The information contained in this document is subject to change without notice
and may not be suitable for all applications. While every precaution has been
taken to ensure the accuracy and completeness of this document, Vertiv
assumes no responsibility and disclaims all liability for damages resulting from
use of this information or for any errors or omissions. Refer to other local
practices or building codes as applicable for the correct methods, tools, and
materials to be used in performing procedures not specifically described in this
document.
The products covered by this instruction manual are manufactured and/or sold
by Vertiv. This document is the property of Vertiv and contains confidential
and proprietary information owned by Vertiv. Any copying, use or disclosure of
it without the written permission of Vertiv is strictly prohibited.
Names of companies and products are trademarks or registered trademarks of
the respective companies. Any questions regarding usage of trademark names
should be directed to the original manufacturer.
Technical Support Site
If you encounter any installation or operational issues with your product, check the pertinent section of this
manual to see if the issue can be resolved by following outlined procedures.
Visit https://www.Vertiv.com/en-us/support/ for additional assistance.
Vertiv | Li ebert® Mini-Mate2™ Installer/Us er Guide
TABLE OF CONTENTS
1 Important Safety Instructions1
1.1 Agency Listed6
2 Nomenclature7
2.1 Nomenclature for Evaporator and Chilled Water Units7
2.2 Nomenclature for Split System Condensing Units9
2.2.1 Indoor Condensing Units for Air Cooled Split Systems9
2.2.2 Outdoor Prop Fan Condensing Units for Air Cooled Split Systems10
2.2.3 Water/Glycol-cooled Condensing Units11
2.3 System Configurations12
3 Site Preparation and Equipment Handling15
3.1 Planning Dimensions15
3.2 Room Preparation15
3.2.1 Duct Work Considerations for the Indoor Air Cooled Condensing Unit15
3.3 Application Limits16
3.4 Indoor Unit Weights17
3.5 Location Considerations18
3.5.1 Location Considerations for Evaporator, Indoor Condensing,andChilled WaterUnits18
3.5.2 Location Considerations for an Outdoor Condensing Unit19
Vertiv | Li ebert® Mini-Mate2™ Installer/Us er Guide
1 IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS
This manual contains important safety instructions that should be followed during the installation and maintenance of the
Liebert®Mini-Mate2. Read this manual thoroughly before attempting to install or operate this unit.
Only qualified personnel should move, install or service this equipment.
Adhere to all warnings, cautions, notices and installation, operating and safety instructions on the unit and in this manual.
Follow all installation, operation and maintenance instructions and all applicable national and local building, electrical and
plumbing codes.
WARNING! Arc flash and electric shock hazard. Open all local and remote electric power-supply disconnect
switches, verify with a voltmeter that power is Off and wear appropriate, OSHA-approved personal protective
equipment (PPE) per NFPA 70E before working within the electric control enclosure. Failure to comply can
cause serious injury or death. Customer must provide earth ground to unit, per NEC, CEC and local codes, as
applicable. Before proceeding with installation, read all instructions, verify that all the parts are included and
check the nameplate to be sure the voltage matches available utility power. The Liebert® controller does not
isolate power from the unit, even in the “Unit Off” mode. Some internal components require and receive
power even during the “Unit Off” mode of the controller. The only way to ensure that there is NO voltage
inside the unit is to install and open a remote disconnect switch. Refer to unit electrical schematic. Follow all
local codes.
WARNING! Risk of electric shock. Can cause equipment damage, injury or death. Open all local and remote
electric power supply disconnect switches and verify with a voltmeter that power is off before working within
any electric connection enclosures. Service and maintenance work must be performed only by properly
trained and qualified personnel and in accordance with applicable regulations and manufacturers’
specifications. Opening or removing the covers to any equipment may expose personnel to lethal voltages
within the unit even when it is apparently not operating and the input wiring is disconnected from the
electrical source.
WARNING! Risk of over pressurization of the refrigeration system. Can cause piping rupture, explosive
discharge of high pressure refrigerant, loss of refrigerant, environmental pollution, equipment damage,
injury, or death. This unit contains fluids and gases under high pressure. Use extreme caution when
charging the refrigerant system. Do not pressurize the system higher than the design pressure marked on
the unit's nameplate. Relieve pressure before cutting into or making connections/disconnections to the
piping system. Local building or plumbing codes may require installing a pressure-relief device in the
system.
Consult local building and plumbing codes for installation requirements of additional pressure-relief devices
when isolation valves are field installed. Do not isolate any refrigerant circuits from over pressurization
protection. The PFH condensing units include a factory installed pressure relief valve mounted on top of the
receiver. The valve is rated for a maximum working pressure of 475 psig.
1 Important Safety Instructions
1
WARNING! Risk of contact with high-speed, rotating fan blades. Can cause injury or death. Open all local and
remote electric power-supply disconnect switches, verify with a voltmeter that power is off, and verify that all
fan blades have stopped rotating before working in the unit cabinet.
WARNING! Risk of electric shock. Can cause serious injury or death. The microprocessor does not isolate
power from the unit, even in the "Unit Off" mode. Some internal components require and receive power even
during the "unit off" mode of the control. Open all local and remote electric power disconnect switches and
verify with a voltmeter that power is Off before working on any component of the system.
WARNING! Risk of improper wiring, piping, moving, lifting and handling. Can cause equipment damage,
serious injury or death. Installation and service of this equipment should be done only by qualified personnel,
wearing appropriate, OSHA-approved PPE, who have been specially-trained in the installation of airconditioning equipment.
WARNING! Risk of improper wire and loose electrical connections. Can cause overheated wire and electrical
connection terminals resulting in smoke, fire, equipment and building damage, injury or death. Use correctly
sized copper wire only and verify that all electrical connections are tight before turning power On. Check all
electrical connections periodically and tighten as necessary.
WARNING! Risk of ceiling collapse and heavy unit falling. Can cause building and equipment damage, serious
injury or death. Verify that the supporting roof structure is capable of supporting the weight of the unit(s)
and the accessories. See Indoor Unit Weights on page17, for the unit weights. Securely anchor the top ends
of the suspension rods and verify that all nuts are tight.
WARNING! Risk of smoke and fire. Can cause activation of fire suppression systems, building evacuation,
dispatching of fire/rescue equipment and personnel and catastrophic canister failure resulting in water
leaks, equipment damage, injury or death. Using a humidifier canister that has reached the end of it’s service
life can be extremely hazardous. If the canister cannot be replaced immediately at the end of life condition,
turn Off the power and water supply to the humidifier and remove the canister until a replacement canister
can be installed. Do not ignore humidifier problem alarms. Resetting humidifier without addressing cause
may result in fire or damage due to leaking water.
CAUTION: Risk of excessive refrigerant line pressure. Can cause tubing and component rupture resulting in
equipment damage and personal injury. Do not close off any field installed refrigerant-line isolation valve for
repairs unless a pressure-relief valve is field- installed in the line between the isolation valve and the check
valve. The pressure-relief valve must be rated 5% to 10% higher than the system-design pressure. An
increase in ambient temperature can cause the pressure of the isolated refrigerant to rise and exceed the
system-design pressure rating (marked on the unit nameplate).
2
Vertiv | Li ebert® Mini-Mate2™ Installer/Us er Guide
NOTICE
CAUTION: Risk of contact with sharp edges, splinters, and exposed fasteners. Can cause injury. Only
properly trained and qualified personnel wearing appropriate, OSHA-approved PPE should attempt to move,
lift, remove packaging from or prepare the unit for installation.
CAUTION: Risk of contact with hot surfaces. Can cause injury. The compressor, refrigerant discharge lines,
fan motor, and some electrical components are extremely hot during unit operation. Allow sufficient time for
them to cool to a touch-safe temperature before working within the unit cabinet. Use extreme caution and
wear appropriate, OSHA-approved PPE when working on or near hot components.
CAUTION: Risk of contact with hot surfaces. Can cause burn injury. The humidifier canister and steam
discharge lines are extremely hot during operation. Allow sufficient time for them to cool to a touch-safe
temperature before handling. Use extreme caution and wear appropriate, OSHA-approved PPE when
performing maintenance on the humidifier.
CAUTION: Risk of contacting caustic substances. Can cause injury. Avoid touching or contacting the gas and
oils with exposed skin. Severe burns will result. Wear appropriate, OSHA-approved PPE when handling
contaminated parts.
Risk of oil contamination with water. Can cause equipment damage.
Liebert®Mini-Mate2DX systems require the use of POE (polyolester) oil. POE oil absorbs water at a much
faster rate when exposed to air than previously used oils. Because water is the enemy of a reliable refrigeration
system, extreme care must be used when opening systems during installation or service. If water is absorbed
into the POE oil, it will not be easily removed and will not be removed through the normal evacuation process. If
the oil is too wet, it may require an oil change. POE oils also have a property that makes them act as a solvent
in a refrigeration system. Maintaining system cleanliness is extremely important because the oil will tend to
bring any foreign matter back to the compressor.
1 Important Safety Instructions
3
NOTICE
NOTICE
Risk of clogged or leaking drain lines and leaking water supply lines. Can cause equipment and building
damage.
This unit requires a water drain connection. Drain lines must be inspected at start-up and periodically, and
maintenance must be performed to ensure that drain water runs freely through the drain system and that lines
are clear and free of obstructions and in good condition with no visible sign of damage or leaks. This unit may
also require an external water supply to operate.
Improper installation, application and service practices can result in water leakage from the unit. Water
leakage can result in catastrophic and expensive building and equipment damage and loss of critical data
center equipment.
Do not locate unit directly above any equipment that could sustain water damage.
We recommend installing a monitored fluid-detection system to immediately discover and report coolant fluid
system and condensate drain line leaks.
Risk of leaking water/glycol. Can cause equipment and building damage.
Improper installation, application, and service practices can result in water leakage from the unit. Do not mount
this unit over equipment and furniture that can be damaged by leaking water. Install a water-tight drain pan
with a drain connection under the cooling unit and the ceiling mounted water/glycol condensing unit. Route the
drain line to a frequently-used maintenance sink so that running water can be observed and reported in a
timely manner. Post a sign to alert people to report water flowing from the secondary drain pan. We
recommend installing monitored leak detection equipment for the unit and supply lines and in the secondary
drain pan. Check drain lines periodically for leaks, sediment buildup, obstructions, kinks and/or damage and
verify that they are free running.
4
Vertiv | Li ebert® Mini-Mate2™ Installer/Us er Guide
NOTICE
Risk of piping system corrosion and freezing fluids. Can cause leaks resulting in equipment and very expensive
building damage. Cooling coils and piping systems are at high risk of freezing and premature corrosion. Fluids
in these systems must contain the proper antifreeze and inhibitors to prevent freezing and premature coil and
piping corrosion. The water or water/glycol solution must be analyzed by a competent local water treatment
specialist before start up to establish the inhibitor and antifreeze solution requirement and at regularly
scheduled intervals throughout the life of the system to determine the pattern of inhibitor depletion.
The complexity of water/glycol solution condition problems and the variations of required treatment programs
make it extremely important to obtain the advice of a competent and experienced water treatment specialist
and follow a regularly scheduled coolant fluid system maintenance program.
Water chemistry varies greatly by location, as do the required additives, called inhibitors, that reduce the
corrosive effect of the fluids on the piping systems and components. The chemistry of the water used must be
considered, because water from some sources may contain corrosive elements that reduce the effectiveness of
the inhibited formulation. Sediment deposits prevent the formation of a protective oxide layer on the inside of
the coolant system components and piping. The water/coolant fluid must be treated and circulating through
the system continuously to prevent the buildup of sediment deposits and or growth of sulfate reducing
bacteria.
Proper inhibitor maintenance must be performed in order to prevent corrosion of the system. Consult glycol
manufacturer for testing and maintenance of inhibitors.
Commercial ethylene glycol, when pure, is generally less corrosive to the common metals of construction than
water itself. It will, however, assume the corrosivity of the water from which it is prepared and may become
increasingly corrosive with use if not properly inhibited.
NOTICE
NOTICE
We recommend installing a monitored fluid-detection system that is wired to activate the automatic-closure of
field installed coolant fluid supply and return shut-off valves to reduce the amount of coolant fluid leakage and
consequential equipment and building damage. The shut-off valves must be sized to close-off against the
maximum coolant fluid system pressure in case of a catastrophic fluid leak.
Risk of frozen pipes and corrosion from improper coolant mixture. Can cause water leaks resulting in
equipment and building damage.
When piping or the cooling unit may be exposed to freezing temperatures, charge the system with the proper
percentage of glycol and water for the coldest design ambient temperature. Automotive antifreeze is
unacceptable and must NOT be used in any glycol fluid system. Use only HVAC glycol solution that meets the
requirements of recommended industry practices.
Risk of no flow condition. Can cause equipment damage. Do not leave the water/coolant fluid-supply circuit in a
no flow condition. Idle fluid allows the collection of sediment that prevents the formation of a protective oxide
layer on the inside of tubes. Keep unit switched On and water/coolant fluid supply circuit system operating
continuously.
1 Important Safety Instructions
5
NOTICE
NOTICE
NOTICE
NOTICE
Risk of improper water supply. Can reduce humidifier efficiency or obstruct humidifier plumbing.
Do not use completely demineralized water with this unit. The water must contain minerals for the electrode
principle to work.
Do not use a hot water source. It will cause deposits that will eventually block the fill-valve opening.
Risk of water backing up in the drain line. Leaking and overflowing water can cause equipment and building
damage.
Do not install an external trap in the drain line. This line already has a factory installed trap inside the cabinet.
Installation of a second trap will prevent drain water flow and will cause the water to overflow the drain pan.
This line may contain boiling water. Use copper or other material that is rated for handling boiling water for the
drain line. Sagging condensate drain lines may inadvertently create an external trap.
Risk of doorway/hallway interference. Can cause unit and/or structure damage. The unit may be too large to fit
through a doorway or hallway while on the skid. Measure the unit and passageway dimensions, and refer to the
installation plans prior to moving the unit to verify clearances.
Risk of damage from forklift. Can cause unit damage. Keep tines of the forklift level and at a height suitable to
fit below the skid and/or unit to prevent exterior and/or underside damage.
NOTICE
Risk of improper storage. Can cause unit damage.
Keep the unit upright, indoors and protected from dampness, freezing temperatures and contact damage.
1.1 Agency Listed
Standard 60-Hz units are CSA Certified to the harmonized U.S. and Canadian product safety standard CSA C22.2 No
236/UL 1995 for “Heating and Cooling Equipment” and are marked with the CSA c-us logo.
6
Vertiv | Li ebert® Mini-Mate2™ Installer/Us er Guide
2 NOMENCLATURE
This section describes the model-number configuration for Liebert® Mini-Mate2 units and components.
2.1 Nomenclature for Evaporator and Chilled Water Units
Table 2.2 below describes each digit of the model number.
Table 2.1 Nomenclature Example
123456789101112
MMD36ENPRED5
Table 2.2 Nomenclature Digit Definitions for Evaporator and Chilled Water Units
DigitDescription
Digits 1 and 2 = the base unit
MM = Mini-Mate2
Digit3 = Disconnect
D = Disconnect switch
Digit4 a nd 5 = Nominal Capacity
24 = 24kBtuh, 60Hzevaporator
35 = 35 kBtuh, 50Hz evaporator
36 = 36 kBtuh, 60Hz evaporator
39 = 39 kBtuh, 3-ton, 50Hz, chilled water
40 = 40 kBtuh, 3-ton, 60Hz, chilled water
2 Nomenclature
Digit6 = Cooling type
C = Chilled-water cooled
E = Split-system evaporator (See Nomenclature for Split System Condensing Units on page9.)
K = Split-system evaporator with free cooling (See Nomenclature for Split System CondensingUnitson page9.)
Digit7 = Refrigerant/Valve type
N = R-407C field supplied
2 = 2-way standard pressure chilled water valve
3 = 3-way standard pressure chilled water valve
Digit8 = Supply power
A = 460V /3ph / 60Hz(3-toncapacity only)
M = 380/415V / 3ph / 50Hz (3-ton capacity only)
P = 208/230V / 1ph / 60Hz
S = 220V / 1ph /50Hz (3-ton capacity only)
Y = 208/230V / 3ph / 60Hz(3-toncapacity only)
X = 277V / 1ph / 60Hz
7
Table 2.2 Nomenclature Digit Definitions for Evaporator and Chilled Water Units (continued)
DigitDescription
Digit9 = Hum idification
R = Remote Humidifier Contact (without canister humidifier)
J = Canister Humidifier and Remote Humidifier Contact
Digit10 = Reheat
0 = No reheat
E = Electric reheat
S = SCR reheat (for DXevaporator without free cooling option)
H = Hot water reheat (chilled water systems only)
Digit11 = Blower type
D = Direct-drive internal blower
B = Belt-drive external blower
Digit12 = Sensor packages
N = Base package of filter-clog and high-temperature sensor
2 = Smoke sensor +Base package
4 = IS-UNITY-DP (BMS) + B ase Pack age
5 = IS-UNITY-DP (BMS) + Smoke sensor+ Base package
8
Vertiv | Li ebert® Mini-Mate2™ Installer/Us er Guide
2.2 Nomenclature for Split System Condensing Units
This section describes the model number configuration for Mini-Mate2 splitssystem condensing units.
2.2.1 Indoor Condensing Units for Air Cooled Split Systems
Table 2.4 below describes each digit of the model number.
Table 2.3 Indoor, Air Cooled Condensing Unit Nomenclature Example
12345678910
MCD36ALAHN
Table 2.4 Nomenclature Digit Definitions for Indoor, Air Cooled Condensing Units
DigitDescription
Digits 1 to 2 = the base unit
MC = Mini-Mate2 condensing unit
Digit3 = Disconnect
D = Disconnect switch
Digit4 a nd 5 = Nominal Capacity
24 = 24 kBtuh,60Hz
35 = 35 kBtuh, 50Hz
36 = 36 kBtuh, 60Hz
Digit6 = Cooling type
A = Air Cooled
Digit7 = Head-pressure control
L = Liebert® Lee-Temp™ Receiver
Digit8 = Supply power
A = 460V /3ph / 60Hz(3-toncapacity only)
M = 380/415V / 3ph / 50Hz (3-ton capacity only)
P = 208/230V / 1ph / 60Hz
S = 220V / 1ph /50Hz (3-ton capacity only)
X = 277V / 1ph / 60 Hz
Y = 208/230V / 3ph / 60Hz(3-toncapacity only)
Digit9 = Hot-gas bypass
H = Hot-gas bypass
Digit10 = Refrigerant
N = R-407C field charged
2 Nomenclature
9
2.2.2 Outdoor Prop Fan Condensing Units for Air Cooled Split Systems
Table 2.6 below describes each digit of the model number.
Table 2.5 Prop Fan Condensing Unit Nomenclature Example
1234567891011
PFH037A—PLN
Table 2.6 Nomenclature Digit Definitions for Outdoor, Prop Fan Condensing Units
DigitDescription
Digits 1 to 3 = the base unit
PFH = Prop-fan condensing unitwith hot gas bypass
Digit4 = Sound level
0 = Standard
Z = Quiet-Line
Digit5 and 6 = Nominal Capacity
27 = 27 kBtuh, 60Hz
36 = 36 kBtuh, 50Hz
37 = 37 kBtuh, 60Hz
Digit7 = Cooling type
A = Air-cooled
Digit8 = Coiltype
— = Standard coil
C = Coated coil (epoxy with UVtopcoat)
Digit9 = Supply power
A = 460V /3ph / 60Hz(3-toncapacity only)
B = 575V /3ph / 60Hz(3-ton capacity only, Quiet-Line not available)
M = 380/415V / 3ph / 50Hz (3-ton capacity only)
P = 208/230V / 1ph / 60Hz
S = 220V / 1ph /50Hz (3-ton capacity only)
Y = 208/230V / 3ph / 60Hz(3-toncapacity only)
Digit10 = Ambient rating/Control
L = 95°F Ambient, Liebert® Lee-Temp™
H = 105°F Ambient, Liebert®Lee-Temp™
Digit11 = Refrigerant
N = R-407C field charged
10
Vertiv | Li ebert® Mini-Mate2™ Installer/Us er Guide
2.2.3 Water/Glycol-cooled Condensing Units
Table 2.8 below describes each digit of the model number.
Table 2.7 Remote, Indoor Water/Glycol Condensing Unit Nomenclature Example
12345678910
MCD38W2AHN
Table 2.8 Nomenclature Digit Definitions for Indoor, Water/Glycol Cooled Condensing Units
DigitDescription
Digits 1 to 2 = the base unit
MC = Mini-Mate2 condensing unit
Digit3 = Disconnect
D = Disconnect switch
Digit4 a nd 5 = Nominal Capacity
26 = 26 kBtuh, 2-ton, 60Hz
37 = 37 kBtuh, 3-ton, 50Hz
38 = 38 kBtuh, 3-ton, 60Hz
Digit6 = Cooling type
W = Water/Glycol-cooled
Digit7 = Head-pressure control
2 = 2-way standard-pressure fluid-regulatingvalv e
3Split-system (outdoor condensing unit) with supply/returnair plenum
4Split-system (outdoorcondensing unit) with ducted supply/return air
5Indoorcondensing unit
6Evaporator
7Outdoor condensingunit
12
Vertiv | Li ebert® Mini-Mate2™ Installer/Us er Guide
Figure 2.2 Water/Glycol Cooled Units
2 Nomenclature
ItemDescriptionItemDescription
Split-system glycol cooled
1
with supply/return air plenum
Split-system glycol cooled
2
with ducted supply/returnair
Split-system water-cooled
3
with supply/return air plenum
Split-system water-cooled
4
with ducted supply/returnair
6Expansion tank
7Pump
8Water/glycol condensing unit
9Evaporator
5Drycooler10Cooling tower
13
Figure 2.3 Chilled Water Units
ItemDescription
1Chilled-water cooled with supply/return air plenum
2Chilled-water cooled withducted supply/return air
14
Vertiv | Li ebert® Mini-Mate2™ Installer/Us er Guide
3 SITE PREPARATION AND EQUIPMENT HANDLING
NOTE: Before installing unit, determine whether any building alterations are required to run piping, wiring and duct
work. Follow all unit dimensional drawings and refer to the submittal engineering dimensional drawings of individual
units for proper clearances.
3.1 Planning Dimensions
The unit dimensions are described in the submittal documents included in the Submittal Drawings.
The following table lists the relevant documents by number and title.
Table 3.1 Dimension Planning Drawings
Docu ment NumberTitle
Split System Evaporators/Chilled Water Units
DPN000193Evaporator/Chilled Water and Option Dimensions, All Direct Drive Blower Units
DPN000194Evaporator/Chilled Water Dimensions, All Belt Drive Blower Units
IndoorCondensingUnits
DPN004420Cabinet Dimensions, Air Cooled Units
DPN004421Cabinet Dimensions, Water/Glycol Cooled Units
3.2 Room Preparation
The room should be well insulated and must have a sealed vapor barrier. The vapor barrier in the ceiling and walls can be a
polyethylene film. Paint on concrete walls and floors should be vapor resistant.
NOTE: The vapor barrier is the single most important requirement for maintaining environmental control in the
conditioned area.
Outside or fresh air should be kept to a minimum when tight temperature and humidity control is required. Outside air adds
to the site’s cooling, heating, dehumidifying and humidifying loads. Doors should be properly sealed to minimize leaks and
should not contain ventilation grilles.
NOTE: Temperature and humidity sensors are located in the wall box. Proper and efficient cooling requires placing
the wall box where discharge air does not directly blow on the sensors.
3.2.1 Duct Work Considerations for the Indoor Air Cooled Condensing Unit
Observe the following when planning the installation of the indoor air cooled condensing unit:
Ensure a satisfactory source of clean air for the condensing unit supply and a means to discharge the hot air without
allowing the supply and discharge air to mix. Consider duct work to outdoor air. Duct work for outdoor air to and from the
condensing unit is optional.
The total external static pressure for the inlet and outlet ducts, including grille, must not exceed 0.5in. of water. Hood intake
and duct work cross-sectional area dimensions should be equal to or greater than the area of the condensing unit intake
flange.
For all duct work installation, see Guidelines for Ducted Systems on page25
3 S ite Preparation and Equipment Handling
15
3.3 Application Limits
Table 3.2 Application Limits for Evaporator and Chilled-water Units
Input voltageRange o f Return Air Co nditions to the U nit*
MinimumMaximumDry Bu lb TemperatureRelative Humidity
–5%+10%65 to 85°F (18 to 29°C)20 to 80%
*The unit will operate at these conditions, but it willnot control to these condition extremes.
Table 3.3 Application Limits for Indoor and Outdoor Air-cooled Condensing Unit
Input Voltage
Condensing Unit Type
MinimumMaximumMinimumMaximum
Entering Dry Bulb Air Temperature
115°F (48°C)standard-
–5%+10%
Outdoor Prop-fan
condensing unit
–30°F (–34°C)
ambient unit*
125°F (52°C)high-ambient
unit*
–5%+10%
Indoorair cooled condensing
unit
–30°F (–34°C)115°F (48°C)*
*Unit capacity ratings are stated for 95°F (35°C) for standard units and 1 05°F (41°C) for PFH high-ambient units. Exceeding these rating points by 20°F
(11°C) will result in lower cooling ca pacities, but will notdamage the equipment.
Table 3.4 Application Limits for Indoor Water/Glycol Cooled Condensing Unit
Input voltageE ntering fluid temperature
MinimumMaximumMinimum*Maximum
–5%+10%65°F (18°C)*115°F (46°C)
*Operation below 65°F (18°C) may result in fluid noise and reduced valve life.
16
Vertiv | Li ebert® Mini-Mate2™ Installer/Us er Guide
3.4 Indoor Unit Weights
Table 3.5 Indoor Unit Weights
Model #Weight, lb (kg)
Cooling Units *
MMD24E225 (102)
MMD35E225 (102)
MMD36E225 (102)
MMD39C230 (104)
MMD40C230 (104)
High static Blower Module85 (39)
3 S ite Preparation and Equipment Handling
17
Table 3.5 Indoor Unit Weights (continued)
Model #Weight, lb (kg)
IndoorCondensingUnits
MCD24A230 (104)
MCD35A240 (109)
MCD36A240 (109)
MCD26W1 75 (79)
MCD37W220 (100 )
MCD38W220 (100)
*Add20 lb. (9kg) to units with free cooling or hot water reheat coils.
3.5 Location Considerations
When determining installation locations, consider that these units contain water and that water leaks can cause damage to
sensitive equipment and furniture below.
NOTICE
Risk of leaking water/glycol. Can cause equipment and building damage.
Improper installation, application, and service practices can result in water leakage from the unit. Do not mount
this unit over equipment and furniture that can be damaged by leaking water. Install a water-tight drain pan
with a drain connection under the cooling unit and the ceiling mounted water/glycol condensing unit. Route the
drain line to a frequently-used maintenance sink so that running water can be observed and reported in a
timely manner. Post a sign to alert people to report water flowing from the secondary drain pan. We
recommend installing monitored leak detection equipment for the unit and supply lines and in the secondary
drain pan. Check drain lines periodically for leaks, sediment buildup, obstructions, kinks and/or damage and
verify that they are free running.
3.5.1 Location Considerations for Evaporator, Indoor Condensing,andChilled WaterUnits
The evaporator or chilled water unit is usually mounted above the suspended ceiling and must be securely mounted to the
roof structure. For ducted systems, the evaporator may be located in a different room from the heat-producing equipment.
For a split system with an indoor condensing unit, the condensing unit may be:
•Installed above the suspended ceiling near the evaporator or closely-coupled with the evaporator.
•In any remote indoor area, subject to the requirements detailed in Piping when Condensing Unit is Above or
Below Evaporator on page35.
Refer to Refrigerant Line Sizes and Equivalent Lengths on page36 for maximum refrigerant line lengths.
The ceiling and ceiling supports of existing buildings may require reinforcement. Be sure to follow all applicable national
and local codes.
Install the ceiling-mounting over an unobstructed floor space if possible. This will allow easy access for routine maintenance
or service. Do not attach additional devices (such as smoke detectors, etc.) to the housing, as they could interfere with the
maintenance or service.
18
Vertiv | Li ebert® Mini-Mate2™ Installer/Us er Guide
NOTE: Temperature and humidity sensors are in the wall box. Install the wall box where discharge air DOES NOT
blow directly on the sensors.
Do not install units in areas where normal unit operating sound may disturb the working environment.
When installing an air cooled or water/glycol cooled unit inside a space, ensure that national and local codes are met for
refrigerant concentration limits that might vary with building type and use.
3.5.2 Location Considerations for an Outdoor Condensing Unit
For a split system with an air cooled, outdoor condensing unit, the condensing unit may be mounted on the roof or remotely
in any outdoor area.
Observe the following when planning the installation of the outdoor unit:
•To ensure a satisfactory air supply, locate air cooled condensing units in an environment with clear air, away
from loose dirt and foreign matter that may clog the coil.
•Condensing units must not be located in the vicinity of steam, hot air or fume exhausts or closer than 18 inches
from a wall, obstruction or adjacent unit.
•Avoid areas where heavy snow will accumulate at air inlet and discharge locations.
•The condensing unit should be located for maximum security and maintenance accessibility. Avoid groundlevel sites with public access. Install a solid base, capable of supporting the weight of the condensing unit.
•The base should be at least 2in. (51mm) higher than the surrounding grade and 2 in. (51mm) larger than the
dimensions of the condensing-unit base. For snowy areas, a base of sufficient height to clear snow accumulation
must be installed.
•Securely attach the unit to the base using the holes provided in the unit mounting rails to prevent unit
movement that might stress refrigerant piping and electrical wiring.
Before beginning, refer to Piping and Refrigerant Requirements on page27 for unit placement, piping guidelines, and
refrigerant-charge requirements for your system.
The condensing unit must be located within the maximum distance from evaporator guidelines listed in 5.2.1 on page35.
3.6 Equipment Inspection and Handling
CAUTION: Risk of contact with sharp edges, splinters, and exposed fasteners. Can cause injury. Only
properly trained and qualified personnel wearing appropriate, OSHA-approved PPE should attempt to move,
lift, remove packaging from or prepare the unit for installation.
Do not uncrate the equipment until it is close to its final location. All required assemblies are banded and shipped in
corrugated containers. If any damage is discovered when the unit is uncrated, report it to the shipper immediately. If any
concealed damage is later discovered, report it to the shipper and to your Vertiv representative.
3.7 Packaging Material
All material used to package this unit is recyclable. Save it for future use or dispose of the material appropriately.
3 S ite Preparation and Equipment Handling
19
This page intentionally left blank
20
Vertiv | Li ebert® Mini-Mate2™ Installer/Us er Guide
4 INSTALLATION
Refer to the appropriate installation procedures depending the configuration and options of your Liebert® Mini-Mate2
Thermal Management System.
4.1 Installing Ceiling Mounted EvaporatorsandCondensing Units
WARNING! Risk of ceiling collapse and heavy unit falling. Can cause building and equipment damage, serious
injury or death. Verify that the supporting roof structure is capable of supporting the weight of the unit(s)
and the accessories. See Indoor Unit Weights on page17, for the unit weights. Securely anchor the top ends
of the suspension rods and verify that all nuts are tight.
NOTICE
Risk of leaking water/glycol. Can cause equipment and building damage.
Improper installation, application, and service practices can result in water leakage from the unit. Do not mount
this unit over equipment and furniture that can be damaged by leaking water. Install a water-tight drain pan
with a drain connection under the cooling unit and the ceiling mounted water/glycol condensing unit. Route the
drain line to a frequently-used maintenance sink so that running water can be observed and reported in a
timely manner. Post a sign to alert people to report water flowing from the secondary drain pan. We
recommend installing monitored leak detection equipment for the unit and supply lines and in the secondary
drain pan. Check drain lines periodically for leaks, sediment buildup, obstructions, kinks and/or damage and
verify that they are free running.
4.1.1 Installing Suspension Rods andMounting Ceiling Units
Refer to the Location Considerations on page18 before beginning installation. These instructions apply to evaporators,
indoor air cooled condensing units, and indoor water/glycol cooled condensing units.
NOTE: Follow all national and local building, electrical and plumbing codes.
•The ceiling and ceiling supports of existing buildings may require reinforcements.
•Four 3/8-in. 16 TPI threaded suspension rods are required and field supplied.
•For units with a high-static blower module, two additional suspension rods are required. Hang the evaporator
before raising/attaching the high-static blower module.
•The factory-supplied 3/8-in. 16 TPI hardware kit includes the remaining installation hardware.
•Recommended clearance between ceiling grids and building structural members is the unit’s height plus 3in.
(76mm).
To install the suspension rods:
1.Install the four field supplied 3/8-in.-16 TPI threaded rods by suspending them from suitable building structural
members so that they will align with the four mounting locations on the unit base.
2.Securely anchor the top ends of the suspension rods with field supplied nuts.
3.Make sure all nuts are tight and locked.
4 Installation
21
To lift and install the unit on the rods:
1.Using a suitable lifting device that is rated for the weight of the unit (see Indoor Unit Weights on page17), raise
the unit and pass the threaded rods through the four mounting locations in the unit base.
2.Attach the threaded rods to the flanges using the plain nuts to hold the unit in place as shown in Figure 4.1
below.
3.Slowly lower the lifting device, making sure that the rods securely hold the weight of the unit.
4.Adjust the plain nuts to distribute the weight of the unit evenly by the rods, making sure that the unit does not
rest on the ceiling grid and that the unit is level.
NOTE: Evaporator units must be level to properly drain condensate. This does not apply to condensing units.
5.Use the Nylock nuts to "jam" the plain nuts in place as shown in Figure 4.1 below.
Figure 4.1 Installing Threaded Rods and Hardware of Ceiling Mounted Units
ItemDescriptionItemDescription
13/8-in. threaded rod, field supplied 73/8-in. fender washer
23/8-in. hex nut83/8-in. hex nut
33/8-in. washer93/8-in. Nylock locking nut
4Sleeve10Unit base pan (reference)
5Bracket on unit
6Isolator
22
Vertiv | Li ebert® Mini-Mate2™ Installer/Us er Guide
4.1.2 Close Coupled Installations forIndoorCondensingUnits
You can mount the evaporator and indoor condensing units directly next to each other, close coupled.
Close coupled installations may take advantage of a single point power kit to allow one power feed to provide input for both
evaporator and condensing units.
To Install Close Coupled Indoor Units
1.If you are using a single point power kit:
•Install the single point power box into the evaporator before assembling the condensing unit to the
evaporator and before raising the unit to the ceiling.
•Route power wire flex conduit into condensing unit when raising units to ceiling.
•Refer to the instructions supplied with kit for details
2.Raise the units to the ceiling before connecting them. See Installing Suspension Rods andMounting Ceiling
Units on page21.
3.Align the four bolt holes in the condensing unit with cage nuts provided on the evaporator.
4.Insert rubber spacers and secure with hardware (field provided).
5.Align the refrigerant connections as shown in Figure 4.2 below.
6.Braze the refrigerant connections together as detailed in Refrigerant Piping on page34.
Figure 4.2 Evaporator/Condensing Unit Close Coupling Connections
4 Installation
ItemDescription
1Close-coupled connections
2Spacer between evaporator and condensing unit in close coupled installations
23
4.2 Installing Air Distribution Components for Evaporators
Your indoor units may include a filter box, ducting, plenums, and grilles. Refer to the appropriate installation procedures for
each.
4.2.1 Installing a Plenum
The 2- and 3-ton, non-ducted evaporators can use the optional ceiling mounted plenum to provide four-way air distribution.
The plenum fastens to the bottom of the evaporator. The plenum includes a 16-in.x25-in.x4-in.
(406-mmx635-mmx102-mm) MERV8 filter (per ASHRAE52.2-2007).
To Install the Plenum
1.Make sure that the evaporator is mounted above the bottom of the T-bar supports with at least 30in.(762mm)
clearance from the return air end to the wall (to provide clearance for replacing filter).
2.Check the contents of the plenum kit.
3.Follow the installation instructions included with the plenum kit.
NOTE: Do not operate the unit without filters installed in the return air system.
4.2.2 Installing a Filter Box
The optional filter box attaches directly to the return air opening of the evaporator. The filter box includes one MERV 8 filter
(per ASHRAE 52.2-2007), 20in. x 20 in. x 4 in. (508mmx508mmx102mm).
NOTE: Do not operate the unit without filters installed in return air system.
24
Vertiv | Li ebert® Mini-Mate2™ Installer/Us er Guide
Loading...
+ 102 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.