Please read this manual
before installing and using
appliance.
Unvented
WARNING: If the information in
this manual is not followed
exactly, a fire or explosion may
result causing property damage,
personal injury of loss of life.
• Do not store or use gasoline or
other flammable vapors and liquids in
the vicinity of this or any appliance.
• WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance
• Do not touch any electrical switch;
do not use any phone in your building
• Immediately call your gas supplier
form a neighbor’s phone. Follow the
gas supplier’s instructions
• If you cannot reach your gas
supplier, call the fire department
• Installation and service must be
performed by a qualified installer,
service agency or the gas supplier.
SAFETY: Accidents are always tragic, especially
because so many of them could have been prevented
with a little care and judgment. There are some basic
good practices we hope you will follow for safe use of
your gas fired room heater.
IMPORTANT: Read this user’s manual carefully and
completely before trying to assemble, operate or
service this heater. Improper use of this heater can
cause serious injury or death from burns, fire,
explosion, electrical shock and carbon monoxide
poisoning.
Early signs of carbon monoxide poisoning resembles
the flu, with headaches, dizziness or nausea. If you
have these signs, the heater may not be working
properly. Get fresh air at once! Have heater serviced.
Some people are more affected by carbon monoxide
than others. These include pregnant women, people
with heart or lung disease or anemia, those under the
influence of alcohol and those at high altitudes.
Begin by ensuring proper installation and servicing.
Follow the installation instructions provided with this
product. Have your heater installed by a qualified
technician. Have the installer show you where the gas
supply shut off valve is located so that you know where
to shut off the gas to the heater. If the connections are
not perfectly seated or tightened, you may have a leak
and therefore a faint gas smell.
Finding a leak is not a DO-IT-YOURSELF procedure.
Some leaks can only be found with the main burner gas
on and this must be done by a qualified technician.
WARNING:
This appliance is for use with gas referenced on
Rating Label. Field conversion is not permitted.
Precautions
• Never use natural gas in a unit designed for lique-
fied petroleum gases.
• Never use liquefied petroleum gases in a unit
designed for natural gas.
• Check all joints and connections. To avoid the
danger of fire, accident or explosion, never check a
potential gas leak with an open flame.
• The VCBV30, VCBV20, VCPV30 and VCPV18
heaters may not be installed in a bedroom or
bathroom.
• The VCBV10 and VCPV10 heaters may be
installed in a bedroom, but not a bathroom.
• The VCPV06 heaters may be installed in a bedroom
or bathroom.
• This appliance is intended for supplemental heating.
•Never install the heater in any of the following
locations:
•Recreational vehicles
• Where curtains, furniture, clothing or other
flammable objects are less than 36” from the
front, top or sides of the heater
• Fireplace
• High traffic area
•Drafty areas
•This heater needs fresh, outside air for ventilation to
run properly. This heater has an oxygen depletion
sensor (ODS) pilot light safety system. The ODS
shuts down the heater if not enough fresh air/oxygen
content (18%) is available.
•Never run heater in confined space. Refer to Page 4.
•If heater shuts off, do not relight until you provide
fresh, outside air. If heater keeps shutting off, have it
serviced.
•Do not run the heater where:
• Flammable liquids or vapors are used or stored
• Dusty condition exists
•Never place any objects on the heater.
•Supervise children when they are in the same room
with heater, never allow them to sit, stand or play on
or around the heater.
•Make sure grille guard is in place before running
heater.
•Do not use heater if any part has been under water.
Immediately call a qualified service technician to
inspect the room heater and to replace any part of
the control system and any gas control which has
been under water.
•Keep appliance area clear and free from combustible materials, gasoline and other flammable vapors
and liquids.
•Turn off heater and let cool before servicing. Only a
qualified technician should service and repair heater.
Table of Contents
General Safety Information ..................................... 2
ModelsTypeMin.Max.SettingMin.Max.
VCBV30MN15,00030,00027” x 24” x 8⁵⁄₈”30 lbs.
VCBV20MNNatural10,00020,0003.0” w.c.7.0” w.c. 10.5” w.c.19³⁄₈” x 22⁷⁄₈” x 8¹⁄₂”22 lbs.
VCBV10MN5,00010,00015¹⁄₂” x 20⁷⁄₁₆” x 7⁷⁄₈”17 lbs.
VCBV30MP15,00030,00027” x 24” x 8¹⁄₂”30 lbs.
VCBV20MPLP10,00020,0008.0” w.c.11.0” w.c. 14.0” w.c.19³⁄₈” x 22⁷⁄₈” x 8¹⁄₂”22 lbs.
VCBV10MP5,00010,00015¹⁄₂” x 20⁷⁄₁₆” x 7⁷⁄₈”17 lbs.
VCPV30MN6,40030,00027” X 24” X 8⁵⁄₈”30 lbs.
VCPV18MN
Natural
VCPV10MN5,50010,00015¹⁄₂” x 20⁷⁄₈” x 7⁷⁄₈”17 lbs.
VCPV06MN2,6006,00015¹⁄₂” x 20⁷⁄₈” x 7⁷⁄₈”17 lbs.
VCPV30MP6,40030,00027” x 24” x 8¹⁄₂”30 lbs.
VCPV18MP
LP
VCPV10MP5,50010,00015¹⁄₂” x 20⁷⁄₈” x 7⁷⁄₈”17 lbs.
VCPV06MP2,6006,00015¹⁄₂” x 20⁷⁄₈” x 7⁷⁄₈”17 lbs.
NOTES: For altitudes above 2,000 feet, reduce the input ratings (Btu/Hr) 4% for each 1,000 feet above sea level.
DO NOT USE THIS HEATER AT AN ELEVATION ABOVE 4,500 FEET
6,40018,000
6,40018,000
6.0” w.c.7.0” w.c. 10.5” w.c.
10.0” w.c.11.0” w.c. 14.0” w.c.
19³⁄₈” x 22⁷⁄₈” x 8¹⁄₂”22 lbs.
19³⁄₈” x 22⁷⁄₈” x 8¹⁄₂”22 lbs.
Front
Panel
Grille
Guard
VCBVMN/MP
Fig. 1 Product identification.
Gas Control
VERMONT
C
astings
Frame
Body
Assembly
3769
Local Codes
VCBV30 / VCBV20 / VCBV10
VCPV30 / VCPV18 / VCPV10 / VCPV06
Certified to
ANSI Z21.11.2b-2002 Unvented Heaters
Install and use heater with care. Follow all local codes.
In the absence of local codes, use the latest edition of
the National Fuel Gas Code ANSI Z223.2, also know as
NFPA54.
Available from:
American NationalNational Fire Protection
Standards Institute, Inc.Association, Inc.
1430 BroadwayBatterymarch Park
New York, NY 10018Quincy, MA 02269
Front
Panel
Grille
Guard
VCPVMN/MP
VERMONT
C
astings
Gas Control
Frame
Body
Assembly
3772
Product Features
Safety Device
This heater has a pilot with an Oxygen Depletion
Sensor shutt-off system (ODS). The ODS pilot is a
required feature for vent-free heaters. The ODS pilot
shuts off the heater if the normal air oxygen content is
reduced to 18%.
Piezo Ignition System
This heater has a piezo ignitor. This system requires no
matches, batteries or other sources to light the heater.
This heater must have fresh air for proper
operation. If not, poor fuel combustion could
result. Read the following instructions to insure
proper fresh air for this and other fuel-burning
appliances in your home.
Modern construction standards have resulted in homes
that are highly energy-efficient and that allow little heat
loss. Your home needs to breathe, however, and all
fuel-burning appliances need fresh air to function
properly and safely. Exhaust fans, clothes dryers,
fireplaces and other fuel burning appliances all use the
air inside the building. If the available fresh air supply is
insufficient to meet the demands of these appliances,
problems can result.
Provide for Adequate Ventilation
Any space within a home can be classified in these
categories:
Unusually tight construction: The air that leaks
around doors and windows may provide enough fresh
air for combustion and ventilation. However, in buildings
of unusually tight construction, you must provide
additional fresh air. Unusually tight construction is
defined as construction where:
Walls and ceilings exposed to the outside atmosphere
have a continuous water vapor retarder with a rating of
one perm or less with openings gasketed or sealed
and;
Caulking or sealants are applied to areas such as joints
around window and door frames, between sole plates
and floors, between wall/ceiling joints, between wall
panels, at penetrations for plumbing, electrical and gas
lines, and at other openings.
Unconfined space: An unconfined space whose
volume is not less than 50 cubic feet for each 1,000
Btu/Hr of the aggregate input rating of all appliances
installed in that space. Rooms communicating directly
with the space in which the appliances are installed,
through openings not furnished with doors are considered a part of the unconfined space.
Confined space: A confined space whose volume is
less than 50 cubic feet for each 1,000 Btu/Hr of the
aggregate input rating of all appliances in that space.
WARNING: You must provide additional ventilation air
in a confined space.
For proper operation of the unit, provide fresh air
opening(s) to the room. Follow the National Fuel Code
NFPA54/ANSI Z223.1, for required size of combustion
and ventilation openings.
NOTICE: A qualified service technician should install
heater. Follow all local codes.
Gas Type
Verify the type of gas supply to be used, either natural
gas or LP (Propane), and make sure the marking on the
appliance rating plate agrees with that of the supply
gas. The rating plate is located on the side of the
heater, which indicates the type of gas the heater is
orificed for.
Items Needed for Heater Installation
Before installing the heater, make sure you have these
items:
• Gas piping (check local codes)
• Test gauge connection
• Sealant (resistant to LP gases) - approved
thread compound
• Manual shut-off valve
*
• Sediment trap - where required
• Ground joint union
• Tee joint and pipe wrench
An installer supplied design-certified manual shut-off valve
*
with 1/8” NPT tap connection.
Locating the Heater
This heater is designed to be mounted on a wall or on
the floor.
WARNING: Never install the heater:
• in a bathroom
,
*
• in a recreational vehicle,
• where curtains, furniture, clothing or other
flammable objects are less than 36” from the
front, top, or sides of the heater,
• as a fireplace insert,
• in high traffic areas, or
• in windy or drafty areas.
Models VCPV06M(N,P) permitted for bathroom installations.
*
WARNING: Vent-free heaters add moisture to the air.
Although this is beneficial, installing heater in rooms
without enough ventilation may cause mildew formation
from too much moisture content. See National Fuel
Code for Fresh Air for Combustion and Ventilation.
This appliance may be installed in an aftermarket*
manufactured (mobile) home, where not prohibited by
state or local codes.
*Aftermarket: Completion of sale, not for purpose of
resale from manufacturer.
This appliance is only for use with the type of gas
indicated on the rating plate. This appliance is not
convertible for use with other gases.
CAUTION: If you install the heater in a home garage:
• Heater must be at least 18” above floor
• Locate heater where moving vehicle will not hit it.
Preparing for Installation
1. Remove heater from carton.
2. Remove all protective packaging applied to heater
for shipment.
3. Check heater for any shipping damage. If heater is
damaged, promptly inform dealer/distributor.
4. Select a location for the heater that will provide
maximum exposure of the radiant surface to the
room, but will not be subjected to accidental contact.
5. Adequate clearance must be available around the
air opening. Refer to Figure 2 for clearances that
must be maintained to the side walls, floor and
horizontal surface surrounding the heater.
Attach Mounting Screws to Wall
NOTE: Wall anchors and mounting screws are in
hardware package provided with heater.
1. Install mounting screws on wall as shown in Figure
3. Use enclosed “paper template” for proper location
of holes. Be sure template is level. It may be necessary to use plastic or lead anchors for plaster walls.
2. Drill holes at marked locations using 9/64” drill bit.
Insert mounting screw.
3. Leave screw head out from wall far enough to attach
heater.
Template
Mounting Screws
RH101
Ceiling
36"
(914mm)
Adjacent Wall
13"
(330mm)
Min.
Screw Holes
A = 21¹⁄₄" (330 mm) @ 30,000 Btu/ hr Model
13¹¹⁄₁₆" (347 mm) @ 18,000/20,000 Btu/ hr Model
9⁷⁄₈" (251 mm) @ 10,000 Btu/ hr Model
9⁷⁄₈" (251 mm) @ 6,000 Btu/ hr Model
Fig. 2 Minimum clearances to floor, adjacent walls and
ceiling.
A
Min.
20"
(508mm)
Min.
RH100
Fig. 3 Use paper template supplied to mark location of
mounting holes. Be sure template is level.
Wall Anchor Method
When mounting heater to hollow walls (wall areas
between studs) or solid walls (concrete or masonry) it
may be necessary to use wall anchors.
1. Place paper template on wall maintaining minimum
clearance. Be sure template is level.
2. Drill holes at marked locations using 5/16” drill bit.
For solid walls, concrete or masonry, drill holes at
least 1” deep.
3. Insert plastic anchor. Tap anchor flush to wall. (Fig.
4)
4. Insert screw into wall anchor leaving screw head out
far enough from wall to attach heater. (Fig. 4)
5. Hang heater on mounting screws in holes provided
at the rear of the heater.
Before connecting the appliance, turn off all gas appliances. Close the main gas valve at the gas meter or Lp
tank. Make certain there is good ventilation where the
installation will be made. Installation should comply with
all applicable building codes and ANSI Z223.1, latest
edition. Use LP gas resistant pipe compound to seal
threaded joints.
An installer supplied, design certified gas pressure
regulator must be installed to bring the gas supply
pressure down to 14” w.c.
WARNING: Never connect an unregulated gas line
to the heater.
IMPORTANT: Check gas line pressure before connect-
ing heater to gas line. Gas line pressure must not be
higher than 14” w.c. If gas line pressure is higher,
1/16"
(1.6mm)
RH102
Fig. 4 Wall anchor.
Floor Installation
1. Heater may only be installed on a noncombustible
flat surface. Wall mounting screws may be used to
keep heater from side movements.
3. Use enclosed “paper template” for proper distance
between holes. Be sure template is level. It may be
necessary to use plastic or lead anchors for plaster
wall.
4. Drill holes at marked locations using 9/64” drill bit.
5. Leave screw head out from wall far enough to attach
heater.
heater gas pressure regulator damage could occur.
NOTE: The gas line connection can be made with 3/8”
black or steel pipe. Internally tinned copper tubing may
be used in certain areas. Check your local codes. Use
pipe of large enough diameter to allow proper gas
volume to heater. If pipe is too small, undue pressure
loss will occur.
CAUTION: Use pipe joint sealant that is resistant to
liquefied petroleum gases.
Install sediment trap in supply line as shown in Figure
6. Locate sediment trap where it is within reach for
Pressure
Regulator
3/8” NPT Nipple
Heater
Cabinet
Screw Holes
X
Floor
RH107
Fig. 5 Optional wall mounting screws for floor installation.
cleaning. Locate sediment trap where trapped matter is
not likely to freeze. A sediment trap prevents moisture
and contaminants from going into the heater controls. If
the sediment trap is not installed or is installed wrong,
the heater may not operate properly.
Test for gas leaks with a mild soap and water solution.
Apply water/soap solution with brush only -
do not over
apply. NEVER test with an open flame.
Pressure Test Gas Supply Piping System
The appliance and its individual shut-off valve must be
disconnected from the gas supply piping system during
any pressure testing of the system at test pressures in
excess of 1/2 psi.
The appliance must be isolated from the gas supply
piping system by closing the individual manual shut-off
valve (Fig. 7) during any pressure testing of the gas
supply system at test pressures equal to or less than
1/2 psi.
Open
Manual
Shut-Off
Valve
Closed
Leak Testing Heater Gas Connections
1. Open manual shut-off valve.
2. Open main gas valve located near gas meter.
3. Make sure control knob of heater is in the OFF
position.
4. Check all joints from manual gas valve up to control
valve and including the manifold assembly. Apply the
soap solution around the connections, valve and
tubing. Soap bubbles will appear where a leak is
present.
5. If a leak is present, immediately turn off gas supply,
tighten any leaky fittings, turn gas on and recheck.
6. To check burner and safety valve, the burner must
be lit. (See Operating Instructions) Check the rest of
the connections for leaks.
FOR YOUR SAFETY - READ THIS SECTION
BEFORE LIGHTING
WARNING: IF YOU DO NOT FOLLOW THESE
INSTRUCTIONS EXACTLY, A FIRE OR EXPLOSION MAY RESULT CAUSING PROPERTY DAMAGE, PERSONAL INJURY OR LOSS OF LIFE.
A. BEFORE LIGHTING smell all around the appliance
area for gas. Be sure to smell next to floor because
some gas is heavier than air and will settle on the
floor.
IF YOU SMELL GAS:
1. Do not try to light any appliance.
2. Do not touch electrical switches; do not use any
phone in your building.
3. Immediately call your gas supplier from a
neighbor’s phone. Follow your gas supplier’s
instructions.
4. If you cannot reach your gas supplier, call the fire
department.
7. Depress control knob while OFF, then turn back to
PILOT/IGN. This should cause the spark from the
piezo ignitor to light the pilot gas. Keep control knob
depressed for ten (10) seconds before releasing. If
pilot does not light, repeat steps 5 – 7, or use a match.
8. To select the heating level desired, partially press
down the control slightly and rotate counterclockwise
. Release the downward pressure on the knob
while continuing to turn until the knob locks at the
desired setting position. Do not operate between the
locked positions.
OFF
PILOT/IGN
LOW
MED
RH105
Fig. 8 Control knob.
PILOT/IGN
HIGH
VCBV10 & VCPV10 Only
HIGH
OFF
LOW
B. Use only your hand to push in or turn the gas valve
control knob. Never use tools. If the knob will not
push in or turn by hand, do not try to repair it, call a
qualified service technician. Force or attempted
repair may result in a fire or explosion.
C. Do not use this appliance if any part has been under
water. Immediately call a qualified service technician
to inspect the appliance and to replace any part of
this control system and any gas control which has
been under water.
Lighting Instructions
1. Read the safety information on previous page.
2. Make sure manual shut-off valve is fully open.
3. Push in gas control knob slightly and turn clockwise
to the OFF position.
4. WAIT 5 MINUTES TO CLEAR OUT ANY GAS. If
you then smell gas, STOP! Follow A in the safety
information. If you do not smell gas, go to next step.
5. Push in gas control knob slightly and turn counter-
clockwise to ‘PILOT/IGN” and depress for five
(5) seconds. This will allow air to bleed from the gas
system.
6. Release control knob pressure and turn clockwise
to “OFF”.
To Turn Off Gas To Heater
Turning Heater Off
Turn control knob clockwise to the OFF position.
Turning Burner Only Off (Pilot stays lit)
Turn control knob clockwise to the PILOT position.
CAUTION: Do not try to adjust heating levels by
using the manual shut-off valve.
NOTE: The thermostat sensing bulb measures the
temperature of air near the heater cabinet. This may not
always agree with room temperature (depending on
housing construction, installation location, room size,
etc.). Frequent use of your heater will let you determine
your own comfort levels.
Manual Lighting Instructions
1. Remove lower front panel.
2. Follow steps 1 through 4 as stated under Lighting
Instructions.
3. Press and turn control knob counterclockwise
to the PILOT/IGN position.
4. With control knob pressed in, strike match, hold
match to pilot until pilot lights.
5. Keep control knob pressed in for 30 seconds after
lighting pilot. After 30 seconds, release control knob.
Each time you light your heater check that the pilot
flame and burner flame patterns are as shown in
Figures 9, 10 and 11. If flame patterns are incorrect,
turn the heater off. Contact your dealer or a qualified
gas technician for assistance. Do not operate the
heater until the pilot flame is correct.
WARNING: If yellow tipping occurs, your heater could
produce increased levels of carbon monoxide. If burner
flame pattern shows yellow tipping, follow instructions
in the Troubleshooting section on page 10. NOTE: Do
not mistake orange flames with yellow tipping. Dirt or
other particles may enter the heater and cause transient patches of orange flame.
Ignitor Electrode
Thermocouple
VCBV Heater
Y ellow T ipping
Correct
Fig. 10 Correct burner flame pattern for the VCBV blue flame
burner.
VCPV Heater
Correct
Incorrect
RH106
Correct
Fig. 9 Proper pilot flame.
Incorrect
P103
Incorrect
Fig. 11 Correct burner flame pattern for the VCPV plaque
Heater produces a clicking
noise just after burner is lit or
turned off.
Gas odor even when control
knob is in OFF position.
Gas odor during combustion.
Heater shuts off on ODS
1. Metal expanding and contracting.
1. Gas leaks. Refer to front page
Warnings.
2. Gas control defective.
1. Foreign matter in gas or on burner
ports.
2. Heater burning vapors form paint,
impurities in air.
3. Gas leaks, refer to front page
Warnings.
1. Not enough fresh air is available.
2. Low gas pressure.
3. ODS pilot partially clogged.
Maintenance
Dust, lint, cobwebs or debris may affect heater performance. The heater draws air into it during normal
operation and in the process dust, lint or debris may be
drawn in also. It is important to keep the burner , gas
control and combustion and circulating air passageways clean. Inspect or have these areas inspected
annually at the beginning of the heating season by a
qualified service person. Depending on the surroundings, the room heater may require frequent cleaning
due to excessive lint or debris.
Before cleaning ensure the gas supply is off and the
gas control knob is in the OFF position. Make sure the
heater is cool.
WARNING: Danger of bodily injury. If fan assembly
accessory is used, turn off power supply at disconnect switch or service panel before removing any
access panels from heater.
1. This is common with heaters. If
noise is excessive, contact a
qualified service technician.
1. Locate and correct leaks immediately.
2. Replace gas control.
1. Check gas passage way and
burner.
2. Ventilate room, stop storing and
using odor causing products near
heater.
3. Locate and correct leaks immediately.
1. Open window.
2. Contact gas supplier.
3. Clean the pilot.
Burner and ODS Pilot Cleaning
Clean the exterior with soft bristle brush, vacuum
cleaner or pressurized air. Never use a wooden toothpick as it may break off and clog the ODS pilot or main
burner port.
Use a flashlight to inspect the main burner inlet to
ensure it is not blocked. If obstruction can be seen, use
a metal wire coat hanger that has been straightened
out.
Use a vacuum cleaner to clean the primary air
openings to the main burner(s).
WARNING: Failure to keep the primary air openings
to the burner(s) clean may result in sooting and
property damage.
In order to clean ODS pilot orifice, use pressurized air
to blow dust out. Sometimes blowing air backwards
through the pilot will get rid of the accumulated dirt. If
that does not work, blow out any dust through primary
air openings of pilot assemblies (Daemyeong has two
openings; one beneath the bimetal strip and the second
one opposite from bimetal strip. Use the one wide
open, do not try to lift the bimetal strip.)
Cleaning Air Passageways
and Unit Casings
Use a vacuum cleaner or pressurized air to clean the
combustion and circulating air passageways and
dampened cloth to clean the cabinet/casing.
The Vermont Castings Majestic Products Company reserves the right to make changes in design, materials, specifications, prices and discontinue
colors and products at any time, without notice.
VCBVMN/MP Unvented Room Heater
Item / Model NumberVCBV10MN/MPVCBV20MN/MPVCBV30MN/MP
7.Nozzle HolderRBM06XX0RBM06XX0RBM06XX0
8a.ODS Pilot Assembly (Daemyeong Korea) - NaturalDS98N02DS98N02DS98N02
8b.ODS Pilot Assembly (Daemyeong Korea) - LPDS98PL02DS98PL02DS98PL02
9.Fix Nut - Nozzle HolderRBM08XX0RBM08XX0RBM08XX0
10a. Main Nozzle - NaturalRBM07XERBM07XARBM07XC
10b. Main Nozzle - LPRBM07F0RBM07B0RBM07E0
11.Bracket - ValveRBP59XX0RBP59XX0RBP59XX0
12a. Gas Control (Daemyeong Korea) - NaturalDMV101PADMV100PADMV100PC
12b. Gas Control (Daemyeong Korea) - LPDMV101PBDMV100PBDMV100PD
Vermont Castings, Majestic Products reserves the right to make changes in design, materials, specifications, prices and discontinue colors and
products at any time, without notice.
VCPVMN/MP Unvented Room Heater
Item / Model NumberVCPV06MN/MPVCPV10MN/MPVCPV18MN/MPVCPV30MN/MP
The following accessories are available from your local Vermont Castings dealer. Each accessory comes with a
separate installation instruction. Be sure to read each instruction thoroughly before installing.
DescriptionModel Number
Manual Fan KitFMA-F
Thermostat Fan KitFMA-FT
Contact Vermont Castings Majestic, Products with
questions concerning prices and policies covering
replacement parts. Parts may be ordered through you
Vermont Castings distributor or dealer.
You will need the following information when ordering
replacemet parts:
• the appliance model number,
Model and serial numbers are listed on the rating
plate (located on right side of heater). Record your
model and serial numbers here for future reference.
Model # ___________________________________
Serial # ___________________________________
• the serial number, and
• a description of the part.
Should you need additional information beyond
what your dealer can furnish, contact:
The Vermont Castings Majestic Products Company
warrants this product to be free form defects in materials and components for two (2) years from the date of
first purchase, provided that the product has been
properly installed, operated and maintained in accordance with all applicable instructions. To make a claim
under this warranty the Bill of Sale or cancelled check
must be presented.
This warranty is extended only to the original retail
purchaser. This warranty covers the cost of part(s)
required to restore this heater to proper operating
condition and an allowance for labor when provided by
a Vermont Castings authorized dealer/distributor.
Warranty part(s) MUST be obtained through authorized
dealers of this product and/or Vermont Castings Majestic Products who will provide original factory replacement parts. Failure to use original factory replacement
parts voids this warranty. The heater MUST be installed
by a qualified installer in accordance with all local
codes and instructions furnished with the unit.
This warranty does not apply to parts that are not in
original condition because of normal wear and tear, or
parts that fail or become damaged as a result of
misuse, accidents, lack of proper maintenance or
defects caused by improper installation. Travel, diagnostic cost, labor, transportation and any and all such
other costs related to repairing defective heater will be
the responsibility of the owner.
TO THE FULL EXTENT ALLOWED BY THE LAW OF
THE JURISDICTION THAT GOVERNS THE SALE OF
THE PRODUCT; THIS EXPRESS WARRANTY EXCLUDES ANY AND ALL OTHER EXPRESSED WARRANTIES AND LIMITS THE DURATION OF ANY AND
ALL IMPLIED WARRANTIES, INCLUDING WARRANTIES OF MERCHANT ABILITY AND FITNESS FOR A
PARTICULAR PURPOSE TO TWO (2) YEARS FROM
THE DATE OF FIRST PURCHASE; AND THE VERMONT CASTINGS MAJESTIC PRODUCTS COMPANY
SHALL NOT BE LIABLE FOR ANY OTHER DAMAGES
WHA TSOEVER INCLUDING INDIRECT, INCIDENTAL
OR CONSEQUENTIAL DAMAGES.
Some states do not allow a limitation on how long an
implied warranty lasts or an exclusion or limitation of
incidental or consequential damages, so the above
limitation on implied warranties, or exclusion or limitation on damages may not apply to you.
This warranty gives you specific legal rights, and you
may also have other rights that vary from state to state.
Always specify model and serial number when communicating with the factory.