Vertiv Geist SVR Series, Geist BRE Series, Geist SP Series, Geist NSV Series, Geist J Series Installer/user Manual

...
Page 1
Geist™
Basic Rack PDU
Installer/User Guide
Page 2
The products covered by this instruction manual are manufactured and/or sold by Vertiv. This document is the property of Vertiv and contains confidential and proprietary information owned by Vertiv. Any copying, use or disclosure of it without the written permission of Vertiv is strictly prohibited.
Names of companies and products are trademarks or registered trademarks of the respective companies. Any questions regarding usage of trademark names should be directed to the original manufacturer.
Technical Support Site
If you encounter any installation or operational issues with your product, check the pertinent section of this manual to see if the issue can be resolved by following outlined procedures. Visit https://www.VertivCo.com/en-us/support/ for additional assistance.
Vertiv™ | Basic Rack PDU Installer/User Guide
Page 3
TABLE OF CONTENTS
1 Overview 1
1.1 Environmental 2
1.1.1 Electrical 2
1.1.2 Regulatory Compliance 3
2 Installation 5
2.1 Mounting 6
2.1.1 Optional surge suppression 16
2.1.2 Optional local metering 16
3 Appendices 19
Appendix A: Rack In-line Power Measurement Unit 19
Appendix B: Troubleshooting 21
i
Page 4
This page intentionally left blank
ii
Vertiv™ | Basic Rack PDU Installer/User Guide
Page 5

1 OVERVIEW

The following rack power distribution units (rPDUs) are covered in this document.
Table 1.1 rPDU Model Series Descriptions
AC MAIN
MODEL INPUT INPUT PLU G TYPE
BR
NSV
SP
SVR
VRT
VSS
BRE
VRTE
J
MJ Single Phase NEMA Straight Blade, NEMATwist Lock 15-20 AMPS 100-120V None
VHV
Single Phase NEMA Straight Blade, NEMATwist Lock 15-20 AMPS 125V Single Pole Thermal
Single Phase IEC C20 16-20 AMPS 125V, 250V
Single Phase/Three Phase
Single Phase/Three Phase
NEMA Straight Blade, NEMATwist Lock, IEC, Hardwired
NEMA Straight Blade, NEMATwist Lock,
IEC, IEC Splashproof, Hardwired,
Schuko, British
RATINGS (CURRENT)
10-20 AMPS 100-120V None
10-20 AMPS
AC MAIN RATINGS (VOLTAGE )
120/208V WYE, 200V, 208-240V
OVERC URRENT PROTECTION TYPE (IF APPLICABL E)
Single Pole Thermalor Hydraulic Magnetic
None
BRD Single Phase NEMA Twist Lock 30 AMPS 125V Single Pole Thermal
VRE Single Phase NEMA Twist Lock 30 AMPS 125V, 250V Single Pole Thermal
VRTD Single Phase NEMA Twist Lock 30 AMPS 125V Single Pole Thermal
Single
XP
Y Three Phase
ZP
Phase/Three Phase
Single Phase/Three Phase
NEMA Straight Blade, NEMATwist Lock,
IEC Splashproof
NEMA Twist Lock, IEC Pin & Sleeve, Hardwired
CS8365, IECPin & Sleeve, Hardwired 35-120 AMPS
30 AMPS
16-32 AMPS
100-120V, 120/208V WYE, 200V, 208-240V
208-240/360­415V WYE
100-120V, 120/208V WYE, 200V, 208-240V
Hydraulic Magnetic
Hydraulic Magnetic
Hydraulic Magnetic
NOTE: Global Versions of the VHV Series are intended to be connected to a 16 Amp AC Main Branch Circuit. Global Versions of the XP Series are intended to be connected to a 32 Amp AC Mains Branch Circuit.
1
Page 6

1.1 Environmental

The operational environmental limits pertaining to Temperature, Humidity and Elevation are as defined in the following tables.
Table 1.2 Temperature Limits
MODEL SERIES
BR, BRE, J, L, NSV, SP, SVR, VHV, VRE, VRT, VRTE, VSS, XP, Y, ZP
OPERATING MINIMUM
10°C (50°F) 45°C (113°F) -40°C (-40°F) 70°C (158°F)
OPERATING MAXIMUM
STORAGE MINIMUM
STORAGE MAXIMUM
BRD, MJ, VRTD 10°C (50°F) 25°C (77°F) -40°C (-40°F) 70°C (158°F)
Table 1.3 Humidity Limits
MINIMUM MAXIMUM
Operating 5% 95% (non-condensing)
Storage 5% 95% (non-condensing)
Table 1.4 Elevation Limits
MODEL SERIES
BR, BRD, BRE, NSV, SP, SVR, VRE, VRT, VRTD, VRTE, VSS
J, L, MJ, VHV, XP,Y, ZP
OPERATING MINIMUM
0 m (0 ft) 2,000 m (6561ft) 0 m (0 ft)
OPERATING MAXIMUM
STORAGE MINIMUM
STORAGE MAXIMUM
15,240 m
(50,000 ft)

1.1.1 Electrical

Electrical product characteristics and performance are defined in the following tables. Please see the product nameplate for additional rating limits.
2
Vertiv™ | Basic Rack PDU Installer/User Guide
Page 7
Table 1.5 Receptacle Ratings
RECE PTACLE TYPE RATINGS
NEMA 5-15R or L5-15R 12A, 125VAC
NEMA 5-20R or L5-20R 16A, 125VAC
NEMA 6-20R or L6-20R 16A, 250 VAC
NEMA L6-30R 24A, 250VAC
NEMA L15-20R 3-phase, 16A@ 250VAC
NEMA L15-30R 3-phase, 24A @ 250VAC
IEC-60320 C13 10A, 250VAC (UL & CSA12A, 250VAC)
IEC-60320 C19 16A, 250VAC (UL & CSA16A, 250VAC)

1.1.2 Regulatory Compliance

Vertiv products are regulated for Safety, Emissions, and Environment Impact per the below agencies and policies.
Underwriter Labratory (UL)
UL Standards are used to assess products; test components, materials, systems and performance; and evaluate environmentally sustainable products, renewable energies, food and water products, recycling systems and other innovative technologies.
The UL standards specific to this equipment (if applicable) are as noted on the device nameplate.
Federal Communications Commission (FCC)
The Federal Communications Commission (FCC) regulates interstate and international communications by radio, television, wire, satellite, and cable in all 50 states, the District of Columbia and U.S. territories. An independent U.S. government agency overseen by Congress, the commission is the United States' primary authority for communications laws, regulation and technological innovation.
The FCC standards specific to this equipment are:
This Class A device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.
This Class A digital apparatus complies with Canadian ICES-003.
Cet appareil numérique de la classe A est conforme à la norme NMB-003 du Canada.
1 Overview
WARNING! Changes or modifications to this unit not expressly approved by the party responsible for compliance could void the user’s authority to operate this equipment.
3
Page 8
ROHS/WEEE
RoHS, also known as Lead-Free, stands for Restriction of Hazardous Substances. RoHS, also known as Directive 2002/95/EC, originated in the European Union and restricts the use of six hazardous materials found in electrical and electronic products. All applicable products in the EU market after July 1, 2006 must pass RoHS compliance. RoHS impacts the entire electronics industry and many electrical products as well.
WEEE stands for Waste from Electrical and Electronic Equipment. WEEE Directive 2002/96/EC mandates the treatment, recovery and recycling of electric and electronic equipment (90% ends up in landfills). All applicable products in the EU market must pass WEEE compliance and carry the Wheelie Bin sticker.
See product label for RoHS/WEEE compliance marks.
4
Vertiv™ | Basic Rack PDU Installer/User Guide
Page 9

2 INSTALLATION

Use the following images in the mounting section to install your rack PDU.
NOTE: Please visit http://www.VertivCo.com/ComplianceRegulatoryInfo for important safety information prior to installation.
To install your unit:
1. Using appropriate hardware, mount the unit to the rack.
2. Plug the rPDU into an appropriately-rated and protected branch-circuit receptacle.
3. Plug in the devices to be powered by the rPDU.
4. Turn on each device connected to the rPDU.
NOTE: It is recommended that all connected equipment is powered on in a sequential manner to avoid high inrush current.
NOTE: XP Series rPDUs may optionally be configured as Isolated Ground units. All Isolated Ground units will be shipped with an enclosure grounding cable. This cable must be connected between the enclosure and a reliable safety ground.
5
Page 10

2.1 Mounting

Optional mounting brackets are sold separately.
Figure 2.1 Full-length Bracket
6
Vertiv™ | Basic Rack PDU Installer/User Guide
Page 11
Figure 2.2 Mini L Bracket
2 Installation
7
Page 12
Figure 2.3 VerticalExtension Bracket
8
Vertiv™ | Basic Rack PDU Installer/User Guide
Page 13
Figure 2.4 Tool-less Mounting Hardware
2 Installation
9
Page 14
Figure 2.5 Tool-less Full-length Bracket
10
Vertiv™ | Basic Rack PDU Installer/User Guide
Page 15
Figure 2.6 Single Side-mount Unit Brackets
2 Installation
11
Page 16
Figure 2.7 Offset Side-mount Brackets
Figure 2.8 7" Extension Brackets (XB-7)
12
Vertiv™ | Basic Rack PDU Installer/User Guide
Page 17
Figure 2.9 Flush Mount Brackets (FM)
Figure 2.10 Adjustable Mount Brackets (AM)
2 Installation
13
Page 18
Figure 2.11 Panel Mount Brackets (PM)
Figure 2.12 23" Conversion Mounting Brackets (23-RM)
14
Vertiv™ | Basic Rack PDU Installer/User Guide
Page 19
Figure 2.13 19" Horizontal/Panel Mount Brackets (7938)
Figure 2.14 Top and Bottom Mounting Clips (9083C & 9084C)
2 Installation
15
Page 20
NOTE: Mounting clips are only intended for use with NSV and VSS Series rPDUs. Using the top and bottom mounting clips, attach the rPDU to the rack as shown.

2.1.1 Optional surge suppression

The SP, SVR, and VSS Series rPDUs include a surge suppression circuit that is designed to prevent voltage surges on the input power line from reaching devices powered by the rPDU. The surge suppression circuit uses Metal Oxide Varistors (MOVs) connected between line, neutral, and ground wires to prevent voltage surges from damaging connected devices.
Figure 2.15 Surge Suppression LEDs
Table 2.1 Surge Protection Ciruit Rating
NUMBER DESCRIPTION
Protection Modes Line-Line, Line-Neutral, Neutral-Ground
Maximum Clamping Voltage 340V
Energy Absorption 720 Joules
Green Light Indicator Power On
Red Light Indicator Surge Protection Active

2.1.2 Optional local metering

Power meter
The Geist PM-1 power meter is a low-power, high accuracy meter capable of measuring true RMS Current, Voltage, Power, and Power Factor. These values are individually shown on a 4-digit LED Display, which continuously scrolls through the four different measured values. Each one of these displayed parameters is defined below. The power meter automatically cycles through the displayed values when the rPDU is connected to AC Mains power.
16
Vertiv™ | Basic Rack PDU Installer/User Guide
Page 21
Current: rPDU output current draw measured in true RMS Amps.
Voltage: rPDU output voltage measured in true RMS Voltage.
Power: rPDU output power measured in Watts – referred to as real or active power.
Power Factor: Ratio of real rPDU output power to apparent rPDU output power.
Figure 2.16 Power Meter Display
Current meter
The Geist CM-1 current meter is a low-power, high accuracy meter capable of measuring true RMS Current. The value of current is continuously shown on a 4-digit LED Display. The Current Meter automatically displays the value of output current when the rPDU is connected to AC Mains power.
Figure 2.17 Current Meter
2 Installation
17
Page 22
This page intentionally left blank
18
Vertiv™ | Basic Rack PDU Installer/User Guide
Page 23

3 APPENDICES

Appendix A: Rack In-line Power Measurement Unit

A.1 Product Specifications
Basic rack PDUs not equipped with local current monitoring can be retrofit with L-Series inline power monitoring units. The L-series products are inline power monitoring units intended for connection between an AC Mains circuit and a Rack Power Distribution Unit (rPDU). The inline power monitoring units are designed to be powered by a single phase AC input circuit and have an outlet or output cord and connector body for connection to an external device (such as an rPDU). The Inline power monitoring units are rated from 12 to 32 Amps depending on the unit’s configuration. Inline power monitoring units can be configured with a Geist local current meter or power meter to perform the monitoring functions.
Table A.1 L-Series Inline Power Monitoring Units
PART # MODEL # AMPS VOLTS PLUG TYPE RECEPTACLE TYPE
12416 GLCE-001C13-00C14 10 230 IECC14 IEC C13
G1113 GLCE-002C19-00C20 16 230 IEC C20 IEC C19
15693 LCE-001C13-00C14 15 125 or 208 IEC C14 IECC13
15694 LCE-002C19-00C20 20 125 or 208 IEC C20 IEC C19
19
Page 24
Figure A.1 L-Series Inline Power Monitoring Unit
A.2 Detachable power supply cords
L-Series Inline Power Monitoring Units may optionally be configured with an AC Inlet for connection to AC Mains power. Use only detachable power supply cords of the appropriate size and type, as stated below, with the unit. Use only with light PVC sheathed flexible cords (according to IEC 60227) or ordinary tough rubber-sheathed flexible cords (according to IEC 60245) that terminate in an attachment plug meeting local/national code requirements.
For Global units use a minimum 1.5 mm2 nominal conductor cross-sectional area detachable power supply cord with ratings of 300 V and 75 °C. The power supply cord cable designation should be H03VV-F, H03VVH2-F, or better.
For North American units use a minimum 14 AWG power supply cord with ratings of 300 V and 75 °C. The power supply cord cable designation should be SJT or better.
To install an L-Series inline power monitoring unit:
NOTE: Please visit http://www.VertivCo.com/ComplianceRegulatoryInfo for important safety information prior to installation.
1. Using the appropriate hardware, mount the In-Line Meter to the rack.
2. Plug the In-Line Meter into de-energized branch circuit receptacle.
3. Connect the external device to the In-Line Meter’s output outlet or connector.
4. Turn on the branch circuit to energize the In-Line Meter.
5. Power on the external device.
NOTE: Branch Circuit should be sized based on the In-Line Meter’s nameplate electrical rating. For North American units, the branch circuit should have a current rating equal to 125% of the unit’s nameplate current rating. For global units, the branch circuit should have a current rating equal to the unit’s nameplate current rating.
20
Vertiv™ | Basic Rack PDU Installer/User Guide
Page 25

Appendix B: Troubleshooting

Ensure all devices plugged in to the rack PDU receptacles are receiving power.
No service or maintenance is required. Do not attempt to open the rPDU or you may void the warranty. There are no serviceable parts inside the rPDU. It is recommended that power be removed from the unit before installing or removing any equipment.
B.1 Technical Support
Technical support can be found at www.VertivCo.com/support.
Americas
Website: www.VertivCo.com/geist
Email: support@VertivCo.com
Telephone: 1-888-630-4445
Europe and Middle East
Technical Support: www.VertivCo.com/en-emea/support
Email: eoc@VertivCo.com
Telephone: 1-800-1155-4499
Asia
Telephone (English): 1-888-630-4445 (US number)
Telephone (Chinese): +86 755 8663 9505
21
Page 26
This page intentionally left blank
22
Vertiv™ | Basic Rack PDU Installer/User Guide
Page 27
Vertiv™ | Basic Rack PDU Installer/User Guide
Page 28
VertivCo.com | Vertiv Headquarters, 1050 Dearborn Drive, Columbus, OH, 43085, USA
© 2019 VertivCo. Allrights reserved. Vertiv and the Vertivlogo are trademarks or registered trademarks ofVertiv Co. Allother names and logos referred to are trade names, trademarks or registered trademarks of their respective owners. While every precaution has been taken to ensure accuracy and completeness herein, VertivCo. assumes no responsibility, and disclaims all liability, for damages resulting from use ofthis information or for any errors or omissions. Specifications are subject to c hange without notice.
VM1228/590-2220-501A