Vermont Castings OXDV30NVSB Installation And Operating Instructions Manual

Page 1
Direct Vent Gas Stove
DANGER
HOT GLASS WILL
CAUSE BURNS.
DO NOT TOUCH GLASS
UNTIL COOLED.
NEVER ALLOW CHILDREN
TO TOUCH GLASS.
A barrier designed to reduce the risk of burns from the hot
viewing glass is provided with this appliance and shall
be installed for the protection of children and
other at risk individuals.
20306543
Installation and Operating Instructions
Models: OXDV30NVSB
WARNING: FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly
could result in serious injury, death or property damage.
Do not store or use gasoline or other
ammable vapors and liquids in the
vicinity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS – Do not try to light any appliance.
– Do not touch any electrical switch; do
not use any phone in your building. – Leave the building immediately. – Immediately call your gas supplier from
a neighbor's phone. Follow the gas
supplier's instructions.
– If you cannot reach your gas supplier,
call the re department.
Installation and service must be performed
by a qualied installer, service agency or
the gas supplier.
WARNING: Improper installation, adjustment,
alteration, service or maintenance can cause
injury or property damage. Refer to this manual. For assistance or additional information consult a qualified installer, service agency or the
gas supplier.
This appliance is for use only with the type of gas
indicated on the rating plate. This appliance is not convertible for use with other gases, unless a certied kit is used.
This appliance may be installed in an aftermarket,* permanently located, manufactured home (USA only) or mobile home, where not prohibited by local codes.
* Aftermarket: Completion of sale, not for purpose of resale, from
the manufacturer.
CERTIFIED
SAFETY BARRIER
INSTALLER: Leave this manual with the appliance.
reference.
20306762 12/14 Rev. 1
Page 2
Oxford Direct Vent / Natural Vent Gas Heater
Table of Contents
PLEASE READ THE INSTALLATION & OPERATING INSTRUCTIONS BEFORE USING APPLIANCE.
Thank you and congratulations on your purchase of an Vermont Castings Group stove.
IMPORTANT: Read all instructions and warnings carefully before starting installation. Failure to follow these
instructions may result in a possible re hazard and will void the warranty.
INSTALLATION & OPERATING INSTRUCTIONS
General Information .................................3
Requirements for the Commonwealth of Massachusetts ....4
Oxford Dimensions .................................5
Installation Requirements ............................6
Locating the Stove ..................................6
Clearance Requirements .............................6
Parallel Installation .................................7
Corner Installation ..................................7
Wall Centerline from Floor ............................7
Wall and Ceiling Clearances ..........................7
Hearth Requirements ...............................7
Gas Specications ..................................8
Gas Inlet and Manifold Pressures ......................8
High Elevations ....................................8
Horizontal Termination - Direct Vent ONLY ...............8
Vertical Termination - Direct Vent ONLY .................9
Vent Termination Clearances ..........................9
General Venting Information - Termination Location .......11
Termination Clearances .............................12
Venting Requirements - Natural Vent ONLY .............12
Venting Requirements and Options - Direct Vent ONLY ....13
Install the Optional Fan .............................14
Venting System Assembly - Direct Vent ................15
Install Vent Adapter Pipe
(Vermont Castings Group Vent Components) ........15
Install Vent Adapter Pipe (Dura-Vent Components) .......16
Side Wall Termination Assembly ......................16
Vent Termination Below Grade .......................18
Vertical (Through the Roof) Vent Assembly ..............18
Venting System Assembly - Natural Vent ...............19
Install the Vent Pipe ................................19
Install the Log Set .................................20
Connect Gas Supply Line ...........................20
Burner Information .................................21
Air Shutter Adjustment & Instructions ..................21
Complete the Assembly .............................22
Install ON/OFF Switch ..............................22
Thermostat Connection (Optional) ....................23
Install the Front ...................................23
Safety Barrier Installation ...........................24
MAINTENANCE
Annual System Inspection ........................... 30
Logset and Burner/Cleaning and Inspection .............30
Care of Cast Iron .................................. 30
Cleaning the Glass ................................ 30
Glass Replacement ................................ 30
Gasket Replacement ............................... 31
Inspect the Vent System Annually ..................... 31
Check the Gas Flame Regularly ......................31
Stove Disassembly ................................31
Wiring Diagram ................................... 32
REPLACEMENT PARTS ...........................33
OPTIONAL ACCESSORIES ........................35
WARRANTY .....................................43
EFFICIENCIES ................................... 44
OPERATION
Your First Fire ....................................25
Pilot and Burner Information .........................25
Flame & Temperature Adjustment ....................25
Flame Characteristics ..............................25
Lighting and Operating Instructions ....................26
Troubleshooting - SIT NOVA 820 Gas Control System .....27
Fuel Conversion Instructions .........................28
Conversion Precautions ............................28
Conversion Procedure ..............................28
2
20306762
Page 3
General Information
The Oxford Direct Vent/Natural Vent Room Heater, Model No. OXDV30NV, is a vented gas appliance listed to the ANSI standard Z21.88-2009 and CSA-2.33-2009 for Vented Room Heaters, and CSA 2.17-M91, Gas-Fired Appliances For Use at High Altitudes.
The installation of the Oxford Direct Vent/Natural Vent Room Heater must conform with local codes, or in the absence of lo­cal codes, with National Fuel Gas Code, ANSI Z223.1/NFPA 54 — latest edition and CSA B-149.1 Installation Code. (EX­CEPTION: Do not derate this appliance for altitude. Maintain the manifold pressure at 3.5” w.c. for Natural Gas and 10.0” w.c. for LP gas at maximum input.)
This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use
with other gases unless a certied kit is used.
Installation and replacement of gas piping, gas utiliza­tion equipment or accessories, and repair and servic­ing of equipment shall be performed only by a qualied agency, preferably NFI or WETT (Canada) certied. The term “qualied agency” means any individual, rm, cor-
poration, or company that either in person or through a
representative is engaged in and is responsible for (a) installation or replacement of gas piping, or (b), the con­nection, installation, repair, or servicing of equipment, who is experienced in such work, familiar with all pre­cautions required, and has complied with all the require­ments of the authority having jurisdiction.
The Oxford Direct Vent/Natural Vent Room Heater should be inspected before use and at least annually by a quali­ed service agency. It is imperative that control compart­ments, burners, and circulating air passageways of the appliance be kept clean.
The Oxford Direct Vent/Natural Vent Room Heater and its individual shut-off valve must be disconnected from the gas supply piping during any pressure testing of that system at test pressures in excess of 1/2 psig (3.5 kPa).
The Oxford Direct Vent/Natural Vent Room Heater must be isolated from the gas supply piping system by closing its in­dividual manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psig.
‘Direct Vent’ describes a sealed combustion system in which incoming outside air for combustion and outgoing exhaust en­ter and exit through two separate concentric passages within the same sealed vent system. The system does not use room air to support combustion. The Direct Vent system permits the gas appliance to be vented directly to the outside atmo­sphere through the side of the house or vertically through the roof. Conventional venting systems (Natural Vent) take air from the room for combustion and vent the exhaust vertically through the roof to the atmosphere.
This appliance is approved for bedroom installations in the U.S. and Canada.
This appliance may be installed in an aftermarket* manufac­tured (mobile) home, where not prohibited by state or local codes.
20306762
Oxford Direct Vent / Natural Vent Gas Heater
WARNING: Operation of this heater when not connected to a properly installed and maintained venting system can result in carbon monoxide (CO) poisoning and pos­sible death.
The Oxford Direct Vent/Natural Vent Room Heater, when installed, must be electrically grounded in accordance with local codes or, in the absence of local codes, with the Na­tional Electrical Code ANSI/NFPA 70, (latest edition), or of the current Canadian Electrical Code C22.1.
Due to high temperatures this appliance should be locat­ed out of trafc and away from furniture and draperies.
WARNING: This appliance is hot while in operation.
Keep children, clothing, and furniture away. Contact may cause burns or ignition of combustible materials.
Children and adults should be alerted to the hazards of high surface temperatures and should stay away to avoid burns or clothing ignition. Young children should be carefully supervised when they are in the same room
as the appliance.
Clothing or other ammable materials should not be placed on or near the appliance.
Any safety screen, glass or guard removed for servic­ing an appliance must be replaced prior to operating the
appliance.
The appliance area must be kept clear and free from combustible materials, gasoline, and other ammable vapors and liquids.
The ow of combustion and ventilation air must not be obstructed. The installation must include adequate ac­cessibility and clearance for servicing and proper op-
eration. WARNING: Do not operate the Room Heater with the
glass panel removed, cracked or broken. Replacement of the panel should be done by a licensed or qualied
service person.
Do not use this appliance if any part has been under water. Immediately call a qualied service technician to inspect the appliance and to replace any part of the con­trol system and any gas control which has been under
water.
Do not burn wood, trash or any other material for which this appliance was not designed. This appliance is de­signed to burn either natural gas or propane only.
This gas appliance must not be connected to a chimney ue serving a separate solid-fuel burning appliance.
CAUTION: Label all wires prior to disconnection when
servicing controls. Wiring errors can cause improper
and dangerous operation. Verify proper operation after servicing.
Proposition 65 Warning: Fuels used in gas, woodburning or
oil red appliances, and the products of combustion of such
fuels, contain chemicals known to the State of California to cause cancer, birth defects and other reproductive harm.
California Health & Safety Code Sec. 25249.6
* Aftermarket: Completion of sale, nor for purpose of resale, from the manufacturer.
3
Page 4
Oxford Direct Vent / Natural Vent Gas Heater
Requirements for the Commonwealth of Massachusetts
All gas tting and installation of this heater shall only be done by a licensed gas tter or licensed plumber.
For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above
nished grade in the area of the venting, including but not
limited to decks and porches, the following requirements
shall be satised:
Installation of Carbon Monoxide Detectors
At the time of installation of the side wall horizontal vented
gas fueled equipment, the installing plumber or gas tter
shall observe that a hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services
of qualied licensed professionals for the installation of
hard wired carbon monoxide detectors.
In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired carbon monoxide detector with alarm and battery
back-up may be installed on the next adjacent oor level.
In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of thirty (30) days to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery operated carbon monoxide detector with an alarm shall be installed.
Approved Carbon Monoxide Detectors
Each carbon monoxide detector as required in accordance with the above provisions shall comply with NFPA 720 and
ANSI/UL 2034 listed and IAS certied.
Signage
A metal or plastic identication plate shall be permanently
mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The sign shall read, in print size no less than one-half (1/2) inch in size, “GAS VENT DIRECTLY
BELOW, KEEP CLEAR OF ALL OBSTRUCTIONS”.
Inspection
The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5.08(2)(a)1 through 4.
Exemptions
The following equipment is exempt from 248 CMR
5.08(2)(a)1 through 4:
The equipment listed in Chapter 10 entitled “Equipment
Not Required To Be Vented” in the most current edition of NFPA 54 as adopted by the Board; and
Product Approved side wall horizontally vented gas fueled
equipment installed in a room or structure separate from the dwelling, building or structure used in whole or in part for residential purposes.
MANUFACTURER REQUIREMENTS
Gas Equipment Venting System Provided
When the manufacturer of Product Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the instructions provided by the manufacturer for installation of the equipment and the venting system shall include:
Detailed instructions for the installation of the venting
system design or the venting system components; and
A complete parts list for the venting system design or
venting system.
Gas Equipment Venting System NOT Provided
When the manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does not provide
the parts for venting the ue gases, but identies “special
venting systems”, the following requirements shall be
satised by the manufacturer:
The referenced “special venting system” instructions shall
be included with the appliance or equipment installation instructions; and
The “special venting systems” shall be Product
Approved by the Board, and the instructions for that system shall include a parts list and detailed installation instructions.
A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment, all venting instructions, all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of the installation.
4
20306762
Page 5
Oxford Direct Vent / Natural Vent Dimensions
Refer to Page 6 for Flue Collar Centerline Dimensions
Oxford Direct Vent / Natural Vent Gas Heater
6³⁄₄"
(172mm)
C
L
Valve Inlet
24¹⁄₂"
(622mm)
28³⁄₈"
(721mm)
Valve
C
L
4³⁄₈"
Inlet
(111mm)
12¹⁄₂"
(318mm)
17"
(419mm)
Fig. 1 Oxford dimensions.
23"
(584mm)
Attention
The Oxford stove is shipped from the factory as a Direct Vent Gas Heater. This heater may be converted into a Natural Vent unit in the eld. If a Natural Vent heater is desired, the FSDHAG Draft Hood must be directly installed to the top of the unit according to the installation instructions. The Draft Hood Adapter is available in the 7FSDHASK stove kit or as a separate item.
When the stove is converted to Natural Vent, it uses 4” vent pipe. For aesthetic purposes the Vermont Castings Group direct vent system may be used up to the ceiling.
20306762
5
Page 6
Oxford Direct Vent / Natural Vent Gas Heater
A
B
E
C
D
Installation Requirements
The installation must conform with local codes or, in the absence of local codes, with the National Fuel Gas Code, ANSI Z223.1/NFPA 54 - latest edition. (EXCEPTION: Do not derate this appliance for altitude. Maintain the mani­fold pressure at 3.5” w.c. for Natural Gas, and 10” w.c. for Propane).
In Canada, installation must be in accordance with the cur­rent CSA B-149.1 Installation Codes and/or local codes.
The installation should be done by a qualied service person who is familiar with the building codes and installation techniques appropriate for your area to accomplish a safe and effective installation.
Your dealer or your local gas supplier will be able to refer a qualied service person.
WARNING: Due to high temperatures, the
HEATER should be located out of trafc and away from furniture and draperies.
The surface of the Heater Is hot when it is in use.
Young children should be watched carefully when
they are in the same room when the Heater is in use,
and they should be taught to avoid the hot surface. Keep any objects that can burn well away from the Heater, and observe the recommended clearances
that follow.
Locating the Stove
In choosing a location for the stove, consider:
• The location of outside walls;
• Where additional heat is needed:
• Where family members gather most often;
• The vent system requirements.
NOTE: We do not recommend the use of wallpaper next to this stove. Over time, radiant heat may cause the wall­paper to shrink, or may adversely affect the binders in the wallpaper adhesive.
Direct Vent System Only
A. Flat on corner wall D. Cross Corner B. Room Divider E. Flat on wall C. Island
Fig. 2 Possible stove locations.
ST207b
Clearance Requirements:
Minimum Clearances to
Combustible Materials
Measure side clearances as shown in Figures 5 and 6 from the outer edge of the cast iron stove top. Measure rear clearances from the outermost surface of the steel rear skirt.
The heater is approved for installation into an alcove con­structed of combustible materials to the dimensions and clearances shown on the next page. The same clearances apply in a standard parallel instal­lation.
WARNING:
Always maintain required clearances (air spaces) to nearby combustibles to prevent
re hazard. Do not ll air spaces with insulation. All
venting components must maintain a 1” (25 mm) clearance to combustible materials. Maintain a 6” (150 mm) clearance when using a single wall pipe.
• The gas appliance and vent system must be vented directly to the outside of the building and never be attached to a chimney serving a separate solid fuel or gas-burning appliance. Each direct vent appli­ance must use its own separate vent system. Com­mon vents are prohibited.
• Refer to the manufacturer’s instructions included with the venting system for complete installation procedures.
6
20306762
Page 7
Oxford Direct Vent / Natural Vent Gas Heater
A
A
B
B
C
L
C
L
B
D
C
A
Parallel Installation:
Minimum Clearance and Flue Centerline,
Direct Vent and Natural Vent
Stove Clearances A: 4" (102 mm) B: 4" (102 mm) Pipe Centerlines C: 15 D: 9" (229 mm)
Fig. 3 Parallel installation, minimum back and side clearances
and ue centerlines.
1
2" (395 mm)
ST128c
Corner Installation:
Minimum Clearance and Flue Centerline
Direct Vent and Natural Vent
Wall Centerline from Floor
A
A
Effective Minimum Wall Thimble 571⁄2" (1461 mm) (Vermont Castings Group Pipe) Centerline 531⁄2" (1359 mm) (Simpson DuraVent Pipe)
Fig. 5 Minimum wall thimble centerline.
ST1121
Wall and Ceiling Clearances
D
B
C
A
A: Rear Wall 4" (102 mm) B: Min. Clearance 451⁄2" (1156 mm)* C: Min. Alcove Height 73 D: Max. Alcove Depth 48" (1220 mm)
Stove Clearance A: 4" (102 mm) Pipe Centerline B: 141⁄2" (370 mm)
Fig. 4 Corner installation, minimum corner clearances and ue
centerline.
ST129c
Sidewall Clearance 4" (102 mm)
* needed for installing DuraVent Minimum Vent Kit #2792 or Vermont Cast­ings Group Minimum Vent Kit #7TFSDVSK.
Fig. 6 Dimensions and clearances to ceiling or alcove.
Hearth Requirements
The heater must be installed on rigid ooring. When the
heater is installed directly on any combustible surface other than wood ooring, a metal or wood panel extend-
1
2" (1867 mm)*
ST1122
ing the full width and depth of the unit must be used as the hearth. There are no other hearth requirements.
20306762
7
Page 8
Oxford Direct Vent / Natural Vent Gas Heater
20
19
18
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
12 345678910 11 12 13 14 15 16 17 18 19 20
Vertical Run (in feet)
(Measured from the appliance flue collar to the top of the vent pipe.)
Horizontal Run (in feet)
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
ST134a FDV28 Horizontal  vent run 12/3/99 djt areas modified 1/11/00 djt
Gas Specications
Max. Min. Input Input
Model Fuel Gas Control BTU/h BTU/h
2465 Nat Millivolt 28,000 20,000 2466 Prop Millivolt 28,000 19,000
Weight: Fully assembled; 202 lbs.
Gas Inlet and Manifold Pressures
Natural LP (Propane) Inlet Minimum 5.5” w.c. 11.0” w.c. Inlet Maximum 14.0” w.c. 14.0” w.c. Manifold Pressure 3.5” w.c. 10.0” w.c.
Oxford Direct Vent/Natural Vent
Certied to:
ANSI Z21.88 / CSA 2.33 Latest Edition
Vented Gas Fireplace Heaters
The installation of your stove must conform with
local codes, or in the absence of local codes, with the National Fuel Gas Code ANSI Z223.1/NFPA 54 ­latest edition, or CSA B149.1 Installation code. (EX­CEPTION: Do not derate this appliance for altitude up to 4,500 feet (1,370 m). Maintain the manifold pressure at 3.5” w.c. for Natural Gas and 10.0” w.c.
for LP Gas.
Input ratings are shown in BTU per hour and are certied without deration for elevations up to 4,500 feet (1,370 m) above sea level.
For elevations above 4,500 feet (1,370 m) in USA, installations must be in accordance with the cur­rent ANSI Z223.1/NFPA 54 and/or local codes hav­ing jurisdiction.
In Canada, please consult provincial and/or local authorities having jurisdiction for installations at
elevations above 4,500 feet (1,370 m).
WARNING: Improper installation, adjustment, alter­ation, service or maintenance can cause injury or property damage. Refer to this manual for correct installation and operational procedures. For assis­tance or additional information consult a qualied
installer, service agency, or the gas supplier.
8
High Elevations
Horizontal Termination -
Direct Vent ONLY
The vent must rise vertically a minimum of 24” (610 mm)
off the top of the unit, before the rst elbow. The horizontal
run may extend up to 20’ (6 m) and include a vertical rise of up to 40’ (12 m). (Fig. 7) Horizontal termination must also meet the criteria shown in Figures 9 through 11.
• Approved vent systems must terminate above and in­cluding the heavy line in Figure 7.
• Two 45° elbows may be substituted for each single 90° elbow.
• With a rise between 2’ - 5’, one 90° or two 45° elbows may be used.
May use up to three
90° Elbows
One 90°
Elbow
Unacceptable Venting
Conguration
ST134a
Fig. 7 Horizontal vent termination window.
20306762
Page 9
Oxford Direct Vent / Natural Vent Gas Heater
20
Vertical Run (in feet)
ST132a FDV28 Vertical vent run 12/3/99 djt area modified 1/11/00 djt
Vertical Termination - Direct Vent ONLY
A vertical vent system must terminate no less than 8' (2.44 m) and no more than 40' (12 m) above the appli-
ance ue collar. A 21⁄4" restrictor plate (supplied) must be used where specied in all vertically terminated vent sys-
tems. (Fig. 8) NOTE: The restrictor plate supplied with the vertical termination should be discarded. Install restrictor plate supplied with stove directly at stove
outlet. A vertically terminated vent system must also con­form to the following criteria:
• No more than three 90° elbows may be used.
• Two 45° elbows may be substituted for one 90° elbow. No more than six elbows may be used.
• Vent must rise a minimum of 2 feet before offset is used.
• Termination height must conform to roof clearance as
specied in Figure 9.
40
39
All Vertical Termi-
38
37
nations in this area
36
Require use of the
35
1
2
4" Restrictor Plate*
34
33
32
31
30
29
28
27
26
Vertical terminations
25
must be within this area
24
23
22
21
20
19
18
16
(Measure from the appliance flue collar to the top of the vent pipe.)
15
14
13
12
11
No Restrictor Plate
10
9
8
7
6
5
4
3
2
1
0
1 2345678910111213141516171819
Horizontal Run (in feet)
Unacceptable Venting
Conguration
Fig. 8 Vertical vent termination window.
*The Restrictor Plate is used on Direct Vent Installations
Only
20306762
ST132a
Vent Termination Clearances
When planning the installation, consider the location of the vent terminal and clearances. Some of the most com­mon clearances to keep in mind are shown in Figure 10.
Important: All vent clearances must be maintained. Check your vent termination clearances against Fig­ures 9 through 11.
The vent should be placed so that people cannot be burned by accidentally touching the vent surfaces when the stove is operating.
The vent termination should be located where it cannot be damaged by such things as automobile doors, lawn mow­ers or snowblowers and it should be located away from areas where it could become blocked by snow, etc.
Some considerations are:
• Obstructions or impediments to venting.
• Nearby combustible materials that could come into contact with combustion exhaust gases.
• Other nearby openings {within 12” (305 mm)} through which exhaust gas could reenter the building.
• All vegetation within 3’ (76 mm) that may interfere with the draft.
Other factors that inuence where the installation will be
sited include the location of outside walls, where addi­tional heat may be desired in the home, where the family members gather most regularly, and perhaps most impor­tantly, the distance limitations of the venting system.
IMPORTANT
Direct Vent Only
• The horizontal termination must not be recessed into the exterior wall or siding.
• Horizontal vent runs must be level toward the vent termination.
• Clearances around the vent termination must be maintained.
• For installations using Simpson DuraVent pipe, par­allel installations with minimum wall clearance have restricted access for connecting the Horizontal Vent Cap straps to the vent pipe. See the maker’s instruc­tions for recommended installation procedures.
9
Page 10
Oxford Direct Vent / Natural Vent Gas Heater
Venting Termination Clearances
Your stove is approved to be vented either through the side wall, or vertical through the roof.
This unit does not require any opening for inspec-
tion of vent pipe.
Only Vermont Castings Group and Duravent vent-
ing components specically approved and labelled for this stove may be used.
Minimum clearances between vent pipes and com-
bustible materials is one (1”) inch (25 mm), except where stated otherwise.
• Venting terminals shall not be recessed into a wall or siding.
• Horizontal venting must be installed on a level plane without an inclining or declining slope.
There must not be any obstruction such as bushes, gar­den sheds, fences, decks or utility buildings within 24” from the front of the termination hood.
Do not locate termination hood where excessive snow or ice build up may occur. Be sure to check vent termina­tion area after snow falls, and clear to prevent accidental blockage of venting system. When using snow blowers, make sure snow is not directed towards vent termination area.
Location of Vent Termination
It is imperative the vent termination be located observing the minimum clearances as shown on this page.
10
20306762
Page 11
Oxford Direct Vent / Natural Vent Gas Heater
V
V
V
V
V
V
V
X
X
X
D
E
B
B
B
C
B
M
B
A
J
K
F
L
VENT TERMINATION AIR SUPPLY INLET
AREA WHERE TERMINAL IS NOT PERMITTED
H
I
Fixed
Closed
Operable
Operable
Fixed
Closed
V
B
INSIDE
CORNER DETAIL
V
A
G
N
N
CFM145a
General Venting Information - Termination Location
Canadian Installations1 US Installations
A = Clearance above grade, veranda, porch, 12” (30cm) 12” (30cm) deck, or balcony
B = Clearance to window or door that may be 6” (15cm) for appliances 6” (15cm) for appliances opened < 10,000Btuh (3kW), 12” (30cm) < 10,000 Btuh (3kW), 9” for appliances > 10,000 Btuh (3kW) and (23cm) for appliances > 10,000 < 100,000 Btuh (30kW), 36” (91cm) Btuh (3kW) and < 50,000 Btuh for appliances > 100,000 Btuh (30kW) (15kW), 12” (30cm) for appliances > 50,000 Btuh (15kW) C = Clearance to permanently closed window 12” (305mm) recommended to 12” (305mm) recommended to prevent window condensation prevent window condensation
D = Vertical clearance to ventilated soft located
above the terminal within a horizontal 18” (458mm) 18” (458mm) distance of 2 feet (610mm) from the center line of the terminal
E = Clearance to unventilated soft 12” (305mm) 12” (305mm)
F = Clearance to outside corner see next page see next page G = Clearance to inside corner (see next page) see next page see next page H = Clearance to each inside of center line 3’ (91cm) within a height of 15’ (5m) 3’ (91cm) within a height of 15’ extended above meter/regulator assembly above the meter/regulator assembly (5m) above the meter/regulator assy I = Clearance to service regulator vent outlet 3’ (91cm) 3’ (91cm) J = Clearance to nonmechanical air supply inlet 6” (15cm) for appliances < 10,000 6” (15cm) for appliances to building or the combustion air inlet to any Btuh (3kW), 12” (30cm) for < 10,000 Btuh (3kW), 9” other appliances appliances > 10,000 Btuh (3kW) and (23cm) for appliances > 10,000 < 100,000 Btuh (30kW), 36” (91cm) Btuh (3kW) and < 50,000 Btuh for appliances > 100,000 Btuh (30kW) (15kW), 12” (30cm) for appliances > 50,000 Btuh (15kW) K = Clearance to a mechanical air supply inlet 6’ (1.83m) 3’ (91cm) above if within 10’ (3m) horizontally L = Clearance above paved sidewalk or paved 7’ (2.13m)† 7’ (2.13m)† driveway located on public property M = Clearance under veranda, porch, deck or 12” (30cm)* 12” (30cm)* balcony N = Clearance above a roof shall extend a minimum of 24” (610mm) above the highest point when it passes through the roof surface, and any other obstruction within a horizontal distance of 18” (450mm).
1 In accordance with the current CSA-B149 Installation Codes 2 In accordance with the current ANSI Z223.1/NFPA 54 National Fuel Gas Codes † A vent shall not terminate directly above a sidewalk or paved driveway which is located between two single family dwellings and serves both dwellings
* only permitted if veranda, porch, deck or balcony is fully open on a minimum 2 sides beneath the oor:
NOTE: 1. Local codes or regulations may require different clearances.
2. The special venting system used on Direct Vent appliances are certied as part of the appliance, with clearances tested and
approved by the listing agency.
3.Vermont Castings Group assumes no responsibility for the improper performance of the appliance when the venting system does not meet these requirements.
Fig. 9 Vent termination clearances.
20306762
2
11
Page 12
Oxford Direct Vent / Natural Vent Gas Heater
Termination Clearances
Termination clearances for buildings with combustible and noncombustible exteriors.
Inside Corner
G
V
G =
Combustible 6" (152 mm)
Noncombustible 2" (51 mm)
Outside Corner
V
F
F =
Combustible 6" (152 mm)
Noncombustible 2" (51 mm)
Alcove Applications*
D
C
V
O
C
E
Balcony ­with no side wall
Balcony ­with perpendicular side wall
M
V
M =
Combustible & Noncombustible 12" (305 mm)
*NOTE: Termination in an alcove space (spaces open only on one side and with an overhang) is permitted with the dimensions
specied for vinyl or non-vinyl siding and softs. 1. There must be a 3’ (914 mm) minimum between termination caps. 2. All
mechanical air intakes within 10’ (1 m) of a termination cap must be a minimum of 3’ (914 mm) below the termination cap. 3. All gravity air intakes within 3’ (914 mm) of a termination cap must be a minimum of 1’ (305 mm) below the termination cap.
Combustible & Noncombustible
M = 24" (610 mm) P = 20” (508 mm)
Fig. 10 Termination clearances.
Venting Requirements - Natural Vent Only
36
34
32
30
28
26
24
22
20
18
16
14
Vertical Run (in feet)
12
10
8
6
4
(Measured from top of the unit before any elbow)
2
1 2 4 6 8 10 12 14 16 18 20 22 24
Fig. 11 Vent termination window - Natural Vent ONLY.
A
B
Horizontal Run (in feet)
E = Min. 6” (152 mm) for
non-vinyl sidewalls Min. 12” (305 mm) for vinyl sidewalls
O = 8’ (2.4 m) Min.
M
V
P
No.
of Caps D 1 3’ (914 mm) 2 x D 2 6’ (1.8 m) 1 x D 3 9’ (2.7 m) 2/3 x D 4 12’ (3.7 m) 1/2 x D
D
= # of Termination caps x 3
Min.
C
= (2 / # termination caps) x D
Max.
C
Min.
Max.
Actual
Actual
Actual
Actual
Actual
584-15
Venting Runs
NOTE: When venting staight vertical, without any elbow, a minimum of 8 ft. vertical is required off the top of the stove.
= Acceptable venting configuration
= Unacceptable venting configuration
A: Vertical installations up to 36 feet (12m) in height. Up to an 18 ft. horizontal vent run can be installed within the vent system using a maximum of two 90-degree elbows or four 45-degree elbows.
B: Vertical installations up to 36 feet (12m) in height. Up to a 24 ft. horizontal vent run can be installed within the vent system using a maximum of two 45-degree elbows. (Ratio = 2/3, Hor./Vert.)
FP567b
NOTE: When using the FSDHAG, the restrictor
plate supplied with the stove is not used.
12
20306762
Page 13
Oxford Direct Vent / Natural Vent Gas Heater
Venting Requirements and Options -
Direct Vent ONLY
Approved Vent System Components
The heater must be vented to the outdoors through an adjacent exterior wall or through the roof. The venting system must be comprised of the appropriate listed venting components speci­ed on this page. These parts are available from DuraVent Cor­poration or your Vermont Castings Group Dealer.
Refer to Figure 4 for dimensions relevant to the standard mini­mum-vent kits.
Simpson DuraVent Components
www.duravent.com Phone: 1-800-835-4429, Fax: 1-707-446-4740
Minimum Horizontal Vent Kit 2792
Starter Pipe Assembly (incl. inner & outer sections) 2768* 90° Elbow, Blk. 46DVA-E90B* 45° Elbow, Gal. 46DVA-E45 6" Straight, Blk. 46DVA-D6B* 9" Straight, Blk. 46DVA-09B 11" - 145⁄8" Adjustable Straight Section 46DVA-08AB 12" Straight 46DVA-12 24" Straight 46DVA-24B* 36" Straight 46DVA-36B 48" Straight 46DVA-48 Horizontal Vent Cap 46DVA-HC* Wall Plate 46DVA-DC Vinyl Siding Shield 46DVA-VSS Snorkel Termination - 14" 46DVA-SNK-14 Snorkel Termination - 36" 46DVA-SNK30 Wall Strap 46DVA-WS Cathedral Ceiling Support Box 46DVA-CS Storm Collar 46DVA-SC Wall Thimble 46DVA-WT Firestop Spacer 46DVA-FS Flashing 0/12 - 6/12 46DVA-F6 Flashing 6/12 - 12/12 46DVA-F12 Steel Chimney Conversion Kit Kit A (65⁄8" - 85⁄8") 46DVA-KCA Kit B (65⁄8" - 101⁄2") 46DVA-KCB Kit C (65⁄8" - 13") 46DVA-KCC Masonry Chimney Kit 46DVA-KMC Vertical Termination Cap (High Wind) 46DVA-VCH
Vertical Termination Cap (Low Prole) 46DVA-VC
*Included in Minimum Horizontal Vent Kit #2792 All DuraVent Straight vent pipe sections have a net length 11⁄2" (37mm) less than the nominal dimension; i.e., a 6" (152mm) Straight pipe sec-
tion has an effective length of 41⁄2" (115mm).
Vermont Castings Group Vent Components
The following kits are available to meet the needs of most in­stallations. All pipe has a 7" outer diameter and includes a 4" diameter inner section. A (CG) designation indicates the part is
nished in Charcoal Gray paint. Consult your dealer about other
vent parts that may be appropriate to complete the installation.
Through the Wall Vent Kit 7TFSSK
(1) 90-Degree Elbow (CG) (1) 24" termination pipe (CG) (1) 24-44" Adjustable Section (1) Side Wall Termination, cool touch with siding shield (1) Firestop (1) Zero-clearance sleeve (1) Hardware package (1) Finishing plate (CG) (1) Finishing collar (CG)
(4) Charcoal Gray ue pipe rings
Vertical Termination Kit, 1/12-6/12 Pitch 7TDVSKVA
(1) Combination Horizontal Offset / Roof Support (1) Vertical Termination (1) Storm Collar (1) 1/12-6/12 Flashing (1) Finishing Plate (CG) (1) Finishing Collar (CG) (1) Polished Brass Flue Pipe Ring (1) Hardware Package
Vertical Termination Kit, 7/12-12/12 Pitch 7TDVSKVB
(1) 7/12 - 12/12 Flashing and all of the other Vertical Termination parts.
Vertical Termination, Flat Roof 7DVSKVF
(1) Flat Flashing and all of the other Vertical Termination parts.
Twist Lock 24” Straight Pipe (CG) 7TFSDVP24
(1) 24” Non-adjustable Pipe (1) Polished Brass Flue Pipe Ring
Twist Lock 48” Straight Pipe (CG) 7TFSDVP48
(1) 48” Nonadjustable Pipe (1) Polished Brass Flue Pipe Ring
Twist Lock 45-Degree Elbow (CG) 7TFSDVT45
for vertical offsets (1) 45-degree Elbow (1) Polished Brass Flue Pipe Ring
Draft Hood Adapter FSDHAG Combination Offset/Roof Support 7DVCS Attic Insulation Shield 7DVAIS 7” Charcoal Gray Pipe Rings, (4) 7FSDRG 7” Polished Brass Pipe Rings (4) 7FSDRP
Selkirk Corporation Vent Components
www.selkirkcorp.com 1301 W. President George Bush Highway Ste. 330 Richardson, TX 75080 Phone: 1-800-992-8368, Fax: 1-877-393-4145
Appliance Adapter 4DT-AAV 90° Elbow, Blk. 4DT-EL90B 45° Elbow, Blk. 4DT-EL45B 6” Straight, Blk. 4DT-06B 9” Straight, Blk. 4DT-09B 4” - 10” Adjustable Straight Section, Blk. 4DT-AJ12 12” Straight, Blk. 4DT-12B 18” Straight, Blk. 4DT-18B 24” Straight, Blk. 4DT-24B 36” Straight, Blk. 4DT-36B 48” Straight, Blk. 4DT-48B Horizontal Vent Cap 4DT-HC Wall Plate 4DT-WT Vinyl Siding Shield 4DT-VS Snorkel Termination - 14” 4DT-ST14 Snorkel Termination - 36” 4DT-ST36 Wall Strap 4DT-WS/B Cathedral Ceiling Support Box 4DT-CCS Storm Collar 4DT-SC Firestop Spacer 4DT-FS Flashing 0/12 - 6/12 4DT-AF6 Flashing 6/12 - 12/12 4DT-AF12 Steel Chimney Horizontal Kit A 4DT-HKA Horizontal Kit B 4DT-HKB Vertical Kit 4DT-VKC Masonry Chimney Kit 4DT-MCK Vertical Termination Cap 4DT-VC
NOTE: Direct vent pipe may be used on the Natural Vent system from the top of the draft hood adapter to the ceiling.
20306762
13
Page 14
Oxford Direct Vent / Natural Vent Gas Heater
Made in USA
Install the Optional Fan
If you are installing the optional convection Fan Kit #2767 (FK26), continue here. If you are not installing a Fan Kit, go to Page 15, Venting System Assembly.
1. The fan kit includes a Blower Assembly and a Rheostat Assembly, connected by a cable. (Fig. 12) The Blower Assembly mounts to the bottom rear of the stove, and the Rheostat mounts to the valve coverplate. The as­sembly includes a ‘snapstat’ which automatically turns the fan On (or Off) above (or below) approximately 109°. The Rheostat also provides a range of fan speed settings from Off (which overrides the snapstat func­tion) to High. Unpack and inspect the Blower assem-
bly. Conrm that the fan spins freely.
WARNING
This appliance is equipped with a three-prong (ground­ed) plug for your protection against shock hazard and should be plugged directly into a properly grounded three-prong receptacle. Do not cut or remove the grounding prong from this plug.
Remove retaining nut from shaft of rheostat. (if pre-
installed)
Insert the rheostat through the hole in the back of
the left side of the valve bracket, aligning the locator pin with the smaller hole in that bracket.
Thread the retaining nut onto the shaft of the rheo-
stat, tightening with a wrench. Do not overtighten.
Attach the control knob to the rheostat shaft.
Use the wire tie to secure the fan and rheostat wire
harnesses together.
Rear Skirt
Sheet Metal Screws
Not Used on RF Models
Not Used on Oxford
Blower Assembly
ST473
Fig. 12 Fan kit components.
Connect to PC Board on RF Models Only
Snapstat Bracket
Snapstat/ Extension Assembly
Rheostat Assembly
Not Used on RF Models
2. Remove the rear skirt insert panel at the bottom of the Rear Skirt (Fig. 13) and fasten the blower assembly to
the rebox back with the two Phillips pan-head bolts originally installed in the rebox back. (‘1’, Fig. 14)
3. Attach the snapstat assembly to the snapstat bracket with two sheet-metal screws. (‘2’, Fig. 14) Attach the snapstat bracket to the stove with a hex-head bolt passing through the bracket and into the stove base. (‘3’, Fig. 14)
4. The rheostat control switch attaches to the left side of the valve bracket at the front of the stove.
Rear Skirt Insert
Fig. 13 Remove rear skirt insert.
Star Washer
Sheet Metal Screws
Phillips Pan Head Bolts
Star Washer
Fig. 14 Attach the fan assembly and the snapstat.
Fig. 15 Attach the fan rheostat.
1
Rheostat Retaining Collar
Rheostat Knob
2
3
ST757
Snapstat
1/4” - 20 Hex Bolt
Snapstat Bracket
ST314
ST758
14
20306762
Page 15
Oxford Direct Vent / Natural Vent Gas Heater
CEMENT
CEMENT
Venting System Assembly - Direct Vent
General Information
The Oxford is approved for installation only with the vent components listed on Page 13. Follow the vent compo­nent instructions exactly.
For U.S. installations: The venting system must conform with local codes and/or the current National Fuel Gas Code, ANSI Z223.1/NFPA 54.
For Canadian installations: The venting system must conform to the current CSA B149.1 installation code.
Install the Vent Adapter Pipe
(Vermont Castings Group Vent Components)
1. Install the Restrictor Plate. Consult the ‘Vent Run
Specications’ on Page 8 to determine whether the
restrictor plate is needed. If so, put the restrictor plate
in place within the inner ue collar as shown in Figure
16.
5. Install the Outer Adapter Pipe. Apply a 1/4” bead of cement around the inside wall of the pipe, about 1”
from the end. Insert the pipe over the stove ue collar,
keeping the vertical seam oriented to the back of the stove. Also, be sure to align holes on the pipe with the
holes on the ue collar of the rebox. Fasten the pipe to the holes in the ue collar with the #12 x 1/2” sheet
metal screws provided. (Fig. 19)
First Section of Vent Pipe
#8 x 1/2” Sheet Metal Screws
4” Inner Starter Pipe
ST211
Fig. 17 Connect the inner starter with the next section of inner vent pipe.
ST759
Fig. 16 Install the restrictor plate only if required for the vent-
ing conguration. Refer to Page 9.
2. Attach Inner Starter Pipe, (found in with the logset), to the next section of inner pipe.
• Run a bead of sealant about 1/2” from the upper end of the Inner starter pipe and join the two sections together.
• Drill three pilot holes into the Inner Starter and se­cure the assembly with three sheet metal screws. (Fig.
17)
3. Dry t the Outer pipe assembly to the stove for the purpose of determining the center line of the pipe on the wall.
• Side Wall Terminations: Dry t the outer elbow with the vertical outer vent and conrm the centerline align­ment with the wall thimble opening.
Remove the pipes and elbows before continuing with
Step 4.
4. Attach the Inner Vent Assembly to the stove.
• Run a bead of sealant around the bottom end of the starter pipe and attach the assembly to the stove using three 1/4-20 x 3/8” Phillips screws provided in the parts bag. (Fig. 18)
ST760
Fig. 18 Attach inner assembly to ue collar.
ST761
Fig. 19 Fasten outer pipe with #12 x 1/2” sheet metal screw.
20306762
15
Page 16
Oxford Direct Vent / Natural Vent Gas Heater
CEMENT
Install the Vent Adapter Pipe
(Simpson Dura-Vent Components)
1. Install the Restrictor Plate. Consult Page 9 to deter­mine whether the restrictor plate is needed. If so, place
the restrictor plate into the inner ue collar. (Fig. 16)
2. Discard the inner starter pipe shipped with the log­set. Using the starter pipe assembly listed on Page 7, slide the inner section out to allow access.
• Run a bead of sealant around the bottom end of the starter pipe and attach the assembly to the stove using three 1/4-20 x 3/8” Phillips screws provided in the parts bag. (Fig. 20)
3. Install the Outer Adapter Pipe. Apply a 1/4” bead of cement around the outside surface, about one inch from the crimped end. (Fig. 21) Orient the vertical seam to the rear, and insert the crimped end of the
outer pipe into the ue collar. Fasten with three sheet
metal screws provided.
1/4-20 x 3/8 Phillips Screws
Inner Adapter Pipe
Side Wall Termination Assembly
1. Locate the vent opening on the wall. Refer to Figure 5, Page 7, to determine the opening centerline. It may be
necessary to rst position the stove and measure to nd the hole location. Depending on whether the wall
is made of combustible materials, cut the opening to the size shown in Figure 22. Combustible wall open­ings must be framed as shown in Figure 22.
Vermont Castings Group System
93⁄8"
(240 mm
93⁄8"
(240 mm
DuraVent
System
10"
(250 mm)
Combustible Wall
10"
(250 mm)
Framing Detail
71⁄2"
(191 mm)
Fig. 20 Simpson DuraVent - install inner adapter pipe.
Fig. 21 Simpson DuraVent - install outer adapter pipe.
ST762
ST763
VO584-100
Fig. 22 Locate vent opening.
2. Measure the wall thickness and cut the wall sleeve sections to proper length (MAXIMUM 12"). Assemble the sleeve with the #8 sheet metal screws supplied. At-
tach the restop plate to the sleeve end with the holes.
(Fig. 23) NOTE: The wall sleeve is required in com­bustible walls only.
3. Install the Wall Firestop/Sleeve assembly into the wall
cutout and fasten the restop to the wall cutout framing
members. (Fig. 23)
12"
(305 mm)
Max. Length
Sleeve
16
Firestop
Fig. 23 Assemble the wall sleeve and restop.
ZCS103
20306762
Page 17
For DuraVent pipe only: Install vent pipe by aligning the
locking system together, sliding the pipes together and twisting clockwise.
• Install 90° elbow. Twist lock as before.
• Slide the wall plate over horizontal run before attach­ing the horizontal run to the elbow. Fasten wall plate to wall.
4. For Vermont Castings Group Vent Pipe only: If nec­essary, measure to determine the vertical length (X) of pipe required from the adapter pipe to the wall cutout centerline, including a 2” (51mm) overlap at the joint. (Fig. 24) use a hacksaw or tin snips to trim the pipe as needed.
X
Oxford Direct Vent / Natural Vent Gas Heater
X
ST215
Fig. 25 Measure the horizontal length.
Trim Collar
Wall Sleeve
ST764
Fig. 24 Determine the vertical pipe length.
5. Install rst the inner then the outer straight pipe
section(s), trimmed end down, to the point of the el­bow. Drill 3 holes through each joint and fasten with sheet metal screws.
6. Seal and install the elbow using 3 sheet metal screws at each joint.
7. Measure, and cut if needed, the appropriate length of pipe section needed to make the connection through the wall. Include a 2” overlap; i.e. from the elbow to the outside wall face, about 2” or the distance required if installing a second 90° elbow. (Fig. 25)
8. Slip the wall plate and trim collar over the interior end of the horizontal pipe and install into the wall sleeve. Seal the joint inside the wall plate if needed to keep cold air from being drawn into the home.
9. Seal the ends and connect the horizontal pipe to the elbow. Fasten the wall plate to the pipe with three sheet metal screws. Slide the trim collar up against the wall plate to cover the screws. (Fig. 26)
ST216
Fig. 26 Install the horizontal pipe and wall plate parts.
Wall Plate
10. For both Vermont Castings Group and DuraVent
Systems: Install the vent terminal. (Fig. 27) Apply
high temperature sealant one inch from the ends of the inner and outer collars. Guide the inner and outer vent termination collars into the adjacent pipes. Dou­ble check that the vent pipes overlap the collars by 2”. Fasten the termination to the wall with the screws pro­vided, and caulk the joint with weatherproof sealant.
11. For Vermont Castings Group only: Install Charcoal Gray Pipe Rings (#7FSDRG) or Polished Brass Pipe Rings (#7FSDRP) at pipe joints, if desired.
Seal Both Terminal Ends
20306762
Caulk Plate Joint with Weatherproof Sealant
Fig. 27 Install the vent terminal.
ST217
17
Page 18
Oxford Direct Vent / Natural Vent Gas Heater
Vent Termination Below Grade
Install Snorkel Kit #7FSDVSKS when it is not possible to meet the required vent termination clearances of 12” (305 mm) above grade level. The snorkel kit will allow instal­lation depth of down to 7” (178 mm) below grade level. The seven inches is measured from the center of the hori­zontal vent pipe as it penetrates the wall. If the venting
system is installed below grade, a window well must be installed with adequate and proper drainage. (Fig.
28)
NOTE: Be sure to maintain side wall clearances and vent
run restrictions. Refer to Figures 3, 4, 7, and 8.
1. Establish the vent hole through the wall.
2. Remove soil to a depth of approximately 16” (406 mm) below the base of the snorkel. Install a window well
(not supplied). Rell the hole with 12” (305 mm) of
coarse gravel and maintain a clearance of at least 4” (102 mm) below the snorkel. (Fig. 28)
3. Install the vent system as described on Pages 15 -
17.
4. Be sure to make a watertight joint around the vent pipe joint at the inside and outside wall joints.
5. Apply high temperature sealant around the inner and outer snorkel collars. Join the pipes and fasten the snorkel termination to the wall with the screws provid­ed.
6. Level the soil to maintain a 4” clearance below the snorkel.
Waterproof Seal Snorkel Termination Cap
4” Clearance
Gravel
Drain
Window Well
Fig. 28 Snorkel kit installation.
If the foundation is recessed, use extension brackets (not supplied) to fasten the lower portion of the snorkel. Fas-
ten the brackets to the wall rst, and then fasten to the
snorkel with self-tapping #8 x 1/2” sheet metal screws. Extend the vent pipes out as far as the protruding wall face. (Fig. 29)
Around Pipe
Firestop
ST1124
Recessed Wall
Firestop
Finishing
Sheet Metal Screws and Bracket
Wall Screws and Anchors
Waterproof Seal Around Pipe
Fig. 29 Use extension brackets to mount snorkel against recessed wall.
Collar
7” Pipe
Wall Plate
ST219
Vertical (Through the Roof)
Vent Assembly
Note that all vertically terminated installations must in­clude the restrictor plate included with the stove. Refer to Figure 8, Page 9.
Make certain the vent system conforms to all other re-
quirements for vertical termination as specied on Page
9.
This installation will require you to rst determine the roof
pitch and use the appropriate vent components. Refer to Figures 8 and 9 on Pages 9 and 11.
1. Locate the nal position of the stove, observing all
clearances for both the vent and the stove.
2. Plumb to the center of the inner (4”) ue collar from the
ceiling above, and mark that location.
3. Cut the opening:
Vermont Castings Group System: 93⁄8" x 93⁄8" (240 x 240 mm)
4. Plumb any additional opening through the roof or oth-
5. Place the stove in its nal position.
6. Install restop(s) #7DVFS and Attic Insulation Shield
7. Install the appropriate roof support and ashing, mak-
DuraVent System: 10" x 10" (254 x 254 mm)
er construction that may be needed. In all cases, the opening must provide a minimum of 1" (25 mm) clear­ance to the vent pipe.
#7DVAIS as needed. (Fig. 30) If there is a room above
ceiling level, a restop must be installed on both the
bottom and top sides of the ceiling joists. If an attic is above ceiling level, an attic insulation shield must be installed.
ing certain that the upper ange of the ashing base is
below the shingles. (Fig. 31)
18
20306762
Page 19
Oxford Direct Vent / Natural Vent Gas Heater
8. Install appropriate pipe sections until the vent run
reaches above the ashing. The enlarged ends of the
vent sections always face downward.
9. Install the storm collar and seal around the joints. (Fig.
31)
10. Add additional vent lengths to achieve the proper overall height.
11. Apply cement to the inner and outer termination col­lars and install the terminal cap.
#7DVAIS Attic Insulation Shield
#7DVFS Use Four 8d Nails
Firestop
In Upper
Floor
Venting System Assembly - Natural Vent
General Information
The heater is shipped from the factory as a Direct Vent Heater. It may be converted to a Natural Vent heater by installing the Model FSDHAG Draft Hood Adapter.
The heater is approved for installation as a Natural Vent. Vermont Castings Group Direct Vent pipe could be used directly after the Draft Hood Adapter up to the ceiling, then B-vent pipe must be used. Do not mix types of B­vent pipe; use components from one maker or the other. Follow the vent component maker’s instructions exactly. The heater will also accept standard or enamelled 7” (150 mm) diameter pipe, around the Type B venting, for deco­rative purposes only. (Fig. 32)
NOTE: The restrictor plate supplied with the stove is not used for Natural Vent applications.
Decorative 7” Pipe
4” B-vent Pipe
Draft Hood Adapter
Vermont Castings Group Direct Vent System may be used Draft Hood up up to the ceiling
ST222
Fig. 30 Install restops and attic insulation shield.
Storm Collar
Flashing
#7DVSKV (A, B of F) Roof Support
Fig. 31 Roof support and ashing.
#7DVFS Firestop in Ceiling
Sealant
Upper edge of
ange goes
under upper shingles
ST221
ST766
Fig. 32 Decorative 7” pipe may be tted around the B-vent
pipe.
The stove, when installed as a Natural vent heater, in­cludes a vent safety switch. (Fig. 63, Page 32) Operating the stove when it is not connected to a properly installed and maintained venting system, or tampering with or dis­connecting the vent safety switch, can result in carbon monoxide (CO) poisoning and possible death.
For U.S. installations: The venting system must conform with local codes and/or the current National Fuel Gas Code, ANSI Z22.1.
For Canadian installations: The venting system must conform to the current CSA B149.1 installation code.
Install the Vent Pipe
Apply a bead of sealant around bottom end of inner start­er pipe (found in bag with logset) and attach to stove. Ap­ply a bead of sealant around top of inner starter pipe and install the FSDHAG Draft Hood according to Draft Hood instructions. (Fig. 33)
20306762
19
Page 20
Oxford Direct Vent / Natural Vent Gas Heater
CEMENT
Attach the rst section of venting to the draft hood. De­pending on the length of the individual venting sections and the lengths of the decorative pipe (if installed), you may need to slip the decorative pipe over the venting sec­tions before attaching upper sections to lower ones. The sections of decorative pipe should be oriented with their seams (if any) toward the wall; sections usually do not need to be fastened at each joint, other than slip sections. If the layout includes a slip section, this should be the last section of pipe visible in the room, at the ceiling. Complete the venting according to the vent maker’s instructions.
ST767
Fig. 33 Install draft hood adapter.
Install the Log Set
1. Remove the logs from their packaging, and inspect each piece for damage. DO NOT INSTALL DAM-
AGED LOGS.
2. Install the rear log centering it side to side on the sheet
metal shelf at the back of the rebox. (Fig. 34) The log will touch both sides and the back wall of the rebox.
3. Install the right log by engaging hole on bottom with pin on the rear log. (Fig. 34) Then set right bottom side on the burner so the edge of the log touches the right side of the rebox. The right log does not use the loca­tor pins on the burner to stay in place.
4. Install the left log by engaging hole on bottom with pin on rear log. (Fig. 34) Then set left bottom side on the burner so the edge of the log touches the left side of
the rebox.
5. Loosely sprinkle the lava rocks directly on top of the burner in front of and between the decorative grate and the right and left logs. Use the lava rock to cover brackets on the burner. (Fig. 35)
20
Left Log
Rear Log
Fig. 34 Install the back, left and right logs.
Decorative Grate
Right Log
LG141
Connect the Gas Supply Line
Check the Rating Plate attached by a steel cable to the
rebox, to conrm that you have the appropriate rebox
for the type of fuel to be used. The Oxford may be con­verted from one gas to another using the appropriate Fuel Conversion Kit listed on Page 34.
CAUTION
This appliance should only be connect­ed by a qualied gas technician. Test to conrm manifold pressures as specied below.
The heater and its individual shutoff valve must be disconnected from the gas supply piping during
any pressure testing of that system at test pres-
sures in excess of 1/2 psig (3.5 kPa).
The heater must be isolated from the gas supply piping system by closing its individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressure equal to or less than 1/2 psig.
There must be a gas shutoff between the stove and
the supply.
In order to connect Natural Gas, use a tting with 3/8” NPT nipple on the valve side and 1/2” natural gas supply line with an input of 28,000 BTUs at a manifold pressure of 3.5” and minimum inlet sup­ply for adjustment of 5.5” w.c.
In order to connect Propane, use a tting with 3/8” NPT nipple on the valve side and 1/2” propane gas supply line with an input of 28,000 BTUs at a mani­fold pressure of 10.0” and minimum inlet supply for adjustment of 11.0” w.c.
20306762
Page 21
Oxford Direct Vent / Natural Vent Gas Heater
In the U.S.; Gas connection should be made in accor­dance with current National Fuel Gas Code, ANSI Z223.1/ NFPA 54. Since some municipalities have additional local codes, be sure to consult your local authority.
In Canada; consult the local authority and CSA-B149.1 installation code.
Always check for gas leaks with a mild soap and water solution. Do not use an open ame for leak testing.
Light the pilot according to the directions on Page 25, be­fore going to the next step.
Burner Information
The appliance must only use the gas specied on the rat­ing plate, unless converted using a Fuel Conversion Kit. To convert from LP to Natural Gas use Kit #30005155. To convert from Natural Gas to LP use Kit #30005154.
Conversion instructions are provided with each kit and beginning on Page 27 in this manual.
This appliance should be connected to the gas supply only by a qualied gas service technician. Follow all local codes.
There must be a gas shut-off between the stove and the supply.
In order to connect Natural Gas, use a tting with 3/8”
NPT nipple on the valve side and 1/2” natural gas supply line with an input of 28,000 BTUs at a manifold pressure of 3.5” and minimum inlet supply for adjustment of 5.5” w.c.
In order to connect Propane, use a tting with 3/8” NPT
nipple on the valve side and 1/2” propane gas supply line with an input of 28,000 BTUs at a manifold pressure of
10.0” and minimum inlet supply for adjustment of 11.0” w.c.
Air Shutter Adjustment
The Oxford is shipped from the factory with the air shut­ter adjusted to the minimum allowed opening. Refer to Table 1. Based on the altitude where the stove is located, a shutter adjustment is acceptable to provide a mixed bal-
ance of ame color/glow. To adjust the shutter opening,
follow the steps below.
NOTE: The air shutter may only be adjusted to a more open position. The factory setting is the minimum allow­able air shutter opening. (Figs. 38 & 39)
To adjust the air shutter, the following procedures should be followed:
1. Remove barrier screen rst by pulling out and up. Re­move stove front. Lift stove front up and then swing bottom out and away to disengage from the stove body. (Fig. 36)
2. Swing open the swiveling latches at the top left and right corners of the glass frame. (Fig. 59, Page 31)
Fig. 36 Remove stove front.
3. Pull the top edge of the glass and frame assembly
away from the rebox, and lift it off its supports on the bottom of the rebox face. Place the assembly out of the way on a at, padded surface such as a counter
protected by a towel.
4. Take the logset out of the rebox if previously in­stalled.
5. Remove the rear log bracket by unfastening the screw. (Fig. 37)
6. Remove the right and left log bracket assembly by unfastening the two screws which hold the burner in place. (Fig. 37)
7. Hold the burner at the right hand side and lift to clear the right burner leg. Then pull to the right to clear the injectors on the left hand side.
8. The air shutter is located on the bottom of the burner to the left. (Fig. 37) Unfasten the two nuts holding the
Remove Screws
Rear Log Bracket
Pilot
Table 1. Air Shutter Adjustment Minimum rear injector inlet openings.
Model Natural Gas LP Direct Vent 1/2” 1/2” Natural Vent 1/2” 1”
20306762
Left & Right Log Bracket Assembly
Fig. 37 Remove rear log bracket and left and right log bracket assembly.
21
Page 22
Oxford Direct Vent / Natural Vent Gas Heater
90¡
PILOT
ADJ
TP
TH
TPTH
shutter in place. The shutter may be adjusted between the factory adjusted 1/2” to fully open. Reassemble the shutter to allow the rear injector air inlet to close from the minimum 1/2” opening to fully open. (Fig. 39) You
may have to try more than once to nd the correct air
shutter opening for best results depending on your al­titude.
9. Refasten the two nuts and assemble the burner into the unit by sliding the burner in at an angle with the
Air Shutter
See Table 1
Fig. 38 Air shutter in original from-the-factory position.
Front Injector Air Inlet
(Original Position)
Burner
ST352
Air Shutter (May be adjusted up to fully open)
Burner
Left Burner Leg
Injector Shoulder
ST353
Fig. 40 Be sure to maintain 90° angle at left burner leg.
Complete the Assembly
• Open the swiveling latches (cams) on the top left and right corners of the glass frame.
• Position the glass and frame against the rebox by
placing the bottom edge on the brackets on the bottom
face of the rebox.
• Swing the assembly against the rebox, and close the latches rmly against the pins protruding from the re-
box top.
Rear Injector Air Inlet
ST351
Fig. 39 Air shutter adjusted.
left side lower than the right side. Slide the left side onto the injectors. Lower the right hand side down into place. Make sure the burner is as far left as possible and the injector shoulders are inside the burner. NOTE: It is very critical to keep the left burner leg, which holds the injectors, at a 90° angle to the base. (Fig. 40) This
keeps the orices aligned with tubes on the inside of the burner. Failure to do so could affect the ame ap-
pearance and performance of the unit.
10.Refasten the right and left log bracket assembly.
11.Refasten the rear log bracket.
12.Replace logs.
13.Replace glass and stove front.
Follow lighting instructions on Page 25. Check ame color
appearance. NOTE: Allow stove to burn for at least 1/2
hour to establish full ame color.
Should color need further adjustment, repeat steps 1
- 12 for air shutter adjustment.
Install ON/OFF Switch
The switch assembly parts are found in the parts bag.
1. Attach switch assembly to left rear side of stove shroud (when facing shroud) using two screws and existing holes in shroud. (Fig. 41)
2. Run wires down back of stove, under bottom of rear shroud to valve.
3. Attach wires to valve terminals. (Fig. 42)
Switch Assembly
Screws
Fig. 41 Attach switch assembly to rear shroud.
Fig. 42 Attach switch wires to valve.
Existing Holes
ST315
ST228
22
20306762
Page 23
Thermostat Connection (optional)
Use only a thermostat rated for 500 millivolts. Check the table below for the appropriate gauge thermo­stat wire to use for the length of lead required in your in­stallation.
Thermostat
Wire / Gauge Maximum Run
18 20 feet 16 20 - 40 feet 14 up to 60 feet
1. Install the wall thermostat in the desired location and run the wires to the stove location. Terminate these leads with 1/4” female connectors.
2. Connect the thermostat wires to the valve. (Fig. 42)
Install the Stove Front
Insert the handle stub into the hole in the front casting. Fasten in place witht he 3/8” locking nut provided. (Fig.
43)
The front attaches to the stove by four steel tabs that en­gage with corresponding cast ribs onto the sides and bot­tom of the stove body. Position the front about 3” down from stove top and lift the plate to engage the upper tabs behind the adjacent ribs on the sides. (Fig. 44) Then lower the front into position, so the lower tabs engage with the corresponding ribs at the bottom.
When properly installed, the bottom of the stove front can­not be pulled away from the sides without also lifting it.
Oxford Direct Vent / Natural Vent Gas Heater
3/8” Locking Nut
ST773
Fig. 43 Insert handle stub into hole in front. Secure with 3/8” locking nut.
Engage steel tabs behind the cast iron bosses
Handle Stub
ST1126
Fig. 44 Install the front plate.
Bottom tabs engage notch in the leg
20306762
23
Page 24
Oxford Direct Vent / Natural Vent Gas Heater
CERTIFIED
SAFETY BARRIER
DANGER
HOT GLASS WILL
CAUSE BURNS.
Safety Barrier Installation Instructions
NOTE: A barrier designed to reduce the risk of burns
from the hot viewing glass is provided with this appliance and shall be installed for the protection of children and other at risk individuals. If the barrier becomes damaged, the barrier shall be replaced with the manufacturer's barrier for this appliance.* Any safety screen, guard, or barrier removed for servicing the appliance must be replaced prior to operating the appliance.
* See parts list for model number.
The safety barrier has been designed to work with the doors open or closed.
1. Remove screen from packaging.
2. Place the two bottom hooks over the bottom edge of the stove opening. Figure 45
3. Press the screen against the stove snapping the two
spring ngers under the lattice until the screen ts
securely in place.
NOTICE: It is the responsibility of the installer to ensure the barrier is afxed to the stove at the time of installa­tion.
DO NOT TOUCH GLASS
UNTIL COOLED.
NEVER ALLOW CHILDREN
TO TOUCH GLASS.
A barrier designed to reduce the risk of burns from the hot
viewing glass is provided with this appliance and shall
be installed for the protection of children and
other at risk individuals.
20306543
WARNING: The safety screen barrier must be installed after the glass front is
in place. It is NOT a replacement for the
glass and the unit must NOT be oper­ated without the glass in place.
Figure 45­Safety Barrier Installation
24
Spring ngers
Hooks
20306762
Page 25
Operation
LO
HI
Turn
counterclockwise
to decrease
flame height
Turn clockwise
to increase
flame height
Oxford Direct Vent / Natural Vent Gas Heater
Your First Fire
Read these instructions carefully and familiarize yourself with the burner controls. Locate the pilot assembly, Figure
46. Follow the lighting instructions on Page 25 exactly.
During the rst re, it is not unusual to smell some odor
associated with new logs, paint and metal being heated. Odors should dissipate within an hour or so, however, you can open a window to provide fresh air to alleviate the condition.
Pilot and Burner Inspection
Each time you light your heater check that the pilot ame and burner ame patterns are as shown in Figure 48. If ame patterns are incorrect, turn the heater off. Contact your dealer or a qualied gas technician for assistance. Do not operate the heater until the pilot ame is correct.
Follow regular maintenance procedures as described on Page 30.
Flame & Temperature Adjustment
For stoves equipped with HI/LO valves, ame adjustment
is accomplished by rotating the HI/LO adjustment knob located near the center of the gas control valve. (Fig. 47)
Fig. 47 Flame adjustment knob for Honeywell valve.
Flame Characteristics
It is important to periodically perform a visual check of
the pilot and the burner ames. Compare them to Figure
47. If any of the ames appear abnormal, call a service
person.
Pilot Assembly
Fig. 46 Pilot assembly location.
20306762
CO106c
ST769
Red Glow
LG143
Fig. 48 Correct pilot and burner ame patterns.
25
Page 26
Oxford Direct Vent / Natural Vent Gas Heater
PILOT
ON
OFF
Lighting and Operating Instructions
FOR YOUR SAFETY READ BEFORE LIGHTING
WARNING:If you do not follow these instructions exactly, a re or explosion
may result causing property damage, personal injury or loss of life.
A. This heater has a pilot which must be lit manually. When
lighting the pilot follow these instructions exactly.
B. BEFORE LIGHTING smell all around the heater area
for gas. Be sure to smell next to the oor because
some gas is heavier than air and will settle on the
oor.
WHAT TO DO IF YOU SMELL GAS
Do not try to light any replace
Do not touch any electric switch
Do not use any phone in your building
Immediately call your gas supplier from a
neighbor’s phone.
Lighting Instructions
1. STOP! Read the safety information above.
2. Turn off all electrical power to the replace.
3. Turn the ON/OFF switch to “OFF” position, set the remote to OFF or set thermostat to lowest level.
4. Open control access panel.
5. Push in gas control knob slightly and turn clockwise
to “OFF”.
O
L
T
I
P
F
F
O
ON
O
F
F
Follow the gas supplier’s instructions.
If you cannot reach your gas supplier, call the
Fire Department
C. Use only your hand to push in or turn the gas control
knob. Never use tools. If the knob will not push in or
turn by hand, do not try to repair it, call a qualied
service technician. Applying force or any attempted
repair may result in a re or explosion.
D. Do not use this replace if any part has been under
water. Immediately call a qualied service technician
to inspect the heater and to replace any part of the control system and any gas control which has been under water.
10. Push the control knob all the way in and hold. Im­mediately light the pilot by repeatedly depressing the
piezo spark ignitor until a ame appears. Continue
to hold the control knob in for about one (1) minute after the pilot is lit. Release knob and it will pop back up. Pilot should remain lit. If it goes out, repeat steps 5 through 8.
SIT NOVA
6. Remove glass door before lighting pilot. (See Glass Frame Removal section).
7. Wait ve (5) minutes to clear out any gas. Then smell for gas, including near the oor. If you smell gas,
STOP! Follow “B” in the safety information above. If you do not smell gas, go to the next step.
8. Visibly locate pilot by the main burner.
9. Turn knob on gas control counterclockwise to “PILOT”.
1. Turn the ON/OFF switch to Off position or set the thermostat to lowest setting.
2. Turn off all electric power to the replace if service
is to be performed.
26
• If knob does not pop up when released, stop and immediately call your service technician or gas supplier.
• If after several tries, the pilot will not stay lit, turn the gas control knob to “OFF” and call your service technician or gas supplier.
11. Replace glass door.
12. Turn gas control knob to “ON” position.
13. Turn the ON/OFF switch to “ON” position or set thermostat to desired setting.
14. Turn on all electrical power to the replace.
To Turn Off Gas To Heater
3. Open control access panel.
4. Push in gas control knob slightly and turn clockwise to “OFF”. Do not force.
5. Close control access panel.
20306762
Page 27
Oxford Direct Vent / Natural Vent Gas Heater
Troubleshooting the Gas Control System
SIT NOVA 820 MILLIVOLT VALVE
NOTE: Before trouble shooting the gas control system, be sure external gas shut off is in the “On” position.
Symptom
1. Spark ignitor will not light
2. Pilot will not stay lit after carefully following lighting instructions
3. Pilot burning, no gas to main burner
4. Frequent pilot outage problem
Possible Causes
A. Defective or misaligned electrode
at pilot
B. Defective ignitor (Push Button)
A. Defective pilot generator (thermo-
couple), remote wall switch
B. Defective automatic valve
A. Wall switch or wires defective
B. Thermopile may not be generat-
ing sufcient millivoltage
C. Plugged burner orice
D. Defective automatic valve opera-
tor
A. Pilot ame may be too low or
blowing (high) causing the pilot safety to drop out
B. Possible blockage of the vent
terminal
Corrective Action
Using a match, light pilot. If pilot lights, turn off pilot and push the red button again. If pilot will not light - check gap at electrode and pilot-should be 1/8” to have a strong spark.
With the control knob in the pilot position, push the control knob all the way and hold. Check for spark at electrode and pilot. If no spark to pilot, and electrode wire is properly connected, replace the battery in the ignitor module and try again. Refer to Maintenance Section. If the problem still exists, replace the ignitor module box.
Check pilot ame. Must impinge on thermocouple/ther­mopile. NOTE: This pilot burner assembly utilizes both a thermocouple and a thermopile. The thermocouple operates the main valve operation (On and Off). Clean
and or adjust pilot for maximum ame impingement on
thermopile and thermocouple.
Turn valve knob to “Pilot”. Maintain ow to pilot; millivolt
meter should read greater than 10mV. If the reading is okay and the pilot does not stay on, replace the gas valve. NOTE: An interrupter block (not supplied) must be used to conduct this test.
Check wall switch and wires for proper connections. Jumper wire across terminals at wall switch, if burner comes on, replace defective wall switch.. If okay, jumper wires across wall switch wires at valve, if burner comes on, wires are faulty or connections are bad.
1. Be sure wire connections form thermopile at gas valve terminals are tight and thermopile is fully inserted into pilot bracket.
2. One of the wall switch wires may be grounded. Re­move wall switch wires form valve terminals if pilot now stays lit, trace wall switch wiring for ground. May
be grounded to replace or gas supply.
3. Check thermopile with millivolt meter. Take reading at thermopile terminals of gas valve. Should read 250-300 millivolts (minimum 150) while holding valve knob depressed in pilot position and wall switch “Off”.
Replace faulty thermopile if reading is below specied
minimum.
Check burner orices for debris and remove.
Turn valve knob to “On”, place wall switch to “On” millivolt meter should read greater than 150mV. If the reading is okay and the burner does not come on, replace the gas valve.
Clean and/or adjust pilot ame for maximum ame im­pingement on thermopile and thermocouple.
Check the vent terminal for blockage (recycling the ue
gases).
20306762
27
Page 28
Oxford Direct Vent / Natural Vent Gas Heater
PILOT
ON
OFF
PILOT
ADJ
L
O
H
I
A
B
C
O
F
F
P
I
L
O
T
O
D
E
F
O
F
F
P
I
L
O
T
O
Fuel Conversion Instructions
WARNING! This conversion kit shall be installed by a qualied service agency in accordance with the manufacturer’s instructions and all applicable codes and requirements of the authority having ju­risdiction. If the information in these instructions is not followed exactly, a re, explosion or production of carbon monoxide may result causing property damage, personal injury or loss of life. The quali­ed service agency is responsible for the proper installation of this kit. The installation is not proper and complete until the operation of the converted appliance is checked as specied in the manufac­turer’s instructions supplied with the kit.
CAUTION: The gas supply shall be shut off prior to disconnecting the electrical power, before pro­ceeding with the conversion.
Main Gas
Gas Supply Inlet
Fig. 49 Attach the gas line to the left side of the valve.
Conversion Precautions
Before proceeding, turn control knob on valve to OFF and turn gas supply OFF. Turn OFF any electricity that may be going to the appliance.
Line
Remove Screws
Rear Log Bracket
Pilot
Left & Right Log Bracket Assembly
Fig. 50 Remove rear log bracket and left and right log bracket assembly.
8. Remove injector orices from left burner leg using
1/2” wrench. (Fig. 55)
9. Install conversion orices. (Refer to Table 2)
SIT 820 Valve
1. Using TORX T20 bit, remove and discard the three (3) pressure regulator mounting screws (A), pressure regulator tower (B) and the spring and diaphragm as­sembly (C). (Fig. 51)
2. Insure the rubber gasket (D) is properly positioned and install the new HI/LO pressure regulator assem­bly to the valve using the new screws (E) supplied with the kit. Tighten the screws securely. (Ref. torque = 25 in/lb) (Fig. 52)
3. Install the enclosed conversion label (F) to the valve body where it can easily be seen. (Fig. 52)
Conversion Procedure
1. Remove stove front. Lift stove front up and then swing bottom out and away to disengage from the stove body. (Fig. 59, Page 30)
2. Swing open the swiveling latches at the top left and right corners of the glass frame. (Fig. 59, Page 31)
3. Pull the top edge of the glass and frame assembly
away from the rebox face. Place the assembly out of the way on a at, padded surface such as a counter
protected by a towel.
4. Remove the logset from the rebox.
5. Remove the rear log bracket by unfastening the screw. (Fig. 50)
6. Remove the right and left log bracket assembly by unfastening the two screws which hold the burner in place. (Fig. 50)
7. Hold the burner at the right hand side and lift to clear the right burner leg. Then pull to the right to clear the injectors on the left hand side.
28
Fig. 51 Remove mounting screws, pressure regulator tower and spring and diaphragm assembly.
Fig. 52 Replace regulator.
20306762
Page 29
Pilot Orice Conversion
90¡
1. Locate pilot. (Fig. 50)
2. Replace pilot orice.
Pilot Type 1
• Remove pilot hood by lifting up. (Fig. 53) Do not re­move snap ring to remove pilot hood. NOTE: It is not necessary to remove the pilot tube for conversion.
• Remove pilot orice with allen wrench. (Fig. 54)
• Install the conversion orice.
• Reinstall pilot hood. Be sure to align hood with index tab.
Oxford Direct Vent / Natural Vent Gas Heater
Pilot
Index Marks
Pilot Bracket
CO105
Fig. 55 Remove pilot hood. (Your pilot may have a different appearance).
Pilot Hood
Pilot Bracket
CO105a
Fig. 53 Remove pilot hood.
Index Tab
Snap Ring
Fig. 54 Remove pilot orice.
Allen Wrench
CO106a
Pilot type 2
Loosen pilot hood turning counterclockwise using a 7/16” wrench. (Fig. 55) NOTE: You may use penetrat­ing oil to prevent pilot hood threads from seizing up.
Remove pilot orice with needlenose pliers. (Fig. 56)
NOTE: Use a wrench to hold pilot tube in place while
removing the orice.
Install the conversion orice.
• Reinstall pilot hood and tighten until mark on pilot hood aligns with mark on pilot bracket.
NOTE: Be sure burner leg remains at a 90° angle to re-
box base after conversion.
21. Replace burner. Slide the burner in at an angle with left side lower than the right side. Slide the left side onto the injectors, making sure the burner leg remains at a 90° angle to the base. Lower the right hand side down in to place. Make sure the burner is as far left as possible and the injector shoulders are inside the burner.
Pilot Orice
CO106b
Fig. 56 Remove pilot orice.
NOTE: It is very critical to keep the left burner leg, which
holds the injectors, at a 90° angle to the base. (Fig.
57) This keeps the orices aligned with the tubes in­side burner. Failure to do so could affect the ame
appearance and performance of the unit.
22. Place conversion label on valve.
23. Reinstall the right and left log bracket assembly.
24. Reinstall the rear log bracket.
25. Replace logs.
26. Replace glass and stove front. Conversion is complete.
Left Burner Leg
Injector Shoulder
ST353
Fig. 57 Be sure to maintain 90° angle at left burner leg.
20306762
29
Page 30
Oxford Direct Vent / Natural Vent Gas Heater
Table 2. Injector Orice Size Matrix
Conversion to Natural Gas Input (BTU/h)
Kit # Front Part # Rear Part # Minimum Maximum
30005155 #54 / .055" 30000514 #44 / .086” 30000334 19,000 28,000
Conversion to LP Input (BTU/h)
Kit # Front Part # Rear Part # Minimum Maximum
30005154 #69 / .029" 30000513 #54 / .055” 30000514 20,000 28,000
Maintenance
Your gas heater will provide years of service with minimal upkeep. The following procedures will help ensure that your stove continues to function properly.
Annual System Inspection
Have the entire heater and venting system inspected an-
nually by a qualied gas technician. Replace any worn or
broken parts.
Logset and Burner /
Cleaning and Inspection
Cleanliness is critical to the proper function of the heater. The logset and burner must all be kept free of dust and unobstructed by debris. Inspect these areas before each use and clean as necessary.
1. Turn the burner OFF and let the heater cool completely before cleaning.
2. Remove the safety barrier by pulling out, then up.
3. Lift the stove front up and then swing the bottom out to disengage it from the heater shell. (Fig. 58)
4. Carefully remove the glass and frame assembly and
place it out of the way on a at, padded surface such
as a counter protected by a towel.
CAUTION
TURN THE PILOT OFF BEFORE PAINTING. ALLOW THE HEATER TO COOL COMPLETELY BEFORE PAINTING.
6. Use a soft bristled brush to sweep dust or debris from the Logs, Pilot and Burner. Use care as the logs are fragile and susceptible to damage. DO NOT USE A
VACUUM TO CLEAN THE LOGS OR BURNER.
7. Replace the glass panel and frame assembly.
8. Replace the Stove Front.
Care of Cast Iron
An occasional dusting with a dry rag will help keep the painted surfaces looking new. Use high-temperature stove paints, available through your local dealer, to touch­up areas as needed. Clean areas to be painted with a wire brush and be sure to cover the logs, burner and valve assembly, glass and frame assembly. Apply the paint sparingly; two light coats of paint will give better results than a single heavy coat.
Clean porcelain enamel surfaces with a soft, damp cloth. Do not use abrasive cleaning agents. If necessary, use only a cleaning agent formulated especially for use on porcelain enamel surfaces.
Fig. 58 Remove the stove front.
5. Carefully inspect the Logs for damage. Contact your local dealer if any damage is evident. DO NOT OPER-
ATE THE HEATER WITH DAMAGED LOGS.
30
Cleaning the Glass
WARNING: Allow the glass cool completely
before attempting to clean.
It will be necessary to clean the glass periodically. During start-up, condensation, which is normal, forms on the in­side of the glass and causes lint, dust and other airborne particles to cling to the glass surface. Also initial paint curing may deposit a slight lm on the glass. It is there­fore recommended that the glass be cleaned two or three times with a non-ammonia household cleaner and warm
water (we recommend gas replace glass cleaner). After
that the glass should be cleaned two or three times during each heating season depending on the circumstances present.
Clean glass after rst two weeks of operation.
20306762
Page 31
Oxford Direct Vent / Natural Vent Gas Heater
Glass Replacement
Replace glass only with Vermont Castings Group ap­proved parts. Refer to Page 33 for Replacement Parts. Refer to Figure 59 and previous instructions for removal of the damaged glass frame.
Fig. 59 Release the latches to release the glass frame.
Gasket Replacement
The heater uses a ‘tadpole’ type gasket to seal between the glass panel and the frame. In time, this gasket can become brittle and compressed and should be replaced. New gasket is available from your dealer.
Shut off the gas supply and allow the stove to cool. Wear safety goggles and a dust mask.
1. Remove the Front, Glass Frame and Glass Panel. (Figs. 59 & 60) Remove the old gasket. Use a razor blade to separate the glass and gasket from the frame, and to clean the glass of any remaining cement or bits of gasket. Use a cold chisel if necessary.
2. Determine the correct length of gasket by laying it out around the edge of the glass. Allow an extra 1 - 2” (25­50 mm). Mark the spot to be cut. Use a utility knife.
3. Starting on a long edge, remove about 6” of the pro-
tective paper strip and apply the at adhesive face of
the gasket around the outside-facing edge of the pan­el. Continue around the panel, applying a bout 6” at a time and being careful to not stretch the material. Do not overlap the gasket ends. (Fig. 60)
4. Apply a thin bead of high temperature silicone rubber sealant along the inside corner of the glass frame, all
around the perimeter. Place the at gasketed side of
the glass panel back into the steel frame. Pinch the rounded inside-facing gasket material to bulk it up.
5. Replace the glass frame and front panel as previously described.
Inspect the Vent System Annually
Have the vent system inspected annually by a qualied
technician. Shut off the main gas supply before inspect­ing the system. Both the inner exhaust pipe and the outer
combustion supply pipe must be checked to conrm that
they are unblocked and in good condition.
Check the Gas Flame Regularly
To ensure that the stove is operating properly, check the
ames periodically to conrms they match Figure 60. The ames will be blue during the rst 15-20 minutes of opera-
tion, and will gradually turn to yellow after that.
Do not use your stove if the ame pattern differs from that shown here. Contact your dealer or a qualied technician
for help.
Stove Disassembly
If there is ever a need to remove the rebox assembly from the stove shell, support the rebox with solid stands
about 6” (150 mm) tall under the left and right outer edges
of the rebox base. Do not set the rebox assembly di­rectly on the oor; this can damage the control valve and/ or the gas lines from the valve to the rebox.
Before removing the rebox from the shell, disconnect
the on/off switch wires from the valve. If the assembly includes the optional fan, disconnect the fan rheostat. If the installation includes a wall thermostat, disconnect the thermostat leads from valve.
Disconnection and reconnection to the gas line should
only be done by a qualied gas service technician.
Upon reinstallation, the vent system must be sealed to
the rebox as shown in the installation section, Page 16. Also be sure the logs are placed in the rebox correctly,
as shown in Figures 34 & 35, Page 20.
Red Glow
Fig. 60 Wrap the gasket material around the outside edge of the glass.
20306762
Fig. 61 Correct ame pattern.
31
Page 32
Oxford Direct Vent / Natural Vent Gas Heater
OFF
ON
Thermopile
Black
Black
Millivolt
Gas Valve
TP/TH
TP
TH
Thermostat
(Optional)
Thermopile
Black
Black
Millivolt
Gas Valve
TP/TH
TP
TH
Thermocouple
Safety Limit
Switch
Valve
Wiring Diagrams
On/Off Switch Wiring
POWER
CORD
FAN
ST124b
Optional Thermostat Wiring
ST124c
Fig. 62 On/Off switch and optional thermostat circuit.
NOTE: IF ANY OF THE ORIGINAL WIRE, AS SUP-
PLIED WITH THE APPLIANCE, MUST BE RE­PLACED, IT MUST BE REPLACED WITH TYPE SF-2, 200° WIRE OR ITS EQUIVALENT.
Chassis Ground
Chassis Ground
WHT
BLK
GRN
BLK
BLK
FAN JUNCTION BOX
Strain Relief
WHT
BLK
BLK
GRN
RHEOSTAT / SNAPSTAT
BLK
ON / OFF Rheostat
Snapstat
BOX
ST153
Fig. 63 Draft hood adapter wiring.
32
ST665
MOTOR
BLK
WHT
BLK
BLK
GRN
Fig. 64 Fan circuit.
ON/OFF RHEOST AT
Schematic Diagram
BLK
WHT
SNAPST AT
20306762
ST236
Page 33
Oxford Direct Vent / Natural Vent Gas Heater
Replacement Parts
1
1a
1c
1b
10
12
21
11
22
28
26
2
3
4
5
16
18
13
9
14
19
20
27
17
23
7
6
40
25
24
31
29
33
36a,b
15a,b, c,d
Vermont Castings Group reserves the right to make changes in design, materials, specications, prices and discontinue colors and products at any
time, without notice.
34
30
8
37
35
32
CEMENT
Ref. Description Oxford
1. Gas Log Assembly - SDV30 20003458
1a. Rear Log 20003459 1b. Right Log 20003460 1c. Left Log 20003461
2. Small Lava Rock Package 57897
3. Top 30001925
4. Front 30001928
5. Door 30001929
6. End, Rt 30001927
7. End, Lt 30001926
8. Leg 30001930
9. Manifold Assembly 20003739
20306762
33
Page 34
Oxford Direct Vent / Natural Vent Gas Heater
Replacement Parts (continued)
Ref. Description Oxford
10. Glass, DV25 1601691
11. Glass Frame Assembly - SDV30 30000127
12. Gasket, Glass - Med. Knit - RDV40 1203702
13. Pilot Top Convertible 10002266
14. Pilot Assembly 3Way N/DV RN 0.199.706 10002264 Pilot Assembly 3Way N/DV RP 0.199.703 10002265
15a. Orice Hood #69 - Front - LP 30000513 15b. Orice Hood #54 - Front - NG 20000130 15c. Orice Hood #54 - Rear - LP 20000130 15d. Orice Hood #44 - Rear - NG 30000334
16. Thermocouple 24” 24D0808
17. Thermopile 18” RS 7533113
18. Electrode Ignitor w/Cable SIT24 10001297
19. Nut Electrode SIT #0.974.144 57886
20. Tubing Pilot w/Fittings 1/8 x 24” 10001296
21. Burner Housing Assembly NG/LP 20002214
22. Grate, Burner - JDV 20002167
23. Ashdoor Handle Assy - E/V/WSI 5004241
24. Handle, Damper - Maple Wood - Blk 1600664
25. Switch ON/OFF - RN/RP Models 30000874
26. Wiring Harness - FSDV32 RN/JDV 10002582
27. Right Log Bracket 20002166
28. Left Log Bracket 20002165
29. Nut, Hex Jam 3/8 -16 TOPLK-Z 1203290
30. Gasket, Base Pan - JDV 20002282
31. Gasket, Base Pan Inner 20002566
32. Gasket Cement, 3 oz tube (not shown) 1206122
33. Gasket, HE Door 1203687
34. Sensor 2450 CMG-8184-0032 10002013
35. Pan Hd, SL 1/4-20 x 3-Z 1201310 36a. Valve Nova SIT820.662 RN (Serial #’s starting with 6414) 20010563 36b. Valve Nova SIT820.653 RP (Serial #’s starting with 6414) 20010645
37. Ignitor Piezo w/Nut SIT 057958
38. Bracket Piezo Ignitor (not shown) 20010876
39. *Magnet, Control Door (not shown) 1408818
40. Safety Barrier 30007256
*Use common super glue or silicone to attach magnets.
Fuel Conversion Kits
Conversion Kit, NG to LP - OXDV30NV Kit #30005154 Conversion Kit, LP to NG - OXDV30PV Kit #30005155
34
20306762
Page 35
Oxford Direct Vent / Natural Vent Gas Heater
Optional Accessories
Fan Kits
FK26 Fan
The FK26 fan helps distribute heated air from within
the rebox out into the room. The fan is controlled by a snapstat that turns power on and off as the rebox tem-
perature rises above and falls below a preset tempera­ture. A rheostat provides for variable fan speeds.
Specications
115 Volt / 60Hz / .75 Amps
Maintenance
The fan itself does not require regular maintenance, how­ever, periodic cleaning of the fan and the surrounding area is required.
Installation
Refer to Page 14 for installation instructions.
Remote Controls
The remote control allows you to turn the heater on or off from anywhere in the room. Refer to Page 32 for wiring diagrams.
Model Functions Controlled RC1 ON/OFF RC2 ON/OFF and Temperature IMTFK Wall mounted thermostat control
Decorative Rings
7” brass or charcoal gray rings are available to add a dec­orative touch to the exposed stove pipe.
Model Description 7FSDRG/4 7” Charcoal Gray Rings (4)
20306762
35
Page 36
Oxford Direct Vent / Natural Vent Gas Heater
36
20306762
Page 37
Oxford Direct Vent / Natural Vent Gas Heater
20306762
37
Page 38
Oxford Direct Vent / Natural Vent Gas Heater
38
20306762
Page 39
Oxford Direct Vent / Natural Vent Gas Heater
LIMITED LIFETIME WARRANTY
PRODUCT COVERED BY THIS WARRANTY All Vermont Castings Group gas stoves equipped with an Insta-Flame Ceramic Burner.
BASIC WARRANTY
Vermont Castings Group (hereinafter referred to collectively as the Company) warrants that your new Vermont Castings Group Gas Fireplace/Stove is free from manufacturing and material defects for a period of one year from the date of purchase, subject to the following conditions and limitations.
EXTENDED LIFETIME WARRANTY
The heat exchanger, where applicable, and combustion chamber of every Vermont Castings Group gas product is warranted for life against through wall perforation. All appliances equipped with an Insta-Flame Ceramic Burner have limited lifetime coverage on the ceramic burner plaque. Warrantees are made to the original owner subject to proof of purchase and the conditions and limitations listed on this Warranty Document
COMPONENT WARRANTY
CAST IRON: All external and internal cast iron parts are warranted for a period of three years.
Note: On porcelain enamel nished external parts and accessories
The Company offers no Warranty on chipping of enamel surfaces. In­spect all product prior to accepting it for any damage to the enamel.
The salt air environment of coastal areas or a high humidity environ­ment can be corrosive to the porcelain enamel nish. These condi­tions can cause rusting of the cast iron beneath the porcelain enamel
nish, which will cause the nish to ake off.
Dye lot variations with replacement parts and/or accessories can oc­cur and are not covered by warranty.
GLASS DOORS: Glass doors are covered for a period of one year. Glass doors are not warranted for breakage due to misuse or accident. Glass doors are not covered for discoloration or burned in stains due to environmental issues, or improper cleaning and maintenance.
BRASS PLATED PARTS AND ACCESSORIES: Brass parts should be cleaned with Lemon oil only. Brass cleaners cannot be used. Mortar
mix and masonry cleaners may corrode the brass nish. The Company
will not be responsible for, nor will it warrant any brass parts which are damaged by external chemicals or down draft conditions.
GAS VALVES: Gas valves are covered for a period of one year
ELECTRONIC AND MECHANICAL COMPONENTS: Electronic and mechanical components of the burner assembly are covered for one year. All steel tube burners are warranted for one year.
ACCESSORIES: Unless otherwise noted all components and Vermont Castings Group company supplied accessories are covered for a period of one year.
CONDITIONS AND LIMITATIONS
• This new Vermont Castings Group product must be installed by a
competent, authorized, service contractor. A licensed technician, as prescribed by the local jurisdiction must perform any installation/ser­vice work. It must be installed and operated at all times in accor­dance with the Installation and Operating instructions furnished with the product. Any alteration, willful abuse, accident, or misuse of the product shall nullify this warranty.
• This warranty is non-transferable, and is made to the original owner,
provided that the purchase was made through an authorized supplier of the Company.
• The customer must pay for any Authorized Dealer in-home travel fees
or service charges for in-home repair work. It is the dealers option whether the repair work will be done in the customer’s home or in the dealer’s shop.
• If upon inspection, the damage is found to be the fault of the manu-
facturer, repairs will be authorized at no charge to the customer parts and/or labor.
• Any part and/or component replaced under the provisions of this war­ranty is covered for six months or the remainder of the original war­ranty, whichever is longest.
• This warranty is limited to the repair of or replacement of part(s) found to be defective in material or workmanship, provided that such part(s) have been subjected to normal conditions of use and service, after
said defect is conrmed by the Company’s inspection.
• The company may, at its discretion, fully discharge all obligations with respect to this warranty by refunding the wholesale price of the defec­tive part(s)
• Any installation, labor, construction, transportation, or other related costs/expenses arising from defective part(s), repair, replacement, or otherwise of same, will not be covered by this warranty, nor shall the Company assume responsibility for same. Further, the Company will not be responsible for any incidental, indirect, or consequential dam­ages except as provided by law.
SOME STATES DO NOT ALLOW FOR THE EXCLUSION OR LIMI-
TATIONS OF INCIDENTAL AND CONSEQUENTIAL DAMAGES OR LIMITATIONS ON HOW LONG AN IMPLIED WARRANTY LASTS, SO THE ABOVE LIMITATIONS MAY NOT APPLY TO YOUR CIR­CUMSTANCES. THIS WARRANTY GIVES YOU SPECIFIC RIGHTS AND YOU MAY HAVE OTHER RIGHTS WHICH VARY FROM STATE TO STATE.
• All other warranties-expressed or implied- with respect to the product, its components and accessories, or any obligations/liabilities on the part of the Company are hereby expressly excluded.
• The Company neither assumes, nor authorizes any third party to as­sume on its behalf, any other liabilities with respect to the sale of this Vermont Castings Group product
• The warranties as outlined within this document do not apply to chim­ney components or other non Vermont Castings Group accessories used in conjunction with the installation of this product..
• Damage to the unit while in transit is not covered by this warranty but is subject to claim against the common carrier. Contact the dealer
from whom you purchased your replace/stove (do not operate the
appliance as this might negate the ability to process the claim with the carrier).
• The Company will not be responsible for:
a) Down drafts or spillage caused by environmental conditions such
as near-by trees, buildings, roof tops, hills, or mountains.
b) Inadequate ventilation or negative air pressure caused by me-
chanical systems such as furnaces, fans, clothes dryers, etc.
• This warranty is void if:
a) The replace has been operated in atmospheres contaminated by
chlorine, uorine, or other damaging chemicals.
b) The replace has been subjected to prolonged periods of damp-
ness or condensation
c) Any damages to the replace, combustion chamber, heat exchang-
er or other components due to water, or weather damage, which is the result of but not limited to, improper chimney/venting installation.
d) Any alteration, willful abuse, accident, or misuse of the product has
occurred.
IF WARRANTY SERVICE IS NEEDED…
1) Contact your supplier. Make sure you have your warranty, your sales receipt, and the model/serial number of your Vermont Cast­ings Group product.
2) DO NOT ATTEMPT TO DO ANY SERVICE WORK YOURSELF.
20306762
39
Page 40
EFFICIENCY RATINGS
EnerGuide Ratings Fire-
Model
OXDV30NV 63.0
place Efciency (%)
Based on CSA P.4.1-09
149 Cleveland Drive • Paris, Kentucky 40361
www.vermontcastingsgroup.com
Loading...