Page 28 of 75
Page 29
System Application Guide SAG582120600
Home
Spec. No. 582120600 (Model 801DB NVGB) Revision BK, September 27, 2017
External Return/Ground Bar Assemblies
Return/Ground Bar Assemblies
8 Panel Bay Return/Ground Bar Assembly 436110200
6 Panel Bay Return/Ground Bar Assembly 436110300
Bonding Strap Kit 534834
Ordering Notes
1) Order Return/Ground Bar Assembly(s) as required. One (1) per bay provides landing positions for each fuse position in
the bay assuming that cables are terminated back to back. If individual termination is required, order two (2) per bay.
2) Order Bonding Strap Kit as required. Bonding Strap Kit includes one strap (P/N 351532900) plus hardware.
3) Order input return lugs (two hole, 1/4" bolt clearance hole, 0.625" centers; or two hole, 3/8" bolt clearance hole, 1" centers)
as required.
Page 29 of 75
Page 30
SAG582120600 System Application Guide
Home Home
Revision BK, September 27, 2017 Spec. No. 582120600 (Model 801DB NVGB)
Seismic Anchor Kit, P/N 545387
Features
Provides four (4) Relay Rack Seismic Mounting Anchors, P/N 216821200.
Restrictions
For use with Lists 105, 106, 107 and 108.
Ordering Notes
1) Order Seismic Anchor Kit P/N 545387 as required.
Transient Voltage Surge Suppressor (TVSS) Device
Features
When properly grounded, the device(s) suppresses transient voltages that are above 60 VDC.
Contains an indicator which lights when circuit has activated to suppress voltages.
Plugs into distribution device mounting positions of a List 115 and List 125 Distribution Panel.
Restrictions
To be used with Distribution Panels List 115 and List 125 only.
All unparalleled Distribution Panels require a TVSS Device, only one (1) TVSS Device required per paralleled groups of Distribution Panels.
Unless otherwise specified, install the TVSS Device in the mounting position closest to the Distribution Panel’s input busbar.
Wire to be sized so that the maximum wire resistance is less than 0.550 milliohms.
Ordering Notes
1) Order kit P/N 520401 (includes TVSS Device P/N 122201 plus lug mounting hardware) as required. Customer to supply
grounding lead(s) with lugs to connect from TVSS Device(s) into customer's grounding network.
Page 30 of 75
Page 31
System Application Guide SAG582120600
TLS/TPS Fuse
Fuseblock
(P/N 248817100)
Fuse Case
GMT-18/100A Alarm Fuse (P/N 248610301) and GMT-X Safety Fuse Cover (P/N 248898700) (Both ordered separately)
Lists 110 and 120 TLS/TPS Fuseblock
1/4 -20 swage studs for installation of customer provided single hole lugs
Max. Lug Width 0.750". Max. Wire Size 2 AWG.
Home
Spec. No. 582120600 (Model 801DB NVGB) Revision BK, September 27, 2017
Distribution Devices and Lug Selection
TLS/TPS Fuses/Fuseblocks, TPL Fuses/Fuseblocks, and Lug Selection for Lists 110 and 120
Features
Each fuse installs into the respective fuseblock.
Restrictions
The fuses and fuseblocks specified in this section are for use in Lists 110 and 120.
Load should not exceed 80% of device rating.
Distribution Panel capacity is 640A maximum continuous.
TLS/TPS Fuseblock: Maximum lug width is 0.750”. Maximum wire size is 2 AWG.
TPL Fuseblock: Maximum lug width is 1.8”. Maximum wire size is 2/0 AWG.
Ordering Notes
1) A List 110 has twelve (12) fuse positions and a List 120 has twenty (20) fuse positions. The fuse panel can be populated
with TLS/TPS fuseblocks (requires one [1] fuse position), TPL fuseblocks (requires two [2] fuse positions), or a combination of TLS/TPS and TPL fuseblocks.
List 110 includes (12) TLS/TPS Fuseblocks P/N 248817100, and List 120 includes (20) TLS/TPS Fuseblocks P/N
248817100. For panels Fuseblocks. For fuse panels shipped separately, the TLS/TPS fuseblocks are factory installed and if TPL fuseblocks are required they will have to be installed in the field.
Order fuses and fuseblocks as required per Table 1 and Table 3.
For each TLS/TPS fuseblock ordered, also order one (1) P/N 248610301 alarm fuse and one (1) P/N 248898700 safety fuse cover. The alarm fuse and safety fuse cover is provided with a TPL fuseblock.
2) See Table 2 and Table 4 for recommended load lugs.
3) See Table 8 and Table 9 for recommended load distribution wire sizes.
configured in a bay, each TPL Fuseblock P/N 516241 ordered replaces (2) P/N 248817100
Page 31 of 75
Page 32
SAG582120600 System Application Guide
Home
Revision BK, September 27, 2017 Spec. No. 582120600 (Model 801DB NVGB)
TLS/TPS Fuses and Fuseblocks
for Use in Lists 110 and 120
Ampere
Rating
3 248230900 TPS-3 TLS003
5 248231000 TPS-5 TLS005
6 248231200 TPS-6 TLS006
10 248231500 TPS-10 TLS010
15 248231800 TPS-15 TLS015
20 248232100 TPS-20 TLS020
25 248232400 TPS-25 TLS025
30 248232700 TPS-30 TLS030
40 248233300 TPS-40 TLS040
50 248233900 TPS-50 TLS050
60 248234200 TPS-60 TLS060
70 248234500 TPS-70 TLS070
Each fuse requires (1) Fuseblock P/N 248817100. See “Ordering Notes” in this section.
For each fuseblock ordered, also order... (1) P/N 248610301 alarm fuse (GMT-18/100A), and (1) P/N 248898700 safety fuse cover (GMT-X).
See Table 8 for recommended load distribution wire sizes.
P/N
Bussmann
P/N
Table 1
TLS/TPS Fuses and Fuseblocks
for Use in Lists 110 and 120
Littelfuse
P/N
Lugs for Fuseblock P/N
248817100
See Table 2
Lugs for Use with Fuseblock P/N 248817100
Used in Lists 110 and 120 Distribution Panels
(single hole, 1/4” bolt clearance hole)
Lead Size (AWG) P/N
8 245350400
6 245350600
4 245350700
2 245350800
Note: Cables larger than 2 AWG require an H-TAP connection.
Table 2
Lugs for Use with Fuseblock P/N 248817100
Used in Lists 110 and 120
Page 32 of 75
Page 33
System Application Guide SAG582120600
Fuse Case
Open Fuse Case View
TPL Fuse
Fuse Installed in
Open Fuse Case
Fuse Installed in
Closed Fuse Case
Lists 110 and 120 TPL Fuseblock
5/16-18 swage studs for installation of customer provided single hole lugs.
Max. Lug Width 1.8". Max. Wire Size 2/0 AWG.
Fuseblock
(P/N 516241)
GMT-18/100A Alarm Fuse (P/N 248610301) and GMT-X Safety Fuse Cover (P/N 248898700) (Both are provided w/ fuseblock)
Home
Spec. No. 582120600 (Model 801DB NVGB) Revision BK, September 27, 2017
Page 33 of 75
Page 34
SAG582120600 System Application Guide
Home
Revision BK, September 27, 2017 Spec. No. 582120600 (Model 801DB NVGB)
TPL Fuses and Fuseblock
for Use in Lists 110 and 120
Required
Ampere
Rating
70 2 248251500
80 2 248252000
100 2 248252600
150 2 248253300
200 2 248254000
225 2 248254500
250 2 248255000
Each fuse requires (1) Fuseblock P/N 516241. See “Ordering Notes” in this section.
Fuseblock P/N 516241 also includes... (1) P/N 248610301 alarm fuse (GMT-18/100A), and (1) P/N 248898700 safety fuse cover (GMT-X).
See Table 9 for recommended load distribution wire sizes.
Distribution
Bus Mounting
Positions
TPL Fuses and Fuseblock
for Use in Lists 110 and 120 Distribution Panels
P/N
Table 3
Lugs for Fuseblock P/N
516241
See Table 4
Lugs for Use with Fuseblock P/N 516241
Used in Lists 110 and 120 Distribution Panels
(single hole, 5/16” bolt clearance hole)
Lead Size (AWG) P/N
6 245351380
4 245351390
2 245351400
1 120224
Note: Cables larger than 2/0 AWG require an H-TAP connection.
Table 4
Lugs for Use with Fuseblock P/N 516241
Used in Lists 110 and 120 Distribution Panels
Page 34 of 75
Page 35
System Application Guide SAG582120600
Home
Spec. No. 582120600 (Model 801DB NVGB) Revision BK, September 27, 2017
Bullet Nose-Type Circuit Breakers, Bullet Nose-Type Fuseblocks e/w TLS/TPS Fuses, and Lug Selection for Lists 115 and 125
Features
Each circuit breaker plugs into one, two or three distribution device mounting position(s).
A single fuseblock provides for installation of a 3 to 125 ampere Bussmann TPS-type or Littelfuse TLS-type fuse. The
fuseblock plugs into a single distribution device mounting position. The fuseblock provides a GMT-A alarm type fuse, which operates open to provide an alarm indication if the distribution fuse opens.
Restrictions
The circuit breakers, fuses, and fuseblocks specified in this section are for use in Lists 115 and 125.
Load should not exceed 80% of device rating.
Distribution Panel capacity is 640A maximum continuous.
Maximum lug width is 0.610”. Maximum wire size is 2 AWG.
Ordering Notes
1) Order circuit breakers per Table 5.
Order fuses per Table 6.
For each fuse ordered, also order one (1) P/N 117201 bullet nose fuseblock.
Fuseblock P/N 117201 also includes...
(1) Alarm Fuse P/N 248610301 and (1) Safety Fuse Cover P/N 248898700.
2) See Table 7 for recommended load lugs.
3) See Table 8 for recommended load distribution wire sizes.
Page 35 of 75
Page 36
SAG582120600 System Application Guide
Toggle-Handle Bullet Nose Circ
u
i
t
B
r
e
a
k
e
r
B
u
ll
e
t N
os
e
Fu
se
h
ol
de
r
, P
/N 117201
(i
nc
l
ud
es
F
us
eholder, Alarm F
us
e,
a
n
d A
la
r
m F
use Safety Cover
)
A
la
rm Fuse
R
eplacement
P/
N 248
610
301
S
afe
ty Fu
se Co
ver
Rep
lacem
ent
P
/N 2
488987
00
T
P
S/
TL
S
F
use
Bullet Nose F
us
e
ho
l
de
r
B
u
l
l
e
t
Nose-Type Distribut
i
o
n
D
e
v
i
c
e
s
f
o
r
L
i
s
t
s
1
1
5
a
n
d
1
2
5
Home
Revision BK, September 27, 2017 Spec. No. 582120600 (Model 801DB NVGB)
Page 36 of 75
Page 37
System Application Guide SAG582120600
Caution
Caution
Caution
Caution
545346 or
Caution
Spec. No. 582120600 (Model 801DB NVGB) Revision BK, September 27, 2017
Toggle-Handle Bullet Nose Type Circuit Breakers
for Use in Lists 115 and 125
P/N
Ampere
Rating
Number of Poles
(and mounting
positions required)
Electrical
1
Trip
(White
Handle)
Electrical/
Mechanical
Trip
2
(Black Handle)
Lugs
1 1 102272 101596
3 1 102273 101597
5 1 102274 101598
10 1 102275 101599
15 1 102276 101600
20 1 102277 101601
25 1 102278 101602
30 1 102279 101603
35 1 102280 101604
40 1 102281 101605
45 1 121998 121997
Up to 2 AWG lead sizes, use lugs in
Table 7 (1/4” clearance holes on 5/8”
centers.
From 1/0 to 350 kcmil lead sizes, use
lugs in Table 7 (Special Crimp Lug).
50 1 102282 101606
60 1 102283 101607
70 1 102284 101608
75 1 102285 101609
80 1 121996 121995
90 1 138887 138888
100 1 102286 101610
125 2 516991 516838
(see
(see
(see
(see
(see
150
below)
175
below)
200
below)
225
below)
250
below)
2 516993 516839
2 144883 144884
2 121831 121832
3 144885 144886
3 121835 121836
Use lugs in Table 7
(Special Crimp Lug).
Use lugs in Table 7 (Special Crimp
Lug) plus special lug adapter P/N
lug adapters listed in Table
7.
See Table 8 for recommended load distribution wire sizes.
Circuit Breaker Alarm Operation:
1
Provides an alarm during an electrical trip condition only.
2
Provides an alarm during an electrical or manual trip condition.
Caution: An overcurrent protective device with a rating of 150 amperes or greater SHALL HAVE an empty
mounting position between it and any other overcurrent protective device.
Table 5
Toggle-Handle Bullet Nose Type Circuit Breakers
for Use in Lists 115 and 125
Page 37 of 75
Page 38
SAG582120600 System Application Guide
Home
Revision BK, September 27, 2017 Spec. No. 582120600 (Model 801DB NVGB)
Bullet Nose-Type Fuseblocks and TLS/TPS Fuses
for Use in Lists 115 and 125
Ampere
Rating
3 248230900 TPS-3 TLS003
5 248231000 TPS-5 TLS005
6 248231200 TPS-6 TLS006
10 248231500 TPS-10 TLS010
15 248231800 TPS-15 TLS015
20 248232100 TPS-20 TLS020
25 248232400 TPS-25 TLS025
30 248232700 TPS-30 TLS030
40 248233300 TPS-40 TLS040
50 248233900 TPS-50 TLS050
60 248234200 TPS-60 TLS060
70 248234500 TPS-70 TLS070
80 118413 -- TLS080
90 118414 -- TLS090
100 118415 -- TLS100
125 139052 -- TLS125
For each fuse ordered, also order a Bullet Nose Fuseblock P/N 117201. Fuseblock P/N 117201 also includes...
(1) P/N 248610301 alarm fuse (GMT-18/100A), and (1) P/N 248898700 safety fuse cover (GMT-X).
See Table 8 for recommended load distribution wire sizes.
P/N
Bussmann
P/N
Littelfuse
P/N
Lugs
Up to 2 AWG lead sizes, use lugs in
Table 7 (1/4” clearance holes on 5/8”
centers.
From 1/0 to 350 kcmil lead sizes, use
lugs in Table 7 (Special Crimp Lug).
Table 6
Bullet Nose-Type Fuseblocks and TLS/TPS Fuses
for Use in Lists 115 and 125
Page 38 of 75
Page 39
System Application Guide SAG582120600
Lugs for Use with P/Ns 547991, 556377, and 556378 Lug Adapter Kits
(two hole, 3/8” bolt clearance holes on 1” centers)
Wire Size
Part Number
either
or
Home
Spec. No. 582120600 (Model 801DB NVGB) Revision BK, September 27, 2017
Lugs for Use with Lists 115 and 125 Distribution Panels
(two hole, 1/4” bolt clearance hole on 5/8” centers)
Lead Size (AWG) P/N
8 245390200
6 245346700
4 245346800
2 245346900
1/0 245393500 (special lug)
2/0 245393600 (special lug)
3/0 245393700 (special lug)
4/0 245393800 (special lug)
250 kcmil 514872 (special lug)
350 kcmil 514873 (special lug)
3-Pole Device Special Adapter 545346
6 AWG 245349900
4 AWG 245350000
2 AWG 245348200
1/0 AWG 245347100
2/0 AWG 245347200
3/0 AWG 245347300
4/0 AWG 245347400
250 kcmil 245347500
300 kcmil 245347600
350 kcmil 245347700
400 kcmil 245347800
500 kcmil 245347900
600 kcmil 245348000
750 kcmil 245348100
For one-pole circuit breaker, cables larger than 2 AWG require an H-TAP connection. For two-pole circuit breaker, use special lugs per table. For three-pole circuit breaker and 3-pole ground/return, use
adapter P/N 545346,
adapter kit P/N 547991, 556377, or 556378 with 2-hole lugs having 3/8”
special lugs per table with
clearance holes on 1” centers. For fuseblock (P/N 117201), cables larger than 2 AWG require H-tap. Special lugs listed above can
be used but will use two positions of the distribution panel.
Table 7
Lugs for Use with Lists 115 and 125 Distribution Panels
Page 39 of 75
Page 40
SAG582120600 System Application Guide
Special Lugs and Adapters Referenced in Table 7
Home
Revision BK, September 27, 2017 Spec. No. 582120600 (Model 801DB NVGB)
Special Lug
(See Table 7 for
Part Numbers)
Special Adapter P/N 545346
Special Lug and Adapter
3-Pole Lug Adapter Kit, P/N 547991
Right Angle
Lug Adapter Kit, P/N 556377
Right Angle
Lug Adapter Kit, P/N 556378
Page 40 of 75
Page 41
System Application Guide SAG582120600
Home
Spec. No. 582120600 (Model 801DB NVGB) Revision BK, September 27, 2017
Box Framework Extensions
One (1) Foot Box Framework Extension
Features
The 1 Foot Box Framework Extension allows a standard 7 foot box framework to
extend to 8 feet.
Restrictions
For use in Lists 105 106, 107 and 108.
Ordering Notes
1) Order as required, P/N 544201.
Two (2) Foot Box Framework Extension
Features
The 2 Foot Box Framework Extension allows a standard 7 foot box framework to
extend to 9 feet.
Restrictions
For use in Lists 105 106, 107 and 108.
Ordering Notes
1) Order as required, P/N 544202.
Four and One-Half (4-1/2) Foot Box Framework Extension
Features
The 4-1/2 Foot Box Framework Extension allows a standard 7 foot box framework to
extend to 11-1/2 feet.
Restrictions
For use in Lists 105 106, 107 and 108.
Ordering Notes
1) Order as required, P/N 544203.
Page 41 of 75
Page 42
SAG582120600 System Application Guide
Home
Revision BK, September 27, 2017 Spec. No. 582120600 (Model 801DB NVGB)
Wiring Notes
Refer also to the next section, Wiring Illustrations.
Bay Frame Grounding Wire Sizes and Lugs Selection
Features
1/4” clearance holes on 5/8" centers are provided for installation of customer provided two-hole lugs.
Restrictions
All lugs for customer connections must be ordered separately.
Customer needs to supply lug mounting bolts and hardware.
Ordering Notes
1) The recommended frame grounding wire size is 6 AWG. The recommended lug is P/N 245346700.
External Alarm Wiring—List 105 and 107 Bays
Features
An external alarm circuit card is located behind the top left panel in each bay. This circuit card provides three sets of
Form C relay contacts for external alarms. Terminal blocks are provided on the circuit card for customer external alarm connections and RS485 connections.
Restrictions
Relay contacts are rated for 1 amp at 60 VDC.
Terminal block wire size capacity is 14 to 26 AWG.
Ordering Notes
1) Recommended Wire Size: 22 AWG for Loop Lengths Up to 200 ft.
18-20 AWG for Loop Lengths Over 200 ft.
External Alarm and Control Wiring—List 106, 206, 108 and 208 Bays
Input/Output Circuit Card Features
An input/output circuit card is located behind the top left panel in each bay. This circuit card provides four alarm relays,
each with one set of Form C relay contacts, for external alarms. Terminal blocks are provided on the circuit card for customer external alarm connections.
Restrictions
Relay contacts are rated for 0.6 amp at 60 VDC.
Terminal block wire size capacity is 14 AWG max.
Ordering Notes
1) Recommended Wire Size: 22 AWG for Loop Lengths Up to 200 ft.
18-20 AWG for Loop Lengths Over 200 ft.
Auxiliary Fuse Circuit Card Features
An auxiliary fuse circuit card is located behind the top right panel in each bay. This circuit card provides four fuses for
auxiliary equipment loads and two fuses for optional external (ABS) power to the Meter/Alarm Panel. All fuses are rated at 1-1/3A. Terminal blocks are provided on the circuit card for auxiliary load connections, external (ABS) meter input power connections, and optional external sense lead connections.
Restrictions
Terminal block wire size capacity is 14 AWG max.
Installer must make system ground/return connection(s) to side A and side B Ground/Return Input busbars located behind circuit card.
Ordering Notes
1) Recommended Wire Size (Auxiliary Fuse load and return): 14 AWG
2) Recommended Wire Size (Ground/Return Input busbars): 14 AWG
Page 42 of 75
Page 43
System Application Guide SAG582120600
Home
Spec. No. 582120600 (Model 801DB NVGB) Revision BK, September 27, 2017
Load Distribution Wire Sizes Selection
Features
Load distribution (load side) leads terminated in the appropriate lug are connected to the ‘load side’ terminations
provided on each Distribution Panel. See Load Distribution Connections under Wiring Illustrations in ACCESSORY DESCRIPTIONS.
Load distribution (return side) leads terminated in the appropriate lug are connected to the ‘load return side’
terminations provided on the optional internal ground/return bars or to external ground/return bars. See Load
Distribution Connections under Wiring Illustrations in ACCESSORY DESCRIPTIONS.
Restrictions
The rating of the distribution device determines the wire size requirements. Refer to the American National Standards Institute (ANSI) approved National Fire Protection Association's (NFPA) National Electrical Code (NEC) and applicable local codes.
All lugs for customer connections must be ordered separately.
Customer needs to supply lug mounting bolts and hardware.
Maximum size of wire to be connected to a single lug position and maximum lug width are listed under Distribution Devices
and Lug Selection in ACCESSORY DESCRIPTIONS.
Ordering Notes
1) The type of distribution device determines the load lug hole size and spacing requirements. The rating of the
distribution device determines the wire size requirements. For wire size and lug selection; refer to Distribution Devices
and Lug Selection in ACCESSORY DESCRIPTIONS and Table 8 and Table 9.
Page 43 of 75
Page 44
SAG582120600 System Application Guide
(3, 4)
(3, 4)
(3, 4) (3, 4)
(3, 4)
(3, 4)
(3, 4)
(3, 4)
(3, 4)
(3, 4)
(3, 4)
(3, 4)
(3, 4)
(3, 4)
(3, 4)
(3, 4)
(3, 4)
(3, 4)
(3, 4)
(3, 4)
(3, 4)
(3, 4)
(3, 4)
(3, 4)
(3, 4)
(3, 4)
(3, 4)
(3, 4)
(3, 4)
(3, 4)
(3)
(3, 4)
(3, 4)
(3)
(3, 4)
(3, 4)
(3, 4)
(3, 4)
(3)
(3, 4)
(3, 4)
Home
Revision BK, September 27, 2017 Spec. No. 582120600 (Model 801DB NVGB)
Recm 90°C Wire Size
(1)
Fuse/Circuit
Breaker
Amperage
14 AWG 12 AWG 10 AWG 8 AWG 6 AWG 4 AWG 2 AWG
Loop Length (feet)
(2)
1, 3, 5,
6, 10A
15A 24
20A -- 29
25A -- -- 37
30A -- -- 31
35A -- -- -- 42
40A -- -- -- 37
45A -- -- -- 33
50A -- -- -- 29
60A -- -- -- -- 39
70A -- -- -- -- 33
75A -- -- -- -- 31
80A -- -- -- -- -- 47
90A -- -- -- -- -- 41
37
58
39
93
62
46
-- -- -- --
-- -- -- --
74
59
49
-- -- --
94
78
67
59
52
47
-- --
-- --
107
94
83
75
62
53
50
--
--
--
--
99
85
79
74
66
100A -- -- -- -- -- -- 59
Wire sizes based on recommendations of the American National Standards Institute (ANSI) approved National Fire
Protection Association's (NFPA) National Electrical Code (NEC). Table 310-16 for copper wire at
and
temperature operating in ambients of
was used. For other operating ambient temperatures, refer to the
conductor
NEC. For operation in countries where the NEC is not recognized, follow applicable codes.
Recommended wire sizes are sufficient to restrict voltage drop to 1.0 volt or less at listed branch current for the loop
lengths shown. Loop length is the sum of the lengths of the positive and negative leads.
Wire Size / Loop Length Combination Calculated using 30°C Ambient Operating Temperature.
Wire Size / Loop Length Combination Calculated using 40°C Ambient Operating Temperature.
Table 8
(cont'd on next page)
Recommended Load Distribution Wire Sizes for
and
Page 44 of 75
Page 45
System Application Guide SAG582120600
(3)
(3, 4)
(3, 4)
(4)
(3, 4)
(3, 4)
(3, 4)
(3)
(3, 4)
(3, 4)
(4)
(3, 4)
(3, 4)
(3, 4)
(3, 4)
(3, 4)
(3, 4)
(3, 4)
(3, 4)
(3, 4)
(3)
(3, 4)
(3, 4)
(3, 4, 7)
(3, 4, 7)
(3, 4, 7)
Home
Spec. No. 582120600 (Model 801DB NVGB) Revision BK, September 27, 2017
(1)
Fuse/
Circuit
Breaker
Amperage
Recm 90°C Wire Size
4 AWG 2 AWG 1/0 AWG 2/0 AWG 3/0 AWG 4/0 AWG 250 kcmil 350 kcmil
Loop Length (feet)
(2)
90A 41
100A -- 59
125A -- 47
150A -- -- 63
175A -- -- -- 68
200A -- -- -- -- 75
225A -- -- -- -- 67
250A -- -- -- -- -- 76
Wire sizes based on recommendations of the American National Standards Institute (ANSI) approved National Fire
Protection Association's (NFPA) National Electrical Code (NEC). Table 310-16 for copper wire at temperature operating in ambients of
66
105
95
76
and
133
119
95
79
was used. For other operating ambient temperatures, refer to the
-- -- -- --
-- -- -- --
120
100
86
-- -- --
-- -- --
108
95
84
-- --
112
100
90
--
--
126
conductor
NEC. For operation in countries where the NEC is not recognized, follow applicable codes.
Recommended wire sizes are sufficient to restrict voltage drop to 1.0 volt or less at listed branch current for the loop
lengths shown. Loop length is the sum of the lengths of the positive and negative leads.
Wire Size / Loop Length Combination Calculated using 30°C Ambient Operating Temperature.
Wire Size / Loop Length Combination Calculated using 40°C Ambient Operating Temperature.
Table 8
(cont'd from previous page)
Recommended Load Distribution Wire Sizes for
and
Page 45 of 75
Page 46
SAG582120600 System Application Guide
(3)
(3, 4)
(3, 4)
(3, 4)
(3, 4)
(3, 4)
(3, 4)
(3, 4)
(3, 4)
(3, 4)
(3, 4)
(3, 4)
(3, 4)
(3, 4)
(3, 4)
(3, 4)
(3, 4)
(3, 4)
(3, 4)
(3, 4)
(3, 4)
(3, 4)
Home
Revision BK, September 27, 2017 Spec. No. 582120600 (Model 801DB NVGB)
(1)
Fuse/
Circuit
Breaker
Amperage
Recm 90°C Wire Size
6 AWG 4 AWG 2 AWG 1/0 AWG 2/0 AWG 3/0 AWG 4/0 AWG
Loop Length (feet)
250
kcmil
(2)
300
kcmil
350
kcmil
70A 33
80A -- 47
100A -- -- 59
150A -- -- -- 63
200A -- -- -- -- -- 75
225A -- -- -- -- -- 67
250A -- -- -- -- -- -- 76
Wire sizes based on recommendations of the American National Standards Institute (ANSI) approved National Fire Protection Association's (NFPA) National Electrical Code (NEC). Table 310-16 for copper wire at
temperature operating in ambients of
53
85
74
135
118
95
-- -- -- -- -- --
-- -- -- -- -- --
119
79
-- -- -- -- --
100
-- -- -- --
95
(3)
84
112
100
(3)
90
-- --
120
108
and
was used. For other operating ambient temperatures, refer to the
National Electrical Code. For operation in countries where the NEC is not recognized, follow applicable codes.
Recommended wire sizes are sufficient to restrict voltage drop to 1.0 volt or less at listed branch current for the loop lengths shown. Loop length is the sum of the lengths of the positive and negative leads.
Wire Size / Loop Length Combination Calculated using 30°C Ambient Operating Temperature.
Wire Size / Loop Length Combination Calculated using 40°C Ambient Operating Temperature.
Single-hole lug, 5/16" bolt clearance hole. Lugs should be crimped per lug manufacturer’s specifications.
Table 9
Recommended Load Distribution Wire Sizes for
conductor
--
126
Page 46 of 75
Page 47
System Application Guide SAG582120600
Home
Spec. No. 582120600 (Model 801DB NVGB) Revision BK, September 27, 2017
DC Input Cable Sizes and Lugs Selection
Features
DC input (-48V) leads terminated in the appropriate lug are connected to the List 145 Bay Input Feed and Shunt
Assembly. See DC Input Connections under Wiring Illustrations in ACCESSORY DESCRIPTIONS.
DC input return leads terminated in the appropriate lug are connected to the optional internal ground/return bars or to
external ground/return bars. See DC Input Connections under Wiring Illustrations in ACCESSORY DESCRIPTIONS.
Restrictions
All lugs for customer connections must be ordered separately.
Customer needs to supply lug mounting bolts and hardware.
Maximum size of wire to be connected to a single lug position and maximum lug width are as shown in the Wiring Illustrations.
Ordering Notes
1) DC input cable size varies depending on power requirements, therefore no specific information is provided for cable size.
Refer to Table 10 for recommended cable sizes and lugs at rated maximum bay load (640A per Distribution Panel, 1800A per Side 6-Panel Bay, 2400A per Side 8-Panel Bay). Note that loads typically should not exceed 80% of capacity; therefore, input cables have been sized for an overcurrent protection device rated at 800A. When making connections, observe correct polarity.
External
Overcurrent
Protection Device
Rating
Ambient
Operating
Temperature
Loop
Length (Ft)
1.0 Voltage Drop
(2)
(1)
Loop
Length (Ft)
0.25 Voltage Drop
(2)
Recm 90°C
Wire Size
(AWG)
(1)
Recommended
Crimp Lug
(3)
800A 40°C
Wire sizes are based on recommendations of the American National Standards Institute (ANSI) approved
National Fire Protection Association's (NFPA) National Electrical Code (NEC). rated at
conductor temperature operating in ambient temperature of
84.5 21.1 750 kcmil
168.9 42.2 (2) 750 kcmil
was used. For other operating
245348100
for copper wire
ambient temperatures, refer to the NEC. For operation in countries where the NEC is not recognized, follow applicable codes.
Recommended wire sizes are sufficient to restrict voltage drop to the voltage shown in the column heading, or
less, at rated full load output current of the system for the loop lengths shown in this column. Loop length is the sum of the lengths of the positive and negative leads.
Two-hole lug, 3/8 bolt clearance hole, 1.00" centers. Lugs should be crimped per lug manufacturer’s
specifications.
Table 10
Recommended DC Input
Wire Size and Lug Selection
Page 47 of 75
Page 48
SAG582120600 System Application Guide
Home
Revision BK, September 27, 2017 Spec. No. 582120600 (Model 801DB NVGB)
Wiring Illustrations
Overall Installer’s Connections
Page 48 of 75
Page 49
System Application Guide SAG582120600
Home
Spec. No. 582120600 (Model 801DB NVGB) Revision BK, September 27, 2017
Bay Frame Grounding Connection
Page 49 of 75
Page 50
SAG582120600 System Application Guide
Home
Revision BK, September 27, 2017 Spec. No. 582120600 (Model 801DB NVGB)
External Alarm and Meter/Alarm Card Input Connections
Page 50 of 75
Page 51
System Application Guide SAG582120600
List 156 Internal Fuse Kit (Connect end with spade lug to terminal 3 or 4 of TB1, connect end with faston connector to lug factory-installed on an Input Feed and Shunt Assembly [-48V Source, see Detail A].) (one or two kits as ordered)
Connect faston connector
end of Internal Fuse Kit
to one of these lugs.
Input Feed and Shunt Assembly
-48V Input - B Feed (for digital meter and alarm circuit card power input) Connect to an external source or to List 156 Internal Fuse Kit, if Feed B req
uired.
-48V Input - A Feed (for digital meter and alarm circuit card power input) Connect to an external source or to List 156 Internal Fuse Kit.
Internal/External “Ground/Return”
(for digital meter and alarm
circuit card power return)
Connect as required.
Access Door Removed
Home
Spec. No. 582120600 (Model 801DB NVGB) Revision BK, September 27, 2017
Page 51 of 75
Page 52
SAG582120600 System Application Guide
Home
Revision BK, September 27, 2017 Spec. No. 582120600 (Model 801DB NVGB)
Page 52 of 75
Page 53
System Application Guide SAG582120600
Home
Spec. No. 582120600 (Model 801DB NVGB) Revision BK, September 27, 2017
Page 53 of 75
Page 54
SAG582120600 System Application Guide
Home
Revision BK, September 27, 2017 Spec. No. 582120600 (Model 801DB NVGB)
Page 54 of 75
Page 55
System Application Guide SAG582120600
Por
tion of bay remov
ed
in illustration for c
larity.
SE
E NE
XT P
AGE I
F TVSS DEVICE IS INS
TAL
LED
IN BULLET
DEVICE M
OUN
TIN
G
BLOCK
-48V Loa
d Con
nec
tio
ns
Loa
d Re
turn
Con
nec
tio
ns
to Optional In
ter
nal
Gro
und
/Ret
urn Busbar
or Cu
sto
mer
Prov
ide
d
External Busb
ar.
-48V L
oad
Con
nec
tion
s
Lo
ad Re
tur
n Co
nnec
tions
to Optional I
nte
rna
l
Gr
oun
d/Re
turn Busbar
or Cu
sto
mer
Prov
ide
d
External Busbar.
Optional Internal
G
ro
u
nd/Return Busbar
(B
ay
L
en
gt
h
, s
ho
w
n)
o
r O
p
ti
on
a
l I
nt
e
rn
al
Ground/Re
t
ur
n B
u
sb
a
r
(Panel Length, see next pages)
or Customer Provided
E
x
te
r
na
l Busbar
Optional Internal G
ro
u
nd
/R
e
turn Busbar
(B
ay
L
en
gt
h
, s
h
ow
n)
or
O
pt
io
n
al
In
t
er
n
al
Ground/Return B
us
b
ar
(Panel Length, see next pages
)
o
r C
ustomer Provided
Ex
t
er
na
l
Bu
sb
a
r
SEE N
EXT
PAG
E IF
TVSS DEVICE I
S
IN
STAL
LED
IN BULLET
DEVICE MO
UNT
ING
BLOCK
Rear View
8-Pane
l Bay
(6-Panel Bay Similar)
Home
Spec. No. 582120600 (Model 801DB NVGB) Revision BK, September 27, 2017
Load Distribution Connections—Lists 106, 108, 206, 208
Page 55 of 75
Page 56
SAG582120600 System Application Guide
5/16-18
s
wage studs
for installation of customer
provided single hole lugs.
(Torq
ue
t
o 132 in-lbs.)
(Maximum Lug Width is 1.800”.)
(Maximum Wire Size is 2/0 AWG.)
1/4-20 swage studs fo
r i
n
stallation of customer provided single hole lugs. (Torque to 72 in-lbs.) (
Maximum Lug Width is 0.750”.)
(Maximum Wire Size is 2
A
WG.)
-48V Load Connections
-48V L
oad
Connections
Rear View
(wired from the rea
r of the bay)
1/4-20 stud
s on 5/8” centers for installation of customer provided two hole lugs. (Torque
to 72 in-lbs.) (Maximum Lug Width is 0.610”.) (Maximum Wire Si
ze is 2 AWG.)
-48V Load Connections* or TVSS Connections (+Ground)*
Ensure leads ar
e connected to
pr
oper polarity for the device installed, either a Distribution Device (load lead connection) or a TVSS Device (ground connection).
*
-48V Load
Connections*
or
TVSS
Connections
(+Ground)*
-48V Lo
ad Connections and
TVSS Device Ground Connections t
o
List 115 and 125 Distribution Panel
Rear View
(wired from the rear of the ba
y)
-48V Load Connectio
ns
t
o
List 110 and 120 Distribution Panel
Home
Revision BK, September 27, 2017 Spec. No. 582120600 (Model 801DB NVGB)
Page 56 of 75
Page 57
System Application Guide SAG582120600
Home
Spec. No. 582120600 (Model 801DB NVGB) Revision BK, September 27, 2017
Page 57 of 75
Page 58
SAG582120600 System Application Guide
Detail C (Page 4)
Top Feed Arrangement Shown For Bottom Feed Arrangement,
Ground Bar Assemblies Are
Installed in Bottom Most
Mounting Positions
Front View
8-Panel Bay
Front View
6-Panel Bay
Optional List 127
Ground Bar Assembly
(Each List 127 provides
two [2] Ground Bar
Assemblies.)
Optional List 117 Ground Bar Assembly (Each List 117 provides two [2] Ground Bar Assemblies.)
Optional List 117 Ground Bar Assembly (Each List 117 provides two [2] Ground Bar Assemblies.)
List 139 Paralleling Bars
Optional Internal
Ground/Return Busbar
Connections
(Distribution Panel Length,
Replaces a Distribution Panel)
Home
Revision BK, September 27, 2017 Spec. No. 582120600 (Model 801DB NVGB)
Page 58 of 75
Page 59
System Application Guide SAG582120600
Optional Internal
Ground/Return Busbar
Connections
(Distribution Panel Length,
Replaces a Distribution Panel)
List 117
Ground Bar
(8-Panel Bay)
List 127
Ground Bar
(6-Panel Bay)
1/4” clearance holes/slots on 5/8” centers for installation of customer provided two hole lugs. (Torque to 72 in-lbs.) (Maximum Lug Width is 0.610”.) (Maximum Wire Size is 2 AWG.)
Typical Lug Installation
0.625” Centers
Right
Side
Left Side
Top
Feed
Bottom
Feed
14 SPACES ON
0.81CENTERS = 11.3
8
15 SPACESON
0.81CENTERS = 12.19
26 SPACESON
0.812 CENTERS = 21.125
25 SPACES ON
0.812 CENTERS = 20.313
Home
Spec. No. 582120600 (Model 801DB NVGB) Revision BK, September 27, 2017
Page 59 of 75
Page 60
SAG582120600 System Application Guide
Internal Ground Bar Assembly (P/O List 117)
Paralleling Bar (List 139)
Hardware Build-Up
3/8-16 x 1-1/4 Bolt 3/8 Belleville Lock Washer 3/8 Flat Washer Internal Ground Bar Assembly Paralleling Bar
TORQUE TO 180 IN-LBS
Detail C (Page 6)
Optional Internal
Ground/Return Busbar
Paralleling Bar
Home
Revision BK, September 27, 2017 Spec. No. 582120600 (Model 801DB NVGB)
Page 60 of 75
Page 61
System Application Guide SAG582120600
3/8” clearance holes/slots on 1.00” centers for installation of customer­provided two hole lugs. (Torque to 180 in-lbs) (Maximum Lug Width is 2.00”) (Maximum Wire Size is 750 kcmil)
Bottom Feed Installations
List 143, 144, 145 or 147 Input Feed and Shunt Assembly
Addtional Input Feed and Shunt Assemblies are installed on any Distribution Panel not paralleled with a Distribution Panel that has an Input Feed and Shunt Assembly installed.
List 143, 144, 145 or 147 Input Feed and Shunt Assembly
3/8” clearance holes/slots on 1.00” centers for installation of customer­provided two hole lugs. (Torque to 180 in-lbs) (Maximum Lug Width is 2.00”) (Maximum Wire Size is 750 kcmil)
Top Feed
Installations
List 143 or 147
List 143 or 147
Rear View
8-Panel Bay
(6-Panel Bay Similar)
Portion of bay removed
in illustration for clarity.
Home
Spec. No. 582120600 (Model 801DB NVGB) Revision BK, September 27, 2017
DC Input Connections
Page 61 of 75
Page 62
O
p
ti
on
a
l L
i
st 14
8 2
4
00
A G
r
ou
nd
/
Re
t
ur
n
I
np
ut
K
it
pr
o
vi
de
s
Ad
d
it
io
n
al
DC
I
np
ut
C
o
nn
ec
t
io
ns
(
Ba
tt
e
ry
R
et
ur
n
Le
ad
s
)
3/
8” c
lea
ran
ce
h
ol
e
s o
n
1
.00”
cen
ter
s fo
r
i
nst
all
ati
on
o
f c
us
tom
er
p
rovi
ded
two
hole
lug
s.
(
Torq
ue
t
o 18
0 in
-lb
s)
(Ma
x. l
ug w
idt
h is 2
.00
”)
(M
a
x.
wir
e siz
e is
750
kcmi
l)
T
op a
nd B
ot
to
m
Fe
e
d
3/8
” cle
ara
nce
hol
es on
1
.00
” centers f
or
in
sta
llat
ion
of c
ust
omer
p
rovided two
hole
lug
s.
(
Torq
ue t
o 18
0 in
-lbs)
(M
ax.
lug
wid
th is
2.00”)
(Max.
wire si
ze is 7
50 kcm
il)
L
ist
148
Fee
d
Op
tio
nal
bonding
s
tra
p (P/
O
List 148
)
can b
e
remov
ed
if not
req
uired.
O
pt
i
on
al
bondi
ng
st
ra
p
(P
/O
L
is
t
14
8
)
can be
r
emo
ved
i
f
no
t
re
qui
red
.
T
o
p F
e
ed
DC
I
np
ut
C
on
ne
c
ti
o
ns
(
Ba
tt
e
ry
Re
t
ur
n Lea
d
s)
Bottom Fe
ed
D
C Input Connec
tions
(Battery Re
turn Leads)
Opti
onal List 14
8 2400A Ground
/Return
Input K
it provides A
dditional DC I
nput
Connections
(Battery Retur
n Leads)
Op
ti
o
na
l L
i
st
1
16
In
t
er
na
l
G
ro
u
nd
/Return Busbar
Arr
an
g
ed
fo
r
To
p F
e
ed
(
L
is
t
12
6 s
i
mi
la
r
)
Op
t
io
na
l
Li
st
1
16
In
t
er
n
al
G
ro
un
d
/R
et
u
rn
B
us
ba
r
A
rr
a
ng
ed
for Bottom Feed
(
Li
s
t 1
2
6 s
im
i
la
r)
Rea
r Vi
ew
8-P
an
el
Ba
y
(
6-P
anel
Bay
Sim
ilar
)
P
orti
on o
f ba
y rem
ove
d
in i
llus
tra
tion
for c
lar
ity
.
Home
SAG582120600 System Application Guide Revision BK, September 27, 2017 Spec. No. 582120600 (Model 801DB NVGB)
Page 62 of 75
Page 63
System Application Guide SAG582120600
Detail D (Page 3)
Optional List 117 Internal
Ground/Return Busbar
(List 127 similar)
Top Feed
DC Input Connections
(Battery Return Leads)
3/8" clearance holes on 1.00" centers for installation of customer provided two hole lugs. (Torque to 180 in-lbs) (Maximum Lug Width is 2.00") (Maximum Wire Size is 4/0 AWG)
Top Feed
Installations
Bottom Feed
DC Input Connections
(Battery Return Leads)
3/8" clearance holes on 1.00" centers for installation of customer provided two hole lugs. (Torque to 180 in-lbs) (Maximum Lug Width is 2.00") (Maximum Wire Size is 4/0 AWG)
Bottom Feed
Installations
Portion of bay removed in illustration for clarity.
Rear View
8-Panel Bay
(6-Panel Bay Similar)
Home
Spec. No. 582120600 (Model 801DB NVGB) Revision BK, September 27, 2017
Page 63 of 75
Page 64
SAG582120600 System Application Guide
Home Home
Revision BK, September 27, 2017 Spec. No. 582120600 (Model 801DB NVGB)
Replacement Alarm, Reference, and Control Fuses, List 105 and 107 Bays
Fuseblock Located in Bay’s Top Center
Features
Control fuses are located on the fuseblock mounted in the top center of each bay.
Note also that distribution fuses also contain alarm-type fuses as detailed in the previous sections of this document.
Restrictions
These fuses are not available for customer connected loads.
Ordering Notes
1) Order replacement fuses as required per Table 11.
Function
Top Fuse: Digital Meter and Alarm Circuit Card Feed A (-48V Input).
Bottom Fuse: Digital Meter and Alarm Circuit Card Feed B (-48V Input).
Safety Fuse Cover
Replaceable Alarm, Reference, and Control Fuses, List 106 and 107 Bays
Size
(Amperes)
1-1/3A
Table 11
Type P/N
Bussmann
GMT-A
Bussmann
GMT-X
Replacement Alarm, Reference, and Control Fuses, List 106 and 108 Bays
Fuses Located on Auxiliary Fuse Card at Top of Bay
Features
Control and auxiliary load fuses are located on the fuseblock mounted at the top right of each bay.
Note also that distribution fuses also contain alarm-type fuses as detailed in the previous sections of this document.
Ordering Notes
1) Order replacement fuses as required per Table 12.
Function
F1, F2: Auxiliary loads, sourced from Feed A (-48V).
F3, F4: Auxiliary loads, sourced from Feed B (-48V).
F5, F6: External ABS (A&B) input to Meter/Alarm Panel
Safety Fuse Cover
Replaceable Alarm, Reference, and Control Fuses, List 106 and 108 Bays
Size
(Amperes)
1-1/3A
Table 12
Type P/N
Bussmann
GMT-A
Bussmann
GMT-X
248610700
248898700
248610700
248898700
Page 64 of 75
Page 65
System Application Guide SAG582120600
Home
Spec. No. 582120600 (Model 801DB NVGB) Revision BK, September 27, 2017
Replacement Circuit Cards, List 105 and 107 Bays
Ordering Notes
1) Refer to the following table.
Item P/N
External Alarm Circuit Card 486339800
Replacement Circuit Cards, List 106, 108, 206, and 208 Bays
Ordering Notes
1) Refer to the following table.
Item P/N
Auxiliary Fuse Card 547760
Input/Output Card 547761
Page 65 of 75
Page 66
SAG582120600 System Application Guide
Home Home
Revision BK, September 27, 2017 Spec. No. 582120600 (Model 801DB NVGB)
SPECIFICATIONS
1.1 DC Operating Voltage
1.1.1 Nominal: -48Vdc.
1.1.2 Range: -42Vdc to -60Vdc.
1.2 Environmental Ratings
1.2.1 Operating Ambient Temperature Range: 0°C to +40°C (+32°F to +104°F).
1.2.2 Storage Ambient Temperature Range: -40°C to +80°C (-40°F to +176°F).
1.2.3 Humidity: This system is capable of operating in an ambient relative humidity range of 0% to 95%, non-condensing.
1.2.4 Altitude: The maximum operating ambient temperature should be de-rated by 10°C at an elevation of 10,000 feet
above sea level. For elevations between 3,000 feet and 10,000 feet, derate the maximum operating ambient temperature linearly.
1.2.5 Mounting: This product is intended only for installation in a Restricted Access Location on or above a non-
combustible surface.
Typical industry standards recommend minimum aisle space clearance of 2'6" for the front of the relay rack and 2' for the rear of the relay rack.
This BDF/CBB uses natural convection. Equipment designed for use in environmentally controlled space.
This product is intended for installation in Network Telecommunication Facilities (CO, vault, hut, or other environmentally controlled electronic equipment enclosure).
This product is intended to be connected to the common bonding network in a Network Telecommunication Facility (CO, vault, hut, or other environmentally controlled electronic equipment enclosure).
1.3 Compliance Information
1.3.1 Safety Compliance: This BDF/CBB is UL Listed (and "cULus") as a DC Power Distribution Center for
Communications Equipment.
1.3.2 NEBS Compliance: Compliance verified by a Nationally Recognized Testing Laboratory (NRTL) per GR-1089-CORE
and GR-63-CORE. Contact Vertiv for NEBS compliance reports.
1.4 Output Ratings
1.4.1 Distribution Panel: 640A maximum continuous.
1.4.2 8-Panel Bay: 2400A, maximum, per side.
4800A, maximum, per bay.
1.4.3 6-Panel Bay: 1800A, maximum, per side.
3600A, maximum, per bay.
1.5 Standard Features—Lists 106 and 108
1.5.1 Fuse/Circuit Breaker Mounting Positions: See description in Distribution Panel List Options section.
1.5.2 External Alarm Circuits: Four (4) relays each provide three (3) sets of Form-C contacts for external alarms. Various
available alarms can be mapped to each of the relays. Contact rating is 2A at 30 VDC.
1.5.3 Local Controls and Indicators: A status indicator at the top of the bay front panel indicates system status. The
Meter/Alarm Panel provides digital metering of load voltage and current individually for each distribution panel. Also displays system alarm messages and adjustment information.
1.5.4 Meter Accuracy (A) Current: ±1.0% (B) Voltage: ±0.1%
1.5.5 Remote Access: Via Web Interface (A) Description: The Web Interface provides remote access to the system monitoring and control functions that
are available locally at the Meter/Control Panel.
(B) Connection: Ethernet, RJ 45 10BaseT jack. This jack has a standard Ethernet pin configuration scheme,
twisted pair. Use shielded Ethernet cable, grounded at both ends. (The Meter/Alarm Panel’s RJ-45 jack is connected to chassis ground.) The Ethernet port is suitable for connection to intra-building or non-exposed wiring or cabling only.
(C) Users: 64, maximum (D) Security:
(1) Password Protection: When logging onto the system, the user is prompted to enter a "User Password".
Page 66 of 75
Page 67
System Application Guide SAG582120600 Spec. No. 582120600 (Model 801DB NVGB) Revision BK, September 27, 2017
(2) Page Access Levels: User configurations provide a "Page Access Level" which can be used to limit the
functions available to a particular user. Eight Page Access Levels are available.
(E) PC Requirements:
(1) Web Browser: Microsoft® Internet Explorer 5.0 or newer is required. (2) Screen Resolution: 1024 x 768 or greater is required.
Page 67 of 75
Page 68
SAG582120600 System Application Guide
Front
3/8-16
Welded Nut
(4)
0.750 Dia. (8 PLACES)
2.275
1.275
1.875
26.000
23.875
23.475
24.475
1.400
2.400
3.000
12.096
12.696
13.696
15.000
Home
Revision BK, September 27, 2017 Spec. No. 582120600 (Model 801DB NVGB)
MECHANICAL SPECIFICATIONS (LIST 106 AND 108)
Floor Hole Drilling Pattern Dimensions
Page 68 of 75
Page 69
System Application Guide SAG582120600
Home
Spec. No. 582120600 (Model 801DB NVGB) Revision BK, September 27, 2017
MECHANICAL SPECIFICATIONS (LIST 206 AND 208)
Floor Hole Drilling Pattern Dimensions
Page 69 of 75
Page 70
SAG582120600 System Application Guide
Home
Revision BK, September 27, 2017 Spec. No. 582120600 (Model 801DB NVGB)
Dimensions, List 108: 8-Bus Bay
Page 70 of 75
Page 71
System Application Guide SAG582120600
Home
Spec. No. 582120600 (Model 801DB NVGB) Revision BK, September 27, 2017
Dimensions, List 208: 8-Bus Bay
Page 71 of 75
Page 72
SAG582120600 System Application Guide
Home
Revision BK, September 27, 2017 Spec. No. 582120600 (Model 801DB NVGB)
Dimensions, List 106: 6-Bus Bay
Page 72 of 75
Page 73
System Application Guide SAG582120600
Home
Spec. No. 582120600 (Model 801DB NVGB) Revision BK, September 27, 2017
Dimensions, List 206: 6-Bus Bay
Page 73 of 75
Page 74
SAG582120600 System Application Guide
Home
Revision BK, September 27, 2017 Spec. No. 582120600 (Model 801DB NVGB)
RELATED DOCUMENTATION
SD582120600 (Power System)
T582120600 (Power System)
Section 5674 (Power System) Section 5823 (Pre-charge Assembly, Spec. No. 510142)
Page 74 of 75
Page 75
System Application Guide SAG582120600
Home
VertivCo.com |
© 2017 NetXte nd™ are trad emarks of V ertiv Energ y Systems, Inc. All o ther tradem arks are th e property of their re spective o wners. complet Specifications are subject to change without notice.
This document manufacture or sell anything that it may describe. Reproduction, disclo
Spec. No. 582120600 (Model 801DB NVGB) Revision BK, September 27, 2017
REVISION RECORD
Change
Revision
Number
Description of Change Date Approved
(ECO)
BB LLP218226 Add new busbar kit P/N 556103. 02/22/2013 Khristebelle Ilagan
BC LLP218456
Add right angle lug adapter kits P/Ns 556377 and
556378.
05/01/2013 John Jasko
Auxiliary Fuse Card Connections illustration revised.
BD LLP219017
Removed rocker handle bullet-nose circuit breakers. Revised notes for 556103. Added “Side by Side Busbar
09/03/2013 John Jasko
Link Kit for Use with List 115 and List 125, P/N 557256”.
Illustration for List 170 added. Relay and alarm settings
BE LLP219319
defaults added to “Ethernet and External Alarm
12/03/2013 John Jasko
Connections” illustration, Detail B for List 106 and 108.
BF LLP219853 Added 90A Bullet Breaker P/Ns 138887 and 138888.
BG LLP220993
BH
BJ
LLP221545
LLP223817
Removed ordering note referencing List 156 from List 106 and List 108 descriptions.
Added Lists 206, 208, 251 and 253. Updated 6 and 8­bay schematics.
Rebranded Vertiv.
02/21/2014 John Jasko
10/07/2014 John Jasko
02/20/2015 Mitchelle Emata
04/25/2017 John Jasko
BK LLP224352 Document converted to latest Vertiv format. 09/27/2017 John Jasko
John Jasko Oct 9, 2017
Craig Oursler Oct 10, 2017
Vertiv Headquarters, 1050 Dearborn Drive, Columbus, OH, 43085, USA
Vertiv Energy Systems, Inc. All rights reserved. Vertiv and the V ertiv logo are trademar ks or regis tered trad emarks of Vertiv Group Corporation. NetPerform™, NetReach™, NetSure™ and
eness of this document, Vertiv Group Corporation assumes no responsibility and disclaims all liability for damages resulting from use of this information or for any errors or omissions.
may contain confidential and/or proprietary information of Vertiv Group Corporation, and its receipt or possession does not convey any right to reproduce, dis close its contents, or to
sure, or use without specific authorization from Vertiv Group Corporation is strictly prohibited.
While every precaution has been taken to ensure accuracy and
Page 75 of 75