A barrier designed to reduce the risk of burns from the hot
viewing glass is provided with this appliance and shall
be installed for the protection of children and
other at risk individuals.
20306543
Installation and Operating Instructions
Models: OXDV30NVSB
WARNING:
FIRE OR EXPLOSION HAZARD
Failure to follow safety warnings exactly
could result in serious injury, death or
property damage.
• Do not store or use gasoline or other
ammable vapors and liquids in the
vicinity of this or any other appliance.
• WHAT TO DO IF YOU SMELL GAS
– Do not try to light any appliance.
– Do not touch any electrical switch; do
not use any phone in your building.
– Leave the building immediately.
– Immediately call your gas supplier from
a neighbor's phone. Follow the gas
supplier's instructions.
– If you cannot reach your gas supplier,
call the re department.
• Installation and service must be performed
by a qualied installer, service agency or
the gas supplier.
WARNING: Improper installation, adjustment,
alteration, service or maintenance can cause
injury or property damage. Refer to this manual.
For assistance or additional information consult
a qualified installer, service agency or the
gas supplier.
This appliance is for use only with the type of gas
indicated on the rating plate. This appliance is
not convertible for use with other gases, unless
a certied kit is used.
This appliance may be installed in an aftermarket,*
permanently located, manufactured home (USA
only) or mobile home, where not prohibited by
local codes.
* Aftermarket: Completion of sale, not for purpose of resale, from
the manufacturer.
CERTIFIED
SAFETYBARRIER
INSTALLER: Leave this manual with the appliance.
CONSUMER: Retain this manual for future
reference.
20306762 12/14 Rev. 1
Page 2
Oxford Direct Vent / Natural Vent Gas Heater
Table of Contents
PLEASE READ THE INSTALLATION & OPERATING INSTRUCTIONS BEFORE USING APPLIANCE.
Thank you and congratulations on your purchase of an Vermont Castings Group stove.
IMPORTANT: Read all instructions and warnings carefully before starting installation. Failure to follow these
instructions may result in a possible re hazard and will void the warranty.
INSTALLATION & OPERATING INSTRUCTIONS
General Information .................................3
Requirements for the Commonwealth of Massachusetts ....4
The Oxford Direct Vent/Natural Vent Room Heater, Model
No. OXDV30NV, is a vented gas appliance listed to the ANSI
standard Z21.88-2009 and CSA-2.33-2009 for Vented Room
Heaters, and CSA 2.17-M91, Gas-Fired Appliances For Use
at High Altitudes.
The installation of the Oxford Direct Vent/Natural Vent Room
Heater must conform with local codes, or in the absence of local codes, with National Fuel Gas Code, ANSI Z223.1/NFPA
54 — latest edition and CSA B-149.1 Installation Code. (EXCEPTION: Do not derate this appliance for altitude. Maintain
the manifold pressure at 3.5” w.c. for Natural Gas and 10.0”
w.c. for LP gas at maximum input.)
This appliance is only for use with the type of gas indicated
on the rating plate. This appliance is not convertible for use
with other gases unless a certied kit is used.
Installation and replacement of gas piping, gas utilization equipment or accessories, and repair and servicing of equipment shall be performed only by a qualied
agency, preferably NFI or WETT (Canada) certied. The
term “qualied agency” means any individual, rm, cor-
poration, or company that either in person or through a
representative is engaged in and is responsible for (a)
installation or replacement of gas piping, or (b), the connection, installation, repair, or servicing of equipment,
who is experienced in such work, familiar with all precautions required, and has complied with all the requirements of the authority having jurisdiction.
The Oxford Direct Vent/Natural Vent Room Heater should
be inspected before use and at least annually by a qualied service agency. It is imperative that control compartments, burners, and circulating air passageways of the
appliance be kept clean.
The Oxford Direct Vent/Natural Vent Room Heater and its
individual shut-off valve must be disconnected from the gas
supply piping during any pressure testing of that system at
test pressures in excess of 1/2 psig (3.5 kPa).
The Oxford Direct Vent/Natural Vent Room Heater must be
isolated from the gas supply piping system by closing its individual manual shutoff valve during any pressure testing of
the gas supply piping system at test pressures equal to or
less than 1/2 psig.
‘Direct Vent’ describes a sealed combustion system in which
incoming outside air for combustion and outgoing exhaust enter and exit through two separate concentric passages within
the same sealed vent system. The system does not use room
air to support combustion. The Direct Vent system permits
the gas appliance to be vented directly to the outside atmosphere through the side of the house or vertically through the
roof. Conventional venting systems (Natural Vent) take air
from the room for combustion and vent the exhaust vertically
through the roof to the atmosphere.
This appliance is approved for bedroom installations in the
U.S. and Canada.
This appliance may be installed in an aftermarket* manufactured (mobile) home, where not prohibited by state or local
codes.
20306762
Oxford Direct Vent / Natural Vent Gas Heater
WARNING: Operation of this heater when not connected
to a properly installed and maintained venting system
can result in carbon monoxide (CO) poisoning and possible death.
The Oxford Direct Vent/Natural Vent Room Heater, when
installed, must be electrically grounded in accordance with
local codes or, in the absence of local codes, with the National Electrical Code ANSI/NFPA 70, (latest edition), or of
the current Canadian Electrical Code C22.1.
Due to high temperatures this appliance should be located out of trafc and away from furniture and draperies.
WARNING: This appliance is hot while in operation.
Keep children, clothing, and furniture away. Contact
may cause burns or ignition of combustible materials.
Children and adults should be alerted to the hazards
of high surface temperatures and should stay away to
avoid burns or clothing ignition. Young children should
be carefully supervised when they are in the same room
as the appliance.
Clothing or other ammable materials should not be
placed on or near the appliance.
Any safety screen, glass or guard removed for servicing an appliance must be replaced prior to operating the
appliance.
The appliance area must be kept clear and free from
combustible materials, gasoline, and other ammable
vapors and liquids.
The ow of combustion and ventilation air must not be
obstructed. The installation must include adequate accessibility and clearance for servicing and proper op-
eration.
WARNING: Do not operate the Room Heater with the
glass panel removed, cracked or broken. Replacement
of the panel should be done by a licensed or qualied
service person.
Do not use this appliance if any part has been under
water. Immediately call a qualied service technician to
inspect the appliance and to replace any part of the control system and any gas control which has been under
water.
Do not burn wood, trash or any other material for which
this appliance was not designed. This appliance is designed to burn either natural gas or propane only.
This gas appliance must not be connected to a chimney
ue serving a separate solid-fuel burning appliance.
CAUTION: Label all wires prior to disconnection when
servicing controls. Wiring errors can cause improper
and dangerous operation.
Verify proper operation after servicing.
Proposition 65 Warning: Fuels used in gas, woodburning or
oil red appliances, and the products of combustion of such
fuels, contain chemicals known to the State of California to
cause cancer, birth defects and other reproductive harm.
California Health & Safety Code Sec. 25249.6
* Aftermarket: Completion of sale, nor for purpose of resale, from the
manufacturer.
3
Page 4
Oxford Direct Vent / Natural Vent Gas Heater
Requirements for the Commonwealth of Massachusetts
All gas tting and installation of this heater shall only be
done by a licensed gas tter or licensed plumber.
For all side wall horizontally vented gas fueled equipment
installed in every dwelling, building or structure used in whole
or in part for residential purposes, including those owned
or operated by the Commonwealth and where the side wall
exhaust vent termination is less than seven (7) feet above
nished grade in the area of the venting, including but not
limited to decks and porches, the following requirements
shall be satised:
Installation of Carbon Monoxide Detectors
At the time of installation of the side wall horizontal vented
gas fueled equipment, the installing plumber or gas tter
shall observe that a hard wired carbon monoxide detector
with an alarm is installed on each additional level of the
dwelling, building or structure served by the side wall
horizontal vented gas fueled equipment. It shall be the
responsibility of the property owner to secure the services
of qualied licensed professionals for the installation of
hard wired carbon monoxide detectors.
In the event that the side wall horizontally vented gas fueled
equipment is installed in a crawl space or an attic, the hard
wired carbon monoxide detector with alarm and battery
back-up may be installed on the next adjacent oor level.
In the event that the requirements of this subdivision can not
be met at the time of completion of installation, the owner
shall have a period of thirty (30) days to comply with the
above requirements; provided, however, that during said
thirty (30) day period, a battery operated carbon monoxide
detector with an alarm shall be installed.
Approved Carbon Monoxide Detectors
Each carbon monoxide detector as required in accordance
with the above provisions shall comply with NFPA 720 and
ANSI/UL 2034 listed and IAS certied.
Signage
A metal or plastic identication plate shall be permanently
mounted to the exterior of the building at a minimum height
of eight (8) feet above grade directly in line with the exhaust
vent terminal for the horizontally vented gas fueled heating
appliance or equipment. The sign shall read, in print size no
less than one-half (1/2) inch in size, “GAS VENT DIRECTLY
BELOW, KEEP CLEAR OF ALL OBSTRUCTIONS”.
Inspection
The state or local gas inspector of the side wall horizontally
vented gas fueled equipment shall not approve the
installation unless, upon inspection, the inspector observes
carbon monoxide detectors and signage installed in
accordance with the provisions of 248 CMR 5.08(2)(a)1
through 4.
Exemptions
The following equipment is exempt from 248 CMR
5.08(2)(a)1 through 4:
• The equipment listed in Chapter 10 entitled “Equipment
Not Required To Be Vented” in the most current edition
of NFPA 54 as adopted by the Board; and
• Product Approved side wall horizontally vented gas fueled
equipment installed in a room or structure separate from
the dwelling, building or structure used in whole or in
part for residential purposes.
MANUFACTURER REQUIREMENTS
Gas Equipment Venting System Provided
When the manufacturer of Product Approved side wall
horizontally vented gas equipment provides a venting
system design or venting system components with the
equipment, the instructions provided by the manufacturer
for installation of the equipment and the venting system
shall include:
• Detailed instructions for the installation of the venting
system design or the venting system components;
and
• A complete parts list for the venting system design or
venting system.
Gas Equipment Venting System NOT Provided
When the manufacturer of a Product Approved side wall
horizontally vented gas fueled equipment does not provide
the parts for venting the ue gases, but identies “special
venting systems”, the following requirements shall be
satised by the manufacturer:
• The referenced “special venting system” instructions shall
be included with the appliance or equipment installation
instructions; and
• The “special venting systems” shall be Product
Approved by the Board, and the instructions for that
system shall include a parts list and detailed installation
instructions.
A copy of all installation instructions for all Product Approved
side wall horizontally vented gas fueled equipment, all
venting instructions, all parts lists for venting instructions,
and/or all venting design instructions shall remain with
the appliance or equipment at the completion of the
installation.
4
20306762
Page 5
Oxford Direct Vent / Natural Vent Dimensions
Refer to Page 6 for Flue Collar
Centerline Dimensions
Oxford Direct Vent / Natural Vent Gas Heater
6³⁄₄"
(172mm)
C
L
Valve Inlet
24¹⁄₂"
(622mm)
28³⁄₈"
(721mm)
Valve
C
L
4³⁄₈"
Inlet
(111mm)
12¹⁄₂"
(318mm)
17"
(419mm)
Fig. 1 Oxford dimensions.
23"
(584mm)
Attention
The Oxford stove is shipped from the factory as a Direct Vent Gas Heater. This heater may be converted into
a Natural Vent unit in the eld. If a Natural Vent heater is desired, the FSDHAG Draft Hood must be directly
installed to the top of the unit according to the installation instructions. The Draft Hood Adapter is available
in the 7FSDHASK stove kit or as a separate item.
When the stove is converted to Natural Vent, it uses 4” vent pipe. For aesthetic purposes the Vermont
Castings Group direct vent system may be used up to the ceiling.
20306762
5
Page 6
Oxford Direct Vent / Natural Vent Gas Heater
A
B
E
C
D
Installation Requirements
The installation must conform with local codes or, in the
absence of local codes, with the National Fuel Gas Code,
ANSI Z223.1/NFPA 54 - latest edition. (EXCEPTION: Do
not derate this appliance for altitude. Maintain the manifold pressure at 3.5” w.c. for Natural Gas, and 10” w.c. for
Propane).
In Canada, installation must be in accordance with the current CSA B-149.1 Installation Codes and/or local codes.
The installation should be done by a qualied service
person who is familiar with the building codes and
installation techniques appropriate for your area to
accomplish a safe and effective installation.
Your dealer or your local gas supplier will be able to
refer a qualied service person.
WARNING: Due to high temperatures, the
HEATER should be located out of trafc and
away from furniture and draperies.
The surface of the Heater Is hot when it is in use.
Young children should be watched carefully when
they are in the same room when the Heater is in use,
and they should be taught to avoid the hot surface.
Keep any objects that can burn well away from the
Heater, and observe the recommended clearances
that follow.
Locating the Stove
In choosing a location for the stove, consider:
• The location of outside walls;
• Where additional heat is needed:
• Where family members gather most often;
• The vent system requirements.
NOTE: We do not recommend the use of wallpaper next
to this stove. Over time, radiant heat may cause the wallpaper to shrink, or may adversely affect the binders in the
wallpaper adhesive.
Direct Vent System Only
A. Flat on corner wall D. Cross Corner
B. Room Divider E. Flat on wall
C. Island
Fig. 2 Possible stove locations.
ST207b
Clearance Requirements:
Minimum Clearances to
Combustible Materials
Measure side clearances as shown in Figures 5 and 6
from the outer edge of the cast iron stove top. Measure
rear clearances from the outermost surface of the steel
rear skirt.
The heater is approved for installation into an alcove constructed of combustible materials to the dimensions and
clearances shown on the next page.
The same clearances apply in a standard parallel installation.
WARNING:
Always maintain required clearances (air
spaces) to nearby combustibles to prevent
re hazard. Do not ll air spaces with insulation. All
venting components must maintain a 1” (25 mm)
clearance to combustible materials. Maintain a 6”
(150 mm) clearance when using a single wall pipe.
• The gas appliance and vent system must be vented
directly to the outside of the building and never be
attached to a chimney serving a separate solid fuel
or gas-burning appliance. Each direct vent appliance must use its own separate vent system. Common vents are prohibited.
• Refer to the manufacturer’s instructions included
with the venting system for complete installation
procedures.
local codes, or in the absence of local codes, with
the National Fuel Gas Code ANSI Z223.1/NFPA 54 latest edition, or CSA B149.1 Installation code. (EXCEPTION: Do not derate this appliance for altitude
up to 4,500 feet (1,370 m). Maintain the manifold
pressure at 3.5” w.c. for Natural Gas and 10.0” w.c.
for LP Gas.
Input ratings are shown in BTU per hour and are
certied without deration for elevations up to 4,500
feet (1,370 m) above sea level.
For elevations above 4,500 feet (1,370 m) in USA,
installations must be in accordance with the current ANSI Z223.1/NFPA 54 and/or local codes having jurisdiction.
In Canada, please consult provincial and/or local
authorities having jurisdiction for installations at
elevations above 4,500 feet (1,370 m).
WARNING: Improper installation, adjustment, alteration, service or maintenance can cause injury or
property damage. Refer to this manual for correct
installation and operational procedures. For assistance or additional information consult a qualied
installer, service agency, or the gas supplier.
8
High Elevations
Horizontal Termination -
Direct Vent ONLY
The vent must rise vertically a minimum of 24” (610 mm)
off the top of the unit, before the rst elbow. The horizontal
run may extend up to 20’ (6 m) and include a vertical rise
of up to 40’ (12 m). (Fig. 7) Horizontal termination must
also meet the criteria shown in Figures 9 through 11.
• Approved vent systems must terminate above and including the heavy line in Figure 7.
• Two 45° elbows may be substituted for each single 90°
elbow.
• With a rise between 2’ - 5’, one 90° or two 45° elbows
may be used.
A vertical vent system must terminate no less than 8'
(2.44 m) and no more than 40' (12 m) above the appli-
ance ue collar. A 21⁄4" restrictor plate (supplied) must be
used where specied in all vertically terminated vent sys-
tems. (Fig. 8) NOTE: The restrictor plate supplied with
the vertical termination should be discarded. Install
restrictor plate supplied with stove directly at stove
outlet. A vertically terminated vent system must also conform to the following criteria:
• No more than three 90° elbows may be used.
• Two 45° elbows may be substituted for one 90° elbow.
No more than six elbows may be used.
• Vent must rise a minimum of 2 feet before offset is
used.
• Termination height must conform to roof clearance as
specied in Figure 9.
40
39
All Vertical Termi-
38
37
nations in this area
36
Require use of the
35
1
2
⁄4" Restrictor Plate*
34
33
32
31
30
29
28
27
26
Vertical terminations
25
must be within this area
24
23
22
21
20
19
18
16
(Measure from the appliance flue collar to the top of the vent pipe.)
15
14
13
12
11
No Restrictor Plate
10
9
8
7
6
5
4
3
2
1
0
1 2345678910111213141516171819
Horizontal Run (in feet)
Unacceptable Venting
Conguration
Fig. 8 Vertical vent termination window.
*The Restrictor Plate is used on Direct Vent Installations
Only
20306762
ST132a
Vent Termination Clearances
When planning the installation, consider the location of
the vent terminal and clearances. Some of the most common clearances to keep in mind are shown in Figure 10.
Important: All vent clearances must be maintained.
Check your vent termination clearances against Figures 9 through 11.
The vent should be placed so that people cannot be
burned by accidentally touching the vent surfaces when
the stove is operating.
The vent termination should be located where it cannot be
damaged by such things as automobile doors, lawn mowers or snowblowers and it should be located away from
areas where it could become blocked by snow, etc.
Some considerations are:
• Obstructions or impediments to venting.
• Nearby combustible materials that could come into
contact with combustion exhaust gases.
• Other nearby openings {within 12” (305 mm)} through
which exhaust gas could reenter the building.
• All vegetation within 3’ (76 mm) that may interfere with
the draft.
Other factors that inuence where the installation will be
sited include the location of outside walls, where additional heat may be desired in the home, where the family
members gather most regularly, and perhaps most importantly, the distance limitations of the venting system.
IMPORTANT
Direct Vent Only
• The horizontal termination must not be recessed
into the exterior wall or siding.
• Horizontal vent runs must be level toward the vent
termination.
• Clearances around the vent termination must be
maintained.
• For installations using Simpson DuraVent pipe, parallel installations with minimum wall clearance have
restricted access for connecting the Horizontal Vent
Cap straps to the vent pipe. See the maker’s instructions for recommended installation procedures.
9
Page 10
Oxford Direct Vent / Natural Vent Gas Heater
Venting Termination Clearances
Your stove is approved to be vented either through the
side wall, or vertical through the roof.
• This unit does not require any opening for inspec-
tion of vent pipe.
• Only Vermont Castings Group and Duravent vent-
ing components specically approved and labelled
for this stove may be used.
• Minimum clearances between vent pipes and com-
bustible materials is one (1”) inch (25 mm), except
where stated otherwise.
• Venting terminals shall not be recessed into a wall or
siding.
• Horizontal venting must be installed on a level plane
without an inclining or declining slope.
There must not be any obstruction such as bushes, garden sheds, fences, decks or utility buildings within 24”
from the front of the termination hood.
Do not locate termination hood where excessive snow or
ice build up may occur. Be sure to check vent termination area after snow falls, and clear to prevent accidental
blockage of venting system. When using snow blowers,
make sure snow is not directed towards vent termination
area.
Location of Vent Termination
It is imperative the vent termination be located observing
the minimum clearances as shown on this page.
10
20306762
Page 11
Oxford Direct Vent / Natural Vent Gas Heater
V
V
V
V
V
V
V
X
X
X
D
E
B
B
B
C
B
M
B
A
J
K
F
L
VENT TERMINATION AIR SUPPLY INLET
AREA WHERE TERMINAL IS NOT PERMITTED
H
I
Fixed
Closed
Operable
Operable
Fixed
Closed
V
B
INSIDE
CORNER DETAIL
V
A
G
N
N
CFM145a
General Venting Information - Termination Location
Canadian Installations1 US Installations
A = Clearance above grade, veranda, porch, 12” (30cm) 12” (30cm) deck, or balcony
B = Clearance to window or door that may be 6” (15cm) for appliances 6” (15cm) for appliances opened < 10,000Btuh (3kW), 12” (30cm) < 10,000 Btuh (3kW), 9” for appliances > 10,000 Btuh (3kW) and (23cm) for appliances > 10,000
< 100,000 Btuh (30kW), 36” (91cm) Btuh (3kW) and < 50,000 Btuh
for appliances > 100,000 Btuh (30kW) (15kW), 12” (30cm) for appliances > 50,000 Btuh (15kW)
C = Clearance to permanently closed window 12” (305mm) recommended to 12” (305mm) recommended to
prevent window condensation prevent window condensation
D = Vertical clearance to ventilated soft located
above the terminal within a horizontal 18” (458mm) 18” (458mm) distance of 2 feet (610mm) from the center line of the terminal
E = Clearance to unventilated soft 12” (305mm) 12” (305mm)
F = Clearance to outside corner see next page see next page
G = Clearance to inside corner (see next page) see next page see next page
H = Clearance to each inside of center line 3’ (91cm) within a height of 15’ (5m) 3’ (91cm) within a height of 15’
extended above meter/regulator assembly above the meter/regulator assembly (5m) above the meter/regulator
assy
I = Clearance to service regulator vent outlet 3’ (91cm) 3’ (91cm)
J = Clearance to nonmechanical air supply inlet 6” (15cm) for appliances < 10,000 6” (15cm) for appliances to building or the combustion air inlet to any Btuh (3kW), 12” (30cm) for < 10,000 Btuh (3kW), 9” other appliances appliances > 10,000 Btuh (3kW) and (23cm) for appliances > 10,000
< 100,000 Btuh (30kW), 36” (91cm) Btuh (3kW) and < 50,000 Btuh
for appliances > 100,000 Btuh (30kW) (15kW), 12” (30cm) for appliances > 50,000 Btuh (15kW)
K = Clearance to a mechanical air supply inlet 6’ (1.83m) 3’ (91cm) above if within 10’
(3m) horizontally
L = Clearance above paved sidewalk or paved 7’ (2.13m)† 7’ (2.13m)† driveway located on public property
M = Clearance under veranda, porch, deck or 12” (30cm)* 12” (30cm)* balcony
N = Clearance above a roof shall extend a minimum of 24” (610mm) above the highest point when it passes through the roof
surface, and any other obstruction within a horizontal distance of 18” (450mm).
1 In accordance with the current CSA-B149 Installation Codes
2 In accordance with the current ANSI Z223.1/NFPA 54 National Fuel Gas Codes
† A vent shall not terminate directly above a sidewalk or paved driveway which is located between two single family dwellings and serves both dwellings
* only permitted if veranda, porch, deck or balcony is fully open on a minimum 2 sides beneath the oor:
NOTE: 1. Local codes or regulations may require different clearances.
2. The special venting system used on Direct Vent appliances are certied as part of the appliance, with clearances tested and
approved by the listing agency.
3.Vermont Castings Group assumes no responsibility for the improper performance of the appliance when the venting system does
not meet these requirements.
Fig. 9 Vent termination clearances.
20306762
2
11
Page 12
Oxford Direct Vent / Natural Vent Gas Heater
Termination Clearances
Termination clearances for buildings with combustible and noncombustible exteriors.
Inside Corner
G
V
G =
Combustible
6" (152 mm)
Noncombustible
2" (51 mm)
Outside Corner
V
F
F =
Combustible
6" (152 mm)
Noncombustible
2" (51 mm)
Alcove Applications*
D
C
V
O
C
E
Balcony with no side wall
Balcony with perpendicular side wall
M
V
M =
Combustible &
Noncombustible
12" (305 mm)
*NOTE: Termination in an alcove space (spaces open only on one side and with an overhang) is permitted with the dimensions
specied for vinyl or non-vinyl siding and softs. 1. There must be a 3’ (914 mm) minimum between termination caps. 2. All
mechanical air intakes within 10’ (1 m) of a termination cap must be a minimum of 3’ (914 mm) below the termination cap. 3. All
gravity air intakes within 3’ (914 mm) of a termination cap must be a minimum of 1’ (305 mm) below the termination cap.
non-vinyl sidewalls
Min. 12” (305 mm) for
vinyl sidewalls
O = 8’ (2.4 m) Min.
M
V
P
No.
of Caps D
1 3’ (914 mm) 2 x D
2 6’ (1.8 m) 1 x D
3 9’ (2.7 m) 2/3 x D
4 12’ (3.7 m) 1/2 x D
D
= # of Termination caps x 3
Min.
C
= (2 / # termination caps) x D
Max.
C
Min.
Max.
Actual
Actual
Actual
Actual
Actual
584-15
Venting Runs
NOTE: When venting staight vertical, without any
elbow, a minimum of 8 ft. vertical is required
off the top of the stove.
= Acceptable venting configuration
= Unacceptable venting configuration
A: Vertical installations up to 36 feet (12m) in
height. Up to an 18 ft. horizontal vent run can be
installed within the vent system using a
maximum of two 90-degree elbows or four
45-degree elbows.
B: Vertical installations up to 36 feet (12m) in
height. Up to a 24 ft. horizontal vent run can be
installed within the vent system using a
maximum of two 45-degree elbows.
(Ratio = 2/3, Hor./Vert.)
FP567b
NOTE: When using the FSDHAG, the restrictor
plate supplied with the stove is not used.
12
20306762
Page 13
Oxford Direct Vent / Natural Vent Gas Heater
Venting Requirements and Options -
Direct Vent ONLY
Approved Vent System Components
The heater must be vented to the outdoors through an adjacent
exterior wall or through the roof. The venting system must be
comprised of the appropriate listed venting components specied on this page. These parts are available from DuraVent Corporation or your Vermont Castings Group Dealer.
Refer to Figure 4 for dimensions relevant to the standard minimum-vent kits.
*Included in Minimum Horizontal Vent Kit #2792
All DuraVent Straight vent pipe sections have a net length 11⁄2" (37mm)
less than the nominal dimension; i.e., a 6" (152mm) Straight pipe sec-
tion has an effective length of 41⁄2" (115mm).
Vermont Castings Group Vent Components
The following kits are available to meet the needs of most installations. All pipe has a 7" outer diameter and includes a 4"
diameter inner section. A (CG) designation indicates the part is
nished in Charcoal Gray paint. Consult your dealer about other
vent parts that may be appropriate to complete the installation.
NOTE: Direct vent pipe may be used on the Natural Vent system
from the top of the draft hood adapter to the ceiling.
20306762
13
Page 14
Oxford Direct Vent / Natural Vent Gas Heater
Made in USA
Install the Optional Fan
If you are installing the optional convection Fan Kit #2767
(FK26), continue here. If you are not installing a Fan Kit,
go to Page 15, Venting System Assembly.
1. The fan kit includes a Blower Assembly and a Rheostat
Assembly, connected by a cable. (Fig. 12) The Blower
Assembly mounts to the bottom rear of the stove, and
the Rheostat mounts to the valve coverplate. The assembly includes a ‘snapstat’ which automatically turns
the fan On (or Off) above (or below) approximately
109°. The Rheostat also provides a range of fan speed
settings from Off (which overrides the snapstat function) to High. Unpack and inspect the Blower assem-
bly. Conrm that the fan spins freely.
WARNING
This appliance is equipped with a three-prong (grounded) plug for your protection against shock hazard and
should be plugged directly into a properly grounded
three-prong receptacle. Do not cut or remove the
grounding prong from this plug.
• Remove retaining nut from shaft of rheostat. (if pre-
installed)
• Insert the rheostat through the hole in the back of
the left side of the valve bracket, aligning the locator
pin with the smaller hole in that bracket.
• Thread the retaining nut onto the shaft of the rheo-
stat, tightening with a wrench. Do not overtighten.
• Attach the control knob to the rheostat shaft.
• Use the wire tie to secure the fan and rheostat wire
harnesses together.
Rear Skirt
Sheet Metal
Screws
Not Used on RF
Models
Not Used
on
Oxford
Blower
Assembly
ST473
Fig. 12 Fan kit components.
Connect to PC Board on
RF Models Only
Snapstat
Bracket
Snapstat/
Extension
Assembly
Rheostat
Assembly
Not Used
on RF
Models
2. Remove the rear skirt insert panel at the bottom of the
Rear Skirt (Fig. 13) and fasten the blower assembly to
the rebox back with the two Phillips pan-head bolts
originally installed in the rebox back. (‘1’, Fig. 14)
3. Attach the snapstat assembly to the snapstat bracket
with two sheet-metal screws. (‘2’, Fig. 14) Attach the
snapstat bracket to the stove with a hex-head bolt
passing through the bracket and into the stove base.
(‘3’, Fig. 14)
4. The rheostat control switch attaches to the left side of
the valve bracket at the front of the stove.
Rear Skirt Insert
Fig. 13 Remove rear skirt insert.
Star Washer
Sheet Metal Screws
Phillips
Pan Head
Bolts
Star
Washer
Fig. 14 Attach the fan assembly and the snapstat.
Fig. 15 Attach the fan rheostat.
1
Rheostat
Retaining Collar
Rheostat Knob
2
3
ST757
Snapstat
1/4” - 20
Hex Bolt
Snapstat
Bracket
ST314
ST758
14
20306762
Page 15
Oxford Direct Vent / Natural Vent Gas Heater
CEMENT
CEMENT
Venting System Assembly - Direct Vent
General Information
The Oxford is approved for installation only with the vent
components listed on Page 13. Follow the vent component instructions exactly.
For U.S. installations: The venting system must conform
with local codes and/or the current National Fuel Gas
Code, ANSI Z223.1/NFPA 54.
For Canadian installations: The venting system must
conform to the current CSA B149.1 installation code.
Install the Vent Adapter Pipe
(Vermont Castings Group Vent Components)
1. Install the Restrictor Plate. Consult the ‘Vent Run
Specications’ on Page 8 to determine whether the
restrictor plate is needed. If so, put the restrictor plate
in place within the inner ue collar as shown in Figure
16.
5. Install the Outer Adapter Pipe. Apply a 1/4” bead of
cement around the inside wall of the pipe, about 1”
from the end. Insert the pipe over the stove ue collar,
keeping the vertical seam oriented to the back of the
stove. Also, be sure to align holes on the pipe with the
holes on the ue collar of the rebox. Fasten the pipe
to the holes in the ue collar with the #12 x 1/2” sheet
metal screws provided. (Fig. 19)
First Section of
Vent Pipe
#8 x 1/2” Sheet
Metal Screws
4” Inner
Starter Pipe
ST211
Fig. 17 Connect the inner starter with the next section of inner
vent pipe.
ST759
Fig. 16 Install the restrictor plate only if required for the vent-
ing conguration. Refer to Page 9.
2. Attach Inner Starter Pipe, (found in with the logset),
to the next section of inner pipe.
• Run a bead of sealant about 1/2” from the upper
end of the Inner starter pipe and join the two sections
together.
• Drill three pilot holes into the Inner Starter and secure the assembly with three sheet metal screws. (Fig.
17)
3. Dry t the Outer pipe assembly to the stove for the
purpose of determining the center line of the pipe on
the wall.
• Side Wall Terminations: Dry t the outer elbow with the vertical outer vent and conrm the centerline alignment with the wall thimble opening.
Remove the pipes and elbows before continuing with
Step 4.
4. Attach the Inner Vent Assembly to the stove.
• Run a bead of sealant around the bottom end of the
starter pipe and attach the assembly to the stove using
three 1/4-20 x 3/8” Phillips screws provided in the parts
bag. (Fig. 18)
ST760
Fig. 18 Attach inner assembly to ue collar.
ST761
Fig. 19 Fasten outer pipe with #12 x 1/2” sheet metal screw.
20306762
15
Page 16
Oxford Direct Vent / Natural Vent Gas Heater
CEMENT
Install the Vent Adapter Pipe
(Simpson Dura-Vent Components)
1. Install the Restrictor Plate. Consult Page 9 to determine whether the restrictor plate is needed. If so, place
the restrictor plate into the inner ue collar. (Fig. 16)
2. Discard the inner starter pipe shipped with the logset. Using the starter pipe assembly listed on Page 7,
slide the inner section out to allow access.
• Run a bead of sealant around the bottom end of the
starter pipe and attach the assembly to the stove using
three 1/4-20 x 3/8” Phillips screws provided in the parts
bag. (Fig. 20)
3. Install the Outer Adapter Pipe. Apply a 1/4” bead of
cement around the outside surface, about one inch
from the crimped end. (Fig. 21) Orient the vertical
seam to the rear, and insert the crimped end of the
outer pipe into the ue collar. Fasten with three sheet
metal screws provided.
1/4-20 x 3/8
Phillips Screws
Inner Adapter
Pipe
Side Wall Termination Assembly
1. Locate the vent opening on the wall. Refer to Figure 5,
Page 7, to determine the opening centerline. It may be
necessary to rst position the stove and measure to
nd the hole location. Depending on whether the wall
is made of combustible materials, cut the opening to
the size shown in Figure 22. Combustible wall openings must be framed as shown in Figure 22.
2. Measure the wall thickness and cut the wall sleeve
sections to proper length (MAXIMUM 12"). Assemble
the sleeve with the #8 sheet metal screws supplied. At-
tach the restop plate to the sleeve end with the holes.
(Fig. 23) NOTE: The wall sleeve is required in combustible walls only.
3. Install the Wall Firestop/Sleeve assembly into the wall
cutout and fasten the restop to the wall cutout framing
members. (Fig. 23)
12"
(305 mm)
Max. Length
Sleeve
16
Firestop
Fig. 23 Assemble the wall sleeve and restop.
ZCS103
20306762
Page 17
For DuraVent pipe only: Install vent pipe by aligning the
locking system together, sliding the pipes together and
twisting clockwise.
• Install 90° elbow. Twist lock as before.
• Slide the wall plate over horizontal run before attaching the horizontal run to the elbow. Fasten wall plate to
wall.
4. For Vermont Castings Group Vent Pipe only: If necessary, measure to determine the vertical length (X) of
pipe required from the adapter pipe to the wall cutout
centerline, including a 2” (51mm) overlap at the joint.
(Fig. 24) use a hacksaw or tin snips to trim the pipe as
needed.
X
Oxford Direct Vent / Natural Vent Gas Heater
X
ST215
Fig. 25 Measure the horizontal length.
Trim Collar
Wall
Sleeve
ST764
Fig. 24 Determine the vertical pipe length.
5. Install rst the inner then the outer straight pipe
section(s), trimmed end down, to the point of the elbow. Drill 3 holes through each joint and fasten with
sheet metal screws.
6. Seal and install the elbow using 3 sheet metal screws
at each joint.
7. Measure, and cut if needed, the appropriate length of
pipe section needed to make the connection through
the wall. Include a 2” overlap; i.e. from the elbow to
the outside wall face, about 2” or the distance required
if installing a second 90° elbow. (Fig. 25)
8. Slip the wall plate and trim collar over the interior end
of the horizontal pipe and install into the wall sleeve.
Seal the joint inside the wall plate if needed to keep
cold air from being drawn into the home.
9. Seal the ends and connect the horizontal pipe to the
elbow. Fasten the wall plate to the pipe with three
sheet metal screws. Slide the trim collar up against
the wall plate to cover the screws. (Fig. 26)
ST216
Fig. 26 Install the horizontal pipe and wall plate parts.
Wall Plate
10. For both Vermont Castings Group and DuraVent
Systems: Install the vent terminal. (Fig. 27) Apply
high temperature sealant one inch from the ends of
the inner and outer collars. Guide the inner and outer
vent termination collars into the adjacent pipes. Double check that the vent pipes overlap the collars by 2”.
Fasten the termination to the wall with the screws provided, and caulk the joint with weatherproof sealant.
11. For Vermont Castings Group only: Install Charcoal
Gray Pipe Rings (#7FSDRG) or Polished Brass Pipe
Rings (#7FSDRP) at pipe joints, if desired.
Seal Both
Terminal Ends
20306762
Caulk Plate Joint with
Weatherproof Sealant
Fig. 27 Install the vent terminal.
ST217
17
Page 18
Oxford Direct Vent / Natural Vent Gas Heater
Vent Termination Below Grade
Install Snorkel Kit #7FSDVSKS when it is not possible to
meet the required vent termination clearances of 12” (305
mm) above grade level. The snorkel kit will allow installation depth of down to 7” (178 mm) below grade level.
The seven inches is measured from the center of the horizontal vent pipe as it penetrates the wall. If the venting
system is installed below grade, a window well must
be installed with adequate and proper drainage. (Fig.
28)
NOTE: Be sure to maintain side wall clearances and vent
run restrictions. Refer to Figures 3, 4, 7, and 8.
1. Establish the vent hole through the wall.
2. Remove soil to a depth of approximately 16” (406 mm)
below the base of the snorkel. Install a window well
(not supplied). Rell the hole with 12” (305 mm) of
coarse gravel and maintain a clearance of at least 4”
(102 mm) below the snorkel. (Fig. 28)
3. Install the vent system as described on Pages 15 -
17.
4. Be sure to make a watertight joint around the vent pipe
joint at the inside and outside wall joints.
5. Apply high temperature sealant around the inner and
outer snorkel collars. Join the pipes and fasten the
snorkel termination to the wall with the screws provided.
6. Level the soil to maintain a 4” clearance below the
snorkel.
Waterproof Seal
Snorkel
Termination
Cap
4” Clearance
Gravel
Drain
Window
Well
Fig. 28 Snorkel kit installation.
If the foundation is recessed, use extension brackets (not
supplied) to fasten the lower portion of the snorkel. Fas-
ten the brackets to the wall rst, and then fasten to the
snorkel with self-tapping #8 x 1/2” sheet metal screws.
Extend the vent pipes out as far as the protruding wall
face. (Fig. 29)
Around Pipe
Firestop
ST1124
Recessed Wall
Firestop
Finishing
Sheet Metal
Screws and
Bracket
Wall Screws
and Anchors
Waterproof
Seal Around
Pipe
Fig. 29 Use extension brackets to mount snorkel against
recessed wall.
Collar
7” Pipe
Wall Plate
ST219
Vertical (Through the Roof)
Vent Assembly
Note that all vertically terminated installations must include the restrictor plate included with the stove. Refer to
Figure 8, Page 9.
Make certain the vent system conforms to all other re-
quirements for vertical termination as specied on Page
9.
This installation will require you to rst determine the roof
pitch and use the appropriate vent components. Refer to
Figures 8 and 9 on Pages 9 and 11.
1. Locate the nal position of the stove, observing all
clearances for both the vent and the stove.
2. Plumb to the center of the inner (4”) ue collar from the
ceiling above, and mark that location.
3. Cut the opening:
Vermont Castings Group System:
93⁄8" x 93⁄8" (240 x 240 mm)
4. Plumb any additional opening through the roof or oth-
5. Place the stove in its nal position.
6. Install restop(s) #7DVFS and Attic Insulation Shield
7. Install the appropriate roof support and ashing, mak-
DuraVent System: 10" x 10" (254 x 254 mm)
er construction that may be needed. In all cases, the
opening must provide a minimum of 1" (25 mm) clearance to the vent pipe.
#7DVAIS as needed. (Fig. 30) If there is a room above
ceiling level, a restop must be installed on both the
bottom and top sides of the ceiling joists. If an attic is
above ceiling level, an attic insulation shield must be
installed.
ing certain that the upper ange of the ashing base is
below the shingles. (Fig. 31)
18
20306762
Page 19
Oxford Direct Vent / Natural Vent Gas Heater
8. Install appropriate pipe sections until the vent run
reaches above the ashing. The enlarged ends of the
vent sections always face downward.
9. Install the storm collar and seal around the joints. (Fig.
31)
10. Add additional vent lengths to achieve the proper
overall height.
11. Apply cement to the inner and outer termination collars and install the terminal cap.
#7DVAIS
Attic
Insulation
Shield
#7DVFS
Use Four 8d
Nails
Firestop
In Upper
Floor
Venting System Assembly - Natural Vent
General Information
The heater is shipped from the factory as a Direct Vent
Heater. It may be converted to a Natural Vent heater by
installing the Model FSDHAG Draft Hood Adapter.
The heater is approved for installation as a Natural Vent.
Vermont Castings Group Direct Vent pipe could be used
directly after the Draft Hood Adapter up to the ceiling,
then B-vent pipe must be used. Do not mix types of Bvent pipe; use components from one maker or the other.
Follow the vent component maker’s instructions exactly.
The heater will also accept standard or enamelled 7” (150
mm) diameter pipe, around the Type B venting, for decorative purposes only. (Fig. 32)
NOTE: The restrictor plate supplied with the stove is
not used for Natural Vent applications.
Decorative 7”
Pipe
4” B-vent
Pipe
Draft Hood
Adapter
Vermont Castings
Group Direct Vent
System may be
used Draft Hood up
up to the ceiling
ST222
Fig. 30 Install restops and attic insulation shield.
Storm Collar
Flashing
#7DVSKV
(A, B of F)
Roof Support
Fig. 31 Roof support and ashing.
#7DVFS
Firestop in
Ceiling
Sealant
Upper
edge of
ange goes
under upper
shingles
ST221
ST766
Fig. 32 Decorative 7” pipe may be tted around the B-vent
pipe.
The stove, when installed as a Natural vent heater, includes a vent safety switch. (Fig. 63, Page 32) Operating
the stove when it is not connected to a properly installed
and maintained venting system, or tampering with or disconnecting the vent safety switch, can result in carbon
monoxide (CO) poisoning and possible death.
For U.S. installations: The venting system must conform
with local codes and/or the current National Fuel Gas
Code, ANSI Z22.1.
For Canadian installations: The venting system must
conform to the current CSA B149.1 installation code.
Install the Vent Pipe
Apply a bead of sealant around bottom end of inner starter pipe (found in bag with logset) and attach to stove. Apply a bead of sealant around top of inner starter pipe and
install the FSDHAG Draft Hood according to Draft Hood
instructions. (Fig. 33)
20306762
19
Page 20
Oxford Direct Vent / Natural Vent Gas Heater
CEMENT
Attach the rst section of venting to the draft hood. Depending on the length of the individual venting sections
and the lengths of the decorative pipe (if installed), you
may need to slip the decorative pipe over the venting sections before attaching upper sections to lower ones. The
sections of decorative pipe should be oriented with their
seams (if any) toward the wall; sections usually do not
need to be fastened at each joint, other than slip sections.
If the layout includes a slip section, this should be the last
section of pipe visible in the room, at the ceiling. Complete
the venting according to the vent maker’s instructions.
ST767
Fig. 33 Install draft hood adapter.
Install the Log Set
1. Remove the logs from their packaging, and inspect
each piece for damage. DO NOT INSTALL DAM-
AGED LOGS.
2. Install the rear log centering it side to side on the sheet
metal shelf at the back of the rebox. (Fig. 34) The log
will touch both sides and the back wall of the rebox.
3. Install the right log by engaging hole on bottom with
pin on the rear log. (Fig. 34) Then set right bottom side
on the burner so the edge of the log touches the right
side of the rebox. The right log does not use the locator pins on the burner to stay in place.
4. Install the left log by engaging hole on bottom with pin
on rear log. (Fig. 34) Then set left bottom side on the
burner so the edge of the log touches the left side of
the rebox.
5. Loosely sprinkle the lava rocks directly on top of the
burner in front of and between the decorative grate
and the right and left logs. Use the lava rock to cover
brackets on the burner. (Fig. 35)
20
Left Log
Rear Log
Fig. 34 Install the back, left and right logs.
Decorative Grate
Right Log
LG141
Connect the Gas Supply Line
Check the Rating Plate attached by a steel cable to the
rebox, to conrm that you have the appropriate rebox
for the type of fuel to be used. The Oxford may be converted from one gas to another using the appropriate Fuel
Conversion Kit listed on Page 34.
CAUTION
This appliance should only be connected by a qualied gas technician. Test to
conrm manifold pressures as specied
below.
The heater and its individual shutoff valve must be
disconnected from the gas supply piping during
any pressure testing of that system at test pres-
sures in excess of 1/2 psig (3.5 kPa).
The heater must be isolated from the gas supply
piping system by closing its individual manual
shutoff valve during any pressure testing of the
gas supply piping system at test pressure equal to
or less than 1/2 psig.
There must be a gas shutoff between the stove and
the supply.
In order to connect Natural Gas, use a tting with
3/8” NPT nipple on the valve side and 1/2” natural
gas supply line with an input of 28,000 BTUs at a
manifold pressure of 3.5” and minimum inlet supply for adjustment of 5.5” w.c.
In order to connect Propane, use a tting with 3/8”
NPT nipple on the valve side and 1/2” propane gas
supply line with an input of 28,000 BTUs at a manifold pressure of 10.0” and minimum inlet supply
for adjustment of 11.0” w.c.
20306762
Page 21
Oxford Direct Vent / Natural Vent Gas Heater
In the U.S.; Gas connection should be made in accordance with current National Fuel Gas Code, ANSI Z223.1/
NFPA 54. Since some municipalities have additional local
codes, be sure to consult your local authority.
In Canada; consult the local authority and CSA-B149.1
installation code.
Always check for gas leaks with a mild soap
and water solution. Do not use an open ame
for leak testing.
Light the pilot according to the directions on Page 25, before going to the next step.
Burner Information
The appliance must only use the gas specied on the rating plate, unless converted using a Fuel Conversion Kit.
To convert from LP to Natural Gas use Kit #30005155. To
convert from Natural Gas to LP use Kit #30005154.
Conversion instructions are provided with each kit and
beginning on Page 27 in this manual.
This appliance should be connected to the gas
supply only by a qualied gas service technician.
Follow all local codes.
There must be a gas shut-off between the stove
and the supply.
In order to connect Natural Gas, use a tting with 3/8”
NPT nipple on the valve side and 1/2” natural gas supply
line with an input of 28,000 BTUs at a manifold pressure
of 3.5” and minimum inlet supply for adjustment of 5.5”
w.c.
In order to connect Propane, use a tting with 3/8” NPT
nipple on the valve side and 1/2” propane gas supply line
with an input of 28,000 BTUs at a manifold pressure of
10.0” and minimum inlet supply for adjustment of 11.0”
w.c.
Air Shutter Adjustment
The Oxford is shipped from the factory with the air shutter adjusted to the minimum allowed opening. Refer to
Table 1. Based on the altitude where the stove is located,
a shutter adjustment is acceptable to provide a mixed bal-
ance of ame color/glow. To adjust the shutter opening,
follow the steps below.
NOTE: The air shutter may only be adjusted to a more
open position. The factory setting is the minimum allowable air shutter opening. (Figs. 38 & 39)
To adjust the air shutter, the following procedures should
be followed:
1. Remove barrier screen rst by pulling out and up. Remove stove front. Lift stove front up and then swing
bottom out and away to disengage from the stove
body. (Fig. 36)
2. Swing open the swiveling latches at the top left and
right corners of the glass frame. (Fig. 59, Page 31)
Fig. 36 Remove stove front.
3. Pull the top edge of the glass and frame assembly
away from the rebox, and lift it off its supports on the
bottom of the rebox face. Place the assembly out of
the way on a at, padded surface such as a counter
protected by a towel.
4. Take the logset out of the rebox if previously installed.
5. Remove the rear log bracket by unfastening the screw.
(Fig. 37)
6. Remove the right and left log bracket assembly by
unfastening the two screws which hold the burner in
place. (Fig. 37)
7. Hold the burner at the right hand side and lift to clear
the right burner leg. Then pull to the right to clear the
injectors on the left hand side.
8. The air shutter is located on the bottom of the burner
to the left. (Fig. 37) Unfasten the two nuts holding the
Remove Screws
Rear Log Bracket
Pilot
Table 1. Air Shutter Adjustment
Minimum rear injector inlet openings.
Model Natural Gas LPDirect Vent 1/2” 1/2”
Natural Vent 1/2” 1”
20306762
Left & Right Log
Bracket Assembly
Fig. 37 Remove rear log bracket and left and right log bracket
assembly.
21
Page 22
Oxford Direct Vent / Natural Vent Gas Heater
90¡
PILOT
ADJ
TP
TH
TPTH
shutter in place. The shutter may be adjusted between
the factory adjusted 1/2” to fully open. Reassemble the
shutter to allow the rear injector air inlet to close from
the minimum 1/2” opening to fully open. (Fig. 39) You
may have to try more than once to nd the correct air
shutter opening for best results depending on your altitude.
9. Refasten the two nuts and assemble the burner into
the unit by sliding the burner in at an angle with the
Air Shutter
See Table 1
Fig. 38 Air shutter in original from-the-factory position.
Front Injector
Air Inlet
(Original Position)
Burner
ST352
Air Shutter
(May be adjusted up to fully open)
Burner
Left Burner Leg
Injector Shoulder
ST353
Fig. 40 Be sure to maintain 90° angle at left burner leg.
Complete the Assembly
• Open the swiveling latches (cams) on the top left and
right corners of the glass frame.
• Position the glass and frame against the rebox by
placing the bottom edge on the brackets on the bottom
face of the rebox.
• Swing the assembly against the rebox, and close the
latches rmly against the pins protruding from the re-
box top.
Rear Injector Air Inlet
ST351
Fig. 39 Air shutter adjusted.
left side lower than the right side. Slide the left side
onto the injectors. Lower the right hand side down into
place. Make sure the burner is as far left as possible
and the injector shoulders are inside the burner. NOTE:
It is very critical to keep the left burner leg, which holds
the injectors, at a 90° angle to the base. (Fig. 40) This
keeps the orices aligned with tubes on the inside of
the burner. Failure to do so could affect the ame ap-
pearance and performance of the unit.
10.Refasten the right and left log bracket assembly.
11.Refasten the rear log bracket.
12.Replace logs.
13.Replace glass and stove front.
Follow lighting instructions on Page 25. Check ame color
appearance. NOTE: Allow stove to burn for at least 1/2
hour to establish full ame color.
Should color need further adjustment, repeat steps 1
- 12 for air shutter adjustment.
Install ON/OFF Switch
The switch assembly parts are found in the parts bag.
1. Attach switch assembly to left rear side of stove shroud
(when facing shroud) using two screws and existing
holes in shroud. (Fig. 41)
2. Run wires down back of stove, under bottom of rear
shroud to valve.
3. Attach wires to valve terminals. (Fig. 42)
Switch Assembly
Screws
Fig. 41 Attach switch assembly to rear shroud.
Fig. 42 Attach switch wires to valve.
Existing Holes
ST315
ST228
22
20306762
Page 23
Thermostat Connection (optional)
Use only a thermostat rated for 500 millivolts.
Check the table below for the appropriate gauge thermostat wire to use for the length of lead required in your installation.
Thermostat
Wire / Gauge Maximum Run
18 20 feet
16 20 - 40 feet
14 up to 60 feet
1. Install the wall thermostat in the desired location and
run the wires to the stove location. Terminate these
leads with 1/4” female connectors.
2. Connect the thermostat wires to the valve. (Fig. 42)
Install the Stove Front
Insert the handle stub into the hole in the front casting.
Fasten in place witht he 3/8” locking nut provided. (Fig.
43)
The front attaches to the stove by four steel tabs that engage with corresponding cast ribs onto the sides and bottom of the stove body. Position the front about 3” down
from stove top and lift the plate to engage the upper tabs
behind the adjacent ribs on the sides. (Fig. 44) Then lower
the front into position, so the lower tabs engage with the
corresponding ribs at the bottom.
When properly installed, the bottom of the stove front cannot be pulled away from the sides without also lifting it.
Oxford Direct Vent / Natural Vent Gas Heater
3/8” Locking
Nut
ST773
Fig. 43 Insert handle stub into hole in front. Secure with 3/8”
locking nut.
Engage steel tabs behind
the cast iron bosses
Handle Stub
ST1126
Fig. 44 Install the front plate.
Bottom tabs engage
notch in the leg
20306762
23
Page 24
Oxford Direct Vent / Natural Vent Gas Heater
CERTIFIED
SAFETYBARRIER
DANGER
HOT GLASS WILL
CAUSE BURNS.
Safety Barrier Installation Instructions
NOTE: A barrier designed to reduce the risk of burns
from the hot viewing glass is provided with this
appliance and shall be installed for the protection of
children and other at risk individuals. If the barrier
becomes damaged, the barrier shall be replaced with
the manufacturer's barrier for this appliance.* Any
safety screen, guard, or barrier removed for servicing
the appliance must be replaced prior to operating the
appliance.
* See parts list for model number.
The safety barrier has been designed to work with the
doors open or closed.
1. Remove screen from packaging.
2. Place the two bottom hooks over the bottom edge of
the stove opening. Figure 45
3. Press the screen against the stove snapping the two
spring ngers under the lattice until the screen ts
securely in place.
NOTICE: It is the responsibility of the installer to ensure
the barrier is afxed to the stove at the time of installation.
DO NOT TOUCH GLASS
UNTIL COOLED.
NEVER ALLOW CHILDREN
TO TOUCH GLASS.
A barrier designed to reduce the risk of burns from the hot
viewing glass is provided with this appliance and shall
be installed for the protection of children and
other at risk individuals.
20306543
WARNING: The safety screen barrier
must be installed after the glass front is
in place. It is NOT a replacement for the
glass and the unit must NOT be operated without the glass in place.
Figure 45Safety Barrier Installation
24
Spring ngers
Hooks
20306762
Page 25
Operation
LO
HI
Turn
counterclockwise
to decrease
flame height
Turn clockwise
to increase
flame height
Oxford Direct Vent / Natural Vent Gas Heater
Your First Fire
Read these instructions carefully and familiarize yourself
with the burner controls. Locate the pilot assembly, Figure
46. Follow the lighting instructions on Page 25 exactly.
During the rst re, it is not unusual to smell some odor
associated with new logs, paint and metal being heated.
Odors should dissipate within an hour or so, however, you
can open a window to provide fresh air to alleviate the
condition.
Pilot and Burner Inspection
Each time you light your heater check that the pilot ame
and burner ame patterns are as shown in Figure 48. If
ame patterns are incorrect, turn the heater off. Contact
your dealer or a qualied gas technician for assistance.
Do not operate the heater until the pilot ame is correct.
Follow regular maintenance procedures as described on
Page 30.
Flame & Temperature Adjustment
For stoves equipped with HI/LO valves, ame adjustment
is accomplished by rotating the HI/LO adjustment knob
located near the center of the gas control valve. (Fig. 47)
Fig. 47 Flame adjustment knob for Honeywell valve.
Flame Characteristics
It is important to periodically perform a visual check of
the pilot and the burner ames. Compare them to Figure
47. If any of the ames appear abnormal, call a service
person.
Pilot Assembly
Fig. 46 Pilot assembly location.
20306762
CO106c
ST769
Red
Glow
LG143
Fig. 48 Correct pilot and burner ame patterns.
25
Page 26
Oxford Direct Vent / Natural Vent Gas Heater
PILOT
ON
OFF
Lighting and Operating Instructions
FOR YOUR SAFETY READ BEFORE LIGHTING
WARNING:If you do not follow these instructions exactly, a re or explosion
may result causing property damage, personal injury or loss of life.
A. This heater has a pilot which must be lit manually. When
lighting the pilot follow these instructions exactly.
B. BEFORE LIGHTING smell all around the heater area
for gas. Be sure to smell next to the oor because
some gas is heavier than air and will settle on the
oor.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any replace
• Do not touch any electric switch
• Do not use any phone in your building
• Immediately call your gas supplier from a
neighbor’s phone.
Lighting Instructions
1. STOP! Read the safety information above.
2. Turn off all electrical power to the replace.
3. Turn the ON/OFF switch to “OFF” position, set the
remote to OFF or set thermostat to lowest level.
4. Open control access panel.
5. Push in gas control knob slightly and turn clockwise
to “OFF”.
O
L
T
I
P
F
F
O
ON
O
F
F
Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the
Fire Department
C. Use only your hand to push in or turn the gas control
knob. Never use tools. If the knob will not push in or
turn by hand, do not try to repair it, call a qualied
service technician. Applying force or any attempted
repair may result in a re or explosion.
D. Do not use this replace if any part has been under
water. Immediately call a qualied service technician
to inspect the heater and to replace any part of the
control system and any gas control which has been
under water.
10. Push the control knob all the way in and hold. Immediately light the pilot by repeatedly depressing the
piezo spark ignitor until a ame appears. Continue
to hold the control knob in for about one (1) minute
after the pilot is lit. Release knob and it will pop back
up. Pilot should remain lit. If it goes out, repeat steps
5 through 8.
SIT NOVA
6. Remove glass door before lighting pilot. (See Glass
Frame Removal section).
7. Wait ve (5) minutes to clear out any gas. Then smell
for gas, including near the oor. If you smell gas,
STOP! Follow “B” in the safety information above. If
you do not smell gas, go to the next step.
8. Visibly locate pilot by the main burner.
9. Turn knob on gas control counterclockwise to
“PILOT”.
1. Turn the ON/OFF switch to Off position or set the
thermostat to lowest setting.
2. Turn off all electric power to the replace if service
is to be performed.
26
• If knob does not pop up when released, stop
and immediately call your service technician or
gas supplier.
• If after several tries, the pilot will not stay lit,
turn the gas control knob to “OFF” and call your
service technician or gas supplier.
11. Replace glass door.
12. Turn gas control knob to “ON” position.
13. Turn the ON/OFF switch to “ON” position or set
thermostat to desired setting.
14. Turn on all electrical power to the replace.
To Turn Off Gas To Heater
3. Open control access panel.
4. Push in gas control knob slightly and turn clockwise
to “OFF”. Do not force.
5. Close control access panel.
20306762
Page 27
Oxford Direct Vent / Natural Vent Gas Heater
Troubleshooting the Gas Control System
SIT NOVA 820 MILLIVOLT VALVE
NOTE: Before trouble shooting the gas control system, be sure external gas shut off is in the “On” position.
Symptom
1. Spark ignitor will not light
2. Pilot will not stay lit after
carefully following lighting
instructions
3. Pilot burning, no gas to
main burner
4. Frequent pilot outage
problem
Possible Causes
A. Defective or misaligned electrode
at pilot
B. Defective ignitor (Push Button)
A. Defective pilot generator (thermo-
couple), remote wall switch
B. Defective automatic valve
A. Wall switch or wires defective
B. Thermopile may not be generat-
ing sufcient millivoltage
C. Plugged burner orice
D. Defective automatic valve opera-
tor
A. Pilot ame may be too low or
blowing (high) causing the pilot
safety to drop out
B. Possible blockage of the vent
terminal
Corrective Action
Using a match, light pilot. If pilot lights, turn off pilot and
push the red button again. If pilot will not light - check
gap at electrode and pilot-should be 1/8” to have a strong
spark.
With the control knob in the pilot position, push the control
knob all the way and hold. Check for spark at electrode
and pilot. If no spark to pilot, and electrode wire is properly
connected, replace the battery in the ignitor module and
try again. Refer to Maintenance Section. If the problem
still exists, replace the ignitor module box.
Check pilot ame. Must impinge on thermocouple/thermopile. NOTE: This pilot burner assembly utilizes both
a thermocouple and a thermopile. The thermocouple
operates the main valve operation (On and Off). Clean
and or adjust pilot for maximum ame impingement on
thermopile and thermocouple.
Turn valve knob to “Pilot”. Maintain ow to pilot; millivolt
meter should read greater than 10mV. If the reading is
okay and the pilot does not stay on, replace the gas valve.
NOTE: An interrupter block (not supplied) must be used
to conduct this test.
Check wall switch and wires for proper connections.
Jumper wire across terminals at wall switch, if burner
comes on, replace defective wall switch.. If okay, jumper
wires across wall switch wires at valve, if burner comes
on, wires are faulty or connections are bad.
1. Be sure wire connections form thermopile at gas valve
terminals are tight and thermopile is fully inserted into
pilot bracket.
2. One of the wall switch wires may be grounded. Remove wall switch wires form valve terminals if pilot
now stays lit, trace wall switch wiring for ground. May
be grounded to replace or gas supply.
3. Check thermopile with millivolt meter. Take reading
at thermopile terminals of gas valve. Should read
250-300 millivolts (minimum 150) while holding valve
knob depressed in pilot position and wall switch “Off”.
Replace faulty thermopile if reading is below specied
minimum.
Check burner orices for debris and remove.
Turn valve knob to “On”, place wall switch to “On” millivolt
meter should read greater than 150mV. If the reading is
okay and the burner does not come on, replace the gas
valve.
Clean and/or adjust pilot ame for maximum ame impingement on thermopile and thermocouple.
Check the vent terminal for blockage (recycling the ue
gases).
20306762
27
Page 28
Oxford Direct Vent / Natural Vent Gas Heater
PILOT
ON
OFF
PILOT
ADJ
L
O
H
I
A
B
C
O
F
F
P
I
L
O
T
O
D
E
F
O
F
F
P
I
L
O
T
O
Fuel Conversion Instructions
WARNING! This conversion kit shall be installed
by a qualied service agency in accordance with
the manufacturer’s instructions and all applicable
codes and requirements of the authority having jurisdiction. If the information in these instructions is
not followed exactly, a re, explosion or production
of carbon monoxide may result causing property
damage, personal injury or loss of life. The qualied service agency is responsible for the proper
installation of this kit. The installation is not proper
and complete until the operation of the converted
appliance is checked as specied in the manufacturer’s instructions supplied with the kit.
CAUTION: The gas supply shall be shut off prior
to disconnecting the electrical power, before proceeding with the conversion.
Main Gas
Gas Supply Inlet
Fig. 49 Attach the gas line to the left side of the valve.
Conversion Precautions
Before proceeding, turn control knob on valve to OFF and
turn gas supply OFF. Turn OFF any electricity that may be
going to the appliance.
Line
Remove Screws
Rear Log Bracket
Pilot
Left & Right Log
Bracket Assembly
Fig. 50 Remove rear log bracket and left and right log bracket
assembly.
8. Remove injector orices from left burner leg using
1/2” wrench. (Fig. 55)
9. Install conversion orices. (Refer to Table 2)
SIT 820 Valve
1. Using TORX T20 bit, remove and discard the three
(3) pressure regulator mounting screws (A), pressure
regulator tower (B) and the spring and diaphragm assembly (C). (Fig. 51)
2. Insure the rubber gasket (D) is properly positioned
and install the new HI/LO pressure regulator assembly to the valve using the new screws (E) supplied
with the kit. Tighten the screws securely. (Ref. torque
= 25 in/lb) (Fig. 52)
3. Install the enclosed conversion label (F) to the valve
body where it can easily be seen. (Fig. 52)
Conversion Procedure
1. Remove stove front. Lift stove front up and then
swing bottom out and away to disengage from the
stove body. (Fig. 59, Page 30)
2. Swing open the swiveling latches at the top left and
right corners of the glass frame. (Fig. 59, Page 31)
3. Pull the top edge of the glass and frame assembly
away from the rebox face. Place the assembly out of
the way on a at, padded surface such as a counter
protected by a towel.
4. Remove the logset from the rebox.
5. Remove the rear log bracket by unfastening the
screw. (Fig. 50)
6. Remove the right and left log bracket assembly by
unfastening the two screws which hold the burner in
place. (Fig. 50)
7. Hold the burner at the right hand side and lift to clear
the right burner leg. Then pull to the right to clear the
injectors on the left hand side.
28
Fig. 51 Remove mounting
screws, pressure regulator
tower and spring and diaphragm
assembly.
Fig. 52 Replace regulator.
20306762
Page 29
Pilot Orice Conversion
90¡
1. Locate pilot. (Fig. 50)
2. Replace pilot orice.
Pilot Type 1
• Remove pilot hood by lifting up. (Fig. 53) Do not remove snap ring to remove pilot hood. NOTE: It is not
necessary to remove the pilot tube for conversion.
• Remove pilot orice with allen wrench. (Fig. 54)
• Install the conversion orice.
• Reinstall pilot hood. Be sure to align hood with index
tab.
Oxford Direct Vent / Natural Vent Gas Heater
Pilot
Index
Marks
Pilot Bracket
CO105
Fig. 55 Remove pilot hood. (Your pilot may have a different
appearance).
Pilot Hood
Pilot
Bracket
CO105a
Fig. 53 Remove pilot hood.
Index Tab
Snap Ring
Fig. 54 Remove pilot orice.
Allen Wrench
CO106a
Pilot type 2
• Loosen pilot hood turning counterclockwise using a
7/16” wrench. (Fig. 55) NOTE: You may use penetrating oil to prevent pilot hood threads from seizing up.
• Remove pilot orice with needlenose pliers. (Fig. 56)
NOTE: Use a wrench to hold pilot tube in place while
removing the orice.
• Install the conversion orice.
• Reinstall pilot hood and tighten until mark on pilot
hood aligns with mark on pilot bracket.
NOTE: Be sure burner leg remains at a 90° angle to re-
box base after conversion.
21. Replace burner. Slide the burner in at an angle with
left side lower than the right side. Slide the left side
onto the injectors, making sure the burner leg remains
at a 90° angle to the base. Lower the right hand side
down in to place. Make sure the burner is as far left
as possible and the injector shoulders are inside the
burner.
Pilot Orice
CO106b
Fig. 56 Remove pilot orice.
NOTE: It is very critical to keep the left burner leg, which
holds the injectors, at a 90° angle to the base. (Fig.
57) This keeps the orices aligned with the tubes inside burner. Failure to do so could affect the ame
appearance and performance of the unit.
22. Place conversion label on valve.
23. Reinstall the right and left log bracket assembly.
24. Reinstall the rear log bracket.
25. Replace logs.
26. Replace glass and stove front.
Conversion is complete.
Left Burner Leg
Injector Shoulder
ST353
Fig. 57 Be sure to maintain 90° angle at left burner leg.
Your gas heater will provide years of service with minimal
upkeep. The following procedures will help ensure that
your stove continues to function properly.
Annual System Inspection
Have the entire heater and venting system inspected an-
nually by a qualied gas technician. Replace any worn or
broken parts.
Logset and Burner /
Cleaning and Inspection
Cleanliness is critical to the proper function of the heater.
The logset and burner must all be kept free of dust and
unobstructed by debris. Inspect these areas before each
use and clean as necessary.
1. Turn the burner OFF and let the heater cool completely
before cleaning.
2. Remove the safety barrier by pulling out, then up.
3. Lift the stove front up and then swing the bottom out to
disengage it from the heater shell. (Fig. 58)
4. Carefully remove the glass and frame assembly and
place it out of the way on a at, padded surface such
as a counter protected by a towel.
CAUTION
TURN THE PILOT OFF BEFORE PAINTING. ALLOW
THE HEATER TO COOL COMPLETELY BEFORE
PAINTING.
6. Use a soft bristled brush to sweep dust or debris from
the Logs, Pilot and Burner. Use care as the logs are
fragile and susceptible to damage. DO NOT USE A
VACUUM TO CLEAN THE LOGS OR BURNER.
7. Replace the glass panel and frame assembly.
8. Replace the Stove Front.
Care of Cast Iron
An occasional dusting with a dry rag will help keep the
painted surfaces looking new. Use high-temperature
stove paints, available through your local dealer, to touchup areas as needed. Clean areas to be painted with a
wire brush and be sure to cover the logs, burner and valve
assembly, glass and frame assembly. Apply the paint
sparingly; two light coats of paint will give better results
than a single heavy coat.
Clean porcelain enamel surfaces with a soft, damp cloth.
Do not use abrasive cleaning agents. If necessary, use
only a cleaning agent formulated especially for use on
porcelain enamel surfaces.
Fig. 58 Remove the stove front.
5. Carefully inspect the Logs for damage. Contact your
local dealer if any damage is evident. DO NOT OPER-
ATE THE HEATER WITH DAMAGED LOGS.
30
Cleaning the Glass
WARNING: Allow the glass cool completely
before attempting to clean.
It will be necessary to clean the glass periodically. During
start-up, condensation, which is normal, forms on the inside of the glass and causes lint, dust and other airborne
particles to cling to the glass surface. Also initial paint
curing may deposit a slight lm on the glass. It is therefore recommended that the glass be cleaned two or three
times with a non-ammonia household cleaner and warm
water (we recommend gas replace glass cleaner). After
that the glass should be cleaned two or three times during
each heating season depending on the circumstances
present.
Clean glass after rst two weeks of operation.
20306762
Page 31
Oxford Direct Vent / Natural Vent Gas Heater
Glass Replacement
Replace glass only with Vermont Castings Group approved parts. Refer to Page 33 for Replacement Parts.
Refer to Figure 59 and previous instructions for removal
of the damaged glass frame.
Fig. 59 Release the latches to release the glass frame.
Gasket Replacement
The heater uses a ‘tadpole’ type gasket to seal between
the glass panel and the frame. In time, this gasket can
become brittle and compressed and should be replaced.
New gasket is available from your dealer.
Shut off the gas supply and allow the stove to cool. Wear
safety goggles and a dust mask.
1. Remove the Front, Glass Frame and Glass Panel.
(Figs. 59 & 60) Remove the old gasket. Use a razor
blade to separate the glass and gasket from the frame,
and to clean the glass of any remaining cement or bits
of gasket. Use a cold chisel if necessary.
2. Determine the correct length of gasket by laying it out
around the edge of the glass. Allow an extra 1 - 2” (2550 mm). Mark the spot to be cut. Use a utility knife.
3. Starting on a long edge, remove about 6” of the pro-
tective paper strip and apply the at adhesive face of
the gasket around the outside-facing edge of the panel. Continue around the panel, applying a bout 6” at a
time and being careful to not stretch the material. Do
not overlap the gasket ends. (Fig. 60)
4. Apply a thin bead of high temperature silicone rubber
sealant along the inside corner of the glass frame, all
around the perimeter. Place the at gasketed side of
the glass panel back into the steel frame. Pinch the
rounded inside-facing gasket material to bulk it up.
5. Replace the glass frame and front panel as previously
described.
Inspect the Vent System Annually
Have the vent system inspected annually by a qualied
technician. Shut off the main gas supply before inspecting the system. Both the inner exhaust pipe and the outer
combustion supply pipe must be checked to conrm that
they are unblocked and in good condition.
Check the Gas Flame Regularly
To ensure that the stove is operating properly, check the
ames periodically to conrms they match Figure 60. The
ames will be blue during the rst 15-20 minutes of opera-
tion, and will gradually turn to yellow after that.
Do not use your stove if the ame pattern differs from that
shown here. Contact your dealer or a qualied technician
for help.
Stove Disassembly
If there is ever a need to remove the rebox assembly
from the stove shell, support the rebox with solid stands
about 6” (150 mm) tall under the left and right outer edges
of the rebox base. Do not set the rebox assembly directly on the oor; this can damage the control valve and/
or the gas lines from the valve to the rebox.
Before removing the rebox from the shell, disconnect
the on/off switch wires from the valve. If the assembly
includes the optional fan, disconnect the fan rheostat. If
the installation includes a wall thermostat, disconnect the
thermostat leads from valve.
Disconnection and reconnection to the gas line should
only be done by a qualied gas service technician.
Upon reinstallation, the vent system must be sealed to
the rebox as shown in the installation section, Page 16.
Also be sure the logs are placed in the rebox correctly,
as shown in Figures 34 & 35, Page 20.
Red
Glow
Fig. 60 Wrap the gasket material around the outside edge of
the glass.
20306762
Fig. 61 Correct ame pattern.
31
Page 32
Oxford Direct Vent / Natural Vent Gas Heater
OFF
ON
Thermopile
Black
Black
Millivolt
Gas Valve
TP/TH
TP
TH
Thermostat
(Optional)
Thermopile
Black
Black
Millivolt
Gas Valve
TP/TH
TP
TH
Thermocouple
Safety Limit
Switch
Valve
Wiring Diagrams
On/Off Switch Wiring
POWER
CORD
FAN
ST124b
Optional Thermostat
Wiring
ST124c
Fig. 62 On/Off switch and optional thermostat circuit.
NOTE: IF ANY OF THE ORIGINAL WIRE, AS SUP-
PLIED WITH THE APPLIANCE, MUST BE REPLACED, IT MUST BE REPLACED WITH TYPE SF-2,
200° WIRE OR ITS EQUIVALENT.
Chassis
Ground
Chassis Ground
WHT
BLK
GRN
BLK
BLK
FAN JUNCTION BOX
Strain Relief
WHT
BLK
BLK
GRN
RHEOSTAT / SNAPSTAT
BLK
ON / OFF
Rheostat
Snapstat
BOX
ST153
Fig. 63 Draft hood adapter wiring.
32
ST665
MOTOR
BLK
WHT
BLK
BLK
GRN
Fig. 64 Fan circuit.
ON/OFF
RHEOST AT
Schematic Diagram
BLK
WHT
SNAPST AT
20306762
ST236
Page 33
Oxford Direct Vent / Natural Vent Gas Heater
Replacement Parts
1
1a
1c
1b
10
12
21
11
22
28
26
2
3
4
5
16
18
13
9
14
19
20
27
17
23
7
6
40
25
24
31
29
33
36a,b
15a,b,
c,d
Vermont Castings Group reserves the right to make changes in design, materials, specications, prices and discontinue colors and products at any
time, without notice.
34
30
8
37
35
32
CEMENT
Ref. Description Oxford
1. Gas Log Assembly - SDV30 20003458
1a. Rear Log 20003459
1b. Right Log 20003460
1c. Left Log 20003461
2. Small Lava Rock Package 57897
3. Top 30001925
4. Front 30001928
5. Door 30001929
6. End, Rt 30001927
7. End, Lt 30001926
8. Leg 30001930
9. Manifold Assembly 20003739
20306762
33
Page 34
Oxford Direct Vent / Natural Vent Gas Heater
Replacement Parts (continued)
Ref. Description Oxford
10. Glass, DV25 1601691
11. Glass Frame Assembly - SDV30 30000127
12. Gasket, Glass - Med. Knit - RDV40 1203702
13. Pilot Top Convertible 10002266
14. Pilot Assembly 3Way N/DV RN 0.199.706 10002264 Pilot Assembly 3Way N/DV RP 0.199.703 10002265
15a. Orice Hood #69 - Front - LP 30000513
15b. Orice Hood #54 - Front - NG 20000130
15c. Orice Hood #54 - Rear - LP 20000130
15d. Orice Hood #44 - Rear - NG 30000334
16. Thermocouple 24” 24D0808
17. Thermopile 18” RS 7533113
18. Electrode Ignitor w/Cable SIT24 10001297
19. Nut Electrode SIT #0.974.144 57886
20. Tubing Pilot w/Fittings 1/8 x 24” 10001296
21. Burner Housing Assembly NG/LP 20002214
22. Grate, Burner - JDV 20002167
23. Ashdoor Handle Assy - E/V/WSI 5004241
24. Handle, Damper - Maple Wood - Blk 1600664
25. Switch ON/OFF - RN/RP Models 30000874
26. Wiring Harness - FSDV32 RN/JDV 10002582
27. Right Log Bracket 20002166
28. Left Log Bracket 20002165
29. Nut, Hex Jam 3/8 -16 TOPLK-Z 1203290
30. Gasket, Base Pan - JDV 20002282
31. Gasket, Base Pan Inner 20002566
32. Gasket Cement, 3 oz tube (not shown) 1206122
33. Gasket, HE Door 1203687
34. Sensor 2450 CMG-8184-0032 10002013
35. Pan Hd, SL 1/4-20 x 3-Z 1201310
36a. Valve Nova SIT820.662 RN (Serial #’s starting with 6414) 20010563
36b. Valve Nova SIT820.653 RP (Serial #’s starting with 6414) 20010645
37. Ignitor Piezo w/Nut SIT 057958
38. Bracket Piezo Ignitor (not shown) 20010876
39. *Magnet, Control Door (not shown) 1408818
40. Safety Barrier 30007256
*Use common super glue or silicone to attach magnets.
Fuel Conversion Kits
Conversion Kit, NG to LP - OXDV30NV Kit #30005154
Conversion Kit, LP to NG - OXDV30PV Kit #30005155
34
20306762
Page 35
Oxford Direct Vent / Natural Vent Gas Heater
Optional Accessories
Fan Kits
FK26 Fan
The FK26 fan helps distribute heated air from within
the rebox out into the room. The fan is controlled by a
snapstat that turns power on and off as the rebox tem-
perature rises above and falls below a preset temperature. A rheostat provides for variable fan speeds.
Specications
115 Volt / 60Hz / .75 Amps
Maintenance
The fan itself does not require regular maintenance, however, periodic cleaning of the fan and the surrounding
area is required.
Installation
Refer to Page 14 for installation instructions.
Remote Controls
The remote control allows you to turn the heater on or off
from anywhere in the room. Refer to Page 32 for wiring
diagrams.
Model Functions ControlledRC1 ON/OFF
RC2 ON/OFF and Temperature
IMTFK Wall mounted thermostat control
Decorative Rings
7” brass or charcoal gray rings are available to add a decorative touch to the exposed stove pipe.
Model Description7FSDRG/4 7” Charcoal Gray Rings (4)
20306762
35
Page 36
Oxford Direct Vent / Natural Vent Gas Heater
36
20306762
Page 37
Oxford Direct Vent / Natural Vent Gas Heater
20306762
37
Page 38
Oxford Direct Vent / Natural Vent Gas Heater
38
20306762
Page 39
Oxford Direct Vent / Natural Vent Gas Heater
LIMITED LIFETIME WARRANTY
PRODUCT COVERED BY THIS WARRANTY
All Vermont Castings Group gas stoves equipped with an Insta-Flame Ceramic Burner.
BASIC WARRANTY
Vermont Castings Group (hereinafter referred to collectively as the
Company) warrants that your new Vermont Castings Group Gas
Fireplace/Stove is free from manufacturing and material defects for a
period of one year from the date of purchase, subject to the following
conditions and limitations.
EXTENDED LIFETIME WARRANTY
The heat exchanger, where applicable, and combustion chamber
of every Vermont Castings Group gas product is warranted for life
against through wall perforation. All appliances equipped with an
Insta-Flame Ceramic Burner have limited lifetime coverage on the
ceramic burner plaque. Warrantees are made to the original owner
subject to proof of purchase and the conditions and limitations listed
on this Warranty Document
COMPONENT WARRANTY
CAST IRON: All external and internal cast iron parts are warranted for a
period of three years.
Note: On porcelain enamel nished external parts and accessories
The Company offers no Warranty on chipping of enamel surfaces. Inspect all product prior to accepting it for any damage to the enamel.
The salt air environment of coastal areas or a high humidity environment can be corrosive to the porcelain enamel nish. These conditions can cause rusting of the cast iron beneath the porcelain enamel
nish, which will cause the nish to ake off.
Dye lot variations with replacement parts and/or accessories can occur and are not covered by warranty.
GLASS DOORS: Glass doors are covered for a period of one year.
Glass doors are not warranted for breakage due to misuse or accident.
Glass doors are not covered for discoloration or burned in stains due to
environmental issues, or improper cleaning and maintenance.
BRASS PLATED PARTS AND ACCESSORIES: Brass parts should be
cleaned with Lemon oil only. Brass cleaners cannot be used. Mortar
mix and masonry cleaners may corrode the brass nish. The Company
will not be responsible for, nor will it warrant any brass parts which are
damaged by external chemicals or down draft conditions.
GAS VALVES: Gas valves are covered for a period of one year
ELECTRONIC AND MECHANICAL COMPONENTS: Electronic and
mechanical components of the burner assembly are covered for one
year. All steel tube burners are warranted for one year.
ACCESSORIES: Unless otherwise noted all components and Vermont
Castings Group company supplied accessories are covered for a period
of one year.
CONDITIONS AND LIMITATIONS
• This new Vermont Castings Group product must be installed by a
competent, authorized, service contractor. A licensed technician, as
prescribed by the local jurisdiction must perform any installation/service work. It must be installed and operated at all times in accordance with the Installation and Operating instructions furnished with
the product. Any alteration, willful abuse, accident, or misuse of the
product shall nullify this warranty.
• This warranty is non-transferable, and is made to the original owner,
provided that the purchase was made through an authorized supplier
of the Company.
• The customer must pay for any Authorized Dealer in-home travel fees
or service charges for in-home repair work. It is the dealers option
whether the repair work will be done in the customer’s home or in the
dealer’s shop.
• If upon inspection, the damage is found to be the fault of the manu-
facturer, repairs will be authorized at no charge to the customer parts
and/or labor.
• Any part and/or component replaced under the provisions of this warranty is covered for six months or the remainder of the original warranty, whichever is longest.
• This warranty is limited to the repair of or replacement of part(s) found
to be defective in material or workmanship, provided that such part(s)
have been subjected to normal conditions of use and service, after
said defect is conrmed by the Company’s inspection.
• The company may, at its discretion, fully discharge all obligations with
respect to this warranty by refunding the wholesale price of the defective part(s)
• Any installation, labor, construction, transportation, or other related
costs/expenses arising from defective part(s), repair, replacement, or
otherwise of same, will not be covered by this warranty, nor shall the
Company assume responsibility for same. Further, the Company will
not be responsible for any incidental, indirect, or consequential damages except as provided by law.
• SOME STATES DO NOT ALLOW FOR THE EXCLUSION OR LIMI-
TATIONS OF INCIDENTAL AND CONSEQUENTIAL DAMAGES OR
LIMITATIONS ON HOW LONG AN IMPLIED WARRANTY LASTS,
SO THE ABOVE LIMITATIONS MAY NOT APPLY TO YOUR CIRCUMSTANCES. THIS WARRANTY GIVES YOU SPECIFIC RIGHTS
AND YOU MAY HAVE OTHER RIGHTS WHICH VARY FROM STATE
TO STATE.
• All other warranties-expressed or implied- with respect to the product,
its components and accessories, or any obligations/liabilities on the
part of the Company are hereby expressly excluded.
• The Company neither assumes, nor authorizes any third party to assume on its behalf, any other liabilities with respect to the sale of this
Vermont Castings Group product
• The warranties as outlined within this document do not apply to chimney components or other non Vermont Castings Group accessories
used in conjunction with the installation of this product..
• Damage to the unit while in transit is not covered by this warranty but
is subject to claim against the common carrier. Contact the dealer
from whom you purchased your replace/stove (do not operate the
appliance as this might negate the ability to process the claim with the
carrier).
• The Company will not be responsible for:
a) Down drafts or spillage caused by environmental conditions such
as near-by trees, buildings, roof tops, hills, or mountains.
b) Inadequate ventilation or negative air pressure caused by me-
chanical systems such as furnaces, fans, clothes dryers, etc.
• This warranty is void if:
a) The replace has been operated in atmospheres contaminated by
chlorine, uorine, or other damaging chemicals.
b) The replace has been subjected to prolonged periods of damp-
ness or condensation
c) Any damages to the replace, combustion chamber, heat exchang-
er or other components due to water, or weather damage, which is the
result of but not limited to, improper chimney/venting installation.
d) Any alteration, willful abuse, accident, or misuse of the product has
occurred.
IF WARRANTY SERVICE IS NEEDED…
1) Contact your supplier. Make sure you have your warranty, your
sales receipt, and the model/serial number of your Vermont Castings Group product.
2) DO NOT ATTEMPT TO DO ANY SERVICE WORK YOURSELF.
20306762
39
Page 40
EFFICIENCY RATINGS
EnerGuide Ratings Fire-
Model
OXDV30NV63.0
place Efciency (%)
Based on CSA P.4.1-09
149 Cleveland Drive • Paris, Kentucky 40361
www.vermontcastingsgroup.com
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.