Vertiv Liebert XDC, XDC160, 189192G3, XDC160AA, 189192G5 User Manual

...
Page 1
Liebert® XDC™
50 & 60 Hz, 130 & 160kW Nominal Cooling Capacity; ModelRevision5orHigher
User Manual
Page 2
Technical Support Site
If you encounter any installation or operational issues with your product, check the pertinent section of this manual to see if the issue can be resolved by following outlined procedures. Visit https://www.VertivCo.com/en-us/support/ for additional assistance.
Page 3
1 Important Safety Instructions 5
2 Product Description 9
2.1 General Product Information 9
2.1.1 Product/System Description 9
2.2 Equipment Inspection 10
2.3 Equipment Handling 10
2.3.1 Handling the Liebert XDC While it is on Skid and Packaged 10
2.3.2 Unpacking the Liebert XDC 11
2.3.3 Removing the Unit from the Skid Using a Forklift 11
2.3.4 Removing the Unit from the Skid using Rigging 12
2.3.5 Moving the Liebert XDC Using Piano Jacks 13
2.3.6 Removing the Unit from the Piano Jacks 14
3 Installation 15
3.1 Mechanical Considerations 15
3.1.1 Positioning the Liebert XDC 15
3.1.2 Placing the Liebert XDC on a Floor Stand 17
3.1.3 Positioning the Liebert XDC with Floor Stand 20
3.2 Electrical Considerations 22
3.2.1 High Voltage Connections 22
3.2.2 Connecting High-Voltage Cables 23
3.3 External Pump Overloads 27
3.4 Extra Low Voltage Connections 28
3.5 Remote Sensor Installation—Proper Placement 34
4 Piping and Filling with Refrigerant: R-134a and R-407C Circuits 37
4.1 European Union Fluorinated Greenhouse Gas Requirements 37
4.2 Recommended Pipe Size 37
4.3 Liebert XDC Interconnection With Liebert XD Cooling Module 38
4.4 Piping Installation Method 38
4.4.1 Piping Installation—R-134a Pumped Circuit 39
4.4.2 Bypass Flow Controllers 39
4.5 Piping Details—Shutoff/Isolation Valves 41
4.6 Filling the Pumped Circuit—R-134a 41
4.6.1 Calculating Refrigerant Charge—Example 44
4.6.2 Piping for Direct Expansion (DX) Circuit—R-407C Air-Cooled Units 45
4.7 Install Double Discharge Risers 45
4.7.1 Air-Cooled Condenser with Liebert Lee-Temp “Flooded Condenser” Head Pressure Control System—R-407C (DX) Circuit 54
4.8 Filling the Direct Expansion (DX) Circuit—R-407C 55
4.9 System Refrigerant Charges Over 55lb. (24.9kg) Require Additional Oil 57
4.9.1 Liebert XDC DX R-407C Circuit Volume 57
5 Installation Checklist 59
Vertiv | Liebert® XDC™ User Manual | 3
Page 4
6 Liebert iCOM Control—Firmware Version XP1.00.009.STD 61
6.1 Liebert iCOM Components and Functions 61
6.2 Display Lamp Indicators 63
6.3 Navigating Through the Liebert iCOM Display 63
6.3.1 Accessing Menus and Settings 64
6.3.2 Cooling Module Overview 64
6.3.3 Entering the Password 65
6.4 Changing Liebert iCOM’s Display Settings 66
6.5 Changing Operational Settings 67
6.6 Graphical Data Record 67
6.7 Liebert iCOM User Menu Icons and Legend 68
6.8 Liebert iCOM User Menu Screens 69
6.9 Liebert iCOM Service Menu Icons and Legend 79
6.10 Liebert iCOM Service Menu Screens 80
7 Start the Liebert XDC with Liebert iCOM 111
7.1 Checklist for Liebert XDC Startup 111
8 Alarm Descriptions and Solutions 115
8.1 Alarm Descriptions 115
8.2 Warning Descriptions 118
8.3 System Shutdown Causes 118
9 Troubleshooting 121
10 Maintenance 123
10.1 Fluorinated Greenhouse Gas Requirements 123
10.2 Air-Cooled Condenser 123
10.3 Water/Glycol Floor Stand Condenser 124
10.3.1 Shell and Tube Condensers 124
10.3.2 Regulating Valves 124
10.3.3 Glycol Solution Maintenance 124
11 Specifications 127
Vertiv | Liebert® XDC™ User Manual | 4
Page 5

1 IMPORTANT SAFETY INSTRUCTIONS

Save These Instructions
This manual contains important safety instructions that should be followed during the installation and maintenance of the Liebert XDC. Read this manual thoroughly before attempting to install or operate this unit.
Only qualified personnel should move, install or service this equipment.
Adhere to all warnings, cautions, notices and installation, operating and safety instructions on the unit and in this manual. Follow all operating and user instructions.
Follow all local codes.
WARNING! Risk of arc flash and electric shock. Can cause equipment damage or death. Disconnect all local and remote electric power supplies and wear protective equipment per NFPA 70E before working within electric control enclosure. Failure to comply can cause serious injury or death. Customer must provide earth ground to unit, per NEC, CEC and local codes, as applicable. Before proceeding with installation, read all instructions, verify that all the parts are included and check the nameplate to be sure the voltage matches available utility power. The Liebert iCOM microprocessor does not isolate power from the unit, even in the Unit Off mode. Some internal components require and receive power even during the Unit Off mode of Liebert iCOM control. The line side of the disconnect switch on the front of the unit contains live high-voltage. The only way to ensure that there is NO voltage inside the unit is to install and open a remote disconnect switch. Refer to unit electrical schematic. Follow all local codes.
WARNING! Risk of unit falling over. Can cause equipment damage, injury and death. The Liebert XDC is top-heavy. Use extreme caution and care when moving and installing this unit.
WARNING! Risk of refrigerant system explosion or rupture from overpressurization. Can cause equipment damage, injury and death. Installer must install a 400 psig pressure relief valve in each of the two R-407C refrigerant circuits of the Liebert XDC system. Do not install shutoff valves between the compressors and the pressure relief valves. For systems requiring EU CE compliance, the pressure relief valves must be CE-certified by a notified body to the EU Pressure Equipment Directive.
CAUTION: Risk of piping and component rupture. Can cause equipment damage and injury. Closing service valves may isolate liquid refrigerant, causing high pressure and rupture of piping. Do not close valves without following recommended procedures for repair, maintenance and replacement of components. Install pressure relief valves in field piping that may become isolated by service valves.
Vertiv | Liebert® XDC™ User Manual | 5
Page 6
NOTICE
CAUTION: Risk of contact with hot surfaces. Can cause burn injury. The compressors, pump motors and refrigerant discharge lines are extremely hot during unit operation. Allow sufficient time for the compressors, pump motors and refrigerant discharge lines to cool before working within the unit cabinet. Use extreme caution and wear protective gloves and arm protection when working on or near hot compressor, pump motors or discharge lines.
CAUTION: Risk of improper installation and startup. Can cause warranty cancellation, equipment damage and injury. Read and follow completely the installation and start up instructions that are factory supplied with the unit.
CAUTION: Risk of sharp edges, splinters and exposed fasteners. Can cause personal injury. Only properly trained personnel wearing appropriate safety headgear, gloves, shoes and glasses should attempt to move, lift, remove packaging from or prepare the unit for installation.
Risk of a leaking coil due to freezing and/or corrosion. Can cause equipment and serious building damage.
NOTICE
Cooling and heat rejection coils, heat exchangers and piping systems that are connected to open cooling towers or other open water/glycol systems are at high risk for freezing and premature corrosion. Fluids in these systems must contain the proper antifreeze and inhibitors to prevent freezing and premature coil corrosion. The water or water/glycol solution must be analyzed by a competent water treatment specialist before startup to establish the inhibitor requirement. The water or water/glycol solution must be analyzed every six months to determine the pattern of inhibitor depletion. The complexity of water-caused problems and their correction makes it important to obtain the advice of a water treatment specialist and follow a regularly scheduled maintenance program.
Risk of leaking chilled water lines. Can cause equipment and building damage.
Lines and joints must be inspected regularly. Improper installation, application and service practices can result in water leakage from the unit. Water leakage can result in severe property damage and loss of critical data center equipment. Do not locate unit directly above any equipment that could sustain water damage. Vertiv recommends installing monitored leak detection equipment for the unit and supply and return lines.
Vertiv | Liebert® XDC™ User Manual | 6
Page 7
NOTICE
Risk of clogged or leaking drain lines. Can cause equipment and building damage.
This unit requires a water drain connection. Drain lines must be inspected regularly and maintenance must be performed to ensure that drain water runs freely through the drain system and that lines are clear and free of obstructions and in good condition with no visible sign of damage or leaks. This unit may also require an external water supply to operate.
Improper installation, application and service practices can result in water leakage from the unit. Water leakage can result in severe property damage and loss of critical data center equipment.
Do not locate unit directly above any equipment that could sustain water damage.
Vertiv recommends installing monitored leak detection equipment for the unit and the supply and return lines.
NOTE: This document must be used with site specific documentation and documentation for other parts of the system (heat rejection devices and cooling modules).
NOTE: Before any action that could cause a disturbance in the Liebert XD system’s cooling function is begun, the facility manager MUST be informed. In addition, after the action is taken and the work is finished, the facility manager MUST be informed.
Figure 1.1 Model number nomenclature
Vertiv | Liebert® XDC™ User Manual | 7
Page 8
This page intentionally left blank.
Vertiv | Liebert® XDC™ User Manual | 8
Page 9

2 PRODUCT DESCRIPTION

2.1 General Product Information

2.1.1 Product/System Description

The Liebert XDC™(X-treme Density Chiller) is a self-contained refrigeration distribution unit designed to cool rooms with high heat producing equipment. There are two distinct circuits, each utilizing different refrigerants and mechanical parts. The R-134a circuit is the “pumped” circuit containing redundant circulating pumps, a brazed plate heat exchanger along with valves and piping. The R-407C circuit is the dual direct expansion circuit containing scroll compressors, expansion valves, brazed plate heat exchanger, and piping. Heat removal is accomplished by using condensers connected to the dual direct expansion circuit. Heat rejection is available in two options: an outdoor air-cooled condenser and a water/glycol condenser. See Figure 2.1 below below.
The Liebert XDC monitors room conditions and prevents coil condensation by maintaining the refrigerant being pumped to the cooling modules at a temperature above the room dew point. All functions, such as temperature control, switching pumps (if necessary), etc., are automatic.
The Liebert XDC’s minimum recommended operating load is 40% of system nominal capacity. For example, a Liebert XDC160 60Hz system’s minimum load would be 64kW. Loading below this value can unfavorably affect system operation.
See Table 11.1 on page127 for the Liebert XDC160 rated cooling capacity.
Figure 2.1 Liebert XDC components
Vertiv | Liebert® XDC™ User Manual | 9
Page 10

2.2 Equipment Inspection

When the unit is delivered, inspect all items for visible and concealed damage. Damage should be immediately reported to the carrier and a damage claim filed with a copy sent to Liebert or to your sales representative.
NOTICE
Risk of improper storage. Can cause equipment damage.
Keep the Liebert XDC upright, indoors and protected from dampness, freezing temperatures and contact damage.

2.3 Equipment Handling

WARNING! Risk of unit falling over. Can cause injury or death. The Liebert XDC is top-heavy. Use extreme caution when moving and installing this unit. Use lifting equipment that is rated for the weight of the unit by an OSHA-certified rating organization. See Table 11.1 on page127 for unit weights. Personnel should be properly trained and certified to move and rig equipment
CAUTION: Risk of sharp edges, splinters and exposed fasteners. Can cause personal injury. Only properly trained personnel wearing appropriate safety headgear, gloves, shoes and glasses should attempt to move, lift, remove packaging from or prepare the unit for installation.

2.3.1 Handling the Liebert XDC While it is on Skid and Packaged

Always keep the unit upright, indoors and protected from damage.
If possible, transport the unit using a forklift truck. Otherwise use a crane with slings and spreader cables. In either case, do NOT press on the top edges of the packaging.
If using a forklift or pallet jack, make sure the forks (if adjustable) are spread to the widest allowable distance to still fit under the skid.
When moving the skidded unit with a forklift, do not lift the unit any higher than 3"(76mm). If circumstances require the unit to be lifted higher than 3"(76mm), great care must be exercised and all by-standing personnel are to be no closer than 20 feet (6m) from the lift point of the unit.
NOTICE
Risk of structural interference. Can cause equipment or building damage.
While on the skid, the unit is too tall (83" [2108mm] overall height) to fit through a standard doorway. Any attempt to move the unit, while skidded, through a standard doorway will cause damage to the unit and to the building.
NOTICE
Risk of damage from forklift. Can cause unit damage.
Keep the forklift tines level and at a height suitable to fit below the skid and/or unit to prevent exterior and/or underside damage.
Vertiv | Liebert® XDC™ User Manual | 10
Page 11
NOTICE
Risk of improper storage. Can cause unit damage.
Keep the Liebert XDC upright, indoors and protected from dampness, freezing temperatures and contact damage.
NOTICE
Risk of overtightening securing straps. Can cause damage to panels.
Place a protective material between the straps of the piano jacks and the unit. Ensure that the straps are not tightened to a point of damaging panels.

2.3.2 Unpacking the Liebert XDC

1. Remove the exterior stretch wrap packaging from the unit, exposing the protective corner and side packaging planks.
2. Remove the corner and side packaging planks from the unit, exposing the bag over the unit. The bag may remain in place for dust and panel protection or removed for immediate unit installation.
3. Remove the bag from the unit when ready to remove the skid for installation.
Figure 2.2 Unpacking the Liebert XDC

2.3.3 Removing the Unit from the Skid Using a Forklift

1. Align the forklift with either the front or rear side of the unit.
Make sure the tines of the forklift are locked at their widest position.
Use the center of gravity indicators to determine the entry points for the tines. The tines must be equally spaced on either side of the center of gravity indicator (see Figure 2.3 on the next page).
Vertiv | Liebert® XDC™ User Manual | 11
Page 12
2. Insert the tines of the forklift under the unit.
Make sure the tines are level. The tines must be low enough to fit under the unit without damaging it.
Make sure the tines extend beyond the opposite side of the unit.
3. Remove the 12 lag bolts and two brackets that secure the unit to the skid.
NOTE: Each lag bolt is 1-1/2" (38mm) long. They can be removed with a 9/16" socket or wrench.
4. Lift the unit to a height that it is not being support by the skid.
5. Move the skid from under the unit.
Figure 2.3 Use a forklift to remove the Liebert XDC from the skid

2.3.4 Removing the Unit from the Skid using Rigging

1. Use the center of gravity indicators on the unit to position the slings. The slings must be equally spaced on either side of the center of gravity indicator (see Figure 2.4 on the facing page).
2. Place slings under the unit using spaces provided between the skid deck boards.
NOTE: Unit is shown without outer packaging. These instructions may be applied with the outer packaging in place.
3. Use spreader bars or an equivalent method to ensure proper protection of the unit.
4. Ensure that the panels, if attached, are well protected from the slings with cushioning material.
NOTE: If rigging is to be used to move the unit closer to the site for installation, place one or two horizontal straps around the unit and vertical straps at mid height.
5. Remove the 12 lag bolts and two brackets that secure the unit to the skid.
NOTE: Each lag bolt is 1-1/2" (38mm) long. They can be removed with a 9/16" socket or wrench.
Vertiv | Liebert® XDC™ User Manual | 12
Page 13
6. Lift the unit off of the skid to an elevation point where the skid is not supporting the weight of the unit.
7. Remove the skid from under the unit.
NOTE: Depending on final installation location and the method of moving the Liebert XDC, the skid may need to remain under the unit.
Figure 2.4 Removing the unit from the skid using rigging

2.3.5 Moving the Liebert XDC Using Piano Jacks

1. Elevate the Liebert XDC with a lifting mechanism, such as a forklift or rigging.
1. Position one piano jack at each end of the Liebert XDC.
2. Lower the unit to a height suitable for placing it on the piano jacks.
3. Put protective material between the Liebert XDC and the piano jacks and straps.
4. Secure the Liebert XDC to the piano jacks.
5. Release the the Liebert XDC from the straps securing it to the lifting mechanism and move the mechanism away from the unit.
Using the piano jacks, at least two properly trained and qualified personnel can move the unit.
Vertiv | Liebert® XDC™ User Manual | 13
Page 14
Figure 2.5 Securing the Liebert XDC to piano jacks

2.3.6 Removing the Unit from the Piano Jacks

1. Lower the Liebert XDC as far as the piano jacks will allow.
2. Undo all strapping holding the piano jacks to the unit.
3. Lift one end of the Liebert XDC off one piano jack with a pry bar or similar device, taking care not to damage the unit’s cabinet.
4. Repeat step 3 to remove the piano jack from under the opposite end of the Liebert XDC.
5. Remove all material used to protect the unit from the piano jacks and strapping.
Vertiv | Liebert® XDC™ User Manual | 14
Page 15

3 INSTALLATION

3.1 Mechanical Considerations

3.1.1 Positioning the Liebert XDC

Install the Liebert XDC according to the site specific documentation and secure the unit to the floor.
The Liebert XDC can be installed near a wall or another Liebert XDC. However, there must be at least 3feet(92cm) clearance in front of the Liebert XDC as service access for components in the unit.
NOTE: During installation of the Liebert XDC, the top, bottom, front and left side of the unit must be accessible.
Figure 3.1 Dimensional data
Table 3.1
Liebert XDC dimensions, weight
Air-Cooled Model
50/60Hz A B* C D E F Domestic Export
XDC160 74 (1880) 34 (864) 33-1/ 8 (841) 33 (838) 72 (1829) 78 (1981) 1975 ( 896) 2109 (957)
*Dimension does not include the bezel ofthe disconnectswitch, the handle or the control bezel.
Vertiv | Liebert® XDC™ User Manual | 15
Dimensional Data, inches (mm)
Shipping Weight
lb. (kg)
Page 16
Figure 3.2 Piping locations
Table 3.2
Liebert XDC piping connection sizes
Piping Outlet Connection Sizes, OD Cu, inches
50/60Hz
A B C D
XDC160 2-1/8 1-1/8 1-3/8 7/8
Source: DPN001599
Vertiv | Liebert® XDC™ User Manual | 16
Page 17

3.1.2 Placing the Liebert XDC on a Floor Stand

WARNING! Risk of top-heavy unit falling over. Improper handling can cause equipment damage, injury or death. Only properly trained and qualified personnel wearing appropriate safety headgear, gloves, shoes and glasses should attempt to move, lift, remove packaging from or prepare unit for installation. Read all of the following instructions before attempting to move, lift, remove packaging from or preparing unit for installation. The water/glycol floor stand can be located beneath the Liebert XDC unit or can be installed nearby.
NOTE: Consult the factory if the Liebert XDC is not installed on the water/glycol condenser floor stand to prevent exceeding the maximum piping distances.
Refer to the floor stand installation sheet shipped inside the water regulating valve package.
1. Move the floor stand assembly to its installation area and uncrate the unit.
2. Position the floor stand in its final location.
3. Insert leveler pads into each floor stand leg.
4. Level the top of the floor stand to the specified height with the flanged adjusting nut.
5. Tighten jam nuts on all legs against flanged adjusting nuts.
6. Using an appropriate lifting device or method, raise the Liebert XDC and move it above the floor stand.
7. Align the welded tabs on top of the floor stand with the inside of the unit frame base (see Detail A in Figure 3.3 on the next page).
8. Maintaining the alignment of the Liebert XDC and the floor stand, lower the Liebert XDC onto the floor stand.
9. Connect the hot gas refrigerant lines from the Liebert XDC to the floor stand with 1-3/8" tubing (see Figure 3.3 on the next page andFigure 3.4 on page20).
10. Connect the liquid refrigerant lines as shown from the Liebert XDC unit to the floor stand with 7/8" tubing (see Figure 3.3 on the next page andFigure 3.4 on page20).
11. Connect the water lines as shown with the provided valving (see Figure 3.3 on the next page andFigure 3.4 on page20).
12. Connect capillary lines from each water regulating valve to condensers in the floor stand (see Figure 3.3 on the next page andFigure 3.4 on page20).
Capillary length is limited to 48" (1219mm).
13. Check the pipes for leaks and evacuate air from all pipes.
14. Insulate all water/glycol lines.
15. Charge each condenser loop with R-407C (see Table 4.15 on page57).
Vertiv | Liebert® XDC™ User Manual | 17
Page 18
Figure 3.3 Water/glycol Liebert XDC on a floor stand—positioning and piping connections
Vertiv | Liebert® XDC™ User Manual | 18
Page 19
Table 3.3
Liebert XDC water/glycol piping connection sizes
Model Piping Outlet Connection Sizes, OD Cu, inches
50/60Hz A B C D
1
E
2
F
XDC160 2-1/8 1-1/8 1-3/8 7/8 2-1/2 2-1/8 or 2-5/8
1. Threaded female connection
2. 2-1/8" for 1" water r egulatingvalve; 2-5/8" for 1- 1/4" water regulating valve
Source: DPN00141 9 Rev. 2
Vertiv | Liebert® XDC™ User Manual | 19
Page 20
Figure 3.4 Piping locations—floor stand and valve assembly

3.1.3 Positioning the Liebert XDC with Floor Stand

Install the Liebert XDC according to the site-specific documentation and secure the unit to the floor.
The Liebert XDC can be installed near a wall or another Liebert XDC. There must be at least 3 feet (914mm) clearance in front of the Liebert XDC for service access. When the Liebert XDC is combined with the optional water/glycol floor stand, Vertiv recommends leaving 3 feet (914mm) of clearance on the left side of the unit.
Vertiv | Liebert® XDC™ User Manual | 20
Page 21
A Liebert XDC on a floor stand is 102 inches (2591 mm) high (see Figure 3.5 below). The unit can be raised or lowered 1.5 inches (38.1 mm) with the leveling feet.
Figure 3.5 Dimensions and clearances for Liebert XDC on floor stand
Vertiv | Liebert® XDC™ User Manual | 21
Page 22

3.2 Electrical Considerations

3.2.1 High Voltage Connections

Make sure the actual supply voltage and frequency correspond to the voltage and frequency indicated on the Liebert XDC’s rating plate.
Connect cables for high voltage supply to the electrical box in the Liebert XDC according to Figure 3.1 on page15, Figure 3.7 on page24 and Figure 3.8 on page25 and make sure that the phases are correctly connected.
WARNING! Risk of electric shock. Can cause death and injury. Disconnect all local and electric remote power supplies before working within.
WARNING! Risk of electrical shock, short circuit and/or control malfunction. Can cause equipment damage injury and death.Damage to wiring or components can make unit unsafe to operate.Use caution when installing wiring to prevent damage to factory wiring.Install protective bushings in wiring knockouts as required to protect wiring from sharp edges.Do not disturb factory wiring or route field-installed wiring over electrical terminals.Use NEC Class 1 wiring for all hazardous voltage electrical power supplies.Check and retighten all wiring connections before starting the unit.
NOTE: Before beginning to install the Liebert XDC, read all instructions, verify that all the parts are included and check the nameplate to be sure the Liebert XDC voltage matches available utility power. Follow all local codes.
Vertiv | Liebert® XDC™ User Manual | 22
Page 23

3.2.2 Connecting High-Voltage Cables

1. Turn the Liebert XDC’s primary disconnect switch to the Off position (see Figure 3.6 below). Open the front doors and push down on the enclosure cover latch to open the hazardous voltage enclosure cover.
Figure 3.6 Front view of Liebert XDC and electrical enclosures
Vertiv | Liebert® XDC™ User Manual | 23
Page 24
2. Determine which knockouts in the electrical enclosure will be used and remove them (see Figure 3.7 below).
Figure 3.7 Electrical enclosure knockout locations for field wiring
Vertiv | Liebert® XDC™ User Manual | 24
Page 25
3. Route the input hazardous voltage electrical power wiring through the top right knockout on the primary electrical enclosure (see Figure 3.7 on the previous page) to the disconnect switch L1, L2 and L3 (see Figure 3.8 below). Observe proper phasing.
4. Connect the ground wire to the ground lug (see Figure 3.8 below andFigure 3.10 on the next page for 60Hz models and Figure 3.9 below andFigure 3.11 on the next page for 50Hz models).
Figure 3.8 60Hz models, high voltage connections—primary disconnect switch
Figure 3.9 50Hz models high voltage connections—primary disconnect switch
Vertiv | Liebert® XDC™ User Manual | 25
Page 26
Figure 3.10 60Hz models high voltage connections—secondary disconnect switch
Figure 3.11 50Hz models high voltage connections—secondary disconnect switch
Vertiv | Liebert® XDC™ User Manual | 26
Page 27

3.3 External Pump Overloads

The Liebert XDC is shipped with external pump overload with trip point settings and DIP switch settings for normal operations. The trip points are in increments of 0.25A and should not be changed from the factory settings. For 460V 60Hz and 380-400V 50Hz units, the trip point is set at 1.5A (Figure 3.12 below). See Figure 3.14 below for factory DIP switch settings for normal operation with reset mode set as automatic and Trip Class 20.
Figure 3.12 460V 60Hz and 400V 50Hz factory setting external pump overload trip point
Figure 3.13 208V factory setting external pump overload trip point
Figure 3.14 Factory DIP switch settings
Vertiv | Liebert® XDC™ User Manual | 27
Page 28

3.4 Extra Low Voltage Connections

Extra Low Voltage (ELV) power output is 30V and 100VA or less.
1. Turn off all unit power before connecting cables or wires. Failure to do so may damage this equipment.
2. Route low voltage electrical connections through the appropriate knockouts as shown in Figure 3.17 on page31.
3. User interface and temperature/humidity sensor wire is NEC Class 2. All electrical installation must comply with all national, state and local requirements.
Figure 3.15 Liebert XDC heat rejection connection points
Vertiv | Liebert® XDC™ User Manual | 28
Page 29
Figure 3.16 Connecting remote temperature/humidity sensors
Vertiv | Liebert® XDC™ User Manual | 29
Page 30
Notes on Figure 3.16 on the previous page
1. See unit electrical schematic, installation and user manuals.
2. Cables A and B provided with each unit. Only one is used as follows:
a. Liebert IntelliSlot-Based Communications—Cable A is pre-connected to P65 on the
microprocessor and I/O board and P65 on Liebert IntelliSlot power supply.
b. Non-Liebert IntelliSlot-Based Communications—Cable B is pre-connected to Terminals
77 & 78 but must be exchanged with Cable A at P65 on the microprocessor and I/O board.
3. Install applicable Liebert IntelliSlot cards.
4. Both cables (P64 and P66) are required.
5. It is not necessary to connect ground coupling on end of cable connected to Sensor A or B.
6. A crossover coupler is provided for unit-to-unit (U2U) networking. Unplug the red cable from P64 on the microprocessor and I/O board and connect to one side of the crossover coupler. The first customer connection point is to P64 on the microprocessor and I/O board. The second customer connection point is to the other side of the crossover coupler. This connects the microprocessor and I/O board and display to the private U2U network.
7. The remote sensors are interchangeable as to which connects to the Liebert XD cooling module and which connects to P2 on CAN ISO.
8. Field-install cables with factory-installed ferrite beads (when provided, typical two places). Each cable must make three passes through the ferrite bead. Locate the ferrite bead on top of the electric box. See instruction sheet provided with the cable assembly.
9. Factory-installed ferrite bead (when provided). Cable passes through ferrite bead three times.
Vertiv | Liebert® XDC™ User Manual | 30
Page 31
Figure 3.17 Electrical enclosure knockout locations for Extra Low Voltage connections
Field Connections—All Units
Place Sensor A in the higher-temperature portion of the cold aisle where the Liebert XD modules are located. Alternatively, it may be placed on the return air side of the primary air mover (e.g., Liebert DS™) in the room if it represents the conditions where all the Liebert XD cooling modules are located. Do not install the sensor where ambient air might cause false readings, for example, near unsealed doors, windows and similar areas.
1. Unpack the two remote temperature/humidity sensors and cables.
One sensor is labeled Sensor A and the other, Sensor B. The sensor cables are interchangeable; each bears labels indicating Sensor End and Unit End.
2. Connect the Sensor End of one of the supplied sensor cables to P66 on Sensor A (see Figure
3.16 on page29).
3. Connect the Unit End of the sensor cable to P4 on the CAN Isolator inside the Liebert XDC (see Figure 3.16 on page29). Secure the terminal plug on the cable shield to the into the terminal plug adjacent to P2 (see Figure 3.16 on page29).
4. Connect the Sensor End of the second sensor cable to P66 on Sensor B (see Figure 3.16 on page29).
5. Connect the Unit End of the cable to P4 on the CAN Isolator inside the Liebert XDC (see Figure
3.16 on page29). Secure the terminal plug on the cable shield to the terminal plug adjacent to P4 (see Figure 3.16 on page29).
Vertiv | Liebert® XDC™ User Manual | 31
Page 32
Field Connections—Optional for All Units
Connect optional field wiring from remote devices to Remote Alarm Device, Common Alarm Output, IGM and Remote Shutdown, if applicable. See terminal strip descriptions in Figure 3.18 on the facing page.
Field Connections—Air-Cooled Units only
Connect field wiring to heat rejection connection terminals on the handy box as shown in Figure 3.15 on page28.
Vertiv | Liebert® XDC™ User Manual | 32
Page 33
Figure 3.18 Extra Low Voltage field connection points
Vertiv | Liebert® XDC™ User Manual | 33
Page 34
DIP Switch and Jumper Settings for remote sensors
The Liebert XDC is shipped with jumpers and DIP switch settings for normal operations. See Figure 3.19 below.
Figure 3.19 DIP switch and jumper settings for remote sensors

3.5 Remote Sensor Installation—Proper Placement

Placement of the two remote temperature/humidity sensors is critical to effective cooling of the conditioned space.
The remote sensors must be installed in areas where conditions are representative of the space conditioned by the Liebert XDC. Vertiv recommends installing the sensors in different areas near the cooling modules served by the Liebert XDC. If the return air side of the primary air mover, such as a Liebert DS, represents the conditions where the Liebert XD cooling modules are located, one sensor could be placed there. Vertiv suggests placing the other sensor on the wall opposite the heat load area (see Figure 3.20 on the facing page for guidance).
Vertiv | Liebert® XDC™ User Manual | 34
Page 35
Figure 3.20 Suggested remote sensor placement
Do not install the sensors where ambient air might cause false readings, for example, near unsealed doors or windows, or areas with stagnant air.
Vertiv | Liebert® XDC™ User Manual | 35
Page 36
This page intentionally left blank.
Vertiv | Liebert® XDC™ User Manual | 36
Page 37

4 PIPING AND FILLING WITH REFRIGERANT: R-134A AND R-407C CIRCUITS

4.1 European Union Fluorinated Greenhouse Gas Requirements

Stationary air conditioning, refrigeration, heat pump equipments and stationary fire protection systems in the European Community market and operating with fluorinated greenhouse gases (f-gas), such as R407C, R134a, R410A, must comply with the F-Gas Regulation: (EC) No. 842/2006 (F-gas). The regulation prohibits, among other actions, venting fluorinated greenhouse gases to the atmosphere.
The F-Gas Regulation requires operators to use all measures that are technically feasible and do not entail disproportionate cost to prevent leakage of these gases, to test for leakage regularly and to recover f-gas before disposing of equipment, as well as during service and maintenance.
Refer to the full regulation for additional details.

4.2 Recommended Pipe Size

NOTE: Follow all local codes on maximum length and size of refrigerant lines. Connect the main pipes between the Liebert XDC and the Liebert XD cooling modules according to site specific documentation and the configuration guide for the Liebert XD system. Elbows and restrictions shall be minimized for proper operation.
Table 4.1
Supply, return pipe sizes for Liebert XD refrigerant loop
Pipe Function Size/Equivalent Pipe Length
Liebert XDC s upply line, from Liebert XDC supply to far thest Liebert XD cooling module
Liebert XDC r eturn line, from farthest coolingmodule to Liebert XDC return
From any model Liebert XDO/ Liebert XDH supply to supply line of L iebert XDC
From any model Liebert XDO/ Liebert XDH return to r eturn line of L iebert XDC
From any model Liebert XDV/Liebert XDCF supply to s upply line of L iebert XDC
From any model Liebert XDV/Liebert XDCF return toreturn line of L iebert XDC
1-1/8" OD (1.025" ID) for lengths up to 60 feet
1-3/8" OD (1.265" ID) for lengths over 60 butless than175 feet
2-1/8" OD (1.985" ID) for lengths upto 60 feet
2-5/8" OD (2.465" ID) for lengths over 60 but less than 175 feet
1/2" OD (0.4 30" ID) for lengths up to 10 feet
7/8" OD (0.785" ID) for lengths over 10 but less than 25 feet
7/8" OD (0.785" ID) for lengths upto 10 feet
1-1/8" OD (1.025" ID) for lengths over 10 but less than 25 feet
1/2" OD (0.4 30" ID) for lengths up to 10 feet
5/8" OD (0.545" ID) for lengths over 10 butless than35
5/8" OD (0.545" ID) for lengths upto 10 feet
7/8" OD (0.785" ID) for lengths over 10 but less than 35 feet
Vertiv | Liebert® XDC™ User Manual | 37
Page 38

4.3 Liebert XDC Interconnection With Liebert XD Cooling Module

All piping must be ASTM (American Society for Testing and Materials) Type ACR copper pipe.
The Liebert XDC may be connected to Liebert XD cooling modules with either Liebert’s XD prefabricated piping assembly or with rigid, off-the-shelf piping. In either setup, piping for the Liebert XD system is arranged in a manner similar to piping for a chilled water system. Liebert XD cooling modules are connected in parallel between main return and supply pipes going to and from the Liebert XDP/Liebert XDC. Figure 4.1 below represents a typical configuration. For piping details, refer to Liebert’s XD System Design Manual, SL-16655. The guidelines provided for pipe size must be strictly followed. Failure to size the main lines and connection lines adequately may result in reduced cooling capacity. The critical aspects of pipe sizing are related to refrigerant volume and pressure drop. Both must be minimized.
Figure 4.1 Liebert XD system diagram

4.4 Piping Installation Method

The assembly and connection means used for piping in the Liebert XD system are similar to those used for conventional refrigeration systems. All piping should be installed with high-temperature brazed joints. Soft soldering is not recommended.
During brazing, the lines must be filled with flowing dry nitrogen to prevent excessive oxidation and scale formation inside the piping. Prevailing good refrigeration practices must be employed for piping supports, leak testing, dehydration and charging. Failure to use good system practices may result in damage to the system. Refer to the ASHRAE refrigeration handbook for general good-practice refrigeration piping.
Insulate all piping lines to prevent condensation in applications where the dew point approaches the R-134a refrigerant temperature.
Vertiv recommends venting the pressure relief valves for both the R-134a and R-407C sides outside the conditioned space where it is open to the atmosphere. The R-134a side relief valve is inside the Liebert XDC unit at the top of the receiver. The R-407C water/glycol-cooled side relief valves are located at each condenser beneath the Liebert XDC unit in the floor stand. The R-407C air-cooled relief valves are located outside within the air-cooled system.
Vertiv | Liebert® XDC™ User Manual | 38
Page 39

4.4.1 Piping Installation—R-134a Pumped Circuit

Vertiv recommends venting the relief pressure of the Liebert XDC (located at the top of the receiver) outside of the conditioned space where it is open to the atmosphere.

4.4.2 Bypass Flow Controllers

Two bypass flow controllers are required to ensure the Liebert XDC pumps operate within the optimum range. These devices are added to the field piping and simulate the flow of additional cooling modules.
Each bypass flow controller must be installed with one shutoff valve to allow the controller to be disabled when cooling modules are added to a Liebert XD system.
Bypass flow controllers should be connected between the main supply and the main return lines of the field piping. The connection points to the main supply and return lines should be in a convenient and accessible location between the Liebert XDP/Liebert XDC and the first Liebert XD module in the circuit. See Figure 4.2 below andFigure 4.3 on the next page for piping details of the bypass flow controller.
Refer to Table 4.2 below to determine the number of bypass flow controllers needed to be open to provide proper refrigerant flow, based on the total nominal cooling capacity of the cooling modules in each Liebert XD system.
Table 4.2
Bypass flow controllers for a Liebert XDC-based system
Required Number of Open
System Load kW
Cumulative Module Model Size
32 to 63 N/A
64 to 95 2
96to 127 1
128 to 1 60 0
Bypass Flow Controllers
Liebert XDC
Figure 4.2 Bypass flow controller details, dimensions
Vertiv | Liebert® XDC™ User Manual | 39
Page 40
Figure 4.3 Bypass flow controller arrangement
Figure 4.4 Bypass flow controller piping
Vertiv | Liebert® XDC™ User Manual | 40
Page 41

4.5 Piping Details—Shutoff/Isolation Valves

Isolation valves must be installed on the Liebert XDC’s refigerant circuit to permit maintenance on the unit (see Figure 4.5 below.)
Figure 4.5 General piping details
Evacuation and Leak Check—R-134a Pumped Circuit
1. Open all service valves, including those located outside of the Liebert XDC.
2. Attach a jumper hose from one of the Schrader valve fittings on a pump outlet before the check valve to a Schrader valve fittings after the check valve.
3. Place 150 psig (1034kPa: 10.34 bars) of dry nitrogen with a tracer of R-134a in the system.
NOTE: Risk of overpressurization. Can cause equipment damage. Do not exceed 150 psig (1034 kPa; 10.34 bars) in the R-134a circuit.
4. Check the system for leaks with a suitable leak finder on the pumps’ suctions lines.
5. After completion of the leak testing, release the test pressure (per local code) and connect to vacuum pump(s) at the Schrader valves.
6. After four hours of pulling a deep vacuum, check the vacuum level and if it has not changed, break the vacuum with dry nitrogen.
7. Pull a second vacuum to 500 microns or less. Recheck the vacuum level after 2 hours.
Insulation
NOTE: Piping should not be insulated before it has been checked for leaks. Applying good insulation to pipes before checking for leaks would prevent easy detection of leaks.
Insulate all piping between the Liebert XDC and cooling modules to prevent condensation where the piping passes through non-conditioned areas.

4.6 Filling the Pumped Circuit—R-134a

1. Connect a charging manifold to the Schrader valve fittings on the pump suctions lines.
Vertiv | Liebert® XDC™ User Manual | 41
Page 42
2. Purge the hoses.
3. Calculate the amount of R-134a refrigerant needed to charge the system, using the values in Table 4.3 below, Table 4.4 below, Table 4.5 on the facing page and Table 4.6 on the facing page; for assistance, refer to Calculating Refrigerant Charge—Example on page44. The section includes a worksheet to calculate system refrigerant charge requirements.
4. Weigh in the calculated charge.
5. After adding the calculated charge, allow the system to sit 15 to 30 minutes to reach equilibrium. Observe the refrigerant level through the sight glasses of the receiver.
6. If the refrigerant level is improper, the charge must be adjusted.
If the level is too high or too low, recalculate the required charge and reduce or increase the amount as needed to reach the proper level.
NOTE: All lengths in Table 4.4 below, Table 4.5 on the facing page and Table 4.6 on the facing page are actual pipe lengths, not equivalent pipe lengths.
NOTE: System refrigerant volume calculations derived from Table 4.3 below, Table 4.4 below, Table
4.5 on the facing page and Table 4.6 on the facing page are based on a fully loaded system. Additional charge may be required for lightly loaded systems.
Table 4.3
System R-134a charge for a Liebert XDC with any model Liebert XDH/Liebert XDO/Liebert XDV/Liebert XDCF
Refrigerant Charge,
lb. (kg)
157 lb. (65.7kg) Liebert XDC
3.55 lb. ( 1.61kg) Liebert XDO
2.32 lb. (1.05kg) Liebert XDV
5.32 lb. ( 2.41 kg) Liebert XDH
1.41 lb. (0.64kg) Liebert XDCF
4.0 lb. (1 .81kg) Liebert XDR
Per Liebert XD Unit
(Excludes Connector Lines to and from Liebert XD Cooling Module)
Table 4.4
System refrigerant charge for the supply and return mains
Refrigerant Charge,
lb/foot (kg/m)
0.45 (0.67) Main supply actual lengthper 1-1/8" OD copper tubing
0.68 (1.01) Main supply actual lengthper 1-3/8" OD copper tubing
0.28 (0.42) Main return actual lengthper 2-1/8" OD copper tubing
0.43 (0.64) Main return actual lengthper 2-5/8" OD copper tubing
Supply/Return Main Length and Diameter
Vertiv | Liebert® XDC™ User Manual | 42
Page 43
Table 4.5
R-134a refrigerant charge for hard-piped connector lines to and from any model Liebert XDH/Liebert XDO/Liebert XDV/Liebert XDCF
Refrigerant Charge,
lb/foot (kg/m)
0.08 (0.12) 1/2" OD Liebert XDO/L iebert XDH/Liebert XDV/Liebert XDCF/Liebert XDR supply connector actuallength
0.13 (0.19) 5/8" OD copper tubing Liebert XDV/Liebert XDCF supply connector actual length
0.26 ( 0.39) 7/8" OD L iebert XDO/Liebert XDH/Liebert XDR supply connector actual length
0.02 (0.03) 5/8" OD copper tubing Liebert XDV/Liebert XDCF return connector actual length
0.04 (0.06) 7/8" OD copper tubingLiebert XDV/Liebert XDCF return connector actual length
0.04 (0.06) 7/8" OD copper tubingLiebert XDH/Liebert XDO/Liebert XDR return connector actual length
0.07 (0.1) 1-1/8" OD copper tubing Liebert XDH/Liebert XDO/Liebert XD R return connector actual length
Hard-Piped Connector Length and Diameter
Table 4.6
R-134a refrigerant charge for Liebert XD Flex Pipe connector lines to and from any model Liebert XDO/Liebert XDH/Liebert XDV/Liebert XDCF
Refrigerant
Charge, lb. (kg)
Supply Line Diameter 1/2"
0.3 lb. (0.14) 4 ft. Liebert XD Flex Pipe L iebert XDH/Liebert XDO/Liebert XDV/Liebert XDCF/Liebert XDR s upply
0.5 lb. (0.23) 6 ft. Liebert XD Flex Pipe L iebert XDH/Liebert XDO/Liebert XDV/Liebert XDCF/Liebert XDR s upply
0.7 lb. (0.32) 8 ft. Liebert XD Flex Pipe Liebert XDH/Liebert XDO/L iebert XDV/L iebert XDCF/Liebert XDR supply
0.8 lb. ( 0.36) 10 ft. Liebert XD Flex Pipe Liebert XDH/Liebert XDO/Liebert XDV/L iebert XDCF/Liebert XDR supply
Return Line Diameter 5/8"
0.01 lb. (0.01) 4 ft. Liebert XD Flex Pipe existing Liebert XDV sys tems
0.02 lb. (0.01) 6 ft. Liebert XD Flex Pipe existingLiebert XDV systems
0.03 lb. (0.01) 8 ft. Liebert XD Flex Pipe existing Liebert XDV sys tems
0.03 lb. (0.01) 1 0 ft. Liebert XD Flex Pipe existingLiebert XDV systems
Return Line Diameter 1"
0.13 lb. (0.06) 4ft L iebert XD Flex Pipe Liebert XDH/L iebert XDO/Liebert XDV/Liebert XDCF/Liebert XDR supply
0.2 lb. (0.096) 6ft Liebert XD Flex Pipe Liebert XDH/Liebert XDO/Liebert XDV/L iebert XDCF/Liebert XDR supply
0.27 lb. (0.126) 8ftLiebert XD Flex Pipe L iebert XDH/Liebert XDO/Liebert XDV/Liebert XDCF/Liebert XDR s upply
0.33 lb. (0.15) 10ft L iebert XD Flex Pipe Liebert XDH/Liebert XDO/Liebert XDV/L iebert XDCF/Liebert XDR supply
Metal L iebert XD Flex Pipe Connector L ength
Vertiv | Liebert® XDC™ User Manual | 43
Page 44

4.6.1 Calculating Refrigerant Charge—Example

Using Table 4.3 on page42,Table 4.4 on page42,Table 4.5 on the previous page andTable 4.6 on the previous page, calculate the refrigerant charge of the individual sections of your Liebert XD system. Add the calculated charge amounts to determine the amount of R-134a refrigerant required for one system combining a Liebert XDC with Liebert XD cooling modules (Liebert XD CoolFrame, Liebert XDH, Liebert XDO and Liebert XDV). The example below combines one Liebert XDC with 20 Liebert XDV8 cooling modules.
Table 4.7
Calculating refrigerant charge—example
Components
Liebert XDC 1 157 157
Liebert XDV8 Cooling Modules 20 2.32 46.4
Supply Main, 1-1/8" 100 0.45 45
Return Main, 2-1/8" 100 0.28 28
Liebert XDV 1 /2" supply Liebert XD Flex Pipes 20 0.8 16
Liebert XDV 5/8" return Liebert XD Flex Pipes 20 0.03 0.6
Number ofUnits
or Piping Length, feet
Pounds
Per Component
Total 293
Table 4.8
Worksheet to calculate refrigerant charge
Components
Number ofUnits
or Piping Length
Pounds
Per Component
Total, lb.
Total
Total
Vertiv | Liebert® XDC™ User Manual | 44
Page 45

4.6.2 Piping for Direct Expansion (DX) Circuit—R-407C Air-Cooled Units

WARNING! Risk of refrigerant system explosion or rupture from overpressurization. Can cause equipment damage, injury or death. Installer must install a 400 psig pressure relief valve in each of the two R-407C refrigerant circuits of the Liebert XDC system. Do not install shutoff valves between the compressors and the pressure relief valves. For systems requiring EU CE compliance, the pressure relief valves must be CE-certified by a notified body to the EU Pressure Equipment Directive.

4.7 Install Double Discharge Risers

For air-cooled systems, double discharge risers must be installed in the hot gas lines that have vertical heights of 15 feet (4.6m) or more (see Figure 4.6 below). This will allow proper oil return to the compressors when the system is running at low loads. A double riser system is constructed of a large diameter riser with a trap at the base and a riser with a smaller diameter in parallel.
At full-load operation, the refrigerant vapor flows up both risers at velocities that are adequate to carry the oil. At low loads, refrigerant vapor velocities are lower and the trap at the bottom of the riser becomes filled with oil. When this happens, refrigerant flows up only the smaller riser.
The trap at the top of the riser must be tied into the top of the line to prevent oil from filling the larger riser. For each double riser used, the maximum height of the riser must not exceed 15 feet (4.6m). Multiple risers must be installed in series as the height of the hot gas line increases. Total maximum height of the hot gas line must not exceed 60 feet (18.3m).
Horizontal discharge lines should be pitched downward in the direction of flow to aid in oil drainage with downward pitch of at least 1/2 inch in 10 feet (13mm in 3m).
Figure 4.6 Double discharge riser layout
Vertiv | Liebert® XDC™ User Manual | 45
Page 46
Contact your local Liebert representative for factory approval whenever a refrigerant piping run exceeds 200 feet (60m) equivalent length or when condensers must be installed below the level of the cooling coil.
For Air-Cooled Liebert Lee-Temp / Flood Back Head Pressure Control Units Only
WARNING! Risk of explosive discharge from high-pressure refrigerant. Can cause injury or death. This unit contains fluids and/or gases under high pressure. Relieve pressure before working with piping.
NOTICE
Risk of refrigerant contamination. Can cause equipment damage and operational problems.
Refrigerant R-407C is a blend of three components and must be introduced and charged from the cylinder only as a liquid.
Refrigerant R-407C uses a POE (polyolester) lubricant. Do not open the compressor unit piping to the atmosphere for more than 15 minutes. The compressors contain POE oil that is very hygroscopic; it quickly absorbs water from the atmosphere. The longer the compressor piping is open to the atmosphere, the harder it will be to fully evacuate. If left open too long, the POE oil may need to be replaced before achieving the required vacuum level.
POE oils also have a property that makes them act as a solvent in a refrigeration system. Maintaining system cleanliness is extremely important because the oil will tend to bring any foreign matter back to the compressor. Refer to the ASHRAE refrigeration handbook for general good-practice refrigeration piping.
Table 4.9
Receivers and head pressure kits for Liebert Lee-Temp condensers
Outdoor Ambient
°F (°C)
-30 to 100 (- 34 to 38) DCSL415 2
-30 to 105 (-34 to41) DCSL616 2
35 to 105 (2 to 41) D CSL616 2
1. 120V heater
2. 230V heater
Condenser
Model 50/60Hz
Condenser
Qty
Receiver
Part #
185010G21/G4
179713G11/G2
181610G21/G4
Receiver
Qty
2
2 179711 G1 2
2
1 179711G2 2
2
2 179711 G1 2
Head
Pressure Kit
Head
Pressure
Kit Qty
Vertiv | Liebert® XDC™ User Manual | 46
Page 47
Figure 4.7 Installation data—Liebert Lee-Temp, one-circuit, four-fan model
Vertiv | Liebert® XDC™ User Manual | 47
Page 48
Figure 4.8 Installation data—Liebert Lee-Temp, one-circuit, high ambient six-fan model
Vertiv | Liebert® XDC™ User Manual | 48
Page 49
Figure 4.9 Liebert XDC piping schematic and Liebert Lee-Temp heater pad wiring
Vertiv | Liebert® XDC™ User Manual | 49
Page 50
Figure 4.10 General arrangement air-cooled Liebert XDC Liebert Lee-Temp Control
Vertiv | Liebert® XDC™ User Manual | 50
Page 51
Table 4.10
Recommended refrigerant line sizes, DX R-407C, OD copper
Liebert XDC 160
Equivalent Length, ft., (m)
50 (15) 1-1/8 7/8
100 (30) 1-1/8 1-1/8
150 (45) 1-3/8 1- 1/8
200 (60) 1-3/8 1- 1/8
* Double risers are required when hot gas vertical rise is 1 5ft. (4.6m) or more (see Install Double Discharge Risers on page45).
Source: DPN000937, Pg. 3, Rev. 11
*Hot Gas Line, in. Liquid Line,in.
Vertiv | Liebert® XDC™ User Manual | 51
Page 52
Figure 4.11 DCSL616 piping connections—two refrigerant circuits connected for parallel flow
Vertiv | Liebert® XDC™ User Manual | 52
Page 53
Table 4.11
Recommended refrigerant line sizes for DCSL616
Liebert XDC 160
Equivalent Length, ft., (m)
50 (15) 1-1/8 7/8
100 (30) 1-1/8 1-1/8
150 (45) 1-3/8 1-1/8
200 (60) 1-3/8 1-1/8
* Double risers are required when hot gas vertical rise is 1 5 feetor more (see Install Double Discharge Risers on page45).
Source: DPN000937, Pg. 4, Rev. 11
*Hot Gas Line, in. Liquid Line, in.
Figure 4.12 DCSL616 piping connections—two refrigerant circuits connected for parallel refrigerant flow
Vertiv | Liebert® XDC™ User Manual | 53
Page 54

4.7.1 Air-Cooled Condenser with Liebert Lee-Temp “Flooded Condenser” Head Pressure Control System—R-407C (DX) Circuit

The Liebert Lee-Temp system consists of a modulating type head pressure control valves and insulated receivers with heater pads to ensure operation at ambient temperatures as low as -30°F (-34.4°C).
Liebert Lee-Temp Piping
Two discharge lines and two liquid lines must be field-installed between the indoor unit and the outdoor condenser. See 4.6.2 on page45 and 4.6.2 on page45 for details.
Liebert Lee-Temp Control Materials Supplied
Built-in, pre-wired condenser control box
Air-cooled condenser
Piping access cover to be reinstalled when piping is complete
Bolts—four per leg (3/8" x 5/8")
Terminal block for two-wire, 24V interlock connection between unit and condenser
Condensate legs—four with one-fan, six on two-and three-fan models and eight on four-fan models
Bolts—used to mount receiver (3/8" x 1-1/4")
Liebert Lee-Temp system:
Insulated storage receiver—one per circuit
Head pressure control assembly (head pressure valves and check valves) - one per circuit
Service valve—one per circuit
Pressure relief valve—one per circuit
Liquid level sight glasses
NOTE: Liebert Lee-Temp heater pads require a separate, continuous electrical source. See nameplate on unit for proper voltage.
Evacuation and Leak Check—R-407C (DX) Circuit (Air and Water/Glycol Systems)
1. If unit power is available, open the unit’s liquid line and hot gas valve solenoid valves using the Tandem Bank 1 and Tandem Bank 2 evacuation function in the Liebert iCOM’s Service Menu. If power is not available to the unit, a field-supplied 24VAC/75VA power source must be directly connected to each of the unit’s solenoid valves..
NOTE: The procedures above allow the technician to use 24VAC power and controls to open liquid line solenoid valve(s) for the dehydration process. If no power is at the unit disconnect, the technician is to use a separate 24VAC source rated at 75 VA and connect to the system liquid line solenoid valve(s) directly.
2. Attach refrigerant gauges to the suction and discharge service valves of the compressor.
3. Open all compressor service valves, including those located outside the Liebert XDC.
4. Connect the tank of dry nitrogen to the Schrader valves on the liquid lines and the hot gas lines.
5. Pressurize the system circuit(s) to 150 PSIG (1034 kPa; 10.34 bars) with dry nitrogen with a trace of refrigerant. Check the system for leaks with a suitable leak finder.
Vertiv | Liebert® XDC™ User Manual | 54
Page 55
6. After completion of leak testing, release the test pressure (per local code) and connect to vacuum pump(s) at the Schrader valves on the liquid lines and on the hot gas lines.
NOTE: There is a check valve in the discharge line and Liebert Lee-Temp piping assembly of each circuit. Ensure that all pressure has been relieved before starting the vacuum pump.
7. Place a jumper hose from the service valve fitting on the outlet of the receiver and the schrader fitting on the discharge header of the condenser. Front-seat the service valve two (2) turns.
8. After 4 hours of pulling a deep vacuum, check the vacuum levels and, if they have not changed, break the vacuum with dry nitrogen.
9. Pull a second and third vacuum to 500 microns or less. Recheck the vacuum level after 2 hours.
10. Once a system has achieved 500 microns, turn off evacuation, close the receiver service valve and remove the jumper hose.

4.8 Filling the Direct Expansion (DX) Circuit—R-407C

NOTE: If necessary, refer to Installation Checklist on page59 to ensure that the system has been properly checked out and is ready to be filled with refrigerant. Any recommended volumes will be approximate. The user must verify that all circuits of the system have been adequately filled.
For Air-Cooled Liebert Lee-Temp / Flood Back Head Pressure Control Units Only
NOTE: Proper safety equipment and proper refrigeration tools are required. Check unit nameplate for correct refrigerant type before topping off or recharging a system.
NOTE: Refrigerant R-407C is a blend of three components, and must be introduced and charged from the cylinder only as a liquid. Refrigerant R-407C uses a POE (polyolester) lubricant. Do not open the compressor unit piping to the atmosphere for more than 15 minutes. The compressors contain POE oil that is very hygroscopic; it quickly absorbs water from the atmosphere. The longer the compressor piping is left open to the atmosphere, the harder it will be to fully evacuate. If left open too long, the POE oil may need to be replaced before achieving the required vacuum level. Refrigerant charging requires unit operation. Refer to Checklist for Liebert XDC Startup on page111.
1. Calculate the amount of charge for the R-407C side of the system. Refer to Table 4.13 on the next page, Table 4.14 on the next page, Table 4.15 on page57 and Figure 4.13 on page57.
2. Weigh in as much of the calculated R-407C charge as possible by utilizing tank heaters on the refrigerant bottles before starting the unit.
NOTICE
Risk of improper operation. Can cause equipment damage.
Before proceeding to step Turn Off the main power to the unit. below, the R-134A side must be charged with the calculated refrigerant charge.
There also must be enough room heat to start the system the system (64kW minimum). If not, running the compressors alone could cause the heat exchanger to freeze and burst.
3. Turn Off the main power to the unit.
4. Disconnect either the low-voltage wires from the #2 compressor contactors holding coils or remove the high-voltage fuses for the #2 compressor bank.
Vertiv | Liebert® XDC™ User Manual | 55
Page 56
5. Turn On the Liebert iCOM controller by pressing the On/Off push button on the front of the Liebert iCOM display (see Figure 6.1 on page61).
6. Set the Min Room Temperature Setpoint to a minimum value of 50°F (10°C) (see Figure 6.7 on page70.
NOTE: The pumps must establish flow before the compressors will start. If the pumps lose flow, the compressors will turn Off. The pressure in the system must be at or above 65psig (448kPa) for the compressor(s) to start. A minimum of 30psig (207kPa) must be maintained for the compressor(s) to continue to operate. The compressor(s) will shut off if the pressure drops to 20psig (138kPa) or lower.
7. Weigh in the rest of the calculated charge.
8. Once Tandem Bank 1 is completely charged, repeat steps Turn Off the main power to the unit. on the previous page through7. above for Tandem Bank 2.
Table 4.12
Indoor unit refrigerant charge—R-407C
Model50/60 Hz Charge/Circuit, lb. (kg)
Liebert XDC160 17.5 (8.0)
Table 4.13
Outdoor air condenser charge—R-407C
Outdoor Ambient, °F (°C Model 50/60 Hz Receiver Part # Charge / Circuit, lb. (kg)
-30 to 100 (- 34 to 38) DCSL415
-30 to 105 (-34 to41) DCSL616
35 to 105 (2 to 41) DCSL616
1. 120V
2. 230V
185010G21/G4
179713G11/G2
181610G21/G4
2
2
2
Table 4.14
Air-cooled systems - liquid line charge - R-407C refrigerant per 100ft (30m) of Type ACR copper tube
O.D., inches Liquid Line, lb. (kg) Hot Gas Line, lb. ( kg)
3/8 3.7 (1.7) -
1/2 6.9 (3.1 ) -
5/8 11.0 (5.0 2.2 ( 1.0)
3/4 15.7 (7.1 ) 3.1 (1.4 )
7/8 23.0 (10.4) 4.5 (2.0)
1-1/8 39.3 ( 17.8) 7.8 (3.5)
1-3/8 59.8 (27.1 11 .8 (5.4)
1-5/8 16.7 (7.6)
200 (91)
254 (115)
164 (75)
Vertiv | Liebert® XDC™ User Manual | 56
Page 57
Table 4.15
Indoor water/glycol-cooled module – R-407C refrigerant charge
Model 60 Hz Charge / Circuit, lb. (kg)
Liebert XDC 1 60 30.0 (13.2) per circuit

4.9 System Refrigerant Charges Over 55lb. (24.9kg) Require Additional Oil

4.9.1 Liebert XDC DX R-407C Circuit Volume

NOTICE
Risk of improper lubrication. May cause equipment damage.
Liebert XDCs refrigerant R-407C circuits with refrigerant charges over 55lb. (24.9kg) require additional oil. See Figure 4.13 below for the amount required for various charge levels.
Once the system has been fully charged with refrigerant, use a hand pump to add the additional oil at the suction side of the system while the system is running.
The amount of oil added by field service must be recorded on a tag attached at the tandem, (the amount added along with the date it was added). This will be documented on a tag located at the tandem compressor and marked “Oil Added Field Service Record.” Refer to the Liebert XDC user manual, SL-16673, available at www.VertivCo.com.
Figure 4.13 Additional oil requirements for refrigerant charge
Vertiv | Liebert® XDC™ User Manual | 57
Page 58
To calculate the oil required, use the following formula:
Additional Oil Required per Circuit = (Refrigerant Charge * 0.4 - 22)
Enter the refrigerant charge in pounds to determine the oil required in ounces
NOTICE
Risk of improper compressor lubrication. Can cause compressor and refrigerant system damage.
Failure to use oil types, viscosities and quantities recommended by the compressor manufacturer may reduce compressor life and void the compressor warranty. See oil types specified in Table 4.16 below.
Do not mix polyol ester (POE) and mineral-based oils.
Do not mix oils of different viscosities.
Consult Vertiv or the compressor manufacturer if questions arise.
Table 4.16
Compressor oil types
Refrigerant Type
Compressor Type
R-407C
CopelandScroll and Digital Scroll POE OIL - ISO 32 Viscosity
Use Copeland®POE Oil ULTRA 22 CC, Mobil EAL Ar ctic 22 CC, Copeland brand U ltra 22 CC, Copelandbrand Ultra 32 CC, Copeland brand Ultra 32­3MAF, Mobil EA L™Arctic 22 CCor Uniqema RL32-3MAF or other Copeland-approved oil.
Vertiv | Liebert® XDC™ User Manual | 58
Page 59

5 INSTALLATION CHECKLIST

1. Unpack and check received material.
2. Position Liebert XDC and secure to floor.
3. Wire high voltage connections.
4. Wire low voltage connections.
NOTE: Risk of unintended pump start. Can cause equipment damage. Do not install the pump fuses for 60Hz until the system is fully charged with refrigerant. Do not remove the locking mechanisms from 50Hz circuit breakers until the system is fully charged with refrigerant. Operating the pumps without a full refrigerant charge can result in equipment damage.
5. Connect Liebert XD cooling module piping to Liebert XDC.
6. Check all circuits of the system for leaks.
7. Hold a vacuum on all circuits of the system.
8. Charge the system with refrigerant.
9. Make sure that all piping has proper insulation.
10. Use double risers in DX hot gas lines that are 15 feet (4.6m) or more in height.
Vertiv | Liebert® XDC™ User Manual | 59
Page 60
This page intentionally left blank.
Vertiv | Liebert® XDC™ User Manual | 60
Page 61

6 LIEBERT ICOM CONTROL—FIRMWARE VERSION XP1.00.009.STD

6.1 Liebert iCOM Components and Functions

The Liebert iCOM controller layout is shown in Figure 6.1 below; the keyboard functions are defined in Table 6.1 on the next page. The Liebert iCOM controller on the Liebert XDC displays the Unit View only.
Figure 6.1 Liebert iCOM display components
Vertiv | Liebert® XDC™ User Manual | 61
Page 62
Table 6.1
Keyboard icons and functions
Icon
Key Name Function
On/Off Key Controls the operational state ofthe cooling unit.
Alarm Key Silences an alarm.
HelpKey A ccesses integrated Help menus.
ESCape Key Returns tothe previous display view.
Enter Key Confirms all s elections andselects icons or text.
Increase Key (Up Arrow)
Moves upward in a menu or increases the value of a selected parameter.
Decrease Key (Down Arr ow)
Left and Right Arrow Keys
Upper LED BlinkingRed—Active, unacknowledgedalarm exists
Upper LED SolidRed—Active, acknowledged alarm exists
Moves downward in a menu or reduces the value ofa selectedparameter.
Navigates throughtext and sections of the display.
Vertiv | Liebert® XDC™ User Manual | 62
Page 63
Table 6.1 Keyboard icons and functions (continued)
Icon
Key Name Function
Amber—Power is available to the unit; unit is NOT operating
Lower LED
Green—Unit is operating with no alarms

6.2 Display Lamp Indicators

The Green lamp will be On only when the Liebert XDC is On and running with no alarms.
The Red lamp will be On if the unit is On and running with an active alarm, or if the unit is shut down because of a certain alarm.
The Red lamp will flash while an alarm is being annunciated. The Red lamp will stop flashing and the beeper in the display will stop beeping when the ALARM SILENCE / ? key is pressed.
The Amber lamp will be On if the Liebert XDC has been shut down at the I/O switch or if the unit has been shut down by an alarm condition.

6.3 Navigating Through the Liebert iCOM Display

The Liebert iCOM displays icons and text for monitoring and controlling your Liebert cooling unit. Figure
6.2 on the next page shows the Liebert iCOM’s home screen for the Liebert XDC.
Vertiv | Liebert® XDC™ User Manual | 63
Page 64
Figure 6.2 Liebert iCOM default home screen for Liebert XDC

6.3.1 Accessing Menus and Settings

Viewing Data
No password is required to view data or settings.
To view data:
1. From the home screen, press the Enter key to view the User Menu (see 6.7 on page68).
2. Press Enter again to highlight the first icon.
3. Use the keyboard’s arrow keys to move to the icon for the data you wish to view.
4. Once that icon is highlighted, press Enter again to open that menu.
If a password is required, see Entering the Password on the facing page.
If a menu has more than one screen, the Liebert iCOM display will have text at the top similar to this: (page 1 of 2).
5. Press Enter to select the first line of data.
6. Use the Up and Down arrow keys to scroll to the desired data point.
7. Press ESC to move back to higher level menus.

6.3.2 Cooling Module Overview

The Liebert iCOM will display an overview of all connected cooling modules. It does not display a system view, which would include units other than the cooling modules.
NOTE: The Liebert iCOM control screens display a setting to select a system view, but the Liebert XDC does not support a system view.
Vertiv | Liebert® XDC™ User Manual | 64
Page 65
To display an overview of all connected coolig modules:
1. At the default home screen on the Liebert iCOM, press the down arrow. This will display the first 10 modules’ outlet temperature and capacity levels. Press ESC to return to the unit view.
Figure 6.3 Cooling module overview, first 10 modules
2. Press the down arrow button again to display the next 10 modules’ outlet temperature and capacity levels.
3. Press ESC to return to the default home screen.

6.3.3 Entering the Password

Most settings in the Liebert iCOM are protected by factory-set passwords. The User Menu password is
1490. The Service Menu password is 5010. To enter the password:
1. From the home screen, press the Enter key to view the User Menu (see 6.7 on page68).
2. Press Enter again to highlight the first icon.
3. Use the keyboard’s arrow keys to move to the icon for the data you wish to change.
4. Once that icon is highlighted, press Enter again to open that menu.
5. Press Enter to highlight the Password line.
6. With the Password line highlighted, press Enter to highlight the first digit in the password.
7. Enter the password, 1490.
Use the Up and Down arrow keys to select a numeral for the first digit of the password.
Move to the next digit of the password with the Right arrow key.
Select the numerals for all four digits with the same process.
8. After all four digits of the password have been entered, press the Enter key.
Vertiv | Liebert® XDC™ User Manual | 65
Page 66
NOTE: Do not press the ESC key or the Liebert iCOM will move to the previous screen and the password must be re-entered before changes may be made.
Figure 6.4 Entering the password

6.4 Changing Liebert iCOM’s Display Settings

No password is required to change the way Liebert iCOM displays data. The Display Setup controls how the unit shows data, such as temperature, date and time.
To change the display settings:
1. From the home screen, press the Enter key to view the User Menu (see 6.7 on page68).
2. Press Enter again to highlight the first icon.
3. Use the keyboard’s arrow keys to move to the Display Setup icon.
4. Once that icon is highlighted, press Enter again to open that menu.
5. Press the Enter key to select the first setting.
Either change that setting or navigate to another setting with the Up and Down arrow keys.
6. Once the desired setting is highlighted, press the Enter key to access that parameter’s display setting options.
7. Use the Up and Down arrow keys to make changes.
8. Press the Enter key to accept the changes.
9. Press the ESC key twice to return to Liebert iCOM’s user menu.
Vertiv | Liebert® XDC™ User Manual | 66
Page 67
Figure 6.5 Display setup screen

6.5 Changing Operational Settings

Changes to the Liebert XDC’s operation settings in the Set Alarms and Setpoints menus require a password. The User Menu password is 1490. The Service Menu password is 5010.
1. From the home screen, press the Enter key to view the User Menu (see 6.7 on the next page).
2. Press Enter again to highlight the first icon.
3. Use the keyboard’s arrow keys to move to the icon for the data you wish to change.
4. Once that icon is highlighted, press Enter again to open that menu.
If a password is required, see Entering the Password on page65.
5. After entering the password, use the Up and Down arrow keys to scroll to and highlight the operational setting to be changed.
6. Press Enter to highlight the values for that setting.
7. Use the Up and Down arrow keys to change the value.
8. Press Enter to accept the change. (The value will no longer be highlighted.)
9. Press ESC to deselect the operational setting. (The setting will no longer be highlighted.)
10. Press ESC again to move to previous screens.

6.6 Graphical Data Record

The Graphical Data Record charts the average temperature from Sensors A and B, the average dew point from Sensors A and B, the supply refrigerant temperature and the supply refrigerant control point.
The temperature scales can be changed to expand or compress the data.
The time scale also can be altered to any of several selectable values.
Vertiv | Liebert® XDC™ User Manual | 67
Page 68
NOTE: Changing the time scale eliminates all previous graphical data and the unit will begin recording new data.

6.7 Liebert iCOM User Menu Icons and Legend

Table 6.2 Liebert iCOM User Menu Icons Descriptions
item descri ption item descri ption
Setpoints - View and change operational setpoints
Spare Parts List - Contains spare parts available ons ite
Event L og - Lists last 400 events and alarms. View Only
Graphic Data Record - Displays average temperature from Sensors A and B, the average dewpoint from Sensors A andB, the supply refrigerant temperature and the supply refrigerant control point graphs; Data is View Only; Display scale is adjustable
View Network - Shows status of all connected units; View Only
Set Alarms - Allows user to change settings for alarms
Sensor Data - Shows r eadings of sensors; View Only
Active Alarms - Lists all current alarms ; View Only
Display Setup - Change settings for display: language and time
TotalRun Hours - Records the r un time of all components andallows settingof limits on run time; View Only
XDIO - D isplays readings for the individual smar t modules; View Only
Service Contacts - Contains key contact information for service
NOTE: Menu shows icons only; text is explanatory and does not appear on the Liebert iCOM display.
Vertiv | Liebert® XDC™ User Manual | 68
Page 69
Figure 6.6 Liebert XDC User Menu screen

6.8 Liebert iCOM User Menu Screens

User menus report general cooling unit operations and status. User Menu screens employ a coding that begins in “U” and is followed by parameters and information, such as settings. Gaining access to some User Menu screens requires entering a password; the User Menu password is 1490.
Check www.VertivCo.com for the latest Liebert iCOM user manual updates, SL-18835.
Vertiv | Liebert® XDC™ User Manual | 69
Page 70
Figure 6.7 Setpoints, page 1 of 2
Min Room Temperature Setpoint—Sets the minimum room temperature the unit will attempt to maintain. If the temperature falls below this point, unit will raise the refrigerant temperature to reduce the amount of cooling.
The setting is intended to keep the room temperature above the setpoint. Without a proper setpoint, the Liebert XDC can lower the room temperature too much, depending on the room dew point and load. This setpoint will reduce the cooling to keep the room temperature above this desired temperature.
NOTE: This is not a true room temperature setpoint. The Liebert XDC has no heaters; it will try to cool as much as possible. If the Liebert XDC is able to cool the room to this setpoint, it will reduce its cooling action to try to keep the room temperature at or above this setpoint.
The default setting is 60°F (15.6°C). The range is 50-80°F (10-27°C).
For optimal cooling performance, the minimum temperature setpoint should be at least 1-2° below the expected temperature at the remote sensors, which may affect placement of the remote sensors. If the minimum temperature setpoint is set above the typical remote temperature sensor reading, it will reduce the Liebert XD cooling output and, in extreme cases, cause erratic Liebert XD performance.
Spare Parts
Spare Parts—The spare parts lists contains a detailed description and part number that can be used to
order parts for the unit. These part numbers are specific to each model and option installed on the unit.
Event Log
Event Log—The event log displays all events and actions that have been generated by the unit. When multiple units are networked you will see the event log of the whole system. Each event shows the unit that generated the alarm, time and date stamp, a description and the event type.
Vertiv | Liebert® XDC™ User Manual | 70
Page 71
Figure 6.8 Set alarms
High Room Air Temperature—Sets the threshold where a high room temperature alarm will occur, based on the actual reading from either remote Sensor A or B. The range for the high room air temperature alarm is 33.8-95°F (1-35°C); the default is 80.0°F (26.7°C).
Low Room Air Temperature—Sets the threshold where a low room temperature alarm will occur, based on the actual reading from either remote Sensor A or B. The range for the high room air temperature alarm is from 33.8 to 95°F (1 to 35°C); the default is 55.0°F (12.8°C).
High Room Dewpoint—Sets the threshold where a high room dew point alarm will occur, based on the calculated values from either remote Sensor A or remote Sensor B. The range for the high room dew point alarm is from 33.8 to 95°F (1 to 35°C); the default is 65°F (18.3°C).
High Refrigerant Temperature—Sets the threshold where a high refrigerant temperature alarm will occur based on the actual reading from the supply refrigerant sensor. The supply refrigerant temperature is from the Liebert XDC to the modules. The range for the high supply refrigerant temperature alarm is from
33.8 to 95°F (1 to 35°C); the default is 80°F (26.7°C).
Vertiv | Liebert® XDC™ User Manual | 71
Page 72
Figure 6.9 Sensor data, page 1 of 2
Sensor A Temperature—Displays the temperature of the remote CAN Temp Humidity sensor designated at Sensor A.
Sensor A Humidity—Displays the humidity of the remote CAN Temp Humidity sensor designated at Sensor A.
Sensor A Dew Point—Displays the dew point of the remote CAN Temp Humidity sensor designated at Sensor A.
Sensor B Temperature—Displays the temperature of the remote CAN Temp Humidity sensor designated at Sensor B.
Sensor B Humidity—Displays the humidity of the remote CAN Temp Humidity sensor designated at Sensor B.
Sensor B Dew Point—Displays the dew point of the remote CAN Temp Humidity sensor designated at Sensor B.
Supply Refrigerant Temperature—Displays the actual supply refrigerant temperature from the Liebert XDC to the modules.
Vertiv | Liebert® XDC™ User Manual | 72
Page 73
Figure 6.10 Sensor data, page 2 of 2
Daily High Temperature—Shows the highest temperature in a rolling 24 hour period for either remote Sensor A or remote Sensor B.
Daily Low Temperature—Shows the lowest temperature in a rolling 24 hour period for either remote Sensor A or remote Sensor B.
Daily High Humidity—Shows the highest humidity in a rolling 24 hour period for either remote Sensor A or remote Sensor B.
Daily Low Humidity—Shows the lowest humidity in a rolling 24 period for either remote Sensor A or remote Sensor B.
Daily High Dewpoint—Shows the highest dew point in a rolling 24 hour period for either remote Sensor A or remote Sensor B.
Daily Low Dewpoint—Shows the lowest dew point in a 24 hour period for either remote Sensor A or remote Sensor B.
Daily High Refrigerant Temperature—Shows the highest supply refrigerant temperature in a rolling 24 hour period from the Liebert XDC to the modules
Daily Low Refrigerant Temperature—Shows the lowest supply refrigerant temperature in a rolling 24 hour period from the Liebert XDC to the modules.
Vertiv | Liebert® XDC™ User Manual | 73
Page 74
Figure 6.11 Display setup
Language—Sets the language on the display. Changing this setting changes all menu parameters to the selected language.
Date—Sets the internal date of the unit. If this unit is connected to other units with the unit-to-unit network connection, each unit will reflect the last date set.
Time—Sets the internal time of the unit. If this unit is connected to other units with the unit-to-unit network connection each unit will reflect the last time set.
Temperature Indication—Selects the actual and setpoint temperature scale. Selecting C will set the unit to display in Celsius and F will set the unit to display in Fahrenheit.
Display Contrast—Changes the contrast of the display to adjust for different viewing angles, low light and bright light conditions. As the display ages, the contrast may require adjustment for viewing.
Buzzer Frequency—Changes the audible noise frequency of the built-in buzzer. The buzzer will sound when its frequency is being adjusted, easing selection of a frequency easily detected when an alarm occurs.
Backlite Off After—Controls how long the backlight remains active when the display is unused. When the buttons on the front display have not been pressed for the time selected in this parameter, the backlight will turn Off, extending the life of the display and saving energy.
Screen—Controls the screen layout. The Liebert XDC has one view, Unit View.
Display Colors—Selects the background color. Inverted sets the display to show white font with blue
background and Normal sets a white background with blue font.
Date Format—Date format changes the month, day and year arrangement shown on the front display and on event time stamps.
Vertiv | Liebert® XDC™ User Manual | 74
Page 75
Figure 6.12 Module status, page 1 of 20
Module Node ID—The location within the CANbus. Each module’s ID is factory-set to 80 and is automatically changed during setup; requires no user action.
Module Labels—A four-character label consisting of two letters and two numerals. This is the standard nomenclature for Data Center Grid assignment of racks. Additionally, the module’s location can be denoted with 10 characters, either letters or non-alphanumeric characters from a built-in list. Either or both labels can be used and are entered using the Module Setup found in the Service menu (S910).
Module Status—Indicates whether the smart module is connected to the CANbus.
U901—Module Node ID/Label/Status.
U902: Refrigerant Temperature—The temperature of the refrigerant entering the Liebert XD smart
module.
Vertiv | Liebert® XDC™ User Manual | 75
Page 76
Figure 6.13 Liebert XDV smart module
U908—Displays the temperature of the air leaving the right and left fan of the Liebert XDV.
U905—Displays the temperature of the air entering the Liebert XDV.
U911—Displays the module type and calculated local module capacity; possible module types are
XDV8SK, XDV8SS, XDV8ST, XDV10SK, XDV10SS and XDV10ST.
U912—Displays the left fan status; possible values are ON and OFF.
U913—Displays the right fan status; possible values are ON, OFF and ON ECON. ON ECON indicates that
only one fan is On.
Figure 6.14 Liebert XDH smart module—each bank shown separately
U905—Displays the temperature of the air leaving the Liebert XDH.
Vertiv | Liebert® XDC™ User Manual | 76
Page 77
U904—Displays the temperature of the air entering the top of the bank of the Liebert XDH.
U907—Displays the temperature of the air entering the bottom of the bank of the Liebert XDH.
U911—Displays the module type and calculated local module capacity; possible module types are
XDH20SK, XDH20SS, XDH32SK and XDH32SS.
U912—Displays the middle fan status; possible values are ON and OFF.
U913—Displays the top and bottom fans’ status; possible values are ON, OFF and ON ECON. (ON ECON
indicates that two fans have been turned On.)
Figure 6.15 Liebert XDO smart module
U907—Displays the temperature of the air entering from the right and left of the Liebert XDO.
U910—Displays the temperature of the air leaving the Liebert XDO.
U911—Displays the module type and calculated local module capacity; possible module types XDO16SK,
XDO16SS and XDO20SS.
U912—Displays the fan status; possible values are ON and OFF.
Vertiv | Liebert® XDC™ User Manual | 77
Page 78
Figure 6.16 Total run hours
Each parameter shows a component, the hours that component has operated and the maximum time the component can operate before the next maintenance.
U502—Pump 1
U503—Pump 2
U504—Compressor 1A
U505—Compressor 1B
U506—Compressor 2A
U507—Compressor 2B
Vertiv | Liebert® XDC™ User Manual | 78
Page 79

6.9 Liebert iCOM Service Menu Icons and Legend

Table 6.3 Liebert iCOM Service Menu Icons Descriptions
Icon descrip ti on i con description
Setpoints - View and change operational setpoints
Unit Diary - Shows all program changes and maintenance performed,
Maintenance/Wellness Settings - Shows all maintenance records, calculates next maintenance date
Diagnostics/Service Mode - Enter Diagnostics/Service Mode for troubleshootingand repair
Set Alarms - Change settings for alarms
Sensor Calibration/Setup- Set up and calibrate sensors for site
Network - Set up or alter network s etting
Options Setup - Enter specific settings for various options
Smar t Module - Setup of alarms and events. S et temperature limits for s upply and return sensors. Label smart modules, view firmwar e version
Service Contacts - Contains key contact information for service
NOTE: Menu shows icons only; text is explanatory and does not appear on the Liebert iCOM display.
Vertiv | Liebert® XDC™ User Manual | 79
Page 80
Figure 6.17 Liebert XDC Service Menu screen

6.10 Liebert iCOM Service Menu Screens

Service menus allow customized settings for site operations. Service Menu screens employ a coding that begins in “S” and is followed by parameters and information, such as settings. Gaining access to most Service Menus requires entering a password; the Service Menu password is 5010; see Entering the
Password on page65 for assistance.
The Liebert iCOM control firmware is being updated constantly. As a result, the Service Menu parameters in this manual may be slightly different than what is shown on a cooling unit’s display. Check www.VertivCo.com for the latest Liebert iCOM User manual updates.
Vertiv | Liebert® XDC™ User Manual | 80
Page 81
Figure 6.18 Setpoints
Min Room Temperature Setpoint—Sets the minimum room temperature the unit will attempt to maintain. If the temperature falls below this point, unit will raise the refrigerant temperature to reduce the amount of cooling. Adjustable from 50 to 80°F (10.0 to 26.7°C), the factory default setting is 60°F (15.6°C).
Temperature Control Type—Selects the type of control the system will use to activate cooling. The Liebert iCOM control has three temperature control types: Proportional, PI and Intelligent.
Proportional—If Proportional Control is selected, the percent cooling requirement is determined by the difference between the air temperature sensor reading and the temperature setpoint. As the air temperature rises above the temperature setpoint, the percent cooling required increases proportionally (from 0 to 100%) over half the programmable temperature proportional band. The percent heating requirement (0 to 100%) is determined the same way when the air temperature falls below the setpoint.
PI—If PI Control is selected, the percent cooling requirement is calculated by adding together two individual terms, proportional and integral. The proportional term is calculated in a manner similar to the previously described Proportional control. The integral term (sometimes called reset action) is calculated by measuring how much and for how long the air temperature has been above or below the setpoint. If the actual air temperature is above the setpoint, the percent requirement is slowly but continuously increased until the total is sufficient to bring the return room air back to the setpoint.
Intelligent—If Intelligent Control is selected, the air temperature is controlled at or near the setpoint. The percent temperature adjustment required is calculated based on logic that is programmed into the control. These rules simulate the actions that would be taken by a human operator manually controlling the system.
Vertiv | Liebert® XDC™ User Manual | 81
Page 82
Temperature Proportional Band—Adjusts the activation points of compressors or rate of change based on the actual sensor values deviation from setpoint. The smaller this number the faster the compressors and valve(s) will increase capacity. Too small of a number may cause the unit to short cycle the compressors or excessively reposition the valve. This parameter is adjustable from 1.8to54.0°F (1.0 to
30.0°C). The factory default setting is 7.0°F (3.9°C).
Temperature Integration Time—Temperature integration takes into consideration the amount of time the actual temperature has deviated from the setpoint. The larger this deviation is the longer the unit will wait before corrective action is taken to achieve the setpoint. This parameter is adjustable from 0 to 15 minutes. The factory default is 0.
Temperature Derivative Time—Monitors the rate of change and will reduce or increase the amount of corrective action based on the actual temperature increasing or decreasing toward the temperature setpoint. This parameter is adjustable from 0-900 seconds. The factory default is 0.
Dewpoint Margin—Selects the difference between the room dew point and the refrigerant temperature control point. This parameter is adjustable from 4.0 to 10.0°F (2.2 to 6.0°C). The factory default setting is
4.0°F (2.2°C).
Minimum Control Point—Sets the minimum supply refrigerant temperature the Liebert XDC will maintain. This parameter is adjustable from 10 to 80°F (5.0 to 27.0°C). The factory default is 55°F (12.8°C).
Min Percent Cooling Setpoint—Selects the lowest percent call for cooling during normal operations. Whenever the unit is not in startup mode or OFF, the percent call for cooling cannot go below this value. The parameter is adjustable from 5 to 30%. The factory default is 5%.
Figure 6.19 Maintenance
Maintenance Frequency Per Year—Sets the number of expected maintenance visits in a one year time span.
Max Bonus—Increases the time until the next required maintenance. A bonus should be assigned when a service visit finds that all components are working optimally.
Vertiv | Liebert® XDC™ User Manual | 82
Page 83
Max Penalty—Decreases the time until the next maintenance cycle. A penalty should be used when a service visit finds excessive wear on components.
Last Maintenance—Date set during the service call. It also indicates to other service personnel the date of the last visit.
Service Engineer—Provides a label for the service representative to list either the company name or representative’s name.
Confirm PM—Confirms that the service representative has completed the preventive maintenance and resets the next maintenance date.
Calculated Next Maintenance—Provides a date to for the next expected maintenance based on the last preventive maintenance performed (Confirm PM), component starts, run hours and the penalty or bonus set in the Liebert iCOM control.
Figure 6.20 Pump 1 settings, page 2 of 7
Number of Starts—Shows the number of starts for the unit’s Pump 1.
Run Hours—Shows the number of run hours for the unit’s Pump 1.
Average Run Time—Shows the average run time of the unit’s Pump 1.
Starts per Day Best—Displays the lowest number of starts in a rolling 24 hour period for Pump 1
Starts per Day Worst—Displays the highest number of starts in a rolling 24 hour period for Pump 1
Number of Alarms—Displays the number of alarms that have occurred with the unit’s Pump 1
Actual Bonus—Displays the actual calculation of wellness for the unit’s Pump 1. The unit will always take
the value from the worst component for the next maintenance indication.
Vertiv | Liebert® XDC™ User Manual | 83
Page 84
Figure 6.21 Pump 2 settings, page 3 of 7
Number of Starts—Displays the number of starts for the unit’s Pump 2.
Run Hours—Displays the number of run hours for the unit’s Pump 2.
Average Run Time—Displays the average run time of the unit’s Pump 2.
Starts per Day Best—Displays the lowest number of starts in a rolling 24 hour period for Pump 2
Starts per Day Worst—Displays the highest number of starts in a rolling 24 hour period for Pump 2
Number of Alarms—Displays the number of alarms that have occurred with the unit’s Pump 2
Actual Bonus—Displays the actual calculation of wellness for the unit’s Pump 2. The unit will always take
the value from the worst component for the next maintenance indication.
Vertiv | Liebert® XDC™ User Manual | 84
Page 85
Figure 6.22 Compressor 1A settings
Number of Starts—Displays the number of starts for the unit’s Compressor 1A.
Run Hours—Displays the number of run hours for the unit’s Compressor 1A.
Average Run Time—Displays the average run time of the unit’s Compressor 1A.
Starts per Day Best—Displays the lowest number of starts in a rolling 24 hour period for Compressor 1A.
Starts per Day Worst—Displays the highest number of starts in a rolling 24 hour period for Compressor 1A.
Number of HP Alarms—Displays the number of high pressure alarms that have occurred with the unit’s
Compressor 1A.
Number of LP Alarms—Displays the number of low pressure alarms that have occurred with the unit’s Compressor 1A.
Actual Bonus—Displays the actual calculation of wellness for the unit’s Compressor 1A. The unit will always take the value from the worst component for the next maintenance indication.
Vertiv | Liebert® XDC™ User Manual | 85
Page 86
Figure 6.23 Compressor 1B settings
Number of Starts—Displays the number of starts for the unit’s Compressor 1B.
Run Hours—Displays the number of run hours for the unit’s Compressor 1B.
Average Run Time—Displays the average run time of the unit’s Compressor 1B.
Starts per Day Best—Displays the lowest number of starts in a rolling 24 hour period for Compressor 1B.
Starts per Day Worst—Displays the highest number of starts in a rolling 24 hour period for Compressor 1B.
Number of HP Alarms—Displays the number of high pressure alarms that have occurred with the unit’s
Compressor 1B.
Number of LP Alarms—Displays the number of low pressure alarms that have occurred with the unit’s Compressor 1B.
Actual Bonus—Displays the actual calculation of wellness for the unit’s Compressor 1B. The unit will always take the value from the worst component for the next maintenance indication.
Vertiv | Liebert® XDC™ User Manual | 86
Page 87
Figure 6.24 Compressor 2A settings
Number of Starts—Displays the number of starts for the unit’s Compressor 2A.
Run Hours—Displays the number of run hours for the unit’s Compressor 2A.
Average Run Time—Displays the average run time of the unit’s Compressor 2A.
Starts per Day Best—Displays the lowest number of starts in a rolling 24 hour period for Compressor 2A.
Starts per Day Worst—Displays the highest number of starts in a rolling 24 hour period for Compressor
2A.
Number of HP Alarms—Displays the number of high pressure alarms that have occurred with the unit’s Compressor 2A.
Number of LP Alarms—Displays the number of low pressure alarms that have occurred with the unit’s Compressor 2A.
Actual Bonus—Displays the actual calculation of wellness for the unit’s Compressor 2A. The unit will always take the value from the worst component for the next maintenance indication.
Vertiv | Liebert® XDC™ User Manual | 87
Page 88
Figure 6.25 Compressor 2B settings
Number of Starts—Displays the number of starts for the unit’s Compressor 2B.
Run Hours—Displays the number of run hours for the unit’s Compressor 2B.
Average Run Time—Displays the average run time of the unit’s Compressor 2B.
Starts per Day Best—Displays the lowest number of starts in a rolling 24 hour period for Compressor 2B.
Starts per Day Worst—Displays the highest number of starts in a rolling 24 hour period for Compressor 2B.
Number of HP Alarms—Displays the number of high pressure alarms that have occurred with the unit’s
Compressor 2B.
Number of LP Alarms—Displays the number of low pressure alarms that have occurred with the unit’s Compressor 2B.
Actual Bonus—Displays the actual calculation of wellness for the unit’s Compressor 2B. The unit will always take the value from the worst component for the next maintenance indication.
Vertiv | Liebert® XDC™ User Manual | 88
Page 89
Figure 6.26 Diagnostics/Service mode, page 1 of 6
HP 1A Alarm Code—Compressor 1A high-pressure alarm code. Values can be 0, 2, 4 or 5. 0 indicates no alarms or the alarm counter has been reset. 2 indicates the high-pressure input has been continuously activated for 30 seconds. 4 indicates there have been four high-pressure situations within 10 minutes. 5 indicates there have been three high-pressure instances within a rolling 12-hour period.
HP 1B Alarm Code—Compressor 1B high pressure alarm code. Values can be 0, 2, 4 or 5. 0 indicates no alarms or the alarm counter has been reset. 2 indicates the high pressure input has been continuously activate for 30 seconds. 4 indicates there have been four high pressure situations within 10 minutes. 5 indicates there have been three high-pressure instances within a rolling 12-hour period.
HP 2A Alarm Code—Compressor 2A high pressure alarm code. Values can be 0, 2, 4, or 5. 0 indicates no alarms or the alarm counter has been reset. 2 indicates the high pressure input has been continuously activate for 30 seconds. 4 indicates there have been four high pressure situations within 10 minutes. 5 indicates there have been three high-pressure instances within a rolling 12-hour period.
HP 2B Alarm Code—Compressor 2B high-pressure alarm code. Values can be 0, 2, 4 or 5. 0 indicates no alarms or the alarm counter has been reset. 2 indicates the high-pressure input has been continuously activate for 30 seconds. 4 indicates there have been four high-pressure situations within 10 minutes. 5 indicates there have been three high-pressure instances within a rolling 12-hour period.
Tandem Bank 1 LP Code—Compressor Circuit 1 low-pressure alarm code. Values can be 0, 1 or 3. 0 indicates no alarms. 1 indicates upon startup of a tandem bank of compressors pressure was not established for the compressors to be able to continue to run. 3 indicates that after operating normally, the low-pressure switch opened and the tandem bank of compressors was unable to establish pressure.
Tandem Bank 2 LP Code—Compressor Circuit 2 low pressure alarm code. Values can be 0,1 or 3. 0 indicates no alarms. 1 indicates upon startup of a tandem bank of compressors pressure was not established for the compressors to be able to continue to run. 3 indicates that after operating normally the low-pressure switch opened and the tandem bank of compressors was unable to establish pressure.
Vertiv | Liebert® XDC™ User Manual | 89
Page 90
Pumpdown Alarms—If a compressor is unable to pump down the circuit within one minute, the liquid line solenoid valve will be toggled ON, then OFF. This is done because the liquid line solenoid valve could be stuck and this could fix it. If, after another minute, the compressor is unable to pump down the circuit, the liquid line solenoid valve will be toggled again. This will continue until either the compressor is able to pump down the circuit or the liquid line solenoid valve is toggled three times. If, after three times of toggling the liquid line solenoid valve and waiting 1 minute, the compressor is still unable to pump down the circuit, the compressor will be turned Off, a pump down failure alarm will be activated for that circuit and the Pump Down Alarm Code for that tandem compressor bank will be set to 1.
There is a re-pump down if the Low Pressure Switch closes again after the compressor has been pumped down; six re-pump down cycles per hour are allowed. At the seventh request of a re-pump-down, the compressor will not be started to re-pump down the circuit again, a pump down failure alarm is activated for that circuit and the Pump Down Alarm Code for that tandem compressor bank is set to 2.
Tandem Bank 1 PD Alarm Code—Compressor Circuit 1 is pump down alarm code; possible values are 0, 1 and 2.
Tandem Bank 2 PD Alarm Code—Compressor Circuit 2 is pump down alarm code; possible values are 0, 1 and 2.
Figure 6.27 Diagnostics/Service mode, page 2 of 6
Manual Mode—Used to place the Liebert iCOM control in manual mode. This is the initial setting necessary to activate any of the following items. When the Liebert iCOM is not in manual mode, each service menu item shows the current status of each parameter.
Pump 1—Used to start the unit’s Pump 1.
Pump 2—Used to start the unit’s Pump 2.
3P Actuator Input Request—A service tool to view the % call for cooling.
Vertiv | Liebert® XDC™ User Manual | 90
Page 91
Figure 6.28 Diagnostics/Service mode, page 3 of 6
Tandem Bank 1LLSV—Controls the liquid line solenoid valve for Compressor Circuit 1. Valves are ON or OFF.
Tandem Bank 2LLSV—Controls the liquid line solenoid valve for Compressor Circuit 2. Valves are ON or OFF.
Compressor 1A—Turns on Compressor 1A and selects the mode of compressor operation. The operation selections are RUN and EVACUATE.
Compressor 1B—Turns on Compressor 1B and selects the mode of compressor operation. The operation selections are RUN and EVACUATE.
Compressor 2A—Turns on Compressor 2A and selects the mode of compressor operation. The operation selections are RUN and EVACUATE.
Compressor 2B—Turns on Compressor 2B and selects the mode of compressor operation. The operation selections are RUN and EVACUATE.
Hot Gas Valve 1 On/Off—Turns on the hot gas solenoid valve for Compressor Circuit 1.
Hot Gas Valve 1 Analog—Sets the hot gas valve % open for Compressor Circuit 1.
Hot Gas Valve 2 On/Off—Turns on the hot gas solenoid valve for Compressor Circuit 2.
Hot Gas Valve 2 Analog—Sets the hot gas valve % open for Compressor Circuit 2.
Vertiv | Liebert® XDC™ User Manual | 91
Page 92
Figure 6.29 Diagnostics/Service mode, page 4 of 6
Tandem Bank 1 Mode—A settable parameter via the service Diagnostics/Service menu. When set to Run, this parameter will allow the user to turn On or Off any single or multiple digital output or set any single or multiple analog output to a specific output setting.
Tandem Bank 2 Mode—A settable parameter via the service Diagnostics / Service menu. When this parameter is set to Run, the control will allow the user to turn ON / OFF any single or multiple digital output or set any single or multiple analog output to a specific output setting.
Manual Mode Control Type—Not currently used.
Manual Deviation—Not currently used.
Analog Output Ramp 1—Sets the value of Analog Output 1 value as a percentage. The factory default for
the Liebert XDC is the hot gas valve 1.
Analog Output Ramp 2—Sets the value of Analog Output 2 value as a percentage. The factory default for the Liebert XDC is the Call for Cooling.
Analog Output Ramp 3—Sets the value of Analog Output 3 value as a percentage. The factory default for the Liebert XDC is the hot gas valve 2.
Analog Output Ramp 4—Sets the value of Analog Output 4 value as a percentage. The factory default for the Liebert XDC is the refrigerant temperature.
Alarm Relay—Used to activate the Liebert iCOM control's common alarm relay output.
Warning Relay—Used to activate the Liebert iCOM control's warning relay output.
Vertiv | Liebert® XDC™ User Manual | 92
Page 93
Figure 6.30 Diagnostics/Service mode, page 5 of 6
Status Remote Shutdown—Displays the status of the unit’s remote shutdown input.
Status Fan Failure—Displays the status of the dry contact to communicate fan failure at a module. (The
dry contacts are not used to communicate a fan failure alarm when using CANbus.)
Status Diff Press Switch 1—Displays the status of the differential pressure switch.
Status Customer Input 1—Displays the status of the customer input 1 alarm.
Status Condensation Detect—Displays the status of the dry contact to communicate condensate
detection at a module.
Status Unit Ready—Shows unit status when a secondary device, such as a fire detection system, is employed.
Vertiv | Liebert® XDC™ User Manual | 93
Page 94
Figure 6.31 Diagnostics/Service mode, page 6 of 6
Status HP1A—Shows the status of the unit’s Compressor 1A high pressure switch input.
Status HP1B—Shows the status of the unit’s Compressor 1B high pressure switch input.
Status HP2A—Shows the status of the unit’s Compressor 2A high pressure switch input.
Status HP2B—Shows the status of the unit’s Compressor 2B high pressure switch input.
Status LP1—Shows the status of the unit’s Compressor Circuit 1 low pressure switch input.
Status LP2—Shows the status of the unit’s Compressor Circuit 2 low pressure switch input.
Figure 6.32 Set alarms, page 1 of 7
Vertiv | Liebert® XDC™ User Manual | 94
Page 95
High Room Air Temperature—Sets the threshold for a high room air temperature alarm. The range for the high room air temperature alarm is from 33.8 to 95°F (1 to 35°C); the default is 80°F(26.7°C).
Low Room Air Temperature—Sets the threshold for a low room air temperature alarm. The range for the low room air temperature alarm is from 33.8 to 95°F (1 to 35°C); the default is 55°F (12.8°C).
High Room Dewpoint—Sets the threshold for a return high dew point alarm. The range for the high room dewpoint alarm is from 33.8 to 95°F (1 to 35°C); the default is 65°F (18.3°C).
High Refrigerant Temperature—Sets the threshold for a high a refrigerant temperature alarm. The range for the high supply refrigerant temperaturealarm is from 33.8 to 95°F (1 to 35°C); the default is 80°F (26.7°C).
Figure 6.33 Set alarms, page 2 of 7
Customer Input 1—Selects the device and operation of the customer input. Each event reflects a different alarm and possible action to the unit. Selectable options are:
Comp Lock PD—This parameter will lockout and pump down the compressor
Call Service
C-Input
Water
Smoke
Customer Input 1 active when—Selects whether the input is normally closed or normally open.
WARNING ACTIVATES ALARM RELAY—Sets the alarm relay (K3) to activate when a warning occurs.
Reset Disabled Alarms—Resets disabled events.
Vertiv | Liebert® XDC™ User Manual | 95
Page 96
Set Alarm Screens, Pages 3-7
The Set Alarm Screens, pages 3 through 7 (Figure 6.34 below throughFigure 6.38 on page100) permit setting the operation of an active alarm. Each event can be enabled or disabled and can be set to operate as an alarm, warning or message. The delay is the time the control waits before reporting the event.
Alarm: Annunciates the buzzer, triggers a monitoring event, triggers the alarm relay and flashes
the red LED on the display
Warning: Annunciates the buzzer, triggers a monitoring event, shows the event in the event viewer / front display and flashes the red LED on the display.
Message: Shows the event in the event viewer and on the front display.
Figure 6.34 Set alarms, page 3 of 7
High Temp Sensor A—Enables or disables the High Temperature Sensor A event, which occurs when the reading from Sensor A is above the user-specified alarm setpoint. Sets how the event is reported: as an alarm, a warning or a message. Specifies how long the control waits before reporting the event.
Low Temp Sensor A—Enables or disables the Low Temperature Sensor A event, which occurs when the reading from Sensor A is below the user-specified alarm setpoint. Sets how the event is reported: as an alarm, a warning or a message. Specifies how long the control waits before reporting the event.
High Temp Sensor B—Enables or disables the High Temperature Sensor B event, which occurs when the reading from Sensor B is above the user-specified alarm setpoint. Sets how the event is reported as an alarm, a warning or a message. Specifies how long the control waits before reporting the event.
Low Temp Sensor B—Enables or disables the Low Temperature Sensor B event, which occurs when the reading from Sensor B is below the user-specified alarm setpoint. Sets how the event is reported: as an alarm, a warning or a message. Specifies how long the control waits before reporting the event.
Vertiv | Liebert® XDC™ User Manual | 96
Page 97
High Dewpoint—Enables or disables the High Dewpoint event, which occurs when the calculated dewpoint at Sensor A or Sensor B is above the user-specified alarm setpoint. Sets how the event is reported: as an alarm, a warning or a message. Specifies how long the control waits before reporting the event.
Sensor A Failure—Enables or disables the Sensor A Failure event, which occurs when the control no longer senses a signal from Sensor A. Sets how the event is reported: as an alarm, a warning or a message. Specifies how long the control waits before reporting the event.
Sensor B Failure—Enables or disables the Sensor B Failure event, which occurs when the control no longer senses a signal from Sensor B. Sets how the event is reported: as an alarm, a warning or a message. Specifies how long the control waits before reporting the event.
Figure 6.35 Set alarms, page 4 of 7
High Refrigerant Temp—Enables or disables the High Refrigerant Temp event, which occurs when the reading from supply refrigerant temperature sensor is above the user-specified alarm setpoint. Sets how the event is reported: as an alarm, a warning or a message. Specifies how long the control waits before reporting the event.
Low Refrigerant Temp—Enables or disables the Low Refrigerant Temp event, which occurs when the reading from supply refrigerant temperature sensor is below the user-specified alarm setpoint. Sets how the event is reported: as an alarm, a warning or a message. Specifies how long the control waits before reporting the event.
Supply Refrigerant Sensor—Enables or disables the Supply Refrigerant Sensor event, which occurs when the control no longer senses a signal from the Supply Refrigerant Sensor. Sets how the event is reported: as an alarm, a warning or a message. Specifies how long the control waits before reporting the event.
Loss of Flow Pump 1—Enables or disables the Loss of Flow Pump 1 event, which occurs when Pump 1 is commanded to run and the differential pressure switch does not sense differential pressure. Sets how the event is reported: as an alarm, a warning or a message. Specifies how long the control waits before reporting the event.
Vertiv | Liebert® XDC™ User Manual | 97
Page 98
Loss of Flow Pump 2—Enables or disables the Loss of Flow Pump 2 event, which occurs when Pump 2 is commanded to run and the differential pressure switch does not sense differential pressure. Sets how the event is reported: as an alarm, a warning or a message. Specifies how long the control waits before reporting the event.
Pump Short Cycle—Enables or disables the Pump Short Cycle event, which occurs when flow is not established by either pump for 30 minutes. Sets how the event is reported: as an alarm, a warning or a message. Specifies how long the control waits before reporting the event.
Compressor(s) Lockout—Enables or disables the Compressor(s) Lockout event, which occurs when the Customer Input 1 is configured for “Comp Lock PD” and 24VAC is applied to the input. Sets how the event is reported: as an alarm, a warning or a message. Specifies how long the control waits before reporting the event.
Figure 6.36 Set alarms, page 5 of 7
Comp 1A High Pressure—Enables or disables the Comp 1A High Pressure event, which occurs when the controls senses a high-pressure signal from Compressor 1 A. Sets how the event is reported: as an alarm, a warning or a message. Specifies how long the control waits before reporting the event.
Comp 1A Short Cycle—Enables the Comp 1A Short Cycle event, which occurs when Compressor 1A turns On, Off, then back On 10 times within 1 hour. Sets how the event is reported: as an alarm, a warning or a message. Specifies how long the control waits before reporting the event.
Comp 1B High Pressure—Enables or disables the Comp 1B High Pressure event, which occurs when the controls senses a high-pressure signal from Compressor 1 B. Sets how the event is reported: as an alarm, a warning or a message. Specifies how long the control waits before reporting the event.
Comp 1B Short Cycle—Enables or disables the Comp 1B Short Cycle event, which occurs when Compressor 1B turns On, Off, then back On 10 times within 1 hour. Sets how the event is reported: as an alarm, a warning or a message. Specifies how long the control waits before reporting the event.
Vertiv | Liebert® XDC™ User Manual | 98
Page 99
Tandem 1 Low Pressure—Enables or disables the Tandem 1 Low Pressure event, which occurs when the low-pressure switch for Tandem Compressor Bank 1 does not send the proper signal during normal operation or during pump-down. Sets how the event is reported: as an alarm, a warning or a message. Specifies how long the control waits before reporting the event.
Tandem 1 Pumpdown Fail—Enables or disables the Tandem 1 Pumdown event, which occurs when the Tandem Compressor Bank 1 suction pressure cannot be pumped down below the threshold during compressor shutdown. Sets how the event is reported: as an alarm, a warning or a message. Specifies how long the control waits before reporting the event.
Figure 6.37 Set alarms, page 6 of 7
Comp 2A High Pressure—Enables or disables the Comp 2A High Pressure event, which occurs when the controls senses a high-pressure signal from Compressor 2A. Sets how the event is reported: as an alarm, a warning or a message. Specifies how long the control waits before reporting the event.
Comp 2A Short Cycle—Enables or disables the Comp 1B Short Cycle event, which occurs when Compressor 1B turns On, Off, then back On 10 times within 1 hour. Sets how the event is reported: as an alarm, a warning or a message. Specifies how long the control waits before reporting the event.
Comp 2B High Pressure—Enables or disables the Comp 2B High Pressure event, which occurs when the controls senses a high-pressure signal from Compressor 2B. Sets how the event is reported: as an alarm, a warning or a message. Specifies how long the control waits before reporting the event.
Comp 2B Short Cycle—Enables or disables the Comp 2B Short Cycle event, which occurs when Compressor 2B turns On, Off, then back On 10 times within 1 hour. Sets how the event is reported: as an alarm, a warning or a message. Specifies how long the control waits before reporting the event.
Tandem 2 Low Pressure—Enables or disables the Tandem 2 Low Pressure event, which occurs when the low-pressure switch for Tandem Compressor Bank 2 does not send the proper signal during normal operation or during pump-down. Sets how the event is reported: as an alarm, a warning or a message. Specifies how long the control waits before reporting the event.
Vertiv | Liebert® XDC™ User Manual | 99
Page 100
Tandem 2 Pumpdown Fail—Enables or disables the Tandem 2 Pumdown event, which occurs when the Tandem Compressor Bank 2 suction pressure cannot be pumped down below the threshold during compressor shutdown. Sets how the event is reported: as an alarm, a warning or a message. Specifies how long the control waits before reporting the event.
Figure 6.38 Set alarms, page 7 of 7
Condensation Detection—Enables or disables the Condensation Detected event, which occurs when water is detected at the Liebert XD cooling module. Sets how the event is reported: as an alarm, a warning or a message. Specifies how long the control waits before reporting the event.
Fan Failure—Enables or disables the Fan Failure event, which occurs when a fan failure occurs at the Liebert XD cooling module. Sets how the event is reported: as an alarm, a warning or a message. Specifies how long the control waits before reporting the event.
Customer Input 1—Enable or disables the Customer Input 1 event, which occurs when 24VAC is applied to the input. Sets how the event is reported: as an alarm, a warning or a message. Specifies how long the control waits before reporting the event.
Smoke Detected—Enable or disables the Smoke Detected event, which occurs when the Customer Input 1 is configured for “Smoke Detected” and 24VAC is applied to the input. Sets how the event is reported: as an alarm, a warning or a message. Specifies how long the control waits before reporting the event.
Water Under Floor—Enable or disables the Water Under Floor event, which occurs when the Customer Input 1 is configured for “Water Under Floor” and 24VAC is applied to the input. Sets how the event is reported: as an alarm, a warning or a message. Specifies how long the control waits before reporting the event.
Unit X disconnected—Not currently used.
Working Hours Exceeded—Enables or disables the Working Hrs Exceeded event, which occurs when a
component has exceeded the user-specified limit. Sets how the event is reported: as an alarm, a warning or a message. Specifies how long the control waits before reporting the event.
Vertiv | Liebert® XDC™ User Manual | 100
Loading...