Vertiv 547692, Netsure RDB Series, 547693, 547694, 547695 Installation And User Manual

...
Page 1
NetSure™ RDB Series
Installation and User Manual, Section 6041 (Revision K, April 28, 2017)
Specification Number: 547692, 547693, 547499, 547694, 547695, 547615, 547696, 547697, 547503, 547500, 547698, 547699, 547501
Page 2
NetSure™ RDB Series
Installation and User Manual, Section 6041
This page is intentionally blank.
Spec. No: 547692, 547693, 547499, 547694, 547695, 547615, Document Code: Se ction 6041 547696, 547697, 547503, 547500, 547698, 547699, 547501 Revision K, April 28, 2017
Page 3
NetSure™ RDB Series
[i]
Installation and User Manual, Section 6041
Table of Contents
Admonishments Used in this Document ................................................................................................................ ii
Important Safety Instructions .............................................................................................................................. iii
Save These Instructions ...........................................................................................................................................iii
Installation ........................................................................................................................................................... 1
Shipment Inspection ............................................................................................................................................... 1
Installing the Rack PDU ........................................................................................................................................... 1
Electrical Connections ........................................................................................................................................... 3
Connecting the Rack PDU DC Input ......................................................................................................................... 3
Connecting the Rack PDU’s DC Output to Customer Equipment .............................................................................. 3
Connecting External Circuit Breaker Alarms ............................................................................................................. 4
Specifications and Technical Data .......................................................................................................................... 5
Conformity and Standards ...................................................................................................................................... 5
Environmental Characteristics ................................................................................................................................. 5
Specifications ......................................................................................................................................................... 5
Dimensions ............................................................................................................................................................ 6
Input Quick Connect Kit ........................................................................................................................................ 12
Output Cable Assemblies ...................................................................................................................................... 12
Replacement Circuit Breakers ............................................................................................................................... 13
Operation ........................................................................................................................................................... 14
Connecting Power to the Loads ............................................................................................................................. 14
Removing Power from the Loads ........................................................................................................................... 14
Alarms .................................................................................................................................................................. 14
Spec. No: 547692, 547693, 547499, 547694, 547695, 547615, Document Code: Se ction 6041 547696, 547697, 547503, 547500, 547698, 547699, 547501 Revision K, April 28, 2017
Page 4
NetSure™ RDB Series
[ii]
DANGER!
if not avoided
WARNING!
serious injury if not avoided equipment, software, data, or service
CAUTION!
moderate injury if not avoided only to equipment, data, or service, even if such use appears to be permitted in some of the applicable standards
ALERT!
data, or service
ALERT!
software corruption, data loss, or service interruption
FIRE SAFETY!
locations of fire
SAFETY!
to a particular source of hazard or to fire safety
Installation and User Manual, Section 6041
Admonishments Used in this Document
Warns of a hazard the reader will be exposed to that will likely result in death or serious injury
. (ANSI, OSHA)
D
an
g
er
Warns of a potential hazard the reader may be exposed to that could result in death or
. This admonition is not used for situations that pose a risk only to
W
ar
n
in
g
Warns of a potential hazard the reader may be exposed to that could result in minor or
. (ANSI)
. (ANSI, OSHA) This admonition is not used for situations that pose a risk
Caution
A
lert
Alert
Fi
re Safet
S
afety
. (OSHA)
Alerts the reader to an action that must be avoided in order to protect equipment, software,
. (ISO)
Alerts the reader to an action that must be performed in order to prevent equipment damage,
. (ISO)
Informs the reader of fire safety information, reminders, precautions, or policies, or of the
-fighting and fire-safety equipment. (ISO)
y
Informs the reader of general safety information, reminders, precautions, or policies not related
. (ISO, ANSI, OSHA)
Spec. No: 547692, 547693, 547499, 547694, 547695, 547615, Document Code: Se ction 6041 547696, 547697, 547503, 547500, 547698, 547699, 547501 Revision K, April 28, 2017
Page 5
NetSure™ RDB Series
[iii]
Please read and follow all safety
information!
The NetSure™ RDB Rack PDU (Power Distribution Unit) is designed to deliver power to information technology and telecommunication equipment.
Improper installation and operation may cause overheating and lead to increased fire hazard. It may also destroy the device and damage other connected systems.
Damaged Rack PDUs or connected cables increase the risk of electric shock or smoldering fire.
Careless handling increases the risk of electric shock.
Repairs should only be performed by qualified service technicians.
W
ar
n
in
g
Installation and User Manual, Section 6041
Important Safety Instructions
Save These Instructions
WARNING!
listed below may result in electric shock, fire hazards, or serious injury. Please safeguard this Installation and User Manual.
Intended Use
Operate the Rack PDU in an indoor environment only within an ambient temperature range and a relative humidity range as listed in “Environmental Characteristics” on page 5. Install the Rack PDU in a clean environment, free of conductive contaminants, moisture, flammable liquids, gases and corrosive substances.
Do not use the Rack PDU in moist environments. If the Rack PDU is exposed to moisture, immediately disconnect the Rack PDU from DC input power by opening the circuit breaker or removing the fuse or breaker supplying DC input to the Rack PDU. Send the Rack PDU to the manufacturer for inspection.
Failure to observe the safety information
Electrical Safety
Check the unit for external signs of damage prior to start­up operation! Do not operate the device if you detect any damage or other deficiencies.
Only use the supplied DC input power cable.
Personal Safety
Never touch the outlets or the Rack PDU with wet or moist hands.
Service
Do not use the Rack PDU for household applications.
Installation and Operation
Installation and start-up must be performed by a qualified service engineer.
Make sure that the total input current of the connected systems does not exceed the current rating specified on the rating plate of the Rack PDU.
Unauthorized changes, modifications, or repairs of the device are performed at the owner’s risk and will void all warranty claims.
Do not open the Rack PDU.
Please contact the nearest customer service center in
case of malfunction! Damage and defects must be repaired immediately.
Always disconnect the unit from power before troubleshooting.
Spec. No: 547692, 547693, 547499, 547694, 547695, 547615, Document Code: Se ction 6041 547696, 547697, 547503, 547500, 547698, 547699, 547501 Revision K, April 28, 2017
Page 6
NetSure™ RDB Series
[iv]
Installation and User Manual, Section 6041
This page is intentionally blank.
Spec. No: 547692, 547693, 547499, 547694, 547695, 547615, Document Code: Se ction 6041 547696, 547697, 547503, 547500, 547698, 547699, 547501 Revision K, April 28, 2017
Page 7
NetSure™ RDB Series
[1]
Ensure proper grounding.
W
ar
ni
n
g
Installation and User Manual, Section 6041
Installation
The NetSure™ RDB Rack PDUs (Power Distribution Units) are designed to be installed on the left and/or right rear frames of IT racks. They can be mounted directly to the rack or use Rack PDU Mounting Kit P/N 547665. See “Dimensions” starting on page 6 for hole dimensions.
Shipment Inspection
Unpack the shipping container, inspect all items for damage and verify that the shipment is complete and undamaged. Report any damage to your local Vertiv Co. representative and the carrier.
Installing the Rack PDU
WARNING!
"Ground Lead Bracket" must be ground bonded to the mounting bracket (if used) or rack frame. The mounting bracket (if used) must be ground bonded to the rack frame. The rack frame must be ground bonded to your site ground. This is typically accomplished through the use of paint free areas and/or grounding washers used when mounting the components.
Figure 1. Mounting Rack PDUs Directly to Rack Frame
The Rack PDU’s
Installing the Rack PDU Directly to a Rack Frame or Existing Mounting Bracket
Install the Rack PDU directly to the rack frame or existing mounting bracket as shown in Figure 1. Note that the supplied "Ground Lead Bracket" is to be placed between the PDU and the rack frame or existing mounting bracket as shown in Figure 1. Use the supplied 1/4-20 screws and 1/4-20 KEPS nuts.
Installing Rack PDUs to a Rack Frame using the Optional Mounting Bracket
If using the Rack PDU Mounting Kit, install the Rack PDU mounting bracket to the left and/or right rear frame of the rack using the appropriate hardware that fits to the cabinet that will be used.
Install the Rack PDUs to the Rack PDU mounting bracket that was previously installed on the frame as shown in Figure 2. Note that the supplied "Ground Lead Bracket" is to be placed between the PDU and the mounting bracket as shown in Figure 2.
Spec. No: 547692, 547693, 547499, 547694, 547695, 547615, Document Code: Se ction 6041 547696, 547697, 547503, 547500, 547698, 547699, 547501 Revision K, April 28, 2017
Page 8
NetSure™ RDB Series
[2]
Installation and User Manual, Section 6041
Figure 2. Mounting Rack PDUs using Optional Mounting Bracket Kit
Spec. No: 547692, 547693, 547499, 547694, 547695, 547615, Document Code: Se ction 6041 547696, 547697, 547503, 547500, 547698, 547699, 547501 Revision K, April 28, 2017
Page 9
NetSure™ RDB Series
[3]
Installation and User Manual, Section 6041
Electrical Connections
Connecting the Rack PDU DC Input
The Rack PDU’s input is designed to be fed from a 200A (max) breaker or fuse using the factory supplied and connected DC input cable assembly and the customer connected input quick connect kits. See Figure 3.
Figure 3. DC Input Connections
Connecting the Rack PDU’s DC Output to Customer Equipment
The Rack PDU’s output circuit breakers are connected to customer equipment via the separately ordered output cable assemblies. A ground lead is also supplied with each output cable. Each ground lead is terminated with a connector on one end (which mates with a connector on a ground wire factory connected to the "Ground Lead Bracket") and left unterminated on the other end. See Figure 4.
Figure 4. DC Output Connections
Spec. No: 547692, 547693, 547499, 547694, 547695, 547615, Document Code: Se ction 6041 547696, 547697, 547503, 547500, 547698, 547699, 547501 Revision K, April 28, 2017
Page 10
NetSure™ RDB Series
[4]
Installation and User Manual, Section 6041
Connecting External Circuit Breaker Alarms
Negative 48Vdc is provided to a set of alarm terminals if any circuit breaker is in the OFF position. See Figure 5.
Figure 5. Alarm Connections
Spec. No: 547692, 547693, 547499, 547694, 547695, 547615, Document Code: Se ction 6041 547696, 547697, 547503, 547500, 547698, 547699, 547501 Revision K, April 28, 2017
Page 11
NetSure™ RDB Series
[5]
-40°F to +104°F (-40°C to +40°C) (Models L6 and L15).
-40°F to +113°F (-40°C to +45°C) (Models H2, H3, and M6).
Storage Temperature
-40°F to +176°F (-40°C to +80°C).
Relative Humidity
0 to 95%, non-condensing.
Operating Elevation
6562 ft (2000m) at full power.
Number
Outlets
RDB - Basic Rack PDUs
Max Watts
Max Amps1
Max kW
Max Amps1
547692
420
10
2.5
60
547693
630
15
3.8
90
547499
840
20
5.0
120
547694
420
10
6.3
150
547695
630
15
8.42
2002
547615
840
20
8.42
2002
547696
1050
25
6.3
150
547697
1260
30
7.6
180
547503
1470
35
8.42
2002
H2
547500
2
3360
80
6.7
160
547698
2100
50
6.3
150
547699
2520
60
7.6
180
547501
2940
70
8.42
2002
Installation and User Manual, Section 6041
Specifications and Technical Data
Conformity and Standards
The NetSure RDB Rack PDU (Power Distribution Unit) has the following agency approval ratings:
UL 60 950-1 + UL 1801 - Recognized (cURus)
In accordance with the Low Voltage Directive, 2006/95/EEC and including amendments by the CE Marking Directive,
93/68/EEC.
Environmental Characteristics
The NetSure RDB Rack PDU (Power Distribution Unit) is designed to operate under the following environmental conditions without damage or degradation in electrical operating characteristics:
Operating Temperature
Specifications
Model
L6
L15
M6
Part
Number
of
6
15
6
Power Rating per Outlet Power Rating per PDU
Input/Output
Voltage
(nominal)
-48Vdc
H3
1
Max Amps rated at end of battery discharge (42V).
2
PDU power rating limited to 200A, 8.4kW each.
Spec. No: 547692, 547693, 547499, 547694, 547695, 547615, Document Code: Se ction 6041 547696, 547697, 547503, 547500, 547698, 547699, 547501 Revision K, April 28, 2017
3
Page 12
NetSure™ RDB Series
[6]
Installation and User Manual, Section 6041
Dimensions
NetSure™ RDB L6, P/Ns 547692, 547693, 547499
Figure 6. NetSure™ RDB L6, P/Ns 547692, 547693, 547499
Spec. No: 547692, 547693, 547499, 547694, 547695, 547615, Document Code: Se ction 6041 547696, 547697, 547503, 547500, 547698, 547699, 547501 Revision K, April 28, 2017
Page 13
NetSure™ RDB Series
[7]
Installation and User Manual, Section 6041
NetSure™ RDB L15, P/Ns 547694, 547695, 547615
Figure 7. RDB L15, P/Ns 547694, 547695, 547615
Spec. No: 547692, 547693, 547499, 547694, 547695, 547615, Document Code: Se ction 6041 547696, 547697, 547503, 547500, 547698, 547699, 547501 Revision K, April 28, 2017
Page 14
NetSure™ RDB Series
[8]
Installation and User Manual, Section 6041
NetSure™ RDB M6, P/Ns 547696, 547697, 547503
Figure 8. RDB M6, P/Ns 547696, 547697, 547503
Spec. No: 547692, 547693, 547499, 547694, 547695, 547615, Document Code: Se ction 6041 547696, 547697, 547503, 547500, 547698, 547699, 547501 Revision K, April 28, 2017
Page 15
NetSure™ RDB Series
[9]
Installation and User Manual, Section 6041
NetSure™ RDB H2, P/N 547500
Figure 9. RDB H2, P/N 547500
Spec. No: 547692, 547693, 547499, 547694, 547695, 547615, Document Code: Se ction 6041 547696, 547697, 547503, 547500, 547698, 547699, 547501 Revision K, April 28, 2017
Page 16
NetSure™ RDB Series
[10]
Installation and User Manual, Section 6041
NetSure™ RDB H3, P/Ns 547698, 547699, 547501
Figure 10. RDB H3, P/Ns 547698, 547699, 547501
Spec. No: 547692, 547693, 547499, 547694, 547695, 547615, Document Code: Se ction 6041 547696, 547697, 547503, 547500, 547698, 547699, 547501 Revision K, April 28, 2017
Page 17
NetSure™ RDB Series
[11]
6.81
2.68
6.000 (TYP)
1.375
1.75 (TYP)
0.218 X 0.562 SLOT (II)
0.218 X 0.375 SLOT (4)
0.281 X 1.000 SLOT (14)
0.218 X 0.562 SLOT (20)
0.25
o
0.147+0.002 (40 PLCS)
2.56
R 0.062 REF
3.69
0.25 X 45 (TYP)
o
73.63
0.000
0.75
2.250
3.25
0.64
1.33
2.02
2.70
3.39
0.000
0.845
3.032
4.785
14.656
19.867
22.847
29.277
32.718
35.617
38.012
40.909
44.357
50.780
53.761
58.971
68.842
70.595
72.782
71.937
1.687
Installation and User Manual, Section 6041
NetSure™ RDB Mounting Bracket, P/N 547665
Figure 11. RDB Mounting Bracket, P/N 547665
Spec. No: 547692, 547693, 547499, 547694, 547695, 547615, Document Code: Se ction 6041 547696, 547697, 547503, 547500, 547698, 547699, 547501 Revision K, April 28, 2017
Page 18
NetSure™ RDB Series
[12]
Contact Size
Mating Anderson
Connector
547668
1/0
55mm²
547669
2/0
70mm²
547670
3/0
95mm²
547671
4/0
120mm²
Installation and User Manual, Section 6041
Input Quick Connect Kit
Provides the mating connector and contacts for the DC Input Cable Assembly factory supplied and connected to the Rack PDU.
P/N
(AWG) (Metric)
Output Cable Assemblies
P/N 547595, P/N 547613 and P/N 555654
Figure 12. P/N 547595, P/N 547613 and P/N 555654
Powerpole
350A, Red
(SB350)
Spec. No: 547692, 547693, 547499, 547694, 547695, 547615, Document Code: Se ction 6041 547696, 547697, 547503, 547500, 547698, 547699, 547501 Revision K, April 28, 2017
Page 19
NetSure™ RDB Series
[13]
NetSure
P/N
Replacement
P/N
547692 547694
547693 547695
547499 547615
547696
143041 (25A)
547697
143042 (30A)
547503
141802 (35A)
547698
142951 (50A)
547699
142952 (60A)
547501
142953 (70A)
547500
142955 (80A)
Installation and User Manual, Section 6041
Output Connector Kits (P/N 554878 and P/N 554944)
Figure 13. Output Connector Kits (P/N 554878 and P/N 554944)
Replacement Circuit Breakers
Rack PDU
Circuit Breakers
142907 (10A)
142908 (15A)
141801 (20A)
Spec. No: 547692, 547693, 547499, 547694, 547695, 547615, Document Code: Se ction 6041 547696, 547697, 547503, 547500, 547698, 547699, 547501 Revision K, April 28, 2017
Page 20
NetSure™ RDB Series
[14]
Improper operation may cause overheating and lead to increased fire hazard. Improper operation may also
destroy the device and damage other connected systems.
Wa
rn
i
ng
Installation and User Manual, Section 6041
Operation
WARNING!
Make sure that the total input current of the connected systems does not exceed the current rating specified on the rating plate of the Rack PDU. Please refer to the operating instructions or the rating plates of the connected systems or the circuit breaker for power specifications.
Connecting Power to the Loads
To connect DC power to the load(s), operate the respective circuit breaker on the Rack PDU to the ON position.
Removing Power from the Loads
To disconnect DC power from the load(s), operate the respective circuit breaker on the Rack PDU to the OFF position.
Alarms
Local Alarm Indicator
Each Rack PDU contains a circuit breaker alarm indicator. This indicator illuminates Red if any circuit breaker on the Rack PDU is in the OFF position.
External Circuit Breaker Alarm
Negative 48Vdc is supplied to a set of terminals when any circuit breaker on the Rack PDU is in the OFF position. These terminals may be connected to customer external alarm circuits.
Spec. No: 547692, 547693, 547499, 547694, 547695, 547615, Document Code: Se ction 6041 547696, 547697, 547503, 547500, 547698, 547699, 547501 Revision K, April 28, 2017
Page 21
NetSure™ RDB Series
[15]
Installation and User Manual, Section 6041
CUSTOMER SERVICE (P RE-SHIPMENT)
Email
Phone
CUSTOMER SUPPORT CENTER (PO ST-SHIPMENT)
Email
Phone
PRODUCT S
Email
Phone
CustomerService.ESNA@VertivCo.com Pricing and availability
1.800.800.1280 option 1
ESNACustomerSupportCenter@VertivCo.com
1.956.661.6867
AccountManagement.ESNA@VertivCo.com
1.800.800.1280 option 2
[1,2]
expediting requests and order tracking. Ask for your company’s dedicated Customer Service Associate.
After an order has shipped, contact our Customer Support Center with related questions, concerns or claims.
Provides quotes and bid responses for custom configured systems and outdoor enclosures for customers and channel partners (Reps, VARs & Distributors).
, purchase orders,
[2]
DC power
SPARE PARTS
Email
Phone
DC POWER DEPOT REPAIR
Email DCpower.Repair@VertivCo.com Creates and processes RMAs for depot repair and refurbishment.
Phone 1.800.800.1280 option 6
INSTALLATION & AFTER MARKET SERVICES
Email
TECHNICAL SUPPORT
Email
Phone
DCpower.Spares@VertivCo.com OSP.Spares@VertivCo.com
1.800.800.1280 option 5
ESNA.FieldService@VertivCo.com
DCpower.TAC@VertivCo.com OSP.TAC@VertivCo.com
1.800.800.5260
Pricing and purchase orders for spare parts, including but not limited to breakers, cables, fuses, rectifier fans, misc. breaker and fuse panels, enclosure fans, doors and switches, etc.
Determines repair and refurbishment lead times and pricing based on warranties/contractual agreements. Provides repair shipping information and status.
Provides quotes for engineering, furnishing and installation of DC power systems, telecom & IT equipment, cabling infrastructure, and field services of existing DC equipment.
Answers technical product and system questions; determines status of warranties and contractual agreements for repair.
[1] Contact Account Management for custom configurations. [2] Contact Spare Parts for parts and accessories.
Spec. No: 547692, 547693, 547499, 547694, 547695, 547615, Document Code: Se ction 6041 547696, 547697, 547503, 547500, 547698, 547699, 547501 Revision K, April 28, 2017
Page 22
NetSure™ RDB Series
© 2017 Vertiv Energy Systems, Inc.
NetPerform ™, NetReach™, N etSure™ and NetXtend™ ar e trademarks of Verti v Energy Sy stems, Inc. All other tradema rks are the property of their respectiv e owners. Specifications subject to change wi thout notice.
The information contained in this document is subject to change without notice and may not be suitable for all applications. While every precaution has been taken to ensure the accuracy and completeness of this document, Vertiv Group Corporation assumes no responsibility and disclaims all liability for damages resulting from use of this information or for any errors or omissions. Refer to other local practices or building codes as applicable for the correct methods, tools, and materials to be used in performing procedures not specifically described in this document.
This document may contain confidential and/or proprietary information of Vertiv Group Corporation, and its receipt or possession does not convey any right to reproduce, disclose its contents, or to manufacture or sell anything that it may describe. Reproduction, disclosure, or use without specific authorization from Vertiv Group Corporation is strictly prohibited.
Names of companies and products are trademarks or registered trademarks of the respective companies. Any questions regarding usage of trademark names should be directed to the original manufacturer.
Installation and User Manual, Section 6041
Spec. No: 547692, 547693, 547499, 547694, 547695, 547615, Document Code: Section 6041 547696, 547697, 547503, 547500, 547698, 547699, 547501 Revision K, April 28, 2017
Loading...