Vermont Castings STLDVPNSC, CRLDVPNSC, PFLDVPPSC, CRLDVPPSC, CLLDVPNSC Installation And Operating Instructions Manual

...
Page 1
Designer Series Direct Vent Gas Fireplace Installation and Operating Instructions
Models: STLDVP(N/P)SC, PFLDV(N/P)PSC, CRLDVP(N/P)SC, CLLDVP(N/P)SC
WARNING: FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly
could result in serious injury, death or property damage.
WHAT TO DO IF YOU SMELL GAS
– Do not try to light any appliance. – Do not touch any electrical switch; do
not use any phone in your building. – Leave the building immediately. – Immediately call your gas supplier from
a neighbor's phone. Follow the gas
supplier's instructions. – If you cannot reach your gas supplier,
call the fi re department.
Installation and service must be performed
by a qualifi ed installer, service agency or the gas supplier.
WARNING: Improper installation, adjustment, alteration, service or maintenance can cause injury or property damage. Refer to this manual. For assistance or additional information consult a qualified installer, service agency or the gas supplier.
This appliance may be installed in an aftermarket,* permanently located, manufactured home (USA only) or mobile home, where not prohibited by local codes.
This appliance is for use only with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases, unless a certifi ed kit is used.
* Aftermarket: Completion of sale, not for purpose of resale, from
the manufacturer.
CERTIFIED
SAFETY BARRIER
DANGER
HOT GLASS WILL
CAUSE BURNS.
DO NOT TOUCH GLASS
UNTIL COOLED.
NEVER ALLOW CHILDREN
TO TOUCH GLASS.
A barrier designed to reduce the risk of burns from
the hot viewing glass is provided with this
appliance and shall be installed.
INSTALLER: Leave this manual with the appliance.
CONSUMER: Retain this manual for
future reference.
20306750 3/15 Rev. 3
Page 2
Designer Series Direct Vent Gas Fireplace
CONTENTS
Thank you and congratulations on your purchase of an
Vermont Castings Group Fireplace.
PLEASE READ THE INSTALLATION AND OPERATION INSTRUCTIONS BEFORE USING THE APPLIANCE!
IMPORTANT: Read all instructions and warnings carefully before starting installation.
Failure to follow these instructions may result in a possible fi re hazard and will void the warranty.
Important Safety Information .....................................3
Code Approval ..................................................................4
Installation Information ...............................................5
Product Specifi cations ......................................................5
High Elevations ................................................................5
Gas Pressures..................................................................5
Gas Specifi cations & Orifi ce Size .....................................5
Fireplace Dimensions .......................................................6
STLDV Framing................................................................8
CRLDV/CLLDV Framing ..................................................9
PFDV Framing ................................................................10
Before Y ou Start .............................................................11
Items Required for Installation........................................11 ..
Firebox Framing .............................................................11
Fireplace Location ..........................................................12
Clearances .....................................................................13
Venting Installation ....................................................14
Installation Precautions ..................................................14
Optional Top Vent Applications .......................................14
Vent Pipe Clearances .....................................................16
Installation Planning .......................................................17
Horizontal & Vertical Termination ...................................17
Termination Location ......................................................18
Vent Graph .....................................................................19
Rear Wall Vent Installation .............................................20
Horizontal w/Vertical Rise Applications ..........................22
Below Grade Installation ................................................24
Vertical Through-the-Roof Applications ..........................25
Installation for Vertical Termination .................................26
Flex Vent Installation ......................................................28
Fireplace Installation .................................................31
Check Gas Type .............................................................31
Install Gas Piping ...........................................................32
Check Gas Pressure .....................................................33
Electrical Installation.......................................................33
Junction Box Wiring........................................................34
Command Center Wall Installation .................................34
Wall Switch Installation ...................................................34
Signature Command Wiring Diagram.............................35
Optional Fan/Blower Systems .......................................36
Signature Command Single Blower BLOTSTSC ...........36
Automatic Dual Thermostat Blower BLOTBLDV ............37
Automatic Single Thermostat Blower BLOTDL ..............37
Glass Frame Removal....................................................38
Rockwool Placement ......................................................39
Log Placement ...............................................................40
Safety Barrier Installation ...............................................42
Operating Instructions ..............................................43
Safety Information ..........................................................43
Operating Instructions ....................................................44
To Turn Off Gas to Appliance .........................................44
Signature Command System Operation..................45
Cleaning and Maintenance .......................................48
Burner, Pilot and Control Compartment .........................48
Pilot Flame .....................................................................48
Burner Flame..................................................................48
Venting System ..............................................................49
Glass Door .....................................................................49
Logs................................................................................49
Rock Wool .....................................................................49
Troubleshooting ........................................................50
Signature Command System .........................................50
Replacement Parts ....................................................51
Firebox Components ......................................................51
Signature Command System .........................................52
Logs................................................................................54
Brick ...............................................................................54
Venting Components ......................................................56
Massachusetts Residents Only................................60
Warranty .....................................................................61
Effi ciencies.................................................................64
2
20306750
Page 3
IMPORTANT SAFETY INFORMATION
Designer Series Direct Vent Gas Fireplace
INSTALLER
Please leave these instructions with the appliance.
OWNER
Please retain these instructions for future reference
Read this owner’s manual carefully and completely before trying to assemble, operate, or service this
replace.
Any change to this fi replace or its controls can be dangerous.
Improper installation or use of this fi replace can cause serious injury or death from fi re, burns,
explosions, electrical shock and carbon monoxide poisoning.
WARNING
This fi replace is a vented product. This fi replace must be properly installed by a qualifi ed service person. The glass door must be properly seated and sealed. If this unit is not properly installed by a qualifi ed service person with glass door properly seated and sealed, combustion leakage can occur.
CARBON MONOXIDE POISONING: Early signs of carbon monoxide poisoning are similar to the fl u with headaches, dizziness and/or nausea. If you have these signs, the fi re- place may not have been installed properly. Get fresh air at once! Have the fi replace inspected and serviced by a qualifi ed service person. Some people are more affected by carbon monoxide than others. These include pregnant women, people with heart or lung disease or anemia, those under the infl uence of alcohol, and those at high altitudes.
Propane/LP gas and natural gas are both odorless. An odor-making agent is added to each of these gases. The odor helps you detect a gas leak. However, the odor added to these gases can fade. Gas may be present even though no odor exists.
Make certain you read and understand all warnings. Keep this manual for reference. It is your guide to safe and proper operation of this fi replace.
1. This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases unless a certifi ed kit is used.
2. For propane/LP fi replace, do not place propane/LP supply tank(s) inside any structure. Locate propane/LP supply tank(s) outdoors. T o prevent performance prob­lems, do not use propane/LP fuel tank of less than 100 lbs. capacity.
3. If you smell gas
shut off gas supply.
do not try to light any appliance.
do not touch any electrical switch; do not use any
phone in your building .
immediately call your gas supplier from a neighbor’s
phone. Follow the gas supplier’s instructions.
4. Never install the fi replace
in a recreational vehicle
where curtains, furniture, clothing, or other fl am-
mable objects are less than 42" from the front, top, or sides of the fi replace
in high traffi c areas
in windy or drafty areas
5. This fi replace reaches high temperatures. Keep children and adults away from hot surfaces to avoid burns or clothing ignition. Fireplace will remain hot for a time after shutdown. Allow surfaces to cool before touching.
6. Young children should be carefully supervised when they are in the same room as the appliance. Toddlers, young children and others may be susceptible to acci­dental contact burns. A physical barrier is recommended if there are at risk individuals in the house. To restrict access to a fi replace or stove, install an adjustable safety gate to keep toddlers, young children and other at risk individuals out of the room and away from hot surfaces.
7. Do not modify fi replace under any circumstances. Any parts removed for servicing must be replaced prior to operating fi replace.
8. Turn fi replace off and let cool before servicing, install- ing, or repairing. Only a qualifi ed service person should install, service, or repair the fi replace. Have burner system inspected annually by a qualified service person.
9. You must keep control compartments, burners, and circulating air passages clean. More frequent cleaning may be needed due to excessive lint and dust. Turn of f the gas valve and pilot light before cleaning fi replace.
10. Have venting system inspected annually by a qualifi ed service person. If needed, have venting system cleaned or repaired. Refer to Cleaning and Maintenance, Page
48.
11. Keep the area around your fi replace clear of combus- tible materials, gasoline, and other fl ammable vapor and liquids. Do not run fi replace where these are used or stored. Do not place items such as clothing or decora­tions on or around fi replace.
.
20306750
3
Page 4
Designer Series Direct Vent Gas Fireplace
IMPORTANT SAFETY INFORMATION
12. Do not use this fi replace to cook food or burn paper or other objects.
13. Never place anything on top of fi replace.
14. Do not use any solid fuels (wood, coal, paper, card­board, etc.) in this fi replace. Use only the gas type indicated on rating plate.
15. This appliance, when installed, must be electrically grounded in accordance with local codes or in the absence of local codes, with the National Electrical
Code, ANSI/NFP A 70, or the Canadian Electrical Code, CSA C22.1.
16. Do not obstruct the fl ow of combustion and ventilation air in any way. Provide adequate clearances around air openings into the combustion chamber along with adequate accessibility clearance for servicing and proper operation.
17. When the appliance is installed directly on carpeting, tile or other combustible material other than wood fl oor- ing, you must set appliance on a metal or wood panel or hearth pad extending the full width and depth of the appliance.
18. Do not use fi replace if any part has been exposed to or has been under water. Immediately call a qualifi ed service technician to inspect the appliance and replace any part of the control system and any gas control which as been submerged in water.
19. Do not operate fi replace if any log is broken.
20. Do not use a blower insert, heat exchanger insert, or any other accessory not approved for use with this replace.
21. Do not operate the fi replace with glass door removed, cracked, or broken.
CODE APPROV AL
Direct Vent type appliances draw all combustion air from outside of the dwelling through the vent pipe.
These appliances have been tested by CSA and found to comply with the established standards for DIRECT VENT GAS FIREPLACE HEATERS in the USA and Canada as follows:
LISTED VENTED GAS FIREPLACE HEATER
TESTED TO:
ANSI Z21.88-2014 / CSA 2.33-2014 STANDARDS
A manufactured home (USA only) or mobile home OEM installation must conform with the Manufactured Home
Construction and Safety Standard, Title 24 CFR, Part 3280, or when such a standard is not applicable, the Standard for Manufactured Home Installations, ANSI/ NCSBCS A225.1, or Standard for Gas Equipped Recre­ational Vehicles and Mobile Housing, CSA Z240.4.
IMPORTANT:
PLEASE READ THE FOLLOWING CAREFULLY
It is normal for fi replaces fabricated of steel to give off some expansion and/or contraction noises during the start up or cool down cycle. Similar noises are found with your furnace heat exchanger or car engine.
IMPORTANT:
PLEASE READ THE FOLLOWING CAREFULLY
It is not unusual for gas fi replace to give off some odor the fi rst time it is burned. This is due to the manufacturing process.
Please ensure that your room is well ventilated during burn off — open all windows.
It is recommended that you burn your fi replace for at least ten (10) hours the fi rst time you use it. Place the fan switch in the “OFF” position during this time.
Never connect unit to private (non-utility) gas wells. This gas is commonly known as wellhead gas.
WARNING
DANGER
HOT GLASS WILL
CAUSE BURNS.
DO NOT TOUCH GLASS
UNTIL COOLED.
NEVER ALLOW CHILDREN
TO TOUCH GLASS.
A barrier designed to reduce the risk of burns from
the hot viewing glass is provided with this
appliance and shall be installed.
4
20306750
Page 5
INSTALLATION INFORMATION
Designer Series Direct Vent Gas Fireplace
PRODUCT SPECIFICATIONS
This appliance has been certifi ed for use with either
natural or propane gas. See appropriate data plates.
This appliance is not for use with solid fuels.
The appliance is approved for bedroom or bedsitting
room installations.
The appliance must be installed in accordance with local
codes if any. If none exist use the current installation code. ANSI Z223.1/NFPA 54 in the USA, CSA B149 in Canada.
This appliance is mobile home approved.
The appliance must be properly connected to a venting
system.
The appliance is not approved for closet or recessed
installations.
HIGH ELEVATIONS
Input ratings are shown in BTU per hour and are certifi ed without deration for elevations up to 4,500 feet (1,370 m) above sea level.
For elevations above 4,500 feet (1,370 m) in USA, installations must be in accordance with the current ANSI Z223.1/NFPA 54 and/or local codes having juris­diction.
In Canada, please consult provincial and/or local authori­ties having jurisdiction for installations at elevations above 4,500 feet (1,370 m).
GAS PRESSURES
Natural Propane (LP) Inlet Minimum 4.5” w.c. 11.0” w.c. Inlet Maximum 10.5” w.c. 13.0” w.c. Manifold Pressure 3.5” w.c. 10.0” w.c.
GAS SPECIFICATIONS & ORIFICE SIZE
Max. Min.
Input Input Orifi ce Model Fuel Controls BTU/h BTU/h Size
PFLDVPNS Nat. SCS 37,000 25,000 #31 PFLDVPPS LP SCS 35,000 27,000 1.8 mm STLDVPNS Nat. SCS 37,000 25,000 #31 STLDVPPS LP SCS 35,000 27,000 1.8 mm CLLDVPNS Nat. SCS 37,000 25,000 #31 CLLDVPPS LP SCS 35,000 27,000 1.8 mm CRLDVPNS Nat. SCS 37,000 25,000 #31 CRLDVPPS LP SCS 35,000 27,000 1.8 mm
Command Center
Figure 1 ­Designer Controls
20306750
Control Box
Gas Valve
FP2815
5
Page 6
Designer Series Direct Vent Gas Fireplace
INSTALLATION INFORMATION
FIREPLACE DIMENSIONS
256M”
(654 mm)
(32 mm)
36QE
(81 mm)
Figure 2 ­STLDV (See-thru) Fireplace Dimensions
356QE” (903 mm)
156M"
3356QE” (840 mm)
386QE” (979 mm)
496QE” (1259 mm)
Centerline of Flue Outlet
2856M”
(718 mm)
116M”
(298 mm)
34”
(864 mm)
7(6
(200 mm)
12"
(305 mm)
47(6”
(1216 mm)
41(6”
(1064 mm)
37(6”
(962 mm)
23" (584 mm)
FP2851
7(6
(200 mm)
156M"
(32 mm)
156
(29 mm)
36M
(95 mm)
21” (533 mm)
1856O" (470 mm)
24” (610 mm)
276M” (705 mm)
256M”
(654 mm)
34”
(864 mm)
556
(130 mm)
Figure 3 ­CLLDV/CRLDV (Corner) Fireplace Dimensions
356QE” (903 mm)
156M"
(32 mm)
3356QE" (840 mm)
386QE” (979 mm)
Centerline of Flue Outlet
2856M”
(718 mm)
466” (1178 mm)
116M”
(298 mm)
47(6”
(1216 mm)
(1064 mm)
7(6
(200 mm)
12"
(305 mm)
41(6”
37(6”
(962 mm)
23" (584 mm)
276M” (705 mm)
FP2852
6
20306750
Page 7
INSTALLATION INFORMATION FIREPLACE DIMENSIONS
Designer Series Direct Vent Gas Fireplace
Centerline of Flue Outlet
116M”
(298 mm)
12"
(305 mm)
7(6
(200 mm)
21”
(533 mm)
2856M”
(718 mm)
156M"
(32 mm)
1856O”
(470 mm)
(654 mm)
156
(29 mm)
256M”
34”
(864 mm)
556
(130 mm)
Figure 4 ­PFLDV (Peninsula) Fireplace Dimensions
356QE” (903 mm)
156M"
(32 mm)
3356QE” (840 mm)
386QE” (979 mm)
466” (1178 mm)
2856M”
(718 mm)
47(6”
(1216 mm)
41(6”
(1064 mm)
37(6”
(962 mm)
23" (584 mm)
7(6
(200 mm)
FP2853
20306750
7
Page 8
Designer Series Direct Vent Gas Fireplace
STLDV FRAMING
23" (1/2" Drywall)
or Adjustable to
226M” (5/8” Drywall)
Noncombustible Material
C
L
(102 mm)
Fold Outer Tabs and Nail to Framing Members
4”
Min.
7”
(178 mm)
Min.
8556QE
(221 mm)
Min.
INSTALLATION INFORMATION
Remove box and Insulation for Top Vent Confi gurations
486QE”
(1224 mm)
NOTE: Glass cen­terline is off center from rought framing dimensions.
22556QE” (576 mm)
5056QE” (1272 mm)
Figure 5 ­STLDV (See-thru) Framing
276” (695 mm)
The fi replace must be secured to the fl oor and/or to framing studs as shown in Figure 5 . Use four (4) wood screws or masonry/ concrete screws to secure fi replace to the fl oor. Use four (4) screws to attach fi replace to framing. The side brackets or nailing fl anges are designed to accommodate two wall boards thicknesses, 1/2" or 5/8".
If using 5/8" drywall, remove framing tabs and re-install on 2nd set of holes positioned slightly inwards
If using 5/8" drywall, remove noncombustible supports, rotate 180° and reinstall to achieve 5/8" depth
The area above and on the sides of the replace must be a noncombustible material.
Figures 5, 6, 7
NOTE
Never install combustible materials over front face of fi replace.
NOTE
8
20306750
Page 9
INSTALLATION INFORMATION
"
CRLDV/CLLDV FRAMING
2756O” (699 mm)
(1/2” Drywall)
Remove box and Insulation for Top Vent Confi gurations
Noncombustible Material
456O
(114 mm)
Min.
or
276” (696 mm)
(5/8” Drywall)
Designer Series Direct Vent Gas Fireplace
4656” (1172 mm)
(1/2” Drywall)
or
46” (1168 mm)
(5/8” Drywall)
556QE
8
486QE
(1224 m
If using 5/8" drywall, remove framing tabs and re-install on 2nd set of holes positioned slightly inwards
Fold Outer Tabs and Nail to Framing Members
27(6” (708 mm)
Figure 6 ­CRLDV and CLLDV (Corner) Framing
7”
(178 mm)
Min.
(221 mm) Min,
466” (1184 mm)
If using 5/8" drywall, remove framing tabs and re-install on 2nd set of holes positioned slightly inwards
If using 5/8" drywall, remove noncombustible supports, rotate 180° and reinstall to achieve 5/8" depth
The fi replace must be secured to the fl oor and/or to framing studs as shown in Figure 6 . Use four (4) wood screws or masonry/ concrete screws to secure fi replace to the fl oor. Use four (4) screws to attach fi replace to framing. The side brackets or nailing fl anges are designed to accommodate two wall boards thicknesses, 1/2" or 5/8".
20306750
The area above and on the sides of the replace must be a noncombustible material.
Figures 5, 6, 7
NOTE
Never install combustible materials over front face of fi replace.
NOTE
9
Page 10
Designer Series Direct Vent Gas Fireplace
STLDV FRAMING
4656” (1172 mm)
(1/2” Drywall)
or
46” (1168 mm)
(5/8” Drywall)
Remove box and Insulation for Top Vent Confi gurations
7”
(178 mm)
Min.
23” (584 mm)
(1/2” Drywall) or Adjustable to 226M” (578 mm)
(5/8” Drywall)
8556QE
(221 mm) Min,
INSTALLATION INFORMATION
Noncombustible Material
486QE”
(1224 mm)
If using 5/8" drywall, remove framing tabs and re-install on 2nd set of holes positioned slightly inwards
Fold Outer Tabs and Nail to Framing Members
Figure 7 ­PFDV (Peninsula) Framing
The fi replace must be secured to the fl oor and/or to framing studs as shown in Figure 7 . Use four (4) wood screws or masonry/ concrete screws to secure fi replace to the fl oor. Use four (4) screws to attach fi replace to framing. The side brackets or nailing fl anges are designed to accommodate two wall boards thicknesses, 1/2" or 5/8".
If using 5/8" drywall, remove noncombustible supports, rotate 180° and reinstall to achieve 5/8" depth
466” (1184 mm)
NOTE: The Vermont Castings Group Model BPWC500 mantel is specially designed to comply with all mantel temperature requirements. Any custom-built mantels must comply with the framing clearances and the use of non­combustibles as shown in Figures 5, 6 and 7.
The area above and on the sides of the replace must be a noncombustible material.
Figures 5, 6, 7
NOTE
Never install combustible materials over front face of fi replace.
NOTE
10
20306750
Page 11
INSTALLATION INFORMATION
Designer Series Direct Vent Gas Fireplace
BEFORE YOU ST ART
Read this homeowner manual thoroughly and follow all instructions carefully. Inspect all contents for shipping damage and immediately inform your dealer if any damage is found. Do not install any unit with damaged, incomplete, or substitute parts. Check your packing list to verify that all listed parts have been received. You should have the following:
Fireplace (Firebox and Burner System)
Log Set Fasteners
Rock Wool Restrictor Plate/Disc (2)
White Toggle Switch Switch Cover Plate
ITEMS REQUIRED FOR INSTALLATION
Phillips Screwdriver Framing Materials
Hammer Wall Finishing Materials
Saw and/or saber saw Level
Measuring Tape Pliers
Electric Drill and Bits Square
Pipe Wrench Tee Joint
Noncombustible Panel
Caulking Material (noncombustible)
Fireplace Surround Material (noncombustible)
Piping Complying with Local Codes
Pipe Sealant Approved for use with Propane/LPG
(Resistant to sulfur compounds)
FIREBOX FRAMING
Firebox framing can be built before or after the appliance is set in place. Construct fi rebox framing following Figure 5, 6 or 7 for your specifi c installation requirements. The framing headers may rest on the top of the fi rebox stand- offs. Do not bring headers below top of standoffs. NOTE: When planning your framing and installation, keep in mind that the gas line and electric power come in on the same end of the fi replace. Refer to Figures 2, 3 & 4 for fi replace dimensions.
The fi rebox may be installed directly on a combustible fl oor or raised on a platform of an appropriate height. When the fi rebox is installed directly on carpeting, tile, or other combustible material, other than wood fl ooring, the fi rebox shall be installed on a metal or wood panel extending the full width and depth of the enclosure.
FINISHING MATERIAL
NOTE: Any remote wiring (i.e. remote control, wall switch,
and optional fan) must be done prior to fi nal fi nishing to avoid costly reconstruction.
Only noncombustible materials (i.e. brick, tile, slate, steel, or other materials with a UL fi re rating of Zero) may be used to cover the black surface of the appliance. A 300°F minimum adhesive may be used to attach facing materi­als to the black surface. If joints between the fi nished wall and the fi replace surround are sealed, a 300°F minimum sealant material (General Electric RTV103 or equivalent) must be used.
Do not fill spaces around firebox with insulation or other materials. This could cause a fi re.
WARNING
20306750
COLD CLIMATE INSULATION
If you live in a cold climate, seal all cracks around your appliance, and wherever cold air could enter the room, with noncombustible material. It is especially important to insulate
NOTE
the outside chase cavity between the studs and under the fl oor on which the appliance rests, if the fl oor is above ground level.
NOTE: Refer to cold climate pilot information on Page 46
for more information on standing pilot vs. intermittent pilot options.
11
Page 12
Designer Series Direct Vent Gas Fireplace
INSTALLATION INFORMATION
FIREPLACE LOCATION
Plan for the installation of your appliance. This includes determining where the unit is to be installed, the vent con­ guration to be used, framing and fi nishing details, and whether any optional accessories (i.e. blower, wall switch, or remote control) are desired. Consult your local building code agency to ensure compliance with local codes, includ­ing permits and inspections.
The following factors should be taken into consideration:
Clearance to side-wall, ceiling, woodwork, and windows.
Minimum clearances to combustibles must be main-
tained.
This fi replace may be installed along a wall, across a
corner, or use an exterior chase. Refer to Figure 8 for suggested locations.
Location should be out of high traffi c areas and away
from furniture and draperies due to heat from appli­ance.
Never obstruct the front opening of the fi replace.
Do not install in the vicinity where gasoline or other
ammable liquids may be stored.
Vent pipe routing. See Venting section found in this
manual for allowable venting confi gurations.
These units can be installed in a bedroom. See National
Fuel Gas Code ANSI Z233.1/NFPA 54 — (current edition), the Uniform Mechanical Code — (current edi­tion), and Local Building Codes for specifi c installation requirements.
These units can be installed in a bathroom.
D
Y
C
Y
Figure 8 ­Locate Fireplace
A Flat on wall
A
B
X
** Island (C) and Room Divider (D) installation is possible as long as the horizontal portion of the vent system (X) does not exceed 20’ (610cm). See details in Venting Section.
* When you install your fi replace in (D) Room divider or (E) Flat on wall corner positions (Y), a minimum of 6” (152mm) clearance must be maintained from the perpendicular wall and the front side edge of the fi replace.
B **Island C *Room divider D *Flat on wall corner Y 6” minimum
12
20306750
Page 13
INSTALLATION INFORMATION
CLEARANCES TO COMBUSTIBLES
Follow these instructions carefully to ensure safe installation. Failure to follow in struc tions exactly can create a fire hazard.
The appliance cannot be installed on a carpet, tile or other combustible material other than wood fl ooring. If installed on
WARNING
carpet or vinyl flooring, the appliance shall be installed on a metal, wood or noncombustible material panel ex tend ing full width and depth of the appliance.
Designer Series Direct Vent Gas Fireplace
12”
Noncombustible Material to Top of Standoffs
16”
12”
Top of Fireplace Opening
6”
256O
10”
Ceiling
Combustible Mantel
72”
(1829 mm)
Min.
6”
(152 mm)
Min.
Figure 9 ­Ceiling and Side Wall Clearances
(305 mm)
Max. Depth
12"
16"
(406 mm)
Min.
FP2544
Side View
FP2818
Top View
Side of Fireplace Opening
Figure 10 ­Mantel Clearance
FP2817
Spacer
Stud
Combustible Material Area
1”
4”
5”
3”
45°
6”
MANTEL CLEARANCES
NOTE: The combustible area above the facing must
not protrude more than 1/2" from the facing. If it does, it is considered a mantel and must meet the mantel requirements listed in this manual.
NOTE: Vermont Castings Group Model BPWC500 Mantel is designed to comply with all mantel temperature requirements.
20306750
Never obstruct or modify the air inlet or outlet grilles (louvers). This may create a fi re hazard.
WARNING
13
Page 14
Designer Series Direct Vent Gas Fireplace
VENTING INSTALLATION
Read all instructions completely and thoroughly before attempting installation. Failure to do so could result in serious injury , property damage or loss of life. Operation of improperly installed and maintained
WARNING
venting system could result in serious injury , property damage or loss of life.
INSTALLATION PRECAUTIONS
Consult local building codes before beginning the installation. The installer must make sure to select the proper vent system for installation. Before installing vent kit, the installer must read this fi replace manual and vent kit instructions.
Only a qualifi ed installer/service person should install the venting system. The installer must follow these safety rules:
Wear gloves and safety glasses for protection.
Use extreme caution when using ladders or when on
rooftops.
Be aware of electrical wiring locations in walls and ceil-
ings. The following actions will void the warranty on your vent­ing system:
Installation of any damaged venting component.
Unauthorized modifi cation of the venting system.
Installation of any component part not manufactured or
approved by Vermont Castings Group
Installation other than permitted by these instructions.
OPTIONAL TOP VENT APPLICATION
The appliance is shipped as a rear vent unit. If the installa­tion layout requires the unit to be a top vent confi guration, the appliance can be converted by following the steps below.
When removing and refi tting the plates and adapter, be sure the associated gaskets are undamaged and refi tted as required.
1. Remove the eight (8) screws securing the fl ue pipe adapter to the fi replace body . Figure 12
2. Set the fl ue pipe adapter aside, complete with the gasket. Do not damage the gaskets as the adapter and gasket must be refi tted.
3. Remove the eight (8) screws securing the fl ue pipe cover to the top of the intake box and remove the cover and gasket. Figure 12
Remove for Top Vent applications
NOTICE
14
Failure to follow these instructions will void the warranty.
FP2895
Figure 11
20306750
Page 15
VENTING INSTALLATION
Designer Series Direct Vent Gas Fireplace
Screws
Flue Pipe Cover
Flue Pipe Adapter
Figure 12 ­Remove 16 screws from Flue Pipe Adapter and Flue Pipe Cover
FP2833
4. Remove six (6) screws securing the fl ue pipe to the back of the intake box and remove the pipe and gasket.
Figure 13
5. Replace the fl ue pipe to top of fi rebox. Ensure the gasket is in place and undamaged. Secure with six (6) screws.
Figure 14
6. Place the fl ue pipe cover and gasket removed in Step 3 over the fl ue opening in bottom of the intake box.
7. Refi t the fl ue pipe adapter and gasket to the top of fi re- place. Secure the adapter with six (6) screws removed in Step 1.
After conversion to top vent confi guration, the 5" (127 mm) flue pipe should be concentric with the 8" (203 mm) outer collar within 1/4".
WARNING
Flue Cover
Flue Pipe
Figure 13 ­Remove Flue Pipe
Flue Pipe
Screws
Screws
FP2834
20306750
FP2835
Figure 14 ­Attach Flue Pipe to Top Vent Confi guration
15
Page 16
Designer Series Direct Vent Gas Fireplace
1
VENTING INSTALLATION
This fi replace must be vented to the outside. The venting system must NEVER be attached to a chimney serving a separate solid fuel burning appliance. Each gas appliance must use a separate vent system. Do not use
WARNING
common vent systems.
*3"
**1”
(1305 mm)
Flue Pipe
**1"
Centerline
516”
to Floor
Horizontal sections of this vent system require a minimum of 3" clearances to combustibles at the top of the fl ue and 1" clearance at the sides and bottom until the ue penetrates the outside wall. A minimum 1" clearance all around the fl ue is acceptable at this point of penetration. Unless the vertical run is 7
⁄2' or higher from fl oor of
replace, the clearance for horizontal run
is 1" on all sides.
WARNING
Vertical sections of this vent system require a minimum of 2" clearance to combustibles at the top of the unit directly above the stand-off. A minimum of 1" clearance all around the fl ue is acceptable thereafter.
37(6”
*3"
**1”
**1"
(962 mm) Flue Pipe
Centerline
to Floor
Figure 15 ­Combustible Clearances for Vent Pipe with Minimum Rise
16
FP2819
* A minimum of 3" clearance to the top is required along horizontal length until fl ue pipe penetrates outside wall.
** A minimum 1" clearance to combustibles permitted all around ue at outside wall
20306750
Page 17
1
2
VENTING INSTALLATION INSTALLATION PLANNING
There are two basic types of direct-vent installation:
Horizontal Termination
Vertical Termination
It is important to select the proper length of vent pipe for the type of termination you choose. It is also important to note the wall thickness.
FOR HORIZONTAL TERMINATION
Select the amount of vertical rise desired. All horizontal run of venting must have 1/4" rise for every 12" of run towards the termination below 71⁄2' of vertical rise from fl oor of fi re- place. With 71⁄2 feet or more of vertical rise from the fl oor of the fi replace, the horizontal run may be level. NEVER run vent piping down.
Y ou may use up to three 90° elbows in this vent confi gura- tion. Refer to Vertical/Horizontal T ermination Confi gurations on Page 21.
Horizontal venting which incorporates the twist lock pipe must be installed on a level plane without an inclining or declining slope.
FOR VERTICAL TERMINATION
Measure the distance from the fi replace fl oor to the ceil- ing. Add the ceiling thickness, the vertical rise in an attic or second story , and allow for suffi cient vent height above the roof line.
NOTE: You may use two 45° elbows in place of a 90° elbow. You must follow rise to run ratios when using 45° elbows. The appliance is approved for use with three 90° elbows maximum or a combination of 90° and 45° elbows up to a maximum of 270°.
Designer Series Direct Vent Gas Fireplace
Never run the vent pipe down. This may cause excessive temperatures which could cause a fi re.
WARNING
For two-story applications, restops are required at each oor level. If an offset is needed in the attic, additional pipe
and elbows will be required. Y ou may use a chase with a vent termination with exposed
pipe on the exterior of the house. See Installing Vent System in a Chase below. If pipe is enclosed in chase, it is not exposed.
It is very important that the venting system maintain its bal­ance between the combustion air intake and the fl ue gas exhaust. Certain limitations apply to vent confi gurations
and must be strictly followed.
INSTALLING A VENT SYSTEM IN AN OUTSIDE CHASE
A chase is a vertical boxlike structure built to enclose venting that runs along the outside of a building. A chase
is required for such venting.
When installing in a chase, you should insulate the chase as you would the outside walls of your home. This is especially important in cold climates. Insulation should be considered a combustible
NOTICE
material. Maintain proper clearances to all combustible materials.
Always maintain minimum clearances around vent systems. The minimum clearances to combustibles for horizontal vent pipe are 3" at the top* and 1" at the sides and bottom of the vent system until the pipe penetrates the nearest vertical wall (1" required). A 1" minimum clearance all around the pipe must be maintained at outside wall and on vertical runs. Do not pack the open air spaces with insulation or other materials. This could
WARNING
cause high temperatures and may present a fi re hazard. *Unless the vertical run is 7
feet or higher from fl oor of fi replace, the clearance for the horizontal run is 1" on all sides.
20306750
Treatment of fi restops and construction of the chase may vary from building type to building type. These instructions are not substitutes for the requirements of local
NOTICE
building codes. You must follow all local building codes.
17
Page 18
Designer Series Direct Vent Gas Fireplace
V
X
X
X
D
E
B
B
B
C
B
M
B
A
J
K
F
L
VENT TERMINATION AIR SUPPLY INLET
AREA WHERE TERMINAL IS NOT PERMITTED
H
I
Fixed
Closed
Operable
Operable
Fixed
Closed
B
INSIDE
CORNER DETAIL
A
G
CFM145a
V
V
V
V
V
V
V
V
TERMINATION LOCATION
Termination Locations
VENTING INSTALLATION
A = Clearance above grade, veranda, porch,
CANADIAN INSTALLATIONS
1
12" (30cm) 12" (30cm)
US INSTALLATIONS
2
deck or balcony
B = Clearance to window or door that may be
opened
C = Clearance to permanently closed window 12" (305mm) recommended to prevent
D = Vertical clearance to ventilated soffi t locat-
6" (15cm) for appliances <10,000 BTU/h (3kW) 12" (30cm) for appliances >10,000 BTU/h (3kW) and <100,000 BTU/h (30kW) 36" (91cm) for appliances >100,000 BTU/h (30kW)
6" (15cm) for appliances <10,000 BTU/h (3kW) 9" (23cm) for appliances >10,000 BTU/h (3kW) and <50,000 BTU/h (15kW) 12" (30cm) for appliances >50,000 BTU/h (15kW)
12" (305mm) recommended to prevent win-
window condensation
dow condensation
18" (458mm) 18" (458mm) ed above the terminal within a horizontal distance of 2' (610 mm) from the center line of the terminal
E = Clearance to unventilated soffi t 12" (305mm) 12" (305mm) F = Clearance to outside corner see next page see next page G = Clearance to inside corner see next page see next page H = Clearance to each inside of center line
extended above meter/regulator assembly
3' (91cm) within a height of 15' (5m) above
the meter/regulator assembly
3' (91cm) within a height of 15' (5m) above
the meter/regulator assembly I = Clearance to service regulator vent outlet 3' (91cm) 3' (91cm) J = Clearance to non-mechanical air supply
inlet to building or the combustion air inlet to any other appliance
6" (15cm) for appliances <10,000 BTU/h (3kW) 12" (30cm) for appliances >10,000 BTU/h (3kW) and <100,000 BTU/h (30kW) 36" (91cm) for appliances >100,000 BTU/h (30kW)
6" (15cm) for appliances <10,000 BTU/h
(3kW)
9" (23cm) for appliances >10,000 BTU/h
(3kW) and <50,000 BTU/h (15kW)
12" (30cm) for appliances >50,000 BTU/h
(15kW) K = Clearance to mechanical air supply inlet 6' (1.83m) 3' (91cm) above if within 10' (3m) horizontally L = Clearance above paved sidewalk or
7' (2.13m)
7' (2.13m)
paved driveway located on public property
M = Clearance under veranda, porch, deck or
12" (30cm)
12" (30cm)
balcony
1 In accordance with the current CSA-B149 Installation Codes 2 In accordance with the current ANSI Z223.1/NFPA 54 National Fuel
Gas Codes
† A vent shall not terminate directly above a sidewalk or paved
driveway which is located between two single family dwellings and serves both dwellings
‡ Only permitted if veranda, porch, deck or balcony is fully open on a
minimum 2 sides beneath the fl oor.
18
NOTE: 1. Local codes or regulations may require different
2. The special venting system used on Direct Vent
3. Vermont Castings Group assumes no responsibility for
clearances. Fireplaces are certifi ed as part of the appliance, with
clearances tested and approved by the listing agency. the improper performance of the appliance when the venting
system does not meet these requirements.
20306750
Page 19
VENTING INSTALLATION
Termination Clearances
Termination clearances for buildings with combustible and noncombustible exteriors.
Inside Corner
G =
G
Combustible 6" (152 mm)
Noncombustible
V
2" (51 mm)
Outside Corner
V
F
Designer Series Direct Vent Gas Fireplace
Alcove Applications*
D
F =
Combustible 6" (152 mm)
Noncombustible 2" (51 mm)
C
O
C
V
E
Balcony - with no side wall
M
V
Figure 17 ­Termination Clearances
*NOTE: Termination in an alcove space (spaces open only on one side and with an overhang) is permitted with the dimensions specifi ed for vinyl or non-vinyl siding and soffi ts. 1. There must be a 3’ (914 mm) minimum between termination caps. 2. All mechanical air intakes within 10’ (1 m) of a termination cap must be a minimum of 3’ (914 mm) below the termination cap. 3. All gravity air intakes within 3’ (914 mm) of a termination cap must be a minimum of 1’ (305 mm) below the termination cap.
M =
Combustible & Noncombustible 12" (305 mm)
HOW TO USE THE VENT GRAPH
The Vent Graph should be read in conjunction with the following vent installation instructions to determine the relationship between the vertical and horizontal dimensions of the vent system.
1. Determine the height of the center of the horizontal vent pipe exiting through the outer wall. Using this dimen­sion on the Sidewall Vent Graph below , locate the point intersecting with the slanted graph line.
2. From the point of this intersection, draw a vertical line to the bottom of the graph.
3. Select the indicated dimension, and position the fi re- place in accordance with same.
Example: If the vertical dimension from the oor of the
replace is 11' (3.4 m) the horizontal run to the face of the outer wall must not exceed 16' (4.9 m).
Sidewall Vent Graph showing the relationship between vertical and horizontal dimensions for a Direct Vent fl ue system.
Balcony - with perpendicular side wall
M
V
P
Combustible & Noncombustible
M = 12" (305 mm) P = 6” (152 mm)
323⁄4" to Center of Horizontal Pipe
E = Min. 2” (51 mm) for
non-vinyl sidewalls Min. 12” (305 mm) for vinyl sidewalls
O = 8’ (2.4 m) Min.
No.
of Caps DMin. CMax. 1 3’ (914 mm) 2 x DActual 2 6’ (1.8 m) 1 x DActual 3 9’ (2.7 m) 2/3 x DActual 4 12’ (3.7 m) 1/2 x DActual
DMin. = # of Termination caps x 3 CMax. = (2 / # termination caps) x DActual
40 38 36 34 32 30
Dimensions in
Feet
28 26 24 22 20 18 16
eg: A
14 12 10
8 6 4 2
2 4 6 8 10 12 14 16 18 20
584-15
Vertical Dimension From the Floor of Unit to the Center of the
Horizontal Vent Pipe
Horizontal dimension from the fi nished outside wall
Figure 18 -
to the center of the pipe on the fi replace
Rear Wall Venting Graph
20306750
19
Page 20
Designer Series Direct Vent Gas Fireplace
VENTING INSTALLATION
REAR WALL VENT INSTALLATION (5" x 8" VENTING ONLY)
When installed as a rear vent unit, this appliance may be vented directly to a termination located on the rear wall behind the appliance. Only an Vermont Castings Group brand termination is allowed for this application.
The maximum horizontal distance between the rear
of the appliance and the termination is 20" (508 mm).
Figure 19
Maximum
20"
(508 mm)
Top View Flat Installation
Figure 19 ­Rear Vent Application Maximum Horizontal Distance
Only one 45 degree elbow is allowed in these installa-
tions.
1. Rigid vent pipes and fi ttings have special twist-lock connections. Assemble the desired combination of pipe and elbows to the appliance adapter.
Twist-Lock Procedure: The female ends of the pipes
and fi ttings have three (3) locking lugs (indentations). These lugs will slide straight into matching slots on the male end of adjacent pipes and fi ttings. Push the pipe sections together and twist one section clockwise approximately one-quarter turn until the sections are fully locked. Figure 20
NOTE: Seal-
ant is not required to assemble fireplace venting. Do not use sili­cone sealant at the inner ue exhaust connec­tions.
Female Locking Lugs
NOTE: Horizontal runs of vent must be supported every three feet (914 mm). Use wall straps for this purpose.
Male Slots
Figure 20 ­Rigid Vent Pipe Con­nections
2. Refer to venting and termination instructions for further instructions.
3. Locate and cut the vent opening in the wall. For com­bustible walls fi rst frame in opening.
1
Combustible Interior Walls: Cut a 12
/2" x 101/2" hole
through the interior wall.
Combustible Exterior Walls: Cut a 101/2" x 101/2"
square hole through the exterior wall frame. Figure 21
Noncombustible Walls: Hole opening should be 81/2"
(216 mm) in diameter.
4. The center of the hole should align with the center line of the horizontal rigid vent pipe end. Allow 1/4" minimum rise per foot. Figure 21
Vent Opening for Combustible Walls
101⁄2”
(267 mm) Min.
101⁄2”
(267 mm)
Min.
Fireplace Hearth
Opening for Noncombustible Wall
81⁄2”
(216 mm)
Figure 21 - Locate vent opening on wall
Fireplace Hearth
Framing Detail
FP2293
5. Apply a bead of non-hardening mastic around the outside edge of vent cap. Position the vent cap in the center of hole on the exterior wall with the word "UP" on the vent cap facing up. Insure proper clearance of 1" to combustibles is maintained. Attach the vent cap with four (4) wood screws supplied. Figure 22
NOTE: Replace the wood screws with appropriate
fasteners for stucco, brick, concrete or other types of siding.
For vinyl siding, stucco or wood exterior, use vinyl
siding standoffs between vent cap and exterior wall for Duravent or Selkirk Terminations only . The vinyl siding standoff prevents excessive heat from melting the vinyl siding material. NOTE: Vermont Castings Group Termination does not require standoff. Bolt the vent cap to the standoff or wall. Apply non-hardening mastic around outside edge of the standoff instead of the vent cap assembly . Use wood screws provided to attach the standoff. Figure 23
20
20306750
Page 21
VENTING INSTALLATION
HOT
Vent Cap
Designer Series Direct Vent Gas Fireplace
Inerior Wall
Surface Vent Cap (Horizontal Termination)
Firestop
Apply Mastic to all Four Sides
Figure 22 ­Install Horizontal Termination
Cut Vinyl Siding Away to Fit Standoff
Apply Mastic to all Four Sides
FP1956
Figure 23 ­Install Duravent/Selkirk Vinyl Siding Standoff and Termination
Nut
Wood Screw
Wood Screw
Standoff #1250 or 5DT-VS (Not required for Vermont Castings Group termination)
HOT
Bolt
6. Slide the stop over the vent pipe before connecting the horizontal run to the vent cap. Figure 24
7. Carefully move the fireplace with vent assembly attached toward the wall and insert the vent pipe into the horizontal termination. The pipe overlap should
1
be a minimum of 1
/4". Apply silicone to the outer pipe connection. Fasten all vent connections with screws provided.
8. Slide the wall thimble against the interior wall surface and attach with screws. Figure 24
Termination
FP1957
Screw
Figure 24 ­Install Firestop on Horizontal Vent Pipe
Do not recess vent termination into any wall. This will cause a fi re hazard.
WARNING
All rear vent through-the-wall applications must use Vermont Castings Group-designed 5 x 8 square termination. No other manu-
facturer's termination is permitted in this
NOTICE
application.
For more information, follow instructions provided with terminations.
NOTICE
Horizontal Vent Pipe
20306750
21
Page 22
Designer Series Direct Vent Gas Fireplace
VENTING INSTALLATION
When installing the appliance as a rear vent unit, the 90° or 45° transition elbow attached directly to the rear of the unit is NOT INCLUDED in the following criteria and calculations and, unless specifi cally mentioned, should be ignored when
WARNING
calculating venting layouts.
HORIZONTAL WITH VERTICAL RISE (THROUGH-THE-WALL) TERMINATION CONFIGURATIONS
Since it is very important that the venting system maintain its balance between the combustion air intake and the fl ue gas exhaust , certain li mitations as to vent confi gurations a pply an d must be s tric tly adhered to.
The Vent Graph, showing the relationship between vertical and horizontal side wall venting, will help to determine the various dimensions allowable. Figure 18
Minimum clearance between vent pipes and combustible materials is 3" on top and 1" from bottom and sides unless otherwise noted (Exception: Outside wall with fi restop: 1" all around pipes are allowed). If the vertical run is 7.5 feet or more, from the fl oor of the fi replace, the clearance is 1" on all sides of the horizontal run.
When vent termination exits through foundations less than 20" below siding outcrop, the vent pipe must be fl ush with the siding.
It is best to locate the fi replace in such a way that minimizes the number of offsets and horizontal vent length.
The horizontal vent run refers to the tot al length of vent pipe from the fl ue collar of the fi replace (or the top of the Transition Elbow) to the face of the fi nished outside wall or the mounting fl ange of the termination.
3 x 90° Elbows
Figure 25 ­Maximum Three (3) 90° Elbows Per Installation
Figure 26 ­Maximum Horizontal Run with No Rise
A
3 x 90° Elbows
FP1176
36"
(914 mm)
Max.
FP1177
90°
B
The maximum number of 90° elbows per side wall
installation is three (3). Figure 25
If a 90° elbow is fi tted directly on the top of the fi replace,
the maximum horizontal vent run before the termination or a vertical rise is 36” (914 mm). Figure 26
If a 90° elbow is used in the horizontal vent run (level
height maintained) the horizontal vent length is reduced by 36". Figure 23. This does not apply if the 90° elbows are used to increase or redirect a vertical rise. Figure
27
Example: According to the vent graph (Page 19) the maximum horizontal vent length in a system with a 7.5' vertical rise is 20’ (6 m) and if a 90° elbow is required in the horizontal vent it must be reduced to 17' (5.2 m).
In Figures 27 and 28 dimension A plus B must not be greater than 17' (5.2 m).
22
Figure 27 ­Horizontal Run Reduction
7’6”
FP2837
20306750
Page 23
5
8
VENTING INSTALLATION
A
10'
7'6"
Figure 28 ­Maximum Vent Run with Elbows
Horizontal 90° Elbow =
3' Reduction
A + B = 17' Maximum
FP2838
Designer Series Direct Vent Gas Fireplace
HORIZONTAL WITH VERTICAL RISE (THROUGH-THE-WALL) APPLICATIONS
B
1. Locate and cut the vent opening in the wall. For
7'
combustible walls fi rst frame in opening.
Combustible Interior Walls: Cut a 121⁄2"H x 101⁄2" W
hole through the interior wall.
Combustible Exterior Walls: Cut a 101⁄2"H x 101⁄2"W
square hole through the exterior wall frame. Figure 25
Noncombustible Walls: Hole opening should be 81⁄2"
(216 mm) in diameter.
2. The center of the hole should line up with the center line of the horizontal rigid vent pipe end. Allow 1/4" minimum rise per foot. Figure 30
Vent Opening for Combustible Walls
10Z\x”
(267 mm) Min.
101⁄2”
(267 mm)
Min.
The maximum number of 45° elbows permitted per side
wall installation is two (2). These elbows can be installed in either the vertical or horizontal run.
For each 45° elbow installed in the horizontal run, the
length of the horizontal run MUST be reduced by 18" (457 mm). This does not apply if the 45° elbows are installed on the vertical part of the vent system.
The maximum number of elbow degrees in a system is
270°. Figure 24
1 2 3 4
1 + 2 + 3 + 4 = 270°
1 2 3 4
Fireplace Hearth
Opening for Noncombustible Wall
8Z\x”
(216 mm)
Figure 30 - Locate vent opening on wall
Fireplace Hearth
Framing Detail
FP2293
You may use a reducer from 5" x 8" to 4" x 6
" or 4" x 7" for horizontal with vertical rise applications. ONLY use framing instructions below when using 4" x 65⁄8" or 4" x 7" venting.
If the reducer is installed at the rear of the unit, you must immediately follow with a 90 elbow for a vertical rise before continuing
WARNING
with any horizontal run. There is a minimum total height of 7 feet from the fi replace fl oor to the last section of pipe before horizontal run. Refer to graph on Page 19.
Figure 29 ­Maximum Elbow Usage
20306750
FP2307
NOTE: #1222DA reducer must be used when 4 x 65⁄8" venting is preferred. #7TDVP58 reducer must be used with 4" x 7" venting is preferred. Reducer must be installed directly onto unit at the fi repalce collar before vertical rise.
23
Page 24
Designer Series Direct Vent Gas Fireplace
1
VENTING INSTALLATION
1. Locate and cut the vent opening in the wall. For com­bustible walls fi rst frame in opening.
Combustible Interior Walls: Cut a 111⁄2"H x 91⁄2" W
hole through the interior wall.
Combustible Exterior Walls: Cut a 9
⁄2"H x 91⁄2"W
square hole through the exterior wall frame. Figure 31
Noncombustible Walls: Hole opening should be 71⁄2"
(190 mm) in diameter.
2. The center of the hole should line up with the center line of the horizontal rigid vent pipe end. Allow 1/4" minimum rise per foot. Figure 31
Vent Opening for Combustible Walls
91⁄2”
(241 mm) Min.
91⁄2”
(241 mm)
Min.
Fireplace Hearth
Opening for Noncombustible Wall
Framing Detail
1. Establish vent hole through the wall.
2.
Remove soil to a depth of approximately 16" below base of snorkel. Install drain pipe. Install window well (not supplied). Refi ll hole with 12" of coarse gravel leaving a clearance of approximately 4" below snorkel. Figure 32
3. Install vent system.
4. Ensure a watertight seal is made around the vent pipe coming through the wall.
5. Apply high temperature sealant caulking (supplied) around the 5" and 8" snorkel collars.
6. Slide the snorkel into the vent pipes and secure to the wall.
7. Level the soil so as to maintain a 4" clearance below snorkel. Figure 32
Screws
Firestop
Minimum 4" Clearance
Ground
24"
Minimum
Window Well
Gravel
71⁄2”
(190 mm)
Figure 31 - Locate vent opening on wall
Fireplace Hearth
FP2293
BELOW GRADE INSTALLATIONS
When it is not possible to meet the required vent terminal clearances of 12" above grade level, a snorkel kit is recom­mended. It allows installation depth down to 7" (178 mm) below grade level. The 7" (178 mm) is measured from the center of the horizontal vent pipe as it penetrates through the wall.
Ensure that sidewall venting clearances are observed. If venting system is installed below ground, we recom­mend a window well with adequate and proper drainage to be installed around the termination area.
If installing a snorkel, a minimum 24" vertical rise is nec­essary. The maximum horizontal run with the 24” vertical pipe is 36". This measurement is taken from the collar of the fi replace (or transition elbow) to the face of the exterior wall. Refer to the Sidewall Venting Graph for extended horizontal run if the vertical exceeds 24".
Figure 32 - Below Grade Installation
If the foundation is recessed, use recess brackets (not supplied) for securing lower por­tion of the snorkel.
Foundation Recess
Fasten brackets to wall first, then secure to snorkel with self drilling #8 x 1/2 sheet metal
Watertight Seal Around Pipe
screws. It will be necessary to extend vent pipes out as far as the protrud­ing wall face. Figure
33
Figure 33 ­Snorkel Installation,
Recessed Foundation
Drain
Foundation Wall
FP1965
Snorkel
Wall Screws
Sheet Metal Screws
FP1966
24
20306750
Page 25
VENTING INSTALLATION VERTICAL THROUGH-THE-ROOF
APPLICATIONS
A restrictor disc must be installed on vertical terminations that are higher than 12' (366 cm).
NOTICE
Install restrictor disc as shown in Figure 34 for vertically vented applications.
Up to two (2) restrictor discs may be needed for 40' instal­lation.
The two (2) restrictor discs suppled will work for most instal­lations. If a third disc is needed order Part No. 56D3027.
Y ou may use a reducer to 4" x 65⁄8" or 4" x 7" in vertically vented applica­tions. If a reducer is used, only one restrictor may be used.
Restrictor Disc
Designer Series Direct Vent Gas Fireplace
10'
Maximum
40' Maximum Height 8' Minimum Height
Support Straps Every 3'
Fireplace Collar
Figure 34 ­Install Restrictor Disc into Fireplace Collar
FP2839
This gas fi replace has been approved for,
Vertical installations up to 40' (12 m) in height. Up to
a 10' (3 m) horizontal vent run can be installed within the vent system using a maximum of two 90° elbows.
Figure 35
NOTE: Horizontal sections of this vent system require a minimum of 3" clearances to combustibles at the top of the fl ue and 1" clearance at the sides and bottom until the ue penetrates the outside wall. A minimum 1" clearance all around the fl ue is acceptable at this point of penetration. Unless the vertical run is 71⁄2 feet or higher form fl oor of replace, the clearance for the horizontal run is 1" on all sides.
Vertical sections of this vent system require a minimum of 1" clearance to combustibles on all sides of the pipe.
10'
Maximum
40' Maximum Height 8' Minimum Height
Support Straps Every 3'
FP2308
Figure 35 ­Support Straps for Horizontal Runs
Example: Maximum horizontal length No elbows = 10’ (3 m)
1x45° elbows = 8.5’ (2.6 m) 2x45° elbows = 7’ (2.1 m)
A minimum of an 8' (2.5 m) vertical rise is required.
Two sets of 45°elbows offsets may be used within the
vertical sections. From 0 to a maximum of 8' (2.5 m) of vent pipe can be used between elbows. Figure 27
The maximum angular variation allowed in the system
is 270°. Figure 27
For the minimum height of the vent above the highest
point of penetration through the roof refer to Page 27, Figure 40.
Up to two 45° elbows may be used within the horizontal
run. For each 45° elbow used on the horizontal plane, the maximum horizontal length must be reduced by 18" (457 mm).
20306750
25
Page 26
Designer Series Direct Vent Gas Fireplace
1
2
1
2
1
2
1
2
1
2
1 2 3 4
1 2
Example: Elbow 1 = 90° Elbow 2 = 45° Elbow 3 = 45° Elbow 4 = 90° Total Angular Variation = 270°
3 4
VENTING INSTALLATION
Roof Flashing
Wall Strap
45° Elbows
FP1669
Ceiling Firstop
Figure 37 ­Offset with Wall Strap and 45° Elbows
Figure 36 ­Maximum Elbow Usage
INSTALLATION FOR VERTICAL TERMINA­TION
1. Determine the route your vertical venting will take. If ceiling joist, roof rafters or other framing will obstruct the venting system, consider an offset. Refer to Figure 32 to avoid cutting load bearing members.
NOTE: Pay special attention to these installation instructions for required clearances (air space) to combustibles when passing through ceilings, walls, roofs, enclosures, attic rafters, etc. Do not pack air spaces with insulation. Also note maximum vertical rise of the venting system and any maximum horizontal offset limitations. Offsets must fall within the parameters shown on Page 19, Figure 18.
2. Set fi replace in desired location. Drop a plumb line down from the ceiling to the position of the fl ue exit. Mark the center point where the vent will penetrate the ceiling. Drill a small locating hole at this point.
Drop a plumb line from the inside of the roof to the locat-
ing hole in the ceiling. Mark the center point where the vent will penetrate the roof. Drill a small locating hole at this point.
FLAT CEILING INSTALLATION
1. Cut a 10 the locating hole as a center point The opening should
be framed to 10 dimensions as shown in Figure 39 using framing lumber the same size as the ceiling joist. If the area above the ceiling is an insulated ceiling or a room, nail fi restop from the top side. This prevents loose insulation from falling into the required clearance space. Figure 39. Otherwise, install fi restop below the framed hole. The restop should be installed with no less than three (3) nails per side. Figure 38 or 39.
2. Assemble the desired lengths of pipe and elbows nec­essary to reach from the burner system fl ue up through the fi restop. Be sure pipe and elbow connections are fully twist-locked. Page 20, Figure 20.
3. Cut a hole in the roof using the locating hole as a center point. (Cover any exposed open vent pipes before
cutting hole in roof). The 10 hole must be measured on the horizontal. Actual length may be larger depending on the pitch of the roof. There must be a 1" minimum clearance from the vent pipe to combustible materials. (Insulation should be considered a combustible material). Frame the opening as shown on Page 20, Figure 21.
4. Connect a section of pipe and extend up through the hole.
" (267 mm) square hole in the ceiling using
" x 10
" (267 x 267 mm) inside
" x 10
" (267 x 267 mm)
26
20306750
Page 27
VENTING INSTALLATION
Designer Series Direct Vent Gas Fireplace
Nails
Firestop
Figure 38 ­If Area Above is a Room, Install Firestop above Framed Hole as Shown
10
10
"
1
2
/
1
/
2
"
NOTE: If the vent pipe passes through any occupied areas above the fi rst fl oor, including storage spaces and closets, you must enclose pipe. You may frame and sheetrock the enclosure with standard construction material. Make sure to meet the minimum allowable clearances to combustibles. Do not fi ll any of the required clearance spaces with insulation.
Horizontal Overhang
2 ft. Min.
Termination Vent
Storm Collar
Flashing
2 ft. Min.
Lowest Discharge Opening
H*
Vertical Wall
12
X
FP1971
FP1970
Nails
Figure 39 ­If Area Above is Not a Room, Install Firestop above Framed Hole as Shown
Firestop
NOTE: If an offset is needed to avoid obstructions, you must support the vent pipe every three (3) feet. Use wall straps for this purpose. Refer to Page 26, Figure 37. Whenever possible, use 45° elbows instead of 90° elbows. The 45° elbow offers less restriction to the fl ow of the fl ue gases and intake air.
5. Place the fl ashing over the pipe section(s) extending through the roof. Secure the base of the fl ashing to the roof and framing with roofi ng nails. Be sure roofi ng material overlaps the top edge of the fl ashing. There must be a 1" clearance from the vent pipe to combus­tible materials.
6. Continue to add pipe sections until the height of the vent cap meets the minimum requirements below.
NOTE: You must increase vent height for steep roof pitches. Nearby trees, adjoining roof lines, steep pitched roofs, and other similar factors may cause poor draft or down-drafting in high winds. Increasing the vent height may solve this problem.
Concentric Vent Pipe
Figure 40 ­Minimum Chimney Clearance
Roof Pitch H (feet) Flat to 6/12 1.0 Over 6/12 to 7/12 1.25 Over 7/12 to 8/12 1.5 Over 8/12 to 9/12 2.0 Over 9/12 to 10/12 2.5 Over 10/12 to 11/12 3.25 Over 11/12 to 12/12 4.0
*H - Minimum height from roof to lowest discharge opening of vent
1" Minimum Clearances to Combustibles
20306750
27
Page 28
Designer Series Direct Vent Gas Fireplace
3
3
4
3
4
VENTING INSTALLATION
FLEX VENT INSTALLATION
1. Flexible UL1777 listed venting may be used in any venting application where rigid direct vent components can be used. All restrictions, clearances and allow-
ances that pertain to the rigid piping apply to the
exible venting. Flex kits may not be modifi ed. Flex kits may be added to the end of a vent run made of rigid vent sections using pipe manufacturer's approved fl ex to pipe adapters. This may occur only if doing so does not violate any of the venting length, height, routing, horizontal to vertical ratio requirements or clearance considerations detailed in this manual.
5" x 8" Flex Vent Pipe
2. The ex adapter starter kit (DVFF8A/8) is used to attach ex venting to the appliance starting collar. It includes
5" inner and 8" outer adapter rings. Figure 41
The inner and outer adapter rings are required to
start all fl ex runs.
Never install damaged or torn fl exible venting.
Over tightening clamps may rip, tear, or otherwise
damage fl exible venting.
The adapter kit does not include individual pipe sec-
tions which may be purchased separately . (UL1777 listed type venting only.)
3. Start the fl exible vent as follows: A. Installing the inner fl ex adapter and pipe. Figure
UL1777 Flex Vent
1
⁄4" Flexible
Pipe and Adapter Outer
DVFF8A/8 Inner Adapter Outer Adapter
Appliance Starting Collar
Figure 41 ­Typical 5" x 8" Appliance Connection
equidistant just
Flex vent pipe spacers: Refer to manufacturer’s specifi cations for correct positioning of the spacer springs to maintain proper distance
NOTE
between inside and outside pipe.
41
Screws
(3 places,
above gear
clamp)
1. Insert the long side of the 5" inner ring into exhaust pipe, gently tap to seat into place, and secure with screws.
2. Slide the small gear clamp over the inner fl exible vent pipe, and push out of the way.
3. Pull and extend the inner fl exible vent.
4. Slide the inner vent onto the adapter collar, for a
minimum 1
" overlap.
5. Locate the clamp at approximately 3/4" from the fl ex end and tighten.
6. Secure the clamped inner section with three self­tapping screws, drilled equidistant, just above the clamp perimeter.
B. Installing the outer fl ex pipe. Figure 41
1. Firmly insert the 8" outer adapter ring into the outer appliance starting collar and secure with screws.
2. Slide the large gear clamp over the outer fl exible vent pipe, and push out of the way.
3. Pull and extend the outer fl exible vent.
4. Slide the outer vent onto the appliance collar outer adapter for a minimum 1
" overlap.
5. Locate the clamp at approximately 3/4" from the ex end and tighten.
6. Secure the clamped outer section with three self­tapping screws, drilled equidistant, just above the clamp perimeter.
C. Routing UL1777 fl ex pipe.
1. Always maintain the required clearance when routing the fl ex vent assembly.
2. Install fi restop spacers, Figure 43, when penetrat- ing ceiling, attic spaces, or walls.
3. Do not allow the fl exible vent to bend in radius tighter than 5" (127 mm). Figure 42
4. Horizontal runs of fl exible vent shall be supported at maximum 2 foot intervals;
UL1777 Flex Vent
vertical runs, five feet inter­vals. Metal strapping, prop­erly secured, is
5° Radius
an acceptable means to sup­port the fl exible vent.
Figure 42 ­Minimum Radius for Flex Vent Section
5. Flexible vent spacers are to be installed at intervals prescribed by the fl exible vent manufacturer; and in such a way as to maintain concentric inner and outer vent spacing.
28
20306750
Page 29
3
VENTING INSTALLATION
Designer Series Direct Vent Gas Fireplace
D. Attaching fl exible venting to vertical termination
assemblies.
1. When using Duravent pipe, an Vermont Cast­ings Group fl ex-to-pipe adapter and/or rigid pipe section(s) is required to connect the fl exible vent assembly to the vertical termination by using three self-penetrating screws.
2. Review Figure 44 and corresponding instruc- tions for proper overlap, clamp and screw place­ment.
3. Three each self-penetrating screws are drilled opposite one another and below the gear clamp.
4. Use only listed and approved terminations and accessories, installed per the installation instruc­tions and Figure 43.
Termination Cap
Flashing
Rigid Pipe Length
Flex to Pipe Adapter
Storm Collar
Roof Support
E. Installing fl exible venting to horizontal termination
assemblies.
1. Connect the 5" fl exible vent to the horizontal termination as in Figure 45.
2. Connect the 8" fl exible vent to the termination ring as in Figure 45.
3. Review Figure 45 for proper overlap and clamp placement.
4. Three each self-penetrating screws are drilled opposite one another and below the gear lamp.
5. Use only listed an approved terminations and accessories, installed per the termination instruc­tions and Figure 45.
Rigid Pipe Length
Screws (3 Places equidistant just above gear clamp)
Gear Clamp
Flex to Pipe Adapter
Gear Clamp
13⁄4" Flexible Pipe and Adapter Outer Collar Overlap
UL1777 Flex Vent
Firestop
DVFF8A/8 5" x 8" to 5" x 8" Flex Adapter
UL1777 Flex PIpe
FP1974
Figure 43 ­Typical Vertical Flex Vent Installation
20306750
Figure 44 ­Typical Pipe Connection
Screws (3 Places equidistant just above gear clamp)
UL1777 Flex Vent
Figure 45 ­Typical Horizontal Flex Vent Installation
Gear Clamp
Vermont Castings Group Horizontal Vent Termination
1
⁄4" Flexible Pipe and
Collar Overlap
29
Page 30
Designer Series Direct Vent Gas Fireplace
3
3
VENTING INSTALLATION
4" x 7" Flex Pipe
If you prefer to use 4" x 7" fl ex pipe, you must install model 7TDVP58 reducer (5" x 8" to 4" x 7") onto the fi replace collar. Then follow the the assembly guidelines for 5" x 8" ex venting.
UL1777 Flex Vent
1
⁄4" Flexible
Pipe and Adapter Outer
5" x 8" to 4" x 7" Adapter (7TDVP58)
Figure 46 ­Typical 4" x 7" Appliance Connection
FP1972a
Gear Clamp
Appliance Starting Collar
Screws (3 places, equidistant just above gear clamp)
Termination Cap
Flashing
Rigid Pipe Length
Flex to Pipe Adapter (DVFFA/8)
Firestop
7TDVP58 5" x 8" to 4" x 7" Reducer
Storm Collar
Roof Support
UL1777 Flex PIpe
FP1974
Figure 47 ­Typical Vertical Flex Vent Installation
Screws (3 Places equidistant just above gear clamp)
Screws (3 Places equidistant just above gear clamp)
UL1777 Flex Vent
4" x 7" Rigid Pipe Length
Flex to Pipe Adapter (DVFFA/8)
Gear Clamp
13⁄4" Flexible Pipe and Adapter Outer Collar Overlap
Gear Clamp
UL1777 Flex Vent
Figure 48 ­Typical Pipe Connection
Vermont Castings Group Horizontal Vent Termination
1
⁄4" Flexible Pipe and
Gear Clamp
Collar Overlap
Figure 49 ­Typical Horizontal Flex Vent Installation
30
20306750
Page 31
FIREPLACE INSTALLATION CHECK GAS TYPE
Use proper gas type for the fi replace you are installing. If you have confl icting gas type, do not install fi replace. See dealer where you purchased the fi replace for proper
replace according to your gas type.
INSTALLING GAS PIPING TO FIREPLACE LOCATION
A qualifi ed installer or service person must connect appliance to gas supply . Follow all local codes.
WARNING
INSTALLATION ITEMS NEEDED
Before installing fi replace and burner system, make sure you have the items listed below.
• External regulator • Tee joint
• Piping (check local codes) • Pipe wrench
• Sealant (resistant to propane/LP gas) (supplied by installer)
• Test gauge connection*
• Sediment trap (recommended)
• Equipment shutoff valve*
• approved fl exible gas line with gas connector (if allowed by local codes — not provided)
* A CSA design-certifi ed equipment shutoff valve with
1/8" NPT tap is an acceptable alternative to test gauge connection. Purchase the CSA design-certifi ed equip- ment shutoff valve from your dealer.
For propane/LP connections only , the installer must supply an external regulator. The external regulator will reduce incoming gas pressure. You must reduce incoming gas pressure to between 11 and 13 inches of water. If you do not reduce incoming gas pressure, burner system regulator damage could occur. Install external regulator with the vent pointing down as shown in Figure 50. Pointing the vent down protects it from freezing rain or sleet.
For propane/LP units, never connect replace directly to the propane/LP supply . This burner system requires an external regulator (not supplied). Install the external regulator between the burner system and
CAUTION
propane/LP supply.
Designer Series Direct Vent Gas Fireplace
100 gal. (min)
External Regulator
Figure 50 ­External Regulator with Vent Pointing Down (Propane/LP Only)
Propane/LP Supply Tank
Vent Pointing Down
FP1977
Use only new black iron or steel pipe. Internally tinned copper or copper tubing can be used per National Fuel Code, Section
2.6.3, providing gas meets hydrogen sulfi de limits, and where permitted by local codes. Gas piping system must be sized to provide minimum inlet pressure (listed on data plate)
CAUTION
at the maximum fl ow rate (BTU/hr). Undue pressure loss will occur if the pipe is too small.
External regulators may be necessary for natural gas. One- or two-pound systems will damage this appliance and may cause re hazard.
WARNING
When using copper or fl ex connectors use only fi ttings approved for gas connections. The gas control inlet is 3/8" NPT.
20306750
31
Page 32
Designer Series Direct Vent Gas Fireplace
FIREPLACE INSTALLATION
GAS SUPPLY LINE INSTALLATION
Only persons licensed to work with gas piping may make the necessary gas connections to this appliance.
WARNING
NOTE : The gas line connection may be made using 1/2"
rigid tubing or an approved fl ex connector. Since some municipalities have additional local codes it is always best to consult your local authorities and the current edition of the National Fuel Gas Code ANSI.Z223.1, NFPA54. In Canada CSA-B149 (1 or 2) Installation Code.
A listed manual shutof f valve must be installed upstream of the appliance. Union tee and plugged 1/8" NPT pressure tapping point should be installed upstream of the appli­ance. Figure 51
IMPORTANT: Install main gas valve (equipment shutoff valve) in an accessible location. The main gas valve is for turning on or shutting off the gas to the fi replace.
Check your building codes for any special requirements for locating equipment shutoff valve to fi replaces.
Apply pipe joint sealant lightly to male threads. This will prevent excess sealant from going into pipe. Excess seal­ant in pipe could result in clogged burner system valves.
A manual shutoff valve must be installed upstream of the appliance. Union tee and plugged 1/8" NPT pressure tapping point should be installed upstream of the
CAUTION
appliance. Figure 51
We recommend that you install a sediment trap/drip leg in supply line as shown in Figure 51. Locate sediment trap/drip leg where it is within reach for cleaning. Install in piping system between fuel supply and burner system. Locate sediment trap/drip leg where trapped matter is not likely to freeze. A sediment trap traps moisture and contami­nants. This keeps them from going into the burner system gas controls. If sediment trap/drip leg is not installed or is installed wrong, burner system may not run properly.
Use pipe joint sealant that is resistant to liquid petroleum (LP) gas.
CAUTION
Approved Flexible Gas Line
Sediment Trap/Drip Leg
Figure 51 ­Gas Connection
CSA Design-Certifi ed Equipment Shutoff Valve with 1/8" NPT Tap*
Tee Joint
Pipe Nipple
3" Minimum
Cap
Natural Gas
From Gas Meter
(4.0" w.c. to 10.5" w.c. Pressure)
Propane/LP
From External Regulator
(11" w.c. to 13" w.c. Pressure)
32
20306750
Page 33
FIREPLACE INSTALLATION
Designer Series Direct Vent Gas Fireplace
CHECK GAS PRESSURE
1. Check gas type. The gas supply must be the same as stated on the appliance’s rating decal. If the gas supply is different from the fi replace, STOP! Do not install the appliance. Contact your dealer immediately.
2. T o ease installation, a 24" (610 mm) fl ex line with manual shut-off valve has been provided with on this appliance. Install and attach 1/2" gas line onto shut-off valve.
3. After completing gas line connection, purge air from gas line and test all gas joints from the gas meter to the replace for leaks. Use a solution of 50/50 water and soap solution or a gas sniffer.
4. To check gas pressures at valve, turn captured screw counter clockwise 2 or 3 turns and then place tubing to pressure gauge over test point. Turn unit to high. Figure 52. After taking pressure reading, be sure and turn captured screw clockwise fi rmly to reseal. Do not over torque. Check test points for gas leaks.
ELECTRICAL WIRING
General
1. This fi replace is equipped with the Signature Control valve which operates on 6 volts. The 6 volt DC adapter plugs into the fi replace junction box A/C power supply. Four (4) “AA” batteries are used for back up during power outages.
2. The Signature Command System can also be operated without A/C power . The system can run on four (4) “AA” batteries for approximately six (6) months under normal use.
3. A/C power must be used to power the A/C module, blowers, lights and AUX accessories if used with this replace.
Optional Accessory Requirements
1. This fi replace may be used with a wall switch, wall mounted thermostat and/or Signature Command wire­less controls.
2. The command center control may be mounted on the wall with the use of the SCSWEK 15ft. wall mount extension kit.
Pressure Inlet
Pressure Outlet
Figure 52 ­Signature Command Valve
Pilot Adjustment Screw
Do not use open fl ame to check for gas leaks.
WARNING
Electrical connections should only be performed by a qualified, licensed electrician. Main power must be off when connecting to main electrical power supply or performing service. All wiring shall be in compliance with all local, city and state codes. The appliance, when installed, must be electrically grounded in accordance with
WARNING
local codes or in the absence of local codes, with the National Electrical Code ANSI/NFP A 70 (latest edition) and Canadian Electrical Code, CSA C22.1.
FP1909a
20306750
Label all wires before disconnecting when servicing controls. Wiring errors can cause improper and dangerous operation.
CAUTION
33
Page 34
Designer Series Direct Vent Gas Fireplace
JUNCTION BOX WIRING
1. This should be done before framing the fi replace. Wire the receptacle into an electrical circuit. Wire with mini­mum 60° C wire in accordance with prevailing codes.
2. Remove the external junction box cover by removing the screw from the side of the outside fi rebox wall. Junction box was installed at the factory.
3. The junction box cover has a factory installed “romex” style strain relief connector. After connecting the wires, route the wire leads through this connector. Refer to the wiring diagram in Figure 53.
FIREPLACE INSTALLATION
120V AC
60Hz
Factory Supplied Not Supplied
Junction Box
Figure 53 ­Junction Box Wiring Diagram
COMMAND CENTER WALL INSTALLATION
The command center may be mounted on the wall with the use of the SCSWEK Kit (15ft. cable, junction box, wall cover).
Mount the junction box provided at the desired location on the wall. Do not extend beyond the 15 ft. wire cable provided. If a longer distance is required, the 15 ft. may be extended up to 30 ft. maximum by using two (2) SCSWEK cables plugged together.
Route the wire from junction box to lower control area at bottom of fi replace. Unplug the 12" cable from the com- mand center. Attach the connector to the pins from wire by pushing in to connector making sure to follow the color code on connector. Plug the 15 ft. extension cable into the 2 ft. cable. Remove command center from the fi replace and plug the other end of the extension cable into the command center. Snap on wall cover provided and screw to junction box.
WALL SWITCH INSTALLATION
The wall switch wire connection is located off the 2 ft. wire harness from the control box to the command center. Fig- ure 54. The connection is labeled “Wall Switch”. Unplug the male and female connectors and connect the two (2) low voltage wires provided. Run wire to desired location on wall. Up to 50 ft. of 18 ga. wire may be used if neces­sary. Attach wires to wall switch. Mount the wall switch in to junction box and screw on cover.
Do not connect wall switch to 110 V circuit.
WARNING
34
20306750
Page 35
FIREPLACE INSTALLATION
Designer Series Direct Vent Gas Fireplace
To Junction Box in Fireplace
Optional
White
Light
{
White Black
Optional
Aux.
{
Black
White Black
Green
Optional
{
Blower
Input 300 Watt Max. Each
Optional A/C Module Replaces 6V Adapter When Used
6V AC Adapter
NOTE: Wall switch wires must be con­nected together if a wall switch is not being used.
Gas In
Plug in
Connector
Optional
AC Module
Connector Pin
To Control Board
Control Board
Conversion NG/LP
Plug-in Connector Stepper Motor to
Ground
Plug-in Connector Control Board to Solenoid
Control Board
DC Power/Green
RF Receiver ON/OFF Button
Black / Thermopile Red / Thermopile
Sensor
Ignitor / Sparker
Plug-in Connector Control Board to Command Center
OFF/LO
LED
ON/HI
Master Switch
Command Center
Gas Out
Pilot
Optional
Wall Switch
Figure 54 ­Signature Command Wiring Diagram
Electrical connections should only be performed by a qualifi ed, licensed electrician. Main power supply must be turned off before connecting fans to the main electrical power
CAUTION
supply or performing service.
20306750
Pilot Gas Tubing
Valve
35
Page 36
Designer Series Direct Vent Gas Fireplace
FIREPLACE INSTALLATION
Electrical Grounding Instructions: This appliance is equipped with a three-prong (grounding) plug for your protection against shock hazard and should be plugged directly into a properly grounded three-prong
WARNING
receptacle.
Electrical connections should only be performed by a qualifi ed licensed electrician. Main power supply must be turned off before connecting the fan to the main electrical power supply or performing service.
WARNING
The black and white wires on the AC box wiring harness are marked ‘Blower’, ‘Light’ and ‘Aux’. It is important to use the wires marked ‘Blower’ or the control will not work
NOTE
correctly.
BLOTSTSC SIGNATURE COMMAND SINGLE BLOWER
To Junction Box In Fireplace
Blower (300w Max)
BLACK
Light
WHITE
Optional AUX
{
{
WHITE BLACK
BLACK WHITE
GREEN
Connector Pin To Contro l Box
AC Module
Blower (300w Max)
Figure 55 ­BLOTSTSC Blower Wiring Diagram (shown with 2 blower kits)
The BLOTSDVSC Blower Kit requires the SCSACM A/C Module and the TSFSC remote to install and operate this kit. Refer to blower instructions for installation.
NOTE: If two (2) blowers are required with the Signature Command System SCSACM & TSFSC remote, two (2) BLOTSTSC Kits must be purchased.
Control Board
FP2708
36
20306750
Page 37
FIREPLACE INSTALLATION
Designer Series Direct Vent Gas Fireplace
BLOTBLDV AUTOMATIC DUAL THERMOSTAT BLOWER
Receptacle
Junction
Box
120VAC
BLACK
GREEN
BLACKWHITE
Speed Control
Figure 56 ­BLOTBLDV Blower Wiring Diagram
Before installing the blower, wire the receptacle into an electrical circuit. This should be done before framing the replace. Wire with minimum 60° C wire in accordance with prevailing codes.
BLOTDL AUTOMATIC SINGLE THERMOSTAT BLOWER
Receptacle
Junction
Box
BLACKBLACKWHITE
FP2685
120VAC
BLACK
GREEN
BLACKWHITE
Speed Control
Figure 57 ­BLOTDL Blower Wiring Diagram
20306750
BLACKBLACKWHITE
37
Page 38
Designer Series Direct Vent Gas Fireplace
GLASS FRAME REMOVAL
FIREPLACE INSTALLATION
NOTE: Y ou must rst remove the safety barrier before you
remove the glass frame. To remove the barrier, simply lift up and pull out until the slots on the screen are clear of their corresponding tabs on the fi rebox. Then proceed to remove the glass frame by following the steps below.
1. Remove access panel by lifting up and out.
2. Release two clamps on bottom of fi replace. Figure 58
3. Tilt glass frame out and lift glass frame up until it clears three tabs on top of fi replace.
4. Set glass frame aside.
Each clamp has a quick spring force. When reinstalling clamps, keep fi ngers clear.
CAUTION
DANGER
HOT GLASS WILL
CAUSE BURNS.
DO NOT TOUCH GLASS
UNTIL COOLED.
NEVER ALLOW CHILDREN
TO TOUCH GLASS.
A barrier designed to reduce the risk of burns from
the hot viewing glass is provided with this
appliance and shall be installed.
Glass Frame
Figure 58 ­Remove Screen Barrier and Glass Frame
38
Safety Barrier
Access Panel
20306750
Page 39
ROCK WOOL PLACEMENT
Place rock wool evenly in dime-sized pieces over the burner ports. Do not place embers over the burner slots. T o better enable the gas to permeate the rock wool, apply the rock wool in light, dime size fl uffy pieces.
Designer Series Direct Vent Gas FireplaceFIREPLACE INSTALLATION
Rock Wool Areas
Pin used with Contemporary Stone Kit
Pin used with Contemporary Stone Kit
Log Placement Pins
Figure 59 ­Rockwool placement
Do not use the entire bag of rock wool to cover the burner. This could cause the fl ame to burn poorly and may lead to sooting.
WARNING
20306750
39
Page 40
Designer Series Direct Vent Gas Fireplace
FIREPLACE INSTALLATION
LOG PLACEMENT
1. Hold log #1 with the rounded end opposite the pilot. NOTE: Log #1 is designed to not be symmetrical. Place log #1 aligning the two (2) pins provided making sure to t the notches in the bottom of the log over the sides of the grate so that it sits fi rmly in place. The log will rest on the grate bar about 1/4" over the top of the burner surface. Figure 60
Log #1
Figure 60
2. Place log #2 so the fat end of the log rests on the 2nd tine of the grate (opposite the pilot) and the thin, right end of the log sits on top of the key provided on the end of log #1 closest to the pilot. Figure 61
Log #2
3. Position log #3 on the key provided on the rounded end of log #1. The other end sits on the "false-bottom hearth" (the sheet metal surrounding the burner and supporting the grate), just outside of the grate. The base of the log should be about 1" from the end of log #2. Figure 62
Log #3
False­Bottom Hearth
Figure 62
4. On the remaining key on the top of log #1 (in the center), place log #4 with the charred area of the log facing down and toward the nearest glass. The other end of the log rests on the second tine from the end closest to the pilot. Figure 63
Figure 61
40
Figure 63
LG968
Log #4
20306750
Page 41
FIREPLACE INSTALLATION
5. Place log #5 on the key provided on log #4. Rest the other end of the log on the "false-bottom hearth" just outside of the grate. It should be almost touching the end of log #1. Figure 64
Log #5
Figure 64
Designer Series Direct Vent Gas Fireplace
20306750
41
Page 42
Designer Series Direct Vent Gas Fireplace
CERTIFIED
FIREPLACE INSTALLATION
SAFETY BARRIER
SAFETY BARRIER INSTALLATION INSTRUCTIONS
NOTE: A barrier designed to reduce the risk of burns
from the hot viewing glass is provided with this appliance and shall be installed for the protection of children and other at risk individuals. If the barrier becomes damaged, the barrier shall be replaced with the manufacturer's barrier for this appliance.* Any safety screen, guard, or barrier removed for servicing the appliance must be replaced prior to operating the appliance.
* See parts list for model number.
WARNING: The safety screen barrier must be installed after the glass front is in place. It is NOT a replacement for the glass and the unit must NOT be operated without the glass in place.
Small Safety Barrier
DANGER
HOT GLASS WILL
CAUSE BURNS.
DO NOT TOUCH GLASS
UNTIL COOLED.
NEVER ALLOW CHILDREN
TO TOUCH GLASS.
A barrier designed to reduce the risk of burns from
the hot viewing glass is provided with this
appliance and shall be installed.
Install the Large Screen
Figure 65
1. Remove screen from packaging.
2. Align the three (3) slots in the top of the screen with the three (3) tabs on top of the fi rebox. These are the tabs on which the glass frame hangs. Slide the screen down onto the tabs.
3. Allow bottom of frame to swing down and attach to magnets which hold it in place.
Install the Small Screen (PFLDV, CRLDV, CLLDV)
Figure 65
1. Remove screen from packaging.
2. Remove the three (3) screws at the bottom of the glass frame.
3. Align the three (3) slots in the top of the screen with the three (3) tabs on top of the fi rebox. These are the tabs on which the glass frame hangs. Slide the screen down onto the tabs.
4. Allow bottom of frame to swing down and attach to magnets which hold it in place.
Figure 65
42
Large Safety Barrier
NOTICE: It is the responsibility of the installer to ensure the barrier is affi xed to the fi replace at the time of instal- lation.
20306750
Page 43
OPERATING INSTRUCTIONS
Designer Series Direct Vent Gas Fireplace
FOR YOUR SAFETY READ BEFORE LIGHTING
If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury or loss of lie.
WARNING
A. This appliance is equipped with an ignition device which automatically lights the pilot. Refer
to the instructions.
B. BEFORE OPERATING smell all around the appliance area for gas. Be sure to smell next to
the fl oor because some gas is heavier than air and will settle on the fl oor.
WHAT TO DO IF YOU SMELL GAS:
Do not attempt to light any appliance.
Do not touch any electric switch; do not use any phone in your building.
• Immediately call your gas supplier from a neighbor's phone. Follow the gas supplier's instructions.
If you cannot reach your gas supplier, call the fi re department.
C. Use only your fi nger to push in the master switch. Never use tools. If the switch will not func-
tion by hand, do not try to repair it. Call a qualifi ed service technician. Force or attempted repair may result in a fi re or explosion.
D. Do not use this appliance if any part of it has been under water. Immediately call a qualifi ed
service technician to inspect the appliance and to replace any part of the control system and any gas control that has been under water.
20306750
43
Page 44
Designer Series Direct Vent Gas Fireplace
OPERATING INSTRUCTIONS
OPERATING INSTRUCTIONS
1. STOP! Read the safety information above.
2. This appliance is equipped with an ignition device which automatically lights the burner. Do not try to light the burner by hand.
3. With fi ve (5) minutes to clear out any gas. Then smell for gas, including near the fl oor. If you smell gas, STOP! Follow "B" in the safety information on page 43. If you do not smell gas, go to next step.
4. Press the master switch to the "ON" (-) position. Within eight (8) seconds it will beep once. This indicates the system is ready.
5. Press "ON " button. Sparker will spark and pilot fl ame will light.
6. Once pilot fl ame is established, the main burner fl ame will light automatically.
7. If the pilot will not stay lit after several tries, turn the master switch to "OFF" and call your service technician or gas supplier.
OFF
OFF
OFF
ON
ON
Command Center
Master Switch
ON
TO TURN OFF GAS TO APPLIANCE
1. Turn master switch to "OFF".
2. Turn off all electrical power to the appliance if service is to be performed.
44
20306750
Page 45
SIGNATURE COMMAND SYSTEM OPERATION
Designer Series Direct Vent Gas Fireplace
FEATURES
Command Center
Easy Access Function Operation and System Confi gura-
tion
Operation Confi rmation/Fault Diagnostic Indications (LED/
Buzzer)
ON/OFF/HI/Med/Low Operation
Optional Wall Mounting
Control Board
Electronic Ignition
Pilot Lockout safety feature
Electric Power Regeneration from Thermopile to save bat-
tery
6-hour Automatic Shut Down Option
Convenient NG/LP Gas Type Conversion
Standing Pilot/Intermittent pilot Conversion
Previous settings Restoration Ability (Memory Off)
Uninterrupted Operation During Power Outage (Automatic
Battery Backup)
ON/OFF RF Remote Receiver
Optional Transmitter Learn Capability
AC Module Board (Optional, requires TSFSC Remote)
RF Receiver ON/OFF
NG/LP Conversion
Control Board
OFF
LED
ON
Master Switch
Command Center
Figure 65 ­Signature Command System Components
Battery Door
To Thermopile
To Sensor
To Command Center
To Stepper Motor
To Valve
To Sparker
Easy Snap-on Design
Embedded Compact 120 VAC Adapter with Auto Battery Back up Feature
Remote Controlled 3-step Blower, Lighting, and On/Off Auxiliary AC Outputs
Transmitter (Optional)
TSFSC TSTSC TSMSC RTSC RMSC Three Flame Height Settings X X X X X Low battery Indication for Transmitter X X X X X Child Proof Lock-out X X X X X LCD Backlight X X X X X Security Codes 16 X X X X X Countdown 6 hr Timer X X X -- -­Standard Thermostatic Control Mode X X -- X -­Smart Mode® Thermostat (Auto Flame & Blower Modulation) X X -- -- -­Three Brightness Settings for Lights X -- -- -- -­Three Speed Control for Blower X -- -- -- -­On/Off Auxiliary X -- -- -- -­Programmable Timer to turn blower on and off X -- -- -- --
BATTERY INSTALLATION
The Command Center uses four (4) "AA" batteries as back up for power outages. The system can operate for ap­proximately six (6) months on battery power.
To Install Batteries (not included):
1. Press down the battery door tabs and pull out to remove battery door.
2. Install the batteries as indicated on Command Center.
3. Close battery door by snapping in place.
4. When the four (4) batteries are installed the system will operate without power.
5. The batteries should be replaced when the LED indicates low battery or at least once a year.
20306750
45
Page 46
Designer Series Direct Vent Gas Fireplace
SIGNATURE COMMAND SYSTEM OPERATION
SYSTEM CONFIGURATION/SETUP
All System confi guration/setup is done on the Command Center.
NOTE: When using On/Off wall switch, the switch must be in the ON position to perform all confi guration set ups at the command center.
COLD CLIMATE OPTION
Choose the Mode That Best Suits Your Needs The Signature Command System is designed to operate
in either Standing Pilot or Intermittent Pilot mode.
The Standing Pilot Mode is best for colder climates
when the pilot must remain on continuously to prevent condensation and ensure reliable operation.
The Intermittent Pilot Mode is ideal for maximum effi -
ciency , igniting the pilot only when needed to start your replace, lowering fuel consumption and reducing your carbon footprint.
Either mode benefi ts from the instantaneous battery back- up, so you never have to worry about a power outage.
NOTE: The Signature Command System comes stan­dard in the Intermittent Pilot mode, so you must follow the instructions below to switch to Standing Pilot Mode if needed.
Intermittent/Standing Pilot Setup (Default intermit-
tent)
1. Holding the ON button on the Command Center while turning on the master switch will toggle between stand­ing pilot and intermittent pilot.
2. After the above operation, one beep (for standing pi­lot) or two beeps (for intermittent pilot) will be given as confi rmation.
Six-hour Safety Shutdown Option (Default ON)
1. The system comes preset from the factory with a six (6) hour shutdown from its last command of operation. This is done to prevent the fi replace from continuing to operate if unattended. You may disable this feature if you wish.
NOTE: By disabling this feature, your fi replace may con-
tinue to operate unattended.
2. When the master switch is in the ON position (“-”), press­ing the ON button and the OFF button on the Command Center simultaneously will toggle between enabling and disabling the six-hour shutdown option.
3. After the above operation, one beep (for enabling the six-hour shutdown option) or two beeps (for disabling the six-hour shutdown option) will be given as confi rma- tion.
Remote Transmitter Learn Function (Default OFF)
1. The RF receiver button located on the Control Board must be in the on position before the learn function can begin. Use paper clip to depress button. One beep for RF receiver ON or two beeps for RF receiver OFF will be given as confi rmation. Refer to Figure 57 for location.
2. After the RF receiver is on, holding the OFF button on the Command Center while turning on the master switch will activate the learn function for the transmitter.
3. After the above operation, two beeps will be given and the green LED on the Command Center will fl ash for 10 seconds.
4. During the 10 seconds, press the OFF button on a transmitter to learn. Another two beeps will be given to confi rm a successful learning. Refer to transmitter instructions for remote operations.
Shutting Off the Standing Pilot (Temporary Shut Off)
To shut off the standing pilot for service or summer shut down, press and hold the ON button on the Command Center for 3 seconds when the master switch is in the ON position (“-”) and the main burner is off.
Note: Pilot will resume the next time system is turned on.
Key Combinations for System Settings
NOTE: When On/Off wall switch is used, it must be in the
On position to perform all system setups.
Function Operation Default Setting
Intermittent/Standing Hold the ON s button while turning on the master switch Intermittent Pilot Setup (Beep once for standing pilot, twice for intermittent pilot) Pilot Standing Pilot Temp. Hold the ON s button 3 seconds (when the master switch Shutoff on the main burner is off) RF Remote Receiver Push the RF receiver On/Off button on the control board RF OFF
On/Off Beep once for ON and beep twice for OFF Learn Remote Hold the OFF t button while turning on the master switch Transmitter (Beep twice then press any handheld remote button) 6-hour safety Press the ON s button and OFF t button simultaneously ON shutdown setup (Beep once for ON, twice for OFF)
46
20306750
Page 47
SIGNATURE COMMAND SYSTEM OPERATION
Designer Series Direct Vent Gas Fireplace
FUNCTIONS/OPERATION
Turning on the fi replace
1. Turn on the master switch and wait for a beep.
2. Press the ON button on the Command Center or turn on wall switch. Pilot will light and burner will come on High setting or last memory setting (See Turning Off Fireplace below). For memory feature.
Pilot Safety Lockout Function
1. If the pilot doesn’t light after sparking for 30 seconds, pilot trial lockout happens. The LED on the Command Center fl ashes Green once every 2 seconds, until re- set.
2. If the pilot fl ame is lost during normal operation, the system will try three (3) times to relight after three (3) failures, fl ame loss lockout happens. The LED on the Command Center fl ashes Red-Green once every 2 seconds, until reset.
3. Turning the master switch on the Command Center to the off position, then ON again will reset the system.
Flame Height Control
1. Press the ON button (on the Command Center) once to turn on the main burner with maximum fl ame height.
2. Press the OFF button to decrease fl ame height. The fi rst two presses will decrease the fl ame height to medium and low.
3. The third press on OFF will turn off the main burner. In standing pilot confi guration, the pilot will stay; in inter- mittent pilot confi guration, the pilot will be shut off.
Turning the Fireplace Off
There are three ways to turn the fi replace off.
1. Flip the master switch to the off (“O”) position. (This will turn the entire system OFF.)
2. Press the OFF button to Medium, Low, then Off.
3. Hold the OFF button anytime for three seconds or by turning off the wall switch. These two commands of OFF are (Memory Off) the system will remember all last settings before turning off. The next time the fi replace is turned on, all settings will resume. To reset, change to the desired settings and shut off by using the Memory Off commands and the system will be reset to those
new settings.
Command Center Operations:
The following functions are available on the Command Center.
Function Operation Power Up Flip the master switch to the ON ("–") position to power up the system Fireplace ON Press the ON s button on the Command Center or turn on wall switch to turn the fi replace on Fireplace OFF Flip the master switch to the OFF ("o") position OR press the OFF t button 3
times OR for Memory Off, hold the OFF t button 3 seconds, or turn off wall switch Flame Height Up Press the ON s button once to turn on the fi replace with maximum fl ame height Flame Height Down Press the OFF t button to lower the fl ame height to Medium and Low
Self Diagnostics Chart:
The Command Center has a self-diagnostic LED enabling you to troubleshoot problems and potentially avoid a service call. Please refer to the charts below for indicator reference.
Fault LED Indication
Conversion Cover Missing One RED (1 time) Spark Fail Two RED (1 time) No Sensor Signal Three RED (1 time) Pilot Lockout - trial One GREEN, every 2 sec. (until manual reset) Pilot Lockout - fl ame loss One RED-GREEN, every 2 sec. (until manual reset) Low Battery One RED, every 10s (continuously) No or Low Thermopile Power Two RED, every 10s (continuously) Learning GREEN Flashes, every 1 sec. (for 10 sec.) AC Power On GREEN solid
Pressure Switch Failure One RED every 2 sec. (until manual reset) Power Vent Only
20306750
47
Page 48
Designer Series Direct Vent Gas Fireplace
CLEANING AND MAINTENANCE
Turn off gas before servicing fi replace. It is recommended that a qualifi ed service technician perform these check-ups at the beginning of each heating season
WARNING
BURNER, PILOT AND CONTROL COMPART­MENT
Keep the control compartment, logs, and burner areas surrounding the logs clean by vacuuming or brushing at least twice a year. Make sure the burner porting, pilot air opening and burner air opening are free of obstructions at all times.
PILOT FLAME
The fl ames from the pilot should be visually checked as soon as the heater is installed and periodically during normal operation. The pilot ame must always be pres- ent when the replace is in operation. Figure 66. The pilot fl ame has four distinct fl ames, one engulfi ng the thermopile, one engulfi ng the sensor, and the other two reaching to the main burners.
Sensor
Thermopile
FP2453
Figure 66 ­Pilot Flame
BURNER
Inspect area around the injector. Remove any lint or foreign material with a brush or vacuum.
BURNER FLAME
The fl ames from the burner should be visually checked as soon as the heater is installed and periodically during normal operation. In normal operation, at full rate, and after operating for about 15 to 30 minutes, the fl ame should be yellow and slightly taller than the rear log. Figure 67
If the fl ame is blue and only in the center, turn off unit and let cool. After unit is cool, remove logs and check to make sure the back holes in the burner are not covered with rock wool. If the back holes are clear, add more rock wool to the center of the burner. Replace logs.
NOTE: The type of installation, vent system confi guration, and wind effects may cause the fl ame patterns to vary.
Figure 67 ­Burner Flame Appearance
48
20306750
Page 49
CLEANING AND MAINTENANCE
Designer Series Direct Vent Gas Fireplace
VENT SYSTEM
The fi replace and venting system should be inspected before initial use and at least annually by a qualifi ed fi eld service person. Inspect the external vent cap on a regular basis to make sure that no debris is interfering with the airfl ow. Inspect entire venting system to ensure proper function.
GLASS DOOR
Thoroughly clean the inside of the glass door after using the fi replace for ten hours. Periodically clean the glass door as necessary.
When cleaning the glass, remember:
Do not remove the glass when hot. Allow glass to
cool before removal.
NEVER use abrasive materials.
Keep children and pets a safe distance away.
Never operate the fi replace without the glass door
properly secured.
Never operate the fi replace if the glass is broken.
Replace any glass that is chipped, cracked, or broken.
Replacement glass door assemblies MUST be supplied by the fi replace manufacturer – No substitute materi-
als may be used.
Handle glass door with care to avoid striking or scratch-
ing it on hard objects.
To clean glass door, follow “Glass Removal” procedure outlined in the Final Installation section. Film deposit on the inside of the glass should be cleaned off using a nontoxic, non-corrosive, non-abrasive, mild-cleaning solution. Simply apply an adequate amount to the glass and wipe off with a damp cloth. After all maintenance has been completed, re-install glass door.
LOGS
Leave logs installed in the fi replace for cleaning. Vacuum surface of the logs with a brush attachment. If logs must be removed for cleaning, handle carefully by holding gently at each end. Gloves are recommended to prevent skin irrita­tion from ceramic fi bers. If skin becomes irritated, wash gently with soap and water. Vacuum surface of logs with brush attachment or brush logs with a soft bristle brush (i.e. clean, dry paintbrush). To place logs back in the fi re- place, see “Log Placement” found in the Final Installation section.
NOTE: Do not use fl uids to clean ceramic fi ber logs.
ROCK WOOL
Replace or add rock wool as required following installa­tion instructions in the Final Installation section of this manual.
20306750
49
Page 50
Designer Series Direct Vent Gas Fireplace
SIGNATURE COMMAND SYSTEM
TROUBLESHOOTING
OPERATION
Install batteries and/or plug in the AC board
Flip the master switch (rocker switch) to the ON position
After the beep
Press the ON button on the Command Center
FAULT
No beep in about 8 seconds
No beep or no sound from the valve indicating pilot solenoid open
No sparking on the pilot
A
B
C
Make sure Command Center and the control board are connected by a 2 feet or 15 feet cable
Check NG/LP conversion cap and control board connections
Check pilot connections
DIAGNOSIS
Using battery?
Check valve connections
Check grounding
Battery polarity wrong?
Battery voltage low?
AC plug is plugged to AC mains?
The 5-pin connector on the AC board broken or bent?
LED on the Command Center does not show solid green?
Check power supply (go through )
A
Go through
B
ACTION
Re-install batteries
Change batteries
Plug the AC plug to AC mains
Repair or replace the AC Board
Replace the AC Board
Replace the Control Board or Command Center
Sparking is happening elsewhere (under the pilot), re-install/replace the pilot
Sparking doesn’t continue
Pilot doesn’t light
Main burner doesn’t light
D
The Control Board is having interference from the surrounding metal (Ground)
E
Check gas supply
F
Go through
E
Go through
The sensor on the pilot is not in the flame (pilot flame too small)?
Re-install the Control Board, move it around or change the Control Board
Sparking is not in the
C
path of gas flow, adjust sparker position or replace the pilot
Adjust sensor position or replace the pilot
50
20306750
Page 51
REPLACEMENT PARTS
Designer Series Direct Vent Gas Fireplace
3
5
4
7.
1
2
6.
FIREBOX COMPONENTS
ST
Item Description
1. Glass Frame Assembly 2 2 1 20302401
2. Access Panel 2 2 1 20302126
3. Glass Frame Assembly, Short -- 1 1 20302151
4. Access Panel, Short -- 1 1 20302127
5. Grate 1 1 1 20301124
6. Large Safety Barrier Assembly 2 2 1 36CSBDL
7. Small Safety Barrier Assemby -- 1 1 36CSBDS Junction Box Assembly (not shown) 1 1 1 26D2128
Qty.
PF
Qty.
CR/CL
Qty.
Designer
LDV Part No.
20306750
51
Page 52
Designer Series Direct Vent Gas Fireplace
SIGNATURE COMMAND SYSTEM
REPLACEMENT PARTS
15
1
12
2
3
13
4
7
11
16
6
5
9
8
52
20306750
Page 53
REPLACEMENT PARTS
Designer Series Direct Vent Gas Fireplace
SIGNATURE COMMAND SYSTEM
Item Description Qty. Designer Natural Designer LP
1. Burner Assy 1 20302188 20302188
2. Venturi Gasket 1 45D0032
3. Venturi Assy 1 69D1119
4. Injector 1 70D0064 20H3153
5. Tube, Union to Venturi 1 20302009 20302009
6. Fitting Brass - Union 5/16 Compression 1 37D0713 37D0713
7. Tube, Elbow to Union 1 20302008 20302008
8. Fitting, 5/16 x 3/8 Brass Male 1 11V0313 11V0313
9. Valve SCS 1 80D0001
10. Bolt M5-.8 x 8 mm 1 20H0108 20H0108
11. Flexline, 18" w/ Shutoff Valve 1 69D0030 69D0030
12. Pilot SCS 1 80D0006
13. Grommet 1 73D0189 73D0189
14. Sealant 1 28D0149 28D0149
15. Control Board SCS 1 80D0018 80D0019
16. Command Center SCS 1 80D0005 80D0005
17. Wire, CC/CB 24" SCS 1 80D0008 80D0008
18. Wire, Valve/control Board SCS 1 80D0010 80D0010
Accessories
SCS Blower Kit (1 blower) 1 BLOTSTSC A/C Module SCS (Opt. blower, lights, & aux. control) 1 SCSACM Blower T-Stat w/speed control (1 blower) 1 BLOTDL SCS Wall Extension Kit (15' Wire, Rough-in Box, Wall Cover) 1 SCSWEK Blower T-Stat w/speed control (2 blowers) 1 BLOTBLDV
NOTE: TSFSC must be used with SCS A/C Module to control lights, blower & aux.
Fuel Conversion Kits - Signature Command System Natural Gas to LP
STLDVCKPS
LP to Natural Gas
STLDVCKNS
20306750
53
Page 54
Designer Series Direct Vent Gas Fireplace
REPLACEMENT PARTS
LOGS
2
1
3
5
4
Item Description Qty. Designer LDV
1. Log #1 1 20302432
2. Log #2 1 20302433
3. Log #3 1 20302434
4. Log #4 1 20302435
5. Log #5 1 20302436
BRICK
1
Traditional Brick
Ref. Description Cottage Red Olde English Vintage Brown
1. End Wall, Traditional 20302517 -- --
2. Long Wall, Traditional 20302518 -- --
3. End Wall, Herringbone -- 20302519 20302521
4. Long Wall, Herringbone -- 20302520 20302522
2
3
Herringbone Brick
4
54
20306750
Page 55
REPLACEMENT PARTS VENT COMPONENTS
1
Designer Series Direct Vent Gas Fireplace
HOT
4
9
5
2
3
6
7
8
11
10
20306750
55
Page 56
Designer Series Direct Vent Gas Fireplace
5
1
VENT COMPONENTS FOR 4" X 65⁄8"
REPLACEMENT PARTS
Current
Duravent
Qty./
Item
Box Description
1 1 Thru-roof Flexible Pipe Termination Kit with fl ex adapter
24" rigid pipe, roof support 4" x 6
1 1 Horizontal Square Termination Cap with built-in
vinyl siding standoff, heat defl ector and fi restop 1 1 Square Horizontal Termination Cap 46DVA-HC 985 4DT-HC 1 1 Round Horizontal Termination Cap 46DVS-HRCS -- -­1 1 Sconce Termination Cap (aluminum) 46DVA-HSC -- -­2 1 Low-Profi le Vertical Termination Cap 46DVA-VC 980 Note 3 6 6" Pipe Length (galvanized) 46DVA-06 908 4DT-06 3 6 9" Pipe Length (galvanized) 46DVA-09 907 4DT-09 3 6 12" Pipe Length (galvanized) 46DVA-12 906 4DT-1 3 6 24" Pipe Length (galvanized) 46DVA-24 904 4DT-4 3 6 36" Pipe Length (galvanized) 46DVA-36 903 4DT-36 3 6 48" Pipe Length (galvanized) 46DVA-48 902 4DT-48 468 4 6 16" Pipe Extension (galvanized) 46DVA-16A -- 4DT-AJ14 5 6 45° Elbow (galvanized) 46DVA-E45 945 4DT-EL45 6 6 90° Elbow (galvanized) 46DVA-E90 990 4DT-EL90 7 6 Adjustable Roof Flashing 0/12 - 6/12 46DVA-F6 943 4DT-AF6 8 6 Storm Collar 46DVA-SC 953 4DT-SC 9 6 1" Firestop 46DVA-FS 963 4DT-FS 9 6 3" Firestop FS3 -- -­10 1 Vinyl Siding Standoff 46DVA-VSS 950 4DT-VS 11 1 Restrictor Disk 45D0551 45D0551 --
⁄2" Pipe Extension (galvanized) 46DVA-08A -- 4DT-AJ
1 Attic Insulation Shield 46DVA-IS -- -­6 Steep Roof Flashing 7/12 - 12/12 46DVA-F12 943S -­8 Horizontal Termination with 1" fi restop BHRT/8 -- -- 8 Flex Adapter Starter DVFA/8 -- --
⁄8" and termination cap
or VCG
Part No.
TRFK -- --
BHRTK BHRTK --
Old
Duravent
or VCG
Part No.
Selkirk
Part No.
NOTE: This termination is not recommended for use with the
Designer Series Fireplaces.
56
20306750
Page 57
VENTING COMPONENTS
5
5
VENT COMPONENTS FOR 5" X 8"
Designer Series Direct Vent Gas Fireplace
Current
Duravent
Qty./
Item
1 1 Horizontal Termination Cap w/Built-in Vinyl Siding
1 1 Horizontal Termination Cap Built-In Vinyl Siding Stand-
1 1 Horizontal Termination Cap Built-In Vinyl Siding Stand-
1 8 Horizontal Termination w/ 1" Firestop BHR58T/8 1 1 Horizontal High Wind Termination Cap 58DVA-HC 1285 5DT-HC -­1 1 Horizontal Temination Cap 5DHT 2 1 V ertical Termination 58DV A-VC 1280 Note Note 3 4 6" Pipe Length 58DVA-06 1208 5DT-06 5D6 3 4 9" Pipe Length 58DVA-09 1207 5DT-09 3 4 12" Pipe Length 58DVA-12 1206 5DT-12 5D12 3 4 24" Pipe Length 58DVA-24 1204 5DT-24 5D24 3 4 36" Pipe Length 58DVA-36 1203 5DT-36 5D36 3 4 48" Pipe Length 58DVA-48 1202 5DT-48 5D48 4 4 81/2" Pipe Extension 58DVA-08A -- 5DT-AJ 4 4 16" Pipe Extension 58DVA-16A -- -­5 4 45° Elbow 58DVA-E45 1245 5DT-EL45 5D456 5 4 45° Swivel Elbow -- -- 5DT-EL45 6 4 90° Elbow 58DVA-E90 1290 5DT-EL90S 5D906 6 4 90° Swivel Elbow -- 1290G 5DT-EL90S 7 6 Flashing, 0/12 to 6/12 Roof Pitch 58DVA-F6 1243 5DT-AF6 5DF 7 Steep Roof Flashing 58DVA-F12 1243S -­8 6 Storm Collar 58DVA-SC 1253 5DT-SC 5DSC 9 4 Firestop 58DVA-FS 1263 5DT-FS 5DFS 9 3" Firestop FS38 FS38 -­10 1 Vinyl Siding Standoff 58DVA-VSS 1250 5DT-VS 5DVS 11 Attic Insulation Shield (not shown) 58DVA-IS -- -­12 8 Flex Adapter Starter (not shown) DVFF8A/8 -- -­13 1 Reducer - 5 x 8 to 4 x 65/8 (not shown) 1222DA 1222DA --
Box Description
Standoff Heat Defl ector, Firestop, and Adjustable Pipe 11" to 14
off, Heat Defl ector, Firestop, 90° Elbow and Adjustable Pipe 11" to 14
off, Heat Defl ector, Firestop, Flexible Pipe 2-" to 48", Adapter
⁄8"
⁄8"
or VCG
Part No.
-- BHR58TK9 -- --
-- BHS58TK -- --
Old
Duravent
or VCG
Part No.
BHSF58TK
Selkirk
Part No.
Metal-Fab
Part No.
NOTE: This termination is not recommended for use with the
Designer Series Fireplaces.
For more information about, or instructions for, the venting components referenced above, please contact the component manufacturer: Selkirk Corporation: www. selkirkcorp.com or 800-992-8368
Duravent: www. duravent.com or 800-835-4429 Metal-Fab, Inc.: www.metal-fabinc.com or 316-943-2351
20306750
57
Page 58
Designer Series Direct Vent Gas Fireplace
584F
VENTING COMPONENTS
HORIZONTAL VENTING - 4" x 7"
Description Model Number Horizontal Vent Termination Kits Rear Vent Hot Touch Termination Kit w/ 10" to 16" 7TBRHTK
Adjustable Termination Pipe, Firestop, and Hot Touch Termination w/ Siding Shield
Up and Out Side Wall Termination Kit w/ 10" to 16" 7TDVSCTK Adjustable Termination Pipe, 90° Elbow, Firestop, and Cool Touch Termination w/ Siding Shield
Rear Vent Cool Touch Termination w/ Siding Shield for 7TRVCT/8 Straight-out Applications and Firestop - 8 pack
Rear Vent Hot Touch Termination w/ Siding Shield for 7TRVHT/8 Straight-out Applications and Firestop - 8 pack
Termination Guard for 7" T.L. Rear Vent Hot Touch 7TRVTG Terminations 97TRVT/7TSVKT)
Snorkel Termination 7TDVSNORK 7" T.L. DVRTSB Termination Screen Guard 7TBSG Up and Out Starter Kit w/ 40" Flex Pipe, Firestop, Cool 7FDVSCTK
Touch Termination w/ Siding Shield, and 2 ea. Clamp Bands
Twist Lock Pipe 20" Termination Pipe - 8 pack 7TDVP20/8 10" - 16" Adjustable Termination Pipe - 4 pack 7TDVPA/4 12" - 18" Adjustable Vent Length 7TDVP1218 35" - 64" Adjustable Vent Length 7TDVP3564 8" Vent Pipe - 4 pack 7TDVP8/4 12" Vent Pipe - 4 pack 7TDVP12/4 24" Vent Pipe - 4 pack 7TDVP24/4 36" Vent Pipe 7TDVP36 36" Vent Pipe - 30 pack 7TDVP36/30 48" Vent Pipe 7TDVP48 48" Vent Pipe - 30 pack 7TDVP48/30 5" x 8" to 4" x 7" Adapter 7TDVP58 Flex Adapter Starter Kit DVFFA/8 Twist Lock Elbows 45° Elbow for Vertical/Horizontal Offset 7TDV45 45° Elbow for Vertical Offsets - 8 pack 7TDV45/8 90° Elbow for Vertical/Horizontal Offset 7TDV90 90° Elbow for Vertical/Horizontal Offset - 8 pack 7TDV90/8
Shields and Supports 1" Firestop 7DV1FS 3" Firestop 7DV3FS 1" Attic Insulation Shield 7DV1AIS Combination Horizontal Offset/Roof Support 7DVCS
58
20306750
Page 59
VENTING COMPONENTS
584F
Designer Series Direct Vent Gas Fireplace
VERTICAL VENTING - 4" x 7"
Description Model Number Vertical Vent Termination Kits Vertical Vent Termination w/ Storm Collar 7TDVSKV
(fl ashing NOT included) Vertical Vent Termination w/ Storm Collar - 8 pack 7TDVSKV/8
(fl ashing NOT included) Vertical Vent Termination w/ 1/12 - 6/12 Flashing, Storm 7TDVSKVA*
Collar and Ceiling Support Kit Vertical Vent Termination w/ 6/12 - 12/12 Flashing, 7TDVSKVB*
Storm Collar and Ceiling Support Kit Vertical Vent Termination w/ Flat Flashing, Storm Collar 7TDVSKVF*
and Ceiling Support Kit
Twist Lock Pipe 20" Rigid Pipe - single pack 7TDVP20 30" Flex Pipe - single pack 7FDVP30 12" - 18" Adjustable Vent Length 7TDVP1218 35" - 64" Adjustable Vent Length 7TDVP3564 8" Vent Pipe - 4 pack 7TDVP8/4 12" Vent Pipe - 4 pack 7TDVP12/4 24" Vent Pipe - 4 pack 7TDVP24/4 36" Vent Pipe 7TDVP36 36" Vent Pipe - 30 pack 7TDVP36/30 48" Vent Pipe 7TDVP48 48" Vent Pipe - 30 pack 7TDVP48/30 5" x 8" to 4" x 7" Adapter 7TDVP58 Flex Adapter Starter Kit DVFFA/8 Twist Lock Elbows 45° Elbow for Vertical/Horizontal Offset 7TDV45 45° Elbow for Vertical Offsets - 8 pack 7TDV45/8 90° Elbow for Vertical/Horizontal Offset 7TDV90 90° Elbow for Vertical/Horizontal Offset - 8 pack 7TDV90/8
Shields and Supports 1" Firestop 7DV1FS 1" Attic Insulation Shield 7DV1AIS Combination Horizontal Offset/Roof Support 7DVCS
20306750
59
Page 60
Designer Series Direct Vent Gas Fireplace
MASSACHUSETTS RESIDENTS ONLY Please read and follow these special requirements
NOTE REGARDING VENTED PRODUCTS
This product must be installed by a licensed plumber or gas fi tter when installed within the Commonwealth of Massachusetts.
Any residence with a direct vent product must have a carbon monoxide (CO) detector installed in the residence.
Installation of the fi replace or vented gas log in the State of Massachusetts requires the damper to be permanently removed or welded in the fully open position.
In addition, a naturally vented gas log may not be installed in a bedroom or bathroom in the State of Massachusetts.
Flex line installation must not exceed 36 inches and must have a T shutoff valve.
NOTE REGARDING VENT FREE PRODUCTS
This product must be installed by a licensed plumber or gas fi tter when installed within the Commonwealth of Massachusetts.
In addition, vent free products may not be installed in a bedroom or bathroom regardless of size or type in the State of Massachusetts.
Flex line installation must not exceed 36 inches and must have a T shutoff valve.
CARBON MONOXIDE DETECTOR REQUIREMENTS
(2) Revise 10.8.3 by adding the following additional requirements:
(a) For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above nished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall be satisfi ed:
1. Installation of carbon monoxide detectors. At the time of installation of the side wall horizontal vented gas fueled equipment, the installing plumber or gas fi tter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is installed on the fl oor level where the gas equipment is to be installed. In addition, the installing plumber or gas fi tter shall observe that a battery operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of qualifi ed licensed professionals for the installation of hard wired carbon monoxide detectors
a. In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired carbon monoxide detector with alarm and battery back-up may be installed on the next adjacent fl oor level.
b. In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of thirty (30) days to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery operated carbon monoxide detector with an alarm shall be installed.
2. Approved Carbon Monoxide Detectors. Each carbon monoxide detector as required in accordance with the above provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certifi ed.
3. Signage. A metal or plastic identifi cation plate shall be permanently mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The sign shall read, in print size no less than one-half (1/2) inch in size, “GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS.”
4. Inspection. The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5.08(2)(a)1 through 4.
(b) Exemptions: The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4:
1. The equipment listed in Chapter 10 entitled "Equipment Not Required To Be Vented" in the most current edition of NFPA 54 as adopted by the Board; and
2. Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the dwelling, building or structure used in whole or in part for residential purposes.
(c) Manufacturer requirements — Gas Equipment Venting System Provided. When the manufacturer of Product Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the instructions provided by the manufacturer for installation of the equipment and the venting system shall include:
1. Detailed instructions for the installation of the venting system design or the venting system components; and
2. A complete parts list for the venting system design or venting system.
(d) Manufacturer requirements — Gas Equipment Venting System Not Provided. When the manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the fl ue gases, but identifi es “special venting systems,” the following requirements shall be satisfi ed by the manufacturer:
1. The referenced "special venting system" instructions shall be included with the appliance or equipment installation instructions; and
2. The “special venting systems” shall be Product Approved by the Board, and the instructions for that system shall include a parts list and detailed installation instructions.
(e) A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment, all venting instructions, all parts lists for venting instructions, and/or all venting design
VENTING COMPONENTS
60
20306750
Page 61
Designer Series Direct Vent Gas Fireplace
LIMITED LIFETIME WARRANTY POLICY
LIFETIME WARRANTY
The following components are warranted for life to the original owner, subject to proof of purchase: Firebox, Combustion Chamber and Heat Exchanger.
FIVE YEAR WARRANTY
The following components are warranted fi ve (5) years to the original owner, subject of proof of purchase: Ceramic Fiber Logs.
BASIC WARRANTY
Vermont Castings Group warrants the components and materials in your gas appliance to be free from manu­facturing and material defects for a period of two years from date of installation. After installation, if any of the components manufactured by Vermont Castings Group in the appliance are found to be defective in materials or workmanship, Vermont Castings Group will, at its option, replace or repair the defective components at no charge to the original owner. Vermont Castings Group will also pay for reasonable labor costs incurred in replacing or repairing such components for a period of two years from date of installation. Any products presented for warranty repair must be accompanied by a dated proof of purchase.
This Limited Lifetime Warranty will be void if the appliance in not installed by a qualifi ed installer in accor- dance with the installation instructions. The Limited Lifetime Warranty will also be void if the appliance is not operated and maintained according to the operating instructions supplied with the appliance, and does not extend to (1) fi rebox/burner assembly damage by accident, neglect, misuse, abuse, alterations, negligence of others, including the installation thereof by unqualifi ed installers, (2) the costs of removal, re-installation or transportation of defective parts on the appliance, or (3) incidental or consequential damage. All service work must be performed by an authorized service representative.
This warranty is expressly in lieu of other warranties, express or implied, including the warranty of mer­chantability of fi tness for purpose and of all other obligations or liabilities. Vermont Castings Group does not assume for it any other obligations or liabilities in connection with sale or use of the appliance. It states that do not allow limitations on how long an implied warranty lasts, or do not allow exclusion of indirect damage, those limitations of exclusions may not apply to you. You may also have additional rights not covered in the Limited Lifetime Warranty.
Vermont Castings Group reserves the right to investigate any and all the claims against the Limited Lifetime Warranty and decide upon method of settlement.
IF WARRANTY SERVICE IS NEEDED:
1. Contact your supplier. Make sure you have your warranty, your sales receipt and the model/ serial number of your Vermont Castings Group product.
2. DO NOT ATTEMPT TO DO ANY SERVICE WORK YOURSELF.
20306750
61
Page 62
Designer Series Direct Vent Gas Fireplace
This page left blank.
62
20306750
Page 63
This page left blank.
Designer Series Direct Vent Gas Fireplace
20306750
63
Page 64
Based on CSA P.4.1-09
EFFICIENCY RATINGS
ENERGUIDE RATINGS
FIREPLACE EFFICIENCY
MODEL
Natural Gas 69.7 67.0
Liquid Propane (LP) 79.4 68.3
PERCENTAGE
(AFUE PERCENTAGE)
D.O.E.
149 Cleveland Drive • Paris, Kentucky 40361
www.vermontcastingsgroup.com
Loading...