To contact Vertiv Liebert Services for information or repair service in the United States, call 800-543-2378.
Liebert Services offers a complete range of startup services, repair services, preventive maintenance plans and
service contracts.
For repair or maintenance service outside the 48 contiguous United States, contact Liebert Services, if available
in your area. For areas not covered by Liebert Services, the authorized distributor is responsible for providing
qualified, factory-authorized service.
For Liebert Services to assist you promptly, please have the following information available:
Part numbers: ___________________________________________________________________________________________________________
Serial numbers:__________________________________________________________________________________________________________
Rating: __________________________________________________________________________________________________________________
Date purchased:_________________________________________________________________________________________________________
Date installed: ___________________________________________________________________________________________________________
Location: ________________________________________________________________________________________________________________
Input voltage/frequency:________________________________________________________________________________________________
Output voltage/frequency:______________________________________________________________________________________________
Battery reserve time:____________________________________________________________________________________________________
Product Warranty Registration
To register for warranty protection, visit the Service and Support section of our Web site at:
www.liebert.com
Click on Product Registration and fill out the form.
This manual contains important instructions that should be followed during installation of your Liebert NX UPS.
Read this manual thoroughly, paying special attention to the sections that apply to your installation, before
working with the UPS. Retain this manual for use by installing personnel.
WARNING
Risk of electrical shock. Can cause personal injury or death.
This UPS has several circuits that are energized with high DC as well as AC voltages. Check for voltage
with both AC and DC voltmeters before working within the UPS. Check for voltage with both AC and DC
voltmeters before making contact.
Only properly trained and qualified personnel wearing appropriate safety headgear, gloves, shoes and
glasses should be involved in installing the UPS or preparing the UPS for installation. When performing
maintenance with any part of the equipment under power, service personnel and test equipment should
be standing on rubber mats.
In case of fire involving electrical equipment, use only carbon dioxide fire extinguishers or those approved
for use in fighting electrical fires.
Extreme caution is required when performing installation and maintenance.
Special safety precautions are required for procedures involving handling, installation and maintenance of
the UPS system. Observe all safety precautions in this manual before handling or installing the UPS
system. Observe all precautions in the Operation and Maintenance Manual, SL-25434, before as well as
during performance of all maintenance procedures. Observe all DC safety precautions before working on
or near the DC system.
WARNING
Risk of heavy unit falling over. Improper handling can cause equipment damage, injury or death.
Exercise extreme care when handling UPS cabinets to avoid equipment damage or injury to personnel.
The UPS module weight is up to 4450 lb. (2019kg).
Locate center of gravity symbols and determine unit weight before handling each cabinet. Test lift and
balance the cabinets before transporting. Maintain minimum tilt from vertical at all times.
Slots at the base of the module cabinets are intended for forklift use. Base slots will support the unit only
if the forks are completely beneath the unit.
Read all of the following instructions before attempting to move, lift, or remove packaging from unit, or
prepare unit for installation.
Risk of electrical shock and fire. Can cause equipment damage, personal injury or death.
Under typical operation and with all UPS doors closed, only normal safety precautions are necessary.
The area around the UPS system should be kept free of puddles of water, excess moisture and debris.
Only test equipment designed for troubleshooting should be used. This is particularly true for
oscilloscopes.
Always check with an AC and DC voltmeter to ensure safety before making contact or using tools. Even
when the power is turned Off, dangerously high potential electric charges may exist at the capacitor
banks and at the DC connections.
All wiring must be installed by a properly trained and qualified electrician.
All power and control wiring must comply with all applicable national, state and local codes.
One person should never work alone, even if all power is disconnected from the equipment. A second
person should be standing by to assist and to summon help in case of an accident.
WARNING
Risk of electrical shock and fire. Can cause equipment damage, injury and death.
Internal battery strapping must not be removed. Failure to heed this warning could result in smoke, fire or
electric hazard. If strapping is removed, consult your local representative before attempting to transport
the battery cabinet.
NOTICE
This unit complies with the limits for a Class A digital device, pursuant to Part 15 Subpart J of FCC rules. These limits
provide reasonable protection against harmful interference in a commercial environment. This unit generates uses and
radiates radio frequency energy and, if not installed and used in accordance with this instruction manual, may cause
harmful interference to radio communications. Operation of this unit in a residential area may cause harmful interference
that the user must correct at his own expense.
NOTE
Materials sold hereunder cannot be used in the patient vicinity (e.g., use where UL, cUL or IEC 60601-1 is
required). Medical applications such as invasive procedures and electrical life support equipment are subject to
additional terms and conditions.
This section describes the requirements that must be taken into account when planning the positioning and
cabling of the Liebert NX uninterruptible power supply and related equipment.
This chapter is a guide to general procedures and practices that should be observed by the installing personnel.
The particular conditions of each site will determine the applicability of such procedures.
WARNING
Risk of electrical shock. Can cause injury or death.
Special care must be taken when working with the batteries associated with this equipment.
When they are connected together, the battery terminal voltage will exceed
400VDC and is potentially lethal.
NOTE
All equipment not referred to in this manual is shipped with details of its own mechanical and electrical
installation.
NOTICE
Risk of incorrect input power connection. Can cause equipment damage.
The standard Liebert NX UPS is suitable for connection to three-phase, three-wire plus ground input power.
NOTE
Do not apply electrical power to the UPS equipment before the arrival of the commissioning engineer.
Connecting power before the commissioning engineer determines the system is properly installed may void the
warranty.
1.2PRELIMINARY CHECKS
Before installing the UPS, please carry out the following preliminary checks:
•Visually examine the UPS equipment for transit damage, both internally and externally. Report any damage to the shipper
immediately.
•Verify that the correct equipment is being installed. The equipment supplied has an identification tag on the interior doors
reporting the type, size and main calibration parameters of the UPS.
•Verify that the UPS room satisfies the environmental conditions stipulated in the equipment specification, paying
particular attention to the ambient temperature and air exchange system.
The UPS module is intended for indoor installation and should be located in a cool, dry, clean-air environment
with adequate ventilation to keep the ambient temperature within the specified operating range (see
Environmental Parameters in Tab le 7).
The Liebert NX UPS is cooled with the aid of internal fans. To permit air to enter and exit and prevent
overheating or malfunctioning, do not cover the ventilation openings.
The Liebert NX UPS is equipped with air filters located behind the front doors. A schedule for inspection of the
air filters is required. The period between inspections will depend upon environmental conditions.
When bottom entry is used, the conduit plate must be installed.
NOTE
The UPS is suitable for mounting on concrete or other non-combustible surface only.
NOTICE
There is a potential risk to the operational integrity of an installed UPS system by the presence of foreign material inside or
in the vicinity of the UPS module.
This risk is especially high if conductive materials find their way inside the UPS module.
The risk potentially involves damage to the installed UPS equipment and subsequent degradation or loss of power to the
connected critical site load.
Vertiv applies the highest safety standards in equipment design to ensure that no live parts are exposed to external
contact, and also to ensure that the equipment is protected against the introduction of foreign bodies during operation.
However, it is not possible for Vertiv to ensure that foreign bodies will not be introduced during on-site installation, or
when the UPS doors and covers are “open” and the electrical terminals are exposed to allow power line connections to be
made by the electrical contractor/installer.
To prevent major disruption to site operations and risk to property and personnel, including the possibility of a fatality,
each site’s facility manager or construction manager must prevent foreign bodies from being introduced into the UPS
module.
All UPS modules are thoroughly inspected by Vertiv engineers prior to placement into service and testing on-site.
However, the person responsible for the site must ensure that the UPS module, and the immediate surroundings, are kept
clean and free from any possible conductive material such as metal foil, food wrappers, cable shields, washers and other
hardware, scrap metal and dust.
If the UPS system is shut down after placement into service and testing are completed, the UPS room must be kept clean
to avoid the possibility (during restart) of the considerable volume of air-flow produced by UPS operation to dislodge
and/or drag any foreign bodies into the equipment, which would result in system failure and possible supply interruption to
the critical site load, and several hours of downtime resulting from the damage typically associated with such events.
If the UPS is left running/operational at the completion of placement into service and testing, the room similarly needs to
be kept clean to prevent foreign bodies from entering the UPS module via its forced air-flow.
1.3.2Storing the UPS and Batteries for Delayed Installation
If the Liebert NX system will not be installed immediately, it must be stored indoors in a clean, dry and cool
location (see Environmental Parameters in Tab le 7 ). If the UPS includes batteries, either internally or in a
battery cabinet, the batteries’ requirements will dictate the storage conditions. Batteries should be unpacked,
installed and charged as soon as possible after delivery.
NOTICE
Risk of failure to properly charge batteries. Can cause permanent damage to batteries and void the warranty.
Batteries will self-discharge during storage. Batteries must be recharged as recommended by the battery manufacturer. A
notice of “Charge Before Date” is affixed to each unit that has batteries inside. The “Charge Before Date” is calculated
based on the batteries being stored at 77°F (25°C). Storage at a higher temperature will increase the rate of self-discharge,
requiring earlier recharge. Consult the battery manufacturer on how to determine when the batteries need to be
recharged.
The maximum operating altitude of the UPS, without derating, is 3300ft. (1000m). At higher altitudes the load
must be reduced according to Table 8.
1.4POSITIONING
The cabinet is structurally designed to handle lifting from the base.
Access to the power terminals, auxiliary terminal blocks and power switches is from the front.
The door can be opened to give access to the power connection bars, auxiliary terminal blocks and power
isolators. The front door can be opened 90 degrees for more flexibility in installations.
1.4.1Moving the Cabinets
The route to be traveled between the point of arrival and the unit’s position must be planned to make sure that
all passages are wide enough for the unit and that floors are capable of supporting its weight (for instance, check
that doorways, lifts, ramps, etc. are adequate and that there are no impassable corners or changes in the level of
corridors).
Ensure that the UPS weight is within the designated surface weight loading (kg/cm2) of any handling equipment.
For weight details, see Tab le 7.
Move the UPS with a forklift or similar equipment to ease the relocation and to reduce vibration. The optional
battery cabinets should be moved with a forklift or similar equipment.
When handling the UPS with a forklift or similar equipment, ensure any lifting equipment used in moving the UPS
cabinet has sufficient lifting capacity. When moving the unit by forklift, care must be taken to protect the panels.
Do not exceed a 15-degree tilt with the forklift. Bottom structure will support the unit only if the forks are
completely beneath the unit.
Handling with straps is not authorized.
WARNING
Risk of heavy unit falling over. Improper handling can cause equipment damage, injury or death.
Because the weight distribution in the cabinet is uneven, use extreme care while handling and
transporting. Take extreme care when handling UPS cabinets to avoid equipment damage or injury to
personnel.
The UPS module weight is up to 4450 lb. (2019kg).
Locate center of gravity symbols and determine unit weight before handling each cabinet. Test lift and
balance the cabinets before transporting. Maintain minimum tilt from vertical at all times.
1.4.2Clearances
The Liebert NX has no ventilation grilles at either side or at the rear of the UPS. Clearance around the front of the
equipment should be sufficient to enable free passage of personnel with the doors fully opened. It is important to
leave a distance of 24in (610mm) between the top of the UPS and any overhead obstacles to allow the module to
be serviced and to permit adequate circulation of air coming out of the unit.
1.4.3Raised-Floor Installations
If the equipment is to be located on a raised floor, it should be mounted on a pedestal suitably designed to
accept the equipment point loading. Refer to the base view to design this pedestal.
1.4.4Kick Plates and Floor Anchors for Special Seismic Certification—Optional
For seismic resistant installations and OSHPD compliance, special floor anchors and kickplates must be used for
the UPS and matching battery cabinets; see Table 18.
The California Office of Statewide Health Planning and Development (OSHPD) enforces International Building
Code requirements for Special Seismic Certification except that the office reduces the required scope of
certifications.
1.4.5Kick Plate Installation—Standard
Kick plates must be installed. If the unit is to be installed in a position that does not permit access to rear kick
plates, then the kick plates must be installed before the unit is placed in its final position.
1.4.6Special Considerations for 1+N Parallel Systems
Consider the grounding configuration of your system before finalizing module placement See 2.5 - Configuring
Ground Connections.
Vertiv recommends matching the impedance in the bypass path of paralleled systems as closely as possible to
ensure good bypass current sharing.
The impedance mismatch can be minimized by controlling the wiring length of each unit. The design and the
layout of the UPS system and associated panels and cabling should be examined closely to ensure that cable
lengths and impedances are closely matched.
For Liebert NX Systems, the total combined cable length of the bypass feeder cables and the module output
cables for each module must be within 5% from maximum to minimum. The combined cable length is the sum of
the length from the common source feeding all the modules to the common output switchboard.
If the cabling impedances need to be greater than 5%, contact your Vertiv representative to calculate whether
the system will result in an overload condition when operating on bypass.
When bringing the 1+N system on-line for the first time or after removing one unit, Vertiv recommends checking
the bypass current mismatch. To check the bypass current mismatch:
1.Place a load on the bypass of each UPS module.
2.View the output current of each unit.
The accuracy of the currents displayed on the UPS module is sufficient for this check. If the mismatch is greater
than 5%, the bypass impedances must be balanced or the load must be limited to less than the maximum rating.
The output switchboard for any 1+N system must be configured with one Module Output Circuit Breaker (MOB)
for each UPS module that is to be connected to that switchboard. The breaker must be equipped with auxiliary
contacts that will be monitored by the UPS in order for interlocks to function properly and for the HMI to indicate
the bypassed status of the module.
Vertiv recommends using magnetic or thermomagnetic breakers. If molded case switches will be used, Vertiv
recommends installing breakers without electronic trip units or to set the trip units high enough to
accommodate high instantaneous currents that may be present when switching a module into an active bus.
For 225-250kVA Modules—Set instantaneous trip settings to allow for 2000A for 2 milliseconds.
For 400-600kVA Modules—Set instantaneous trip settings to accommodate 3000A for 2 milliseconds
1.4.7Unpacking and Unloading the Cabinet from the Pallet
The utmost care must be taken when removing the packaging to prevent damage to the equipment. Check all
packaging materials to ensure that no important items are discarded. Once the packaging has been removed,
the UPS must be taken off the pallet by removing the retaining screws, as illustrated in Figure 1, and lifting the
unit off using a fork lift Do not remove the retaining brackets securing the UPS to the pallet because they are
used to fasten the UPS to the floor, except where OSHPD compliance is required and the optional OSHPD
seismic anchoring kits are used.
Figure 1Unpacking
1.5SYSTEM COMPOSITION
A UPS system can comprise a number of equipment cabinets, depending on the individual system design
requirements: e.g., UPS cabinet, battery cabinet, maintenance bypass cabinet. In general, all the cabinets used in
a particular installation are of the same height. Refer to the drawings provided in 4.0 - Installation Drawings for
the positioning of the cabinets as shown in Figure 2.
This chapter provides guidelines for qualified installers who must have knowledge of local wiring practices
pertaining to the equipment to be installed.
WARNING
Risk of electrical shock. Can cause injury or death.
The UPS contains high DC as well as AC voltages. Check for voltage with both AC and DC voltmeters
before working within the UPS.
Only properly trained and qualified personnel wearing appropriate safety headgear, gloves, shoes and
glasses should be involved in installing the UPS or preparing the UPS for installation.
2.1EXTERNAL PROTECTIVE DEVICES
For safety, it is necessary to install circuit breakers in the input AC supply and external battery system. Given that
every installation has its own characteristics, this section provides guidelines for qualified installation personnel
with knowledge of operating practices, regulatory standards and the equipment to be installed.
External overcurrent protection must be provided. See Figure 14 for overload capacity.
2.2POWER CABLES
The UPS requires both power and control cabling. All control cables, whether shielded or not, should be run
separately from the power cables in metal conduits or metal ducts that are electrically bonded to the metalwork
of the cabinets to which they are connected.
The cable design must comply with the voltages and currents in Ta bles 9 through 12, follow local wiring
practices and take into consideration the environmental conditions (temperature and physical support media),
room temperature and conditions of installation of the cable and system’s overload capacity (see 5.0 - Specifications).
WARNING
Risk of electrical shock. Can cause injury or death.
Before cabling the UPS, ensure that you are aware of the location and operation of the external isolators
that connect the UPS input/bypass supply to the power distribution panel.
Check that these supplies are electrically isolated, and post any necessary warning signs to prevent their
inadvertent operation.
When sizing battery cables, a maximum volt drop of 2VDC is permissible at the current ratings given in Table 12.
The following are guidelines only and are superseded by local regulations and codes of practice where
applicable:
•The grounding conductor should be sized according to the fault rating, cable lengths, type of protection, etc. The
grounding cable connecting the UPS to the main ground system must follow the most direct route possible.
•Consideration should be given to the use of paralleled smaller cables for heavy currents, as this can ease installation
considerably.
•AC and DC cables must be run in conduits according to local codes, national codes and standard best practices. This will
prevent creation of excess EMI fields.
See 3.2.3 - Capacity on Demand (Softscale) Upgrades.
Nominal input current (considered continuous) is based on full-rated output load. Maximum current includes
nominal input current and maximum battery recharge current (considered noncontinuous).
Continuous and noncontinuous current are defined in the NEC.
Maximum input current is controlled by the current limit setting, which is adjustable. Values shown are for
maximum current limit. If a smaller input feed breaker is used, the input current limit can be adjusted; see your
Vertiv representative for more information. The input current limit should not be set less than 105% of the
current needed to support the inverter at full load for normal operation.
This results in sufficient power to recharge the battery in a reasonable time and to operate over the published
input voltage range.
2.3.1Single or Dual Input Feeds
The Liebert NX 225-600 kVA may be fed from single reference sources or dual asynchronous sources. If a
single-input configuration will be used, the utility source must be cabled to the rectifier input busbars. See
Figures 13 and 18.
2.3.2Automatic Transfer Switches
If the UPS is to be fed from an automatic transfer switch, the transfer switch must have a programmed delay of
100 milliseconds for transfers between two sources.
The rectifier input, bypass, output and battery power cables (all require lug-type terminations) are connected to
busbars in the I/O sections (refer to 4.0 - Installation Drawings).
Equipment Ground
The equipment ground busbar is in the I/O sections as shown in (refer to 4.0 - Installation Drawings). The
grounding conductor must be connected to the ground busbar and bonded to each cabinet in the system.
All cabinets and cabling should be grounded in accordance with local regulations.
NOTE
Proper grounding reduces problems in systems caused by electromagnetic interference.
WARNING
Failure to follow adequate grounding procedures can result in electric shock hazard to personnel, or the
risk of fire, should a ground fault occur.
All operations described in this section must be performed by properly trained and qualified electricians
or technical personnel. If any difficulties are encountered, contact Vertiv. See the back page of this
manual for contact information.
Once the equipment has been positioned and secured, connect the power cables as described below (refer to
the appropriate cable connection drawing in 4.0 - Installation Drawings):
1.Verify that the UPS equipment is isolated from its external power source and all the UPS power isolators are open.
2.Check that these supplies are electrically isolated and post any necessary warning signs to prevent their inadvertent
operation.
3.Open exterior and interior panels on the front of the I/O sections.
4.Connect the ground to the equipment ground busbar located in the I/O sections.
5.Make power connections and tighten the connections to the proper torque.
Ensure correct phase rotation.
WARNING
Risk of electrical shock. Can cause injury or death.
If the load equipment will not be ready to accept power on the arrival of the commissioning engineer,
ensure that the system output cables are safely isolated at their termination.
WARNING
Risk of electrical shock. Can cause injury or death.
When connecting the cables between the battery extremities to the circuit breaker, always connect the
circuit breaker end of the cable first.
6.For control connection details, see 2.4 - Control Cable and Communication.
7.Close and secure the interior and exterior doors.
8.Attach the kick plates to the bottom of the unit.
NOTE
If the unit is to be installed in a position that does not permit access to rear kick plates, then the kick plates must
be installed before the unit is placed in its final position.
Based on your site’s specific needs, the UPS may require auxiliary connections to manage the battery system
(external battery circuit breaker), communicate with a personal computer or provide alarm signaling to external
devices, or for Remote Emergency Power Off (REPO). Refer to Figures 9 and 15.
The Liebert NX is equipped with the following interfaces:
•XS3 - Slot for Liebert IntelliSlot™ or ManageUPS™ communication card
•XS6 - Slot for LIFE
•X3 - Reserved
•X6 - Serial interface for external LIFE Services
•XT1/2 - Not Used
•X9 - Reserved
•XT3/8 - 4-pole screw connector for REPO Input and REPO Status
•XT4 - Reserved
•TB1 - 16-pole screw connector for input contacts
•TB2 - 16-pole screw connector for output contacts
•X19A/B - 2x15-pole connectors for parallel UPS connection
•X20 - RJ-45 interface for synchronization with external signal
•XT1 - Not Used
•TB3 - Battery Interface and Key Status
•TB4 - SKRU Enable
2.4.1Slot for Liebert IntelliSlot™ or ManageUPS™ Communication Cards—XS3
This slot is the interface for the Liebert network communication cards. This adapter provides an independent
external network interface for communication with network monitoring and building management systems.
™
Services modem
Units built since June 2016 are equipped with either the Liebert IntelliSlot system or the ManageUPS system.
Previous units included a factory-installed ManageUPS system, which provided connectivity to SNMP and
Modbus.
The Liebert IntelliSlot platform includes the Liebert IS-UNITY-DP™ and Liebert IS-485 EXI™ cards. The platform
communicates with Vertiv software tools and services, including Trellis®, Liebert SiteScan® Web and Liebert
Nform®.
The Liebert IS-UNITY-DP supports up to two third-party protocols along with HTTP/S (Web), Vertiv Protocol,
SMTP and SMS.
Third-party protocols available on the Liebert IS-UNITY-DP card are:
•BACnet IP—BACnet over Internet Protocol
•BACnet MSTP—BACnet Master-Slave/Token-Passing (MSTP) communications protocol over an RS-485 serial network
(also known as BACnet MSTP RS-485)
•Modbus RTU
•Modbus TCP
•SNMP versions 1, 2c and 3
NOTE
No more than two protocols may be enabled on one card.
Only one version of BACnet may be selected, either BACnet IP or BACnet MSTP.
Only one version of Modbus may be selected, either Modbus TCP or Modbus RTU.
Only one of the protocols can use the 485 port; choosing two 485 protocols will cause conflicts.
The Liebert IS-485 EXI Card connects to a Liebert SiteLink-E™, allowing Liebert SiteScan Web 4.0 monitoring
and control.
Protocols available on the ManageUPS card, depending on the card model, are:
!
•Modbus RTU—Modbus Remote Terminal Unit (RTU) communication protocol over RS-232, RS-422 and RS-485
•Modbus TCP—Modbus Transmission Control Protocol over Internet Protocol (also known as Modbus TCP/IP)
•SNMP version 1
•Ethernet
•HTTP/Web
2.4.2Slot for LIFE Services Products—XS6
This slot is the reserved interface for LIFE Services modem card. This card provides an independent external
modem interface for communication with LIFE Services service station. Ask your local Vertiv representative for
more details on LIFE Services and its benefits for your UPS system.
2.4.3Serial Interface for Liebert LIFE Services Cards (Serial Input/Output)—X6
The service interface is a SUB-D nine-pin male connector for RS-232 serial communication. It is used for
communications with external LIFE Services or other special Liebert applications.
2.4.4Connector for REPO (Input and Status)—XT3/8
This four-pole screw connector allows:
•Switching off the UPS from a remote source (e.g., push button)
•Providing status to an external system regarding whether the REPO is active
To perform a remote emergency power off, it is necessary to connect an emergency stop button to the UPS via a
shielded cable not exceeding 66ft. (20m) in length. The switch must be “Closed” under normal operating
conditions and be equipped with a mechanism that maintains it in the “Open” position after it has been pressed.
If this button is not installed, a jumper lead must be connected between Pins 1 and 2. For an indication of REPO
status, connect Pin 3 and Pin 4 to an external system.
Table 1REPO connection
PinSignalExplanation
1 & 2REPO Input ContactREPO active when open
3 & 4REPO Status ContactOpen when REPO is active
Use 16-22AWG cable.
WARNING
The external push button must be voltage free and isolated from all sources and GND. The external REPO
system must not exceed 24V and 20mA.
NOTE
The external EPO switch must latch open when activated.
This 16-pole screw connector allows the connection of six individual configurable output contacts. Each contact
is rated for 24VDC 1A. The maximum potential difference between the pins must not exceed 24VDC.
Table 2Customizable output contacts
Pin
SignalExplanation
1Normally Closed
2Normally Open
3Normally Closed
4Normally Open
5Normally Closed
6Normally Open
7Normally Closed
8Normally Open
9Common Pins 1-8
10Not Available
11Normally Closed
12Normally Open
13Common Pins 11-12
14Normally Closed
15Normally Open
16Common Pins 14-15
Alarm Summary
Bypass Active
Low Battery
AC Fail
Selectable
Selectable
Use 16-22AWG cable. The selectable contacts can be customized (by qualified technicians only) to perform
various functions.
2.4.6Customizable Input Contact—TB1
This 16-pole screw connector allows the connection of four individual configurable input contacts.
Each contact is rated for 24VDC 1A. The maximum potential difference between the pins must not exceed 24VDC.
Table 3Customizable input contacts
Pin
SignalExplanation
1Input #1 (24VDC out)
2Input #1 (24VDC signal)
3Input #2 (24VDC out)
4Input #2 (24VDC signal)
5Input #3 (24VDC out)
6Input #3 (24VDC signal)
7Input #4 (24VDC out)
8Input #4 (24VDC signal)
9-16Common Pins 1-8Not Available
1. This contact is used for the MBB auxiliary contacts. See Figure 5.
2. For 1+N systems, the auxiliary contacts for the MOB breaker must be connected to these inputs. See Figure 5. A shorting switch may be connected here for
Load Bank Breaker/Testing.
Selectable
Selectable
Selectable
Selectable
1
2
Use 16-22AWG cable. All input contacts can be programmed using service software.
WARNING
To drive the inputs, use no-voltage contacts. Do not use voltages supplied by external power supply.
An active economizer Eco Mode is enabled on the Liebert NX 225-600kVA UPS. The mode is incorporated in all
single-module systems and in multi-module (distributed bypass) units with Firmware Version 1.04 or newer.
For details on Eco Mode operation, refer to the Liebert NX operation manual, SL-25354, available at the Liebert
Web site: www.liebert.com. See Figures 20 and 21 for recommended wiring layout.
Eco Mode must be set up by an Vertiv Liebert Services customer engineer. Once set up, Eco Mode becomes the
default operating mode: It shifts the load to bypass if utility power is within specified limits and to
double-conversion (on-line) mode if utility power falls outside the limits.
The UPS can be set up so that Eco Mode can be activated and deactivated by the operator. A Liebert Services
engineer must program an input contact to suppress Eco Mode. A key switch or other device, supplied and
installed by others, can be used to provide the signal that deactivates Eco Mode to the input contact. Operating
the key switch (or other device) allows the UPS to return to Eco Mode as its default mode of operation. Contact
Liebert Services for details.
Additionally, a standby generator mode is available that may be activated by a contact closure (typically from the
generator). This mode shuts Off battery charging and brings the UPS out of Eco Mode while the generator is
providing the power.
2.4.8Connector for Parallel UPS Connection—X19A, X19B
This interface is used for paralleling two or more UPS’s with each other.
2.4.9RJ-45 Interface for Synchronization with External Signal—X20
This interface is used to communicate with an external synchronization device, such as Load Bus Sync Module
(for two modules only) or the Multibus Sync Module (for up to 11 modules). See the manuals related to these
options for more details.
The interface can be used to synchronize the outputs of multiple UPS devices, even when they do not have a
common output. This enables an external static switching device to commutate between UPS outputs in the
event of a malfunction, without creating synchronization problems.
2.4.10 UPS Control Contacts with Battery Cabinet or Module Battery Disconnect
These contacts are used to communicate between the UPS module and Battery cabinets or Module Battery
Disconnects.
Table 4Battery interface
Ter mi na l
BlockPinConnects to (Description of External Item)
1Battery Interface Board TB1154-1
TB3
2Battery Interface Board TB1154-2
3Battery Interface Board TB1154-3
4Battery Interface Board TB1154-4
Use Belden 9156 equivalent wire. Total length of cable from UPS to all battery interface connections must be less
than 1000ft (300m).
2.4.11 UPS Control Contacts with Global Maintenance Bypass
!
These contacts are used to communicate between the UPS module and Maintenance Bypass.
Table 5Maintenance bypass key status
Ter mi na l
BlockPinDescription
5Key status switch, closed = key inserted
TB3
1. See 2.6 - Distributed Static Switch (1+N) System Cabling Layouts for 1+N systems with a Maintenance Bypass.
2. Key Status Input must be Form-C contact.
6Key status switch, common
7Key status switch, closed = key removed
Use 14AWG cable wire up to 500ft. (150m).
Table 6Maintenance Bypass SKRU Enable
Ter mi na l
BlockPinDescription
1Maintenance Bypass Cabinet, closed = load not on inverter
TB4
1. For 1+N systems with a maintenance Bypass, these contacts must be run to each module from an isolated source.
2. These contacts must be run separately from all other control cables.
2Maintenance Bypass Cabinet, common
3Maintenance Bypass Cabinet, closed = load on inverter
Use 14AWG cable wire up to 500ft. (150m)
2.5CONFIGURING GROUND CONNECTIONS
Liebert NX 225-600kVA is compatible with solidly grounded wye sources or a high resistance ground system, if
compatible. Refer to 2.5.3 - High-Resistance Ground Systems.
NOTE
Early production models may not be compatible with high-resistance ground systems.
Improper grounding is the largest single cause of UPS installation and startup problems. Grounding techniques
vary significantly from site to site, depending on several factors.
Proper grounding should be based on the appropriate NEC sections, but safe and proper equipment operation
requires further enhancements. The following pages detail recommendations for grounding various system
configurations to ensure optimal UPS system performance.
CAUTION
The UPS ground lug must be solidly connected to the service entrance ground by an appropriately sized
wire conductor per the NEC.
Each conduit or raceway containing phase conductors must also contain a ground wire, both for UPS
input and output, which are solidly connected to the ground terminal at each termination point.
Conduit-based grounding systems tend to degrade over time. Therefore, using conduit as a grounding
conductor for UPS applications may degrade UPS performance and cause improper UPS operation.
This configuration must NOT be used when single-phase loads are directly connected to the UPS. Please note
that whenever the UPS module transfers to or from bypass, two AC sources (UPS output and bypass) are briefly
connected together and circulating current must flow. In this configuration, the current flows through the ground
path, possibly tripping ground fault interrupters (GFI’s) and distorting the output voltage waveform. Proper
adjustment of ground fault interrupters is necessary to avoid unwanted tripping. The time delay should be set to
at least 0.2 seconds to prevent tripping when the UPS performs a transfer or retransfer operation.
NOTICE
Risk of improper installation. Can cause equipment damage.
Failure to set the ground fault interrupters properly could cause loss of power to the critical load.
Figure 3Grounding diagram—Three-wire single-module systems
Liebert NX 400-600kVA units produced on or after August 1, 2013, with serial numbers as indicated below, are
compatible with High Resistance Ground (HRG) applications. Earlier production units may NOT be compatible
with HRG application and may either bear no label or be specifically labeled as not compatible. If the Liebert NX
UPS is NOT labeled as either compatible or not compatible, contact the factory before installing the unit in an
HRG application.
Liebert NX Serial Numbers/Compatibility with High Resistance Ground
NX 225-600 kVA serial numbers are structured as follows:
21XXXXXXXX1 38X XX XXXX
(Digits 12, 13 and 14 are underlined above)
Digits 12 and 13 of the serial number represent the year of production
Example—1 3 = calendar year 2013; 1 4 would represent calendar year 2014.
Digits 1 and 3 represent the month
Example—1-9 = January-September, A = October, B = November, C = December
(e.g. 1 38 = August 2013, 1 3C= December 2013)
HRG compatibility was instituted for Liebert NX 400-600kVA units effective August 1, 2013, so serial numbers
with Digits 12,13 and 14 of 1 38 or higher designate Liebert NX 400-600kVA units that have HRG compatibility.
Contact the factory for HRG compatibility for Liebert NX 225-300kVA units.
2.6DISTRIBUTED STATIC SWITCH (1+N) SYSTEM CABLING LAYO UTS
The output switchboard for a 1+N system must be configured with one Module Output Circuit Breaker (MOB) for
each UPS module to be connected to that switchboard. The breaker must be equipped with auxiliary contacts
that will be monitored by the UPS so that interlocks will function properly and for the HMI to indicate the
bypassed status of the module. Vertiv recommends using magnetic or thermomagnetic breakers. If molded case
switches will be used, Vertiv recommends installing breakers without electronic trip units or to set the trip units
as follows:
•For 225-300kVA Modules: 2000A for 2 milliseconds
•For 400-600kVA Modules: 3000A for 2 milliseconds.
The input circuit breaker, which feeds the rectifier, is a option because some configurations may not require this
if a maintenance bypass with a rectifier input breaker is located close to the UPS module
3.1.2External Battery Temperature Sensor—Optional
For systems that do not use Liebert NX Battery Cabinets, an optional temperature sensor can be installed to
monitor the battery cabinet or ambient room temperature. This sensor is connected to the BIB board. This
sensor will allow the Liebert NX UPS to perform temperature compensation charging.
3.1.3Matching Liebert NX Battery Cabinet
The optional matching Liebert NX Battery Cabinet can be used to obtain the desired autonomy time. The
battery cabinets are designed to be either attached to the UPS or separate from the UPS (for details, see the
Liebert NX Battery Cabinet installation manual, SL-25430, available at Liebert’s Web site: www.liebert.com)
3.1.4Battery Interface Box
The battery interface box contains a battery interface board. The battery interface box is required when an NX
225-600kVA UPS is installed with any non-Liebert battery cabinet, non-matching MBD or Battery Isolation
Switch (BIS).
One battery interface box is required for each non-Liebert battery cabinet, MBD or BIS.
3.1.5Local EPO Button
A local EPO button with protective cover is available. This option is typically installed at the factory but may be
field-installed by Liebert Services.
3.2COMMUNICATIONAND MONITORING
•Liebert IS-UNITY-DP™ card, supports any two of the following: BACnet IP; BACnet MSTP; Modbus RTU; Modbus TCP; and
SNMP versions 1, 2c and 3
•Liebert IS-485 EXI
•ManageUPS
3.2.1Remote Status Panel
Available as surface mount. The power supply for the remote status panel is factory-installed in the UPS module
and must be ordered with the unit.
3.2.2Alber Monitoring System
The matching Liebert NX Battery Cabinet allows installing an optional Alber® battery monitoring system in the
cabinet. The Alber battery monitoring by Liebert continuously checks all critical battery parameters, such as cell
voltage, overall string voltage, current and temperature. Automatic periodic tests of internal resistance of each
battery will verify the battery’s operating integrity.
Additional capabilities include automatic internal DC resistance tests and trend analysis, providing the ability to
analyze performance and aid in troubleshooting.
3.2.3Capacity on Demand (Softscale) Upgrades
Modules that were ordered and installed as Capacity on Demand soft-scalable modules can be upgraded to
either full 300kVA/KW (from 225 or 250kVA/kW) or 600kVA KW(400 and 500kVA/kW). If this upgrade is
planned, breakers and conductors should be sized for the final capacity.
™
card connects to Liebert SiteLink-E for Liebert SiteScan® Web monitoring
™
card: SNMP v1, Ethernet, HTTP/Web; Modbus RTU and Modbus TCP.
The accessories and options listed in sections 3.1 through 3.2.1 may be applied to the individual modules in a
multi-module (1+N) system or a synchronized dual bus (2N) system.
3.3.1Paralleling Cable Kit
A DB-15 module-to-module communication cable is required for 1+N parallel systems. A kit with two cables, each
82ft. (25m) long, is available. At least one kit is required for each add-on UPS module; the number of kits required
is one fewer than the number of UPS modules in the 1+N system (e.g., six UPS modules would require five kits).
3.3.2Load Bus Sync Controller
Distributes common reference synchronization signal for up to two Liebert NX 225-600 UPS modules. A typical
installation would have two modules synchronized to a common bypass line.
3.3.3Multi-Bus Synch Module (MBSM)
This module is available to support up six or up to 11 UPS modules, and is generally configured to synchronize all
modules to a reference bus (e.g., bypass line). See the manual for this module for more details.
Remove the low-voltage control wire plate (at the top of the unit and then expose the area by removing the
inside cover plate), punch the conduit holes, land the conduit, and then route the control wire to the “chimney
stack” toward the bottom of the unit.
Run the control wires to through the conduit plate provided. If the unit is not on a raised floor, then insert a
rubber grommet into the conduit plate hole (at the bottom of the entry location for the low-voltage control
wiring).
Maximum Heat Dissipation, Full Load, BTU/hr41,00045,00054,00072,00090,000108,000
Color Black (ZP-7021)
Front Door Opening (for serviceability)More than 90°
Degree of Protection for UPS Enclosure IP 20 (with and without front door open)
Minimum Clearance, Top, in (mm) 24 (610)
UPS Rating, kVA
225250300400500600
+10% to -30%
(The UPS will operate at voltages down to -12.5% of nominal at 100% load
without discharging the battery. The UPS will operate without discharging the
battery at 70% of full nominal load with voltage down to -30% of nominal.)
1 to 90 (selectable) in 1 sec. Increments
(Walk-in begins after a 7-second source qualification time. Special settings
are available to permit shorter walk-in times for use with flywheels. Consult
factory for details.)
Synchronized to bypass: ±1.2 Hz (1.2Hz default setting, adjustable up to ±
3.6Hz by factory service personnel)
Synchronized to internal clock ±0.06Hz
1.Nominal input current (considered continuous) is based on full-rated output load. Maximum current includes nominal
input current and maximum battery recharge current (considered non-continuous). Continuous and non-continuous
current are defined in NEC 100.
2.For breaker coordination while the module is overloaded, see the current-versus-time values on the overload curves.
3.Nominal battery voltage is shown at 2.0 volts/cell.
4.Maximum Battery current at End of Discharge level of 1.65 volts per cell.
5.External DC Circuit Overcurrent Protective Device—Caution: To reduce the risk of fire, connect only to a circuit with the
maximum branch circuit overcurrent protection recommended in Tab le 1 3 in accordance with the National Electric Code,
ANSI/NFPA 70.
1. Recommended cable sizes are 167°F (75°C) (THW) wire at 86°F (30°C) ambient.
2. For continuous operations not at 86°F (30°C), Vertiv recommend that the site planner choose the appropriate cable type based on the particular installation
requirements.
3. Recommended conduit is based on FMC type conduit.
Vol tage
(VAC)
Vol tage
(VAC)
(# of conduits); size of conduits; # -size of phase cables per conduit;
size of cable for ground per conduit
(# of conduits); size of conduits; # -size of phase cables per conduit;
Vertiv and the Vertiv logo are trademarks or registered trademarks of Vertiv Co. All other names and logos referred to are trade names,
trademarks or registered trademarks of their respective owners.
While every precaution has been taken to ensure accuracy and completeness herein, Vertiv Co. assumes no responsibility, and disclaims all
liability, for damages resulting from use of this information or for any errors or omissions. Specifications are subject to change without notice.
This document may contain confidential and/or proprietary information of Liebert Corporation, and its receipt or possession does not convey
any right to reproduce, disclose its contents, or to manufacture or sell anything that it may describe. Reproduction, disclosure, or use without
specific authorization from Liebert Corporation is strictly prohibited.
SL-25353_REV8_07-17
, 1050 Dearborn Drive, Columbus, OH, 43085, USA
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.