Vermont Castings INDVRCBSB, INDVRBSSB, INDVRBMSB, INDVRBDSB Installation And Operating Instructions Manual

Page 1
DANGER
HOT GLASS WILL
CAUSE BURNS.
DO NOT TOUCH GLASS
UNTIL COOLED.
NEVER ALLOW CHILDREN
TO TOUCH GLASS.
A barrier designed to reduce the risk of burns from the hot
viewing glass is provided with this appliance and shall
be installed for the protection of children and
other at risk individuals.
20306543
CERTIFIED
SAFETY BARRIER
Intrepid® Direct Vent Gas Heater Installation and Operating Instructions
Model: INDVRCBSB, INDVRBSSB, INDVRBMSB, INDVRBDSB
WARNING: FIRE OR EXPLOSION HAZARD
Failure to follow safety warnings exactly could result in serious injury, death or property damage.
Do not store or use gasoline or other
ammable vapors and liquids in the vicinity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS
– Do not try to light any appliance. – Do not touch any electrical switch; do
not use any phone in your building. – Leave the building immediately. – Immediately call your gas supplier from
a neighbor's phone. Follow the gas
supplier's instructions. – If you cannot reach your gas supplier,
call the re department.
Installation and service must be performed
by a qualied installer, service agency or the gas supplier.
WARNING: Improper installation, adjustment, alteration, service or maintenance can cause injury or property damage. Refer to this manual. For assistance or additional information consult a qualified installer, service agency or the gas supplier.
This appliance may be installed in an aftermarket, permanently located, manufactured home (USA only) or mobile home, where not prohibited by local codes.
This appliance is for use only with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases, unless a certied kit is used.
INSTALLER: Leave this manual with the appliance.
CONSUMER: Retain this manual for future
reference.
20306761 12/14 Rev. 1
Page 2
Intrepid® Direct Vent - Rear Vent Gas Heater
Table of Contents
Thank you and congratulations on your purchase of a Vermont Castings stove.
PLEASE READ THE INSTALLATION & OPERATING INSTRUCTIONS BEFORE USING APPLIANCE.
IMPORTANT: Read all instructions and warnings carefully before starting installation. Failure to follow these
instructions may result in a possible re hazard and will void the warranty.
INSTALLATION AND OPERATING INSTRUCTIONS
General Information. .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . 3
Requirements for the Commonwealth of Massachusetts......4
Stove Dimensions..........................................5
Installation Requirements ..................................6
Locating the Stove .........................................6
Clearance Requirements ...................................6
Minimum Clearances, Parallel Installation,
Corner Installation. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . 7
Wall and Ceiling Clearances ...............................7
Mantel Clearances. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . 7
Hearth Requirements ......................................7
Gas Specications .........................................8
Air Shutter Setting .........................................8
Gas Inlet and Manifold Pressures ...........................8
High Elevations. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . 8
Horizontal Termination .....................................8
Vertical Termination . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . 9
Restrictor Plate Adjustment for Extended Pipe Runs .. . .. . .. . 9
Vent Termination Clearances ..............................10
Termination Location ......................................11
Termination Clearances .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. 12
MAINTENANCE
Annual System Inspection. .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. 37
Log set and Burner Cleaning ..............................37
Care of Cast Iron .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. 37
Cleaning the Glass .......................................37
Glass Replacement . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. 37
Gasket Replacement......................................38
Inspect the Vent System Annually ..........................38
Check the Gas Flame Regularly ...........................38
Stove Disassembly .......................................38
Wiring Diagrams. .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. 39
REPLACEMENT PARTS . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. 41
OPTIONAL ACCESSORIES . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. 42
WARRANTY .............................................43
EFFICIENCIES ...........................................44
INSTALLATION
Install Optional FK20 Fan Kit ..............................13
Venting System Components. .. . .. . .. . .. . .. . .. . .. . .. . .. . .. 14
Venting System Assembly, General Information,
Options, Planning .................................15
Rear Vent ................................................16
Horizontal Installation .....................................17
Vertical Installation. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. 19
Cathedral Ceiling Installation ..............................21
General Maintenance .....................................22
Supplemental Canadian Instructions .. . .. . .. . .. . .. . .. . .. . .. 22
Vertical Through Existing Chimney .........................22
Converting a Class-A Metal Chimney or Masonry
Chimney to a Direct Vent System....................25
Connect Gas Supply Line .................................27
Burner Information ........................................28
Complete the Assembly .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. 28
Install ON/OFF Switch . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. 28
Install the Front Plate......................................28
Thermostat Connection .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. 28
Install the Log Set.........................................29
Safety Barrier Installation .................................30
OPERATION
Your First Fire .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. 31
Pilot and Burner Inspection ................................31
Flame & Temperature Adjustment ..........................31
Flame Characteristics .....................................31
Extension Knobs. .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. . .. 31
Lighting and Operating Instructions ........................32
Troubleshooting ..........................................33
Fuel Conversion Instructions ..............................34
2
20306761
Page 3
Intrepid® Direct Vent - Rear Vent Gas Heater
Installation & Operating Instructions
The Intrepid Direct Vent room Heater, Model INDVR is a vented gas appliances listed to ANSI Standard Z21.88-2005 and CSA-
2.33-2005 for Vented Room Heaters, and CSA 2.17-M91, Gas­Fired Appliances For Use at High Altitudes.
The installation of the Intrepid Direct Vent Room Heater must conform with local codes, or in the absence of local codes, with National Fuel Gas Code, ANSI Z223.1/NFPA 54 — latest edition and CSA B-149.1 (EXCEPTION: Do not derate this appliance for altitude. Maintain the manifold pressure at 3.5” w.c. for Natural Gas and 10” w.c. for LP gas at maximum input.) Refer to page 8 (RF only).
This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other
gases unless a certied kit is used.
Installation and replacement of gas piping, gas utilization equipment or accessories, and repair and servicing of equip­ment shall be performed only by a qualied agency, preferably NFI or WETT (Canada) certied. The term “qualied agency” means any individual, rm, corporation, or company that either in person or through a representative is engaged in and is responsible for (a) installation or replacement of gas piping, or (b), the connection, installation, repair, or servic­ing of equipment, who is experienced in such work, familiar with all precautions required, and has complied with all the requirements of the authority having jurisdiction.
The Intrepid Direct Vent Room Heater should be inspected before use and at least annually by a qualied service agency. It is imperative that control compartments, burners, and cir­culating air passageways of the appliance be kept clean.
The Intrepid Direct Vent Room Heater and the individual shut-off valve must be disconnected from the gas supply piping during any pressure testing of that system at test pressures in excess of 1/2 psig (3.5 kPa).
The Intrepid Direct Vent Room Heater must be isolated from the gas supply piping system by closing the individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psig.
An accessible tap is located above the pilot/on-off knob for check­ing the inlet pressure.
‘Direct Vent’ describes a sealed combustion system in which in­coming outside air for combustion and outgoing exhaust enter and exit through two separate concentric passages within the same sealed vent system. The system does not use room air to support combustion. The Direct Vent system permits the gas appliance to be vented directly to the outside atmosphere through the side of the house or vertically through the roof.
This appliance is approved for bedroom installations in the U.S. and Canada.
This appliance may be installed in an aftermarket* manufactured (mobile) home, where not prohibited by state or local codes.
WARNING: Operation of this heater when not connected to a properly installed and maintained venting system can result in carbon monoxide (CO) poisoning and possible death.
The Intrepid Direct Vent Room Heater, when installed, must be electrically grounded in accordance with local codes or, in the absence of local codes, with the National Electrical Code ANSI/ NFPA 70, (latest edition), or of the current Canadian Electrical Code C22.1.
Due to high temperatures this appliance should be located out of trafc and away from furniture and draperies.
WARNING: This appliance is hot while in operation. Keep children, clothing, and furniture away. Contact may cause burns or ignition of combustible materials.
Children and adults should be alerted to the hazards of high surface temperatures and should stay away to avoid burns or clothing ignition. Young children should be carefully su­pervised when they are in the same room as the appliance.
Clothing or other ammable materials should not be placed on or near the appliance.
Any safety screen, glass or guard removed for servicing an appliance must be replaced prior to operating the appliance.
The appliance area must be kept clear and free from com­bustible materials, gasoline, and other ammable vapors and liquids.
The ow of combustion and ventilation air must not be ob­structed. The installation must include adequate accessibility and clearance for servicing and proper operation.
WARNING: Do not operate the Room Heater with the glass panel removed, cracked or broken. Replacement of the panel should be done by a licensed or qualied service person.
Do not use this appliance if any part has been under water. Immediately call a qualied service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water.
Do not burn wood, trash or any other material for which this appliance was not designed. This appliance is designed to burn either natural gas or propane only.
This gas appliance must not be connected to a chimney ue serving a separate solid-fuel burning appliance.
CAUTION: Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation.
Verify proper operation after servicing.
* Aftermarket: Completion of sale, nor for purpose of resale, from the manufacturer.
Intrepid
Direct Vent / Rear Vent
Certied to:
ANSI Z21.88-2014 / CSA Z2.33-2014
Vented Gas Fireplace Heaters
Proposition 65 Warning: Fuels used in gas, woodburning or
oil red appliances, and the products of combustion of such
fuels, contain chemicals known to the State of California to cause cancer, birth defects and other reproductive harm.
California Health & Safety Code Sec. 25249.6
20306761
3
Page 4
Intrepid® Direct Vent - Rear Vent Gas Heater
Installation & Operating Instructions
Requirements for the Commonwealth of Massachusetts
All gas tting and installation of this heater shall only be done by a licensed gas tter or licensed plumber.
For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above
nished grade in the area of the venting, including but not
limited to decks and porches, the following requirements
shall be satised:
Installation of Carbon Monoxide Detectors
At the time of installation of the side wall horizontal vented
gas fueled equipment, the installing plumber or gas tter
shall observe that a hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure served by the side wall horizontally vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services
of qualied licensed professionals for the installation of
hard wired carbon monoxide detectors.
In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired carbon monoxide detector with alarm and battery
back-up may be installed on the next adjacent oor level.
In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of thirty (30) days to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery operated carbon monoxide detector with an alarm shall be installed.
Approved Carbon Monoxide Detectors
Each carbon monoxide detector as required in accordance with the above provisions shall comply with NFPA 720 and
ANSI/UL 2034 listed and IAS certied.
Signage
A metal or plastic identication plate shall be permanently
mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The sign shall read, in print size no less than one-half (1/2) inch in size, “GAS VENT DIRECTLY
BELOW, KEEP CLEAR OF ALL OBSTRUCTIONS”.
Inspection
The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5.08(2)(a)1 through 4.
Exemptions
The following equipment is exempt from 248 CMR
5.08(2)(a)1 through 4:
The equipment listed in Chapter 10 entitled “Equipment
Not Required To Be Vented” in the most current edition of NFPA 54 as adopted by the Board; and
Product Approved side wall horizontally vented gas fueled
equipment installed in a room or structure separate from the dwelling, building or structure used in whole or in part for residential purposes.
MANUFACTURER REQUIREMENTS
Gas Equipment Venting System Provided
When the manufacturer of Product Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the instructions provided by the manufacturer for installation of the equipment and the venting system shall include:
Detailed instructions for the installation of the venting
system design or the venting system components; and
A complete parts list for the venting system design or
venting system.
Gas Equipment Venting System NOT Provided
When the manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does not provide
the parts for venting the ue gases, but identies “special
venting systems”, the following requirements shall be
satised by the manufacturer:
The referenced “special venting system” instructions shall
be included with the appliance or equipment installation instructions; and
The “special venting systems” shall be Product
Approved by the Board, and the instructions for that system shall include a parts list and detailed installation instructions.
A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment, all venting instructions, all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of the installation.
4
20306761
Page 5
Intrepid® Direct Vent - Rear Vent Gas Heater
Intrepid Stove Dimensions
21³⁄₈"
(543 mm)
Centerline
of Flue Pipe
18”
(457 mm)
Valve Inlet
C
L
(102 mm)
4”
13¹¹⁄₁₆” (347 mm)
16⁷⁄₁₆
(418 mm)
24¹⁄₄
(616 mm)
21³⁄₁₆” (538 mm)
6¹⁄₂
(165 mm)
C
Valve
Inlet
L
Fig. 1 Intrepid dimensions.
13⁷⁄₈” (352 mm)
21³⁄₄” (553 mm)
20306761
5
Page 6
Intrepid® Direct Vent - Rear Vent Gas Heater
Installation Requirements
The installation must conform with local codes or, in the absence of local codes, with the National Fuel Gas Code, ANSI Z223.1/NFPA 54 - latest edition. (EXCEPTION: Do not derate this appliance for altitude. Maintain the man­ifold pressure at 3.5 inches w.c. for Natural Gas, and 10 inches w.c. for Propane).
In Canada, installation must be in accordance with the current CSA B-149.1 Installation Codes and/or local codes.
The installation should be done by a qualied service person who is familiar with the building codes and installation techniques appropriate for your area to accomplish a safe and effective installation.
Your dealer or your local gas supplier will be able to refer a qualied service person.
WARNING: Due to high temperatures, the HEATER should be located out of trafc and away from furniture and draperies.
The surface of the Heater is hot when it is in use. Young children should be watched carefully when they are in the same room when the Heater is in use, and they should be taught to avoid the hot surface. Keep any objects that can burn well away from the Heater, and observe the recommended clearances that follow.
Locating the Stove
In choosing a location for the stove, consider:
• The location of outside walls;
• Where additional heat is needed:
• Where family members gather most often;
• The vent system requirements.
NOTE: We do not recommend the use of wallpaper next to this stove. Over time, radiant heat may cause the wall­paper to shrink, or may adversely affect the binders in the wallpaper adhesive.
A
B
Fig. 2 Possible stove locations.
C
D
ST942
WARNING:
Always maintain required clearances
(air spaces) to nearby combustibles to prevent re hazard. Do not ll air spaces
with insulation. All venting components must maintain a 1” (25 mm) clearance to combus­tible materials. Maintain a 6” (152 mm) clearance when using single wall pipe. Maintain a 2” (51 mm) clearance on top and 1” (25 mm) on sides and bottom when venting straight off the rear.
• The gas appliance and vent system must be vented directly to the outside of the building and never be attached to a chimney serving a separate solid fuel or gas-burning appliance.
• Refer to the manufacturer’s instructions included with the venting system for complete installation procedures.
Clearance Requirements
Minimum Clearances to Combustible Materials
Measure side clearances as shown in Figures 3, 4 and 5 from the outer edge of the cast iron stove top. Measure rear clearances from the outermost surface of the steel rear skirt.
This heater is approved for installation into an alcove con­structed of combustible materials to the dimensions and clearances shown on the next page.
The same clearances apply in a standard parallel instal­lation.
6
20306761
Page 7
Intrepid® Direct Vent - Rear Vent Gas Heater
C
L
18³⁄₄"
(476 mm)
2¹⁄₂"
(64 mm)
4"
(102 mm)
4"
(102 mm)
Max. Vent
Length
24” (610 mm)
2" (51 mm)
2"
(51 mm)
7¹⁄₂"
(190 mm)
Max. Vent
Length
24" (610 mm)
9"
(230 mm)
Max. Mantel
Width
Refer to
Fig. 6
4"
(102 mm)
Sidewall/
Trim
2¹⁄₂"
(63 mm)
Rear Wall
A
B
3" (75mm) Min.
Parallel Installation: Minimum Clearance
and Flue Centerline
ST947
Fig. 3 Parallel Installation, minimum back and side clearance.
Corner Installation: Minimum Clearance and
Flue Centerline
Mantel Clearances
Combustible Mantel or Trim Materials
Noncombustible Materials
ST382
A (Max.) B (Min.)
9" 10 (230 mm) (270 mm)
71⁄2" 9" (190 mm) (230 mm)
6" 71⁄2" (152 mm) (190 mm)
41⁄2" 6" (114 mm) (152 mm)
3" 41⁄2" (76 mm) (114 mm)
11⁄2" 3" (38 mm) (76 mm)
A = Depth of Mantel and/or Top Trim B = Height from Top of Heater
Fig. 6 Mantel / top trim clearances.
1
2"
ST948
Fig. 4 Corner installation, minimum corner clearance and ue
centerline.
Wall and Ceiling Clearances
Fig. 5 Alcove and ceiling clearances.
20306761
ST949
Hearth Requirements
The Intrepid Heater must be installed on rigid ooring. When
the heater is installed directly on any combustible surface
other than wood ooring, a metal or wood panel extending
the full width and depth of the unit must be used as the hearth. There are no other hearth requirements.
7
Page 8
Intrepid® Direct Vent - Rear Vent Gas Heater
20
19
18
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
Vertical Run (in feet)
Measured after the first elbow. (Transition elbow)
Horizontal Run (in feet)
21
22
23
24
25
26
27
28
29
30
ST134a FDV28 Horizontal vent run 12/3/99 djt areas modified 1/11/00 djt
Gas Specications
Max. Min. Input Input Model Fuel Gas Control BTU/h BTU/h
INDVR Series Nat Millivolt 18,500 12,500 INDVR Series Prop Millivolt 16,000 12,000
Air Shutter Setting
Minimum injector air inlet opening
Model Natural Gas LP INDVR 1/2” Open 1/2” Open
Weight: Fully assembled 350 lbs.
Gas Inlet and Manifold Pressures
Natural LP (Propane)
Inlet Minimum 5.5” w.c. 11.0” w.c.
Inlet Maximum 14.0” w.c. 14.0” w.c.
Manifold Pressure 3.5” w.c. 10” w.c.
The installation must conform with local codes or, in the absence of local codes, with the National Fuel Gas Code, ANSI Z223.1/NFPA 54 - latest edition. (EXCEPTION: Do not derate this appliance for altitude. Maintain the manifold pressure at 3.5” w.c. for Natural Gas and 10” w.c. for Propane.)
Horizontal Termination
Except for straight-through the wall vent installations.
The vent must rise vertically a minimum of 24” (610 mm)
after the rst elbow directly off the back of the unit, before
the next elbow. The horizontal run may extend up to 20’ (6 m) and include a vertical rise of up to 40’ (12 m). (Fig. 7) Horizontal termination must also meet the criteria shown in Figures 11 and 12.
• Approved vent systems must terminate above and including the heavy line in Figure 7.
• Two 45° elbows may be substituted for each single 90˚
elbow.
• With a rise between 2’ - 5’, one 90° or two 45° elbows
may be used (Excluding the rst elbow directly off the
back of the unit.
Unacceptable
Venting Conguration
High Elevations
Input ratings are shown in BTU per hour and are certied without deration for elevations up to 4,500 feet (1,370m) above sea level.
For elevations above 4,500 feet (1,370m) in USA, installations must be in accordance with the cur­rent ANSI Z223.1/NFPA 54 and/or local codes having jurisdiction.
In Canada, please consult provincial and/or local authorities having jurisdiction for installations at elevations above 4,500 feet (1,370m).
WARNING: Improper installation, adjustment, alteration, service or maintenance can cause injury or property damage. Refer to this manual for correct installation and operational proce­dures. For assistance or additional information
consult a qualied installer, service agency, or the gas supplier.
8
May use up to
four 90° Elbows
(Including elbow
directly off back of
unit.)
Two 90°
Elbows
Unacceptable
Venting Conguration
Fig. 7 Horizontal vent termination window.
ST134f
20306761
Page 9
Intrepid® Direct Vent - Rear Vent Gas Heater
20
19
18
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
20
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19
Vertical Run (in feet)
(Measured after the first elbow. (Transition elbow)
Horizontal Run (in feet)
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
ST132f Pinstar Vertical vent run 10/9/00 djt
Vertical Termination
A vertical vent system must terminate no less than 8’ (2.44 m) and no more than 40’ (12 m) above the appli-
ance ue collar. A restrictor plate (supplied) must be used (where specied) in all vertically terminated vent systems.
NOTE: The restrictor plate supplied with the vertical termination kit should be discarded. Install restrictor plate according to recommendations in Figure 10. A
vertically terminated vent system must also conform to the following criteria:
No more than three 90° elbows may be used.
Two 45° elbows may be substituted for one 90° elbow.
No more than six elbows may be used.
Vent must rise a minimum of 2 feet before offset is
used.
Termination height must conform to roof clearance as
specied in Figure 11.
All Vertical Terminations in this area Re­quire use of the Restrictor Plate*
Fig. 8 Vertical vent termination window.
20306761
Vertical terminations
must be within this area
Venting Conguration
No Restrictor
Plate
Unacceptable
ST132g
Restrictor Plate Adjustment
for Extended Pipe Runs
This stove is shipped with a restrictor plate in the Parts Bag. Adjustments can be made by loosening the adjust­ment screw to allow the restrictor plate to slide up or down. (Fig. 9) A guide for usage is shown in Figure 10.
NOTE: Some installations may require some adjustment
by the installer for optimum ame appearance. Optimum ame appearance is a ame that is not subject to tall, dirty yellow ames producing soot or ames lifting off of the
ember bed ports.
Restrictor Plate Adjustment
1. Remove the logs if installed.
2. Remove the adjustment screw in the back wall of the
rebox.
3. Install restrictor plate as shown in Figure 9 with angle on plate on the top right side. Secure with adjustment screw.
4. Adjust restrictor according to examples in Figure 10.
5. Install logs following log installation instructions.
Restrictor Plate
ST936
Fig. 9 Restrictor plate.
Examples for Extended Run/Restrictor Plate Settings ­top of plate to center of bolt
1. 90° elbow, 40’ (12 m) vertical - 2
2. 90° elbow, 20’ (6 m) vertical, 90° elbow, 8’ (2.4 m) horizontal - 27⁄8" (73 mm)
Figure 10
7
8" (73 mm)
9
Page 10
Intrepid® Direct Vent - Rear Vent Gas Heater
Vent Termination Clearances
When planning the installation, consider the location of the vent terminal and clearances. Some of the most common clearances to keep in mind are shown in Figure 11.
Important: All vent clearances must be maintained. Check your vent termination clearances against Fig­ures 11 and 12.
The vent should be placed so that people cannot be burned by accidentally touching the vent surfaces when the stove is operating.
The vent termination should be located where it cannot be damaged by such things as automobile doors, lawn mowers or snowblowers and it should be located away from areas where it could become blocked by snow, etc.
Some considerations are:
Obstructions or impediments to venting.
Nearby combustible materials that could come into
contact with combustion exhaust gases.
Other nearby openings {within 9” (230 mm)} through
which exhaust gas could reenter the building.
All vegetation within 3’ (914 mm) that may interfere with
the draft.
Other factors that inuence where the installation will be
sited include the location of outside walls, where additional heat may be desired in the home, where the family mem­bers gather most regularly, and perhaps most importantly, the distance limitations of the venting system.
Your stove is approved to be vented either through the side wall, or vertical through the roof.
Vermont Castings Group does not require any open-
ing for inspection of vent pipe.
Only venting components specically approved and
labelled for this stove may be used.
Minimum clearances between vent pipes and com-
bustible materials is one (1”) inch (25mm), except where stated otherwise.
Venting terminals shall not be recessed into a wall or
siding.
Horizontal venting must be installed on a level plane
without an inclining or declining slope.
There must not be any obstruction such as bushes, garden sheds, fences, decks or utility buildings within 24” from the front of the termination hood.
Do not locate termination hood where excessive snow or ice build up may occur. Be sure to check vent termination area after snow falls, and clear to prevent accidental blockage of venting system. When using snow blowers, make sure snow is not directed towards vent termination area.
Location of Vent Termination
It is imperative the vent termination be located observing the minimum clearances as shown in Figure 11.
IMPORTANT
The horizontal termination must not be recessed
into the exterior wall or siding.
Horizontal vent runs must be level toward the vent
termination.
Clearances around the vent termination must be
maintained.
10
20306761
Page 11
V
X
X
X
D
E
B
B
B
C
B
M
B
A
J
K
F
L
VENT TERMINATION AIR SUPPLY INLET
AREA WHERE TERMINAL IS NOT PERMITTED
H
I
Fixed
Closed
Operable
Operable
Fixed
Closed
B
INSIDE
CORNER DETAIL
A
G
CFM145a
V
V
V
V
V
V
V
V
TERMINATION LOCATION
Figure 11 – Termination Locations
Intrepid® Direct Vent - Rear Vent Gas Heater
A = Clearance above grade, veranda, porch,
CANADIAN INSTALLATIONS
1
12" (30cm) 12" (30cm)
US INSTALLATIONS
2
deck or balcony
B = Clearance to window or door that may be
opened
C = Clearance to permanently closed window 12" (305mm) recommended to prevent
D = Vertical clearance to ventilated soft
6" (15cm) for appliances <10,000 BTU/h (3kW) 12" (30cm) for appliances >10,000 BTU/h (3kW) and <100,000 BTU/h (30kW) 36" (91cm) for appliances >100,000 BTU/h (30kW)
6" (15cm) for appliances <10,000 BTU/h (3kW) 9" (23cm) for appliances >10,000 BTU/h (3kW) and <50,000 BTU/h (15kW) 12" (30cm) for appliances >50,000 BTU/h (15kW)
12" (305mm) recommended to prevent
window condensation
window condensation
18" (458mm) 18" (458mm) located above the terminal within a hor­izontal distance of 2' (610 mm) from the center line of the terminal
E = Clearance to unventilated soft 12" (305mm) 12" (305mm)
F = Clearance to outside corner see next page see next page
G = Clearance to inside corner see next page see next page
H = Clearance to each inside of center line
extended above meter/regulator assembly
3' (91cm) within a height of 15' (5m) above
the meter/regulator assembly
3' (91cm) within a height of 15' (5m) above the meter/regulator assembly
I = Clearance to service regulator vent outlet 3' (91cm) 3' (91cm)
J = Clearance to non-mechanical air supply
inlet to building or the combustion air inlet to any other appliance
6" (15cm) for appliances <10,000 BTU/h
(3kW)
12" (30cm) for appliances >10,000 BTU/h
(3kW) and <100,000 BTU/h (30kW)
36" (91cm) for appliances >100,000 BTU/h
(30kW)
6" (15cm) for appliances <10,000 BTU/h (3kW) 9" (23cm) for appliances >10,000 BTU/h (3kW) and <50,000 BTU/h (15kW) 12" (30cm) for appliances >50,000 BTU/h (15kW)
K = Clearance to mechanical air supply inlet 6' (1.83m) 3' (91cm) above if within 10' (3m) horizontally
L = Clearance above paved sidewalk or
7' (2.13m)
7' (2.13m)
paved driveway located on public property
M = Clearance under veranda, porch, deck or
12" (30cm)
12" (30cm)
balcony
1 In accordance with the current CSA-B149 Installation Codes 2 In accordance with the current ANSI Z223.1/NFPA 54 National Fuel
Gas Codes
† A vent shall not terminate directly above a sidewalk or paved
driveway which is located between two single family dwellings and
serves both dwellings
‡ Only permitted if veranda, porch, deck or balcony is fully open on a
minimum 2 sides beneath the oor.
20306761
NOTE: 1. Local codes or regulations may require different clear-
2. The special venting system used on Direct Vent Fireplac-
3. Vermont Castings Group assumes no responsibility for
ances.
es are certied as part of the appliance, with clearances
tested and approved by the listing agency.
the improper performance of the appliance when the venting system does not meet these requirements.
11
Page 12
Intrepid® Direct Vent - Rear Vent Gas Heater
Outside Corner
Inside Corner
Termination Clearances
Termination clearances for buildings with combustible and noncombustible exteriors.
Alcove Applications*
TERMINATION CLEARANCES
Termination clearances for buildings with combustible and non-combustible exteriors.
F =
F
Combustible 6" (152 mm)
Noncombustible 2" (51 mm)
G =
G
Combustible 6" (152 mm)
Noncombustible
V
2" (51 mm)
V
C
D
C
V
O
E
Balcony - with no side wall
M
V
Balcony - with perpendicular side wall
M
V
P
M =
Combustible & Noncombustible 12" (305 mm)
*NOTE: Termination in an alcove space (spaces open only on one side
and with an overhang) is permitted with the dimensions specied for vinyl or non-vinyl siding and softs. 1. There must be a 3' (914 mm) min-
imum between termination caps. 2. All mechanical air intakes within 10'
Combustible & Noncombustible
M = 12" (305 mm) P = 6” (152 mm)
(1 m) of a termination cap must be a minimum of 3' (914 mm) below the termination cap. 3. All gravity air intakes within 3' (914 mm) of a termina­tion cap must be a minimum of 1' (305 mm) below the termination cap.
Fig. 12 Termination clearances.
E = Min. 2” (51 mm) for
non-vinyl sidewalls Min. 12” (305 mm) for vinyl sidewalls
O = 8’ (2.4 m) Min.
No. of
Caps D
1 3' (914 mm) 2 x Dactual
2 6' (1.8 m) 1 x Dactual
3 9' (2.7 m) 2/3 x Dactual 4 12' (3.7 m) 1/2 x Dactual
D
= Number of Termination caps x 3
Min.
C
= (2 / Number termination caps) x D
Max.
min. Cmax.
Actual
12
20306761
Page 13
Installation
A
Unpack the Stove
The stove is shipped fully assembled on its back. Unpack the stove and carefully set it upright.
CAUTION
Porcelain enamelled surfaces are fragile. Handle por­celain enamelled castings tenderly. Familiarize yourself with the assembly steps before you begin and proceed with deliberation and care. If possible, have assistance available.
Place enamelled castings on a soft, cushioned surface until you are ready to assemble.
Avoid contact between the castings and other hard surfaces or objects.
NOTE: Verify the two relief doors (located on top of the rebox) are properly seated on the gasket. The doors sit ush on the gasket, and should lift easily from the seal around the opening.
Intrepid® Direct Vent - Rear Vent Gas Heater
Remove Four (4) Screws (Retain for future use)
KT899
Fig. 13 Remove four (4) screws holding rear fan cover in place. Retain for future use.
1/4-20 x 3/8’ Phillips Screw
If you are installing the fan, install it before com­pleting the stove venting.
If you are not installing a fan, proceed to the ap­propriate vent assembly section.
Install Optional Fan Kit FK20
Fan Kit Contents:
#10 x 1/2” phillips screws, 2
Control Knob Wire Tie
Retaining Nut Snapstat
Snapstat Bracket
Blower Assembly w/ Rheostat Control & Snapstat
1. Remove the rear fan cover by removing the four (4) screws holding the cover in place on the rear shroud. (Fig. 13) Retain the screws for future use.
2. Attach the Snapstat to the bracket using two (2) #10 x 1/2” Phillips screws. (Fig. 14)
3. Locate and remove the 1/4-20 x 3/8” hex head bolt in-
stalled in the hole in the right rear ledge of the rebox. (A,
Fig. 14) Use that bolt to secure the snapstat bracket to
the rebox. The mounting hole is slotted to allow you to
adjust the bracket so the snapstat head makes contact
with the rebox surface. (Fig. 14)
4. Attach the fan to the rebox by reusing the two (2) pan
head 1/4-20 screws on the top edge and the two (2) #10 x 1/2” sheet metal screws on the side edges. (Fig. 15)
5. The rheostat control switch attaches to the control panel plate provided on the front of the stove.
1/2” Sheet Metal Screw
Snapstat
Fig. 14 Attach snapstat.
Upper Flange
#10 x 1/2” Sheet Metal Screw
1/4-20 x 3/8” Screws (2)
#10 x 1/2” Sheet Metal Screw
Fig. 15 Use screws removed earlier to attach fan kit to rebox.
Snapstat Bracket
KT900
To Control Valve
KT901
Insert the switch box shaft through the hole in the
back of the left side of the panel, aligning the locator pin with the smaller hole in the panel. (Fig. 17)
Attach the retaining nut to the switch control shaft to
secure it to the plate.
Attach the control knob to the rheostat shaft.
20306761
13
Page 14
Intrepid® Direct Vent - Rear Vent Gas Heater
Rheostat
Retaining Nut
KT902
Fig. 16 Correct position of fan skirt installation.
Use the wire tie to secure the fan and rheostat wire
harnesses together to the tubing under the bottom
of the unit.
Venting System Components
Approved Vent System Components
The Intrepid Heater must be vented to the outdoors through an adjacent exterior wall or through the roof. The venting system must be comprised of the appropriate
listed venting components specied on this page. These
parts are available from DuraVent Corporation. See Figure 4 for dimensions relevant to the standard
minimum-vent kits.
DuraVent Components
www.duravent.com Phone: 1-800-835-4429, Fax: 1-707-446-4740
Minimum Horizontal Vent Kit 46DVA-KHC
Venting Component required for: Basic Straight Through-the-Wall Installation
Horizontal Termination Cap 46DVA-HRC Vermont Castings Group Zero Clearance Sleeve (included) 54623 Firestop 46DVA-WFS Wall Thimble Cover 46DVA-DC 24” Straight (Maximum length) 46DVA24B Hardware Package (2 req’d) 56167
NOTE: DuraVent Wall Thimble, 46DVA-WT is not ap- proved for use with this appliance except in noncombus­tible masonry walls.
For corner installation add: 45° Elbow, Blk. 46DVA-E45B
Venting Components
90° Elbow, Blk. 46DVA-E90B* 45° Elbow, Blk. 46DVA-E45B 6" Straight, Blk. 46DVA-06B* 9" Straight, Blk. 46DVA-09B 81⁄2" Pipe Extension, Blk 46DVA-08AB* 16" Pipe Extension, Blk 46DVA-16AB 12" Straight 46DVA-12
Rheostat Knob
Fig. 17 Attach rheostat to bracket.
KT903
24" Straight 46DVA-24B* 36" Straight 46DVA-36B 48" Straight 46DVA-48 Square Horizontal Termination Cap 46DVA-HC Sconce Horizontal Termination Cap 46DVA-HSC Round Horizontal Termination Cap 46DVA-HRC Wall Plate 46DVA-DC* Vinyl Siding Standoff 46DVA-VSS Snorkel Termination - 14" 46DVA-SNK14 Snorkel Termination - 36" 46DVA-SNK30 Wall Strap 46DVA-WS Cathedral Ceiling Support Box 46DVA-CS Storm Collar 46DVA-SC Firestop Spacer 46DVA-FS Flashing 0/12 - 6/12 46DVA-F6 Flashing 6/12 - 12/12 46DVA-F12 Wall Thimble 46DVA-WT* Wall Thimble Cover (Brass) 3PVP-TKV Wall Firestop 46DVA-WFS Attic Insulation Shield 46DVA-IS Co-Linear Vent Adapter 46DVA-GCL Steel Chimney Conversion Kit Kit A (6
5
8" - 85⁄8") 46DVA-KCA
Kit B (65⁄8" - 101⁄2") 46DVA-KCB Kit C (65⁄8" - 13") 46DVA-KCC Masonry Chimney Conversion Kit 46DVA-KMC Vertical Termination Cap (High Wind) 46DVA-VCH
Vertical Termination Cap (Low Prole) 46DVA-VC
*Included in Minimum Horizontal Vent Kit 46DVA-KHC
All DuraVent Straight vent pipe sections have a net length 11⁄2" (37 mm) less than the nominal dimension; i.e., a 6” (152 mm) Straight pipe section has an effective length of 41⁄2" (115 mm).
Refer to the DuraVent website for additional compo­nents. (www.duravent.com)
14
20306761
Page 15
Intrepid® Direct Vent - Rear Vent Gas Heater
Venting System Assembly
General Information
The Intrepid is approved for installation only with the Dura Vent components listed on page 14. Follow these and the vent component instructions exactly.
For U.S. installations: The venting system must conform with local codes and/or the current National Fuel Gas Code, ANSI Z223.1/NFPA 54
For Canadian installations: The venting system must conform to the current CSA B149.1 installation code.
Options
The DuraVent Direct Vent Pro offers a complete line of component parts for both horizontal and vertical installa­tion. Many items are offered in decorative black as well
as galvanized nish. The galvanized pipe and ttings may
be used for concealed locations such as attics, or spaces
where corrosion is a factor, such as above the rooine.
Decorative black painted sections are recommended for use on visible interior runs. Decorative brass trim kits are available for both Wall Thimbles and Ceiling Support Box­es. Snorkel Terminations are available for applications which may require vertical rise on the building exterior.
Planning Your Installation
There are two basic types of Direct Vent Pro installa­tions:
Horizontal Termination (Figs. 18 and 19) Vertical Terminations (Fig. 20)
When planning your installation, it will be necessary to select the proper length of vent pipe for your particular requirement. For horizontal installations, check these in­structions to determine the minimum clearance from the rear of the appliance to the wall. It is also important to note the wall thickness. Select the amount of vertical rise de­sired or required, for “vertical-to-horizontal” installations (verify that it is within the minimum and maximum limits. Refer to page 8). To determine the length of vent pipe re­quired for vertical installations, measure the distance from the appliance ue outlet to the ceiling, the ceiling thick­ness, the vertical rise in an attic or second story, and allow
for sufcient vent height above the rooine. For multi-sto­ry applications, restops are required at each oor/ceiling
level. If an offset is needed in the attic, additional pipe and elbows will be required.
Figure 18
Zero Clearance Wall Sleeve
Round Ceiling Support / Wall Thimble Cover
Pipe Section
ST973
Figure 19
Pipe Section
90° Elbow
Pipe Section
Square Horizontal Termination
Firestop
Square Horizontal Termination Cap
Zero Clearance Wall Sleeve
Firestop
Round Ceiling Support / Wall Thimble Cover
90° Elbow
20306761
ST974
15
Page 16
Intrepid® Direct Vent - Rear Vent Gas Heater
10"
(254 mm)
10"
(254 mm)
7¹⁄₂" Dia.
(190 mm)
18¹⁄₄"
(464 mm)
to
Center of
Opening
Figure 20
Round Ceil­ing Support / Wall thimble
Pipe Section
Vertical High Wind Termination Cap (shown)
Storm Collar
Roof Flashing
Ceiling Firestop
Cathedral Ceiling Support Box
90°Elbow
Vent Opening - Combustible Wall
Framing Detail
Vent Opening - Noncombustible Wall
VO584-100b
Fig. 21 Locate vent opening. NOTE: Zero clearance sleeve is required for combustible wall installations.
3. Install the Wall Firestop/Sleeve assembly into the wall
cutout and fasten the restop to the wall cutout framing
members. (Fig. 23)
10” x 10” (254 x 254 mm) Wall Opening
Zero Clear­ance Sleeve
- Seal Around
Firestop
Wall Plate
ST975
Rear Vent
Use components listed on page 14 under ‘Basic Straight through-the-Wall Installation’ for an installation where the heater is parallel to the wall and the vent system extends straight back through that wall.
1. Locate the vent opening on the wall. Refer to Figures 20 & 21 to determine the top of the opening centerline.
It may be necessary to rst position the stove and mea­sure to nd the hole location. Depending on whether the
wall is made of combustible materials, cut the opening to the size shown in Figure 21. Combustible wall openings must be framed as shown in Figure 21.
2. Measure the wall thickness and cut the zero clearance
sleeve sections to proper length (MAXIMUM 12”). Assemble the sleeve with the #8 sheet metal screws
supplied. Attach the restop plate to the sleeve end with
the holes. (Fig. 22) NOTE: The zero clearance sleeve is required in combustible walls only.
16
Seal Around Terminal
ST950
All Components Must Remain Concentric
Fig. 22 Intrepid minimum horizontal rear vent installation.
12”
(305mm)
Max. Length
Firestop
Sleeve
#8 Sheet Metal Screws
ZCS103
Fig. 23 Assemble the wall sleeve and restop.
20306761
Page 17
4. Slip the wall cover over the interior end of the horizontal pipe and install into the zero clearance sleeve. Seal the joint inside the wall plate if needed to keep cold air from being drawn into the home.
5. Install the vent terminal. (Fig. 22) Guide the inner and outer vent termination collars into the adjacent pipes. Double check that the vent pipes overlap the collars by 2”. Fasten the termination to the outside wall with the screws provided, and caulk the joint with weatherproof sealant.
6. Use wall straps to support vertical pipe runs at 4’ (1219 mm) intervals.
Horizontal Installation
Step 1. Set the gas appliance in its desired location.
Check to determine if wall studs or roof rafters are in the way once the venting system is attached. If this is the case, you may want to adjust the location of the appli­ance.
Step 2. DirectVent Pro pipe and ttings are designed with
special twist-lock connections. To connect the venting
system to the appliance ue outlet, a twist-lock appliance
adaptor is built into the appliance at the factory. Assemble the desired combinations of black pipe sections and el­bows to the appliance adapter with pipe seams oriented
towards the wall or oor, as much out of view as possible.
(Fig. 24)
Figure 24
Intrepid® Direct Vent - Rear Vent Gas Heater
Figure 25
ST977
2. Horizontal vent runs of vent pipe must be supported to prevent any downward sags. Horizontal pipe sec­tions should be supported at least every 4’ (1.2 m). Wall straps can be used for this purpose. Alternatively, plumbers tape or other suitable noncombustible mate­rial can be used to support the vent pipe.
3. DirectVent Pro venting requires no sealant.
Step 3. With the appliance adapter and pipe section at­tached, slide the stove into its correct location. Mark the wall for a square hole that measures 10” x 10” (254 x 254 mm). The centerline of the pipe should line up with the center of the square hole. (Fig. 26) Cut and frame the square hole in the exterior wall where the vent will be terminated. If the wall being penetrated is constructed of noncombustible material only, i.e. masonry block, brick or concrete only, a hole with zero clearance is acceptable.
NOTES:
ST976
NOTES:
1. Twist-lock procedure: Line up locking lugs on male and female ends of pipe sections. Insert the male end of pipe into the female end until the locking lugs are covered. Twist the female end clockwise an eighth of a turn to lock sections together. (Fig. 25) Screws are not required to secure the joint, but are acceptable pro­vided they do not penetrate the inner wall of the vent pipe.
Center of Hole
C
L
Figure 26
ST978
1. The horizontal run of venting must be level, or have a 1/4” (6 mm) rise for every 1’ (305 mm) of run toward the termination. Never allow the vent to run downward. A downward slope can trap heat and become a pos-
sible re hazard.
20306761
17
Page 18
Intrepid® Direct Vent - Rear Vent Gas Heater
2. The location of the horizontal vent termination on an exterior wall must meet all local and national building codes, and must not be easily blocked or obstructed. Refer to Pages 10 and 11 for proper Termination Clear­ances.
For installations requiring a vertical rise on the exterior of the building, 14” (356 mm) and 36” (914 mm) tall snor­kel terminations are available. (Fig. 27) Follow the same installation procedures as used for standard horizontal terminations. If the snorkel termination must be installed below grade level, (i.e. basement application), proper drainage must be provided to prevent water from enter­ing the snorkel termination. (Fig. 28) Do not attempt to enclose the snorkel within the wall or any other type of enclosure.
Figure 27
Snorkel
12” (305 mm)
Minimum
(102 mm)
4”
NOTES:
1. The four (4) wood screws provided should be replaced
Figure 29
Wood Screws
with appropriate fasteners for use on brick, block, con­crete or other types of sidings.
2. For buildings with vinyl siding or stuc­co, another compo­nent must be used between the hori­zontal termination cap and the wall
HOT
surface. The vinyl siding standoff pre-
ST981
vents excessive heat from possibly melting the vinyl siding material. Vi­nyl siding standoffs are not required with snorkels. For vinyl wall installations a 4-piece vinyl siding standoff should be assembled and installed between the hori­zontal termination cap and the exterior wall. (Fig. 30) The vinyl should be cut away to the outer edges of the assembled standoff.
ST979
Snorkel
Figure 28
12” (305 mm)
Minimum
4” (102 mm)
ST980
Step 4. Position the horizontal termination cap in the cen­ter of the square framed hole, and attach to the exterior wall with the four (4) wood screws provided. Before at­taching the vent termination cap to the exterior wall, run a bead of non-hardening silicone sealant around the outside edges to make a seal between the cap and the wall. The arrow on the vent cap should be pointing up. Ensure proper clearances to combustible materials are maintained. (Fig. 29)
Figure 30
Cut Back Siding
ST982
Sconce Cap
4 pc. Vinyl Siding Standoff
Wood Screws (4 Req.)
Round Cap
Wood Screw
IMPORTANT: You must attach the four (4) pieces of the new vinyl siding standoff to the horizontal termination cap in specic order to ensure a weather tight t. Loosely as­semble the four parts, in order, around the base of the hor-
izontal termination cap. Place the rst of four pieces along
the upper edge of the cap, then using two (2) screws per side, secure each piece to the pre-drilled holes along both sides of the cap, nally, attach the nal piece to the bot­tom edge of the cap. Tighten all screws and mount cap, with all four (4) pieces attached, directly onto the wall with the four (4) 21⁄2" (64 mm) screws provided. (Fig. 30)
18
20306761
Page 19
Intrepid® Direct Vent - Rear Vent Gas Heater
3. When penetrating through stucco wall, install the
counter ashing. The counter ashing allows stucco, or other materials, to be nished directly to the sides of the termination cap. First attach the counter ash-
ing to the base of the horizontal termination cap with the small screws provided, then mount entire assem­bly onto the wall with the four (4) 2
1
2" (64 mm) wood
screws provided.
4. If the optional copper version of the horizontal termina­tion cap is installed, use an appropriate noncombusti­ble material to avoid direct contact between the galva­nized and copper metals to prevent possible galvanic reaction.
Step 5. Before connecting your horizontal pipe sections to the horizontal termination cap, slide the wall thimble cover over the pipe section nearest the interior side of wall. (Fig. 31)
Step 6. Slide the appliance and vent assembly towards the wall, carefully inserting the pipe section into the cap assembly. It is important the pipe section extends into the back of the termination cap with a minimum overlap of 11⁄4" (32 mm). Use the two (2) sheet metal screws pro- vided to secure the pipe section to the back of the termi­nation cap. The wall thimble cover will cover the screw heads. (Fig. 31)
Figure 31
Zero Clearance Wall Sleeve
Sheet Metal Screws
ST983
Wall Thimble Cover
Firestop
Step 7. Slide the wall thimble cover up to the wall surface and attach to the wall with screws provided. (Fig. 32) Ap­ply optional decorative brass trim to wall thimble cover if desired.
Vertical Installation
Step 1. Check these installation instructions for required
clearances (air spaces) to combustibles when passing through ceilings, walls, roofs, enclosures, attic rafters or other nearby combustible surfaces. Do not pack air spac­es with insulation. Check these instructions for maximum vertical rise of the venting system and any maximum hori­zontal offset limitations.
Figure 32
Wood Screws
ST984
Step 2. Set the gas appliance
Figure 33
in the desire location. Drop a plumb bob down from the ceil­ing to the position of the ap-
pliance ue exit, and mark the
location where the vent will penetrate the ceiling. Drill a small hole at this point. Next, drop a plumb bob from the roof to the hole previously drilled in
Mark Location
Mark and Drill
the ceiling, and mark the spot where the vent will penetrate the roof. (Fig. 33) Determine if ceiling joists, roof rafters, fram­ing or other materials will ob­struct the venting system. You
Plumb Bob
may wish to relocate the appli­ance or to offset, to avoid cut­ting load-bearing members.
Step 3. To install the round ceil­ing support/wall thimble cover
in a at ceiling, cut a 10” x 10”
(254 x 254 mm) square hole in the ceiling (unless otherwise
specied) centered on the hole
ST985
drilled in Step 2. Frame the hole as shown in Figure 34.
Step 4. If the twist-lock appliance adapter has not been installed on the stove, do so now.
Step 5. Assemble the desired pipe sections and elbows necessary to reach from the appliance adapter up through the round ceiling cover or support box. Ensure that all pipe and elbow connections are in their fully twist-locked position.
Step 6. Cut a hole in the roof centered on the small drill hole placed in the roof in Step 2. The opening should be
of sufcient size to meet the minimum requirements for clearance to combustibles, as specied. Continue to as-
20306761
19
Page 20
Intrepid® Direct Vent - Rear Vent Gas Heater
Figure 34
semble pipe sections and elbows as neces­sary to reach up through the roof line. Galvanized pipe and elbows may be utilized in the attic,
Ceiling Joists
Cut and Frame
as well as above the
rooine. The galvanized nish is desirable above the rooine, due to high-
er corrosion resistance.
Decorative Ceiling Support Cover
1
1
2" Wood
Screws
Figure 35
ST986
ST987
Figure 36
Pipe Extension
Pipe Section
NOTES:
1. If exact lengths or dis­tances must be met be­tween elbow offsets or
Wall Strap / Plumbers Tape
elsewhere, use the pipe extensions to adjust onto standard pipe sections. (Fig. 35)
2. If an offset is necessary in the attic to avoid ob-
45° Elbow
45° Elbow
structions, it is important to support the vent pipe in order to avoid excessive stress on the elbows. Wall
ST988
straps or plumber tape may be used for this pur­pose. (Fig. 36)
3. Wherever possible, use 45° elbows instead of 90° el-
bows. The 45° elbow offers less restriction to the ow of ue gases and intake air.
Step 7. Slip the roof ashing over the pipe section(s) pro- truding through the roof. Use a non-hardening sealant be-
tween the roof ashing and the roong to prevent water leakage. Secure the base of the roof ashing to the roof with roong nails. Ensure the roong material overlaps
the top edge of the roof ashing. (Fig. 38) Verify that you
have at least the minimum clearances to combustibles at
the rooine and in the attic.
Step 8. Continue to add pipe sections until the height of the system (before adding the cap) meets the minimum building codes require­ments as described in Table 2, Figure 37. Note that for steep
Figure 37
Dimension ‘H’ from Table 2
H
roof pitches, the vent height must be in­creased. In high wind conditions, nearby trees, adjoining rooi­nes, steep pitched roofs and other similar
ST989
factors can result in
Table 2
Roof Pitch Minimum Height
Flat 7/12 1’ (914 mm) Over 7/12 to 8/12 1’6” (457 mm) Over 8/12 to 9/12 2’ (610 mm) Over 912 to 10/12 2’6” (762 mm) Over 10/12 to 11/12 3’3” (990 mm) Over 11/12 to 12/12 4’ (1.2 m) Over 12/12 to 14/12 5’ (1.5 m) Over 14/12 to 16/12 6’ (1.8 m) Over 16/12 to 18/12 7’ (2.1 m) Over 18/12 to 20/12 7’3” (2.3 m) Over 20/12 to 21/12 8’ (2.4 m)
poor draft, or down drafting. In these cases, increasing the vent height or switching to the high wind termination cap may help to solve the problem.
Step 9. Slip the storm collar over the pipe section, and
push it down to the top of the roof ashing. (Fig. 38) Use
non-hardening sealant between the storm collar and the pipe section
Step 10. Holding the bottom of the termination cap only, twist lock the cap onto the last pipe section protruding
above the rooine.
NOTES:
1. For multi-story vertical installations, a ceiling restop is required at the second oor, and any subsequent oors. (Fig. 39) Cut and frame a 9” x 9” (229 x 229 mm) square opening for installation of the ceiling restop.
2. If vent passes through any occupied areas above the
rst oor, including closets and storage spaces, it must
be enclosed. The enclosure may be framed and cov­ered with sheet rock with standard construction materi­als, but required clearances to combustibles must be maintained. Consult these installation instructions for the minimum allowable clearances between the out-
20
20306761
Page 21
Intrepid® Direct Vent - Rear Vent Gas Heater
High Wind Vertical Termination
Storm Collar
Roof Flashing
Optional
Low Prole
Termination Cap
Secure Flashing with Non-harden­ing Sealant and
Roong Nails
Figure 38
side of the vent pipe and the combustible surfaces of the en-
ST990
closure. Do not ll re­quired air spaces with insulation.
3. If venting system passes through an attic space an at­tic insulation shield must be installed to prevent con­tact between pipe sections and the insulation. Nail the
base to oor of attic and adjust shield for appropriate
insulation level, then attach the collar at the top of as­sembly. (Fig. 39) For vaulted ceilings, the attic insu­lation shield cannot be installed. To prevent building insulation and other debris from entering the support box or contacting the pipe, a chase enclosure can be constructed around the support box. Ensure proper clearance to combustibles are maintained.
Cathedral Ceiling Installation
Step 1. Follow installation Step 1 and 2 under Vertical
Termination.
Step 2. Using the plumb bob, mark the centerline of the venting system on the ceiling and drill a small hole through the ceiling and roof at this point. From the roof, locate the drill hole and mark the outline of the Cathedral Ceiling Support Box.
Step 3. Remove shingles or other roof covering as neces­sary to cut the rectangular hole for the support box. Cut the hole 1/8” (3 mm) larger than the support box outline.
Step 4. Lower the support box through the hole in the roof until each side of the bottom of the support box protrudes at least 2” (51 mm) below the ceiling. (Fig. 40) Align the support box both vertically and horizontally with a level.
Figure 39
Required Clearance
Figure 40
Cathedral Ceiling Support Box
Attic Insulation Shield
ST991
Level
ST992
Nails
Minimum Clearance
Minimum Clearance
2” Min. Below Finished Ceil­ing
Cut Hole 1/8” Larger than Sup­port Box
Temporarily tack the support box in place through the in­side walls and into the roof sheathing.
Step 5. Using tin snips, cut the support box from the top
corners down to the rooine, and fold the resulting aps over the roof sheathing. The aps may be trimmed as
needed. (Fig. 41) Before nailing it to the roof, run a bead of non-hardening sealant around the support box to make a seal between the support box and the roof. Clean out any combustible material from inside the support box.
Step 6. Follow Steps 4 and 5 of the Vertical Installation instructions.
Step 7. Place the support clamp (provided with the sup­port box) inside the support box (at the bottom), and se­cure to the pipe section. The clamp allows the support box to support the weight of the pipe sections. Continue to
add pipe sections until you are above the rooine.
20306761
21
Page 22
Intrepid® Direct Vent - Rear Vent Gas Heater
Figure 41
ST993
Step 8. Follow Steps 7 through 10 of the Vertical Installa­tion instructions
Step 9. Install the black trim collar around the outside of the Cathedral ceiling support box. The two pieces of the trim collar slide over one another to allow for easy adjust­ment around the support box. Using the six (6) screws provided, secure the four corners and the overlapping sections of the trim collar to the underside of ceiling. You may want to predrill the holes for the overlapped sections for ease of installation. (Fig. 42)
Figure 42
Overlap
Cathedral Ceil­ing Support Box
ST994
Ceiling Trim
Screws
General Maintenance
Conduct an inspection of the venting system annually. Recommended areas to inspect are as follows:
1. Check areas of the venting system which are exposed to the elements for corrosion. These will appear as rust spots or streaks, and in extreme cases, holes. These components should be immediately replaced.
2. Remove the vertical terminations cap and shine a
ashlight down the vent. Remove any bird nests, or
other foreign material.
3. Check for evidence of excessive condensation, such as water droplets forming in the inner liner, and subse­quently dripping out at joints. Continuous condensate
can cause corrosion of caps, pipe and ttings. It may
be caused by having excessive lateral runs, too many elbow and exterior portions of the system being ex­posed to cold weather.
4. Inspect joints to verify that no pipe sections or ttings
have been disturbed or loosened. Also check mechan­ical supports such as wall straps or plumbers tape for rigidity.
Supplemental Canadian Instructions
When installing DirectVent Pro on appliances in Canada, a 2-piece decorative wall thimble is required in order to comply with IR #41. (Fig. 18 and 20) Install galvanized exterior wall thimble plate on exterior of building and black decorative wall thimble plate on the interior side of wall. Install wall thimble centered through a square framed opening in wall. Be sure to maintain all minimum clear­ances. When installing DirectVent Pro vertically through
oors, a ceiling restop is required at every oor/ceiling
level.
Vertical Through Existing Chimney
The heater must be vented to the outdoors through an ex-
isting masonry or prefabricated replace chimney system
through the roof.
The heater is approved to be vented to the outdoors through
any solid-fuel replace chimney that has been constructed
or installed in accordance with the national, Provincial/State and local building codes and is constructed of noncombus­tible materials. For Venting Requirements, refer to page
10. Refer to Venting Components on page 14.
Converting a Class-A Metal Chimney or Ma­sonry Chimney to a Direct Vent System
Application
These instructions apply to the DuraVent Direct Vent Con­version kits for factory-built Class-A metal chimneys and masonry chimneys. These venting systems, in combination with the gas appliance, have been tested and listed by a major testing agency such as UL, AGA, Omni or Warnock Hersey. Check the manufacturer’s rating plate and instruc-
tion manual to conrm that a DuraVent Direct Vent Chimney
Conversion system is approved for use on the brand name appliance you have selected.
IMPORTANT
Read all instructions carefully before starting the instal­lation. Failure to follow these instructions may create a re or other safety hazard, and will void the warranty. Be sure to check the appliance manufacturer’s instal­lation instructions for specic venting and clearance to combustible requirements, which may vary from one appliance to another.
22
20306761
Page 23
Intrepid® Direct Vent - Rear Vent Gas Heater
Use Conversion Kit A (#0931) for the following chimney: 6” ID Metalbestos 6” ID Security Chimney 6” ID Jackes - Evans 6” ID Hart & Cooley 6” ID Pro Jet
Use Conversion Kit B (#0932) for the following chimney: 6” ID DuraVent 7” & 8” ID Metalbestos 7” ID Security Chimney 7” & 8” ID Jackes - Evans 7” & 8” ID Hart & Cooley 7” & 8” ID Pro Jet 6” & 7” ID Metal -Fab 6” & 7” ID American Metals
Use Conversion Kit C (#0933) for the following chimney: 7” & 8” ID DuraVent 8” ID Air Jet 8” ID Metal Fab 8” ID American Metals
0909B
ST955
Installation Precautions
The DuraVent Direct Vent System is an engineered product that has been designed and tested for use with an approved list of direct vent gas appliances. The DuraVent warranty will
be voided, and serious re, health or other safety hazards
may result from any of the following actions:
to factory-built metal ceiling-supported type systems and masonry through-the-wall type systems. NOTE: You cannot install a Conversion Kit in a through-the­wall type factory-built metal chimney.
General Installation
Two different types of direct vent conversion systems are described here. One is through an existing factory-built metal chimney going through the ceiling. The other is through the wall of an existing masonry chimney. Follow the appropriate directions for your situation.
A typical direct vent conversion of a factory-built metal chimney is shown in Figure 43. The concept of the direct vent conversion is to connect an adapter to an Underwrit-
ers Laboratories listed 4” diameter aluminum ex pipe (DuraVent’s DuraFlex is an example of a UL listed ex pipe). The ex is then passed down through the center of
the existing metal chimney system. Three sizes of termi-
nation caps are available which should t most sizes and
makes of metal chimney systems. The Retro Connector
(909B) is then attached to the bottom of the ex pipe. Both
the cap adapter and retro connector are attached to the existing chimney with sheet metal screws. The appliance is then connected to the chimney with appropriate black direct vent pipe and an adjustable length section.
A typical conversion of an existing masonry chimney is shown in Figure 45. For installation through the wall of an existing masonry chimney, a cap adapter (985K) and
ashing are used at the top of the masonry chimney. The 4”
aluminum liner is connected to the adapter and is passed down the chimney and out through the masonry wall. This is attached to the retro connector (909B) which is in turn, attached to the masonry wall and is then connected to the direct vent pipe leading to the appliance.
Installation of any damaged Direct Vent compo-
nent.
Unauthorized modication of the Direct Vent Sys-
tem.
Installation of any component part not manufactured
or approved by DuraVent.
Installation other than as instructed by DuraVent and
the appliance manufacturer.
Consult your local building codes before beginning the installation. Have the existing installation inspected by a
qualied chimney sweep or professional installer, prior to
converting to direct vent. The existing chimney system must be in serviceable condition, and functionally sound. The
direct vent conversion described herein applies only
20306761
23
Page 24
Intrepid® Direct Vent - Rear Vent Gas Heater
ST956 metal chim conv 7/07
Figure 43
Converting a Factory-Built Metal Chimney
Termination Cap
Top Adapter 0985K, 0986K or 0987K
Existing Metal Chimney System
4” Aluminum Flex Pipe
Figure 44
Co-Linear Insert
Vertical Termination Cap
Chimney Liner Termination Kit
3” Flex
Retro Connector 0909B
Co-Axial to Co-Linear Connector
Any Black Direct Vent Pipe Plus an Adjustable Length to Make a Proper Connector
ST995
ST956
24
20306761
Page 25
Intrepid® Direct Vent - Rear Vent Gas Heater
Figure 45
Converting a Masonry Chimney
Termination Cap
Top Adapter
Flashing
4” Flex Liner
Installation Instructions for Converting a Fac­tory-Built Metal Chimney
1. Remove the existing chimney cap.
2. Measure the distance from the top end of the chimney to the bottom of the ceiling support box, add 3” to this
measurement and cut a section of 4” ex pipe to that length (the ex should already be extended to its nominal
length).
3. Connect the end of the ex pipe section to the underside
of the cap adapter you have selected using three (3) sheet metal screws. (Fig. 46)
Top Adapter
Sheet Metal Screws
Retro Connector
Black Direct Vent Pipe
ST961
Flex
Figure 46
ST957
Pipe
4. Pass the ex pipe down through the center of the chim­ney system, and center the adapter on the top of the chimney pipe. Drill four (4) 1/8” diameter holes through the adapter and into the chimney top. Insure that you are in fact, drilling into the metal on the chimney. Twist-lock the termination cap (980, 991 or 930) onto the adapter. (Figs. 47 and 48)
Figure 48
Figure 47
5. Pull the ex pipe down through the ceiling support box,
Termination Cap
Sheet Metal Screws
Drill
Four (4)
1/8” Diameter
Holes
until it protrudes approximately 3” (76 mm). Connect
the ex pipe to the retro connector by slipping it into
3
4"(121 mm) diameter sleeve on the top side of
the 4 the connector. Use three (3) sheet metal screws to assemble these two parts.
20306761
25
Page 26
Intrepid® Direct Vent - Rear Vent Gas Heater
Sheet Metal Screws (3)
Existing Ceiling Support Box
ST960
Sheet Metal Screws (3)
Figure 49
6. Push the ex pipe back up into the ceiling support box,
center the retro connector and attach it to the support box or decorative sleeve for double wall solid packed pipe, with the sheet metal screws furnished. The holes in the retro connector are pre-punched. (Fig. 49)
7. The connection between the appliance and the retro connector may be completed with sections of black direct vent pipe, together with an adjustable length.
Installation Instructions for Converting a Ma­sonry Chimney
IMPORTANT: The existing masonry ue opening need to
have an area of at least 35 square inches (226 square mm)
to insure proper intake/exhaust ow.
1. Before cutting any holes, assemble the desired sections of black direct vent pipe to determine the center of the masonry penetration.
2. Once the center point of the penetration has been deter­mined, cut a 6” (152 mm) diameter hole in the masonry. Be careful, if the hole is too large, the retro connector might not mount properly. If the hole is too small, then the appliance might starve for intake air. If there is a frame wall in front of the masonry wall, cut and frame a 10” (254 mm) clear square opening in the wall (centered around the 6” (152 mm) masonry opening). If there is sheet rock only (no studs) in front of the masonry, the 10” (254 mm) clear opening is still needed, but does not need to be framed. This allows the retro connector to mount directly on the masonry and provide clearance to the combustibles. (Fig. 54)
3. Secure the ashing (705C) to the top of the masonry
chimney using a bead of non-hardening sealant-adhe-
sive. If the ashing is larger than the top of the chimney, then cut and fold ashing as needed to t chimney. (Fig.
50)
4. To determine the length of ex required, measure from 3” (76 mm) above the top of the ashing down to the level
of the opening. Add to this measurement the distance from the center of the chimney to out through the wall.
Cut a piece of 4” (102 mm) ex to this length (the ex
should already be extended to its nominal length).
5. Connect the 4” ex liner to the cap adapter (985K) using
three sheet metal screws. (Fig. 46)
Cut & Bend Flashing as Needed to Fit Chimney
Figure 50
Sealant ­Adhesive
6. Feed the 4” ex liner through the ashing into the chim-
ney. Continue to feed the liner out through the opening in the masonry wall.
7. Secure the cap adapter to the ashing. Use three (3)
sheet metal screws through the side of the adapter
into the ange on the ashing as shown in Figure 51.
Twist-lock the termination cap (980,991, 930) on to the cap adapter.
High Wind Termination Cap
Standard Termination Cap
Top Adapter
Sheet Metal Screws (3)
Flashing
ST963
Figure 51
8. Attach the ex to the retro connector. Use three sheet metal screws to attach the ex liner to the connector.
(Fig. 52) Mount the retro connector to the masonry wall using masonry bolts. Re-drill larger holes on connector as needed. Be careful to insure that the connector is centered in the opening and the mounting holes line up with the masonry wall.
9. Slide the wall thimble cover (940) over the retro connector and secure the with masonry bolts as shown in Figure
53. If you have a framed wall in front of the masonry, use wood screws to mount the wall thimble cover to the framed wall, over the retro connector and the 10” (254 mm) square framed opening as shown in Figure 54. If needed, add a section of direct vent pipe to the retro connector in order to extend through the opening in the wall thimble cover.
26
20306761
Page 27
Intrepid® Direct Vent - Rear Vent Gas Heater
10. The connection between the appliance and the retro connector may be completed with the section of black direct vent pipe, together with an adjustable length pipe section.
6” Diameter Opening in Masonry Wall
Retro Connector
Masonry Bolts (3) (Not included)
Figure 52
Retro Connector
Wall Thimble Cover
Masonry Bolts (4) (Not included)
Figure 53
Stud Wall
10” X 10” Framed Opening in Wall
Retro Connector
Wall Thimble Cover
ST964
ST965
Connect the Gas Supply Line
Check the rating plate attached by a steel cable to the
rebox, to conrm that you have the appropriate rebox
for the type of fuel to be used. The Intrepid may be con­verted from one gas to another using the appropriate Fuel Conversion Kit listed on page 42.
CAUTION
This appliance should only be connected by a qualified gas technician. Test to conrm manifold pressures as specied below.
The Intrepid Heater and the individual shutoff valves must be disconnected from the gas supply piping during any pressure testing of that system at test pressures in excess of 1/2 psig (3.5 kPa).
The Intrepid Heater must be isolated from the gas supply piping system by closing the individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressure equal to or less than 1/2 psig.
There must be a gas shutoff between the stove and the supply.
In order to connect Natural Gas, use a tting with 3/8” NPT nipple on the valve side and 1/2” natural gas supply line with a minimum input of 21,000 BTUs at a minimum inlet pressure of 5.5” w.c.
In order to connect Propane, use a tting with 3/8” NPT nipple on the valve side and 1/2” propane gas supply line with a minimum input of 21,000 BTUs at a minimum inlet pressure of 11.0” w.c.
In the U.S.: Gas connection should be made in accordance
with current National Fuel Gas Code, ANSI Z223.1/NFPA
54. Since some municipalities have additional local codes, be sure to consult your local authority.
In Canada: consult the local authority and CSA-B149.1 installation code.
Connect the gas supply and test for leaks. Use a mild soap and water solution applied with a brush no larger than 1” (25 mm). Never apply soap and water solution with a spray
bottle. Do not use an open ame for leak testing.
Masonry Chimney
Masonry Bolts (4) (Not included)
Figure 54
20306761
ST966
27
Page 28
Intrepid® Direct Vent - Rear Vent Gas Heater
PILOT
ADJ
TP
TH
TPTH
INTREPID
Burner Information
The appliance must only use the gas specied on the
rating plate, unless converted using a Vermont Castings Fuel Conversion Kit. Refer to page 42 for correct Fuel Conversion Kit for your stove model.
Coversion instructions are provided with each kit and on page 34 of this manual.
THIS APPLIANCE SHOULD BE CONNECTED TO THE
GAS SUPPLY ONLY BY A QUALIFIED GAS SERVICE TECHNICIAN. FOLLOW ALL LOCAL CODES.
THERE MUST BE A GAS SHUT-OFF BETWEEN THE
STOVE AND THE SUPPLY.
Complete the Assembly
• Open the swiveling latches (cams) on the top left and right corners of the glass frame.
• Position the glass and frame against the rebox by
placing the bottom edge on the brackets on the bottom
face of the rebox.
• Swing the assembly against the rebox, and close the latches rmly against the pins protruding from the rebox
top.
Install ON/OFF Switch
The switch assembly parts are found in the parts bag.
1. Apply wiring harness to the ON/OFF switch terminals then insert into cut out on switch housing. The ON/OFF switch will ‘snap’ into the cutout. (Fig. 55)
2. Run wires through cut out in side of shroud, under bot­tom of rear shroud to valve.
3. Using supplied #10 x 1/2” screws, attach switch housing over cut out opening in rear shroud.
4. Attach wires to valve terminals. (Fig. 56)
ST228
Fig. 56 Attach switch wires to valve.
Install the Front Plate
Grasp the Front Plate and lift it into position, engaging the two steel tabs at the upper corners behind the adjacent bosses in the Side Plates. (Fig. 57) Seat the Front against the Sides so that the tabs at the bottom lip engage with the notches in the edge of the stove base.
When properly installed, the bottom of the Front Plate cannot be pulled away from the sides without also lifting it up.
If you are installing optional Warming Shelves, do so now, according to the instructions supplied with that kit.
Bottom Tabs Engage Notch in Base
Fig. 57 Install stove front.
ST967
Thermostat Connection
(Optional) R Models Only
Wire Harness
Switch As­sembly
Fig. 55 Attach switch assembly to rear shroud.
Screw
28
ST1120
Use only a thermostat rated for 500 - 750 millivolts.
Check the table below for the appropriate gauge ther­mostat wire to use for the length of lead required in your installation.
Thermostat
Wire / Gauge Maximum Run
18 40 feet 20 25 feet 22 16 feet
1. Install the wall thermostat in the desired location and run the wires to the stove location. Terminate these leads with 1/4” female connectors.
2. Connect the thermostat wires to the valve. (Fig. 56)
This completes assembly of the Intrepid stove.
20306761
Page 29
Install the Log Set
Remove the logs from their packaging and inspect each piece for damage. DO NOT INSTALL DAMAGED LOGS.
CAUTION: Before installation, inspect ember bed burner for damage. Do not use ember bed if damaged or cracked. NOTE: Small, shallow surface cracks are acceptable.
1. Install the rear log by matching the notch on the bottom left of the log on the raised notch on back left side of the ember bed. Cutout on bottom right side is clearance for pilot assembly. (Fig. 58) Gently push right side of log back until it contacts thermopile on pilot assembly.
Rear Log
Intrepid® Direct Vent - Rear Vent Gas Heater
Left Log
Right
Log
Figure 60
4. Install top log by mating hole on bottom of log with locating pin on top right side of rear log. (Fig. 61) Posi­tion log so it is angled down toward the area where the front two logs meet.
Figure 58
2. Place the left front log on the pin locator on ember bed. Position the log over the air inlet hole and on notched out portion of ember bed. (Fig. 60)
3. Place front right log on ember bed by mating notch on bottom of log with raised notch on ember bed. Position over the air inlet hole and on notched out portion of ember bed. (Fig. 60)
Raised Notch
Pin
Pilot Assembly
Raised Notch
Left Log
Figure 61
Ember Bed
Back Log
Top Log
Right Log
Figure 59
20306761
29
Page 30
Intrepid® Direct Vent - Rear Vent Gas Heater
CERTIFIED
SAFETY BARRIER
DANGER
HOT GLASS WILL
CAUSE BURNS.
Safety Barrier Installation Instructions
NOTE: A barrier designed to reduce the risk of burns from the hot viewing glass is provided with this appliance and shall be installed for the protection of children and other at risk individuals. If the barrier becomes damaged, the barrier shall be replaced with the manufacturer's barrier for this appliance.* Any safety screen, guard, or barrier removed for servicing the appliance must be replaced prior to operating the appliance.
* See parts list for model number.
The safety barrier has been designed to work with the doors open or closed.
1. Remove screen from packaging.
2. Align screen on stove front and adjust spring n­gers as needed. Press into place until spring ngers
engage. Figure 62
3. Press the screen against the stove snapping the two
spring ngers until the screen ts securely in place.
NOTICE: It is the responsibility of the installer to ensure
the barrier is afxed to the stove at the time of instal­lation. The barrier is designed to be installed with the doors open or closed.
DO NOT TOUCH GLASS
UNTIL COOLED.
NEVER ALLOW CHILDREN
TO TOUCH GLASS.
A barrier designed to reduce the risk of burns from the hot
viewing glass is provided with this appliance and shall
be installed for the protection of children and
other at risk individuals.
20306543
WARNING: The safety screen barrier must be installed after the glass front is in place. It is NOT a replacement for the glass and the unit must NOT be oper­ated without the glass in place.
Adjustable spring
ngers
Figure 62 ­Safety Barrier Installation
30
20306761
Page 31
Operation
H
I
L
O
O
F
F
O
N
O
F
F
E A
P
I
L
O
T
THTP
TP
TH
L
O
H
I
Turn
counterclockwise
to increase
flame height
Turn clockwise
to decrease
flame height
Intrepid® Direct Vent - Rear Vent Gas Heater
The Intrepid is operated with the operable door front plate in place with the doors open or closed. To open the front doors, pull either door toward you.
Your First Fire
Read these instructions carefully and familiarize yourself with the burner controls shown in Figure 63. Locate the pilot assembly, Figure 64. Follow the lighting instructions on exactly.
During the rst re, it is not unusual to smell some odor
associated with new logs, paint and metal being heated. Odors should dissipate within a few hours. You can open a window to provide fresh air to alleviate the condition.
Inlet Pressure Tap
Manifold Pressure Tap
Pilot Adjustment Screw
Fig. 63 NOVA SIT valve control.
Regulator Control Knob
Gas Control Knob
ST941
Flame & Temperature Adjustment
For stoves equipped with HI/LO valves, ame adjustment
is accomplished by rotating the HI/LO adjustment knob located near the center of the gas control valve. (Fig. 65)
Flame Characteristics
It is important to periodically perform a visual check of the
pilot and the burner ames. Compare them to Figure 66. If any of the ames appear abnormal call a service person.
Fig. 65 Flame adjustment knob for SIT valve.
PSE Pilot
SIT Pilot
Pilot Assembly
Fig. 64 Pilot Assembly location.
Pilot and Burner Inspection
Each time you light your heater check that the pilot ame and burner ame pattern are as shown in Figure 66. If ame patterns are incorrect, turn the heater off. Contact your dealer or a qualied gas technician for assistance.
Do not operate the heater until the pilot ame is correct.
Follow regular maintenance procedures as described on page 37.
20306761
Fig. 66 Correct pilot and burner ame patterns.
Extension Knobs
On/Off and Hi/Lo control knob extensions have been in-
cluded in the nish bag. These may be installed on the
appropriate knob by aligning the notch on the existing knob (Fig. 63) with the tab on the inside of the extension knob (Fig. 67) Push the extension knob as far as it will go onto the existing knob.
Tab - align with notch
Fig. 67 Extension knob.
on existing knob
31
Page 32
Intrepid® Direct Vent - Rear Vent Gas Heater
PILOT
ON
OFF
ON
P
I
L
O
T
O
F
F
O
F
F
3/8" - 1/2"
Lighting and Operating Instructions
FOR YOUR SAFETY READ BEFORE LIGHTING
WARNING:If you do not follow these instructions exactly, a re or explosion
may result causing property damage, personal injury or loss of life.
A. This heater has a pilot which must be lit manually.
When lighting the pilot follow these instructions ex­actly.
B. BEFORE LIGHTING smell all around the heater area
for gas. Be sure to smell next to the oor because
some gas is heavier than air and will settle on the
oor.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any replace
• Do not touch any electric switch
• Do not use any phone in your building
• Immediately call your gas supplier from a neighbor’s
phone. Follow the gas supplier’s instructions.
Lighting Instructions
1. STOP! Read the safety information above.
2. Turn off all electrical power to the replace.
3. Turn the On/Off switch to “OFF” position, set the remote to OFF or set thermostat to lowest level.
4. Open control access panel.
5. Push in gas control knob slightly and turn clockwise
to “OFF”.
6. Remove glass door before lighting pilot. (See Glass
• If you cannot reach your gas supplier, call the Fire Department
C. Use only your hand to push in or turn the gas control
knob. Never use tools. If the knob will not push in or
turn by hand, do not try to repair it, call a qualied
service technician. Applying force or any attempted
repair may result in a re or explosion.
D. Do not use this replace if any part has been under
water. Immediately call a qualied service technician
to inspect the heater and to replace any part of the control system and any gas control which has been under water.
piezo spark ignitor until a ame appears. Continue to
hold the control knob in for about one (1) minute after the pilot is lit. Release knob and it will pop back up. Pilot should remain lit. If it goes out, repeat steps 5 through 8.
• If knob does not pop up when released, stop and immediately call your service technician or gas supplier.
SIT NOVA
Honeywell
Frame Removal section).
7. Wait ve (5) minutes to clear out any gas. Then smell for gas, including near the oor. If you smell gas,
STOP! Follow “B” in the safety information above. If you do not smell gas, go to the next step.
8. Visibly locate pilot by the main burner.
9. Turn knob on gas control counterclockwise to “PILOT”.
10. Push the control knob all the way in and hold. Im­mediately light the pilot by repeatedly depressing the
1. Turn the On/Off switch to Off position or set the thermostat to lowest setting.
2. Turn off all electric power to the replace if service
is to be performed.
32
• If after several tries, the pilot will not stay lit, turn the gas control knob to “OFF” and call your service technician or gas supplier.
11. Replace glass door.
12. Turn gas control knob to “ON” position.
13. Turn the On/Off switch to “ON” position or set ther­mostat to desired setting.
14. Turn on all electrical power to the replace.
To Turn Off Gas To Heater
3. Open control access panel.
4. Push in gas control knob slightly and turn clockwise to “OFF”. Do not force.
5. Close control access panel.
20306761
Page 33
Intrepid® Direct Vent - Rear Vent Gas Heater
Troubleshooting the Gas Control System
SIT NOVA 820 MILLIVOLT VALVE
NOTE: Before trouble shooting the gas control system, be sure external gas shut off is in the “On” position.
Symptom
1. Spark ignitor will not light
2. Pilot will not stay lit after carefully following lighting instructions
3. Pilot burning, no gas to main burner
4. Frequent pilot outage problem
Possible Causes
A. Defective or misaligned electrode
at pilot
B. Defective ignitor (Push Button)
A. Defective pilot generator (thermo-
couple), remote wall switch
B. Defective automatic valve
A. Wall switch or wires defective
B. Thermopile may not be generat-
ing sufcient millivoltage
C. Plugged burner orice
D. Defective automatic valve opera-
tor
A. Pilot ame may be too low or
blowing (high) causing the pilot safety to drop out
B. Possible blockage of the vent
terminal
Corrective Action
Using a match, light pilot. If pilot lights, turn off pilot and push the red button again. If pilot will not light - check gap at electrode and pilot-should be 1/8” to have a strong spark.
With the control knob in the pilot position, push the control knob all the way and hold. Check for spark at electrode and pilot. If no spark to pilot, and electrode wire is properly connected, replace the battery in the ignitor module and try again. Refer to Maintenance Section. If the problem still exists, replace the ignitor module box.
Check pilot ame. Must impinge on thermocouple/ther­mopile. NOTE: This pilot burner assembly utilizes both a thermocouple and a thermopile. The thermocouple operates the main valve operation (On and Off). Clean
and or adjust pilot for maximum ame impingement on
thermopile and thermocouple.
Turn valve knob to “Pilot”. Maintain ow to pilot; millivolt
meter should read greater than 10mV. If the reading is okay and the pilot does not stay on, replace the gas valve. NOTE: An interrupter block (not supplied) must be used to conduct this test.
Check wall switch and wires for proper connections. Jumper wire across terminals at wall switch, if burner comes on, replace defective wall switch.. If okay, jumper wires across wall switch wires at valve, if burner comes on, wires are faulty or connections are bad.
1. Be sure wire connections form thermopile at gas valve terminals are tight and thermopile is fully inserted into pilot bracket.
2. One of the wall switch wires may be grounded. Re­move wall switch wires form valve terminals if pilot now stays lit, trace wall switch wiring for ground.
May be grounded to replace or gas supply.
3. Check thermopile with millivolt meter. Take reading at thermopile terminals of gas valve. Should read 250-300 millivolts (minimum 150) while holding valve knob depressed in pilot position and wall switch “Off”. Replace faulty thermopile if reading is
below specied minimum.
Check burner orices for debris and remove.
Turn valve knob to “On”, place wall switch to “On” millivolt meter should read greater than 150mV. If the reading is okay and the burner does not come on, replace the gas valve.
Clean and/or adjust pilot ame for maximum ame
impingement on thermopile and thermocouple.
Check the vent terminal for blockage (recycling the ue
gases).
20306761
33
Page 34
Intrepid® Direct Vent - Rear Vent Gas Heater
H
I
L
O
H
I
L
O
LP Configuration
Natural Gas Configuration
H
I
L
O
Fuel Conversion Instructions
WARNING! This conversion kit shall be installed by a qualied service agency in accordance with the manufacturer’s instructions and all applicable codes and requirements of the authority having ju­risdiction. If the information in these instructions is not followed exactly, a re, explosion or production of carbon monoxide may result causing property damage, personal injury or loss of life. The qualied service agency is responsible for the proper instal­lation of this kit. The installation is not proper and complete until the operation of the converted appli­ance is checked as specied in the manufacturer’s
instructions supplied with the kit.
CAUTION: The gas supply shall be shut off prior to disconnecting the electrical power, before proceed­ing with the conversion.
Main
Gas Supply Inlet
Fig. 68 Attach the gas line to the right side of the valve.
Gas Line
ST226b
4. Insert a 5/32” or 4 mm Allen wrench into the hexagonal key-way of the screw (Fig. 70), rotate it counterclock­wise until it is free and extract it.
5. Check that the screw is clean and if necessary remove dirt.
6. Flip the screw. (Fig. 71)
7. Using the Allen wrench as shown in Figure 72, rotate the screw clockwise and tighten until snug.
WARNING: Do not overtighten the screw. Rec­ommended to grip the wrench by the short side.
8. Verify that if the conversion is from NG to LP, the screw must be reassembled with the red o-ring visible. (Fig.
73)
9. Replace the black protection cap.
WARNING: Check that also the pilot and main burner injectors are appropriate for the gas type.
I
H
O
L
I
H
O
L
I
H
O
L
Before proceeding, turn control knob on valve to OFF and turn gas supply OFF. Turn OFF any electricity that may be going to the appliance.
1. Remove stove front. Lift stove front up and then swing bottom out and away to disengage from the stove body (page 38, Fig. 82).
2. Swing open the swiveling latches at the top left and right corners of the glass frame (page 38, Fig. 83).
3. Pull the top edge of the glass and frame assembly
away from the rebox face. Place the assembly out of the way on a at, padded surface such as a counter
protected by a towel.
4. Remove the logset from the rebox.
Valve Conversion
1. Turn control knob to the OFF position, and shut off the gas supply to the valve.
2. Allow the valve to cool to room temperature.
3. Remove the black protection cap by hand. (Fig. 69)
34
Conversion Precautions
Conversion Procedure
Figure 69
Figure 70
Figure 71
Figure 72
Figure 73
Red O-ring Visible
Red O-ring NOT Visible
Pilot Orice Conversion
1. Locate pilot. (Fig. 74)
2. Replace pilot orice.
Pilot Type 1
• Remove pilot hood by lifting up. (Fig. 75) Do not remove snap ring to remove pilot hood. NOTE: It is not necessary to remove the pilot tube for conver­sion.
20306761
CO141
Page 35
Pilot Assembly
Fig. 74 Pilot Assembly location.
• Remove pilot orice with Allen wrench. (Fig. 76)
• Install the conversion orice.
• Reinstall pilot hood. Be sure to align hood with in­dex tab.
Pilot Hood
ST935
Intrepid® Direct Vent - Rear Vent Gas Heater
Pilot Hood
Index Marks
Pilot Bracket
Fig. 77 Remove pilot hood. (Your pilot may have a different appearance.)
Fig. 78 Remove pilot orice.
CO105
Pilot
Orice
CO106b
Pilot Bracket
Fig. 75 Remove pilot hood.
Index Tab
Snap Ring
Fig. 76 Remove pilot orice.
Allen Wrench
CO105a
CO106a
Pilot type 2
• Loosen pilot hood turning counterclockwise using a 7/16" wrench. (Fig. 77) NOTE: You may use pene­trating oil to prevent pilot hood threads from seizing up.
• Remove pilot orice with needlenose pliers. (Fig.
78) NOTE: Use a wrench to hold pilot tube in place
while removing the orice.
• Install the conversion orice.
• Reinstall pilot hood and tighten until mark on pilot hood aligns with mark on pilot bracket.
Burner Orice Conversion
1. Remove three (3) 3/8" nuts on bottom side of burner pan. (Fig. 79)
2. Carefully remove ember bed by tilting the right side up and lifting out toward the right side of the unit. (Fig.
80)
Remove Nut
Bottom View
Remove Nuts
Fig. 79 Remove three (3) nuts securing ember bed in place.
ST918
3. Remove injector orice from left burner bracket with a
1/2" wrench.
4. Install conversion orice. (Refer to Table 3)
5. The air shutter is factory set according to table on page 8 and should not need adjustment. The air shut-
ter opening may be veried by measuring as shown
in Figure 81.
20306761
35
Page 36
Intrepid® Direct Vent - Rear Vent Gas Heater
Orice
Bracket
Pem Studs
Fig. 80 Tilt ember bed slightly to correctly place on venturi and air shutter.
Orice
Bracket
Orice
Air Shutter
ST919
All Models
1. Replace burner making sure venturi on bottom of em-
ber bed aligns with orice and is seated properly on
air shutter assembly. (Fig. 80) Make sure burner is slid into place at a slight angle and opposite to how it was removed. When burner is slid into place, the three (3) pem studs should slide down through clearance holes into the bottom of the control panel.
2. Thread and tighten 3/8" nuts back onto pem studs on underneath side of control panel, reversing Step 1 shown in Figure 79.
3. Reinstall logs as per instructions on page 29.
4. Place conversion label on valve.
5. Replace glass, stove front and safety barrier.
6. Restore gas to system and relight appliance according to Lighting Instructions on page 32.
7. Leak check the system using a gas leak detector solu­tion.
8. Relight the main burner in both the “HI” and “LO” posi­tions to verify proper burner ignition and operation.
Conversion is complete.
CO142
Fig. 81 The air shutter setting is 1/2” (13 mm) from the orice
bracket to the edge of the air shutter.
Table 3. Injector Orice Size Matrix
Conversion to LP
Input (BTU/h)
Kit # Orice Part # Minimum Maximum 20012921 #56 (.0465”) 30000336 12,000 16,000
Conversion to Natural Gas Input (BTU/h) Kit # Orice Part # Minimum Maximum
20012910 #47 (.0785”) 20003054 12,500 18,500
36
20306761
Page 37
Maintenance
DANGER
HOT GLASS WILL
CAUSE BURNS.
DO NOT TOUCH GLASS
UNTIL COOLED.
NEVER ALLOW CHILDREN
TO TOUCH GLASS.
A barrier designed to reduce the risk of burns from the hot
viewing glass is provided with this appliance and shall
be installed for the protection of children and
other at risk individuals.
20306543
Your Intrepid Gas Heater will provide years of service with minimal upkeep. The following procedures will help ensure
that your stove continues to function properly.
Annual System Inspection
Have the entire heater and venting system inspected an-
nually by a qualied gas technician. Replace any worn or
broken parts.
Logset and Burner
Cleaning and Inspection
Cleanliness is critical to the proper function of the heater. The logset and burner must all be kept free of dust and unobstructed by debris. Inspect these areas before each use and clean as necessary.
1. Turn the burner OFF and let the heater cool completely before cleaning.
2. Remove the safety barrier and lift the stove front up, then swing the bottom out to disengage it from the heater shell. (Fig. 82)
3. Carefully remove the glass and frame assembly and
place it out of the way on a at, padded surface such
as a counter protected by a towel.
4. Carefully inspect the Logs for damage. Contact your local dealer if any damage is evident. DO NOT OPER-
ATE THE HEATER WITH DAMAGED LOGS.
5. Use a soft bristled brush to sweep dust or debris from the Logs, Pilot and Burner. Use care as the logs are fragile and susceptible to damage.
6. Replace the glass panel and frame assembly.
7. Replace the Stove Front.
Intrepid® Direct Vent - Rear Vent Gas Heater
Cleaning the Glass
WARNING: Let the glass cool completely before attempting to clean.
It will be necessary to clean the glass periodically. During start-up, condensation, which is normal, forms on the in­side of the glass and causes lint, dust and other airborne particles to cling to the glass surface. Also initial paint
curing may deposit a slight lm on the glass. It is therefore
recommended that the glass be cleaned two or three times with a non-ammonia household cleaner and warm water
(we recommend gas replace glass cleaner). After that the
glass should be cleaned two or three times during each heating season depending on the circumstances present.
Clean glass after rst two weeks of operation.
Glass Replacement
Care of Cast Iron
An occasional dusting with a dry rag will help keep the painted surfaces looking new. Use high-temperature stove paints, available through your local dealer, to touch-up ar­eas as needed. Clean areas to be painted with a wire brush and be sure to cover the logs, burner and valve assembly, glass and frame assembly. Apply the paint sparingly; two light coats of paint will give better results than a single heavy coat.
Clean porcelain enamel surfaces with a soft, damp cloth. Do not use abrasive cleaning agents. If necessary, use only a cleaning agent formulated especially for use on porcelain
enamel surfaces.
20306761
CAUTION
TURN THE PILOT OFF BEFORE PAINTING. ALLOW THE HEATER TO COOL COMPLETELY BEFORE
PAINTING.
Replace glass only with Vermont Castings Group approved parts. Refer to page 41 for replacement parts. Refer to Figures 82 and 83 for removal of the damaged glass frame.
1. Remove the safety barrier by pulling gently on the
edges until the spring ngers release.
2. Open the swiveling latches (cams) on the top left and right corners of the glass frame. Figure 82
3. Position the glass and frame against the rebox
by placing the bottom edge on the brackets on the
bottom face of the rebox.
4. Swing the assembly against the rebox, and close the latches rmly against the pins protruding from the rebox top.
37
Page 38
Intrepid® Direct Vent - Rear Vent Gas Heater
Fig. 82 Remove the safety barrier and stove front.
Fig. 84 Wrap the gasket material around the outside edge of
the glass.
4. Apply a thin bead of high temperature silicone rubber sealant along the inside corner of the glass frame, all
around the perimeter. Place the at gasketed side of
the glass panel back into the steel frame. Pinch the rounded inside-facing gasket material to bulk it up.
5. Replace the glass frame and front panel as previously described.
Inspect the Vent System Annually
Have the vent system inspected annually by a qualied
technician. Shut off the main gas supply before inspect­ing the system. Both the inner exhaust pipe and the outer
combustion supply pipe must be checked to conrm that
they are unblocked and in good condition.
NOTE: Shown without top for clarity.
Fig. 83 Release the latches to release the glass frame.
Gasket Replacement
The Intrepid Gas Heater uses a ‘tadpole’ type gasket to seal between the glass panel and the frame. In time, this gasket can become brittle and compressed and should be replaced. New gasket is available from your dealer.
Shut off the gas supply and allow the stove to cool. Wear safety goggles and a dust mask.
1. Remove the Front, Glass Frame and Glass Panel. (Figs. 81, 82) Remove the old gasket. Use a razor blade to separate the glass and gasket from the frame, and to clean the glass of any remaining cement or bits of gasket. Use a cold chisel if necessary.
2. Determine the correct length of gasket by laying it out around the edge of the glass. Allow an extra 1 - 2” (25­50 mm). Mark the spot to be cut. Use a utility knife.
3. Starting on a long edge, remove about 6” of the pro-
tective paper strip and apply the at adhesive face of
the gasket around the outside-facing edge of the panel. Continue around the panel, applying about 6” at a time and being careful to not stretch the material. Do not overlap the gasket ends. (Fig. 84)
Check the Gas Flame Regularly
To ensure the stove is operating properly, check the ames periodically to conrm they match page 31, Figure 66. The ames will be blue during the rst 15-20 minutes of opera-
tion, and will gradually turn to yellow after that.
Do not use your stove if the ame pattern differs from that
shown here. Contact your Vermont Castings dealer or a
qualied technician for help.
Stove Disassembly
If there is eve r a n eed to remove the  reb ox as semb ly fr om the stove shell, support the rebox with solid stands about
6” (152 mm) tall under the left and right outer edges of the
rebox base. Do not set the rebox assembly directly on the oor; this can damage the control valve and/or the gas lines from the valve to the rebox.
Before removing the rebox from the shell, disconnect the
on/off switch wires from the valve. If the assembly includes the optional fan, disconnect the fan rheostat. If the installa­tion includes a wall thermostat, disconnect the thermostat leads from valve.
Disconnection and reconnection to the gas line should only
be done by a qualied gas service technician.
Upon reinstallation, the vent system must be sealed to the
rebox as discussed in the venting section. Also be sure the logs are placed in the rebox correctly, as shown on
page 29, Figures 58-61.
38
20306761
Page 39
FAN JUNCTION BO X
FAN
Strain Relief
Chassis Ground
B L K
GRN
GRN
WHT
ON / OFF Rheostat
Chassis Ground
Snapstat
BLK
B L K
BLK
BLK
B L K
WHT
RHEOSTAT / SNAPSTAT
BOX
POWER
CORD
MOTOR
Snapstat
ON/OFF RHEOSTAT
White
White
Black
White
Black
Green
Black
Power
On/Off Switch
OFF
ON
Thermopile
Black
Black
Millivolt
Gas Valve
TP/TH
TP
TH
Thermostat
(Optional)
Thermopile
Black
Black
TP/TH
TP
TH
Wiring
Optional Thermostat
Wiring
Intrepid® Direct Vent - Rear Vent Gas Heater
Wiring Diagrams
ST124b
Fig. 85 On/off switch and optional thermostat circuit.
NOTE: IF ANY OF THE ORIGINAL WIRE, AS SUP­PLIED WITH THE APPLIANCE, MUST BE RE­PLACED, IT MUST BE REPLACED WITH TYPE SF-2, 200°C WIRE OR ITS EQUIVALENT.
ST124c
ST153
Schematic Diagram
ST968
Fig. 86 Fan circuit.
20306761
39
Page 40
Intrepid® Direct Vent - Rear Vent Gas Heater
14
15
16
24a
26
27
25
28
30
29
24b
32a,b
38
10
39
3
12
40
7
8
21
23
1a
1b
1c
1
2
31a,b
36
17
35
4
5
6
33
9
37
CEMENT
42
11
13
18
19
20
22
41
1d
44
45
46
47
49
Vermont Castings Group reserves the right to make changes in design, materials, specications, prices and discontinue colors and products at any
time, without notice.
Intrepid Direct Vent/Rear Vent Gas Heater
Model: INDVR
Ref. Description Intrepid
1. Log Set - Complete 20012552 1a. Log Rear 20013111 1b. Log Right 20012549 1c. Log Left 20013112 1d. Log Top 20013113
2. Ember Bed Assembly 20012906
3. Top Refer to Enamel Parts Chart
4. Front, Operable Door Refer to Enamel Parts Chart
40
20306761
Page 41
Intrepid® Direct Vent - Rear Vent Gas Heater
Intrepid Direct Vent/Rear Vent Gas Heater (continued):
Model: INDVR
Ref. Description Intrepid
5. Door Right Refer to Enamel Parts Chart
6. Door Left Refer to Enamel Parts Chart
7. Left End Refer to Enamel Parts Chart
8. Right End Refer to Enamel Parts Chart
9. Leg Refer to Enamel Parts Chart
10. Door, Control 30003945
11. Hinge, Control Door 1601670
12. Rear Shroud Assembly 30004132
13. Clip, Rear Shroud 30004002
14. Glass Frame Assembly 30004068
15. Glass 30004067
16. Gasket, Glass - Med. Knit 1203702
17. Restrictor Plate 20013026
18. Heat Shield Top 30004128
19. Collar, Duravent 30004131
20. Starter 4” 30004130
21. FK20 Fan Subassembly
22. Fan Cover Shroud 30004014
23. Valve Nova SIT820.852 20012218 24a. Pilot Assembly 3Way N/DV RN 0.199.706 10002264
Pilot Assembly 3Way N/DV RP 0.199.703 10002265 24b. Pilot, PSE - NA175 20001115
Pilot, PSE - LP175 20001116
25. Pilot Top Convertible 10002266
26. Thermocouple 24” 7531137
27. Electrode Ignitor w/Cable SIT24 10001297
28. Thermopile 18” RS 7533113
29. Nut Electrode SIT #0.974.144 57886
30. Tubing Pilot w/Fittings 1/8 x 24” 10001296
31a. Pilot Orice #62 - NG Top Convertible 10002268 31b. Pilot Orice #35 - LP Top Convertible 10002269 32a. Orice Hood - LP (#56/.0465”) 30000336 32b. Orice Hood - Nat. (.0795”) 20013155
33. Ignitor Piezo w/Nut SIT 52464
34. Bracket Piezo Ignitor (not shown) 20010876
35. Manifold Assembly 20012918
36. Air Shutter Assembly 20012517
37. Wiring Harness 10002582
38. Trim ON/OFF Switch 30000874
39. Gasket, Control Plate 30004200
40. Gasket, HE Door 1203687
41. Gasket, Flue Collar 30004021
42. Gasket Cement 1206122
43. *Magnet, Door (not shown) 1408818
44. Knob Extension - Hi/Lo 55162
45. Knob Extension - On/Off 55163
46. Tie Bracket Assembly 20012514
47. Right Burner Support Assembly 20012909
48. Switch Housing 30005040
49. Safety Barrier 30007255
*Use common super glue or silicone to attach magnets.
20306761
41
Page 42
Intrepid® Direct Vent - Rear Vent Gas Heater
Intrepid Direct Vent/Rear Vent Gas Heater (continued):
Model: INDVR
Fuel Conversion Kits
Conversion Kit, NG to LP Kit #20012921 Conversion Kit, LP to NG Kit #20012910
Shell Enamel Part Numbers - Intrepid
Color Top Left End Right End Front Left Door Right Door Leg
Classic 30003930 30003934 30003935 30003931 30003932 30003933 1306333 Biscuit 30004239 30004237 30004238 30004240 30004241 30004242 30003182 Bordeaux 30006762 30006760 30006761 30006763 30006764 30006765 30006716 Brown Majolica 30004921 30004919 30004920 30004922 30004924 30004925 30004918
Optional Accessories
Fan Kits
FK20 Fan
The fan helps distribute heated air from within the rebox
out into the room. The fan is controlled by a snapstat that
turns power on and off as the rebox temperature rises
above and falls below a preset temperature. A rheostat provides for variable fan speeds.
Specications
115 Volt / 60Hz / .75 Amps
Maintenance
The fan itself does not require regular maintenance, how­ever, periodic cleaning of the fan and the surrounding area is required.
Installation
Refer to page 13 for installation instructions.
Remote Controls
The remote control allows you to turn the heater on or off from anywhere in the room. Refer to page 38 for wiring diagrams. These remote controls are for use on RN/RP model stoves.
Model Functions Controlled
RC1 ON/OFF RC2 ON/OFF and Temperature IMTFK Wall mounted thermostat control
Warming Shelf
Warming shelves add versatility to your stove; they can be used to keep foods warm at mealtime.
Model Color
0098 Classic Black 1373 Brown Majolica 1376 Biscuit 1380 Bordeaux The shelf installation is completed in three stages. First attach the shelf loosely to the stove, leaving the screws
loose enough to allow nal adjustments. Then, position the shelf and adjust the brackets so the shelf ts correctly.
Finally, tighten the screws.
Refer to the instructions included with each warming shelf for complete installation procedures.
42
20306761
Page 43
Intrepid® Direct Vent - Rear Vent Gas Heater
LIMITED LIFETIME WARRANTY
PRODUCT COVERED BY THIS WARRANTY All Vermont Castings brand gas stoves, gas inserts, and gas replaces installed in the United States of America or Canada.
LIMITED LIFETIME WARRANTY Vermont Castings Group warrants that all cast iron parts, the
combustion chamber, ceramic burner, and heat exchanger of every Vermont Castings gas product will be free of defective material or workmanship during the period the product is owned by the original owner subject to proof of purchase and the conditions and limitations listed on this warranty document.
BASIC ONE-YEAR WARRANTY Vermont Castings Group warrants to the original owner that your
new Vermont Castings Gas Appliance is free from defects in material or workmanship for a period of one year from the date of purchase, subject to the following conditions and limitations. Labor to replace these parts is covered for one year, reimbursed per our warranty service fee schedule.
COMPONENT WARRANTY LIMITATATIONS PORCELAIN ENAMEL FINISHED PARTS: Vermont Castings Group
offers no warranty on chipping of enamel surfaces. Inspect all products prior to accepting them for any damage to the enamel. The salt air environment of coastal areas or a high humidity
environment can be corrosive to the porcelain enamel nish.
These conditions can cause rusting of the cast iron beneath the
porcelain enamel nish, which will cause the nish to ake off.
Color lot variations with parts and/or accessories can occur and are not covered by warranty.
GLASS: Glass is not warranted for breakage due to misuse or accident.
Glass is not covered for discoloration or stains due to environmental issues, or improper cleaning and maintenance.
PLATED PARTS AND ACCESSORIES: Brass, nickel, and gold parts
should be cleaned with Lemon oil only. Commercial cleaners cannot be used. Mortar mix and masonry cleaners corrode the brass
nish. The Vermont Castings Group will not be responsible for,
nor will it warrant any brass parts which are damaged by external chemicals or down draft conditions.
ACCESSORIES: Unless otherwise noted, Vermont Castings Group
supplied accessories are covered for a period of one year.
GENERAL CONDITIONS AND LIMITATIONS
• This Vermont Castings product must be installed or serviced by
a qualied installer, preferably NFI or WETT (Canada) certied,
as prescribed by the local jurisdiction. It must be installed and operated at all times in accordance with the Installation and Operating instructions furnished with the product. Any alteration, willful abuse, accident, or misuse of the product shall nullify this warranty.
• This warranty is non-transferable, and is made to the original owner, provided that the purchase was made through an authorized supplier of Vermont Castings branded Vermont Castings Group products.
• Parts covered under the Limited Lifetime Warranty will be covered for the lifetime of the appliance up to a maximum of seven (7) years after Vermont Castings Group discontinues the model. The maximum amount recoverable under this warranty is limited to the purchase price of the product and, if Vermont Castings Group is unable to provide replacement or repair in an expedient and cost effective manner, Vermont Castings Group may discharge all obligations under this warranty by refunding the purchase price of the product.
• Any labor and related repair charges relating to the cost and expenses of replacing or repairing defective components under
the Limited Lifetime Warranty are not covered, except as provided for under the Basic One-Year Warranty.
• Any part or component replaced under the provisions of this warranty is covered for six months or the remainder of the original warranty, whichever is longest.
• Any installation, labor, construction, transportation, or other related costs/expenses arising from defective part(s), repair, replacement, or otherwise of same, will not be covered by this warranty, nor shall the Company assume responsibility for same. IN NO EVENT SHALL
Vermont Castings Group BE LIABLE FOR ANY INCIDENTAL
OR CONSEQUENTIAL DAMAGES CAUSED BY DEFECTS IN
THE PRODUCT except as provided by law
• SOME STATES DO NOT ALLOW FOR THE EXCLUSION OR LIMITATIONS OF INCIDENTAL AND CONSEQUENTIAL DAMAGES OR LIMITATIONS ON HOW LONG AN IMPLIED WARRANTY LASTS, SO THE ABOVE LIMITATIONS MAY NOT APPLY TO YOUR CIRCUMSTANCES. THIS WARRANTY GIVES YOU SPECIFIC RIGHTS AND YOU MAY HAVE OTHER RIGHTS WHICH VARY FROM STATE TO STATE.
• All other warranties expressed or implied with respect to the product, its components and accessories, or any obligations/liabilities on the part of the Company are hereby expressly excluded.
• The Company neither assumes, nor authorizes any third party to assume on its behalf, any other liabilities with respect to the sale of this Vermont Castings product
• The warranties as outlined within this document do not apply to chimney components or other non Vermont Castings Group accessories used in conjunction with the installation of this product.
• Damage to the unit while in transit is not covered by this warranty but is subject to claim against the common carrier. Contact the
dealer from whom you purchased your replace/stove (do not
operate the appliance as this might negate the ability to process the claim with the carrier).
• The Company will not be responsible for:
a) Down drafts or spillage caused by environmental conditions such
as near-by trees, buildings, roof tops, hills, or mountains.
b) Inadequate ventilation or negative air pressure caused by
mechanical systems such as furnaces, fans, clothes dryers, etc.
• This warranty is void if:
a) The replace has been operated in atmospheres contaminated
by chlorine, uorine, or other damaging chemicals.
b) The replace has been subjected to prolonged periods of dampness
or condensation
c) Any damages to the replace, combustion chamber, heat exchanger
or other components due to water, or weather damage, which is the result of but not limited to, improper chimney/venting installation.
d) Any alteration, willful abuse, accident, or misuse of the product
has occurred.
IF WARRANTY SERVICE IS NEEDED...
Contact your installing Vermont Castings dealer. Make sure
you have your warranty, your sales receipt, the model number and serial number of your Vermont Castings Group product. If you’re the installing dealer is unknown or unable to provide necessary parts or service, a list of Authorized Vermont Casting dealers can be located on the internet at www.vermontcastings. com
20306761
43
Page 44
Based on CSA P.4.1-09
Efciency Ratings
EnerGuide Ratings D.O.E Model Fireplace Efciency (%) (AFUE%)
INDVR 68.0 76.5
149 Cleveland Drive • Paris, Kentucky 40361
www.vermontcastingsgroup.com
Loading...