Vertiv Liebert XDP User Manual

Liebert® XDP™
50 & 60 Hz, 160kW Nominal Capacity; ModelRevision5orhigher
User Manual
Technical Support Site
If you encounter any installation or operational issues with your product, check the pertinent section of this manual to see if the issue can be resolved by following outlined procedures. For additional assistance, visit https://www.VertivCo.com/en-us/support/
Important Safety Instructions 1
1 Product Description 5
1.1 General Product Information 5
1.1.1 Product/System Description 5
1.1.2 Minimum Load 5
1.2 Equipment Inspection 6
1.3 Equipment Handling 6
1.3.1 Handling the Liebert XDP While it is on Skid and Packaged 6
1.3.2 Unpacking the Liebert XDP 7
1.3.3 Removing the Unit from the Skid Using a Forklift 8
1.3.4 Removing the Unit from the Skid using Rigging 8
1.3.5 Moving the Liebert XDP Using Piano Jacks 9
1.3.6 Removing the Unit from the Piano Jacks 10
2 Installation 11
2.1 Mechanical Considerations 11
2.1.1 Positioning the Liebert XDP 11
2.2 Electrical Considerations 12
2.2.1 Connecting High-Voltage Cables 13
2.2.2 External Pump Overloads 16
2.2.3 Extra Low Voltage (ELV) Connections 18
2.2.4 DIP Switch and Jumper Settings for Remote Sensors 20
2.3 Field Connections—Optional for All Units 21
2.4 Remote Sensor Installation—Proper Placement 22
3 Piping 25
3.1 European Union Fluorinated Greenhouse Gas Requirements 25
3.2 Connection Sizes 25
3.2.1 Recommended Pipe Size 25
3.3 Liebert XDP Interconnection with Liebert XD Cooling Modules 26
3.4 Piping Installation Methods 26
3.4.1 Piping Installation—R-134a Pumped Circuit 26
3.4.2 Piping Mains 27
3.4.3 Bypass Flow Controller 27
3.5 Piping Details—Shutoff/Isolation Valves 29
3.5.1 Evacuation and Leak Check—R-134a Pumped Circuit 30
3.5.2 Insulation 30
3.6 Filling the Pumped Circuit—R-134a 31
3.6.1 Calculating Refrigerant Charge—Example 33
3.7 Checklist for Proper Installation 34
4 Liebert iCOM Control—Firmware Version XP1.00.010.STD 35
4.1 Liebert iCOM Components and Functions 35
Vertiv | Liebert® XDP™ User Manual | 3
4.2 Display Lamp Indicators 37
4.3 Navigating Through the Liebert iCOM Display 37
4.3.1 Accessing Menus and Settings 38
4.3.2 Cooling Module Overview 38
4.3.3 Entering the Password 39
4.4 Changing Liebert iCOM’s Display Settings 40
4.5 Changing Operational Settings 41
4.6 Graphical Data Record 41
4.7 Liebert iCOM User Menu Icons and Legend 42
4.8 Liebert iCOM User Menu Screens 43
4.9 Liebert iCOM Service Menu Icons and Legend 52
4.10 Liebert iCOM Service Menu Screens 53
5 Start the Liebert XDP with Liebert iCOM 77
5.1 Checklist for Liebert XDP Startup 77
5.2 Starting the Liebert XDP with Liebert iCOM Controller 78
6 Alarm Descriptions and Solutions 81
6.1 Alarm Descriptions 81
6.2 Warning Descriptions 83
6.3 System Shutdown Causes 83
7 Troubleshooting 85
8 Maintenance 88
8.1 Fluorinated Greenhouse Gas Requirements 88
9 Specifications 89
Vertiv | Liebert® XDP™ User Manual | 4

IMPORTANT SAFETY INSTRUCTIONS

SAVE THESE INSTRUCTIONS
This manual contains important safety instructions that should be followed during the installation and maintenance of the Liebert XDP. Read this manual thoroughly before attempting to install or operate this unit.
Only qualified personnel should move, install or service this equipment.
Adhere to all warnings, cautions, notices and installation, operating and safety instructions on the unit and in this manual. Follow all operating and user instructions.
Follow all local codes.
WARNING! Risk of arc flash and electric shock. Can cause equipment damage or death.
Disconnect all local and remote electric power supplies and wear protective equipment per NFPA 70E before working within electric control enclosure. Failure to comply can cause serious injury or death.
Customer must provide earth ground to unit, per NEC, CEC and local codes, as applicable.
Before proceeding with installation, read all instructions, verify that all the parts are included and check the nameplate to be sure the voltage matches available utility power.
The Liebert iCOM microprocessor does not isolate power from the unit, even in the Unit Off mode. Some internal components require and receive power even during the Unit Off mode of Liebert iCOM control.
The line side of the disconnect switch on the front of the unit contains live high-voltage.
The only way to ensure that there is NO voltage inside the unit is to install and open a remote disconnect switch. Refer to unit electrical schematic.
Follow all local codes.
WARNING! Risk of unit falling over. Can cause property damage, injury or death.
The XDP is top-heavy. Use extreme caution and care when moving and installing this unit.
Vertiv | Liebert® XDP™ User Manual | 1
CAUTION: Risk of piping and component rupture. Can cause equipment damage or injury.
System is pressurized. Relieve pressure through access valve before working on unit. System is pressurized. Relieve pressure through access valve before working on unit. Closing service valves may isolate liquid refrigerant, causing high pressure and rupture of piping. Do not close valves without following recommended procedures for repair, maintenance and replacement of components. Install pressure relief valves in field piping that may become isolated by service valves.
Risk of improper installation and/or startup. Can cause injury, equipment damage, or warranty cancellation. Read and follow completely the installation and start up instructions that are factory supplied with the unit
CAUTION: Risk of contact with hot surfaces. Can cause injury.The pump motors are extremely hot during unit operation. Allow sufficient time for them to cool before working within the unit cabinet. Use extreme caution and wear protective gloves and arm protection when working on or near the pump motors.
CAUTION: Risk of sharp edges, splinters and exposed fasteners. Can cause injury.Only properly trained and qualified personnel wearing appropriate safety headgear, gloves, shoes and glasses should attempt to move, lift, remove packaging from or prepare the unit for installation.
NOTICE
NOTICE
NOTICE
Risk of leaking chilled water lines. Can cause equipment and building damage.
Lines and joints must be inspected regularly. Improper installation, application and service practices can result in water leakage from the unit. Water leakage can result in severe property damage and loss of critical data center equipment. Do not locate unit directly above any equipment that could sustain water damage. Vertiv recommends installing monitored leak detection equipment for the unit and supply and return lines.
Risk of overhead interference. Can cause unit and/or building damage.
The unit may be too tall to fit through a doorway while on the skid. Measure the unit and doorway heights and refer to the installation plans to verify clearances prior to moving the unit.
Risk of damage from forklift. Can cause unit damage.
Keep the forklift tines level and at a height suitable to fit below the skid and unit to prevent exterior and underside damage.
Vertiv | Liebert® XDP™ User Manual | 2
NOTICE
Risk of improper storage. Can cause unit damage.
Keep the Liebert XDP upright, indoors and protected from dampness, freezing temperatures and contact damage.
NOTE: This document is intended to be used together with site specific documentation and documentation for other parts of the system (heat rejection devices and cooling modules).
NOTE: Before any action that could cause a disturbance in the XD system’s cooling function is begun, the facility manager MUST be informed. In addition, after the action is taken and the work is finished, the facility manager MUST be informed.
Figure 1.1 Model number nomenclature
Vertiv | Liebert® XDP™ User Manual | 3
This page intentionally left blank.
Vertiv | Liebert® XDP™ User Manual | 4

1 PRODUCT DESCRIPTION

1.1 General Product Information

1.1.1 Product/System Description

Liebert’s XDP refrigerant distribution unit is an interface between the building chilled water system and the cooling modules in the Liebert XD system. It is designed to circulate and control refrigerant to the cooling modules that are in the room with heat-producing equipment. The Liebert XDP is rated for 160kW (546,000BTU/H) of cooling.
The Liebert XDP consists of a cabinet that includes a heat exchanger, circulating pump(s), control valve, receiver, controls, valves and piping.
The Liebert XDP monitors room conditions and prevents coil condensation by maintaining the refrigerant being pumped to the cooling modules at a temperature above the room’s dew point.
All functions, such as switching pumps (if applicable), controlling refrigerant temperature, etc., are automatic.
Figure 1.1 Liebert XDP components

1.1.2 Minimum Load

The Liebert XDP's minimum recommended operating load is 30% of system nominal capacity. The Liebert XDP160 is rated for 160kW (546,000BTU/H) of cooling, therefore the system's minimum recommended load is 48kW (163,800BTU/H). Loading below this value can unfavorably affect system operation. Consult the factory for any loading below this recommendation.
To achieve the minimum recommended load, the capacity of all connected modules must total at least 48kW (163,800BTU/H). Seethe following table..
Vertiv | Liebert® XDP™ User Manual | 5
Table 1.1 Number of Liebert XD cooling modules required to achieve at least 48kW (163,800 BTU/H) load
Liebert XD Module Type
XDCF10 XDV8 XDV10 XDO16 XDO20 XDH20 XDH32 XDR20
Number ofLiebert XD cooling modules required to achieve at least 4 8kW (163,800BTU/H) load
5 6 5 3 3 3 2 3

1.2 Equipment Inspection

When the unit is delivered, inspect all items for visible and concealed damage. Damage should be immediately reported to the carrier and a damage claim filed with a copy sent to Vertiv and to your sales representative.

1.3 Equipment Handling

WARNING! Risk of unit falling over. Can cause injury or death.
The Liebert XDP is top-heavy. Use extreme caution when moving and installing this unit. Use lifting equipment that is rated for the weight of the unit by an OSHA-certified rating organization. See Table 8.1 on page89 for unit weights. Personnel should be properly trained and certified to move and rig equipment.
CAUTION: Risk of sharp edges, splinters and exposed fasteners. Can cause injury .
Only properly trained and qualified personnel wearing appropriate safety headgear, gloves, shoes and glasses should attempt to move, lift, remove packaging from or prepare the unit for installation.

1.3.1 Handling the Liebert XDP While it is on Skid and Packaged

Always keep the unit upright, indoors and protected from damage.
If possible, transport the unit using a forklift truck. Otherwise use a crane with belts or cables. In either case, do NOT press on the top edges of the packaging.
If using a forklift, make sure the forks (if adjustable) are spread to the widest allowable distance to still fit under the skid.
When moving the skidded unit with a forklift truck, do not lift the unit any higher than 6" (152mm). If circumstances require the unit to be lifted higher than 6" (152mm), great care must be exercised and all by-standing personnel are to be no closer than 20 feet (6m) from the lift point of the unit.
NOTICE
Risk of structural interference. Can cause equipment or building damage.
Vertiv | Liebert® XDP™ User Manual | 6
NOTICE
NOTICE
NOTICE
While on the skid, the unit is too tall (83" [2108mm] overall height) to fit through a standard doorway. Any attempt to move the unit, while skidded, through a standard doorway will cause damage to the unit and to the building.
Risk of damage from forklift. Can cause unit damage.
Keep tines of the forklift level and at a height suitable to fit below the skid and/or unit to prevent exterior and/or underside damage.
Risk of improper storage. Can cause unit damage.
Keep the Liebert XDP upright, indoors and protected from dampness, freezing temperatures and contact damage.
Risk of overtightening securing straps. Can cause damage to panels.
Place a protective material between the straps of the piano jacks and the unit. Ensure that the straps are not tightened to a point of damaging panels.

1.3.2 Unpacking the Liebert XDP

1. Remove the exterior stretch wrap packaging from the unit, exposing the protective corner and side packaging planks.
2. Remove and set aside filter dryer kit.
3. Remove the corner and side packaging planks from the unit, exposing the bag over the unit. The bag may remain in place for dust and panel protection or removed for immediate unit installation.
4. Remove the bag from the unit when ready to remove the skid for installation.
Figure 1.2 Unpacking the Liebert XDP
Vertiv | Liebert® XDP™ User Manual | 7

1.3.3 Removing the Unit from the Skid Using a Forklift

1. Align the forklift with either the front or rear side of the unit.
Make sure the tines of the forklift are locked to the widest position.
Use the center of gravity indicators to determine the entry points for the tines. The tines must be equally spaced on either side of the center of gravity indicator.
2. Insert the tines of the forklift under the unit.
Make sure the tines are level. The tines must be low enough to fit under the unit without damaging it.
Make sure the tines extend beyond the opposite side of the unit.
3. Remove the 12 lag bolts and two brackets that secure the unit to the skid.
NOTE: Each lag bolt is 1-1/2" (38mm) long. They can be removed with a 9/16" socket or wrench.
4. Lift the unit to a height that it is not being support by the skid.
5. Move the skid from under the unit.
Figure 1.3 Use a forklift to remove the Liebert XDP from the skid

1.3.4 Removing the Unit from the Skid using Rigging

1. Use the center of gravity indicators on the unit to position the slings. The slings must be equally spaced on either side of the center of gravity indicator. Refer to Figure 1.4 on the facing page.
2. Place slings under the unit using spaces provided between the skid deck boards.
NOTE: Unit is shown without outer packaging. These instructions may be applied with the outer packaging in place
3. Use spreader bars or an equivalent method to ensure proper protection of the unit.
4. Ensure that the panels, if attached, are well protected from the slings.
Vertiv | Liebert® XDP™ User Manual | 8
NOTE: If rigging is to be used to move the unit closer to the site for installation, place one or two horizontal straps around the unit and vertical straps at mid height.
5. Remove the 12 lag bolts and two brackets that secure the unit to the skid.
NOTE: Each lag bolt is 1-1/2" (38mm) long. They can be removed with a 9/16" socket or wrench.
6. Lift the unit off of the skid to an elevation point where the skid is not supporting the weight of the unit.
7. Remove the skid from under the unit.
Figure 1.4 Removing the unit from the skid using rigging

1.3.5 Moving the Liebert XDP Using Piano Jacks

1. Elevate the Liebert XDP with a lifting mechanism, such as a forklift or rigging.
1. Position one piano jack at each end of the Liebert XDP.
2. Lower the unit to a height suitable for placing it on the piano jacks.
3. Put protective material between the Liebert XDP and the piano jacks and straps.
4. Secure the Liebert XDP to the piano jacks.
5. Release the the Liebert XDP from the straps securing it to the lifting mechanism and move the mechanism away from the unit.
Using the piano jacks, at least two properly trained and qualified personnel can move the unit.
Vertiv | Liebert® XDP™ User Manual | 9
Figure 1.5 Securing the Liebert XDP to piano jacks

1.3.6 Removing the Unit from the Piano Jacks

1. Lower the Liebert XDP as far as the piano jacks will allow.
2. Undo all strapping holding the piano jacks to the unit.
3. Lift one end of the Liebert XDP off one piano jack with a pry bar or similar device, taking care not to damage the unit’s cabinet.
4. Repeat step 3 to remove the piano jack from under the opposite end of the Liebert XDP.
5. Remove all material used to protect the unit from the piano jacks and strapping.
Vertiv | Liebert® XDP™ User Manual | 10

2 INSTALLATION

2.1 Mechanical Considerations

2.1.1 Positioning the Liebert XDP

Install the Liebert XDP according to the site specific documentation and secure the unit to the floor.
The Liebert XDP can be installed near a wall or another Liebert XDP. However, there must be at least 3feet(92cm) clearance in front of the Liebert XDP as service access for components in the unit.
For additional technical information, refer to the System Design and Configuration Document for the Liebert XD™System, SL-16655. The document is available in electronic format at Vertiv’s Web site,
www.VertivCo.com, as well as from your local Vertiv representative.
Figure 2.1 Dimensions
Table 2.1 Liebert XDP Dimensions
Model
50/60Hz
XDP160 38(965) 34 (864) 33-1/ 8 ( 841) 33 (838) 36 (914) 78 (1981) 1 020 (462) 1083 (491)
*The dimension does not include the bezel of the disconnect switch.
Vertiv | Liebert® XDP™ User Manual | 11
Dimensional Data, inches (mm) Shipping Weight, lb. (kg)
A B* C D e H Domestic Export
Figure 2.2 Piping access points
Table 2.2 Unit piping outlet connection sizes, inches, OD Cu
Model Pipe ConnectionPoint
50/60 Hz A B C D
XDP160 2-1/8 1-1/8 2-5/8 2-5/8

2.2 Electrical Considerations

Make sure the actual supply voltage and frequency correspond to the voltage and frequency indicated on the Liebert XDP’s rating plate. The unit must be installed in accordance with national wiring regulations.
Vertiv | Liebert® XDP™ User Manual | 12
Connect cables for high voltage supply to the electrical box in the Liebert XDP according to Figure 2.5 on page16 and make sure that the phases are correctly connected.
WARNING! Risk of electric shock. Can cause injury or death.
Disconnect all local and remote electric power before working within the unit
WARNING! Risk of electrical shock, short circuit and/or control malfunction. Can cause equipment damage, injury or death.
Damage to wiring or components can make unit unsafe to operate.
Use caution when installing wiring to prevent damage to factory wiring.
Install protective bushings in wiring knockouts as required to protect wiring from sharp edges.
Do not disturb factory wiring or route field-installed wiring over electrical terminals.
Use NEC Class 1 wiring for all hazardous voltage electrical power supplies.
Check and retighten all wiring connections before starting the unit.

2.2.1 Connecting High-Voltage Cables

1. Turn the Liebert XDP’s disconnect switch to the Off position (see Figure 2.3 on the next page). Open the front doors and push down on the enclosure cover latch to open the hazardous voltage enclosure cover.
Vertiv | Liebert® XDP™ User Manual | 13
Figure 2.3 Front view of Liebert XDP and electrical enclosure
2. Determine which knockouts in the electrical enclosure will be used and remove them (see Figure 2.4 on the facing page).
Vertiv | Liebert® XDP™ User Manual | 14
Figure 2.4 Electrical enclosure knockout location for hazardous voltage wiring
3. Route the input hazardous voltage electrical power wiring through the top left knockout (see Figure 2.4 above) to the disconnect switch L1, L2 and L3 (see Figure 2.5 on the next page andFigure 2.6 on the next page). Observe proper phasing.
4. Connect the ground wire to the ground lug (see Figure 2.5 on the next page andFigure 2.6 on the next page), which is in the middle left of the enclosure.
Vertiv | Liebert® XDP™ User Manual | 15
Figure 2.5 High voltage connections—60Hz
Figure 2.6 High voltage connections—50Hz

2.2.2 External Pump Overloads

The Liebert XDP is shipped with external pump overload with trip point settings and DIP switch settings for normal operations. The trip points are in increments of 0.25A and should not be changed from the factory settings. For 460V, the trip point is set at 1.5A (Figure 2.7 on the facing page). For 208V, the trip point is set at 2.7A (Figure 2.8 on the facing page). See Figure 2.9 on page18 for factory DIP switch settings for normal operation with reset mode set as automatic and Trip Class 20.
Vertiv | Liebert® XDP™ User Manual | 16
Figure 2.7 460V factory setting external pump overload trip point
Figure 2.8 208V factory setting external pump overload trip point
Vertiv | Liebert® XDP™ User Manual | 17
Figure 2.9 Factory DIP switch settings

2.2.3 Extra Low Voltage (ELV) Connections

Extra Low Voltage power output is 30V and 100VA or less.
1. Turn off all unit power before connecting cables or wires. Failure to do so may damage this equipment (refer to Figure 2.10 below).
2. Route low voltage electrical connections through the appropriate knockouts as indicated below.
Figure 2.10 Electrical enclosure knockout locations for Extra Low Voltage
Vertiv | Liebert® XDP™ User Manual | 18
Figure 2.11 Connecting the remote temperature/humidity sensors
Vertiv | Liebert® XDP™ User Manual | 19

2.2.4 DIP Switch and Jumper Settings for Remote Sensors

The Liebert XDP is shipped with jumpers and DIP switch settings for normal operation. See Figure 2.12 below.
Figure 2.12 DIP switch and jumper settings
Vertiv | Liebert® XDP™ User Manual | 20
Figure 2.13 Unit-to-unit networking connections

2.3 Field Connections—Optional for All Units

Connect field wiring from the optional Liebert XD cooling module condensation detection circuit to terminal strip locations COMM. (24) and H2O (51).
Connect optional field wiring from remote devices to remote alarm device, common alarm outputs, site monitor and remote shutdown, if applicable. See terminal strip descriptions in Figure 2.14 on the next page.
Vertiv | Liebert® XDP™ User Manual | 21
Figure 2.14 Liebert XDP extra low voltage field connections points

2.4 Remote Sensor Installation—Proper Placement

Placement of the two remote temperature/humidity sensors is critical to effective cooling of the conditioned space.
Vertiv | Liebert® XDP™ User Manual | 22
The remote sensors must be installed in areas where conditions are representative of the space conditioned by the Liebert XDP. Vertiv recommends installing the sensors in different areas near the cooling modules served by the Liebert XDP. If the return air side of the primary air mover, such as a Liebert DS, represents the conditions where the Liebert XD cooling modules are located, one sensor could be placed there. Vertiv suggests placing the other sensor on the wall opposite the heat load area (see Figure 2.15 below for guidance).
Do not install the sensors where ambient air might cause false readings, for example, near unsealed doors or windows, or areas with stagnant air.
1. Unpack the two remote temperature/humidity sensors and cables.
One sensor is labeled Sensor A and the other Sensor B. The sensor cables are interchangeable; each bears labels indicating Sensor End and Unit End.
2. Connect the Sensor End of one of the supplied sensor cables to P66 on Sensor A (see Figure
2.11 on page19).
3. Connect the Unit End of the sensor cable to P67 on the Liebert iCOM input/output board inside the Liebert XDP. Secure the ring terminal on the cable shield to the electric box adjacent to P67 (see Figure 2.11 on page19).
4. Connect the Sensor End of the second sensor cable to P66 on Sensor B (see Figure 2.11 on page19).
5. Connect the Unit End of the cable to P67 on the Liebert iCOM display (see Figure 2.11 on page19). Secure the ring terminal on the cable shield to the grounding screw adjacent to P67.
Figure 2.15 Suggested remote sensor placement
Vertiv | Liebert® XDP™ User Manual | 23
This page intentionally left blank.
Vertiv | Liebert® XDP™ User Manual | 24

3 PIPING

3.1 European Union Fluorinated Greenhouse Gas Requirements

Stationary air conditioning, refrigeration, heat pump equipment and stationary fire protection systems in the European Community market and operating with fluorinated greenhouse gases (f-gas), such as R407C, R134a, R410A, must comply with the F-Gas Regulation: (EC) No. 842/2006 (F-gas). The regulation prohibits, among other actions, venting fluorinated greenhouse gases to the atmosphere.
The F-Gas Regulation requires operators to use all measures that are technically feasible and do not entail disproportionate cost to prevent leakage of these gases, to test for leakage regularly and to recover f-gas before disposing of equipment, as well as during service and maintenance.
Refer to the full regulation for additional details.

3.2 Connection Sizes

The copper pipe connections on the Liebert XDP are:
Building Chilled Water Supply Building Chilled Water Return
2-5/8" OD
2-5/8" OD
Refrigerant Supply 1-1/8" OD Refrigerant Return 2-1/8" OD

3.2.1 Recommended Pipe Size

Connect the main pipes between the Liebert XDP and the Liebert XD cooling modules according to site specific documentation and the configuration guide for the Liebert XD system.
Elbows and restrictions must be minimized to get good fluid flow.
Table 3.1
Supply, return pipe sizes for refrigerant loop
Pipe Function Size / Equivalent Pipe Length
Liebert XDP supply line, from Liebert XDP supply to farthest L iebert XD cooling module
Liebert XDP return line, from farthest Liebert XD cooling module to Liebert XDP return
From any model Liebert XDO/Liebert XD H supply to supply line of L iebert XDP
From any model Liebert XDO/Liebert XD H return to return line of Liebert XDP
From any model Liebert XDV/Liebert XDCF s upply to supply line of L iebert XDP
From any model Liebert XDV/Liebert XDCF r eturn to return line of Liebert XDP
1-1/8" OD for lengths upto 60 feet
1-3/8" OD for lengths over 60 but less than175 feet
2-1/8" OD for lengths up to 60 feet
2-5/8" OD for lengths over 60 but less than175 feet
1/2" OD for lengths upto 10 feet
7/8" OD for lengths over 10 butless than 25 feet
7/8" OD for lengths up to 10 feet
1-1/8" OD for lengths over 1 0 but less than 25 feet
1/2" OD for lengths upto 10 feet
5/8" OD for lengths over 10 butless than 35 feet
5/8" OD for lengths up to 10 feet
7/8" OD for lengths over 10 butless than 35 feet
Vertiv | Liebert® XDP™ User Manual | 25
Loading...
+ 67 hidden pages