LIEBERT® TDU
TRANSFORMER DISTRIBUTION UNIT
Quick Installation User Guide
SAVE THESE INSTRUCTIONS:
This manual contains important
instructions that are to be followed
during installation and
maintenance of the TDU.
I M P OR TA N T: Before installing,
connecting to supply or operating
your Liebert TDU, please review
the Safety and Regulatory sheet.
IN STAL L ATI ON
1. Inspecting the TDU
Inspect the TDU for any signs
of obvious damage. If damage is
visible, do not proceed and call
our warranty support line at
1-800-222-5877 menu option 3,
or email at
VertivCo.com
microups.warranty@
.
2. Choosing a location
Install in a temperaturecontrolled environment free of
corrosive and conductive
contaminants. Avoid locations
near heat or water sources and
exposed to direct sunlight. For
proper ventilation, leave four
inches clearance on all sides of
the TDU. The input outlet should
be nearby and easily accessible.
3. Installing the TDU
The TDU may be installed in a
rack by attaching the brackets
to the TDU, installing the rail kit
in the rack if needed, then
installing into the rack. The
TDU may also be installed in
the vertical/tower orientation.
NOTE : This TDU is not for use in a
computer room as defined in the
standard for the protection of
electronic computer/data
processing equipment of ANSI/
NFPA 75.
CONNECTIONS
1. Connecting Loads
There are two groups of five
outputs, one on each side of
the fan. Connect loads to each
MODEL DESIGN CONFIGURATIONS
# DESCRIPTION
1 NEMA L6-30 Input Cable
2 NEMA L6-20 Input Cable
3 Output Group 1
4 Output Group 2
5 NEMA 5-15/20 Output Receptacles
6 NEMA L5-20R Output Receptacles
7 NEMA L5-30R Output Receptacles
8 20A Output Breakers
9 30A Output Breakers
group not exceeding the group
rating or breaker rating. See
Specifications.
2. Connecting Input
Ensure that all the loads are
first powered o. Connect the
TDU input to only a Liebert
NOTE : When connecting to a
Liebert® GXT4™ series UPS, the
UPS must be configured to start on
inverter. See the UPS User Guide
for Instructions.
UPS with an output voltage
rated to 200-240VAC.
590-1811-501B/SL-23206_REV1 1
![](/html/e4/e41a/e41a964e00ebd2e421fa149a27aa7dd964120c35bad5f505595f482885e1b390/bg2.png)
LIEBERT® TDU
TRANSFORMER DISTRIBUTION UNIT
Quick Installation User Guide
Output Voltage (Vac, 1Ø)
Input Voltage (Vac)
208V Rotary Switch Postition 240V Rotary Switch Position
200 - 100
208 120 -
220 125 110
230 - 115
240 - 120
SPECIFICATIONS
MODELS
TDU-3500RTL620 TDU-4000RTL630 TDU-6000RTL630
Total Rating @ 208 VAC input 3440 VA / 3440 W 4000 VA / 4000 W 5050 VA / 5050 W
Output 1 Max 1750 VA / 1750 W 2000 VA / 2000 W 3000 VA / 3000 W
Output 2 Max 1750 VA / 1750 W 2000 VA / 2000 W 3000 VA / 3000 W
INPUT
Voltage Range 200-240 VAC
Frequency Range 60/50 Hz
Plug L6-20 L6-30 L6-30
OUTPUT
Receptacles “(8) NEMA 5-15/20R, (2) L5-20R” (8) NEMA 5-15/20R, (2) L5-20R (8) NEMA 5-15/20R, (2)
Protection (2) 20A breakers (2) 20A breakers “(4) 20A breakers,
Voltage Regulation 120 VAC (100/110/115/125 VAC)
Frequency Range Same as Input
Efficency 94%
PHYSICAL
Unit Dimensions, W x D x H, in (mm) - 438 x 525 x 88 in (430 x 574 x 85 mm)
Shipping Dimensions W x D x H, in (mm) - 258 x 672 x 550 in (607 x 270 x 747 mm)
Unit Weight (kg) 47.2
Shipping Weight (kg)* ~50.4
OPERATION ENVIRONMENT
Temperature 32-104°F (0-40°C)
Elevation Up to 3,000m @ 25°C without derating
Humidity 0-95 % RH (non-condensing)
Noise Level Less than 55dB
COMPLIANCE
Safety UL 1778
EMC FCC Part 15, Class B
ESD EN61000-4-2; Air discharge: Level 3 ; Contact discharge: Level 2
Susceptibility EN61100-4-3, Level 3
L5-30R
(2) 30A breakers”
To contact Vertiv Technical Support: visit www.VertivCo.com
© 2018 Verti v Co. All rights res erved. Vertiv an d the Vertiv logo are tra demarks or regis tered trademar ks of Vertiv Co. All othe r names and logo s referred to are trad e names,
tradema rks or registere d trademarks of thei r respective own ers. While ever y precaution ha s been taken to ensu re accuracy and co mpleteness h erein, Vertiv Co. a ssumes no
respon sibility, and disc laims all liabili ty, for damages res ulting from use of thi s information or fo r any errors or omis sions. Speci fications are s ubject to change w ithout notice.
2 590-1811-501B/SL-23206_REV1