WARNING:
FIRE OR EXPLOSION HAZARD
Failure to follow safety warnings exactly
could result in serious injury, death or
property damage.
• Do not store or use gasoline or other
ammable vapors and liquids in the
vicinity of this or any other appliance.
• WHAT TO DO IF YOU SMELL GAS
– Do not try to light any appliance.
– Do not touch any electrical switch; do
not use any phone in your building.
– Leave the building immediately.
– Immediately call your gas supplier from
a neighbor's phone. Follow the gas
supplier's instructions.
– If you cannot reach your gas supplier,
call the re department.
• Installation and service must be performed
by a qualied installer, service agency or
the gas supplier.
WARNING: Improper installation, adjustment,
alteration, service or maintenance can cause
injury or property damage. Refer to this manual.
For assistance or additional information consult
a qualified installer, service agency or the
gas supplier.
This appliance may be installed in an aftermarket,*
permanently located, manufactured home (USA
only) or mobile home, where not prohibited by
local codes.
This appliance is for use only with the type of gas
indicated on the rating plate. This appliance is
not convertible for use with other gases, unless
a certied kit is used.
* Aftermarket: Completion of sale, not for purpose of resale, from
the manufacturer.
CERTIFIED
AFETYBARRIER
DANGER
HOT GLASS WILL
CAUSE BURNS.
DO NOT TOUCH GLASS
UNTIL COOLED.
NEVER ALLOW CHILDREN
TO TOUCH GLASS.
A barrier designed to reduce the risk of burns from
the hot viewing glass is provided with this
appliance and shall be installed.
INSTALLER: Leave this manual with the appliance.
CONSUMER: Retain this manual for
future reference.
20306760 12/14 Rev. 1
Stardance® Direct Vent/Natural Vent Gas Heater
Table of Contents
PLEASE READ THE INSTALLATION & OPERATING INSTRUCTIONS BEFORE USING APPLIANCE.
Thank you and congratulations on your purchase of a Vermont Castings stove.
IMPORTANT: Read all instructions and warnings carefully before starting installation. Failure to follow these
instructions may result in a possible re hazard and will void the warranty.
Installation & Operating Instructions
General Information .........................................................3
Requirements for Massachusetts .....................................4
The Stardance Direct Vent/Natural Vent Room Heater, Model
Nos. SDDVTCB, SDDVTEB, SDDVTBS, SDDVTBD, SDDVTBM,
SDDVTCSCB, SDDVTCSEB, SDDVTCSBS, SDDVTCSBD, SDDVTCSBM is a vented gas appliance listed to the ANSI Standard
Z21.88-2009 and CSA 2.33-2009 for Vented Room Heaters, and
CSA 2.17-M91, Gas-Fired Appliances For Use at High Altitudes.
The installation of the Stardance Direct Vent/Natural Vent Room
Heater must conform with local codes, or in the absence of local codes, with National Fuel Gas Code, ANSI Z223.1/NFPA 54
— latest edition and CSA B-149.1 Installation Code. (EXCEPTION: Do not derate this appliance for altitude. Maintain the
manifold pressure at 3.5” w.c. for Natural Gas and 10.0” w.c. for
LP gas at maximum input.)
This appliance is only for use with the type of gas indicated on
the rating plate. This appliance is not convertible for use with
other gases unless a certied kit is used.
Installation and replacement of gas piping, gas utilization
equipment or accessories, and repair and servicing of
equipment shall be performed only by a qualied agency,
preferably NFI or WETT (Canada) certied. The term “qualied agency” means any individual, rm, corporation, or
company that either in person or through a representative
is engaged in and is responsible for (a) installation or replacement of gas piping, or (b), the connection, installation,
repair, or servicing of equipment, who is experienced in
such work, familiar with all precautions required, and has
complied with all the requirements of the authority having
jurisdiction.
The Stardance Direct Vent/Natural Vent Room Heater should
be inspected before use and at least annually by a qualied
service agency. It is imperative that control compartments,
burners, and circulating air passageways of the appliance
be kept clean.
The Stardance Direct Vent/Natural Vent Room Heater and its
individual shut-off valve must be disconnected from the gas supply piping during any pressure testing of that system at test pressures in excess of 1/2 psig (3.5 kPa).
The Stardance Direct Vent/Natural Vent Room Heater must be
isolated from the gas supply piping system by closing its individual manual shutoff valve during any pressure testing of the
gas supply piping system at test pressures equal to or less than
1/2 psig.
‘Direct Vent’ describes a sealed combustion system in which incoming outside air for combustion and outgoing exhaust enter
and exit through two separate concentric passages within the
same sealed vent system. The system does not use room air to
support combustion. The Direct Vent system permits the gas appliance to be vented directly to the outside atmosphere through
the side of the house or vertically through the roof. Conventional
venting systems (Natural Vent) take air from the room for combustion and vent the exhaust vertically through the roof to the
atmosphere.
This appliance is approved for bedroom installations in the U.S.
and Canada.
This appliance may be installed in an aftermarket* manufactured
(mobile) home, where not prohibited by state or local codes.
WARNING: Operation of this heater when not connected to a
properly installed and maintained venting system can result
in carbon monoxide (CO) poisoning and possible death.
Stardance® Direct Vent/Natural Vent Gas Heater
The Stardance Direct Vent/Natural Vent Room Heater, when installed, must be electrically grounded in accordance with local
codes or, in the absence of local codes, with the National Electrical Code ANSI/NFPA 70, (latest edition), or of the current Canadian Electrical Code C22.1.
Due to high temperatures this appliance should be located
out of trafc and away from furniture and draperies.
WARNING: This appliance is hot while in operation. Keep
children, clothing, and furniture away. Contact may cause
burns or ignition of combustible materials.
Children and adults should be alerted to the hazards of high
surface temperatures and should stay away to avoid burns
or clothing ignition.
Young children should be carefully supervised when they
are in the same room as the appliance. Toddlers, young children and others may be susceptible to accidental contact
burns. A physical barrier is recommended if there are at risk
individuals in the house. To restrict access to a replace
or stove, install an adjustable safety gate to keep toddlers,
young children and other at risk individuals out of the room
and away from hot surfaces.
Clothing or other ammable materials should not be placed
on or near the appliance.
Any safety screen, glass or guard removed for servicing
an appliance must be replaced prior to operating the appli-
ance.
The appliance area must be kept clear and free from combustible materials, gasoline, and other ammable vapors
and liquids.
The ow of combustion and ventilation air must not be obstructed. The installation must include adequate accessibility and clearance for servicing and proper operation.
WARNING: Do not operate the Room Heater with the glass
panel removed, cracked or broken. Replacement of the panel should be done by a licensed or qualied service person.
Do not use this appliance if any part has been under water.
Immediately call a qualied service technician to inspect the
appliance and to replace any part of the control system and
any gas control which has been under water.
Do not burn wood, trash or any other material for which this
appliance was not designed. This appliance is designed to
burn either natural gas or propane only.
This gas appliance must not be connected to a chimney ue
serving a separate solid-fuel burning appliance.
CAUTION: Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dan-
gerous operation.
Verify proper operation after servicing.
* Aftermarket: Completion of sale, nor for purpose of resale, from the
manufacturer.
Proposition 65 Warning: Fuels used in gas, woodburning or
oil red appliances, and the products of combustion of such
fuels, contain chemicals known to the State of California to
cause cancer, birth defects and other reproductive harm.
California Health & Safety Code Sec. 25249.6
20306760
3
Stardance® Direct Vent/Natural Vent Gas Heater
Installation Requirements
Requirements for the Commonwealth of
Massachusetts
All gas tting and installation of this heater shall only be
done by a licensed gas tter or licensed plumber.
For all side wall horizontally vented gas fueled equipment
installed in every dwelling, building or structure used in
whole or in part for residential purposes, including those
owned or operated by the Commonwealth and where
the side wall exhaust vent termination is less than seven
(7) feet above nished grade in the area of the venting,
including but not limited to decks and porches, the following
requirements shall be satised:
Installation of Carbon Monoxide Detectors
At the time of installation of the side wall horizontal vented
gas fueled equipment, the installing plumber or gas tter
shall observe that a hard wired carbon monoxide detector
with an alarm is installed on each additional level of the
dwelling, building or structure served by the side wall
horizontal vented gas fueled equipment. It shall be the
responsibility of the property owner to secure the services
of qualied licensed professionals for the installation of
hard wired carbon monoxide detectors.
In the event that the side wall horizontally vented gas fueled
equipment is installed in a crawl space or an attic, the hard
wired carbon monoxide detector with alarm and battery
back-up may be installed on the next adjacent oor level.
In the event that the requirements of this subdivision can
not be met at the time of completion of installation, the
owner shall have a period of thirty (30) days to comply with
the above requirements; provided, however, that during
said thirty (30) day period, a battery operated carbon
monoxide detector with an alarm shall be installed.
Approved Carbon Monoxide Detectors
Each carbon monoxide detector as required in accordance
with the above provisions shall comply with NFPA 720 and
ANSI/UL 2034 listed and IAS certied.
Signage
A metal or plastic identication plate shall be permanently
mounted to the exterior of the building at a minimum
height of eight (8) feet above grade directly in line with
the exhaust vent terminal for the horizontally vented gas
fueled heating appliance or equipment. The sign shall
read, in print size no less than one-half (1/2) inch in size,
“GAS VENT DIRECTLY BELOW, KEEP CLEAR OF ALL
OBSTRUCTIONS”.
Inspection
The state or local gas inspector of the side wall horizontally
vented gas fueled equipment shall not approve the
installation unless, upon inspection, the inspector observes
carbon monoxide detectors and signage installed in
accordance with the provisions of 248 CMR 5.08(2)(a)1
through 4.
Exemptions
The following equipment is exempt from 248 CMR
5.08(2)(a)1 through 4:
• The equipment listed in Chapter 10 entitled “Equipment
Not Required To Be Vented” in the most current edition
of NFPA 54 as adopted by the Board; and
• Product Approved side wall horizontally vented gas
fueled equipment installed in a room or structure
separate from the dwelling, building or structure used
in whole or in part for residential purposes.
MANUFACTURER REQUIREMENTS
Gas Equipment Venting System Provided
When the manufacturer of Product Approved side wall
horizontally vented gas equipment provides a venting
system design or venting system components with the
equipment, the instructions provided by the manufacturer
for installation of the equipment and the venting system
shall include:
• Detailed instructions for the installation of the venting
system design or the venting system components;
and
• A complete parts list for the venting system design or
venting system.
Gas Equipment Venting System NOT Provided
When the manufacturer of a Product Approved side wall
horizontally vented gas fueled equipment does not provide
the parts for venting the ue gases, but identies “special
venting systems”, the following requirements shall be
satised by the manufacturer:
• The referenced “special venting system” instructions
shall be included with the appliance or equipment
installation instructions; and
• The “special venting systems” shall be Product
Approved by the Board, and the instructions for that
system shall include a parts list and detailed installation
instructions.
A copy of all installation instructions for all Product
Approved side wall horizontally vented gas fueled
equipment, all venting instructions, all parts lists for venting
instructions, and/or all venting design instructions shall
remain with the appliance or equipment at the completion
of the installation.
4
20306760
7" Outer Dia.
7" Outer Dia.
Stardance® Direct Vent/Natural Vent Gas Heater
Stardance Direct Vent / Natural Vent Dimensions
Flue Collar
(73 mm)
C
L
2⁷⁄₈”
12⁵⁄₈”
(321 mm)
SDDVT Models
25¹⁄₂"
(648 mm)
(178 mm)
8³⁄₄"
(222 mm)
Supply Inlet
9"
(229 mm)
26³⁄₄"
(680 mm)
C
L
C
L
2⁷⁄₈”
(73 mm)
C
L
Flue Collar
3"
(76 mm)
12⁵⁄₈”
(321 mm)
SDDVTC Models
14¹⁄₂"
(355 mm)
(178 mm)
7³⁄₄”
(197 mm)
Supply Inlet
Supply Inlet
8"
(203 mm)
Figure 1 Stardance dimensions.
Attention
The Stardance stove is shipped from the factory as a Direct Vent Gas Heater. This heater
may be converted into a Natural Vent unit in the eld. If a Natural Vent heater is desired,
the Vermont Castings Z31B00 FSDHAG Draft Hood must be directly installed to the top of
the unit according to the installation instructions. The Draft Hood Adapter is available in
the 7FSDHASK stove kit or as a separate item.
When the Stardance stove is converted to Natural Vent, it uses 4” vent pipe. For aesthetic
purposes the Vermont Castings Group direct vent system may be used up to the ceiling.
20306760
5
A
B
E
C
D
Stardance® Direct Vent/Natural Vent Gas Heater
Installation Requirements
The installation must conform with local codes or, in the
absence of local codes, with the National Fuel Gas Code,
ANSI Z223.1/NFPA 54 - latest edition. (EXCEPTION: Do
not derate this appliance for altitude. Maintain the manifold pressure at 3.5 inches w.c. for Natural Gas, and 10
inches w.c. for Propane).
In Canada, installation must be in accordance with the current CSA B-149.1 Installation Codes and/or local codes.
The installation should be done by a qualied service
person who is familiar with the building codes and
installation techniques appropriate for your area to
accomplish a safe and effective installation.
Your dealer or your local gas supplier will be able to
refer a qualied service person.
WARNING: Due to high temperatures, the
HEATER should be located out of trafc and
away from furniture and draperies.
The surface of the Heater Is hot when it is in use.
Young children should be watched carefully when
they are in the same room when the Heater is in use,
and they should be taught to avoid the hot surface.
Keep any objects that can burn well away from the
Heater, and observe the recommended clearances
that follow.
DANGER
ST207
Figure 2 Possible stove locations.
Clearance Requirements
Minimum Clearances to Combustible
Materials
Measure side clearances as shown in Figures 3 and 4
from the outer edge of the cast iron stove top. Measure
rear clearances from the outermost surface of the steel
rear skirt.
The Stardance heater is approved for installation into an
alcove constructed of combustible materials to the dimensions and clearances shown on the next page.
The same clearances apply in a standard parallel installation.
HOT GLASS WILL
CAUSE BURNS.
DO NOT TOUCH GLASS
UNTIL COOLED.
NEVER ALLOW CHILDREN
TO TOUCH GLASS.
A barrier designed to reduce the risk of burns from
the hot viewing glass is provided with this
appliance and shall be installed.
Locating the Stove
In choosing a location for the stove, consider:
• The location of outside walls;
• Where additional heat is needed:
• Where family members gather most often;
• The vent system requirements.
NOTE: We do not recommend the use of wallpaper next
to this stove. Over time, radiant heat may cause the wallpaper to shrink, or may adversely affect the binders in the
wallpaper adhesive.
6
Warning:
• Always maintain required clearances (air
spaces) to nearby combustibles to prevent
re hazard. Do not ll air spaces with insula-
tion. All venting components must maintain a
1” (25 mm) clearance to combustible materials.
Maintain a 6” (150 mm) clearance when using a
single wall pipe.
• The gas appliance and vent system must be
vented directly to the outside of the building and
never be attached to a chimney serving a separate solid fuel or gas-burning appliance. Each
direct vent appliance must use its own separate
vent system. Common vents are prohibited.
• Refer to the manufacturer’s instructions included with the venting system for complete installation procedures.
The installation of your Vermont Castings stove must
conform with local codes, or in the absence of local
codes, with the National Fuel Gas Code ANSI Z223.1/
NFPA 54 - latest edition, or CSA B149.1 Installation
code. (EXCEPTION: Do not derate this appliance for
altitude up to 4,500 feet (1,370m). Maintain the manifold pressure at 3.5” w.c. for Natural Gas and 10.0” w.c.
for LP Gas.
Input ratings are shown in BTU per hour and are cer-
tied without deration for elevations up to 4,500 feet
(1,370m) above sea level.
For elevations above 4,500 feet (1,370m) in USA, installations must be in accordance with the current ANSI
Z223.1/NFPA 54 and/or local codes having jurisdiction.
In Canada, please consult provincial and/or local authorities having jurisdiction for installations at elevations
above 4,500 feet (1,370m).
WARNING: Improper installation, adjustment, alteration, service or maintenance can cause injury or
property damage. Refer to this manual for correct
installation and operational procedures. For assistance or additional information consult a qualied
installer, service agency, or the gas supplier.
8
High Elevations
Horizontal Termination -
Direct Vent ONLY
The vent must rise vertically a minimum of 24” (610 mm)
off the top of the unit, before the rst elbow. The horizontal
run may extend up to 20’ (6 m) and include a vertical rise
of up to 40’ (12 m). (Figure 7) Horizontal termination must
also meet the criteria shown in Figures 9 through 11.
• Approved vent systems must terminate above and including the heavy line in Figure 7.
• Two 45° elbows may be substituted for each single 90°
elbow.
• With a rise between 2’ - 5’, one 90° or two 45° elbows
may be used.
May use up to
three 90° Elbows
One 90°
Elbow
Figure 7 Horizontal vent termination window.
Unacceptable
Venting Congureation
ST134a
20306760
20
Horizontal Run (in feet)
40
ST132bFDV28Vertical vent run1/08
Stardance® Direct Vent/Natural Vent Gas Heater
Vertical Termination - Direct Vent ONLY
A vertical vent system must terminate no less than 8’
(2.44 m) and no more than 40’ (12 m) above the appli-
ance ue collar. A restrictor plate (supplied) must be used
where specied in all vertically terminated vent systems.
(Figure 8) NOTE: The restrictor plate supplied with
the vertical termination should be discarded. Adjust
the restrictor plate according to recommendations in
Figure 10. A vertically terminated vent system must also
conform to the following criteria:
• No more than three 90° elbows may be used.
• Two 45° elbows may be substituted for one 90° elbow.
No more than six elbows may be used.
• Vent must rise a minimum of 2 feet before offset is
used.
• Termination height must conform to roof clearance as
specied in Figure 9.
39
38
37
All Vertical Termina-
36
tions in this area
35
Require use of the
34
Restrictor Plate*
33
32
31
30
29
28
27
26
25
Vertical Terminations
24
must be within this
23
Plate
area
Unacceptable Venting
Conguration
22
21
Vertical Run (in feet)
20
19
18
16
(Measure from the appliance flue collar to the top of the vent pipe.)
15
14
13
12
11
10
9
8
7
No Restrictor
6
5
4
3
2
1
0
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19
ST132b
The Stardance stove is shipped with a restrictor plate in
the Parts Bag. Adjustments can be made by loosening the
adjustment screw to allow the restrictor plate to slide up or
down. (Figure 9) A guide for usage is shown in Figure 10.
NOTE: Some installations may require some adjustment
by the installer for optimum ame appearance. Optimum
ame appearance is a ame that is not subject to tall, dirty
yellow ames producing soot or ames lifting off of the
ember bed ports.
Restrictor Plate Adjustment
1. Remove the logs if installed.
2. Remove the adjustment screw in the back wall of the
rebox.
3. Install restrictor plate as shown in Figure 9 with angle
on plate on the top right side. Secure with adjustment
screw.
4. Adjust restrictor according to examples in Figure 10.
5. Install logs following log installation instructions.
Figure 9 SDDVT/SDDVTCS restrictor plate.
Examples for Extended Run/Restrictor Plate Settings
1. Vertical 40’ (12 m) - restrictor plate lowered completely
2. Vertical 20’ (6 m), 90° elbow, 8’ (2.4 m ) horizontal -
*The restrictor Plate is used on Direct Vent Installations
Only.
20306760
9
Stardance® Direct Vent/Natural Vent Gas Heater
Vent Termination Clearances
When planning the installation, consider the location of the
vent terminal and clearances. Some of the most common
clearances to keep in mind are shown in Figure 11.
Important: All vent clearances must be maintained.
Check your vent termination clearances against Figures 11 through 13.
The vent should be placed so that people cannot be burned
by accidentally touching the vent surfaces when the stove
is operating.
The vent termination should be located where it cannot be
damaged by such things as automobile doors, lawn mowers or snowblowers and it should be located away from areas where it could become blocked by snow, etc.
Some considerations are:
• Obstructions or impediments to venting.
• Nearby combustible materials that could come into contact with combustion exhaust gases.
• Other nearby openings {within 12” (305 mm)} through
which exhaust gas could reenter the building.
• All vegetation within 3’ (76 mm) that may interfere with
the draft.
Other factors that inuence where the installation will be
sited include the location of outside walls, where additional
heat may be desired in the home, where the family members gather most regularly, and perhaps most importantly,
the distance limitations of the venting system.
Your stove is approved to be vented either through the side
wall, or vertical through the roof.
• Vermont Castings Group does not require any opening
for inspection of vent pipe.
• Only Vermont Castings Group and DuraVent venting
components specically approved and labelled for this
stove may be used.
• Minimum clearances between vent pipes and combustible materials is one (1”) inch (25 mm), except where
stated otherwise.
• Venting terminals shall not be recessed into a wall or
siding.
• Horizontal venting must be installed on a level plane
without an inclining or declining slope.
There must not be any obstruction such as bushes, garden
sheds, fences, decks or utility buildings within 24” from the
front of the termination hood.
Do not locate termination hood where excessive snow or
ice build up may occur. Be sure to check vent termination
area after snow falls, and clear to prevent accidental blockage of venting system. When using snow blowers, make
sure snow is not directed towards vent termination area.
Location of Vent Termination
It is imperative the vent termination be located observing
the minimum clearances as shown on this page.
IMPORTANT
Direct Vent Only
• The horizontal termination must not be recessed into
the exterior wall or siding.
• Horizontal vent runs must be level toward the vent
termination.
• Clearances around the vent termination must be
maintained.
• For installations using DuraVent pipe, parallel installations with minimum wall clearance have restricted
access for connecting the Horizontal Vent Cap straps
to the vent pipe. See the maker’s instructions for recommended installation procedures.
10
20306760
Stardance® Direct Vent/Natural Vent Gas Heater
General Venting Information - Termination Location
INSIDE
CORNER DETAIL
G
V
A
D
E
V
L
B
CFM145a
C
V
F
V
B
Fixed
Closed
Operable
B
V
Operable
B
B
V
Fixed
Closed
V
A
B
X
J
H
M
I
N
X
K
V
VENT TERMINATION AIR SUPPLY INLET
V
X
Canadian Installations1 US Installations
AREA WHERE TERMINAL IS NOT PERMITTED
2
A = Clearance above grade, veranda, porch, 12” (30cm) 12” (30cm)
deck, or balcony
B = Clearance to window or door that may be 6” (15cm) for appliances 6” (15cm) for appliances
opened < 10,000Btuh (3kW), 12” (30cm) < 10,000 Btuh (3kW), 9”
for appliances > 10,000 Btuh (3kW) and (23cm) for appliances > 10,000
< 100,000 Btuh (30kW), 36” (91cm) Btuh (3kW) and < 50,000 Btuh
for appliances > 100,000 Btuh (30kW) (15kW), 12” (30cm) for
appliances > 50,000 Btuh (15kW)
C = Clearance to permanently closed window 12” (305mm) recommended to 12” (305mm) recommended to
prevent window condensation prevent window condensation
D = Vertical clearance to ventilated soft located
above the terminal within a horizontal 18” (458mm) 18” (458mm)
distance of 2’ (610mm) from the center
line of the terminal
E = Clearance to unventilated soft 12” (305mm) 12” (305mm)
F = Clearance to outside corner see next page see next page
G = Clearance to inside corner (see next page) see next page see next page
H = Clearance to each inside of center line 3’ (91cm) within a height of 15’ (5m) 3’ (91cm) within a height of 15’
extended above meter/regulator assembly above the meter/regulator assembly (5m) above the meter/regulator
assy
I = Clearance to service regulator vent outlet 3’ (91cm) 3’ (91cm)
J = Clearance to nonmechanical air supply inlet 6” (15cm) for appliances < 10,000 6” (15cm) for appliances
to building or the combustion air inlet to any Btuh (3kW), 12” (30cm) for < 10,000 Btuh (3kW), 9”
other appliances appliances > 10,000 Btuh (3kW) and (23cm) for appliances > 10,000
< 100,000 Btuh (30kW), 36” (91cm) Btuh (3kW) and < 50,000 Btuh
for appliances > 100,000 Btuh (30kW) (15kW), 12” (30cm) for
appliances > 50,000 Btuh (15kW)
K = Clearance to a mechanical air supply inlet 6’ (1.83m) 3’ (91cm) above if within 10
feet (3m) horizontally
L = Clearance above paved sidewalk or paved 7’ (2.13m)† 7’ (2.13m)†
driveway located on public property
M = Clearance under veranda, porch, deck or 12” (30cm)* 12” (30cm)*
balcony
N = Any other obstruction within a horizontal distance of 18” (450mm).
1 In accordance with the current CSA-B149 Installation Codes
2 In accordance with the current ANSI Z223.1/NFPA 54 National Fuel Gas Codes
† A vent shall not terminate directly above a sidewalk or paved driveway which is located between two single family dwellings and serves both dwellings
* only permitted if veranda, porch, deck or balcony is fully open on a minimum 2 sides beneath the oor:
NOTE: 1. Local codes or regulations may require different clearances.
2. The special venting system used on Direct Vent units are certied as part of the appliance, with clearances tested and
approved by the listing agency.
3. Vermont Castings Group assumes no responsibility for the improper performance of the appliance when the venting system
does not meet these requirements.
Figure 11 Vent termination clearances.
20306760
11
Termination Clearances
Stardance® Direct Vent/Natural Vent Gas Heater
Termination clearances for buildings with combustible and noncombustible exteriors.
Inside Corner
G =
G
Combustible
6" (152 mm)
Noncombustible
V
2" (51 mm)
Balcony -
with no side wall
M
V
M =
Combustible &
Noncombustible
12" (305 mm)
*NOTE: Termination in an alcove space (spaces open only on one side and with an overhang) is permitted with the dimensions
specied for vinyl or non-vinyl siding and softs. 1. There must be a 3’ (914 mm) minimum between termination caps. 2. All
mechanical air intakes within 10’ (1 m) of a termination cap must be a minimum of 3’ (914 mm) below the termination cap. 3. All
gravity air intakes within 3’ (914 mm) of a termination cap must be a minimum of 1’ (305 mm) below the termination cap.
Figure 12 Termination clearances.
Outside Corner
F =
Combustible
6" (152 mm)
V
Noncombustible
2" (51 mm)
F
Balcony -
with perpendicular side wall
M
V
P
Combustible &
Noncombustible
M = 12" (305 mm)
P = 6” (152 mm)
Alcove Applications*
D
C
O
C
V
E
E = Min. 2” (51 mm) for
non-vinyl sidewalls
Min. 12” (305 mm) for
vinyl sidewalls
O = 8’ (2.4 m) Min.
No.
of Caps D
1 3’ (914 mm) 2 x D
2 6’ (1.8 m) 1 x D
3 9’ (2.7 m) 2/3 x D
4 12’ (3.7 m) 1/2 x D
NOTE: When venting staight vertical, without any
elbow, a minimum of 8 ft. vertical is required
off the top of the stove.
= Acceptable venting configuration
= Unacceptable venting configuration
A: Vertical installations up to 36 feet (12m) in
height. Up to an 18 ft. horizontal vent run can be
installed within the vent system using a
maximum of two 90-degree elbows or four
45-degree elbows.
B: Vertical installations up to 36 feet (12m) in
height. Up to a 24 ft. horizontal vent run can be
installed within the vent system using a
maximum of two 45-degree elbows.
(Ratio = 2/3, Hor./Vert.)
NOTE: When using the FSDHAG, the restrictor plate
supplied with the stove is not used.
20306760
Stardance® Direct Vent/Natural Vent Gas Heater
Venting Requirements and Options -
Direct Vent ONLY
Approved Vent System Components
The Stardance Heater must be vented to the outdoors
through an adjacent exterior wall or through the roof. The
venting system must be comprised of the appropriate
listed venting components specied on this page. These
parts are available from DuraVent Corporation, Selkirk
Corporation or your Vermont Castings Dealer.
See Figure 4 for dimensions relevant to the standard minimum-vent kits.
All DuraVent Straight vent pipe sections have a net length
11⁄2” (37mm) less than the nominal dimension; i.e., a 6”
(152mm) Straight pipe section has an effective length of
41⁄2” (115mm).
Selkirk Corporation Vent Components
www.selkirkcorp.com
1301 W. President George Bush Highway Ste. 330
Richardson, TX 75080
Phone: 1-800-992-8368, Fax: 1-877-393-4145
NOTE: Direct vent pipe may be used on the Natural Vent
system from the top of the draft hood adapter to the ceiling.
13
Stardance® Direct Vent/Natural Vent Gas Heater
Vermont Castings Group Vent Components
The following kits are available to meet the needs of most
installations. All pipe has a 7” outer diameter and includes
a 4” diameter inner section. A (CG) designation indicates
the part is nished in Charcoal Gray paint. Consult your
dealer about other vent parts that may be appropriate to
complete the installation.
NOTE: Direct vent pipe may be used on the Natural Vent
system from the top of the draft hood adapter to the ceiling.
20306760
Stardance® Direct Vent/Natural Vent Gas Heater
Install the Optional Fan - SDDVT Series
If you are installing the optional convection Fan Kit #2767
(FK26), continue here. If you are not installing a Fan Kit,
go to Page 16, Venting System Assembly.
1. The fan kit includes a Blower Assembly and a Rheo-
stat Assembly, connected by a cable. (Figure 14) The
Blower Assembly mounts to the bottom rear of the
stove, and the Rheostat mounts to the valve bracket to the left of the valve. The assembly includes a
‘snapstat’ which automatically turns the fan On (or Off)
above (or below) approximately 109°. The Rheostat
also provides a range of fan speed settings from Off
(which overrides the snapstat function) to High. Un-
pack and inspect the Blower assembly. Conrm the
WARNING
This appliance is equipped with a three-prong (grounded) plug for your protection against shock hazard and
should be plugged directly into a properly grounded
three-prong receptacle. Do not cut or remove the
grounding prong from this plug.
Snapstat
Bracket
Snapstat/
Not Used on
Stardance
Extension
Assembly
Rheostat
Assembly
installed)
• Insert the rheostat through the hole in the back of
the left side of the valve bracket, aligning the locator
pin with the smaller hole in that bracket.
• Thread the retaining nut onto the shaft of the rheo-
stat, tightening with a wrench. Do not overtighten.
• Attach the control knob to the rheostat shaft.
• Use the wire tie to secure the fan and rheostat wire
harnesses together.
Rear Skirt
Sheet Metal
Screws
Rear Skirt
Insert
Figure 15 Remove rear skirt insert.
Star Washer
Sheet Metal Screws
2
Phillips
Pan Head
Bolts
1
ST313
Snapstat
1/4” - 20
Hex Bolt
Blower
Assembly
ST473a
Figure 14 Fan kit components.
fan spins freely.
2. Remove the rear skirt insert panel at the bottom of the
Rear Skirt (Figure 15) and fasten the blower assembly
to the rebox back with the two Phillips pan-head bolts
originally installed in the rebox back. (‘1’, Figure 16)
3. Attach the snapstat assembly to the snapstat brack-
et with two sheet-metal screws. (‘2’, Figure 16) Attach
the snapstat bracket to the stove with a hex-head bolt
passing through the bracket and into the stove base.
(‘3’, Figure 16)
4. The rheostat control switch attaches to the left side of
the valve bracket at the front of the stove. (Figure 17)
• Remove retaining nut from shaft of rheostat. (if pre-
Star
Washer
3
NOTE: Shown
without shell for
clarication
Figure 16 Attach the fan assembly and the snapstat.
Rheostat Retaining
Collar
Rheostat Knob
Figure 17 Attach the fan rheostat.
Snapstat
Bracket
ST314
ST347a
20306760
15
CEMENT
CEMENT
Stardance® Direct Vent/Natural Vent Gas Heater
Venting System Assemlby - Direct Vent
General Information
The Stardance is approved for installation only with the
vent components listed on Pages 13 & 14. Follow the vent
component instructions exactly.
For U.S. installations: The venting system must conform
with local codes and/or the current National Fuel Gas
Code, ANSI Z223.1/NFPA 54.
For Canadian installations: The venting system must
conform to the current CSA B149.1 installation code.
Install the Vent Adapter Pipe
(Vermont Castings Group Vent Components)
1. Attach Inner Starter Pipe, (found in the parts bag),
to the next section of inner pipe.
• Run a bead of sealant about 1/2” from the upper
end of the Inner starter pipe and join the two sections
together.
• Drill three pilot holes into the Inner Starter and secure the assembly with three sheet metal screws. (Figure 18)
First Section of Vent
Pipe
#8 x 1/2” Sheet
Metal Screws
3” Inner
Starter PIpe
ST211
Figure 18 Connect the inner starter with the next section of
inner vent pipe.
2. Dry t the Inner Pipe assembly to the stove for the
purpose of determining the center line of the pipe
on the wall.
• Side Wall Terminations: Dry t the outer elbow with
the vertical outer vent and conrm the centerline align-
ment with the wall thimble opening.
3. Attach the Inner Vent Assembly to the stove.
• Run a bead of sealant around the bottom end of the
starter pipe and attach the assembly to the stove using
three 1/4-20 x 3/8” Phillips screws provided in the parts
bag. (Figure 19)
4. Install the Outer Adapter Pipe. Apply a 1/4” bead of
cement around the inside wall of the pipe, about 1”
from the end. Insert the pipe over the stove ue collar,
keeping the vertical seam oriented to the back of the
stove. Also, be sure to align holes on the pipe with the
holes on the ue collar of the rebox. Fasten the pipe
to the holes in the ue collar with the #12 x 1/2” sheet
metal screws provided. (Figure 20)
ST212a
Figure 19 Attach inner assembly to ue collar.
ST213
Figure 20 Fasten outer pipe with #12 x 1/2” sheet metal screw.
Install the Vent Adapter Pipe
(DuraVent Components)
1. Discard the inner starter pipe shipped with the stove.
Using the starter pipe assembly listed on Page 7, slide
the inner section out to allow access.
• Run a bead of sealant around the bottom end of the
starter pipe and attach the assembly to the stove using
three 1/4-20 x 3/8” Phillips screws provided in the parts
bag. (Figure 21)
2. Install the Outer Adapter Pipe. Apply a 1/4” bead of
cement around the outside surface, about one inch
from the crimped end. (Figure 22) Orient the vertical
seam to the rear, and insert the crimped end of the
outer pipe into the ue collar. Fasten with three sheet
metal screws provided.
16
20306760
Loading...
+ 36 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.