Vertiv EXM Parallel Cabinet User Manual

Page 1
Liebert®
EXM™ Parallel Cabinet
User Manual—10-200kVA, 60Hz
Page 2
The information contained in this document is subject to change without notice and may not be suitable for all applications. While every precaution has been taken to ensure the accuracy and completeness of this document, Vertiv assumes no responsibility and disclaims all liability for damages resulting from use of this information or for any errors or omissions. Refer to other local practices or building codes as applicable for the correct methods, tools, and materials to be used in performing procedures not specifically described in this document.
The products covered by this instruction manual are manufactured and/or sold by Vertiv This document is the property of Vertiv and contains confidential and proprietary information owned by Vertiv. Any copying, use or disclosure of it without the written permission of Vertiv is strictly prohibited.
Names of companies and products are trademarks or registered trademarks of the respective companies. Any questions regarding usage of trademark names should be directed to the original manufacturer.
Technical Support Site
If you encounter any installation or operational issues with your product, check the pertinent section of this manual to see if the issue can be resolved by following outlined procedures. Visit https://www.VertivCo.com/en-us/support/ for additional assistance.
Page 3
TABLE OF CONTENTS
IMPORTANT SAFETY INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
SAVE THESE INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1.0 M
1.1 Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.2 Preliminary Checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.3 Environmental Considerations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.4 Positioning. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.5 Cable Entry . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.6 Power Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
ECHANICAL INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.3.1 Room . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.3.2 Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.4.1 Moving the Cabinets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.4.2 Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.4.3 Floor Installation/Anchoring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.6.1 Power Cable Connection Procedure. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.0 INSTALLATION DRAWINGS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
3.0 S
3.1 Electrical Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28
3.2 Torque Requirements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29
PECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27
FIGURES
Figure 1 Cabinet arrangement—Liebert EXM UPS, battery cabinets, Liebert Parallel Cabinet7
Figure 2 Parallel (1+1, 2+0) cabinet, 10-200kVA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Figure 3 One-line diagram, Parallel (2+1) Cabinet, 10-160kVA. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Figure 4 Main components—300mm 1+1 Liebert EXM Parallel Cabinet . . . . . . . . . . . . . . . . . . . . . . 14
Figure 5 Main components—600mm 2+1 Liebert EXM Parallel Cabinet, . . . . . . . . . . . . . . . . . . . . . 15
Figure 6 Main components—800mm 2+1 Liebert EXM Parallel Cabinet. . . . . . . . . . . . . . . . . . . . . . 16
Figure 7 Main components—800mm 1+1 and 2+0 Liebert EXM Parallel Cabinet. . . . . . . . . . . . . 17
Figure 8 Outline drawing—300mm Liebert EXM Parallel Cabinet. . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Figure 9 Outline drawing—600mm Liebert EXM Parallel Cabinet. . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Figure 10 Outline drawing—800mm Liebert EXM Parallel Cabinet. . . . . . . . . . . . . . . . . . . . . . . . . . . .20
Figure 11 Control wiring diagram, Liebert EXM Parallel Cabinet, 1+1 and 2+0 paralleling . . . . . 21
Figure 12 Control wiring diagram, Liebert EXM Parallel Cabinet, 2+1 paralleling . . . . . . . . . . . . . . 22
Figure 13 Control wiring diagram, Liebert EXM Parallel Cabinet, 2+0 and 1+1 paralleling with
SKRU23 Figure 14 Control wiring diagram, Liebert EXM Parallel Cabinet, 2+1 paralleling with SKRU. . .24
Figure 15 Control Wiring Diagram, Liebert EXM Parallel Cabinet, 2+1 with REPO . . . . . . . . . . . . .25
Figure 16 Control wiring diagram, Liebert EXM Parallel Cabinet, 2+0 and 1+1 with REPO . . . . .26
i
Page 4
TAB LES
Table 1 Power wiring for Liebert EXM UPS to Liebert EXM Parallel Cabinet . . . . . . . . . . . . . . . . . 9
Table 2 Control wiring for Liebert EXM UPS to Liebert EXM Parallel Cabinet . . . . . . . . . . . . . . . 10
Table 3 Control wiring for Liebert EXM UPS to Liebert EXM Parallel Cabinet with SKRU inter-
lock11
Table 4 Liebert EXM Parallel Cabinet specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27
Table 5 Liebert EXM Parallel Cabinet output currents, 1+1 configuration. . . . . . . . . . . . . . . . . . . .28
Table 6 Liebert EXM Parallel Cabinet output currents, 2+0 and 2+1 configurations . . . . . . . . .28
Table 7 Recommended lug sizes (compression type) M10, 3/8" bolt . . . . . . . . . . . . . . . . . . . . . . . .29
Table 8 Busbar torque for power wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29
Table 9 Terminal block torque with compression lugs for control wiring . . . . . . . . . . . . . . . . . . . .29
ii
Page 5

Important Safety Instructions

!
!
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS
This manual contains important instructions that should be followed during installation of your Liebert EXM Parallel Cabinet.
WARNING
Risk of moving heavy units and tipping hazard. Can cause equipment damage, injury and death.
Exercise extreme care when handling cabinets to avoid equipment damage or injury to personnel. The Liebert EXM Parallel Cabinet’s weight ranges from 263-714lb. 119.3 to
323.8kg. Locate center of gravity symbols and determine unit weight before handling each
cabinet. Test lift and balance the cabinets before transporting. Maintain minimum tilt from vertical at all times. Slots at the base of the cabinets are intended for forklift use. Base slots will support the unit only if the forks are completely beneath the unit.
In case of fire involving electrical equipment, use only carbon dioxide fire extinguishers or those approved for use in fighting electrical fires.
Extreme caution is required when performing maintenance. Be constantly aware that the system contains high DC as well as AC voltages. Check for voltage with both AC and DC voltmeters prior to making contact.
AVERTISSEMENT
Le centre de gravité élevé des appareils présente un risque de renversement lors des déplacements pouvant entraîner des dommages matériels, des blessures et même la mort.
Faites preuve d’une extrême prudence lors de la manutention des armoires afin d’éviter de les endommager ou de blesser le personnel. Les armoires de dérivation d’entretien EXM de Liebert pèsent de 263 à 714 lb (de 119,3 à 323,8 kg). Identifiez les symboles de centre de gravité et déterminez le poids de l’appareil avant
de manipuler chaque armoire. Testez le levage et l’équilibre des armoires avant de transporter l’appareil. Maintenez en tout temps l’inclinaison verticale minimale.
Les fentes situées à la base des armoires sont conçues pour utiliser le chariot élévateur. Les fentes situées à la base peuvent soutenir le système seulement si les fourches se trouvent complètement sous le système.
En cas d’incendie associé à du matériel électrique, n’utilisez que des extincteurs à dioxyde de carbone ou homologués pour la lutte contre les incendies d’origine électrique. Les opérations d’entretien requièrent une extrême prudence.
Soyez toujours conscient du fait que le système contient des tensions c.c. et c.a. élevées. Vérifiez les tensions avec des voltmètres c.a. et c.c. avant d’établir tout contact.
Vertiv | Liebert
®
EXM™ Parallel Cabinet User Manual | 1
Page 6
Important Safety Instructions
!
Read this manual thoroughly before working with the Liebert Parallel Cabinet. Retain this manual for use by installing personnel.
WARNING
Risk of arc flash and electric shock. Can cause equipment damage, injury and death. Under typical operation and with all doors closed, only normal safety precautions are
necessary. The area around the system should be kept free of puddles of water, excess moisture and debris.
Special safety precautions are required for procedures involving handling, installation and maintenance of the Liebert Parallel Cabinet. Observe all safety precautions in this manual before handling or installing the Liebert Parallel Cabinet. Observe all precautions in the Operation and Maintenance Manual, before as well as during performance of all maintenance procedures.
This equipment contains circuits that are energized with high voltage. Only test equipment designed for troubleshooting should be used. This is particularly true for oscilloscopes. Always check with an AC and DC voltmeter to ensure safety before making contact or using tools. Even when the power is turned Off, dangerously high potential electric charges may exist.
All power and control wiring should be installed by a qualified electrician. All power and control wiring must comply with the NEC and applicable local codes.
ONLY properly trained and qualified personnel should perform maintenance on the Liebert Parallel Cabinet. When performing maintenance with any part of the equipment under power, service personnel and test equipment should be standing on rubber mats. The service personnel should wear insulating shoes for isolation from direct contact with the floor ground.
One person should never work alone, even if all power is removed from the equipment. A second person should be standing by to assist and summon help in case of an accident.
Vertiv | Liebert
®
EXM™ Parallel Cabinet User Manual | 2
Page 7
Important Safety Instructions
!
AVERTISSEMENT
Risque d’arc ou de décharge électrique pouvant entraîner des dommages matériels, des blessures et même la mort. Les précautions de sécurité habituelles suffisent lorsque le système est en mode de fonctionnement normal et que toutes les portes sont fermées. La zone entourant le système doit être exempte de flaques d’eau, d’humidité excessive et de débris. Des précautions de sécurité spéciales sont requises pour les procédures associées à la manutention, à l’installation et à l’entretien de l’armoire de dérivation d’entretien. Observez toutes les précautions de sécurité décrites dans le présent manuel avant de manipuler ou d’installer l’armoire de dérivation d’entretien. Observez également toutes les précautions décrites dans le manuel d’utilisation et d’entretien, avant et pendant toutes les procédures d’entretien. Cet équipement comporte des circuits à haute tension. Seuls des équipements d’essai conçus pour le dépannage doivent être utilisés. Cette mise en garde couvre notamment les oscilloscopes. Utilisez toujours un voltmètre c.a. et c.c. pour vérifier les tensions avant d’établir un contact ou d’utiliser des appareils. Des tensions dangereusement élevées peuvent demeurer dans le système même une fois l’alimentation coupée. Tous les câbles d’alimentation et de contrôle doivent être installés par un électricien qualifié. Tous les câbles d’alimentation et de contrôle doivent être conformes au Code national de l’électricité des États-Unis (NEC) et ainsi qu’aux codes locaux en vigueur. L’entretien de l’armoire de dérivation d’entretien ne doit être confié qu’à des professionnels qualifiés et dûment formés. Les responsables de l’entretien et l’équipement d’essai doivent reposer sur des tapis de caoutchouc lors de toute intervention sur une pièce d’équipement sous tension. Les responsables de l’entretien doivent porter des chaussures isolantes pour prévenir tout contact direct avec le plancher. Une personne ne devrait jamais travailler seule, même si toute l’alimentation de l’équipement est coupée. Une deuxième personne devrait toujours être présente pour porter assistance ou chercher de l’aide en cas d’accident.
Vertiv | Liebert
®
EXM™ Parallel Cabinet User Manual | 3
Page 8
Mechanical Installation
!
!

1.0 MECHANICAL INSTALLATION

1.1 INTRODUCTION

This section describes the requirements that must be taken into account when planning the positioning and cabling of the Liebert EXM Parallel Cabinet.
This chapter is a guide to general procedures and practices that should be observed by the installing engineer. The particular conditions of each site will determine the applicability of such procedures.
WARNING
Risk of arc flash and electric shock. Can cause equipment damage, injury and death. Installation must be performed only by properly trained and qualified personnel wearing appropriate safety clothing. Eye protection should be worn to prevent injury from accidental electrical arcs. Remove rings, watches and all other metal objects. Only use tools with insulated handles. Wear rubber gloves.
AVERTISSEMENT
Risque d’arc ou de décharge électrique pouvant entraîner des dommages matériels, des blessures et même la mort.
L’installation ne doit être confiée qu’à des professionnels qualifiés et dûment formés portant des vêtements de sécurité adéquats.
Des lunettes de sécurité doivent être portées afin de prévenir les blessures en cas d’arcs accidentels. Retirez montre, bagues et tout autre objet métallique. Utilisez uniquement des outils dont le manche est isolé. Portez des gants de protection en caoutchouc.
NOTICE
Risk of improper installation. Can cause equipment damage and void warranty. The Liebert EXM Parallel Cabinet should be installed by a qualified engineer in accordance with the
information contained in this chapter All equipment not referred to in this manual is shipped with details of its own mechanical and electrical
installation. Do not apply electrical power to the UPS equipment before the arrival of the commissioning engineer.

1.2 PRELIMINARY CHECKS

Before installing the Liebert EXM Parallel Cabinet, carry out the following preliminary checks:
• Visually examine the equipment for transit damage, both internally and externally. Report any damage to the shipper immediately.
• Verify that the correct equipment is being installed. The equipment supplied has an identification tag on the back of the main door reporting: the type, size and main calibration parameters of the UPS.
• Verify that the room satisfies the environmental conditions stipulated in the equipment specifications, paying particular attention to the ambient temperature and air exchange system.
Vertiv | Liebert
®
EXM™ Parallel Cabinet User Manual | 4
Page 9
Mechanical Installation

1.3 ENVIRONMENTAL CONSIDERATIONS

1.3.1 Room

The Liebert EXM Parallel Cabinet is intended for indoor installation and should be located in a cool, dry, clean-air environment with adequate ventilation to keep the ambient temperature within the specified operating range (see 3.0 - Specifications).
All models of the Liebert EXM Parallel Cabinet are convection-cooled. To permit air to enter and exit and prevent overheating or malfunctioning, do not cover the ventilation openings.
When bottom entry is used, the conduit plate can be removed and punched and replaced. The bottom conduit plate must be replaced for proper airflow. If necessary to cool the room, install a system of room extractor fans.
NOTE
The Liebert EXM Parallel Cabinet is suitable for mounting only on concrete and other noncombustible surfaces.

1.3.2 Storage

Should the equipment not be installed immediately, it must be stored in a room for protection against excessive humidity and or heat sources (see Tab le 4).

1.4 POSITIONING

The cabinet is structurally designed to handle lifting from the base. Access to the power terminals, auxiliary terminals blocks and power switches is from the top and
sides. The top and side removable panels are secured to the chassis by screws. The side panel can be
removed for access to the power connections bars, auxiliary terminal blocks and power isolators.

1.4.1 Moving the Cabinets

The route to be travelled between the point of arrival and the unit’s position must be planned to make sure that all passages are wide enough for the unit and that floors are capable of supporting its weight (for instance, check that doorways, lifts, ramps, etc. are adequate and that there are no impassable corners or changes in the level of corridors).
Ensure that the cabinet weight is within the designated surface weight loading (kg/cm2) of any handling equipment. See Ta bl e 4 for the weight of the Liebert EXM Parallel Cabinet 300mm, 600mm and 800mm models.
Ensure that any lifting equipment used in moving the cabinet has sufficient lifting capacity. The Liebert EXM Parallel Cabinet can be handled with a forklift or similar equipment. For
operations with a fork lift, refer to installation drawings in 2.0 - Installation Drawings. Because the weight distribution in the cabinet is uneven, use extreme care during handling and
transporting. When moving the unit by forklift, care must be taken to protect the panels. Do not exceed a
15-degree tilt with the forklift.
Vertiv | Liebert
®
EXM™ Parallel Cabinet User Manual | 5
Page 10
Handling the unit with straps is not authorized.
!
!
WARNING
Risk of moving heavy units and tipping hazard. Can cause equipment damage, injury and death.
Exercise extreme care when handling cabinets to avoid equipment damage or injury to personnel. The Liebert EXM Parallel Cabinet’s weight ranges from 263 to 714 lb. (119.3 to
323.8kg) Locate center of gravity symbols and determine unit weight before handling each
cabinet. Test lift and balance the cabinets before transporting. Maintain minimum tilt from vertical at all times.
AVERTISSEMENT
Le centre de gravité élevé des appareils présente un risque de renversement lors des déplacements pouvant entraîner des dommages matériels, des blessures et même la mort. Faites preuve d’une extrême prudence lors de la manutention des armoires afin d’éviter de les endommager ou de blesser le personnel. Les armoires de dérivation d’entretien EXM de Liebert pèsent de 263 à 714 lb (de 119,3 à 323,8 kg) Identifiez les symboles de centre de gravité et déterminez le poids de l’appareil avant de manipuler chaque armoire. Testez le levage et l’équilibre des armoires avant de transporter l’appareil. Maintenez en tout temps l’inclinaison verticale minimale.
Mechanical Installation

1.4.2 Clearances

Liebert EXM Parallel Cabinet’s have no ventilation grilles at either side or at the rear. Clearance around the front of the equipment should be sufficient to enable free passage of personnel with the doors fully opened. It is important to leave a distance of 24" (610mm) between the top of the cabinet and any overhead obstacles to permit adequate circulation of air coming out of the unit.

1.4.3 Floor Installation/Anchoring

The installation diagrams in 2.0 - Installation Drawings of this manual identify the location of the holes in the base plate through which the equipment can be bolted to the floor. If the equipment is to be located on a raised floor it should be mounted on a pedestal suitably designed to accept the equipment point loading.

1.5 CABLE ENTRY

Cables can enter the Liebert EXM Parallel Cabinet from the bottom or top.
Vertiv | Liebert
®
EXM™ Parallel Cabinet User Manual | 6
Page 11
Mechanical Installation
!
!

1.6 POWER CABLES

The Liebert EXM Parallel Cabinet requires both power and control cabling once it has been mechanically installed. All control cables must be separate from the power cables. Run control cables in metal conduits or metal ducts that are electrically bonded to the cabinets they are connected to.
The cable design must comply with the voltages and currents provided in Ta bl es 5 and 6, follow local wiring practices and take into consideration the environmental conditions (temperature and physical support media).
For cable entry locations, refer to Figures 8 and 9.
WARNING
Risk of electric shock. Can cause equipment damage, injury and death. Before cabling up the cabinet, ensure that you are aware of the location and operation of
the external isolators that connect the input/bypass supply. Check that these supplies are electrically isolated, and post any necessary warning signs to
prevent their inadvertent operation.
AVERTISSEMENT
Risque de décharge électrique pouvant entraîner des dommages matériels, des blessures et même la mort.
Avant de procéder au câblage de l’armoire, assurez-vous que vous êtes au courant de l’emplacement et du fonctionnement des isolateurs externes qui raccordent l’alimentation d’entrée ou de dérivation.
Vérifiez que ces raccords sont isolés électriquement et installez tous les panneaux d’avertissement nécessaires pour empêcher leur utilisation accidentelle.
The following are guidelines only and are superseded by local regulations and codes of practice where applicable:
• Take special care when determining the size of the neutral cable (grounded conductor), because current circulating on the neutral cable may be greater than nominal current in the case of nonlinear loads.
• The grounding conductor should be sized according to local or NEC codes, cable lengths, type of protection, etc. The grounding cable connecting the UPS to the main ground system must follow the most direct route possible.
• Consider using smaller, paralleled cables for heavy currents as a way of easing installation.
Vertiv | Liebert
®
EXM™ Parallel Cabinet User Manual | 7
Page 12
Mechanical Installation
Liebert
EXM
Liebert
EXM
Liebert
EXM
Parallel
Cabinet
(Matching)
Battery
Cabinet
(Matching)
Liebert
EXM
Battery
Cabinet
(Matching)
Battery
Cabinet
(Matching)
Parallel Cabinet
(Matching)
Liebert
EXM
Figure 1 Cabinet arrangement—Liebert EXM UPS, battery cabinets, Liebert Parallel Cabinet
Vertiv | Liebert
®
EXM™ Parallel Cabinet User Manual | 8
Page 13
Mechanical Installation
!
!
!
!

1.6.1 Power Cable Connection Procedure

The system input, UPS bypass, UPS output and system output cables (all require lug type terminations) are connected to power blocks behind the power isolator switches as shown in
2.0 - Installation Drawings. These are accessible when the side or top panel is removed.
Equipment Ground
The equipment ground busbar is near the input and output power supply connections as shown in 2.0 - Installation Drawings. The grounding conductor must be connected to the ground busbar.
All cabinets and cable trunking should be grounded in accordance with local regulations.
WARNING
Risk of electric shock. Can cause equipment damage, injury and death. Failure to follow adequate grounding procedures can result in electric shock hazard to
personnel and the risk of fire, should a ground fault occur.
AVERTISSEMENT
Risque de décharge électrique pouvant entraîner des dommages matériels, des blessures et même la mort. Le non-respect des procédures de mise à la terre peut entraîner des risques d’électrocution du personnel, ou des risques d’incendie en cas de défectuosité de la mise à la terre.
WARNING
Risk of electric shock. Can cause equipment damage, injury and death. The operations described in this section must be performed by authorized electricians or properly trained and qualified technical personnel wearing adequate safety clothing, eye protection and gloves. If you have any difficulties, do not hesitate to contact Vertiv. See the back page of this manual for contact information.
AVERTISSEMENT
Risque de décharge électrique pouvant entraîner des dommages matériels, des blessures et même la mort.
Toutes les opérations décrites dans cette section ne doivent être effectuées que par des électriciens ou des techniciens professionnels dûment formés et qualifiés portant gants, lunettes et vêtements de protection adéquats. En cas de problème, n’hésitez pas à communiquer avec Vertiv. Pour obtenir les renseignements de contact, consultez la dernière page de ce manuel.
NOTE
Proper grounding considerably reduces problems in systems caused by electromagnetic interference.
Once the equipment has been finally positioned and secured, connect the power cables as described in the following procedure.
Refer to the appropriate cable connection drawing in 2.0 - Installation Drawings.
1. Verify that the equipment is isolated from its external power source and all the power isolators are open. Check that these supplies are electrically isolated and post any necessary warning signs to prevent their inadvertent operation.
2. Remove the panels.
Vertiv | Liebert
®
EXM™ Parallel Cabinet User Manual | 9
Page 14
Mechanical Installation
3. Connect the ground and any necessary main bonding jumper to the equipment ground busbar.
NOTE
The grounding and neutral bonding arrangement must be in accordance with local and national codes of practice.
NOTE
Care must be taken when routing power cables. Ensure that the cables do not touch other busbars.
4. See Ta b le 1 for all power connections.
5. Tighten the connections to the proper torque (see Tab l e 8 ). Ensure correct phasing.
6. Connect the control wiring from the Liebert EXM Parallel Cabinet terminal block TB1 to the Liebert EXM UPS Bypass Module (X9 J23 and J26). Tighten the connections to the proper torque (see Ta bl e 8).
7. Replace the panels. If your system has an SKRU interlock, refer to Ta bl e 3.
Table 1 Power wiring for Liebert EXM UPS to Liebert EXM Parallel Cabinet
System Configuration
Liebert EXM 10-20kVA 2+0
Liebert EXM 10-40kVA 1+1
Liebert EXM 30-40kVA 2+0
Liebert EXM 10-40kVA 2+1
From To
Utility UPS 1 AC Input
Utility UPS 2 AC Input
Utility TB4
UPS 1 AC Output TB1
UPS 2 AC Output TB2
TB1 MOB1
TB2 MOB2
TB5 Critical Load
Utility UPS 1 AC Input
Utility UPS 2 AC Input
Utility MBB
UPS 1 AC Output TB1
UPS 2 AC Output TB2
TB1 MOB1
TB2 MOB2
TB5 Critical Load
Utility UPS 1 AC Input
Utility UPS 2 AC Input
Utility UPS 3 AC Input
Utility TB4
UPS 1 AC Output TB1
UPS 2 AC Output TB2
UPS 3 AC Output TB3
TB1 MOB1
TB2 MOB2
TB3 MOB3
TB5 Critical Load
Vertiv | Liebert
®
EXM™ Parallel Cabinet User Manual | 10
Page 15
Table 1 Power wiring for Liebert EXM UPS to Liebert EXM Parallel Cabinet (continued)
System Configuration
Liebert EXM 60-100kVA 1+1
Liebert EXM 60-100kVA 2+0
Liebert EXM 60-100kVA 2+1
Liebert EXM 120-200kVA 1+1
Liebert EXM 120-160kVA 2+0
Liebert EXM 120-160kVA 2+1
From To
Utility UPS 1 AC Input
Utility UPS 2 AC Input
Utility TB4
UPS 1 AC Output TB1
UPS 2 AC Output TB2
TB1 MOB1
TB2 MOB2
TB5 Critical Load
Utility UPS 1 AC Input
Utility UPS 2 AC Input
Utility MBB
UPS 1 AC Output MOB1
UPS 2 AC Output MOB2
Parallel Cabinet Output Critical Load
Utility UPS 1 AC Input
Utility UPS 2 AC Input
Utility UPS 3 AC Input
UPS 1 AC Output MOB1
UPS 2 AC Output MOB2
UPS 3 AC Output MOB3
Parallel Cabinet Output Critical Load
Utility UPS 1 AC Input
Utility UPS 2 AC Input
Utility MBB
UPS 1 AC Output MOB1
UPS 2 AC Output MOB2
Parallel Cabinet Output Critical Load
Utility UPS 1 AC Input
Utility UPS 2 AC Input
Utility UPS 3 AC Input
Utility MBB
UPS 1 AC Output MOB1
UPS 2 AC Output MOB2
UPS 3 AC Output MOB3
Parallel Cabinet Output Critical Load
Mechanical Installation
Vertiv | Liebert
®
EXM™ Parallel Cabinet User Manual | 11
Page 16
Table 2 Control wiring for Liebert EXM UPS to Liebert EXM Parallel Cabinet
System Configuration From Liebert EXM UPS Bypass Module TB1
UPS 1
X9J26-9 TB1-8
X9J26-11 TB1-7
X9J26-13 TB1-1
2+1 1+1 and 2+0
2+1
UPS2
UPS3
X9J26-15 TB1-2
X9J26-9 TB1-10
X9J26-11 TB1-9
X9J26-13 TB1-3
X9J26-15 TB1-4
X9J26-9 TB1-12
X9J26-11 TB1-11
X9J26-13 TB1-5
X9J26-15 TB1-6
Mechanical Installation
Vertiv | Liebert
®
EXM™ Parallel Cabinet User Manual | 12
Page 17
Mechanical Installation
Table 3 Control wiring for Liebert EXM UPS to Liebert EXM Parallel Cabinet with SKRU interlock
System Configuration From Liebert EXM UPS Bypass Module TB7
UPS1
X9J23-4 TB7-1
2+1 1+1 & 2+0
2+1
UPS2
UPS3
X9J23-6 TB7-2
X9J23-4 TB7-3
X9J23-6 TB7-4
X9J23-4 TB7-5
X9J23-6 TB7-6
Notes
Refer to the Liebert EXM UPS installation manual, SL-25648, SL-25650 or SL-26100 for additional details about the Liebert EXM 10-40kVA, 60-100kVA and 120-200kVA UPS’s. The manual is available at the Liebert Web site: www.liebert.com
The following are guidelines only and are superseded by local regulations and codes of practice where applicable.
• Take special care when determining the size of the neutral cable because current circulating on the neutral
cable may be greater than nominal current in the case of non-linear loads.
• The ground conductor should be sized according to local or NEC codes, cable lengths, type of protection,
etc. The ground cable connecting the UPS to the main ground system must follow the most direct route possible.
• Consideration should be given to the use of smaller, paralleled cables for heavy currents, as a way to ease
installation.
• In most installations, the load is connected to a distribution network of individually protected busbars fed
by the Liebert EXM Parallel Cabinet output rather than being connected directly to the Liebert EXM Parallel Cabinet itself. Where this is the case, the Liebert EXM Parallel Cabinet output cables can be rated to suit the individual distribution network demands rather than being fully load-rated.
• To avoid increasing formation of electromagnetic interference, do not form coils when laying the power
cables.
Vertiv | Liebert
®
EXM™ Parallel Cabinet User Manual | 13
Page 18

2.0 INSTALLATION DRAWINGS

EXM11015 Rev. 2
NOTES:
1. Install in accordance with national and local electrical codes.
2. Input and bypass must share the same single source.
3. A neutral is required from the system AC input source. A full capacity neutral conductor is recommended. Grounding conductors are recommended.
4. Bypass and rectifier inputs and output cables must be run in separate conduits.
5. Control wiring must be run in separate conduits.
6. Customer must supply shunt trip breaker with 120V coil.
7. 2+0 available only from 10-160 kVA; 180 and 200 kVA are 1+1 only.
* UPS 1
AC Input
4 Wire + Grd
See Note 6
Field-Supplied Wiring
* External Overcurrent Protection By Others
LEGEND MOB - Module Output Breaker MIB - Maintenance Isolation Breaker MBB- Maintenance Bypass Breaker
* UPS 2
AC Input
4 Wire + Grd
See Note 6
Liebert EXM #2 UPS Cabinet
*System
AC Input
4 Wire + Grd
Liebert EXM Parallel Cabinet
AC Output
4 Wire + Grd
Liebert EXM #1 UPS Cabinet
Battery
Battery
Static
Bypass
Output Busbar
Static
Bypass
Output Busbar
MBB
MIB
OPT. K
MOB1
MOB2
Figure 2 Parallel (1+1, 2+0) cabinet, 10-200kVA
Installation Drawings
Vertiv | Liebert
®
EXM™ Parallel Cabinet User Manual | 14
Page 19
Figure 3 One-line diagram, Parallel (2+1) Cabinet, 10-160kVA
EXM11016 Rev. 2
NOTES:
1. Install in accordance with national and local electrical codes.
2. Input and bypass must share the same single source.
3. A neutral is required from the system AC input source. A full capacity neutral conductor is recommended. Grounding conductors are recommended.
4. Bypass and rectifier inputs and output cables must be run in separate conduits.
5. Control wiring must be run in separate conduits.
6. Customer must supply shunt trip breaker with 120V coil.
* UPS 1
AC Input
4 Wire + Grd
See Note 6
Field-Supplied Wiring
* External Overcurrent Protection By Others
LEGEND MOB - Module Output Breaker MIB - Maintenance Isolation Breaker MBB- Maintenance Bypass Breaker
* UPS 2
AC Input
4 Wire + Grd
See Note 6
* UPS 3
AC Input
4 Wire + Grd
See Note 6
Liebert EXM #3 UPS Cabinet
*System
AC Input
4 Wire + Grd
Liebert EXM Parallel Cabinet
AC Output
4 Wire + Grd
Liebert EXM #1 UPS Cabinet
Liebert EXM #2 UPS Cabinet
Battery
Battery
Battery
Static
Bypass
Static
Bypass
Output Busbar
Output Busbar
Static
Bypass
Output Busbar
MBB
MIBOPT. K
MOB1
MOB2
MOB3
Installation Drawings
Vertiv | Liebert
®
EXM™ Parallel Cabinet User Manual | 15
Page 20
Figure 4 Main components—300mm 1+1 Liebert EXM Parallel Cabinet
Installation Drawings
(See Detail A)
(See Detail A)
67.8"
(1721mm)
(305mm)
1.8" (46mm)
0.65" (17mm)
TB3
TB2
12"
Ø 0.56" (14mm)
14 Places
2.8"
(71mm)
1.38"
(35mm)
(44mm)
Ø 0.38" (9.7mm)
LEFT SIDE VIEW
NEUTRAL BUSBAR
1.75"
9 Places
Panel Removed
2.2" (56mm) 8 Places
1.75" (44mm) 3 Places
DETAIL A
2.7"
(69mm)
Neutral Busbar
Ground Busbar
MOB1
MOB2
MIB
MBB
(191mm)
1.6"
(41mm)
0.65"
1.3"
(33mm)
TB5
7.5"
GROUND BUSBAR
RIGHT SIDE
Panel Removed
Ø 0.44" (11mm) 8 Places
0.59" (15mm)
1.3" (33mm)
(See Detail A)
FRONT VIEW Door Removed
0.79"
(20mm)
2.1"
(53mm)
(17mm)
0.79"
(20mm)
6 Places
NOTES
1. All dimensions are in inches (mm).
2. Control wiring and power wiring must be run in separate conduits.
3. All wiring is to be in accordance with national and local electrical codes.
4. If maintenance bypass cabinet is attached to UPS, Vertiv will supply the interconnection cables.
EXM16015 Rev. 1
Vertiv | Liebert
®
EXM™ Parallel Cabinet User Manual | 16
Page 21
Figure 5 Main components—600mm 2+1 Liebert EXM Parallel Cabinet,
Ground
Busbar
Neutral Busbar
MOB2
MOB1
Installation Drawings
LEFT SIDE VIEW
Panel Removed
2.8"
(71mm)
1.75"
(44mm)
MOB3
MBB
MIB
Output
Busbars
(See Detail A)
TB1
1.7" (43mm) 8 Typically
GROUND and
NEUTRAL BUSBAR
FRONT VIEW
Door Removed
Input
Busbars
67"
(1702mm)
19.4"
(493mm)
RIGHT SIDE
Panel Removed
NOTES
1. Control wiring and power wiring must be run in separate conduits.
2. All wiring is to be in accordance with national and local electrical codes.
3. If maintenance bypass cabinet is attached to UPS, Vertiv will supply the interconnection cables.
®
Vertiv | Liebert
EXM™ Parallel Cabinet User Manual | 17
1.75"
(44mm)
8 Typically
DETAIL A
Phase Busbar
Connections
EXM16017 Rev. 1
Page 22
Figure 6 Main components—800mm 2+1 Liebert EXM Parallel Cabinet
Installation Drawings
Main Input Busbar
(See DETAIL A)
Neutral Busbar
(See DETAIL B)
MOB1
(See DETAIL C)
MIB
Ground Busbar
(See DETAIL D)
1.65"
(42mm)
1.75"
(44mm)
DETAIL A
NOTES
1. All dimensions are in inches (mm).
2. Control wiring and power wiring must be run in separate conduits.
3. All wiring is to be in accordance with national and local electrical codes.
4. If maintenance bypass cabinet is attached to UPS, Vertiv will supply the interconnection cables.
5. 2+1 available only from 120-160 kVA.
FRONT VIEW
With Door Removed
0.55"
(14mm)
0.56" (14mm)
Bypass Input Busbar (See DETAIL A)
MOB2
MOB3
(1598mm)
MBB
58.6"
(1488mm)
20.5"
(521mm)
1.69" (43mm) Typically
62.9"
18.2"
(462mm)
DETAIL B
16.7"
(424mm)
18.3"
(465mm)
SIDE VIEW
With Panel Removed
0.56" (14mm)
(44mm)
1.75" (44mm)
1.75"
DETAIL C
ISOMETRIC
VIEW
0.61"
(15mm)
0.44" (11mm)
1.75"
(44mm)
1.65"
(42mm)
DETAIL D
EXM16110 Rev. 0
0.56" (14mm)
0.71"
(18mm)
Vertiv | Liebert
®
EXM™ Parallel Cabinet User Manual | 18
Page 23
Figure 7 Main components—800mm 1+1 and 2+0 Liebert EXM Parallel Cabinet
1.65"
(42mm)
1.65"
(42mm)
0.71"
(18mm)
0.55"
(14mm)
0.56"
(14mm)
0.44" (11mm)
0.56" (14mm)
0.56"
(14mm)
1.75"
(44mm)
1.75" (44mm)
1.75"
(44mm)
1.26"
(32mm)
18.3"
(465mm)
18.5"
(470mm)
16.9"
(429mm)
62.9"
(1598mm)
58.6"
(1488mm)
20.5"
(521mm)
MBB
MIB
MOB2
MOB1
(See DETAIL C)
Main Input Busbar
(See DETAIL A)
Bypass Input Busbar (See DETAIL A)
Neutral Busbar
(See DETAIL B)
Ground Busbar
(See DETAIL D)
0.61"
(15mm)
1.75"
(44mm)
SIDE VIEW
With Panel Removed
FRONT VIEW
With Door Removed
ISOMETRIC
VIEW
DETAIL B
DETAIL A
DETAIL C
DETAIL D
1.69" (43mm) Typically
NOTES
1. All dimensions are in inches (mm).
2. Control wiring and power wiring must be run in separate conduits.
3. All wiring is to be in accordance with national and local electrical codes.
4. If maintenance bypass cabinet is attached to UPS, Vertiv will supply the interconnection cables.
5. 1+1 available from 120-200 kVA, 2+0 available from 120-160 kVA.
EXM16109 Rev. 2
Installation Drawings
Vertiv | Liebert
®
EXM™ Parallel Cabinet User Manual | 19
Page 24
Figure 8 Outline drawing—300mm Liebert EXM Parallel Cabinet
34.3"
(872mm)
NOTES
1. All dimensions are in inches (mm).
2. 24" (610) minimum clearance above unit for air exhaust. 36" (914) front access required for service.
3. Keep cabinet within 15 degrees of vertical.
4. Top and bottom cable entry available through removable access plates. Remove, punch to suit conduit size and replace.
5. Unit bottom is structurally adequate for forklift handling.
6. Control wiring and power wiring must be run in separate conduits.
7. Copper cables only are recommended.
8. All wiring is to be in accordance with national and local electrical codes.
FRONT
DETAIL A
TOP VIEW
BOTTOM VIEW
RIGHT SIDE VIEW
FRONT VIEW
EXM12010A Rev. 3
Leveler
Cable Entry Area 10" x 15.7" (254mm x 399mm)
See Detail A
39.1" (993mm)
Cable Entry Area 10" x 11.8" (254mm x 300mm)
Cable Entry Area
8.3" x 7.9" (211mm x 201mm)
8.6" (218mm)
34.3"
(872mm)
12.1
(300mm)
11.8"
(300mm)
Installation Drawings
Vertiv | Liebert
®
EXM™ Parallel Cabinet User Manual | 20
Page 25
Figure 9 Outline drawing—600mm Liebert EXM Parallel Cabinet
23.6"
(600mm)
NOTES
1. 24" (610) minimum clearance above unit for air exhaust. 36" (914) front access required for service.
2. Keep cabinet within 15 degrees of vertical.
3. Top and bottom cable entry available through removable access plates. Remove, punch to suit conduit size and replace.
4. Unit bottom is structurally adequate for forklift handling.
5. Control wiring and power wiring must be run in separate conduits.
6. Copper cables only are recommended.
7. All wiring is to be in accordance with national and local electrical codes.
BOTTOM VIEW
TOP VIEW
RIGHT SIDE VIEW
DETAIL A
FRONT VIEW
Cable Entry Area
20.7" x 17.7" (526mm x 450mm)
Control Cable Entry
5.9" x 2" (150mm x 51mm)
Control Cable Entry
4.7" x 1.6" (119mm x 41mm)
Cable Entry Area
20.7" x 16.9" (526mm x 429mm)
39.8" (1010mm)
Caster
Leveler
EXM12012A Pg. 1, Rev. 3
78.7"
(2000mm)
20.4"
(518mm)
34.3"
(872mm)
28.3"
(719mm)
Brkt.
Centers
2.9" (74mm)
15.0"
(381mm)
FRONT
4.5"
(114mm)
18.5"
(470mm)
1.8"
(45mm)
See
Detail A
1.6"
(41mm)
23.9"
(608mm)
Installation Drawings
Vertiv | Liebert
®
EXM™ Parallel Cabinet User Manual | 21
Page 26
Figure 10 Outline drawing—800mm Liebert EXM Parallel Cabinet
EXM12016 Rev. 2
Front View
Right Side View
Bottom View
Top View
DETAIL A
Leveler
Caster
39.8" (1010mm)
28.3" (719mm)
31.8" (808mm)
31.3" (800mm)
78.7"
(2000mm)
34.3"
(872mm)
1.8"
(45mm)
See DETAIL A
28.3" (719mm) Breakout
Centers
22.8"
(579mm)
Control Cable Entry
4.7" x 1.6" (119mm x 41mm)
Power Cable Entry
26.8" (681mm) X 16.8" (427mm)
Power Cable Plate
28.3" (719mm) X
17.5" (445mm)
Control Cable Entry
5.9" x 2.0" (150mm x 51mm)
2.9" (74mm)
NOTES:
1. All dimensions are in inches (mm).
2. 24" (610) minimum clearance above unit for air exhaust. 36" (914) front access required for service.
3. Keep cabinet within 15 degrees of vertical.
4. Top and bottom cable entry is available through removable access plates. Remove, punch to suit conduit size and replace.
5. Unit bottom is structurally adequate for forklift handling.
6. Control wiring and power wiring must be run in separate conduits.
7. All wiring is to be done in accordances with national and local electrical codes.
Installation Drawings
Vertiv | Liebert
®
EXM™ Parallel Cabinet User Manual | 22
Page 27
Figure 11 Control wiring diagram, Liebert EXM Parallel Cabinet, 1+1 and 2+0 paralleling
607845
Sheet 4 Rev. 1
Phase B
Phase C
Neutral
Customer Input
Neutral
Customer Main
Ground BUSBAR
Ground
Phase A
Phase B
Phase C
Phase A
Phase B
Phase C
Phase A
Ground Electrode
(See Note 2)
Ground to
Unit Frame
Phase B
Phase C
Phase A
AUX
MBB
MIB
C
N/O
N/C
AUX
C
N/O
N/C
AUX
C
N/O
N/C
W22
W27 W26 W25
W23
W24
W19
W38
W39
W43
W44
W35
W36
W37
W40
W41
W42
W10
W11
W12
W13
W14
W15
W04
W05
W06
W01
W02
W03
W20
W21
TB5
TB1
TB4
TB1
TB2
MOB2
MOB1
9911111313
15 15
123456789101112
BIB2
BIB1
MX
MX
12
1212
13
14
11
11
12
10
10
G19 Only
G19 Only
G19 Only
G19 Only
G19 Only
G19 Only
100
400
200
601
X2
AC Output
AC Output
Fuse
Fuse
FH1
FH1
*Option
FH2
*Option
FH2
0
N
0A
0B
0C
0N
0A
0B
0C
MFP_O
MFP_S
MFP_C
Main_abnl_O
Main_abnl_S
Main_abnl_C
X9J24
13524
6
MFP_O
MFP_S
MFP_C
Main_abnl_O
Main_abnl_S
Main_abnl_C
X9J24
13524
6
X9J26
GND_Dry
GND_Dry
Q5_Status
Q3_Status
15
13
11
9
X9J26
GND_Dry
GND_Dry
Q5_Status
Q3_Status
15
13
11
9
X9J23
BFP_O
BFP_S
BFP_C
INV_O
INV_S
INV_C
13524
6
X9J23
BFP_O
BFP_S
BFP_C
INV_O
INV_S
INV_C
13524
6
1
3
1
3
91113
15
91113
15
2#UPS
1#UPS
PE
mN
C
B
A
PE
mN
C
B
A
AC Input
AC Input
2+0 Paralleling Cabinet
1+1 Paralleling Cabinet
Wiring Legend
Factory-Supplied Wiring
Factory or Field-Supplied Wiring
Field-Supplied Wiring
NOTES:
1. Wiring furnished by factory. Consult
installation manual for UPS connections.
2. Customer-furnished grounding electrode
conductor to be installed in accordance
with National Electric Code Article 250-26.
DETAIL A
DETAIL B
DETAIL A
DETAIL B
Installation Drawings
Vertiv | Liebert
®
EXM™ Parallel Cabinet User Manual | 23
Page 28
Figure 12 Control wiring diagram, Liebert EXM Parallel Cabinet, 2+1 paralleling
Phase B
Phase C
Phase A
Phase B
Phase C
W33
W38
W39
W43
W40
W01
W02
W03
W04
W05
W06
W07
W08
W09
W35
W36
W37
W30
W31
W32
W41
W42
W44
W34
BIB3
BIB2
BIB1
Phase A
Phase B
Phase C
Neutral
Customer Input
Neutral
Customer Main
Ground BUSBAR
Ground Electrode
(See Note 2)
Ground to
Unit Frame
Ground
Phase A
Phase B
Phase C
Phase A
MX
G8, G9 Only
G8, G9 Only
G8, G9
Only
G8, G9
Only
G8, G9 Only
G8, G9 Only
AC Input
AC Input
AC Output
AC Output
Wiring Legend
Factory-Supplied Wiring
Factory or Field-Supplied Wiring
Field-Supplied Wiring
AC Output
AC Input
Fuse
Fuse
Fuse
2#UPS
3#UPS
G8, G9 Only
G8, G9 Only
9
10
15
11
MX
MX
AUX
PE
mN
X9J23
X9J23
X9J23
BFP_O
BFP_S
BFP_C
INV_O
INV_S
INV_C
BFP_O
BFP_S
BFP_C
INV_O
INV_S
INV_C
MFP_O
MFP_S
MFP_C
Main_abnl_O
Main_abnl_S
Main_abnl_C
MFP_O
MFP_S
MFP_C
Main_abnl_O
Main_abnl_S
Main_abnl_C
X9J26
X9J26
X9J26
X9J24
X4
X9J24
X9J24
C
B
A
PE
FH1
FH1
FH1
FH2
FH2
*Option
*Option
*Option
FH2
mN
C
B
A
PE
mN
C
B
A
Phase B
Phase C
MBB
MIB
TB1
MOB1
MOB2
MOB3
Phase A
C
N/O
N/C
14
11
10
9
12
13
GND_Dry
GND_Dry
Q5_Status
Q3_Status
GND_Dry
GND_Dry
Q5_Status
Q3_Status
15
13
11
9
15
13
11
9
GND_Dry
GND_Dry
Q5_Status
Q3_Status
15
13
11
9
13524
6
13524
6
13524
6
13524
6
13524
6
1
3
1
3
1
3
91113
15
91113
15
9
999
11
11 1111
13
13 1313
15
15 15 15
BFP_O
BFP_S
BFP_C
INV_O
INV_S
INV_C
13524
6
MFP_O
MFP_S
MFP_C
Main_abnl_O
Main_abnl_S
Main_abnl_C
0
N
0
A
0
B
0
C
0
N
0
A
0
B
0
C
0
N
0
A
0
B
0
C
AUX
AUX
C
N/O
N/C
C
N/O
N/C
AUX
C
N/O
N/C
123456789101112
601
300
200100
400
2+1 Paralleling
607845
Sheet 5 Rev. 1
DETAIL A
DETAIL B
DETAIL B
DETAIL A
Installation Drawings
Vertiv | Liebert
®
EXM™ Parallel Cabinet User Manual | 24
Page 29
Installation Drawings
2+0 and 1+1 Paralleling Cabinet with SKRU
X9J23
BFP_O
BFP_S
BFP_C
INV_O
INV_S
INV_C
13524
6
X9J23
BFP_O
BFP_S
BFP_C
INV_O
INV_S
INV_C
13524
6
MFP_O
MFP_S
MFP_C
Main_abnl_O
Main_abnl_S
Main_abnl_C
X9J24
13524
6
MFP_O
MFP_S
MFP_C
Main_abnl_O
Main_abnl_S
Main_abnl_C
X9J24
13524
6
AC Input
AC Input
AC Output
AC Output
2#UPS
1#UPS
Fuse
Fuse
PE
mN
C
B
A
PE
mN
C
B
A
X9J26
GND_Dry
GND_Dry
Q5_Status
Q3_Status
15
13
11
9
X9J26
GND_Dry
GND_Dry
Q5_Status
Q3_Status
15
13
11
9
FH1
FH1
FH2
*Option
FH2
*Option
FH2
*Option
0
N
0N
0A
0A0B0B
0C
0C
EPO-NC
+12V
+12V
EPO-NO
1 2 3 4
EPO-NC
+12V
+12V
EPO-NO
1 2 3 4
J2
J2
4 WHT
6 BLK
4 WHT
3 WHT
1 WHT
6 BLK
4 BLK
2 BLK
51
52
53
54
55
56
57
58
TB7
TB5
MBB
MOB1
MOB2
Customer
Neutral
Neutral
Phase C
Phase B
Phase A
FU2
2A
FU1
2A
Inner Door
120VAC
Lamp
K0
SKPM
Pushbutton
MIB
123456
703
701
702
706
710
X1 X2
4
3344
3
704
AUX
AUX
C
N/O
N/C
C
N/O
N/C
Wiring Legend
Factory-Supplied Wiring
Factory or Field-Supplied Wiring
607983
Sheet 3 Rev. 2
DETAIL A
DETAIL A
DETAIL B
DETAIL B
Figure 13 Control wiring diagram, Liebert EXM Parallel Cabinet, 2+0 and 1+1 paralleling with SKRU
Vertiv | Liebert
®
EXM™ Parallel Cabinet User Manual | 25
Page 30
Figure 14 Control wiring diagram, Liebert EXM Parallel Cabinet, 2+1 paralleling with SKRU
AC Input
AC Output
AC Output
AC Output
3#UPS
2#UPS
1#UPS
Fuse
Fuse
Fuse
PE
mN
C
B
A
AC Input
PE
mN
C
B
A
AC Input
PE
mN
C
B
A
FH1
FH1
FH1
FH2
*Option
FH2
*Option
FH2
*Option
0
N
0A
0B
0C
0N
0A
0B
0C
0N
0A
0B
0C
MFP_O
MFP_S
MFP_C
Main_abnl_O
Main_abnl_S
Main_abnl_C
X9J24
MFP_O
MFP_S
MFP_C
Main_abnl_O
Main_abnl_S
Main_abnl_C
X9J24
MFP_O
MFP_S
MFP_C
Main_abnl_O
Main_abnl_S
Main_abnl_C
X9J24
X9J26
GND_Dry
GND_Dry
Q5_Status
Q3_Status
15
13
11
9
X9J26
GND_Dry
GND_Dry
Q5_Status
Q3_Status
15
13
11
9
X9J26
GND_Dry
GND_Dry
Q5_Status
Q3_Status
15
13
11
9
X9J23
BFP_O
BFP_S
BFP_C
INV_O
INV_S
INV_C
13524
6
X9J23
BFP_O
BFP_S
BFP_C
INV_O
INV_S
INV_C
13524
6
X9J23
BFP_O
BFP_S
BFP_C
INV_O
INV_S
INV_C
13524
6
EPO-NC
+12V
+12V
EPO-NO
1 2 3 4
J2
EPO-NC
+12V
+12V
EPO-NO
1 2 3 4
J2
EPO-NC
+12V
+12V
EPO-NO
1 2 3 4
J2
4 WHT
4 WHT
6 BLK
6 BLK
4 WHT
6 BLK
51
52
53
57
56
58
59
54
55
x2
50
2+1 Paralleling Cabinet with SKRU
MOB2
MOB1
MOB3
AUX
AUX
AUX
C
N/O
N/C
C
N/O
N/C
C
N/O
N/C
3 WHT
1 WHT
4 BLK
5 WHT
6 BLK
2 BLK
TB7
MBB
MIB
123456
Neutral
Phase C
Phase B
Phase A
Customer
Neutral
FU2
2A
FU1
2A
701
702
703
706
704
608126
Sheet 2 Rev. 0
Inner Door
Lamp
K0
SKPM
Pushbutton
710
4
3344
3
120VAC
DETAIL A
DETAIL A
DETAIL
DETAIL B
Installation Drawings
Vertiv | Liebert
®
EXM™ Parallel Cabinet User Manual | 26
Page 31
Figure 15 Control Wiring Diagram, Liebert EXM Parallel Cabinet, 2+1 with REPO
2+1 Paralleling Cabinet with REPO
AC Output
Fuse
FH1
*Option
FH2
0N
0A
0B
0C
1#UPS
2#UPS
3#UPS
MFP_O
MFP_S
MFP_C
Main_abnl_O
Main_abnl_S
Main_abnl_C
X9J24
4
6
13524
6
MFP_O
MFP_S
MFP_C
Main_abnl_O
Main_abnl_S
Main_abnl_C
X9J24
13524
6
MFP_O
MFP_S
MFP_C
Main_abnl_O
Main_abnl_S
Main_abnl_C
X9J24
13524
6
X9J26
GND_Dry
GND_Dry
Q5_Status
Q3_Status
15
13
11
9
X9J26
GND_Dry
GND_Dry
Q5_Status
Q3_Status
15
13
11
9
X9J26
GND_Dry
GND_Dry
Q5_Status
Q3_Status
15
13
11
9
X9J23
BFP_O
BFP_S
BFP_C
INV_O
INV_S
INV_C
13524
6
X9J23
BFP_O
BFP_S
BFP_C
INV_O
INV_S
INV_C
13524
6
X9J23
BFP_O
BFP_S
BFP_C
INV_O
INV_S
INV_C
13524
6
PE
mN
C
B
A
PE
mN
C
B
A
PE
mN
C
B
A
AC Input
AC Input
AC Input
EPO-NC
+12V
+12V
EPO-NO
1 2 3 4
J2
EPO-NC
+12V
+12V
EPO-NO
1 2 3 4
J2
EPO-NC
+12V
+12V
EPO-NO
1 2 3 4
J2
AC Output
Fuse
FH1
*Option
FH2
0N
0A
0B
0C
AC Output
Fuse
FH1
*Option
FH2
0N
0A
0B
0C
MOB2
MOB1
MOB3
AUX
AUX
C
N/O
N/C
AUX
C
N/O
N/C
C
N/O
N/C
99
66
65
757677
78
x2
x2
64
63
MIB
MBB
WHT 708
MX
709
BLK
WHT 708
WHT 708
709 BLK
711 BLK
709
BLK
K4
Setting to 0.5 Sec.
FU3 2A
714
3456
2187
XFMR
24Vac
8
7
1
2
5
4
9
BLK 714
WHT 713
WHT 715
WHT 713
120Vac
67
100
101
102
A
B
K3
3
4
5
6
2
1
8
9
7
Neutral
Phase C
Phase B
Phase A
Customer
Neutral
TB8
123456 789
Remote EPO
Latching Pushbutton
608244
Sheet 2 Rev. 1
Wiring Legend
Factory-Supplied Wiring
Factory or Field-Supplied Wiring
Installation Drawings
Vertiv | Liebert
®
EXM™ Parallel Cabinet User Manual | 27
Page 32
Figure 16 Control wiring diagram, Liebert EXM Parallel Cabinet, 2+0 and 1+1 with REPO
2+0 & 1+1 Paralleling Cabinet with REPO
Wiring Legend
Factory-Supplied Wiring
Factory or Field-Supplied Wiring
AC Output
AC Output
Fuse
Fuse
FH1
FH1
*Option
FH2
*Option
FH2
0N
0A
0B
0C
0N
0A
0B
0C
MFP_O
MFP_S
MFP_C
Main_abnl_O
Main_abnl_S
Main_abnl_C
X9J24
13524
6
MFP_O
MFP_S
MFP_C
Main_abnl_O
Main_abnl_S
Main_abnl_C
X9J24
13524
6
2#UPS
1#UPS
PE
mN
C
B
A
PE
mN
C
B
A
AC Input
AC Input
X9J26
GND_Dry
GND_Dry
Q5_Status
Q3_Status
15
13
11
9
X9J26
GND_Dry
GND_Dry
Q5_Status
Q3_Status
15
13
11
9
X9J23
BFP_O
BFP_S
BFP_C
INV_O
INV_S
INV_C
13524
6
X9J23
BFP_O
BFP_S
BFP_C
INV_O
INV_S
INV_C
13524
6
EPO-NC
+12V
+12V
EPO-NO
1 2 3 4
J2
EPO-NC
+12V
+12V
EPO-NO
1 2 3 4
J2
62
63
64
65
66
67
102 101
99
61
Neutral
Phase C
Phase B
Phase A
Customer
Neutral
MIB
MOB1
MOB2
MBB
XFMR
A
B
K3
K4
Setting to 0.5 Sec.
Remote EPO
Latching Pushbutton
FU3 2A
WHT 715
WHT 713
711 BLK
714
BLK 714
WHT 713
120Vac
24Vac
WHT 708
WHT 712
WHT 708
MX
MX
709 BLK
709
BLK
709
BLK
8
7
3
3
4
4
5
5
6
6
2
2
1
1
8
8
9
7
7
1
2
5
4
9
TB8
12345 6789
AUX
C
N/O
N/C
AUX
C
N/O
N/C
607983
Sheet 4 Rev. 3
Installation Drawings
Vertiv | Liebert
®
EXM™ Parallel Cabinet User Manual | 28
Page 33

3.0 SPECIFICATIONS

Table 4 Liebert EXM Parallel Cabinet specifications
Model Size
Cabinet Width
Input Parameters
Input Voltage to Bypass, VAC 208/120V or 220/127V, 3-Phase, 4-Wire
Input Current Refer to UPS User Manual
Input Frequency 60
Output Parameters
Output Power, kW 10-40 60-100 120-200
Output Voltage, VAC 208/120V or 220/127V, 3-Phase, 4-Wire
Output Current, AAC Refer to Tables 5 and 6
Output Frequency 60
Physical Parameters and Standards
Dimensions, in. (mm)
Cabinet Width, side panels attached 11.81 (300) 23.62 (600) 31.49 (800)
Depth, in. (mm) 39.4 (1000)
Height, in. (mm) 78.74 (2000)
Weight, lb (kg)
1+1 & 2+0 263 (119.3)
1+1 & 2+0
2+1 594 (269.4)
1+1 & 2+0 686 (311.2)
2+1 714 (323.8)
Color Black (ZP-7021)
Degree of Protection for UPS Enclosure IP 20 (with and without front door open)
Standards and conformities
Minimum Clearance, Top, in. (mm) 24 (610)
Minimum Clearance, Back, in. (mm) 0
Minimum Clearance, Sides, in. (mm) 0
Cable Entrance Top or Bottom
Environmental Parameters
Storage Temperature Range, °F (°C) -13 to 158 (-25 to 70)
Operating Temperature, °F (°C) 32 to 104 (0 to 40) (UPS)
Relative Humidity
Maximum Altitude above MSL, ft. (m) Refer to the UPS manual, SL-25648, SL-25650 or SL-26100.
10-40kVA 60-100kVA 120-200kVA
300mm 600mm 800mm
594 (269.4)
UL1778 5th Edition; CSA 22.2 107-3-14
ISTA Procedure 1H; WEEE
Maximum 95% Non-Condensing
(Operating and Non-Operating)
Specifications
Vertiv | Liebert
®
EXM™ Parallel Cabinet User Manual | 29
Page 34

3.1 ELECTRICAL CHARACTERISTICS

NOTE
The breakers and cables used must be in accordance with NEC ANSI/NFPA 70. A disconnect breaker must be provided for AC input, Bypass and AC output. Recommended cable sizes are suitable for operation at a maximum temperature of 104°F (40°C).
Table 5 Liebert EXM Parallel Cabinet output currents, 1+1 configuration
1+1 Configuration
System
Rating
10 28 40 M10 50 (1) #6 (1) #2
15 42 60 M10 85 (1) #4 (1) #2
20 56 70 M10 115 (1) #2 (1) #2
30 83 110 M10 130 (1) 1/0 (1) 2/0
40 111 150 M10 175 (1) 3/0 (1) 4/0
60 167 225 M12 285 (1) 300 (2) 2/0
80 222 300 M12 400 (2) 3/0 (2) 4/0
100 278 350 M12 460 (2) 4/0 (2) 300 kcmil
120 333 450 M12 620 (2) 350 kcmil (2) 500 kcmil
140 389 500 M12 620 (2) 350 kcmil (2) 500 kcmil
160 444 600 M12 760 (2) 500 kcmil
180 500 700 M12 930 (3) 350 kcmil (3) 500 kcmil
200 555 700 M12 930 (3) 350 kcmil (3) 500 kcmil
Nominal Output
Current
OCP Device
Rating Bolt Size
75°C
Current Total
Copper
Wire
Aluminum
Specifications
Wire
Table 6 Liebert EXM Parallel Cabinet output currents, 2+0 and 2+1 configurations
2+0 and 2+1 Configuration
UPS Size
in Parallel
10 20 56 70 M10 115 (1) #2 (1) #2
15 30 83 110 M10 130 (1) 1/0 (1) 2/0
20 40 111 150 M10 175 (1) 3/0 (1) 4/0
30 60 167 225 M10 400 (2) 3/0 (2) 4/0
40 80 222 300 M10 460 (2) 4/0 (2) 300 kcmil
60 120 333 450 M12 501 (2) 300 kcmil (2) 350 kcmil
80 160 444 600 M12 607 (3) 4/0 (3) 300 kcmil
100 200 555 700 M12 752 (3) 300 kcmil (4) 250 kcmil
120 240 666 1000 M12 1003 (4) 300 kcmil (4) 500 kcmil
140 280 778 1000 M12 1091 (4) 350 kcmil (4) 500 kcmil
160 320 888 1200 M12 1337 (4) 500 kcmil
System
Rating
Nominal
Output Current
OCP Device
Rating
Bolt Size
75°C
Current Total
Copper
Wire
NOTE
For UPS input, bypass and output currents, see UPS user manuals.
Aluminum
Wire
Vertiv | Liebert
®
EXM™ Parallel Cabinet User Manual | 30
Page 35
Table 7 Recommended lug sizes (compression type) M10, 3/8" bolt
Cable Size
#8AWG 54132 60104-TB
#6AWG 54136 60109
#4AWG 54140 60114
#2AWG 54143 60118 54811BE
#1AWG 54148 60124 54857BE
#1/0AWG 54109 60130 256-30695-593
#2/0AWG 54110 60136 54862BE 60238
#3/0AWG 54111 60142 54864BE 60244
#4/0AWG 54112 60148 54866BE 60250
250kcmil 54174 60154 54868BE 60256
300kcmil 54179 60160 54870BE 60262
350kcmil 256-30695-112 54872BE 60267
400kcmil
500kcmil 256-30695-339 54876BE 60273
T&B Copper
One Hole
256-30695-
1403
T&B Aluminum
One Hole
—54874BE60269
T&B Copper
Two-Hole
256-030695-
868
256-030695-
733
T&B Aluminum
Two-Hole
Specifications

3.2 TORQUE REQUIREMENTS

All electrical connections must be tight. Tables 8 and 9 provide the torque values for the connections to the Liebert EXM Parallel Cabinet.
Use these values unless the equipment is labeled otherwise.
Table 8 Busbar torque for power wiring
Bolt Shaft Size
3/8" (M10) 192 (22)
1/2" (M12) 428 (48)
Table 9 Terminal block torque with compression lugs for control wiring
AWG Wire Size
or Range
#22 - #14
NOTE
Refer to the manufacturer’s data for proper torque for circuit breaker power connections.
Tor qu e
lb-in (Nm)
Tor qu e
lb-in (Nm)
3.5 to 5.3
(0.4 to 0.6)
Vertiv | Liebert
®
EXM™ Parallel Cabinet User Manual | 31
Page 36
Specifications
Vertiv | Liebert
®
EXM™ Parallel Cabinet User Manual | 32
Page 37
Page 38
VertivCo.com | Vertiv Headquarters, 1050 Dearborn Drive, Columbus, OH, 43085, USA
© 2018 Vertiv Co. All rights reserved. Vertiv and the Vertiv logo are trademarks or registered trademarks of Vertiv Co. All other names and logos referred to are trade names, trademarks or registered trademarks of their respective owners. While every precaution has been taken to ensure accuracy and completeness herein, Vertiv Co. assumes no responsibility, and disclaims all liability, for damages resulting from use of this information or for any errors or omissions. Specifications are subject to change without notice.
SL-25654_REV5_8-18