Vermont Castings BFC36 Homeowner's Installation And Operating Manual

Page 1
BFC
Balanced Flue (Closed Combustion) Heat-Circulating Fireplace
BFC36
Homeowner’s Installation and
Operating Manual
For use in the U.S. / Canada Underwriter’s Laboratories Report No. MH7603
DO NOT DISCARD THIS MANUAL: Retain for future use.
7412647 1/13 Rev. 21
Page 2
BFC36 Balanced Flue Heat-Circulating Fireplace
Table of Contents
Safety Information ......................................................................................3
Specications and Framing .......................................................................4
Parts Identication ....................................................................................5
Chimney Requirements ............................................................................6
Planning Information .................................................................................. 7
Installation .................................................................................................8
Replacement Parts ..................................................................................18
Accessories .............................................................................................20
Warranty...................................................................................................23
2
BFC36
Listed
UL127 / ULC-S610
Standard for Factory Built Fireplaces
7412647
Page 3
BFC36 Balanced Flue Heat-Circulating Fireplace
Safety Information
Please Read This Manual Before Installing and Using Fireplace
IMPORTANT: Read all instructions and warnings carefully before starting installation. Failure to follow these instructions
may result in a possible re hazard and will void the warranty.
Description
The BFC36 replace is a solid fuel, woodburning replace. The BFC36 is a balanced ue (closed combustion) heat­circulating replace which receives outside combustion air through the chimney system. This unique system results in much higher efciency since valuable room air is not used for combustion.
The BFC36 is a decorative replace which provides ef­cient supplemental heat compared to other wood burning replaces. It should not be used as a primary source of heat.
CAUTION: Overloading the rebox with wood may result in overring and damage to refractory components, the grate and doors.
Any such action may possibly cause a re hazard.
Consult local building codes to ensure that you are in compliance before installing the replace.
This replace and chimney system must be vented to the out-of-doors.
Do not obstruct or modify air inlets/outlets in any manner.
Do not install combustible materials on any of the black replace surround.
Burn only solid wood fuel or gas logs. The BFC36 is intended for operation only with the
doors closed. Do not install a solid fuel burning insert or other prod-
ucts not specied for use with this replace.
Precautions
Vermont Castings Group replaces and component parts have been thoroughly tested and will operate safely when installed in accordance with instructions provided in this manual. Carefully read and understand all instructions before beginning installation.
If you notice any damage to replace or component parts, immediately report damage to your Vermont Castings Group dealer.
Only use Vermont Castings Group components or the war­ranty will be voided and a re hazard may be created.
Vermont Castings Group warranty will be voided by and Vermont Castings Group disclaims any responsibility for the following actions:
Installation by any other than a qualied installer,
preferably NFI or WETT (Canada) certied.
Installation of any damaged replace or chimney
component;
Modication of replace, chimney assembly or
any component parts thereof; (except for chase ashings as detailed in Vermont Castings Group Chimney Top installation instructions).
Installation other than as instructed by Vermont
Castings Group; or
Installation and/or use of any component part
not manufactured or approved by Vermont Cast­ings Group in combination or assembly with a Vermont Castings Group replace system, not­withstanding any independent testing laboratory or other third party approval of such component parts or accessory.
Proposition 65 Warning: Fuels used in gas, wood-
burning or oil red appliances, and the products of combustion of such fuels, contain chemicals known to the State of California to cause cancer, birth defects and other reproductive harm.
California Health & Safety Code Sec. 25249.6
WARNING: Check with your electronics manufacturer before installing a television or other electronic de­vice above this replace.
Drafts
The replace should not be located in areas that create drafts (ie: frequently opened doors and central heating air inlets/outlets) that hamper the normal ow of air into
the re.
Gas Logs
If you plan to install a gas log, the gas line should be in­stalled before framing the replace. The gas line must be installed by a certied gas line installer.
7412647
3
Page 4
BFC36 Balanced Flue Heat-Circulating Fireplace
6
" (16mm)
56O" (13mm)
56O"
326"
(829mm)
41(6" (1064mm)
6"
(16mm)
56QE"
(49mm)
" (914mm)
"
(533mm)
56QE" (176mm)
56QE" (179mm)
Recessed Nailing Flange
1356O" Dia. (343mm)
Rough Opening Width 43"
Rough Opening Height
Rough Opening Depth
Gas Line Access
5156QE" (1297mm)
5156QE"
(1297mm)

6QE
" (1834mm)
6M"
(197mm)
23"
(584mm)
"
(610mm)
6QE"
(624mm)
3956M"
(997mm)
556QE"
(246mm)
35"
(889mm)
"
(279mm)
Gas Line Access
56O"
(902mm)
36"
(914mm)
(1092mm)
11" Dia. (179mm) 8" Dia. (203mm)
56
" (918mm)
A
B
C
BFC36 Balanced Flue Heat-Circulating Fireplace
Fig. 1 BFC36 specications and framing.
Fig. 1a Hearth dimensions.
Front Width Back Width Depth A B C
BFC36 32Z\x" 20M\zn" 17C\v" (826 mm) (519 mm) (451 mm)
FP1531
4
7412647
Page 5
Batt Insulation (Cut out around restop)
Firestop
Ceiling Level
BFC36 Balanced Flue Heat-Circulating Fireplace
Termination Cap
Storm Collar
Pan Flashing
Draftstop
Gas Line Ac­cess Hole (Each Side)
Top Grille and Air Outlet
Standoff
Trim Ledge Standoff
Surround
Glass Door
Romex Pigtail
Gas Line Access Knock­out (Each Side)
Air Inlet
Basket Grate
Bottom Grille
Metal Safety Strip(s) Shown not inplace (1,2 or 3 pieces)
Nailing Flange
Fig. 2 Fireplace and chase parts identication.
7412647
FP554c
5
Page 6
BFC36 Balanced Flue Heat-Circulating Fireplace
D
Rise
B
G
H
B
Offset
C
E
6 FT.
G
H
A
Hearth Floor
Chimney Section
CHIMNEY FLUE EXIT
Elbow
TCS8A Support
Example 1 Example 2 Example 3
Offset
Rise
Chimney Requirements - Offset Installations
Notes: G + H cannot exceed 20 feet.
Air Space Clearances: = 2” Min. to Combustibles
Illustration Key
The following safety rules apply to offset installations (letters correspond with illustration above):
A. Height of the chimney is measured from the hearth to the chimney exit.
BFC36 Maximum: 50’0” Minimum: Without Elbows 14’6” With 2 Elbows* 14’6” With 4 Elbows* 21’0”
B. Do not use more than 4 elbows per chimney.
Attach the straps of the return (top) elbow to a structural framing member.
The offset (rst) elbow of any pair does not have straps.
Offset
IWF282
Rise
30°
Return
Elbow
30° Offset Elbow
30°
Return
Elbow
30°
Offset
Elbow
FP269
C. The chimney cannot be more than 30˚ (45˚ in Canada) from the vertical plane in any installation*.
D. The maximum length of the angled run of the total chimney system is 20 feet. (G plus H cannot exceed 20 feet.)
E. A chimney support (Model TCS8A) is required every 6 feet of angled run of chimney. Chimney supports are required for every 30 feet and 60 feet of vertical chimney height above the hearth.
Determine the offset distance of your chimney arrangement from the centerline of the replace to the centerline of the chimney where it is to pass through the rst ceiling.
NOTE: This offset distance may not be your full offset distance. See Examples 2 and 3.
30˚ Elbow Offsets
1’
0 0 0 0 0 3” 11” 1 0 0 0 0 8Z\v" 20" 0 1 0 0 0 11Z\v" 25Z\v" 2 0 0 0 0 13Z\x" 29Z\v" 1 1 0 0 0 16Z\x" 34Z\v" 0 0 1 0 0 20Z\v" 40C\v" 2 1 0 0 0 21C\v" 43Z\x" 0 0 0 1 0 26Z\v" 51Z\v" 0 1 1 0 0 28Z\x" 55Z\v" 1 0 0 1 0 31Z\x" 60Z\v” 0 1 0 1 0 34Z\x" 65Z\x" 0 0 2 0 0 37Z\x" 70C\v" 1 1 0 1 1 41Z\x" 77C\v" 0 0 1 1 1 45" 83C\v" 0 1 2 0 1 47Z\v" 87Z\x" 0 0 0 2 1 51" 94" 0 1 1 1 1 53Z\v" 98" 0 0 3 0 1 56Z\v" 103Z\v" 0 1 0 2 1 59Z\v" 108Z\x" 0 0 2 1 1 62Z\v" 113Z\x" 0 1 3 0 1 64Z\x" 117Z\x" 0 0 1 2 1 68Z\v" 124" 0 1 2 1 1 70Z\x" 128" 0 0 0 3 1 74Z\v" 134Z\x" 0 1 1 2 2 78" 140C\v" 0 0 3 1 2 81" 146" 0 1 0 3 2 84" 151Z\v" 0 0 2 2 2 87" 156Z\x" 0 1 3 1 2 89Z\v" 160Z\v" 0 0 1 3 2 93" 166C\v" 0 1 2 2 2 95Z\v" 170C\v" 0 0 0 4 2 99Z\v" 177C\v" 0 1 1 3 2 101Z\v" 181C\v" 0 0 3 2 2 104Z\v" 186Z\v" 0 1 0 4 2 107Z\v" 191Z\x" 0 0 2 3 2 110Z\v" 196C\v" 0 1 3 2 3 114" 203Z\v" 0 0 1 4 3 117C\v" 209C\v" 0 1 2 3 3 120" 213Z\x" 0 0 0 5 3 123C\v" 220"
1¹⁄₂'
3’ 4’
Chimney
Support
Fig. 3 Chimney system requirements.
6
7412647
Page 7
BFC36 Balanced Flue Heat-Circulating Fireplace
L
1
L
1
L
T
TOTAL
LENGTH
(LT)
INSTALLED
LENGTH
(L1)
56O
"
56O
"
56O
"
56O
"
56O
"
56O
"
56O
"
56O
"
TRIPLE
WALL
81 818 83 84
2' Min.
2' Min.
3'
Min.
0 To 10'
3'
Min.
0 To 10'
Reference Point
Planning Information
Preplanning an installation is very important to ensure safety and to save time and money. An installer must predetermine where a replace will be set and how the chimney system will be run.
Mounting the Fireplace
A replace may only be mounted on the following sur­faces:
1. A at combustible surface.
2. A raised wooden platform.
3. A concrete block or other solid object placed beneath each of the four (4) corners of the replace.
The replace must be spaced 1” (25 mm) from a combus- tible back wall and 1/2” (13 mm) from a combustible side wall or support. (Page 13, Fig. 17)
Planning the Chimney Run
Determine how the chimney will be run, length of run and chimney components required to complete the job. (Fig. 4)
Never install a chimney below minimum heights.
The Ten Foot Rule
Major U.S. building codes specify a minimum chimney height above the roof top. The “Ten Foot Rule” is a re safety rule and not a draft rule. To ensure proper draft, it is recommended that you always meet or exceed the “Ten Foot Rule,” especially when installing a termination on a high pitch roof. (Fig. 5)
The key points of the “Ten Foot Rule” are:
1. If the horizontal distance from the chimney to the peak of the roof is 10’ (3m) or less, the top of the chimney must be at least 2’ (610mm) above the peak of the roof, but never less than 3’ (914mm) in height above the highest point where it passes through the roof.
2. If a horizontal distance from the chimney to the peak of the roof is more than 10’ (3 m), a chimney height refer­ence point is established on the surface of the roof a distance of 10’ (3m) from the chimney in a horizontal plane. The top of the chimney must be at least 2’ (610 mm) above the reference point, but never less than 3’ (914 mm) in height above the highest point where it passes through the roof.
Fig. 4 Installed lengths of chimney sections.
In planning a chimney system, it is important to know:
1. The height of a chimney is measured from the hearth to the exit point on the termination.
2. A chimney cannot be offset more than 30° from a vertical plane.
3. A chimney may run straight up or it may be necessary to offset it to avoid obstructions.
4. The maximum length of an angled run (total chimney system) is 20’ (6 m).
5. No more than 2 offsets (4 total 30° elbows in U.S./or 2 total 45° elbows in Canada) per replace may be used.
6. A guy wire stabilizer is required for chimneys extending more than 6’ (1.8 m) above a roof line.
7412647
FP288a
AC246
Fig. 5 Ten Foot Rule illustration.
Chimney Supports
The chimney system is supported by the replace for verti­cal chimney heights less than 30’ (9m) above the hearth. Chimney supports are required if the vertical height ex­ceeds 30’ (9m). Locate chimney supports at ceiling holes or other structural framing at 30’ (9m) heights. Spacing between chimney supports must not exceed 30’ (9m). Use Chimney Support Model TCS8A. (NOTE: The TCS8A cannot be mounted directly to the replace.) Support provided by elbow straps fullls the support requirement only if they are spaced as previously described. (A chimney support is 2Z\x" (64mm) long when installed.)
Angled chimney runs require a support every 6’ 1.8m) in addition to the elbow straps. Chimney supports are used for this function. (Fig. 6)
7
Page 8
BFC36 Balanced Flue Heat-Circulating Fireplace
Chimney Sup­port Strap
Chase Installation
A chase is a vertical box-like structure which encloses the replace and/or chimney. Chases are typically built on the outside of the house with replace opening cut into the outer wall of a room. (Page 4, Fig. 2)
If you need help in determining replace location or how the chimney system should be run, contact your Vermont Castings Group dealer for assistance.
TCS8A
Fig. 6 Chimney support installation.
FP284a
Installation
Insulating Fireplace Enclosure
for Cold Climates
If you live in a cold climate, it is not required but highly recommended that you insulate replace enclosure to
eliminate cold air penetration as much as possible.
Insulate base of replace with a noncombustible insula­tion rated for a minimum of 300°F. Insulating is very important for outside wall installations over a concrete slab. If replace is installed on a platform, insulation should be placed on top of the platform before replace is set. (Fig. 7)
When a replace is installed in a chase or on a outside wall, enclosure should be treated like any outside wall in a home. Insulation should be installed on the inside wall as well as the outside wall(s). In a chase, it is also a good idea to install a restop at the rst ceiling level above the replace and enclose the chase with sheeting material. Insulation may then be installed above sheet­ing material to assure the space around the replace is totally protected. (Fig. 2)
When installing the chimney, DO NOT caulk between outer pipe and restop. It is vital that some air be allowed to ow through this very thin gap.
CAUTION: When installing a replace in an insu­lated enclosure, be sure all required air spaces are maintained. (Page 13, Fig. 17)
Hard Flat Surface
Insulation
Platform
FPC555a
Fig. 7 Insulating between platform and replace.
Framing
Framing can be constructed before or after the replace is set in place, however, most installers build the frame before setting the replace.
Frame replace with 2 x 4 lumber or heavier materials. Refer to framing dimensions in Figure 1 for basic replace specications.
NOTE: Framing should be positioned to accommodate wall covering and replace facing material.
8
7412647
Page 9
BFC36 Balanced Flue Heat-Circulating Fireplace
86M"
(222mm)
Electrical Wire Installation
The fan requires 120V AC, 60 Hz power which may be connected from the right side of the replace. This power connection must be completed before the replace is se­cured and nish material applied.
NOTE: Refer to instruction sheet for Model SCVS Variable Speed Fan control for speed control wiring schematic.
The lower cavity of the replace may be accessed by removing the lower grille. Lift grille and pull lower side out to remove.
1. If using romex type power supply wiring, install a strain relief tting into the small access hole in the lower right side of the replace outer wrapper.
2. Route house power wires into the replace through the tting.
3. Extend these wires through large front hole of right side oor support.
4. Using supplied junction box assembly, connect and secure house romex wiring to duplex outlet. Ensure correct polarity and that the ground wire is securely connected.
5. Secure romex wiring using supplied strain relief tting at rear of junction box. Re-assemble junction box.
6. Secure romex wiring at strain relief tting in replace outer wrapper.
7. Mount junction box mounting plate to inside face of right side oor support using two self-tapping sheet metal screws.
8. Plug blower cord into duplex outlet.
9. Replace lower grille.
Chimney Set-up
Since you have already preplanned the chimney run, you should know exactly how the installation is to be ac­complished — how much pipe is required, the number of elbows, if any, and type of termination to be used.
CAUTION: REPORT TO YOUR DEALERS ANY PARTS DAMAGED IN SHIPMENT, SPECIFICALLY CHECK THE END CONNECTION OF CHIMNEY SECTIONS AND ELBOWS.
NOTE: The BFC36 replace must use Vermont Castings Group Model triple wall 8” chimney components only. The installation procedure described in this manual applies only to this system.
Straight-Up Chimney Installation
To mark the centerline of the ue, put the replace in nal position and measure out from the wall: 8C\v" (222 mm). Mark a spot on the ceiling directly above the replace. Draw a line parallel to the back wall through this mark. (Fig. 8)
Using a plumb bob positioned directly over center point of replace ue collar, mark the ceiling to establish the chimney center point. (Fig. 8)
Chimney Centerline
Actual Center­point
Plumb Line
Plumb Bob
Imaginary Center­point
FPC556a
Fig. 8 Locate centerline of chimney with plumb line.
Offset Installation
In order to clear an obstruction, it may be necessary to offset chimney from vertical. This is accomplished by us­ing elbows. Use the 30° Offset Elbow table on Page 5 to determine proper offset and parts required.
Each offset requires two (2) elbows. The second elbow is equipped with support straps. It is very important to install the second elbow in each offset as close to the ceiling or support as possible so that the elbow straps can be secured to framing members to help support the weight of the chimney.
Determine offset distance of your chimney arrangement from centerline of replace to centerline of chimney where it is to pass through ceiling.
Locate center point of the chimney on ceiling as though a straight up chimney arrangement is to be used. Measure your offset dimension from straight up chimney center point on ceiling.
7412647
9
Page 10
BFC36 Balanced Flue Heat-Circulating Fireplace
Ceiling Chimney Hole/
Possible Obstructions
The size of the hole in ceiling will vary with the angle at which the chimney passes through ceiling.
Drive a nail up through ceiling at marked chimney center point. Go to oor above and see where hole will be cut. Check to see where existing ceiling joists and other pos­sible obstructions are located...i.e. wiring, plumbing etc... If necessary, re-position chimney and/or replace to avoid obstructions.
Cutting the Hole
Cover replace collar opening and cut proper sized chim­ney hole in chimney.
Framing the Ceiling Hole
Frame the ceiling chimney hole as shown in Figure 9. It is good practice to use framing lumber that is the same size as the ceiling joists; this is a requirement at attic level.
Existing Ceiling Joists
17Z\x
(445mm)
17Z\x
(445mm)
Chimney Hole
Positioning, Safety Strips,
Securing the Fireplace
Slide replace into position.
Lift the replace front slightly and slide the metal safety strips under front bottom edge about 1Z\x” (38 mm), allowing the remainder to extend in front of rebox. Overlap strips at least 1/2” (13 mm) to provide a positive joint. (Flat safety strips are packed with replace.) (Fig. 11)
Metal Safety Strips (1,2 or 3 pcs.)
“Z” Safety Strip (not sup­plied)
Hearth Ext.
FP557b
1Z\x
(38mm)
Z\x” (13mm)
Min. Overlap
Fire­place
Plat­form
New Framing Members
Fig. 9 Typical frame for ceiling chimney hole.
Ceiling
FP551b
The following table gives restop spacer model num­bers:
Chimney Hole Size
Angle of Chimney at Ceiling Size of Chimney Vertical 30° FS2A FS6A 8” Flue 17Z\x” x 17Z\x 17M\₈” x 29⁵\₈ (445 x 445mm) (454 x 753mm)
Fig. 10 Ceiling chimney hole sizes necessary for installing restop spacer.
The inside dimension of the frame must be the same as the hole size selected from Figure 10 in order to provide required the 2” (51 mm) air space between the outside diameter of the chimney and the edges of the framed
ceiling hole.
Fig. 11 Safety strip installation.
Safety strips are used to ensure that any combustible ma­terials in front of the replace are protected even though a non-combustible hearth extension is required.
If replace is to be elevated above the oor, a “Z” shaped metal safety strip must be fabricated and used to protect combustible surfaces in front of the replace. This “Z” shaped safety strip is not provided but must be fabricated of metal with each horizontal leg at least 1Z\x” (38mm) wide and equal in length to the metals strips provided with the replace.
NOTE: Safety strips are not required over non-combustible oors where all supports at the base of the replace are noncombustible.
Four (4) nailing anges are supplied with the replace (found on the replace hearth). To level the box and se­cure it rmly in place, remove the nailing anges from the hearth and install at the sides of the replace as shown in Figure 12.
10
7412647
Page 11
BFC36 Balanced Flue Heat-Circulating Fireplace
UP
Nail Top Standoffs
Nail Side­Nailing Flanges
FPC549a
Fig. 12 Fasten replace in position.
Installing the
Chimney System
Start by attaching the rst chimney section to the collar on top of the replace.
Install the pipe as pictured in Figure 13. When you get a good lock, you will hear the pipe clearly snap together. Once sections are snap-locked in place, it is extremely difcult to get them apart. Make sure the pipe is rmly
snapped and locked together as each pipe section is mounted.
Pipe Section
Pipe Rim
Hem
Lance
Pipe Hem
Elbow Strap
Angled Strap
FP270/271
Fig. 14 Attach straps to a structural framing member.
Support Structure
Elbow Strap (must be tight)
Ceiling Hole Framing
Angled Firestop
Chimney Support Strap (must be tight)
Installing the Firestop Spacer
in the Ceiling Hole
A restop spacer is used to keep pipe spaced properly and required for safety.
Nail the restop spacer (at each corner) to the framing members of the ceiling hole. NOTE: A restop spacer is not required at the roof.
Hole sizes listed in Figure 10 for angled restop spacers provide minimum required air space to chimney pipe for ceiling thickness up to 8” (203 mm). When combined thickness of ceiling material, ceiling joists and ooring material exceeds 8” (203 mm), adjustments must be made in framing to assure that minimum air spaces to chimney are maintained.
Proper Firestop Spacer Installation
Fig. 13 Install pipe, listening for the snap-lock to fasten.
When installing elbows, only outer pipe will snap- lock. Middle pipes simply slide into position. Be sure to always attach straps on upper elbow to a structural framing mem­ber. (Fig. 14)
Continue installing the pipe as required until pipe is installed up through the ceiling. At this point, you must install a restop spacer.
7412647
FPC558a
Figure 15 shows different installation procedures for both an area that is an attic and an area that is not an attic.
If the area above the ceiling is not an attic, position the restop spacer with the ange on the ceiling side and the angled portion extending up into the hole.
If the area above the ceiling is an attic, position the restop spacer with the ange on the top of the framed hole and the angled portion extending down into the hole.
Firestop spacers are not available for, nor are they required on vertical walls.
DO NOT put any sealant around the area where the outer pipe slides through the restop spacer. If you seal this area, it may cause a re hazard.
11
Page 12
BFC36 Balanced Flue Heat-Circulating Fireplace
Attic Installation
Nails (4)
Ceiling Installation
Firestop
Spacer
Joist
NOTE: If the attic insulation shield is used, the restop is not required in the attic installation.
Fig. 15 Installing restop spacer.
Canadian Requirements
for Insulation Shield
In Canada, an attic insulation shield is required to pre­vent attic insulation from contacting the chimney section. NOTE: If the attic insulation shield is used, the restop is not required in the attic installation. Framing dimensions for the chimney hole should measure 17Z\x” x 17Z\x” (445 x 445 mm). An attic shield MUST be installed on top of attic joists (above the oor level). (Fig. 16)
Attic Insula­tion Shield
Nails (4 required)
Joist
Firestop
Spacer
Nails (4)
FP593
Continue Installing
Pipe to Complete Run
Continue attaching pipe sections to complete system to next level always being careful that the pipe is rmly snap­locked in place before proceeding to next pipe section.
Chimney Supports
If chimney supports are required, they are installed the same as elbows. Nail chimney support straps to adjacent structural framing, as shown on Page 8, Figure 8. Bend straps as necessary and make sure they are secure so they will support the weight of the chimney. A chimney support is 2Z\x" (64 mm) long when installed. Consider this dimension when determining how many straight chimney sections are needed.
NOTE: Chimney supports are generally used in long runs in a chase installation.
Attic Joist
Base Flanges
Ceiling
FP263
Fig. 16 Attic shield installation (Canadian requirement).
NOTE: In the U.S., it is a good idea, although not always
required, to install an attic insulation shield where blown-in insulation is planned to be used in the attic.
Install the attic insulation shield with the anges on its base extending down into the framing hole. Nail each corner of attic insulation shield to the framing members of the ceiling hole using 8d nails. Attic shields are not required at the roof.
12
Additional Ceilings
If you encounter additional ceilings, repeat same steps required for rst ceiling installation. See restop illustration in Page 11, Figure 15.
Penetrating the Roof
Run pipe to rooine. Since chimney system must be vented to the out-of-doors, you must use an approved Vermont Castings Group termination.
If a chase is used, refer to the installation manual provided with the termination cap.
Locate Chimney Centerpoint On Roof
Use same procedure detailed in locating center point of the ue system.
Drive a nail up through roof at the center point. This will determine center point on outside of the roof.
Cut and Frame Roof Hole
Size of roof hole varies with the type of chimney termina­tion installed. Refer to installation instructions provided
7412647
Page 13
BFC36 Balanced Flue Heat-Circulating Fireplace
FRONT VIEW
SIDE VIEW
Air Space Clearances
with Vermont Castings Group chimney termination to nd correct size of roof hole.
There must be a 1Z\x” (38 mm) air space between outermost portion of chimney sections and any adjacent combustible surfaces. (Combustible surfaces include burnable materi­als such as: ceiling members, joists, ooring, combustible insulation and roof structures.)
WARNING: Do not pack required air spaces with in­sulation or other materials.
Mark an outline of the roof hole around the center of the point nail. NOTE: Hole dimensions given in the chimney top installation instructions are horizontal dimensions; therefore, the hole size must be marked on the roof ac­cordingly.
Cover the opening of the installed chimney so debris can­not get into the system.
Cut and frame the hole. It is good practice to use framing lumber that is the same size as the rafters. Install the frame securely because the chimney top and ashing anchored to the frame must be able to withstand heavy winds.
Install Remainder of Chimney Sections
Since you have already preplanned the height of your termination according to the Ten Foot Rule, continue to install pipe to the predetermined height.
Check the chimney top installation instructions for details on how high above the roof top the chimney sections (all pipes) should extend.
Finish Wall
Finish the wall with material of your choice. Do not install a combustible mantel shelf less than 12” (305 mm) above the grille opening. Do not install a mantel face plate less than 6” (159 mm) from top of grille opening. (Fig. 20)
If a combustible material is used below a at mantel shelf, consult your local building codes for minimum clearance from top of replace opening to bottom of mantel shelf.
All joints (top, bottom and sides) where wall or decorative facing material meets replace surround must be com­pletely sealed with a noncombustible material. (Figures 18 and 19)
NOTE: No side wall protection is required for replaces installed at 45° to two (2) side walls (corner installation).
Combustible framing material MUST NOT penetrate AIR SPACE (shaded areas).
2”
Standoff
Z\x” air space to
sides
Installing Top Housing
or Termination
Follow the installation instructions provided with the Vermont Castings Group chimney termination you have selected.
Installing Chimney in a Chase
Refer to Page 4, Figure 2 for an illustration of a typical chase installation.
CAUTION: Treatment of restop spacers and construction of chase may vary with type of building. These instructions are not a substitute for local building codes. You must check your local building codes to determine specic re­quirements for your city or state. NOTE: Other building materials may be required in addition to restop spacers.
Finishing
CAUTION: All joints between the nished wall and the
replace surround (top/sides) must be sealed with non­combustible material to prevent cold air leakage into the room. Only noncombustible material may be applied to the facing of the replace surround. (Black painted area) (Fig. 17)
Wall Shield
Only noncom­bustible material may be applied as facing to the black replace surround.
Fig. 17 Minimum clearances to combustibles.
Hearth Extension
Firestop
1” Air Space to Back
Z\x” Air Space to Sides
0” Clearance to Floor
FPC559a
7412647
13
Page 14
BFC36 Balanced Flue Heat-Circulating Fireplace
1Z\x" Ref.
B
C
Combustible materials are permitted within a shaded area shown in Figure 21 titled Minimum Wall Clearances.
*
* *
Z\x"
12"
(305mm)
Max.
12" (305mm)
Min.
1Z\x"
(38mm)
6"
(159mm)
Min.
Combustible Mantel Shelf and Trim
Side View
2 x 4 Stud
Finished Wall
Finished Wall
Stud
Standoff
Noncombustible Material
Circulating Front
Fireplace Opening
Fireplace Front
Must be sealed with noncom­bustible material
Fig. 18 Mantel clearance.
* 12” from top of grille opening.
** 6” from top of grille opening.
FP531b
Face Plate
Fig. 19 Combustible mantel clearances.
14
MA81
7412647
Page 15
BFC36 Balanced Flue Heat-Circulating Fireplace
Minimum Wall Clearances
WITH Noncombustible Surround Facing
WITHOUT Noncombustible Surround Facing
Minimum Hearth Extension Dimensions
(for On-Site Construction)
G
H
G
J
Seal cracks between the fireplace and hearth extension with noncombustible material
Safety strips must overlap 56O" minimum
May install noncombustible decorative covering OR .018" min. sheet metal
Fireplace Hearth
Combustible Floor
1/2” Min. EH2416 or equal “R” value
4" MIN.
Firebox
Opening
A - Min. clearance to combustible perpendicular wall
B - Min. clearance to combustible perpendicular wall when using noncombustible wall shield*
Side Wall
Side Wall
F**
C**
E
E
D
4" Brick (Example material)
Combustible material permitted within shaded area.
*
Noncombustible wall shield requires 1" EH2416 insulation (minimum R Value = 1.85) between decorative noncombustible rigid covering and combustible wall. Minimum height and width is 40" x 40".
**
Dimension/degree of angle will vary depending on thickness
of noncombustible surround facing.
Shaded area starts 1/2" from away from edge of unit
4"
Side Wall Protection
Adjacent combustible side walls that are within minimum dimensions shown in Figure 23 of the replace opening must be protected with a specically built wall shield as described in Figure 17.
The special wall shield design described in Figure 18 is an alternate method of adding protection to side walls. Rt must =1.09 minimum.
Examples of wall shield insulation:
1. Manville - CERAFORM 126, K=.27, 1/2 inches thick
2. EH2416, K = .458, 1 inch thick required.
Hearth Installation
A hearth extension is required to protect a combustible oor in front of the replace. Refer to Figure 20 for minimum dimensions and mounting detail.
Note: Hearth Extension must not cover the air inlet opening of a replace.
The hearth extension described in Figure 20 must be a durable non-combustible material with a minimum (total) Rt value of 1.09; refer to Figure 21 for examples. The overall height (above a combustible oor), depth and width must be as indicated, with the extension centered to the replace opening.
The top of insulation must be covered with a non-combus­tible decorative covering or a piece of .018” minimum sheet
metal, to protect hearth extension material. (Fig. 20)
Secure the hearth extension to the oor to prevent shift­ing, using trim molding or other similar means at three (3) outer edges. Seal crack between the replace hearth and hearth extension with a non-combustible material. (Figs.
20 and 22)
WARNING: Hearth extension must be installed in ac-
Fig. 20 Combustible side wall protection and hearth extension dimensions.
7412647
A B C D E F G H J
BFC36 26” 12” 17° 25° 12” 8” 8” 18” 47Z\v 660 mm 305 mm 305 mm 203 mm 203 mm 457 mm 1200 mm
FP594b
15
Page 16
BFC36 Balanced Flue Heat-Circulating Fireplace
COMMON MATERIALS AND FACTORS
MATERIAL K*
R
MINIMUM
THICKNESS
EH2416 Micor 300
Common Brick
0.458
5.0
1.09 0.50 in.**
0.10 5.46 in.**
R Value is for 1/2 inch. * Units of K = BTU/SQ FT/HR/˚F/IN ** Thickness of Listed Material
cordance with Figure 22 and must not cover the bottom front opening of the circulating model.
Alternate noncombustible materials may be used providing the (total) thermal resistance (Rt value) of the alternate material employed is greater than or equal to R = 1.09 Thermal resistance (R) or thermal conductivity (K), may be obtained from manufacturer of the material. Factors are related by the formula K = 1/R. (Fig. 21)
T = given thickness R = thermal resistance for a given thickness (T) K = thermal conductivity
Noncombustible material with a lower R value may be used, provided thickness of material is sufciently greater
to maintain an equivalent (total) thermal resistance (Rt).
Wall Covering
Noncombustible Decorative Fac­ing
Seal all cracks between replace surround and wall ma­terials with noncom­bustible material.
Noncombus­tible Decorative Covering
Hearth Exten­sion Insulation
FP550
Fig. 22 Sealing gaps.
Side View
2 x 4” Header
- Do not notch at standoffs
Seal crack between replace and hearth extension with noncom­bustible material
Safety Strips ­Must be overlapped 1/2” minimum
Fig. 21 Hearth extension material factors.
Example of Determining Hearth Extension Equiva­lents
To determine the thickness required for any new mate­rial:
NEW K of new material (per inch) thickness required = --------------------------------------- X of listed
thickness K of listed material (per inch) material
Example for Common Brick
T (new) = 5.0/0.458 x 0.50 in. = 5.46 in. (new required
thickness).
16
FP533ADD
Glass Door Operation
The BFC36 is intended for use only with the doors fully closed. (Fig. 23)
Correct Wrong
Fig. 23 Correct door position.
KT108b
7412647
Page 17
BFC36 Balanced Flue Heat-Circulating Fireplace
1"
Min.
1/2"
Operation
Before the rst re, the location of the upper refractory bafe (ceiling panel) should be checked. This part oats intentionally and may move out of place during shipping or installation of the replace. If the bafe is out of place, the resulting improper air ow will cause dirty glass and improper combustion. The bafe should be centered side­to-side between the refractory sidewalls and be pulled for­ward (toward the glass doors) until it rests on the front sheet metal ledge.
Refer to the publication “How to Enjoy Your Woodburning Fireplace” for starting and maintaining a wood re.
Note that the BFC36 does not have a damper to open or close. This is a tremendous efciency increasing advan­tage since there is no damper to potentially leave open after a re dies down. House air will not escape up the chimney. Note also that the doors should remain closed at all times except when starting or reloading a re.
Burn only seasoned rewood. Typically, only two or three burning logs are needed to provide efcient supplemental heat and a bright decorative re. In general, fresh wood should not be loaded higher than about 2/3 the height of the rebox.
Installing Line for Gas Logs
Vermont Castings Group replaces are designed to accept a 1/2” (13 mm) gas line for installation of an approved gas appliance. (Vermont Castings Group manufactures a wide variety of gas logs for use in Vermont Castings Group replaces.)
Be sure to have the appliance installed in accordance with building codes.
Gas connection may enter from either left or right side of the replace.
Locate appropriate gas line in the outer casing of replace and remove insulation from gas line tube. (Fig. 24)
From inside the replace, locate the knockout on the re­brick -- be sure you are on the appropriate or “gas line” side of the replace. Using a at bladed screwdriver or small chisel and hammer, carefully tap around the knockout until it loosens and falls out.
Install 1/2” (13 mm) certied gas pipe through opening. After gas pipe installation is complete, use insulation that was removed from gas line tube to repack space around the pipe. Material should be inserted from outside of the replace and packed tightly to totally seal between the pipe and tube.
NOTE: Gas pipe should not come in contact with any wood structures until it has reached a point at least 1” (25 mm) away from replace side.
Hole in Outer Casing
Gas Line Tube
Ceramic Knockout
Hole in Outer Cas­ing
Fig. 24 Gas line access.
Fireplace Top View
Supply Line
Repack Insu­lation
Ceramic Knockout (both sides)
FP560a
BTU input of a gas appliance installed in replace should be rated less than 100,000 BTU/Hr.
Gas pipe installation is intended for connection to a deco­rative gas appliance only when (1.) incorporating an auto­matic shutoff device and (2.) complying with the Standard for Decorative Gas Appliances for Installation in Vented Fireplaces (ANSI Z21.60) or CSA draft requirements for Gas-Fired Log Lighters for Woodburning Fireplaces (Draft No. 4, August 1993).
Decorative gas appliance should be installed in accordance with the National Fuel Gas Code, ANSI Z223.1/NFPA 54 (latest edition).
CAUTION: When using decorative gas appli­ance, ue damper must be set in fully open position. Glass doors on the replace must also be fully opened.
WARNING: Do not operate an unvented gas log set in this replace with the chimney re­moved.
WARNING: When installing an unvented gas log set, the model CABL or CABR 4” adjust­able hood must be used.
7412647
17
Page 18
BFC36 Balanced Flue Heat-Circulating Fireplace
1
2
3
5
6
7
8
9
10
11
12
13
14
16
15
19
18
17
4
24
20
22
21
25
23
23
26
27
28
29
Vermont Castings Group reserves the right to make changes in design, materials, specications, prices and discontinue colors and products at any time, without notice.
BFC Balanced Flue Fireplace
Ref. Description BFC36
1. Top Grille - Painted 3126160
2. Bottom Grille - Painted 3126160
3. Grate Assembly 7579218
4. Left Door Assembly Complete 30004361
5. Right Door Assembly Complete 30004362
6. Rear Firebrick 2353145
7. Side Firebrick (two per replace) 2353146
8. Hearth Firebrick 2353140
9. Nailing Flange (four per replace) 2422198
10. Fiberglas Rope Gasket (Outer Collar) 7547137
11. Top Refractory 2353147
12. Front Brick Retainer 2353163
13. Cable Clip (For Blower Assembly) 7522241
14. Plug Button (two per replace) 7522239
15. Left Door Gasket 20013999
16. Right Door Gasket 20013998
18
7412647
Page 19
BFC36 Balanced Flue Heat-Circulating Fireplace
BFC Balanced Flue Fireplace (continued)
Ref. Description BFC36
17. Blower Assembly - FKSX-A 20000620
18. Grate Retainer 2353179
19. Junction Box Assembly 3126161
20. Ceramic Glass Panel (two per replace) 30004352
21. Flat Gasket 3/4” Wide (two per replace) 20013997
22. Knob (two per replace) 1600657
23. Bushing (four per replace) 1201895
24. Pan Hd, PH 1/4-20 x 1 Black (two per replace) 1200907
25. Spacer (two per replace) 1600070
26. Spring Clip 30004450
27. #8-18 x 1/2” Decorative Screw 7521180
28. Hinge Spacer (two per replace) 30004360
29. BFC Door Assembly 20014006
7412647
19
Page 20
BFC36 Balanced Flue Heat-Circulating Fireplace
Accessories
The following accessories for this appliance are available from your local Vermont Castings Group distributor. Should you need additional information beyond what your distributor can furnish, contact: Vermont Castings Group, 149 Cleveland Drive, Paris, KY 40361, Attn: Technical Services.
CAUTION: This replace and chimney assembly is a highly engineered system, and, as such, must be operated only with Vermont Castings Group approved components. If you use an unapproved component to make any modications, you may create a possible re hazard and will void the Vermont Castings Group warranty. In addition, such action may void the coverage provided by the owner’s insurance.
Model NumberDescriptionAccessory
Hearth Extension Insulation Provides hearth extension oor protection EH2416 Grate for BR/BC36/42 Holds rewood in rebox RBG-BFC36 Hearth Patch Compound Patch cracks in hearth HPC-1
See your Vermont Castings Group Fireplaces distributor or dealer for nishing Marble and Mantels, available in a wide selection of styles.
20
7412647
Page 21
BFC36 Balanced Flue Heat-Circulating Fireplace
Chimney Components
Component Description Model Number Chimney Support Used to support chimney for each of TCS8A
30’ vertical height and 6’ of angled chimney run (8” ue) Firestop Required at each oor level and attic on FS2A (8” straight ue)
multi-story installation FS6A (8” 30° inclined ue) Attic Insulation Shield Required in Canada FS2100HT Traditional Top Housing Top housing of simulated brick pattern T20B
available in red, tan or white. Appropriate (single ue) adapter is required (8CA). Flashing included. TL20B (extra tall single ue)
Housing Extension Extends Traditional Top Housing on 202036 steep pitched roofs (single ue)
Contemporary Chase Top Used to terminate chimney at the top of a Termination chase. Flashing is not included. TT200C Adapter Kit (TT8CB) is required.
Chase Top Housing Used with chase terminations to prevent rain entry. FL88 (8” ue)
Contemporary Flashing 8-6-12 with 8” ue Required for Contemporary Round Top 0 to 6/12 pitch termination to prevent rain entry. 8-12-12 with 8” ue (6/12 to 12/12 pitch)
Chimney Sections 8” ue 81 (1’ long) Used to build chimney systems. 818 (1Z\x’ long) 83 (3’ long) 84 (4’ long)
Chimney Elbows Used to develop offset chimney systems. Only 30° elbows are available. (Elbows 830A-2 packed 2 per carton - upper and lower (8” 30° ue) elbow set.)
Round Top Termination Used to terminate chimney on the roof. RT8C Flashing not included. (8” ue)
Extended Round Top Chase Used to terminate chimney at the top of a RT8CL Termination chase. Adapter Kit included. Flashing not (8” ue) included.
Adapter Kit Required to connect triple-wall chimney 8CA with Traditional Top Housing (T20B or TL20B) (8” ue)
Adapter Kit Required to unite chimney with TT8CB Contemporary Chase Top. (TT200C)
7412647
21
Page 22
BFC36 Balanced Flue Heat-Circulating Fireplace
22
7412647
Page 23
BFC36 Balanced Flue Heat-Circulating Fireplace
LIMITED WARRANTY
Factory-Build Fireplace and Components
(Except Blowers)
What is Covered and For How Long
Five-Year Coverage: For ve years from the date this replace and components are rst purchased for use, Vermont
Castings Group will, at its option, repair or replace any defective part of this replace or components, or refund to you a sum not to exceed the factory retail price in effect at the time of purchase.
Ten-Year Coverage: From the sixth through the tenth year following the date this replace or accessory is rst pur­chased for use, Vermont Castings Group will make available to you, at our factory, a free replacement for any defective part in this replace or accessory.
Twenty-Five-Year Availability of Replacement Parts: From the eleventh through the twenty-fth year following the date this replace or accessory is rst purchased for use, Vermont Castings Group will make available at our factory replacement parts for this replace or accessory, which you may purchase for the list price current at the time your purchase order is received.
What is Not Covered
• This limited warranty does not cover:
• Transportation or shipping cost.
• The cost of a service call to diagnose trouble.
• Painted surfaces.
• Damage or defect caused by improper installation, accident, misuse, abuse or alteration.
• Poor ventilation of smoke or gases caused by air-conditioning and heating systems, exhaust fans, or pressure dif­ferentials produced by wind.
• Broken glass components.
• Cracks in ceramic and castable parts that do not affect safe operation.
• We do not warrant this replace to be in compliance with your local building code. Building codes vary greatly throughout the country, and you should determine whether your local building code contains restrictions on the use of this replace before you purchase it.
• Blowers or fans, which are warranted separately.
• Heat loss due to the passage of heat or air through or around the replace.
Also, under our ve year coverage, we do not pay the cost of removal and replacement of any portion of the structure in which the replace is situated, made necessary by the repair, removal or re-installation of the replace.
And under our twenty-ve year warranty of availability of replacement parts, we only promise to maintain a supply of replacement parts at our factory for you to purchase.
Limitations and Exclusions
1. No one has authority to add to or vary this limited warranty, or to create for Vermont Castings Group any other obliga­tions of liability in connection with this replace and accessory.
2. Vermont Castings Group shall not be liable for incidental, consequential, special or contingent damages you might suffer as a result of its breach of this written warranty or any implied warranty. Some states do not allow the exclusion of limitation of incidental or consequential damages, so the above limitations may not apply to you.
3. This warranty applies only to a replace sold and used in the United States.
For information about this warranty, contact: Vermont Castings Group
149 Cleveland Drive Paris, Kentucky 40361
7412647
23
Page 24
BFC36 Balanced Flue Heat-Circulating Fireplace
24
Vermont Castings Group
149 Cleveland Drive • Paris, Kentucky 40361
www.Vermont Castings Group.com
7412647
Loading...