Vermont Castings Radiance RADVTSCBM, Radiance RADVTSCBD, Radiance RADVTCBSB, Radiance RADVTBSSB, Radiance RADVTBDSB Installation And Operating Instructions Manual

...
RADVT Series Radiance® Direct Vent Gas Heater
S
Installation and Operating Instructions
Models: RADVTSCCB, RADVTSCBS, RADVTSCBD, RADVTSCBM,
RADVTCBSB, RADVTBSSB, RADVTBDSB, RADVTBMSB
WARNING: FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly
could result in serious injury, death or property damage.
Do not store or use gasoline or other
ammable vapors and liquids in the
vicinity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS – Do not try to light any appliance.
– Do not touch any electrical switch; do
not use any phone in your building. – Leave the building immediately. – Immediately call your gas supplier from
a neighbor's phone. Follow the gas
supplier's instructions.
– If you cannot reach your gas supplier,
call the re department.
Installation and service must be performed
by a qualied installer, service agency or
the gas supplier.
WARNING: Improper installation, adjustment,
alteration, service or maintenance can cause
injury or property damage. Refer to this manual. For assistance or additional information consult a qualified installer, service agency or the
gas supplier.
This appliance may be installed in an aftermarket,* permanently located, manufactured home (USA only) or mobile home, where not prohibited by local codes.
This appliance is for use only with the type of gas
indicated on the rating plate. This appliance is not convertible for use with other gases, unless a certied kit is used.
* Aftermarket: Completion of sale, not for purpose of resale, from
the manufacturer.
CERTIFIED
AFETY BARRIER
DANGER
HOT GLASS WILL
CAUSE BURNS.
DO NOT TOUCH GLASS
UNTIL COOLED.
NEVER ALLOW CHILDREN
TO TOUCH GLASS.
A barrier designed to reduce the risk of burns from
the hot viewing glass is provided with this
appliance and shall be installed.
INSTALLER: Leave this manual with the appliance.
CONSUMER: Retain this manual for
future reference.
20306759 0416 Rev. 5
CONTENTS
Radiance® Direct Vent Gas Heater
PLEASE READ THE INSTALLATION & OPERATING INSTRUCTIONS BEFORE USING APPLIANCE.
Thank you and congratulations on your purchase of a Vermont Castings stove. IMPORTANT: Read all instructions and
warnings carefully before starting installation. Failure to follow these instructions may result in a possible re hazard
and will void the warranty.
Table of Contents
Important safety information ....................................... 3
Massachusetts Residents Only ......................................... 4
Pre-installation.............................................................. 5
Stove Dimensions ............................................................. 5
Installation Requirements .................................................. 6
Clearance Requirements................................................... 6
Parallel Installation ............................................................ 7
Corner Installation ............................................................. 7
Wall and Ceiling Clearances ............................................. 7
Hearth Requirements ....................................................... 7
Gas Specications............................................................. 8
Gas Inlet and Manifold Pressures ..................................... 8
High Elevations ................................................................. 8
Horizontal Termination ...................................................... 8
Vertical Termination ........................................................... 9
Restrictor Plate Adjustment
for Extended Pipe Runs .................................................... 9
Vent Termination Clearances .......................................... 10
General Venting Information - Termination Location ........11
Termination clearances. .................................................. 12
Assembly and installation ......................................... 13
Venting Requirements and Options................................. 13
Assembling the Stove ..................................................... 14
Install the Optional Fan - RADVT Model (Millivolt only) �� 15
Venting System Assembly ............................................... 16
Before You Start .............................................................. 16
Install the Vent Adapter Pipe ........................................... 17
Assemble Slip Sections ................................................... 18
Secure the Vent Sections ................................................ 18
Disassemble Vent Sections ............................................. 19
Horizontal Termination Cap ............................................. 19
Divert Roof Run-off .......................................................... 20
Vertical Side Wall Installation .......................................... 20
Vent Termination Below Grade ........................................ 21
Vertical Through-The-Roof Application/Installation ......... 22
Install Log Set.................................................................. 24
Install ON/OFF Switch - RADVT Model (Millivolt only) .... 26
Thermostat Connection (optional) ................................... 26
Signature Command® System (SC) ............................... 26
Junction Box Wiring......................................................... 27
Command Center Wall Installation .................................. 27
Wall Switch Installation ................................................... 27
Connect the Gas Supply Line.......................................... 28
Burner Information........................................................... 28
Signature Command Wiring Diagram.............................. 29
Install the Safety Barrier .................................................. 30
Install the Mesh and Grill ................................................. 30
Operating instructions ............................................... 31
Pilot and Burner Inspection ............................................. 31
Flame & Temperature Adjustment ................................... 31
Flame Characteristics...................................................... 31
Lighting and Operating Instructions................................. 32
Troubleshooting ............................................................... 33
Read before lighting ........................................................ 34
Signature command operating instructions ............ 36
Features .......................................................................... 36
Battery installation ........................................................... 36
System conguration/setup ............................................. 36
Operating instructions ............................................... 38
Turning on the stove ........................................................ 38
Command Center Operations ......................................... 38
Initialization and Setting up ............................................. 39
Safety Features ............................................................... 43
Troubleshooting ......................................................... 44
Fuel conversion .......................................................... 46
Cleaning and maintenance ........................................ 51
Annual System Inspection ............................................... 51
Logset and Burner / Cleaning and Inspection ................. 51
Care of Cast Iron ............................................................. 51
Cleaning the Glass .......................................................... 51
Gasket Replacement ....................................................... 52
Inspect the Vent System Annually ................................... 52
Check the Gas Flame Regularly ..................................... 52
Glass Replacement ......................................................... 52
Wiring diagrams ......................................................... 53
Replacement parts ..................................................... 55
Optional accessories ................................................. 58
Limited lifetime warranty .......................................... 59
22 20306759
Radiance® Direct Vent Gas Heater
IMPORTANT SAFETY INFORMATION
The Radiance Direct Vent Room Heater, Model Nos. RAD­VTCBSB, RADVTBSSB, RADVTBDSB, RADVTBMSB, RAD­VTSCCB, RADVTSCBS, RADVTSCBD, RADVTSCBM, is a vented gas appliance listed to the ANSI Standard Z21.88-2014 and CSA 2.33-2014 for Vented Room Heaters, and CSA 2.17­M91, Gas-Fired Appliances For Use at High Altitudes.
The installation of the Radiance Direct Vent Room Heater must conform with local codes, or in the absence of local codes, with National Fuel Gas Code, ANSI Z223.1/NFPA 54 — latest edition and CSA B-149.1 Installation Code. (EXCEPTION: Do not derate this appliance for altitude. Maintain the manifold pressure at 3.5 inches w.c. for Natural Gas and 10 inches w.c. for LP gas at maximum input.)
This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other
gases unless a certied kit is used.
Installation and replacement of gas piping, gas utilization equipment or accessories, and repair and servicing of equip­ment shall be performed only by a qualied agency, prefer­ably NFI or WETT (Canada) certied. The term “qualied agency" means any individual, rm, corporation, or company that either in person or through a representative is engaged in and is responsible for (a) installation or replacement of gas piping, or (b), the connection, installation, repair, or servic­ing of equipment, who is experienced in such work, familiar with all precautions required, and has complied with all the requirements of the authority having jurisdiction.
The Radiance Direct Vent Room Heater should be inspected before use and at least annually by a qualied service agency. It is imperative that control compartments, burners, and circulating air passageways of the appliance be kept clean.
The Radiance Direct Vent Room Heater and its individual shut-off valve must be disconnected from the gas supply piping during any pressure testing of that system at test pressures in excess of 1/2 psig (3.5 kPa).
The Radiance Direct Vent Room Heater must be isolated from the gas supply piping system by closing its individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psig.
An accessible tap is located above the pilot/On-Off knob for checking the inlet pressure.
‘Direct Vent’ describes a sealed combustion system in which incoming outside air for combustion and outgoing exhaust enter and exit through two separate concentric passages within the same sealed vent system. The system does not use room air to support combustion. The Direct Vent system permits the gas appliance to be vented directly to the outside atmosphere through the side of the house or vertically through the roof. Conventional venting systems (Natural Vent) take air from the room for com­bustion and vent the exhaust vertically through the roof to the atmosphere.
This appliance is approved for bedroom installations in the U.S. and Canada.
This appliance may be installed in an aftermarket* manufactured (mobile) home, where not prohibited by state or local codes.
WARNING: Operation of this heater when not connected to a properly installed and maintained venting system can result in carbon monoxide (CO) poisoning and possible death.
The Radiance Direct Vent Room Heater, when installed, must be electrically grounded in accordance with local codes or, in the absence of local codes, with the National Electrical Code ANSI/ NFPA 70, (latest edition), or of the current Canadian Electrical Code C22.1.
Due to high temperatures this appliance should be located out of trafc and away from furniture and draperies.
WARNING: This appliance is hot while in operation. Keep
children, clothing, and furniture away. Contact may cause burns or ignition of combustible materials.
Children and adults should be alerted to the hazards of high surface temperatures and should stay away to avoid burns
or clothing ignition.
Young children should be carefully supervised when they are in the same room as the appliance. Toddlers, young children and others may be susceptible to accidental con­tact burns. A physical barrier is recommended if there are at risk individuals in the house. To restrict access to a stove or stove, install an adjustable safety gate to keep toddlers, young children and other at risk individuals out of the room and away from hot surfaces.
Clothing or other ammable materials should not be placed
on or near the appliance.
Any safety screen, glass or guard removed for servicing an appliance must be replaced prior to operating the appliance.
The appliance area must be kept clear and free from com­bustible materials, gasoline, and other ammable vapors and liquids.
The ow of combustion and ventilation air must not be obstructed. The installation must include adequate acces­sibility and clearance for servicing and proper operation.
WARNING: Do not operate the Room Heater with the glass
panel removed, cracked or broken. Replacement of the panel should be done by a licensed or qualied service person.
Do not use this appliance if any part has been under water. Immediately call a qualied service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water.
Do not burn wood, trash or any other material for which this appliance was not designed. This appliance is designed to burn either natural gas or propane only.
This gas appliance must not be connected to a chimney ue serving a separate solid-fuel burning appliance.
CAUTION: Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation.
Verify proper operation after servicing.
Aftermarket: Completion of sale, nor for purpose of resale,
*
from the manufacturer�
20306759
3
IMPORTANT SAFETY INFORMATION
Radiance® Direct Vent Gas Heater
REQUIREMENTS FOR THE COMMONWEALTH OF MASSACHUSETTS
All gas tting and installation of this heater shall only be done by a licensed gas tter or licensed plumber.
For all side wall horizontally vented gas fueled equipment
installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven
(7) feet above nished grade in the area of the venting,
including but not limited to decks and porches, the following
requirements shall be satised:
Installation of Carbon Monoxide Detectors
At the time of installation of the side wall horizontal vented gas fueled equipment, the installing plumber or gas tter
shall observe that a hard wired carbon monoxide detec­tor with an alarm is installed on each additional level of the dwelling, building or structure served by the side wall
horizontal vented gas fueled equipment. It shall be the
responsibility of the property owner to secure the services
of qualied licensed professionals for the installation of
hard wired carbon monoxide detectors.
In the event that the side wall horizontally vented gas fueled
equipment is installed in a crawl space or an attic, the hard wired carbon monoxide detector with alarm and battery
back-up may be installed on the next adjacent oor level.
In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of thirty (30) days to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery operated carbon mon­oxide detector with an alarm shall be installed.
Approved Carbon Monoxide Detectors
Each carbon monoxide detector as required in accordance with the above provisions shall comply with NFPA 720 and
ANSI/UL 2034 listed and IAS certied.
Signage
A metal or plastic identication plate shall be per­manently mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The sign shall read, in print size no less than one-half (1/2) inch in size, “GAS VENT DIRECTLY BELOW, KEEP CLEAR OF ALL OBSTRUCTIONS".
Inspection
The state or local gas inspector of the side wall horizontally
vented gas fueled equipment shall not approve the installa­tion unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5.08(2)(a)1 through 4.
Exemptions
The following equipment is exempt from 248 CMR 5.08(2) (a)1 through 4:
• The equipment listed in Chapter 10 entitled “Equipment Not Required To Be Vented" in the most current edition of NFPA 54 as adopted by the Board; and
Product Approved side wall horizontally vented gas fu­eled equipment installed in a room or structure separate from the dwelling, building or structure used in whole or in part for residential purposes.
MANUFACTURER REQUIREMENTS
Gas Equipment Venting System Provided
When the manufacturer of Product Approved side wall hor-
izontally vented gas equipment provides a venting system
design or venting system components with the equipment, the instructions provided by the manufacturer for installation of the equipment and the venting system shall include:
• Detailed instructions for the installation of the venting system design or the venting system components; and
• A complete parts list for the venting system design or venting system.
Gas Equipment Venting System NOT Provided
When the manufacturer of a Product Approved side wall
horizontally vented gas fueled equipment does not provide the parts for venting the ue gases, but identies “special
venting systems", the following requirements shall be sat-
ised by the manufacturer:
• The referenced “special venting system" instructions shall be included with the appliance or equipment in­stallation instructions; and
• The “special venting systems" shall be Product Ap­proved by the Board, and the instructions for that sys­tem shall include a parts list and detailed installation instructions.
A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equip­ment, all venting instructions, all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of the installation.
Radiance Direct Vent
Certied to:
ANSI Z21.88-2014 / CSA 2.33-2014
Vented Gas Heaters
44 20306759
Proposition 65 Warning: Fuels used in gas, wood-burning
or oil red appliances, and the products of combustion of
such fuels, contain chemicals known to the State of California to cause cancer, birth defects and other reproductive harm. California Health & Safety Code Sec. 25249.6
Radiance® Direct Vent Gas Heater
29-3/4"
(758 mm)
31"
(787 mm)
7" Outer Dia. (178 mm)
Flue Collar
L
C
4-3/4"
(120 mm)
14-7/8"
(378 mm)
RADIANCE
28"
(711 mm)
5"
(127 mm)
18-1/4"
(464 mm)
Supply
Inlet
PRE-INSTALLATION
RADIANCE DIRECT VENT
Weight: Fully assembled; 350 lbs.
STOVE DIMENSIONS
Fig. 1 Radiance dimensions.
20306759
5
A
B
E
C
D
PRE-INSTALLATION
INSTALLATION REQUIREMENTS
The installation must conform with local codes or, in the absence of local codes, with the National Fuel Gas Code, ANSI Z223.1/NFPA 54 - latest edition. (EXCEPTION: Do not derate this appliance for altitude. Maintain the mani­fold pressure at 3.5" w.c. for Natural Gas, and 10" w.c. for Propane).
In Canada, installation must be in accordance with the current CSA B-149.1 Installation Codes and/or local codes.
The installation should be done by a qualied service
person who is familiar with the building codes and instal­lation techniques appropriate for your area to accomplish a safe and effective installation.
Your dealer or your local gas supplier will be able to refer
a qualied service person.
WARNING
Due to high temperatures, the heater should be located
out of trafc and away from furniture and draperies.
The surface of the Heater Is hot when it is in use. Young children should be watched carefully when they are in the same room when the Heater is in use, and they should be taught to avoid the hot surface. Keep any objects that can burn well away from the Heater, and observe the recommended clearances that follow.
DANGER
Radiance® Direct Vent Gas Heater
Direct Vent System Only
A. Flat on corner wall B. Room Divider C. Island
Fig. 2 Possible stove locations.
D. Cross Corner E. Flat on wall
ST207a
CLEARANCE REQUIREMENTS
Minimum Clearances to Combustible Materials
Measure side clearances as shown in Figures 3, 4 and 5 from the outer edge of the cast iron stove top. Measure rear clearances from the outermost surface of the steel rear skirt.
The Radiance heater is approved for installation into an alcove constructed of combustible materials to the dimen­sions and clearances shown on the next page.
The same clearances apply in a standard parallel instal­lation.
HOT GLASS WILL
CAUSE BURNS.
WARNING
DO NOT TOUCH GLASS
UNTIL COOLED.
NEVER ALLOW CHILDREN
TO TOUCH GLASS.
A barrier designed to reduce the risk of burns from
the hot viewing glass is provided with this
appliance and shall be installed.
In choosing a location for the stove, consider:
• The location of outside walls;
• Where additional heat is needed:
• Where family members gather most often;
• The vent system requirements.
NOTE: We do not recommend the use of wallpaper next to this stove. Over time, radiant heat may cause the wallpaper to shrink, or may adversely affect the binders in the wallpaper adhesive.
66 20306759
• Always maintain required clearances (air spaces) to
nearby combustibles to prevent re hazard. Do not ll air spaces with insulation. All venting components
must maintain a 1" (25 mm) clearance to combus­tible materials. The gas appliance and vent system must be vented directly to the outside of the building and never be attached to a chimney serving a sepa­rate solid fuel or gas-burning appliance.
• Refer to the manufacturer’s instructions included with the venting system for complete installation pro­cedures.
Radiance® Direct Vent Gas Heater
42" (1070mm)
Min. Alcove Width
48"
(1220mm)
Max. Alcove
Depth
6"
(150mm)
6"
(150mm)
4" (102mm)
18"
(457mm)
18"
(457mm)
6"
(150mm)
6"
(150mm)
C
L
C
L
A
A
C
D
B
PRE-INSTALLATION
PARALLEL INSTALLATION
Minimum Clearance and Flue Centerline
ST130
Fig. 3 Parallel installation, minimum back and side clearances, and ue centerlines.
CORNER INSTALLATION
Minimum Clearance and Flue Centerline
Wall Centerline from Floor
Direct Vent Only
ST131b
A Effective Minimum Centerline 57" (1448 mm) (HHT Pipe) 55" (1399 mm) (DuraVent Pipe)
Fig. 5 Minimum wall centerline.
WALL AND CEILING CLEARANCES
Fig. 4 Corner installation, minimum corner clearances and ue
centerline.
ST129
Direct Vent Only
A: Rear Wall 4" (102 mm) B: Min. Clearance 44" (1118 mm)* C: Min. Alcove Height 72" (1830 mm)* D: Max. Alcove Depth 48" (1220 mm) Sidewall Clearance 6" (150 mm)
*needed for installing DuraVent Minimum Vent Kit #2792 or HHT Minimum Vent Kit #SLP-FSSK.
Fig. 6 Dimensions and clearances to ceiling or alcove.
ST101b
HEARTH REQUIREMENTS
The Radiance Heater must be installed on rigid ooring.
When the heater is installed directly on any combustible
surface other than wood ooring, a metal or wood panel
extending the full width and depth of the unit must be used as the hearth. There are no other hearth requirements.
20306759
7
20
19
18
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
Vertical Run (in feet)
(Measured from the appliance flue collar to the top of the vent pipe.)
Horizontal Run (in feet)
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
ST134b Radiance Horizontal vent run 6/07
PRE-INSTALLATION
Radiance® Direct Vent Gas Heater
GAS SPECIFICATIONS
Max.
Input
Model Fuel Control
RADVT Nat.
RADVT LP
RADVTSC Nat.
RADVTSC LP
Millivolt Manual
Millivolt Manual
Signature
Command
Signature
Command
BTU/h
38,000 25,000
36,000 25,000
38,000 25,000
36,000 25,000
GAS INLET AND MANIFOLD PRESSURES
Natural Liquid Propane
Inlet Minimum 5.5" w.c. 11.0" w.c.
Inlet Maximum 14.0" w.c. 14.0" w.c.
Manifold Pressure 3.5" w.c. 10.0" w.c.
The installation of your Vermont Castings stove must conform with local codes, or in the absence of local codes, with the National Fuel Gas Code ANSI Z223.1/ NFPA 54 - latest edition, or CSA B149.1 Installation code. (EXCEPTION: Do not derate this appliance for altitude up to 2,000 (610 m) for natural gas and 4,500 feet (1,370 m) for LP Gas. Maintain the mani­fold pressure at 3.5" w.c. for Natural Gas and 10.0"
w.c. for LP Gas.
HIGH ELEVATIONS Input ratings are shown in BTU per hour and are certied without deration for elevations up to 2,000 feet (610 m) for natural gas and 4,500 feet (1,370 m) for LP gas above sea level.
In the USA installations with elevations above 2,000 feet (610 m) for natural gas and 4,500 feet (1,370 m) for LP gas must be in accordance with the current ANSI Z223.1/NFPA 54 and/or local codes having
jurisdiction.
In Canada, please consult provincial and/or local authorities having jurisdiction for installations at elevations above 2,000 feet (610 m) for natural gas and 4,500 feet (1,370 m) for LP gas.
Improper installation, adjustment, alteration, service or maintenance can cause injury or property damage. Refer to this manual for correct installation and oper­ational procedures. For assistance or additional infor-
mation consult a qualied installer, service agency, or
the gas supplier.
88 20306759
WARNING
Min. Input
BTU/h
HORIZONTAL TERMINATION
The vent must rise vertically a minimum of 24" (610 mm)
off the top of the unit, before the rst elbow. The horizontal
run may extend up to 20’ (6m) and include a vertical rise
of up to 40’ (12 m). (Figure 7) Horizontal termination must
also meet the criteria shown in Figures 10 through 12.
• Approved vent systems must terminate above and in­cluding the heavy line in Figure 7.
• Two 45° elbows may be substituted for each single 90° elbow.
• With a rise between 2’ - 5’, one 90° or two 45° elbows may be used.
May use up to
three 90° Elbows
No Restrictor Plate
Required
One 90°
Elbow
Fig. 7 Horizontal vent termination window.
Unacceptable
Venting Conguration
ST134a
Radiance® Direct Vent Gas Heater
20
19
18
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
20
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19
Vertical Run (in feet)
(Measure from the appliance flue collar to the top of the vent pipe.)
Horizontal Run (in feet)
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
ST132a FDV28 Vertical vent run 12/3/99 djt
PRE-INSTALLATION
VERTICAL TERMINATION
A vertical vent system must terminate no less than 8’ (2.44
m) and no more than 40’ (12 m) above the appliance ue
collar. A restrictor plate (supplied) must be used, where
specied, in all vertically terminated vent systems. (Refer
to Figure 8) NOTE: The restrictor plate supplied with the vertical termination should be discarded. Adjust the restrictor plate according to recommendations in Figure
10. A vertically terminated vent system must also conform to the following criteria:
• No more than three 90° elbows may be used.
• Two 45° elbows may be substituted for one 90° elbow. No more than six 45° elbows may be used.
• Vent must rise a minimum of 2 feet (305 mm) before offset is used.
• Termination height must conform to roof clearance as
specied in Figure 11.
All Vertical Ter-
minations in this
area Require use
of the Restrictor
Plate*
RESTRICTOR PLATE ADJUSTMENT FOR EXTENDED PIPE RUNS
The Radiance stove is shipped with a restrictor plate in the Parts Bag. Adjustments can be made by loosening the adjustment screw to allow the restrictor plate to slide up or down. (Figure 9) A guide for usage is shown in Figure 10.
NOTE: Some installations may require some adjustment
by the installer for optimum ame appearance. Optimum ame appearance is a ame that is not subject to tall, dirty yellow ames producing soot or ames lifting off of the
ember bed ports.
Restrictor Plate Adjustment
Remove the screw in the back wall of the rebox.
• Install restrictor plate as shown in Figure 9 with cut out on left side. Secure with adjustment screw.
• Measure from center of screw to top edge of diverter (Figure 9) to adjust plate according to guidelines in Figure 10.
• Tighten attachment screw.
• Install logs following log installation instructions.
Adjustment Screw
**No Restrictor Plate
Fig. 8 Vertical vent termination window.
20306759
Vertical terminations
must be within this
area
Unacceptable
Venting Conguration
**
ST132a
Fig. 9 Loosen screw to adjust restrictor plate.
Examples for Extended Run/Restrictor Plate Settings
Vertical 20’
(6 m), 90°
elbow, out 8’
(2.4 m)
Vertical 11’
(3.4 m), 90°
elbow, out 2’
(610 mm)
Vertical 40’
(12 m)
Vertical 5’
(1.5 m), 90°
elbow, out 5’
(1.5 m)
Restrictor plate measurement from top of plate to center of screw:
3
4” (70 mm)
2
from center
of screw to
top edge of
plate
Figure 10
Plate down
to top of slot
Plate down
to top of slot
23⁄8” (60 mm)
from center of screw to top edge of
plate
ST917
9
PRE-INSTALLATION
Radiance® Direct Vent Gas Heater
VENT TERMINATION CLEARANCES
When planning the installation, consider the location of the vent terminal and clearances. Some of the most common clearances to keep in mind are shown in Figure 11.
Important: All vent clearances must be maintained. Check your vent termination clearances against Fig­ures 11 and 12.
The vent should be placed so that people cannot be burned by accidentally touching the vent surfaces when the stove is operating.
The vent termination should be located where it cannot be damaged by such things as automobile doors, lawn mowers or snowblowers and it should be located away from areas where it could become blocked by snow, etc.
Some considerations are:
• Obstructions or impediments to venting.
• Nearby combustible materials that could come into con­tact with combustion exhaust gases.
• Other nearby openings {within 12" (305 mm)} through which exhaust gas could reenter the building.
• All vegetation within 3’ (76 mm) that may interfere with the draft.
Other factors that inuence where the installation will be
sited include the location of outside walls, where additional heat may be desired in the home, where the family mem­bers gather most regularly, and perhaps most importantly, the distance limitations of the venting system.
IMPORTANT
The horizontal termination must not be recessed into the exterior wall or siding.
Horizontal vent runs must be level toward the vent
termination.
Clearances around the vent termination must be maintained.
For installations using DuraVent pipe, parallel instal­lations with minimum wall clearance have restricted access for connecting the Horizontal Vent Cap straps to the vent pipe. See the maker’s instructions for rec­ommended installation procedures.
Your stove is approved to be vented either through the side wall, or vertical through the roof.
• HHT does not require any opening for inspection of vent pipe.
• Only HHT SLP venting components or DuraVent vent-
ing components specically approved and labeled for
this stove may be used.
• Minimum clearances between vent pipes and combus­tible materials is one (1") inch (25 mm), except where stated otherwise.
• Venting terminals shall not be recessed into a wall or siding.
Horizontal venting must be installed on a level plane without an inclining or declining slope.
There must not be any obstruction such as bushes, garden sheds, fences, decks or utility buildings within 24" from the front of the termination hood.
Do not locate termination hood where excessive snow or ice build up may occur. Be sure to check vent termination area after snow falls, and clear to prevent accidental block­age of venting system. When using snow blowers, make sure snow is not directed towards vent termination area.
LOCATION OF VENT TERMINATION
It is imperative the vent termination be located observing the minimum clearances as shown in this manual.
1010 20306759
Radiance® Direct Vent Gas Heater
V
X
X
X
D
E
B
B
B
C
B
M
B
A
J
K
F
L
VENT TERMINATION AIR SUPPLY INLET
AREA WHERE TERMINAL IS NOT PERMITTED
H
I
Fixed
Closed
Operable
Operable
Fixed
Closed
B
INSIDE
CORNER DETAIL
A
G
CFM145a
V
V
V
V
V
V
V
V
N
GENERAL VENTING INFORMATION - TERMINATION LOCATION
PRE-INSTALLATION
A = Clearance above grade, veranda, porch, deck
CANADIAN INSTALLATIONS
1
12" (30cm) 12" (30cm)
US INSTALLATIONS
2
or balcony
B = Clearance to window or door that may be
opened
C = Clearance to permanently closed window 12" (305mm) recommended to prevent window
D = Vertical clearance to ventilated soft located
6" (15cm) for appliances <10,000 BTU/h (3kW)
12" (30cm) for appliances >10,000 BTU/h (3kW) and <100,000 BTU/h (30kW)
36" (91cm) for appliances >100,000 BTU/h (30kW)
6" (15cm) for appliances <10,000 BTU/h (3kW)
9" (23cm) for appliances >10,000 BTU/h (3kW) and <50,000 BTU/h (15kW)
12" (30cm) for appliances >50,000 BTU/h (15kW)
12" (305mm) recommended to prevent window
condensation
condensation
18" (458mm) 18" (458mm)
above the terminal within a horizontal distance
of 2' (610 mm) from the center line of the terminal
E = Clearance to unventilated soft 12" (305mm) 12" (305mm)
F = Clearance to outside corner see next page see next page
G = Clearance to inside corner see next page see next page
H = Clearance to each inside of center line
extended above meter/regulator assembly
3' (91cm) within a height of 15' (5m) above the meter/regulator assembly
3' (91cm) within a height of 15' (5m) above the meter/regulator assembly
I = Clearance to service regulator vent outlet 3' (91cm) 3' (91cm)
J = Clearance to non-mechanical air supply inlet
to building or the combustion air inlet to any other appliance
6" (15cm) for appliances <10,000 BTU/h (3kW)
12" (30cm) for appliances >10,000 BTU/h (3kW) and <100,000 BTU/h (30kW)
36" (91cm) for appliances >100,000 BTU/h (30kW)
6" (15cm) for appliances <10,000 BTU/h (3kW)
9" (23cm) for appliances >10,000 BTU/h (3kW) and <50,000 BTU/h (15kW)
12" (30cm) for appliances >50,000 BTU/h (15kW)
K = Clearance to mechanical air supply inlet 6' (1.83m) 3' (91cm) above if within 10' (3m) horizontally
L = Clearance above paved sidewalk or paved
7' (2.13m)
7' (2.13m)
driveway located on public property
M = Clearance under veranda, porch, deck or
12" (30cm)
12" (30cm)
balcony
N = Clearance above a roof shall extend a minimum of 24” (610mm) above the highest point when it passes through the roof
surface, and any other obstruction within a horizontal distance of 18” (450mm).
1 In accordance with the current CSA-B149 Installation Codes 2 In accordance with the current ANSI Z223.1/NFPA 54 National Fuel
Gas Codes
† A vent shall not terminate directly above a sidewalk or paved
driveway which is located between two single family dwellings and serves both dwellings
‡ Only permitted if veranda, porch, deck or balcony is fully open on a
minimum 2 sides beneath the oor.
Fig. 11 Vent termination clearances.
20306759
NOTE: 1. Local codes or regulations may require different
2. The special venting system used on Direct Vent
3. HHT assumes no responsibility for the improper
clearances.
Fireplaces are certied as part of the appliance, with
clearances tested and approved by the listing agency.
performance of the appliance when the venting system does not meet these requirements.
11
PRE-INSTALLATION
Termination Clearances
Termination clearances for buildings with combustible and noncombustible exteriors.
Inside Corner
G =
G
Combustible 6" (152 mm)
Noncombustible
V
2" (51 mm)
Outside Corner
V
F
F =
Combustible 6" (152 mm)
Noncombustible 2" (51 mm)
Radiance® Direct Vent Gas Heater
Alcove Applications*
C
D
C
V
O
E
Balcony - with no side wall
V
M =
Combustible & Noncombustible 12" (305 mm)
*NOTE: Termination in an alcove space (spaces open only on one side and with an overhang) is permitted with the dimensions
specied for vinyl or non-vinyl siding and softs. 1. There must be a 3’ (914 mm) minimum between termination caps. 2. All me­chanical air intakes within 10’ (1 m) of a termination cap must be a minimum of 3’ (914 mm) below the termination cap. 3. All gravity air intakes within 3’ (914 mm) of a termination cap must be a minimum of 1’ (305 mm) below the termination cap.
Fig. 12
TERMINATION CLEARANCES.
Balcony - with perpendicular side wall
E = Min. 2” (51 mm) for
non-vinyl sidewalls Min. 12” (305 mm) for vinyl sidewalls
O = 8’ (2.4 m) Min.
M
Combustible & Noncombustible
M = 12" (305 mm) P = 6” (152 mm)
M
V
P
No.
of Caps D 1 3’ (914 mm) 2 x D 2 6’ (1.8 m) 1 x D 3 9’ (2.7 m) 2/3 x D 4 12’ (3.7 m) 1/2 x D
D
= # of Termination caps x 3
Min.
C
= (2 / # termination caps) x D
Max.
C
Min.
Max.
Actual
Actual
Actual
Actual
Actual
584-15
1212 20306759
Radiance® Direct Vent Gas Heater
ASSEMBLY AND INSTALLATION
VENTING REQUIREMENTS AND OPTIONS
Approved Vent System Components
The Radiance Heater must be vented to the outdoors through an adjacent exterior wall or through the roof. The venting system must be comprised of the appropriate listed
venting components specied on this page. These parts
are available from DuraVent Corporation or your Vermont Castings Dealer.
See Figure 4 for dimensions relevant to the standard minimum-vent kits.
HHT Components*
Free Standing Stove Kit w/adj. Termination Cap, SLP24-BK, SLP6-BK, SLP6A-BK, SLP90-BK, SLP-WT-BK & CCSLP
Vertical Termination cap - High Wind (includes storm collar)
Decorative Wall Thimble Cover SLP-WT-BK
Decorative ceiling restop - black SLP-DCF-BK
Cathedral ceiling support - black SLP-CCS-BK
4" (100mm) pipe length - black SLP4-BK
6" (150mm) pipe length - black SLP6-BK
12" Pipe length-black SLP12-BK
24" Pipe length-black SLP24-BK
36" (915mm) pipe length - black SLP36-BK
48" Pipe length-black SLP48-BK
3"–6" (75 - 150mm) telescoping pipe extension - black
3"–12" telescoping pipe extension-black SLP12A-BK
45 degree elbow-black SLP45-BK
90 degree elbow-black SLP90-BK
Radiance, Stardance, Oxford SLP adapter CCSLP
*CCSLP adapter is required when using HHT components.
SLP-FSSK
SLP-TVHW
SLP6A-BK
DuraVent Components
Minimum Horizontal Vent Kit 2792
Starter Pipe Assembly (incl. inner &
2768*
outer sections)
90° Elbow, Blk. 46DVA-E90B*
45° Elbow, Gal. 46DVA-E45
6" Straight, Blk. 46DVA-06B*
9" Straight, Blk. 46DVA-09B
11" - 14
5
8" Adjustable Straight Section 46DVA-08AB
12" Straight 46DVA-12
24" Straight 46DVA-24B*
36" Straight 46DVA-36B
48" Straight 46DVA-48
Horizontal Vent Cap 46DVA-HC*
Wall Plate 46DVA-DC
Vinyl Siding Shield 46DVA-VSS
Snorkel Termination - 14" 46DVA-SNK14
Snorkel Termination - 36" 46DVA-SNK30
Wall Strap 46DVA-WS
Cathedral Ceiling Support Box 46DVA-CS
Storm Collar 46DVA-SC
Firestop Spacer 46DVA-FS
Flashing 0/12 - 6/12 46DVA-F6
Flashing 6/12 - 12/12 46DVA-F12
Steel Chimney Conv. Kit A (6
Steel Chimney Conv. Kit B (6
5
8" - 85⁄8") 46DVA-KCA
5
8" -
46DVA-KCB
101⁄2")
Steel Chimney Conv. Kit C (6
5
8" - 13") 46DVA-KCC
Masonry Chimney Conversion Kit 46DVA-KMC
Vertical Termination Cap (High Wind) 46DVA-VCH
Vertical Termination Cap (Low Prole) 46DVA-VC
*Included in Minimum Horizontal Vent Kit #2792
20306759
All DuraVent Straight vent pipe sections have a net length
1
2" (37mm) less than the nominal dimension; i.e., a 6"
1 (152 mm) Straight pipe section has an effective length of 41⁄2" (115 mm).
13
ASSEMBLY AND INSTALLATION
ASSEMBLING THE STOVE
Tools Required
• Phillips screwdriver (stub)
• Utility knife
Metal drill bit: size 28 (.140"/3.5mm)
• Flat-blade screwdriver
• Power drill
• Reciprocating saw
• 9/16" wrench
Parts Bag Contents:
• Three (3) Vent Screws
• Two (2) Switch bracket screws
• Wood handle w/insert lifter (handle for operable door)
• Restrictor Plate
• 4" Starter pipe
• On-Off switch, housing, and wiring harness
• Three (3) Phillips round-head bolts, 1/4"- 20 x 1/2"
• One (1) Tube of Vent Gasket Cement
• Four (4) CS, Hex Hd 3/8-16 x 1 Gr 2-Z
• Four (4) Washer, Fl 3/8-Z
• LP Conversion Kit
• Homeowner’s Installation and Operating Manual
Unpack and Assemble Legs
The Radiance is shipped upright. Cut the shipping straps before beginning assembly.
1. Slide stove to the rear of the pallet just far enough to access rear leg holes. Make sure the stove does not tip over backwards. (Figure 13)
2. Attach the rear legs using 3/8" hex head bolts and
at washer supplied. Tighten with a 9/16" wrench
or socket. Remove and discard the large slot-head
screws using the at-blade screwdriver.
3. Carefully tip the stove onto its rear legs. Adjust the pallet to allow access to one of the front leg holes. Be sure to leave the pallet under the stove to prevent the stove from falling fully forward. (Figure 14)
CAUTION
To prevent valve tubing from being crushed or damaged, do not rest valve or ignitor on wooden pallet.
Radiance® Direct Vent Gas Heater
ST720
Fig. 13 Slide stove back just far enough to access rear leg holes.
Washer
ST721
Fig. 14 Carefully tip stove onto back legs. Leave pallet under stove to keep stove from falling fully forward.
4. Have your assistant attach one leg using the hard­ware described.
5. Move the pallet to allow access to the other front leg hole. Attach remaining leg.
6. Remove pallet and allow stove to gently rest on all four legs.
7. Adjust leg levelers to compensate for irregularities in the hearth.
Hex Head Bolt
1414 20306759
NOTE: Verify the two relief doors (located on top of the rebox) are properly seated on the gasket. The doors should sit ush on the gasket, and should lift easily from the seal around the opening.
Radiance® Direct Vent Gas Heater
WARNING
This appliance is equipped with a three-prong (grounded)
plug for your protection against shock hazard and should
be plugged directly into a properly grounded three-prong receptacle. Do not cut or remove the grounding prong from this plug.
INSTALL THE OPTIONAL FAN - RADVT MODELS
(MILLIVOLT ONLY - SEE PAGE 27 FOR SC MODEL)
If you are installing the optional convection Fan Kit #2767 (FK26), continue here. It is easiest to install fan kit before connecting gas line.
1. The fan kit includes a Blower Assembly and a Rheostat Assembly, connected by a cable. (Fig. 15) The Blower Assembly mounts to the bottom rear of the stove, and the Rheostat mounts to the valve cover plate. The as­sembly includes a ‘snapstat’ which automatically turns the fan On (or Off) above (or below) approximately 109°. The Rheostat also provides a range of fan speed settings from Off (which overrides the snapstat func­tion) to High. Unpack and inspect the Blower assem-
bly. Conrm that the fan spins freely.
ASSEMBLY AND INSTALLATION
ST147
Fig. 16 Remove rear shroud.
Side Shield
Snapstat
Snapstat Bracket
Not Used On Radiance
Blower Assembly
ST473a
Fig. 15 Fan kit components.
Snapstat/ Extension Assembly
Rheostat Assembly
2. Remove the rear shroud panel (Fig. 16) and fasten
the blower assembly to the rebox back with the two
bolts provided. (Fig. 17)
3. Attach the snapstat assembly to the snapstat brack­et with two sheet-metal screws. Attach the snapstat bracket to the side shield. (Fig. 17)
4. The rheostat control switch attaches to the left side of the valve bracket at the front of the stove. (Fig. 18)
Remove retaining nut from shaft of rheostat. (if pre­installed)
Bolts
Fig. 17 Attach blower assembly and snapstat.
Rheostat
Rheostat Retaining Collar
Rheostat Knob
Fig. 18 Attach the fan rheostat.
ST149
ST347a
Insert the rheostat through the hole in the back of the left side of the valve bracket, aligning the locator pin with the smaller hole in that bracket.
Thread the retaining nut onto the shaft of the rheo­stat, tightening with a wrench. Do not overtighten.
Attach the control knob to the rheostat shaft.
Use the wire tie to secure the fan and rheostat wire harnesses together.
20306759
15
Outside Wall
Finishing Material (Vinyl Siding, etc.)
ASSEMBLY AND INSTALLATION
Radiance® Direct Vent Gas Heater
VENTING SYSTEM ASSEMBLY
CAUTION
All HHT Direct Vent Stoves have been tested and approved to ANSI/CSA Standards and will operate safely when installed in accordance with this instruction manual. Read all instructions before starting installation,
then follow these instructions carefully to maximize
stove performance and safety. Report damaged parts to your dealer.
WARNING
Always maintain minimum clearances around vent
systems. Rear/Top Vent Vertical Side wall: Horizontal
sections of this vent system require a minimum of 3” (76 mm) clearances to combustibles at the top of the
ue and 1” (25 mm) clearance at the sides and bottom until the ue penetrates the outside wall. A minimum 1” clearance all around the ue is acceptable at this point of penetration. If vertical rise is 71⁄2 feet (2.3 m) or higher
when top venting, the clearance to combustibles is 1” on
all sides of the horizontal run. FOR VERTICAL RUNS
ONLY, maintain a 1” (25 mm) minimum clearance to all sides. Do not pack the open air spaces around the stove
or ue with insulation or other materials. Any horizontal
run must have a 1/4” rise for every one (1) foot of run towards the vent termination. Never run the vent level or down.
• These models are approved to use HHT direct vent pipe components and HHT termination kits, and Du­raVent components. No other venting system compo­nents may be used.
Horizontal runs must be supported every 3 feet (914 mm) using wall straps. Vertical runs must be supported every 8 feet (2.4 m) using wall straps. Slip wall straps loosely on to pipe. Attach straps to framing members using nails or screws. Tighten nut/bolt to secure pipe.
• The stove and venting system should be inspected
before initial use and at least annually by a qualied eld service person. Inspect the external vent cap on a
regular basis to make sure that no debris is interfering
with the airow. Inspect entire venting system to ensure
proper function.
Failure to follow these instructions may create a possible
re hazard and will void the warranty.
Any common venting of this gas appliance with other gas appliances is not allowed.
Important Safety Information
The termination cap MUST be vented directly to the out­side. The termination kit MUST NEVER be connected to
a chimney ue(s) servicing a separate solid-fuel burning
appliance or any other appliances.
• Termination cap MUST NOT be recessed into a wall (see Figure 19).
• The installation must conform with local codes or in the absence of local codes, with the National Fuel Gas Code, ANSI Z223.1 (in the United States) or with the current installation code CSA B149 (in Canada).
WARNING
WARNING
Fig. 19 Termination cap on wall
BEFORE YOU START
Plan your installation. Set the stove in place and survey how to best vent the unit. Select the appropriate termination kit and vent pipe for the installation. Read these instructions and the stove Homeowner’s Manual before beginning
installation. After vent conguration has been decided,
begin attaching pipe to unit.
Items required for installation:
Tools:
Phillips screwdriver Hammer
Saw and/or saber saw Level
Measuring Tape Electric drill and bits
Pliers Square
Building Supplies:
Framing materials
Wall nishing materials
Caulking Material (noncombustible)
1616 20306759
Radiance® Direct Vent Gas Heater
Align
Seams
Rotate
WARNING
Refer to pages 8 and 9 of this manual for the minimum and maximum venting requirements of your stove and
for approved horizontal vent termination locations prior to installation. Failure to do so may cause re hazard.
WARNING
Any horizontal run must have a 1/4” rise for every one
(1) foot of run towards the vent termination. Never allow the vent pipe to run down. This could cause high tem-
peratures and may present a re hazard.
WARNING
Termination cap must be positioned so the embossed arrow is pointed up.
General Information
The Radiance is approved for installation only with the vent components listed on page 13. Follow the vent component instructions exactly.
For U.S. installations: The venting system must conform with local codes and/or the current National Fuel Gas Code, ANSI Z223.1/NFPA 54.
For Canadian installations: The venting system must con­form to the current CSA B149.1 installation code.
INSTALL THE VENT ADAPTER PIPE
(Vermont Castings SLP Vent Components)
1. Attach Inner Starter Pipe, (found in the Parts Bag), to the next section of inner pipe.
2. Run a bead of sealant about 1/2" from the upper end of the Inner starter pipe and join the two sections to­gether.
3. Drill three pilot holes into the Inner Starter and secure the assembly with three sheet metal screws. (Figure
20)
4. Dry t the Inner Pipe assembly to the stove for the purpose of determining the center line of the pipe on the wall.
5. Side Wall Terminations: Dry t the outer elbow with
the vertical outer vent and conrm the centerline
ASSEMBLY AND INSTALLATION
ST211
Fig. 20 Connect the inner starter with the next section of inner vent pipe.
alignment with the wall thimble opening.
6. Attach the Inner Vent Assembly to the stove.
7. Place a 3⁄8" bead of millpack caulk around the inside of the cast starter collar. Insert the 65⁄8" outer adapt­er into the cast outer starting collar and press down
rmly.
8. Install the CCSLP Outer Adapter Pipe.
9. Place a 3⁄8" bead of millpack caulk around the 4" crimped end of the starter collar on the stove. Attach the SLP pipe to the adapter, and secure by aligning
adapter and pipe seams, pressing down rmly until
pipe stops, and twisting to lock into place. (Figure 21)
20306759
ST648a
Fig. 21 Attach inner assembly to ue collar.
17
ASSEMBLY AND INSTALLATION
ASSEMBLE SLIP SECTIONS
The outer ue of the slip section should slide over the outer ue of the pipe section and into (inner ue) the last pipe
section (see Figure 23).
Slide together to the desired length, making sure that a
11⁄2" outer ue overlap is maintained between the pipe
section and slip section.
The pipe and slip section need to be secured by driving two 1/2 in. screws through the overlapping portions of the
outer ues using the pilot holes (see Figure 24).
This will secure the slip section to the desired length and prevent it from separating. The slip section can then be attached to the next pipe section.
If the slip section is too long, the inner and outer ues of
the slip section can be cut to the desired length.
WARNING
Risk of Fire/Explosion! DO NOT break seals on slip sections. Use care when removing termination cap from slip pipe. If slip section seals are broken during removal of the termination cap, vent may leak.
Radiance® Direct Vent Gas Heater
Fig. 24 Screws into Slip Section
SECURE THE VENT SECTIONS
Vertical sections of SLP pipe must be supported every 8 ft.
The SLP restop includes tabs that may be used to secure
vertical sections.
The vent support or plumber’s strap (spaced 120° apart) may be used to secure the vertical sections of pipe (see Figure 25).
Horizontal sections of vent must be supported every 5 ft
with a vent support or plumber’s strap (see Figure 26).
CORRECT INCORRECT
Fig. 22 Make sure the seams are not aligned to prevent unintentional disconnection.
Fig. 23 Slip Section Pilot Holes
WARNING
Risk of Fire/Explosion/Asphyxiation! Improper support may allow vent to sag and separate. Use vent run supports and connect vent sections per installation instructions. DO NOT allow vent to sag below connection point to appliance.
Fig. 25 Securing Vertical Pipe Sections
1818 20306759
Loading...
+ 42 hidden pages