The information contained in this document is subject to change without notice
and may not be suitable for all applications. While every precaution has been
taken to ensure the accuracy and completeness of this document, Vertiv
assumes no responsibility and disclaims all liability for damages resulting from
use of this information or for any errors or omissions. Refer to other local
practices or building codes as applicable for the correct methods, tools, and
materials to be used in performing procedures not specifically described in this
document.
The products covered by this instruction manual are manufactured and/or sold
by Vertiv. This document is the property of Vertiv and contains confidential
and proprietary information owned by Vertiv. Any copying, use or disclosure of
it without the written permission of Vertiv is strictly prohibited.
Names of companies and products are trademarks or registered trademarks of
the respective companies. Any questions regarding usage of trademark names
should be directed to the original manufacturer.
Technical Support Site
If you encounter any installation or operational issues with your product, check the pertinent section of this
manual to see if the issue can be resolved by following outlined procedures.
Visit https://www.Vertiv.com/en-us/support/ for additional assistance.
Vertiv | Liebert® Min i-Mate™ Install er/User Guide
TABLE OF CONTENTS
1 Important Safety Instructions1
2 Nomenclature and Components7
2.1 Mini-Mate Model Number Nomenclature7
2.2 Component Location9
3 Pre-installation PreparationandGuidelines11
3.1 Planning Dimensions11
3.2 Location Considerations11
3.2.1 Location Considerations for Outdoor Condensing Unit12
3.3 Connections and System Setup12
3.4 Operating Conditions12
3.4.1 Cooling, Humidification, and Dehumidification13
Vertiv | Liebert® Min i-Mate™ Install er/User Guide
1 IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS
This manual contains important safety instructions that should be followed during the installation and maintenance of the
Liebert®Mini-Mate. Read this manual thoroughly before attempting to install or operate this unit.
Only qualified personnel should move, install or service this equipment.
Adhere to all warnings, cautions, notices and installation, operating and safety instructions on the unit and in this manual.
Follow all installation, operation and maintenance instructions and all applicable national and local building, electrical and
plumbing codes.
WARNING! Arc flash and electric shock hazard. Open all local and remote electric power supply disconnect
switches, verify with a voltmeter that power is Off and wear appropriate, OSHA-approved personal protective
equipment (PPE) per NFPA 70E before working within the electric control enclosure. Failure to comply can
cause serious injury or death. Customer must provide earth ground to unit, per NEC, CEC and local codes, as
applicable. Before proceeding with installation, read all instructions, verify that all the parts are included and
check the nameplate to be sure the voltage matches available utility power. The Liebert® controller does not
isolate power from the unit, even in the “Unit Off” mode. Some internal components require and receive
power even during the “Unit Off” mode of the controller. The only way to ensure that there is NO voltage
inside the unit is to install and open a remote disconnect switch. Refer to unit electrical schematic. Follow all
local codes.
WARNING! Risk of electric shock. Can cause equipment damage, injury or death. Open all local and remote
electric power supply disconnect switches and verify with a voltmeter that power is off before working within
any electric connection enclosures. Service and maintenance work must be performed only by properly
trained and qualified personnel and in accordance with applicable regulations and manufacturers’
specifications. Opening or removing the covers to any equipment may expose personnel to lethal voltages
within the unit even when it is apparently not operating and the input wiring is disconnected from the
electrical source.
WARNING! Risk of electric shock. Can cause serious injury or death. The Liebert® iCOM microprocessor does
not isolate power from the unit, even in the "Unit Off" mode. Some internal components require and receive
power even during the "unit off" mode of the Liebert® iCOM control. Open all local and remote electric power
disconnect switches and verify with a voltmeter that power is Off before working on any component of the
system.
WARNING! Risk of electric shock. Can cause injury or death. Open all local and remote electric power-supply
disconnect switches and verify that power is Off with a voltmeter before working within the condensate
pump electrical connection enclosure. The Liebert® iCOM™ does not isolate power from the unit, even in the
“Unit Off” mode. Some internal components require and receive power even during the “Unit Off” mode of the
Liebert®iCOM.
1 Important Safety Instr uctions
1
WARNING! Risk of over-pressurization of the refrigeration system. Can cause explosive discharge of highpressure refrigerant, loss of refrigerant, environmental pollution, equipment damage, injury, or death. This
unit contains fluids and gases under high pressure. Use extreme caution when charging the refrigerant
system. Do not pressurize the system higher than the design pressure marked on the unit's nameplate.
Relieve pressure before cutting into or making connections/disconnections to the piping system. Local
building or plumbing codes may require installing a pressure-relief device in the system. Consult local
building and plumbing codes for installation requirements of additional pressure-relief devices when
isolation valves are field installed. Do not isolate any refrigerant circuit from over-pressurization protection.
Do not close off any field-installed, refrigerant-line isolation valves for repairs unless a pressure-relief valve is
field- installed in the line between the isolation valve and the check valve. The pressure-relief valve must be
rated 5% to 10% higher than the system-design pressure. An increase in ambient temperature can cause the
pressure of the isolated refrigerant to rise and exceed the system-design pressure rating (marked on the
unit nameplate).
WARNING! Risk of improper moving. Can cause equipment damage, injury or death. Use only lifting
equipment that is rated for the unit weight by an OSHA-certified rating organization. The center of gravity
varies depending on the unit size and selected options. The slings must be equally spaced on either side of
the center of gravity indicator. Unit weights are listed in Table 3.2 on page13.
WARNING! Risk of contact with high-speed rotating fan blades. Can cause serious injury or death. Open all
local and remote electric power-supply disconnect switches, verify with a voltmeter that power is off, and
verify that all fan blades have stopped rotating before working in the unit cabinet or on the fan assembly. If
control voltage is applied, the fan motor can restart without warning after a power failure. Do not operate the
unit with any or all cabinet panels removed.
WARNING! Risk of improper wiring, piping, moving, lifting and handling. Can cause equipment damage,
serious injury or death. Installation and service of this equipment should be done only by qualified personnel
who have been specially-trained in the installation of air-conditioning equipment and who are wearing
appropriate, OSHA-approved PPE.
WARNING! Risk of improper wire sizing/rating and loose electrical connections. Can cause overheated wire
and electrical connection terminals resulting in smoke, fire, equipment and building damage, injury or death.
Use correctly sized copper wire only and verify that all electrical connections are tight before turning power
On. Check all electrical connections periodically and tighten as necessary.
WARNING! Risk of improper humidifier-canister maintenance. Can cause smoke and fire, activation of fire
suppression systems, building evacuation, dispatching of fire/rescue equipment and personnel, and
catastrophic canister failure resulting in water leaks, equipment damage, injury, or death. Using a humidifier
canister that has reached the end of it’s service life can be extremely hazardous. If the canister cannot be
replaced immediately at the end of life condition, turn Off the power and water supply to the humidifier and
remove the canister until a replacement canister can be installed. Do not ignore humidifier problem alarms.
Resetting humidifier without addressing cause may result in fire or damage due to leaking water.
2
Vertiv | Liebert® Min i-Mate™ Install er/User Guide
CAUTION: Risk of improper moving, lifting and handling. Can cause equipment damage or injury. Only
properly trained and qualified personnel should work on this equipment. Evaporator fan modules weigh in
excess of 37 lb (17kg). Use proper lifting techniques and wear appropriate, OSHA-approved PPE to avoid
injury and dropping the fan module during removal. Equipment used in handling/lifting, and/or installing the
fan assembly must meet OSHA requirements. Use handling/lifting equipment rated for the weight of the fan
assembly. Use ladders rated for the weight of the fan assembly and technicians if used during installation.
Refer to handling/lifting, and/or installation equipment operating manual for manufacturer's safety
requirements and operating procedures.
CAUTION: Risk of improper moving, lifting and handling. Can cause equipment damage or injury. Only
properly trained and qualified personnel should work on this equipment. Condenser fan modules weigh in
excess of 37 lb (17kg). Use proper lifting techniques and wear appropriate, OSHA-approved PPE to avoid
injury and dropping the fan module during removal. Equipment used in handling/lifting, and/or installing the
fan assembly must meet OSHA requirements. Use handling/lifting equipment rated for the weight of the fan
assembly. Use ladders rated for the weight of the fan assembly and technicians if used during installation.
Refer to handling/lifting, and/or installation equipment operating manual for manufacturer's safety
requirements and operating procedures.
CAUTION: Risk of contact with sharp edges, splinters, and exposed fasteners. Can cause injury. Only
properly trained and qualified personnel wearing appropriate, OSHA-approved PPE should attempt to move,
lift, remove packaging from or prepare the unit for installation.
NOTICE
CAUTION: Risk of contact with hot surfaces. Can cause injury. The electronics housing, humidifier
components, compressor, refrigerant discharge lines, fan motor, and some electrical components are
extremely hot during unit operation. Allow sufficient time for them to cool to a touch-safe temperature before
working within the unit cabinet. Use extreme caution and wear appropriate, OSHA-approved PPE when
working on or near hot components.
CAUTION: Risk of exposure to harmful noise levels. Can cause hearing injury or loss. Depending on the
installation and operating conditions, a sound pressure level greater than 70dB(A) may arise. Take
appropriate technical safety measures. Operating personnel must wear appropriate, OSHA-approved PPE
and observe all appropriate hearing-protection safety requirements.
Risk of improper power supply connection. Can cause equipment damage and loss of warranty coverage.
Prior to connecting any equipment to a main or alternate power source (for example: back-up generator
systems) for start-up, commissioning, testing, or normal operation, ensure that these sources are correctly
adjusted to the nameplate voltage and frequency of all equipment to be connected. In general, power source
voltages should be stabilized and regulated to within ±10% of the load nameplate nominal voltage. Also, ensure
that no three-phase sources are single phased at any time.
1 Important Safety Instr uctions
3
NOTICE
NOTICE
NOTICE
Risk of oil contamination with water. Can cause equipment damage.
Liebert®Mini-Mate systems require the use of POE (polyolester) oil. POE oil absorbs water at a much faster
rate when exposed to air than previously used oils. Because water is the enemy of a reliable refrigeration
system, extreme care must be used when opening systems during installation or service. If water is absorbed
into the POE oil, it will not be easily removed and will not be removed through the normal evacuation process. If
the oil is too wet, it may require an oil change. POE oils also have a property that makes them act as a solvent
in a refrigeration system. Maintaining system cleanliness is extremely important because the oil will tend to
bring any foreign matter back to the compressor.
Risk of improper refrigerant charging. Can cause equipment damage.
Refrigerant charge must be weighed into air-cooled compressorized systems before they are started. Starting
digital scroll compressors without proper refrigerant charging can cause the compressors to operate at less
than 5°F (–15°C) evaporator temperature and at less than 55psig (379kPa). Operation for extended periods at
less than 55psig (379kPa) can cause premature compressor failure.
Risk of clogged or leaking drain lines and leaking water supply lines. Can cause equipment and building
damage.
This unit requires a water drain connection. Drain lines must be inspected at start-up and periodically, and
maintenance must be performed to ensure that drain water runs freely through the drain system and that lines
are clear and free of obstructions and in good condition with no visible sign of damage or leaks.
Improper installation, application and service practices can result in water leakage from the unit. Water
leakage can result in catastrophic and expensive building and equipment damage and loss of critical data
center equipment.
Do not locate unit directly above any equipment that could sustain water damage.
We recommend installing a monitored fluid detection system to immediately discover and report coolant fluid
system and condensate drain line leaks.
4
Vertiv | Liebert® Min i-Mate™ Install er/User Guide
NOTICE
NOTICE
Risk of leaking water/glycol. Can cause equipment and building damage. Improper installation, application,
and service practices can result in water leakage from the unit. Do not mount this unit over equipment and
furniture that can be damaged by leaking water. Install a water-tight drain pan with a drain connection under
the cooling unit and the ceiling mounted water/glycol condensing unit. Route the drain line to a frequently-used
maintenance sink so that running water can be observed and reported in a timely manner. Post a sign to alert
people to report water flowing from the secondary drain pan. We recommend installing monitored leak
detection equipment for the unit and supply lines and in the secondary drain pan. Check drain lines
periodically for leaks, sediment buildup, obstructions, kinks and/or damage and verify that they are free
running.
Risk of piping-system corrosion and freezing fluids. Can cause leaks resulting in equipment and very expensive
building damage. Cooling coils and piping systems are at high risk of freezing and premature corrosion. Fluids
in these systems must contain the proper antifreeze and inhibitors to prevent freezing and premature coil and
piping corrosion. The water or water/glycol solution must be analyzed by a competent local water treatment
specialist before start up to establish the inhibitor and antifreeze solution requirement and at regularly
scheduled intervals throughout the life of the system to determine the pattern of inhibitor depletion.
The complexity of water/glycol solution condition problems and the variations of required treatment programs
make it extremely important to obtain the advice of a competent and experienced water treatment specialist
and follow a regularly scheduled coolant fluid system maintenance program.
NOTICE
Water chemistry varies greatly by location, as do the required additives, called inhibitors, that reduce the
corrosive effect of the fluids on the piping systems and components. The chemistry of the water used must be
considered, because water from some sources may contain corrosive elements that reduce the effectiveness of
the inhibited formulation. Sediment deposits prevent the formation of a protective oxide layer on the inside of
the coolant system components and piping. The water/coolant fluid must be treated and circulating through
the system continuously to prevent the buildup of sediment deposits and or growth of sulfate reducing
bacteria.
Proper inhibitor maintenance must be performed in order to prevent corrosion of the system. Consult glycol
manufacturer for testing and maintenance of inhibitors. Commercial ethylene glycol, when pure, is generally
less corrosive to the common metals of construction than water itself. It will, however, assume the corrosivity of
the water from which it is prepared and may become increasingly corrosive with use if not properly inhibited.
We recommend installing a monitored fluid-detection system that is wired to activate the automatic-closure of
field-installed coolant-fluid supply and return shut-off valves to reduce the amount of coolant-fluid leakage and
consequential equipment and building damage. The shut-off valves must be sized to close-off against the
maximum coolant-fluid system pressure in case of a catastrophic fluid leak
Risk of frozen pipes and corrosion from improper coolant mixture. Can cause water leaks resulting in
equipment and building damage.
When piping or the cooling unit may be exposed to freezing temperatures, charge the system with the proper
percentage of glycol and water for the coldest design ambient temperature. Automotive antifreeze is
unacceptable and must NOT be used in any glycol fluid system. Use only HVAC glycol solution that meets the
requirements of recommended industry practices.
1 Important Safety Instr uctions
5
NOTICE
NOTICE
NOTICE
NOTICE
Risk of no-flow condition. Can cause equipment damage. Do not leave the water/coolant fluid supply circuit in a
no-flow condition. Idle fluid allows the collection of sediment that prevents the formation of a protective oxide
layer on the inside of tubes. Keep unit switched On and water/coolant fluid-supply circuit system operating
continuously.
Risk of improper water supply. Can reduce humidifier efficiency or obstruct humidifier plumbing.
Do not use a hot water source. It will cause deposits that will eventually block the fill-valve opening.
Risk of water backing up in the drain line. Leaking and overflowing water can cause equipment and building
damage.
Do not install an external trap in the drain line. This line already has a factory installed trap inside the cabinet.
Installation of a second trap will prevent drain water flow and will cause the water to overflow the drain pan.
Sagging condensate drain lines may inadvertently create an external trap.
Risk of doorway/hallway interference. Can cause unit and/or structure damage. The unit may be too large to fit
through a doorway or hallway while on the skid. Measure the unit and passageway dimensions, and refer to the
installation plans prior to moving the unit to verify clearances.
NOTICE
Risk of damage from forklift. Can cause unit damage. Keep tines of the forklift level and at a height suitable to
fit below the skid and/or unit to prevent exterior and/or underside damage.
NOTICE
Risk of improper storage. Can cause unit damage.
Keep the unit upright, indoors and protected from dampness, freezing temperatures and contact damage.
Agency Listed
Standard 60-Hz units are CSA Certified to the harmonized U.S. and Canadian product safety standard CSA C22.2 No
236/UL 1995 for “Heating and Cooling Equipment” and are marked with the CSA c-us logo.
6
Vertiv | Liebert® Min i-Mate™ Install er/User Guide
2 NOMENCLATURE AND COMPONENTS
This section describes the model number for Liebert® Mini-Mate units and components.
2.1 Mini-Mate Model Number Nomenclature
The tables below describe each digit of the 25-digitconfigurationnumber. The 14-digit model number consists of the first
10 digits and last 4 digits of the configuration number.
Model Number Digit Definitions below describes each digit of the model number.
Table 2.1 Mini-Mate 25-Digit Configuration Number
ModelNumber Digits 1 to 10ModelDetailsModelNumber Digits11to14
1234 5678 9101 112131415161 71819202122232425
MT0 6 0H E 1A0SH20D0U0P00A###
Table 2.2 Model Number Digit Definitions
Digit andDescription
Digits 1 and 2 = Unit Family
MT = Mini-Mat e Ceil ing System
Digits 3, 4, 5 = Nominal Cooli ng C apaci ty
036 = 36kBtuh
048 = 48kBtuh
060 = 60 kBtuh
Digit 6 = Air Di rect ion and Discharge
H = H oriz onta l air flow
Digit 7 = System ty pe
E = Split System evapora tor
Digit 8 = Fan type
1 = Dir ect Dri ve EC mot or (va ria ble-speed)
Digit 9 = Supply power
A = 460V / 3ph / 60 Hz
B = 575V / 3ph / 60 Hz (0 48 a nd 060 models only )
C = 208V / 3ph / 60Hz (0 48 and 060 models only)
D = 230V / 3ph / 60Hz (0 48 and 060 models only)
P = 20 8-230 /1ph/60Hz (0 36 model only)
Y = 20 8-230 /3ph/60 Hz (0 36 model onl y)
Digit 10 = Evaporator T ype
0 =Spli t System evapora tor
Digit 11 = Humidifier
0 = No humidifier
S = Steam-gen caniste r humidifier
2 Nomenclature an d Components
7
Table 2.2 Model Number Digit Definitions (continued)
Digit andDescription
Digit 12 = Display t ype
H = 9-i n. r emote display, I ntell iSlot -based monitori ng ( 048 and 0 60 models onl y)
1 = 9-in. remote display , iCOM-based monitor ing (036 model only)
Digit 13 = R eheat
0 = No reheat
2 = Elect ri c reheat
5 = SCR reheat ( 048 and 0 60 models only )
Digit 14 = Coi l, Valve, Pr essure
0 = Split Sy stem evaporat or
Digit 15 = H igh-v olta ge options
D = Non-locki ng di sconnect, 5k SCCR ( 048 and 0 60 models onl y)
L = Locking disconnect, 5kA SCCR (0 36 model only)
M = Locking disconnect, 65k SCCR (0 48 a nd 0 60 models onl y)
Digit 16 = Low-vol tage options
0 = None
L = Low vol tage te rminal pac kage (LVTP)
Digit 17 = Monitoring Cards
0 = No card, Intel liSlot onl y (048 and 0 60 models onl y)
U = IS-UNITY- DP card, factor y-i nstall ed (048 a nd 0 60 models only)
B = BACnet, Modbus, SNMP using iCOM board (036 model only)
Digit 18 = Sensors
0 = None
S = Smoke sensor
H = H igh Temperat ure sensor
F = Smoke and high temper atur e sensor
Digit 19 = P acka ging
P = Domesti c
C = Wood cr at e export
Digits 20, 21 = Future use
Digit 22 = Factory configurati on code
A = No SFA’s ( Any Alpha lett er exc ept S)
S = SFA
Digit23-25 = Factory Configuration Number
8
Vertiv | Liebert® Min i-Mate™ Install er/User Guide
2.2 Component Location
The unit component locations are described in the submittal documents included in the Submittal Drawings on page63.
The following tables list the relevant documents by number and title.
Table 2.3 Component Location Drawings
Document NumberTitle
DPN004808Evaporator Unit, 3 Ton
DPN004179Evaporator Unit, 4 Ton and 5 Ton
2 Nomenclature an d Components
9
This page intentionally left blank
10
Vertiv | Liebert® Min i-Mate™ Install er/User Guide
3 PRE-INSTALLATION PREPARATIONANDGUIDELINES
NOTE: Before installing unit, determine whether any building alterations are required to run piping, wiring and duct
work. Follow all unit dimensional drawings and refer to the submittal engineering dimensional drawings of individual
units for proper clearances.
Refer to Model Number Digit Definitions on page7, and submittal drawings to determine the type of system being installed
and anticipate building alterations, piping and duct work needed.
The unit dimensions, pipe connection locations, and piping schematics are described in the submittal documents included
in the Submittal Drawings on page63.
•Confirm that the room is properly insulated and has a sealed vapor barrier.
•For proper humidity control, keep outside or fresh air to an absolute minimum (less than 5% of total air
circulated in the room).
•Install the units as close as possible to the largest heat load.
•Allow at least the minimum recommended clearances for maintenance and service. See the appropriate
submittal drawings for dimensions.
•We recommend installing a water detection system. Contact your Vertiv representative for information.
3.1 Planning Dimensions
The unit dimensions described in the submittal documents included in the Submittal Drawings on page63.
The following table lists the relevant documents by number and title.
Table 3.1 Dimension Planning Drawings
Document NumberTitle
DPN004800Cabinet dimensions, 3 ton DX m odule
DPN004055Cabinet dimensions, 4 tonand 5 ton DX m odule
Filter and Ducting O ptions
DPN004805Dimensional data, filter box and duct flange, 3 ton
DPN004807Dimensional data, air distributionplenum 3 ton
DPN004166Dimensional data, filter box and duct flange, 4 and 5 ton
DPN004842Dimensional data, bottom discharge grille, 4 and 5 ton
3.2 Location Considerations
When determining installation locations, consider that these units contain water and that water leaks can cause damage to
sensitive equipment and furniture below.
The evaporator is usually mounted above the dropped ceiling and must be securely mounted to the roof structure. For
ducted systems, the evaporator may be located in a different room. See Guidelines for Ducted Systems on page37 for
additional guidelines. For a split system with an air cooled, outdoor condensing unit, the condensing unit may be mounted
on the roof or remotely in an outdoor area. See Location Considerations for Outdoor Condensing Unit on the next page for
additional guidelines.
Refer to Refrigerant Line Sizes and Equivalent Lengths on page18 for maximum refrigerant line lengths.
3 Pr e-inst allation Preparationand Guidelin es
11
The ceiling and ceiling supports of existing buildings may require reinforcement. See Mini-Mate Unit Weights on the facing
page. Be sure to follow all applicable national and local codes.
For a split system with an indoor condensing unit, the condensing unit may be:
•Installed above the suspended ceiling near the evaporator.
•In any remote indoor area, subject to the requirements detailed in Table 4.3 on page17.
Refer to Refrigerant Line Sizes and Equivalent Lengths on page18 for maximum refrigerant line lengths.
Install the ceiling mounted unit over an unobstructed floor space if possible. This will allow easy access for routine
maintenance or service. Do not attach additional devices (such as smoke detectors, etc.) to the housing, as they could
interfere with the maintenance or service.
Do not install units in areas where normal unit operating sound may disturb the working environment.
3.2.1 Location Considerations for Outdoor Condensing Unit
Observe the following when planning the installation of the outdoor unit:
•To ensure a satisfactory air supply, locate air cooled condensing units in an environment with clear air, away
from loose dirt and foreign matter that may clog the coil.
•Condensing units must not be located in the vicinity of steam, hot air, or fume exhausts or closer than 18 inches
from a wall, obstruction or adjacent unit.
•Avoid areas where heavy snow will accumulate at air inlet and discharge locations.
•The condensing unit should be located for maximum security and maintenance accessibility. Avoid groundlevel sites with public access. Install a solid base, capable of supporting the weight of the condensing unit.
•The base should be at least 2in. (51mm) higher than the surrounding grade and 2 in. (51mm) larger than the
dimensions of the condensing unit base. For snowy areas, a base of sufficient height to clear snow accumulation
must be installed.
Before beginning, refer to Piping and Refrigerant Requirements on page15 for unit placement, piping guidelines, and
refrigerant charge requirements for your system.
3.3 Connections and System Setup
•The unit requires a drain, which must comply with all applicable codes. This drain line may contain boiling
water. See Drain Line Installation Requirements on page28, for details.
•Electrical service is required for all models. Electrical service must conform to national and local electrical
codes. See equipment nameplate for details.
•Plan the routing of wiring, piping, and duct work to the unit. Refer to the appropriate piping connection location
drawings, piping schematics, and electrical connection drawings for your system in .
NOTE: Seal openings around piping and electrical connection to prevent air leakage. Failure to do so could reduce the
unit’s cooling performance.
3.4 Operating Conditions
The Liebert® Mini-Mate must be operated in a conditioned space within the operating envelope that ASHRAE recommends
for data centers. Operating the Mini-Mate outside of this envelope can decrease equipment reliability. Refer to ASHRAE’s
publication, “Thermal Guidelines for Data Processing Environments.”
12
Vertiv | Liebert® Min i-Mate™ Install er/User Guide
3.4.1 Cooling, Humidification, and Dehumidification
For operation in the Cooling, Humidification, or Dehumidification modes, the Liebert® Mini-Mate unit’s return air
requirements for proper unit operation are:
•Maximum dew point of 59°F (15°C)
•Minimum 65°F (20°C)DB
•Maximum 85°F (29.4°C) DB
3.4.2 Heating
For operation in the Heating mode, the Liebert® Mini-Mate unit’s return air requirements for proper unit operation are:
•Maximum humidity: less than 80% RH and less than 64°F (17.8°C) dew point.
•Maximum dry bulb of 80°F (27°C)
3.5 Mini-Mate Unit Weights
Table 3.2 Mini-Mate Unit Weights
Model#Weight, lb(kg)
MT036328 (149)
MT048*498 (226)
MT060*498 (226)
* for 57 5-V units, add 32lb (14.5kg)
3.6 Equipment Inspection and Handling
SAFETY INFORMATION
WARNING! Risk of improper moving, lifting, or handling of the unit. Can cause equipment damage, injury or
death. Read all of the following instructions and verify that all lifting and moving equipment is rated for the
weight of the unit before attempting to move, lift, remove packaging from or prepare the unit for installation.
Unit weights are specified in section Mini-Mate Unit Weights above.
CAUTION: Risk of contact with sharp edges, splinters, and exposed fasteners. Can cause injury. Only
properly trained and qualified personnel wearing appropriate, OSHA-approved PPE should attempt to move,
lift, remove packaging from or prepare the unit for installation.
NOTICE
Risk of doorway/hallway interference. Can cause unit and/or structure damage. The unit may be too large to fit
through a doorway or hallway while on the skid. Measure the unit and passageway dimensions, and refer to the
installation plans prior to moving the unit to verify clearances.
NOTICE
Risk of damage from forklift. Can cause unit damage. Keep tines of the forklift level and at a height suitable to
fit below the skid and/or unit to prevent exterior and/or underside damage.
3 Pr e-inst allation Preparationand Guidelin es
13
NOTICE
Risk of improper storage. Keep the unit upright, indoors and protected from dampness, freezing temperatures
and contact damage.
Upon arrival of the unit and before unpacking:
•Verify that the labeled equipment matches the bill of lading.
•Carefully inspect all items for visible or concealed damage.
•Report damage immediately to the carrier and file a damage claim with a copy sent to Vertiv or to your sales
representative.
Equipment Recommended for Handling the Unit:
•Forklift
•Pallet jack
14
Vertiv | Liebert® Min i-Mate™ Install er/User Guide
4 PIPING AND REFRIGERANT REQUIREMENTS
All fluid and refrigeration connections to the unit, with the exception of the condensate drain and humidifier supply line, are
sweat copper. Factory installed piping brackets must not be removed. Field installed piping must be installed in
accordance with local codes and must be properly assembled, supported, isolated, and insulated. Avoid piping runs
through noise sensitive areas, such as office walls and conference rooms.
Refer to specific text and detailed diagrams in this manual for other unit specific piping requirements.
The following pipe connections are required:
•Refrigerant piping connections between the evaporator unit and the condensing unit.
•A drain line from the unit or a drain line from the optional condensate pump (if applicable).
•A drain line from the secondary drain pan (if applicable).
•A water supply line to the optional humidifier (if applicable).
•On water/glycol systems: connections to a water or glycol loop. See Water/Glycol Loop Piping Guidelines on
page21, for additional requirements.
The pipe connection locations, piping general arrangement, and schematics are described in the submittal documents
included in the Submittal Drawings on page63.
The following tables list the relevant documents by number and title.
Table 4.1 Piping General Arrangement Drawings
Document NumberTitle
Air Cooled System
DPN004060Pipingarrangement, 3, 4 and 5 ton split system
Water/Glycol CooledSystem
DPN004893Piping arrangement, 3, 4 and 5 ton split system
Table 4.2 Piping Connection Drawings
Document NumberTitle
DPN004801Primary connection loca tions, 3 ton DX m odule
DPN004806Condensate pump c onnection locations, 3 ton
DPN004056Primary connection locations, 4 ton and 5 ton DX module
DPN004077Condensate pump connection locations, 4 ton and 5 ton
4.1 Refrigerant Piping and Charging
WARNING! Risk of over-pressurization of the refrigeration system. Can cause explosive discharge of highpressure refrigerant, loss of refrigerant, environmental pollution, equipment damage, injury, or death. This
unit contains fluids and gases under high pressure. Use extreme caution when charging the refrigerant
system. Do not pressurize the system higher than the design pressure marked on the unit's nameplate.
4 Pipin g and Refrigeran t Requirements
15
Consult local building and plumbing codes for installation requirements of additional pressure relief devices when isolation
valves are field installed. Do not isolate any refrigerant circuits from over-pressurization protection.
NOTICE
Risk of oil contamination with water. Can cause equipment damage.
Liebert®Mini-Mate systems require the use of POE (polyolester) oil. POE oil absorbs water at a much faster
rate when exposed to air than previously used oils. Because water is the enemy of a reliable refrigeration
system, extreme care must be used when opening systems during installation or service. If water is absorbed
into the POE oil, it will not be easily removed and will not be removed through the normal evacuation process. If
the oil is too wet, it may require an oil change. POE oils also have a property that makes them act as a solvent
in a refrigeration system. Maintaining system cleanliness is extremely important because the oil will tend to
bring any foreign matter back to the compressor.
•Evaporators and condensing units ship with an inert gas holding charge. Do not vent the evaporator and
condensing unit until all refrigerant piping is in place, ready for connection to the unit and condensing unit.
•Use copper piping with a brazing alloy with a minimum temperature of 1350°F (732°C), such as Sil-Fos. Avoid
soft solders, such as 50/50 or 95/5.
•Use a flow of dry nitrogen through the piping during brazing to prevent formation of copper oxide scale inside
the piping. When copper is heated in the presence of air, copper oxide forms. POE oils will dissolve these
oxides from inside the copper pipes and deposit them throughout the system, clogging filter driers and
affecting other system components.
•A pure dry nitrogen flow of 1-3 ft3/min (0.5-1.5 l/s) inside the pipe during brazing is sufficient to displace the air.
Control the flow using a suitable measuring device.
•Ensure that the tubing surfaces to be brazed are clean and that all burrs have been removed from the ends of
the tubes.
•Ensure that all loose material has been cleaned from inside the tubing before brazing.
•Protect all refrigerant line components within 18in. (460mm) of the brazing site by wrapping them with a wet
cloth or with a suitable heat sink compound.
•Isolate piping from building using vibration isolating supports.
•When sealing openings in walls and to reduce vibration transmission, use a soft, flexible material to pack
around the tubes to prevent tube damage.
•When installing remote condensing units above the evaporator, the suction gas lines should be trapped at the
evaporator. These traps will retain refrigerant oil in the off cycle. When the unit starts, oil in the traps is carried
up the vertical risers and returns to the compressors. For rises over 25ft (7.6m), trap every 20ft (6m)or
evenly-divided.
•Consult factory if piping run exceeds 150ft(46m) equivalent length.
•Keep piping clean and dry, especially on units with R-410A refrigerant.
•Avoid piping runs through noise sensitive areas.
•Do not run piping directly in front of discharge air stream.
•Refrigerant oil – do not mix oil types.
Refer to ASHRAE Refrigeration Handbook for general, good practice refrigeration piping.
NOTE: All indoor and outdoor suction line piping must have 1/2 in. minimum of insulation. All outdoor insulation must
be UV and ozone resistant.
16
Vertiv | Liebert® Min i-Mate™ Install er/User Guide
NOTE: Proper safety equipment and proper refrigeration tools are required when working with R-410A refrigerant.
Check unit serial tag for correct refrigerant type before topping off or recharging a system.
NOTE: Refrigerant R-410A uses a POE (polyolester) lubricant. The refrigerant must be introduced and charged from
the cylinder only as a liquid.
NOTE: When installing field piping, you must take care to protect all refrigerant lines from the atmosphere especially
when using refrigerants with POE oils. Do not allow the piping to stand open to air for more than 15minutes. Units
designed for R-410A have a compressor that contains POEoil, which quickly absorbs water from the air. The longer
that the refrigerant piping is left open to air, the harder it will be to fully evacuate the system. If left open too long, the
POE oil may require replacement to achieve the required vacuum level.
•Refer to Refrigerant Line Sizes and Equivalent Lengths on the next page, for recommended refrigerant piping
sizes based on equivalent pipe lengths.
•Refer to the condensing unit's Installer/User Guide for the complete charging procedure of the system.
4.1.2 Piping when Condensing Unit is Above or Below Evaporator
Refer to Table 4.3 below for the maximum vertical rise/fall between condensing unit and evaporator.
When installing remote condensing units above the evaporator, trap the suction gas line at the evaporator as shown in
Figure 4.1 below. Traps recommended at the base of riser exceeding 5 ft. (1.5 m) and every 20 ft. (6 m) of vertical rise. This
trap will retain refrigerant oil during the "Off" cycle. When the unit starts, oil in the trap is carried up the vertical riser and
returns to the compressor.
When installing remote condensing units below the evaporator, trap the suction gas line with an inverted trap the height of
the evaporator as shown in the following figure. This prevents refrigerant migration to the compressor during "Off" cycles.
Table 4.3 Pipe Length and Condensing Unit Elevation Relative to Evaporator
Maximum Equivalent Pipe Length, ft. (m)
150 (45)50 (15)15 (4.6)
Maximum CondensingUnit Level Above
Evaporator, ft. (m)
Maximum CondensingUnit Level Below
Evaporator, ft. (m)
Figure 4.1 Refrigerant Piping Diagram When Condenser is Above or Below Evaporator
NOTE: Any horizontal pipe must be pitched down toward the condensing unit at a minimum rate of 1/2 in. (13 mm) per
10 ft. (3 mm) to assure oil return to compressor.
4 Pipin g and Refrigeran t Requirements
17
4.2 Refrigerant Line Sizes and Equivalent Lengths
The following tables list the information required to field install the refrigerant piping for the system.
Table 4.4 Recommended Refrigerant Line Sizes, O.D.cubyEquivalentLength
3 Ton4 Ton5 Ton
Equivalent Length, ft (m)
50 (15)7/81/27/81/21-1/81/2
75 (23)7/81/21-1/81/21-1/85/8
100 (30)7/81/21-1/85/81-1/85/8
125 (38)7 /81/21-1/8¹5/81-1/85/8
150 (45)7/81/21-1/85/81 -1/85/8
Consult factor y for proper line sizing for runs l onger than maximum equival ent length shown.
1.Use one li ne size smaller on suction lines for v ert ica l risers.
Source: DPN000 788 Rev. 13
SuctionLiquidSuctionLiquidSuctionLiquid
18
Vertiv | Liebert® Min i-Mate™ Install er/User Guide
4.2.1 Refrigerant Charge Requirements forAir Cooled Systems
To calculate the charge requirements:
1.Determine the charge for your units by model number from the following tables.
2. Determine the charge for the piping by line size and length.
3. Add these all together to obtain the total refrigerant charge for your system.
Table 4.7 PFD Condensing Unit R-410A Refrigerant Charge
Model#Charge, lb(kg)
PFD037A-*L113.4 (6.1)
PFD037A-*H127 (12.2)
PFD054A-*L127 (12.2 )
PFD067A-*L127 (12.2)
PFDZ67A-*L157 (25.8)
PFD067A-*H157 (25.8)
4 Pipin g and Refrigeran t Requirements
19
4.2.2 Additional Oil Requirements for Digital Scroll Compressors
NOTICE
Risk of improper compressor lubrication. Can cause compressor and refrigerant system damage.
Failure to use oil types, viscosities and quantities recommended by the compressor manufacturer may reduce
compressor life and void the compressor warranty.
•Do not mix polyolester (POE) and mineral-based oils.
•Do not mix oils of different viscosities.
•Consult your Vertiv sales representative, visit https://www.Vertiv.com/en-us/support/, or contact the
compressor manufacturer if questions arise.
System charges may require additional oil charge to be added. See Table 4.8 below, for the amount required for various
system charge levels.
After the system has been fully charged with refrigerant, use a hand pump to add the additional oil at the suction side of the
system while the system is running.
On the tag marked “Oil Added Field Service Record,” attached to each compressor, record the date the oil was added and
the amount of oil added.
Table 4.8 Additional Oil Required per Refrigerant
Charge
3 Ton4 Ton5 Ton
Refrigerant System
Charge per Circuit,
lb (kg)*
<40 (18.1)000
40 (18.1)4 (120)4 (120)6 (180)
50 (22.7)6 (180)6 (180)9 (270)
60 (27.2)8 (240)8 (240)12 (350)
70 (31.8)10 (300)10 (300)15 (440)
80 (36.3)12 (350)12 (350)18 (530)
* System Charge = indoor unit + condensing unit + refrigerant lines.
For system charges over 80lb. (36.3 kg), consult your Vertiv representative.
Source: DP N003950 Rev 5.
Additional Oil Required Per Circuit, oz (ml)
Table 4.9 Compressor Oil types for R-410A Refrigerant
Compressor TypeOil Type
Copeland Digital ScrollPOE Oil - ISO 32 Centistoke Viscosity
1. Use CopelandP OE Oil ULTRA 32-3MAF or other Copeland approved oils.
Source: DP N003950. Rev. 5
1
20
Vertiv | Liebert® Min i-Mate™ Install er/User Guide
4.3 Water/Glycol Loop Piping Guidelines
WARNING! Risk of improper piping installation, leak checking, fluid chemistry and fluid maintenance can
cause equipment damage and personal injury. Installation and service of this equipment should be done only
by qualified personnel who have been specially trained in the installation of air conditioning equipment and
who are wearing appropriate, OSHA approved PPE.
NOTICE
Risk of frozen pipes and corrosion from improper coolant mixture. Can cause water leaks resulting in
equipment and building damage.
When the cooling unit or piping may be exposed to freezing temperatures, charge the system with the proper
percentage of glycol and water for the coldest design ambient temperature. Automotive antifreeze is
unacceptable and must NOT be used in any glycol fluid system. Use only HVAC glycol solution that meets the
requirements of recommended industry practices. Do not use galvanized pipe.
NOTICE
Risk of piping system corrosion and freezing fluids. Can cause leaks resulting in equipment and expensive
building damage. Cooling coils and piping systems are at high risk of freezing and premature corrosion. Fluids
in these systems must contain an inhibitor to prevent premature corrosion.
The system coolant fluid must be analyzed by a competent fluid treatment specialist before start up to
establish the inhibitor level and evaluated at regularly scheduled intervals throughout the life of the system to
determine the pattern of inhibitor depletion. The fluid complexity and variations of required treatment
programs make it extremely important to obtain the advice of a competent and experienced fluid treatment
specialist and follow a regularly scheduled coolant fluid system maintenance program.
Fluid chemistry varies greatly as do the required additives, called inhibitors, that reduce the corrosive effect of
the fluids on the piping systems and components.
The chemistry of the coolant fluid used must be considered, because some sources may contain corrosive
elements that reduce the effectiveness of the inhibited formulation. Sediment deposits prevent the formation of
a protective oxide layer on the inside of the coolant system components and piping. The coolant fluid must be
treated and circulating through the system continuously to prevent the buildup of deposits and/or growth of
bacteria. Proper inhibitor maintenance must be performed to prevent corrosion of the system.
Consult fluid manufacturer for testing and maintenance of inhibitors.
Commercial grade coolant fluid is generally less corrosive to the common metals of construction than water
itself. It will, however, assume the corrosivity of the coolant fluid from which it is prepared and may become
increasingly corrosive with use if not properly inhibited.
Vertiv recommends installing a monitored fluid detection system that is wired to activate the automatic
closure of field installed coolant fluid supply and return shut-off valves to reduce the amount of coolant fluid
leakage and consequential equipment and building damage. The shut-off valves must be sized to close off
against the maximum coolant fluid system pressure in case of a catastrophic fluid leak.
4 Pipin g and Refrigeran t Requirements
21
NOTICE
Risk of no-flow condition. Can cause equipment damage.
Do not leave the water/coolant fluid supply circuit in a no-flow condition. Idle fluid allows the collection of
sediment that prevents the formation of a protective oxide layer on the inside of tubes. Keep unit switched On
and water/coolant fluid supply circuit system operating continuously.
•Use copper piping with a brazing alloy with a minimum temperature of 1350°F (732°C), such as Sil-Fos. Avoid
soft solders, such as 50/50 or 95/5.
•Follow local piping codes and safety codes.
•Qualified personnel must install and inspect system piping.
•The water/glycol cooled system will operate in conjunction with a cooling tower, city water or drycooler.
•Contact a local water consultant regarding water quality, corrosion protection and freeze protection
requirements.
•Install manual shut-off valves at the supply and return line to each unit to permit routine service and
emergency isolation of the unit.
•When the fluid quality is poor, we recommend installing a 16-20# mesh Y-strainer filter in the supply line to
extend the service life of the coaxial condensers. These filters must be easily replaced or cleaned.
•Install a monitored, fluid-detection system that is wired to activate the automatic closure of field installed
coolant fluid supply and return shut-off valves to reduce the amount of coolant fluid leakage and consequential
equipment and building damage. The shut-off valves must be sized to close off against the maximum coolant
fluid system pressure in case of a catastrophic fluid leak.
Coolant Regulating Valve Requires No Adjustment
Water/glycol cooled units include a coolant flow regulating valve that is factory adjusted and should not need field
adjustment.
Contact Vertiv technical support before making any adjustments.
4.3.1 Refrigerant Charge Requirements forWater/Glycol Cooled Systems
To calculate the charge requirements:
1.Determine the charge for your units by model number from the following tables.
2. Determine the charge for the piping by line size and length.
3. Add these all together to obtain the total refrigerant charge for your system.
4.3.2 Evacuation and Leak Testing Water/Glycol Cooled Systems
For proper leak check and evacuation, you must open all system valves and account for all check valves, see Figure 4.2 on
the next page.
4 Pipin g and Refrigeran t Requirements
23
Figure 4.2 Valves and Connections for Water/Glycol Condensing Unit
ItemDescription
1Suction line
2Schrader port with v alve core
3Apply a manifold gauge hose on the suction line and discharge line Schrader port.
42-stage scroll compressor
5High-pressure switch
6Tube-in-tube condenser
7Water/Glycol supply line
82-way water regulating va lve
9Water/Glycol return line
10Fluid supply to unit
11Fluid return from unit
12Hose bibs (required, field supplied)
13Shut-off valves (required, field supplied)
14Liquidline
24
Vertiv | Liebert® Min i-Mate™ Install er/User Guide
ItemDescription
153-way water regulating valve (optional)
To evacuate and leak test the system:
1.Connect a manifold gauge hose on the discharge and suction line Schrader ports, open the service valve, and
place a 150Psig(1034kPa)charge of dry nitrogen with a tracer of refrigerant, then check the system for leaks
with a suitable leak detector.
2. After completion of leak testing, release the test pressure, (observe local code) and pull an initial deep vacuum
of 500microns on the system with a suitable pump.
3. After fourhours, check the pressure readings and, if they have not changed, break vacuum with dry nitrogen.
Pull a second and third vacuum to 500 microns or less. Re-check the pressure after twohours.
When the three checks are complete, proceed to Charging Water/Glycol Cooled Systems on the next page.
4 Pipin g and Refrigeran t Requirements
25
Loading...
+ 65 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.