Vertiv NetSure, M830B, M830D User Manual

NetSure™ Control Unit (NCU)
M830B, M830D
Benefits
y Easily monitor and adjust system
parameters with a simple, graphic user interface accessed through an on-board color display or web pages supported by all major browsers.
y Numerous connectivity options
that support integration into a wide variety of networks – IPv4, IPv6, Modbus, SNMP, TL1, EEM,
YDN23 and dual network port
option for permanent and local craft port connections.
y Leverage advanced battery and
generator management controls, including soft start, time controls, starter battery check with recharge, bad-grid equalization recovery, current limiting, fuel monitoring with theft alarms and support for multiple battery technologies, including lithium.
y Rapidly turn-up system
with easily uploaded/ downloaded pre-programmed configuration files.
y Decrease energy costs by
eectively managing multiple energy sources such as generators and solar panels.
The advanced NetSure™ Control Unit (NCU) from Vertiv takes remote monitoring and control to the next level with a user-friendly color interface, secure connectivity, data statistics and multiple communication options.
Description
The NetSure Control Unit (NCU) is an advanced controller designed for a wide range of DC power applications, enabling remote monitoring and control of modern communication sites. The factory-installed (standard) or field-added NCU is backward compatible with existing NetSure™ power systems, controlling all aspects of the power chain, including AC mains, DC power plant, battery backup, diesel generator, and the local site environment. The addition of optional interface boards enables the user to access an even greater set of site parameters.
Battery management features include temperature compensation, thermal runaway management, recharge current limit, reserve time prediction, and optional midpoint monitoring. Battery testing options include scheduled battery testing and short duration battery testing. Thresholds for battery current measurement, detailed alarms, inventory management and three LVD levels can be programmed easily through the controller. Control of rectifiers (24V, 48V and 400V) and converters (24V, 48V, 400V and solar) is possible in this convenient pluggable module.
Network element management support for data communication is also available via standard protocols, such as SNMP version 2 or 3, or Modbus. In addition, Modbus device integration for many industry standard monitoring devices is now possible with the versatile NCU controller.
Patented Intelligent Load Management from Vertiv enables you to see power usage down to the fuse or circuit breaker level. To prevent site overload, load levels of each rack can be measured in relation to rack capacity. Rack load monitoring requires optional system distribution measurement devices for the fuse or circuit breaker positions.
M830B
Expanded information and alarm data can be monitored or controlled via password protected and encrypted web browsers, including Internet Explorer, Firefox, Google Chrome, and Apple Safari.
M830D
NetSure™ Control Unit (NCU)
Technical Specifications
General
Power Supply 19 VDC to 60 VDC
Power Consumption 18 W maximum, 4W typical
Environmental
Operating
Relative Humidity 0 to 90%
-20°C to +65°C (nominal), -40°C to +75°C (extended conditions) /
-4°F to +149°F (nominal), -40°F to +167°F (extended conditions)
Safety and Standards Compliance
Electrical IEC 60950-1, EN 60950-1, UL 60950-1
EMC EN 300 386, 2001 Class B; FCC Part 15, Class B
Environmental CE; NEBS Level 3
Mechanical Data M830B M830D
Dimensions (H x W x D)
Standard Installation Methods Hot pluggable in stand-alone or embedded power plants
Weight 1 kg / 2.2 lbs.
43.4 x 86 x 208 (mm)
1.65 x 3.41 x 8.33 (inches)
86.2 x 87 x 208 (mm)
3.41 x 3.42 x 8.33 (inches)
Inputs/Outputs M830B M830D
Display 128 x 160 Pixels TFT LCD 320 x 240 Pixels TFT LCD
Communication RS232, RS485, Ethernet, USB (for software upgrades)
Protocol IPv4, IPv6, HTTPS, SNMP V 2/ V 3, EEM, SocTpe, Rsoc, Modbus
Analog Inputs
Digital Inputs
Outputs 3 LVD mono or bistable contactors
2 battery currents, 1 load current, 1 bus voltage, 2 battery voltages, 2 temperatures, fuel level sensor and much more with additional interface boards
1 input for status of surge protective device auxiliary contacts, 12 load fuses, 6 battery fuses, bi-stable contactor status
Ordering Information
NetSure™ Control Unit User Interface
Web Interface Home Page
To access the product warranty process, optimize your after-sales experience, and obtain more information, please register your Vertiv products at
Vertiv.com/ProductRegistrationLATAM
Model Model Number Description
M830B 1M830BXX NCU3.0+ controller, 1 x 2 RU
M830D 1M830DXX NCU3.0+ controller, 2 x 2 RU
Optional Interface Board
EIB 5 relay outputs, 8 DC voltages, 3 DC currents, 2 temperatures
IB1 4 relay outputs, 4 digital inputs
IB2 8 relay outputs, 8 digital inputs, 2 temperatures
IB4 1 additional Ethernet port
Supervision Modules
SMDU 4 shunts, 1 voltage input, 20 fuse alarms, and 2 LVD controls
SMDU+ 25 shunts, and 25 fuse alarms
SMTEMP Temperature concentrator with up to 8 temperature sensors
SMDUH 20 Hall effect sensors to measure DC distribution load current from 0 A to 100 A
Vertiv.com | Vertiv Headquarters, 1050 Dearborn Drive, Columbus, OH, 43085, USA
© 2020 Vertiv G roup Corp. All right s reserved. Vertiv ™ and the Vertiv logo are tr ademarks or regis tered trademarks of Ver tiv Group Corp. All o ther names and log os referred to are trade n ames, trademar ks or registered tra demarks of their res pective owners . While every precauti on has been taken to en sure accuracy and c ompleteness he re, Vertiv Group Cor p. assumes no resp onsibility, and dis claims all liabili ty, for damages resu lting from use of this inf ormation or for any erro rs or omissions . Specificatio ns, rebates and oth er promotional oers are su bject to change at Ver tiv’s sole discret ion upon notice.
NCU Controller (R12/20)