PLEASE READ THIS MANUAL
BEFORE INSTALLING AND USING
APPLIANCE
WARNING!
IF THE INFORMATION IN THIS
MANUAL IS NOT FOLLOWED
EXACTLY, A FIRE OR EXPLOSION
MAY RESULT CAUSING PROPERTY
DAMAGE, PERSONAL INJURY OR
LOSS OF LIFE.
FOR YOUR SAFETY
Installation and service must be
performed by a qualified installer,
service agency or the gas supplier.
WHAT TO DO IF YOU SMELL GAS:
• Do not try to light any appliance.
• Do not touch any electric switch; do
not use any phone in your building.
• Immediately call your gas supplier
from your neighbor’s phone. Follow
Homeowner’s Installation and
Operating Manual
the gas suppliers instructions.
• If you cannot reach your gas supplier
call the fire department.
DO NOT STORE OR USE
GASOLINE OR OTHER
FLAMMABLE VAPORS AND
LIQUIDS IN THE VICINITY OF THIS
OR ANY OTHER APPLIANCE.
INSTALLER: Leave this manual with the appliance.
CONSUMER: Retain this manual for future reference.
20000584 1/07 Rev. 16
DVBR Series Direct Vent Gas Fireplace
Table of Contents
Please Read the Installation & Operating Instructions Before Using Appliance.
Thank you and congratulations on the purchase of a CFM Corporation fireplace.
IMPORTANT: Read all instructions and warnings carefully before starting installation. Failure to follow these
instructions may result in a possible fire hazard and will void the warranty.
Installation & Operating Instructions
General Information ....................................................................................................................3
This gas appliance should be installed by a qualified installer in
accordance with local building codes and with current CSA-B149.1 Installation codes for Gas Burning Appliances and
Equipment. If the unit is being installed in a mobile home, the
installation should comply with the current CAN/CSA Z 240.4
code. For U.S.A Installations follow local codes and/or the
current National Fuel Gas Code. ANSI Z223.1/NFPA 54.
In the Commonwealth of Massachusetts, all gas fitting
and installation of this heater shall only be done by a
licensed gas fitter or licensed plumber.
FOR SAFE INSTALLATION AND OPERATION PLEASE
NOTE THE FOLLOWING:
1. This fireplace gives off high temperatures and should be
located out of high traffic areas and away from furniture
and draperies.
2. Children and adults should be alerted to the hazards of the
high surface temperatures of this fireplace and should stay
away to avoid burns or ignition of clothing.
3. Children should be carefully supervised when in the same
room as your fireplace.
4. Under no circumstances should this fireplace be modified.
Parts removed for servicing should be replaced prior to
operating this fireplace again.
5. Installation and any repairs to this fireplace must be
performed by a qualified installer, service agency or gas
supplier. A professional service person should be contacted
to inspect this fireplace annually. Make it a practice to have
all of your gas fireplaces checked annually. More frequent
cleaning may be required due to excess lint and dust from
carpeting, bedding material, etc.
6. Control compartments, burners and air passages in this
fireplace should be kept clean and free of dust and lint.
Make sure the gas valve and pilot light are turned off before you attempt to clean this fireplace.
7. The venting system (chimney) of this fireplace should be
checked at least once a year and if needed your venting
system should be cleaned.
8. Keep the area around your fireplace clear of combustible
materials, gasoline and other flammable vapor and liquids.
This fireplace should not be used as a drying rack for cloth
ing, nor should Christmas stocking or decorations be hung
in the area of it.
9. Under no circumstances should any solid fuels (wood,
coal, paper or cardboard etc.) be used in this fireplace.
10. The flow of combustion and ventilation air must not be
obstructed in any way.
11. When fireplace is installed directly on carpeting, vinyl tile or
any combustible material other than wood, this fireplace
must be installed on a metal or wood panel extending the
full width and depth of the fireplace.
12. This fireplace requires adequate ventilation and combustion
air to operate properly.
13. This fireplace must not be connected to a chimney flue
serving a separate solid fuel burning fireplace.
14. When the fireplace is not in use it is recommended that the
gas valve be left in the OFF position.
DVBR Series Direct Vent Gas Fireplace
WARNING: Check with your electronics manufacturer
before installing a television or other electronic device above this fireplace.
This appliance may be installed in an aftermarket
permanently located, manufactured home or mobile home,
where not prohibited by local codes.
This appliance is only for use with the type of gas indicated
on the rating plate. This appliance is not convertible for
use with other gases, unless a certified kit is used.
Th e DV B R ha s bee n app roved for mobil e hom e
installations.
Proposition 65 Warning: Fuels used in gas, wood-
burning or oil fired appliances, and the products of
combustion of such fuels, contain chemicals known to
the State of California to cause cancer, birth defects
and other reproductive harm.
California Health & Safety Code Sec. 25249.6
IMPORTANT:
PLEASE READ THE FOLLOWING CAREFULLY
Remove any plastic from trim parts before turning the
fireplace ON.
It is normal for fireplaces fabricated of steel to give off
some expansion and/or contraction noises during the
start up or cool down cycle. Similar noises are found
with your furnace heat exchanger or car engine. It is
not unusual for your gas fireplace to give off some odor
the first time it is burned. This is due to the manufacturing process.
Please ensure that your room is well ventilated
-open all windows.
It is recommended that you burn your fireplace for at
least ten (10) hours the first time you use it. If the op
tional fan kit has been installed, place the fan switch in
the “OFF” position during this time.
-
-
20000584
3
DVBR Series Direct Vent Gas Fireplace
P - Rough Opening Width
Rough
Opening
Height
Rough
Opening
Depth
S
S
T
5/8” (16 mm)
R
Q
G
H
I
M
N
5/8” (16 mm)
E
D
F
O
B
A
C
K
L
Gas Line
Access
"
Electrical
Access
C
L
J
K
"
"
Fireplace Dimensions (Installed as Top Vent)
Fig. 2 Fireplace specifications and framing dimensions.
Ref. DVBR36 DVBR42A 40” (1016 mm) 46” (1168 mm)
B 36” (614 mm) 36” (914 mm)
C 36” (914 mm) 42” (1067 mm)
D 23¹⁄₄” (591 mm) 24¹⁄₄” (616 mm)
E 6³⁄₈” (162 mm) 6³⁄₈” (162 mm)
F 6³⁄₈” (162 mm) 5³⁄₈” (137 mm)
G 20” (508 mm) 20” (508 mm)
H 6³⁄₄” (172 mm) 6³⁄₄” (172 mm)
I 22” (559 mm) 28” (711 mm)
J 13¹⁄₄” (337 mm) 13¹⁄₄” (337 mm)
K 3” (76 mm) 3” (76 mm)
L 6¹⁄₂” (165 mm) 6¹⁄₂” (165 mm)
M 4” (102 mm) Dia. 4” (102 mm) Dia.
N 7” (178 mm) Dial. 7” (178 mm) Dia.
Framing DimensionsO 40¹⁄₂” (1029 mm) 40¹⁄₂” (1029 mm)
P 41” (1041 mm) 47” (1194 mm)
R 64³⁄₄” (1645 mm) 69¹⁄₂” (1765 mm)
S 45³⁄₄” (1162 mm) 49” (1245 mm)
T 32³⁄₈” (822 mm) 35¹⁄₄” (895 mm)
Q 20¹⁄₂” (521 mm) 20¹⁄₂” (521 mm)
4
20000584
DVBR Series Direct Vent Gas Fireplace
O - Rough Opening Width
Rough
Opening
Height
Rough
Opening
Depth
R
R
S
5/8” (16 mm)
Q
P
G
H
5/8” (16 mm)
E
D
F
N
B
A
C
J
K
Gas Line
Access
"
Electrical
Access
I
J
"
"
L
M
Fireplace Dimensions (Installed as Rear Vent)
Fig. 3 Fireplace specifications and framing dimensions.
Ref. DVBR36 DVBR42A 40” (1016 mm) 46” (1168 mm)
B 36” (614 mm) 36” (914 mm)
C 36” (914 mm) 42” (1067 mm)
D 23¹⁄₄” (591 mm) 23¹⁄₄” (591 mm)
E 6³⁄₈” (162 mm) 6³⁄₈” (162 mm)
F 6³⁄₈” (162 mm) 5³⁄₈” (137 mm)
G 20” (508 mm) 20” (508 mm)
H 22” (559 mm) 28” (711 mm)
I 13¹⁄₄” (337 mm) 13¹⁄₄” (337 mm)
J 3” (76 mm) 3” (76 mm)
K 6¹⁄₂” (165 mm) 6¹⁄₂” (165 mm)
L 29¹⁄₂” (749 mm) 29¹⁄₂” (749 mm)
M 30¹⁄₄” (768 mm) 30¹⁄₄” (768 mm)
Framing DimensionsN 40¹⁄₂” (1029 mm) 40¹⁄₂” (1029 mm)
O 41” (1041 mm) 47” (1194 mm)
P 20¹⁄₂” (521 mm) 20¹⁄₂” (521 mm)
Q 64
R 45³⁄₄” (1162 mm) 49” (1245 mm)
S 32³⁄₈” (822 mm) 35¹⁄₄” (895 mm)
³⁄₄” (1645 mm) 69¹⁄₂” (1765 mm)
20000584
5
DVBR Series Direct Vent Gas Fireplace
J
F
G
H
I
Mantel
Leg
O
N
M
L
K
A B C
D
E
V
W
X
Y
Z
Fireplace
Y
E
A
B
C
D
F
Y
B
X
Locating Your Fireplace
LU584-1
Fig. 1 Locating Gas Fireplace
A) Flat on wall B) Cross corner C) **Island
D) *Room divider E) *Flat on wall corner F) Chase installation
Y) 6” minimum
Note (Fig. 1):
** Island (C) and Room Divider (D) installation is possible as long as
the horizontal portion of the vent system (X) does not exceed 20’ (610
cm). See details in Venting Section.
* When you install your fireplace in(D) Room divider or (E) Flat on
wall corner positions (Y), a minimum of 0” (0mm) clearance must be
maintained from the perpendicular wall and the front of the fireplace.
Top of Combustion
Chamber
Bottom of Door Trim
CFM146a
Mantel Chart
Mantel Mantel from Top
Ref. Shelf Depth Ref. of Comb. Chamber
V 14” (356 mm) A 18” (457 mm)
W 12” (305 mm) B 16” (406 mm)
X 10” (254 mm) C 14” (356 mm)
Y 8” (203 mm) D 12” (305 mm)
Z 1
Fig. 4a Combustible mantel minimum installation.
¹⁄₂” (38 mm) E 8” (203 mm)
Clearance to Combustibles
Appliance
Top ......................................................... 0” (0 mm)
Top of unit to ceiling .......................... 36” (914 mm)
Front of unit to combustibles ............. 36” (914 mm)
Venting
Concentric sections of DV Vent ................... 1” (25 mm)
Nonconcentric sections of DV Vent
Sides and bottom ................................. 1” (25 mm)
Top ........................................................ 2” (51 mm)
Mantels
The height that a combustible mantel is fitted above the
fireplace is dependent on the depth of the mantel. This
also applies to the distance between the mantel leg (if
fitted) and the fireplace.
For the correct mounting height and widths, refer to
Figures 4a and 4b and the Mantel Chart below.
The distances and reference points are not affected by
the fitting of a bay window front trim kit.
Noncombustible mantels and legs may be installed at
any height and width around the appliance. When using
paint or lacquer, it must be heat resistant to prevent
discoloration.
6
Black
Surround Face
CFM164a
Side of
Combustion Chamber
CFM170
Mantel Leg Mantel Leg from Side
Ref. Depth Ref. of Combusion Opening
F 14” (356 mm) K 14” (356 mm)
G 12” (305 mm) L 12” (305 mm)
H 10” (254 mm) M 10” (254 mm)
I 8” (203 mm) N 8” (203 mm)
J 4” (102 mm) O 3
¹⁄₂” (89 mm)
Fig. 4b Combustible mantel minimum installation.
20000584
DVBR Series Direct Vent Gas Fireplace
Hearth
A hearth is not mandatory but is recommended for
aesthetic purposes. We recommend a noncombustible
hearth which projects out 12” (305 mm) or more from
the front of the fireplace.
Cold climate installation recommendation:
When installing this unit against a noninsulated exterior wall or chase, it is
mandatory that the outer walls be insulated
to conform to applicable insulation codes.
Framing and Finishing
Check fireplace to make sure it is levelled
and properly positioned.
NOTE: If the optional Metro Face Kit (DVBR36 only)
is to be installed, the fireplace may be placed on a
4” (102 mm) raised platform. Raising the fireplace
will give the best aestethic appearance but is not
required.
To mount the appliance:
1. Choose the location.
2. Nailing flanges are supplied with the fireplace (found
on the fireplace hearth). To level the box and secure
it firmly in place, remove the nailing flanges from
the hearth and install at the sides of the fireplace as
shown in Figure 5.
Nail Top
Standoffs
Gas Specifications
Max. Min.
Gas Input Input
Model Fuel Control B.T.U.H B.T.U.H.
DVBR36RN Natural Gas Millivolt Hi/Lo 24,000 16,000
DVBR36RP Propane Millivolt Hi/Lo 24,000 17,500
DVBR42RN Natural Gas Millivolt Hi/Lo 27,000 18,000
Input ratings are shown in BTU per hour and are
certified without deration for elevations up to
4,500 feet (1,370m) above sea level.
For elevations above 4,500 feet (1,370m) in USA,
installations must be in accordance with the
current ANSI Z223.1/NFPA 54 and/or local codes
having jurisdiction.
In Canada, please consult provincial and/or local
authorities having jurisdiction for installations at
elevations above 4,500 feet (1,370m).
Gas Line Installation
Nail Sidenailing
Flanges
FP549
Fig. 5 Nailing flanges.
Final Finishing
Noncombustible materials such as brick and tile can be
extended over the black face of the unit (Do not cover
the glass door.) If a Trim Kit is to be installed, brick and
tile will have to be installed flush with the side of this
appliance.
20000584
When purging gas line the front glass must
be removed.
The gas pipeline can be brought in through the right
side of the appliance. Knockouts are provided at convenient locations to allow for the gas pipe installation
and testing of any gas connection.
The gas line connection can be made with 3/8” copper
tubing, 1/2” rigid pipe or an approved flex connector.
Since some municipalities have additional local codes,
it is always best to consult your local authority and the
CSA-B149.1 installation codes. For US installations
consult the current National Fuel Gas Code, ANSI
Z223.1/NFPA 54.
7
DVBR Series Direct Vent Gas Fireplace
OUTSIDE
ELECTRICAL BOX
INSIDE
FRONT OF UNIT
1/2” Gas Supply
1/2” NPT X 1/2” Flare Shut-off Valve
3/8” Flex line
(from valve)
FP297A
Fig. 6 Typical gas supply installation.
Always check for gas leaks with a mild
soap and water solution applied with a
brush no larger than 1” (25 mm). Never
apply soap and water solution with a spray
bottle. Do not use an open flame for leak
testing.
The fireplace valve must not be subjected
to any test pressures exceeding 1/2 psi.
Isolate or disconnect this or any other gas
appliance control from the gas line when
pressure testing.
The gas control is equipped with a captured screw type
pressure test point, therefore it is not necessary to provide a 1/8” test point up stream of the control.
When using copper or flex connector use only approved
fittings. Always provide a union when using black
iron pipe so the gas line can be easily disconnected for
burner or fan servicing. (Fig. 6) See the gas specifications for pressure details and ratings.
Remote Switch Installation
Do not wire the remote ON/OFF wall switch
for this gas appliance into a 120v power
supply.
EB-1 Electrical Box
The fireplace, when installed, must be electrically connected and grounded in accordance with local codes or, in the absence
of local codes, with the current CSA C22.1
Canadian Electrical Code.
For USA installations, follow the local
codes and the national Electrical Code
ANSI/NFPA No. 70.
It is strongly suggested that the wiring of
the EB-1 Electrical Junction Box be carried
out by a licensed electrician.
Ensure that the power to the supply line
has been disconnected before commenc-
ing this procedure.
EB1 (Receptacle) Hook-Up
1. Remove contents from plastic bag. Remove knockout in center of electrical box. Remove coverplate
from fireplace and knockout. Insert connector
through coverplate, plate and box. Screw nut on
connector with screws provided (2) to secure the
coverplate to the plate.
2. Connect black positive wire to brass screw (polar
ized side) of receptacle. The white wire is connected
to chrome screw. The ground wire is connected to
green ground screw of the receptacle. Fit receptacle
into electrical box.
3. Screw cover plate provided to electrical box.
4. Secure receptacle to fireplace.
-
1. Thread wire through the electrical knockout located
on either side of fireplace. Do not cut wire or insula
tion on metal edges. Ensure that wire is protected.
Run the other end to a conveniently located wall
receptacle box.
2. Attach wire to switch and install switch into receptacle box. Attach cover plate to switch.
3. Connect wiring to gas valve. (Fig. 7)
Fig. 7 Remote switch wiring diagram for R models.
Thermopile
Gas Valve
Switch
8
-
FP580
Fig. 9 EB-1 receptacle.
W584-9
20000584
DVBR Series Direct Vent Gas Fireplace
Optional Top Vent Application
The DVBR36/42 fireplace is shipped as a rear vent unit.
If the layout requires a top vent, convert the unit following the steps below.
DVBR36
1. Remove the eight (8) screws securing outer collar
adapter to fireplace. (Be careful not to damage insulation.) (Fig. 10)
2. Set outer collar adapter aside.
Remove
Screws (4)
Outer Collar
Adapter
Flue Pipe
Rear View
6. Secure flue cover to back of flue outlet. Be sure to
replace gasket. (Fig. 12)
7. Install flue pipe to top of unit with four (4) screws. Be
sure to replace gasket. (Fig. 12)
8. Set insulation in back of unit foil side down.
9. Secure outer collar adapter to unit with the round
collar on top, secure with eight (8) screws.
NOTE: Be sure not to damage any gasket material.
Flue Pipe
Flue
Pipe
Replace
Screws
(4)
Foil Side
Insulation
Fig. 12 Replace flue cover and flue pipe.
Replace
Screws (4)
DVT584-604
Remove Screws (4)
DVT584-602
Fig. 10 Remove screws from outer collar adapter.
3. Remove insulation on top of collector box. (Fig. 11)
4. Remove the four (4) screws securing flue cover to
top of unit and remove flue cover. (Fig. 11)
5. Remove the four (4) screws securing flue pipe to
back of unit. Remove flue pipe. (Fig. 11)
Insulation
Remove
Flue
Cover
Flue
Pipe
Remove Screws
(4)
Fig. 11 Remove flue cover and flue pipe.
Screws (4)
DVT584-603
DVT584-605
Fig. 13 Completed conversion.
20000584
9
DVBR Series Direct Vent Gas Fireplace
DVBR42
1. Remove the seven (7) screws securing the heat
shield cover plate to the fireplace. (Fig. a) Discard
the heat shield cover plate.
2. Carefully remove the square piece of insulation
along the perforations. (Fig. b) Discard insulation.
3. Remove the eight (8) screws securing outer collar
adapter to fireplace. (Be careful not to damage insulation.) (Fig. 10)
Remove Insulation
FP1543
Fig. b Remove and discard insulation.
4. Set outer collar adapter aside.
5. Remove insulation on top of collector box. (Fig. 11)
6. Remove the four (4) screws securing flue cover to
top of unit and remove flue cover. (Fig. 11)
7. Remove the four (4) screws securing flue pipe to
back of unit. Remove flue pipe. (Fig. 11)
8. Secure flue cover to back of flue outlet. Be sure to
replace gasket. (Fig. 12)
9. Install flue pipe to top of unit with four (4) screws. Be
sure to replace gasket. (Fig. 12)
10. Set insulation in back of unit foil side down.
11. Secure outer collar adapter to unit with the round
collar on top, secure with eight (8) screws.
NOTE: Be sure not to damage any gasket material.
General Venting
Your fireplace is approved to be vented either through
the side wall, or vertical through the roof.
• Only CFM Corporation venting components specifically approved and labelled for this fireplace
may be used.
• Venting terminals shall not be recessed into a wall or
siding.
• Horizontal venting which incorporates the twist lock
pipe must be installed on a level plane without an
inclining or declining slope.
• Horizontal venting which incorporates the use of flex
venting shall have an inclining slope from the unit of
1/2” (13 mm) per12” (305 mm).
There must not be any obstruction such as bushes,
garden sheds, fences, decks or utility buildings within
24” from the front of the termination hood.
Do not locate termination hood where excessive snow
or ice build up may occur. Be sure to check vent termination area after snow falls, and clear to prevent accidental blockage of venting system. When using snow
blowers, make sure snow is not directed towards vent
termination area.
Location of Vent Termination
It is imperative the vent termination be located observing the minimum clearances as shown on the following
page.
10
20000584
DVBR Series Direct Vent Gas Fireplace
V
V
V
V
V
V
V
X
X
X
D
E
B
B
B
C
B
M
B
A
J
K
F
L
VENT TERMINATION AIR SUPPLY INLET
AREA WHERE TERMINAL IS NOT PERMITTED
H
I
Operable
Operable
Fixed
Closed
V
B
INSIDE
CORNER DETAIL
V
A
G
N
N
CFM145a
General Venting Information - Termination Location
deck, or balcony
B = Clearance to window or door that may be 6” (15cm) for appliances 6” (15cm) for appliances opened < 10,000Btuh (3kW), 12” (30cm) < 10,000 Btuh (3kW), 9” for appliances > 10,000 Btuh (3kW) and (23cm) for appliances > 10,000
< 100,000 Btuh (30kW), 36” (91cm) Btuh (3kW) and < 50,000 Btuh
for appliances > 100,000 Btuh (30kW) (15kW), 12” (30cm) for appliances > 50,000 Btuh (15kW)
C = Clearance to permanently closed window 12” (305mm) recommended to 12” (305mm) recommended to
prevent window condensation prevent window condensation
D = Vertical clearance to ventilated soffit located above the terminal within a horizontal 18” (458mm) 18” (458mm) distance of 2 feet (610mm) from the center line of the terminal
E = Clearance to unventilated soffit 12” (305mm) 12” (305mm)
F = Clearance to outside corner see next page see next page
G = Clearance to inside corner (see next page) see next page see next page
H = Clearance to each inside of center line 3’ (91cm) within a height of 15’ (5m) 3’ (91cm) within a height of 15’
extended above meter/regulator assembly above the meter/regulator assembly (5m) above the meter/regulator
assy
I = Clearance to service regulator vent outlet 3’ (91cm) 3’ (91cm)
J = Clearance to nonmechanical air supply inlet 6” (15cm) for appliances < 10,000 6” (15cm) for appliances to building or the combustion air inlet to any Btuh (3kW), 12” (30cm) for < 10,000 Btuh (3kW), 9” other appliances appliances > 10,000 Btuh (3kW) and (23cm) for appliances > 10,000
< 100,000 Btuh (30kW), 36” (91cm) Btuh (3kW) and < 50,000 Btuh
for appliances > 100,000 Btuh (30kW) (15kW), 12” (30cm) for appliances > 50,000 Btuh (15kW)
K = Clearance to a mechanical air supply inlet 6’ (1.83m) 3’ (91cm) above if within 10’
(3m) horizontally
L = Clearance above paved sidewalk or paved 7’ (2.13m)† 7’ (2.13m)† driveway located on public property
M = Clearance under veranda, porch, deck or 12” (30cm)‡ 12” (30cm)‡ balcony
N = Clearance above a roof shall extend a minimum of 24” (610mm) above the highest point when it passes through the roof
surface, and any other obstruction within a horizontal distance of 18” (450mm).
1 In accordance with the current CSA-B149 Installation Codes
2 In accordance with the current ANSI Z223.1/NFPA 54 National Fuel Gas Codes
† A vent shall not terminate directly above a sidewalk or paved driveway which is located between two single family dwellings and serves both dwellings
‡ only permitted if veranda, porch, deck or balcony is fully open on a minimum 2 sides beneath the floor:
NOTE: 1. Local codes or regulations may require different clearances.
2. The special venting system used on Direct Vent appliances are certified as part of the appliance, with clearances tested and
approved by the listing agency.
3. CFM Corporation assumes no responsibility for the improper performance of the appliance when the venting system does not
meet these requirements.
Fig. 14 Vent termination clearances.
20000584
2
11
DVBR Series Direct Vent Gas Fireplace
Outside Corner
Inside Corner
Termination Clearances
Termination clearances for buildings with combustible and noncombustible exteriors.
G =
Combustible
6" (152 mm)
Noncombustible
2" (51 mm)
F =
Combustible
6" (152 mm)
Noncombustible
2" (51 mm)
G
Balcony with no side wall
M =
Combustible &
Noncombustible
12" (305 mm)
M
Balcony with perpendicular side wall
M = 24" (610 mm)
P = 20” (508 mm)
M
F
Alcove Applications*
C
D
C
E
V
V
Combustible &
Noncombustible
V
V
V
E = Min. 6” (152 mm) for
non-vinyl sidewalls
Min. 12” (305 mm) for
vinyl sidewalls
O = 8’ (2.4 m) Min.
O
P
*NOTE: Termination in an alcove space (spaces open only on one side and with an overhang) is permitted with the dimensions
specified for vinyl or non-vinyl siding and soffits. 1. There must be a 3’ (914 mm) minimum between termination caps. 2. All
mechanical air intakes within 10’ (1 m) of a termination cap must be a minimum of 3’ (914 mm) below the termination cap. 3. All
gravity air intakes within 3’ (914 mm) of a termination cap must be a minimum of 1’ (305 mm) below the termination cap.
Fig. 15 Termination clearances.
Canadian Installations
The venting system must be installed in accordance
with the current CSA-B149.1 installation code.
USA Installations
The venting system must conform to local codes and/or
the current National Fuel Code ANSI Z223.1/NFPA 54.
Only venting components manufactured by CFM Corpo
ration may be used in Direct Vent systems.
General Information Assembling Vent Pipes
* Be sure the vent is actually crushed before proceeding. Apply a tug to be sure the vent will not slip off the
collars.
Repeat process with 7” flex vent pipe. The same procedure must be performed on the vent side.
-
No.
of Caps D
1 3’ (.9 mm) 2 x D
2 6’ (1.8 m) 1 x D
3 9’ (2.7 m) 2/3 x D
4 12’ (3.7 m) 1/2 x D
D
= # of Termination caps x 3
Min.
C
= (2 / # termination caps) x D
Max.
C
Min.
Apply High Temperature
Sealant
Max.
Actual
Actual
Actual
Actual
Actual
584-15
Before joining the flex vent pipe to the unit, apply a
bead of high temperature sealant* (provided) to the 4”
pipe exiting the fireplace. Secure flex vent pipe in place
with a hose clamp (provided).
*Be sure the flex pipe overlaps at least 1” (25mm) onto
the collars of the fireplace and termination. If the termination has an internal bead, be sure to overlap and
secure 1” (25 mm) past the bead.
12
Flex Vent Pipes
Hose Clamp
FP1471
Fig. 16 Apply high temperature sealant to 4” and 7” pipes.
20000584
Twist Lock Pipes
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
3
4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
eg: A
eg: B
When using CFM Corporation twist-lock pipe, it is not
necessary to use silicone to seal the twist-lock joints.
The only areas that need silicone are the collars on the
fireplace, the telescoping pipe (if used) and the horizontal termination connection (when necessary). The
female (flared) end secures to the fireplace first with the
male end away from the fireplace.
To join the pipes together, simply align the beads of the
male end with the grooves of the female end, twisting
the pipe until the flange on the female end touches the
external bead on the male end. Secure the joints with
three (3) sheet metal screws. (Fig. 17)
To make assembly easier, apply lubricant (vaseline or
similar) on the male end of the twist-lock pipe.
DVBR Series Direct Vent Gas Fireplace
Vertical Dimension from the Floor of the Unit
to the Center of the Horizontal Vent Pipe
Male End
Screw Holes
Fig. 17 Twist-Lock pipe joints.
How to Use the Vent Graph
The Vent Graph should be read in conjunction with the
following vent installation instructions to determine the
relationship between the vertical and horizontal dimensions to the vent system.
1. Determine the height of the center of the horizontal
vent pipe exiting through the outer wall. Using this
dimension on the Sidewall Vent Graph (Fig. 18),
locate the point intersecting with the slanted graph
line.
2. From the point of this intersection, draw a vertical
line to the bottom of the graph.
3. Select the indicated dimension, and position the
fireplace in accordance with same.
EXAMPLE A:
If the vertical dimension from the floor of the unit is 11
feet (3352 mm) the horizontal run to the face of the
outer wall must not exceed 14’ (4267 mm).
EXAMPLE B:
If the vertical dimension from the floor of the unit is 7’
(2133mm), the horizontal run to the face of the outer
wall must not exceed 8¹⁄₂’ (2590 mm).
20000584
Female
End
TWL100
Horizontal Dimension from the Outside Face of the
Wall to the Center of the Fireplace Vent Flange
DV Graph
Fig. 18 Sidewall venting graph. (Dimensions in feet.)
Refer to Page 19 for venting
requirements for snorkels.
Rear Wall Vent Applications
When installed as a rear vent unit this appliance may be
vented directly to a termination located on the rear wall
behind the appliance.
• Only CFM Corporation venting components are ap-
proved to be used in these applications (See ‘Venting
Components’ listed for different installation requirements).
• The maximum horizontal distance between the rear
of the appliance (or end of the transition elbow in a
corner application) and the outside face of the rear
wall is 20” (508mm). (Fig. 19, 20 )
• Only one 45° elbow is allowed in these installations.
Locate and cut the vent opening in the wall.
For combustible walls first frame in opening. (Fig. 21)
NOTE: When using flex vent, the opening will have to
be measured according to the 1” (25 mm) rise in 24”
(610 mm) vertical run.
Combustible Walls:
Cut a 10³⁄₈”H x 9³⁄₈” W (265 mm
x 240 mm) hole through the exterior wall and frame as
shown. (Fig. 21)
Noncombustible Walls:
Hole opening should be 7¹⁄₂”
(191 mm) diameter.
Zero clearance sleeve is only required for
combustible walls.
Step 2
Measure wall thickness and cut zero clearance sleeve
parts to proper length (Maximum 12” / 305mm). Assemble sleeve to its maximum opening (10³⁄₈” x 9³₈”)
and attach to firestop assembly. (Fig. 22)
Step 3
Measure the horizontal length requirement for the venting including a 2” (51 mm) overlap, i.e. from the elbow
to the outside wall face plus 2” (51 mm). (Fig. 20)
Fireplace Hearth
Vent Opening - Noncombustible Wall
7¹⁄₂" Dia.
(191 mm)
Fireplace Hearth
Fig. 21 Locate vent opening on wall.
#8 Screws (2)
#8 Screws
(2)
Adjustable Zero
Clearance Sleeve
Fig. 22 Adjustable zero clearance sleeve.
VO584-100
Max. Length
12” (294 mm)
#8 Screws (2)
Firestop
CFM135a
Step 4
Install the 4” (102 mm) vent to the appliance collar and
secure with three (3) sheet metal screws. Install the 7”
(175 mm) vent pipe to the appliance collar and secure
with three (3) sheet metal screws. It is not necessary to
seal this connection. If a 45° elbow is being used attach
the elbow to the appliance in the same manner then attach the venting to the elbow.
It is critical that there is no downward
slope away from the appliance when connecting the vent or elbow.
Step 5
Guide the venting through the vent hole as you place
the appliance in its installed position. Guide the 4”
(102 mm) and 7” (175 mm) collar of the vent termination into the outer ends of the venting. Do not force
the termination. If the vent pipes do not align with the
termination, remove and realign the venting at the appliance flue collars. (Fig. 23) Attach the termination to the
wall as outlined in the instruction sheet supplied with
the termination.
14
20000584
Finished
1/2" (13mm)
12" (305mm)
Wall
DVBR Series Direct Vent Gas Fireplace
These ends
screwed to appliance
Fig. 23 Side view of final unit location, twist lock pipe.
These ends should
be even
Vent
Termination
FP1005
Rear Wall Vent Installations -
Flex Vent Pipe
Follow Steps 1 and 2 on Page 14.
Step 3
Install the 4” (102 mm) flex vent pipe to the appliance
collars described in “General Information Assembling
Vent Pipes”, Page 12. If the installation requires a 45°
angle, grasp the vent pipe close to the appliance collar
and bend to 45°. DO NOT exceed 45°. (Fig. 24)
Termination
Flex Section
Appliance Collars
FP1473
Fig. 24 Grasp the vent pipe close to the collar and bend to
45° angle. Do not exceed 45°.
Install the 7” vent pipe in the same manner as Step 2.
NOTE: There must be a 1” (25 mm) rise in 24”
(610 mm) length of flex vent.
Step 4
Assemble the flex vent to the collars on the termination
as you did on the appliance.
FP1472
Fig. 25 There must be a 1” rise in 24” length.
Vertical Sidewall Applications
Since it is very important that the venting system
maintain its balance between the combustion air
intake and the flue gas exhaust, certain limitations
as to vent configurations apply and must be strictly
adhered to.
The Vent Graph, showing the relationship between ver
tical and horizontal side wall venting, will help to determine the various dimensions allowable.
Minimum clearance between vent pipes and combustible materials is 1” (25 mm) on top, bottom and
sides unless otherwise noted.
When vent termination exits through foundations less
than 20” (508mm) below siding outcrop, the vent pipe
must flush up with the siding.
It is best to locate the fireplace in such a way that mini
mizes the number of offsets and horizontal vent length.
The horizontal vent run refers to the total length of vent
pipe from the flue collar of the fireplace (or the top of
the Transition Elbow) to the face of the outer wall.
Horizontal plane means no vertical rise exists on this
portion of the vent assembly.
When installing the appliance as a rear
vent unit, the 90° or 45° Transition Elbow
attached directly to the rear of the unit is
NOT INCLUDED in the following criteria
and calculations, and unless specifically
mentioned should be ignored when calculating venting layouts.
• The maximum number of 90° elbows per side wall
installation is three (3). (Fig. 26)
• If a 90° elbow is fitted directly on top of the fireplace
flange the maximum horizontal vent run before the
termination or a vertical rise is 36” (914mm). (Fig.
27)
-
-
20000584
15
DVBR Series Direct Vent Gas Fireplace
1
2
3
4
1
2
3
4
36"
(914mm)
Max.
36"
(914mm)
Max.
7'6"
A
B
90
o
A + B = 17' (Max.)
3 x 90°
Elbows
FP1176
Fig. 26 Maximum three (3) 90° elbows per installation.
Fig. 27 Maximum horizontal runwith no rise.
3 x 90°
Elbows
FP1177
• If a 90° elbow is used in the horizontal vent run
(level height maintained) the horizontal vent length
is reduced by 36” (914mm). (Fig. 28, 29) This does
not apply if the 90° elbows are used to increase or
redirect a vertical rise. (Fig. 26)
Example: According to the vent graph (Page 15) the
maximum horizontal vent length in a system with a
7¹⁄₂” (191mm) rise is 20” (508mm) and if a 90° elbow is
required in the horizontal vent it must be reduced to 17’
(5.2m).
7’
A
10’
(254cm)
A + B = 17’ Max.
8’
(244cm)
Fig. 29 Maximum vent run with elbows.
(178cm)
B
V584-201
In Figure 28 & 29, dimension A plus B must not be
greater than 17’ (5.2m)
• The maximum number of 45° elbows permitted per
side wall installation is two (2). These elbows can be
installed in either the vertical or horizontal run.
• For each 45° elbow installed in the horizontal run,
the length of the horizontal run MUST be reduced by
18” (457mm). This does not apply if the 45° elbows
are installed on the vertical part of the vent system.
Locate vent opening on the wall. It may be necessary
to first position the fireplace and measure to obtain hole
location. Depending on whether the wall is combustible
or noncombustible, cut opening to size. (Fig. 31) (For
combustible walls first frame in opening.)
NOTE: When using flex vent, the opening will have to
be measured according to the 1” (25 mm) rise in 24”
(610 mm) vent run.
Combustible Walls:
238mm) hole through the exterior wall and frame as
shown. (Fig. 31)
Noncombustible Walls:
(191 mm) in diameter.
Vent Opening Combustible Wall
9³⁄₈”
(240mm)
Cut a 9³⁄₈”H x 9³⁄₈”W (238mm x
Hole opening must be 7¹⁄₂”
9³⁄₈”
(240mm)
Max. Length
12” (294 mm)
#8 Screws (2)
Firestop
#8 Screws (2)
#8 Screws
(2)
Adjustable Zero
Clearance Sleeve
Fig. 32 Adjustable zero clearance sleeve.
CFM135a
Step 4
Apply a band of silicone to the inner and outer flue
collars of the fireplace and using appropriate length of
pipe section(s) attach to fireplace with three (3) screws.
Follow with the installation of the inner and outer elbow,
again secure joints as described in the “Connecting
Vent Pipe” section.
Framing Detail
Fireplace Hearth
Vent Opening Non-
combustible Wall
7¹⁄₂” Dia.
(190mm)
Fireplace Hearth
Fig. 31 Locate vent opening on wall.
Step 2
VO584-100
FP1181
Fig. 33 Vertical height requirements.
Measure wall thickness and cut zero clearance sleeve
parts to proper length (MAXIMUM 12” / 305mm). Assemble sleeve and attach to firestop with #8 sheet
metal screws (supplied). Install firestop assembly. (Fig.
29)
Zero clearance sleeve is only required for
combustible walls.
Step 5
Measure the horizontal length requirement including a
2” (50mm) overlap, i.e. from the elbow to the outside
wall face plus 2” (50mm) (or the distance required if
installing a second 90° elbow). (Fig. 34)
Always install horizontal venting on a level
plane.
Step 3
Place fireplace into position. Measure the vertical height
(X) required from the base of the flue collars to the center of the wall opening. (Fig. 33)
Step 6
Use appropriate length of pipe sections - telescopic or
fixed - and install. The sections which go through the
wall are packaged with the starter kit, and can be cut to
suit if necessary.
20000584
17
DVBR Series Direct Vent Gas Fireplace
X
X
12"
(305mm)
6"
(152mm)
5"
(127mm)
6"
(172mm)
6" (165mm)
Sealing vent pipe and firestop gaps with high temperature sealant will restrict cold air being drawn in
around fireplace.
FP1182
Fig. 34 Horizontal length requirement.
Step 7
Apply high temperature sealant to 4” (102 mm) and
7” (175 mm) collars or the termination one inch away
from crimped end. Guide the vent terminations 4” and
7” collars into their respective vent pipes. Double check
that the vent pipes overlap the collars by 2” (51 mm).
Secure the termination to the wall with screws provided
and caulk around the wall plate to weatherproof. As an
alternative to screwing the termination directly to the
wall, you may also use expanding plugs or an approved
exterior construction adhesive. You may also attach the
termination with screws through the inner body into the
4” vent pipe, however for this method, you must extend
the 4” pipe approximately 6” (152 mm) beyond the outer
face of the wall.
Support horizontal pipes every 3’ (91 cm)
with metal pipe straps.
Vertical Sidewall Installation
Flex Vent Pipe
spring 5” (127 mm) from the previously installed spring.
Place the next spring 6” (152 mm) from the last spring.
Finally place the last spring 12” (305 mm) from the last
spring installed. (Fig. 35)
4” Flex Vent
Pipe
Spacer
Spring
FP1474
Fig. 35 Install spacer springs.
Step 4
Install the 4” (102 mm) flex vent pipe to the appliance
collar as described on Page 12. Secure the end with the
first spring 6³⁄₄” (172 mm) from the flex pipe end to the
unit.
Step 5
Slide the 7” (178 mm) flex vent pipe over the 4” flex
vent pipe and secure the 7” collar as described on Page
12.
Step 6
Bend the flex pipe horizontal so the bottom of the
horizontal pipe measure 6¹⁄₂” (165 mm) from the top of
the unit immediately after the 90° formation. (Fig. 36)
Be sure to follow the 1” (25 mm) rise in a 24” (610 mm)
horizontal run rule.
Step 7
Install the 4” flex then 7” flex to the termination.
NOTE: The 40” (1016 mm) flex vent is used for 90° off
the top of the unit then out the back wall.
Follow Step 1 and 2 on Page 17.
Step 3
Install the four (4) spacer springs on the 4” flex vent
pipe. When installing the spacer springs around the 4”
pipe, stretch the spring to approximately 15” (381 mm),
wrap the spring around the pipe and interlock the ends
of the spacer spring approximately 2” (51 mm). Measure
6³⁄₄” (172 mm) from the end of the pipe. Place
18
the next
FP1475
Fig. 36 Bend flex vent at 90° so horizontal portion is 6¹⁄₂”
(165 mm) off top of unit.
20000584
DVBR Series Direct Vent Gas Fireplace
Below Grade Installation
When it is not possible to meet the required vent terminal
clearances of 12” (305 mm) above grade level, a snorkel
kit is recommended. It allows installation depth down
to 7” (178 mm) below grade level. The 7” (178 mm) is
measured from the center of the horizontal vent pipe as it
penetrates through the wall.
Ensure the sidewall venting clearances are observed. If venting system is installed below ground,
we recommend a window well with adequate and
proper drainage to be installed around the termination area.
If installing a snorkel, a minimum 24” (610 mm) vertical
rise is necessary. The maximum horizontal run with the
24” vertical pipe is 36” (914 mm). This measurement
is taken from the collar of the fireplace (or transition
elbow) to the face of the exterior wall. See the Sidewall
Venting Graph for extended horizontal run if the vertical
exceeds 24” (610 mm).
1. Establish vent hole through the wall (Fig. 31)
2. Remove soil to a depth of approximately 16”
(406mm) below base of snorkel. Install drain pipe.
Install window well (not supplied). Refill hole with 12”
(305mm) of coarse gravel leaving a clearance of approximately 4” (102 mm) below snorkel. (Fig. 37)
3. Install vent system.
4. Ensure a watertight seal is made around the vent
pipe coming through the wall.
5. Apply high temperature sealant caulking (supplied)
around the 4” and 7” snorkel collars.
6. Slide the snorkel into the vent pipes and secure to
the wall.
7. Level the soil so as to maintain a 4” (102 mm) clear
ance below snorkel. (Fig. 37)
Zero Clearance
Sleeve if Required
Firestop
7” Pipe
Foundation Wall
* A minimum of 24” (608
mm) vertical pipe must be
installed when using the
7TDVSKS kit.
Fig. 37 Below grade installation.
7DVSK (Snorkel)
4” Clearance
Min.
Window
Well
Gravel
Drain
BG400
-
Do not back fill around snorkel.
A clearance of at least 4” must be main
-
tained between the snorkel and the soil.
If the foundation is recessed, use recess brackets (not
supplied) for securing lower portion of the snorkel. Fasten brackets to wall first, then secure to snorkel with self
drilling #8 x 1/2 sheet metal screws. It will be necessary
to extend vent pipes out as far as the protruding wall
face. (Fig. 38)
• Vertical installations up to 40’ (12m) in height. Up
to a 10’ (3 m) horizontal vent run can be installed
within the vent system using a maximum of two 90°
elbows. (Fig. 41)
• Up to two 45° elbows may be used within the hori-
zontal run. For each 45° elbow used on the horizontal plane, the maximum horizontal length must be
reduced by 18” (450mm).
Example: Maximum horizontal length:
No elbows = 10’ (3 m)
1 x 45° elbow = 8.5’ (2.6 m)
2 x 45° elbows = 7’ (2.1 m)
• A minimum of an 8’ (2.5 m) vertical rise is required.
• Two sets of 45° elbow offsets may be used within the
vertical sections. From 0 to a maximum of 8’ (2.5 m)
of vent pipe can be used between elbows. (Fig. 42)
• 7DVCS supports offsets. (Fig. 44) This application
will require that you first determine the roof pitch
and use the appropriate starter kit. (Refer to Venting
Components List)
• The maximum angular variation allowed in the sys-
tem is 270°. (Fig. 42)
• The minimum height of the vent above the highest
point of penetration through the roof is 2’ (610mm).
(Fig. 45) Refer to Note 2, Page 11.
20000584
19
DVBR Series Direct Vent Gas Fireplace
1
2
3
4
1
2
3
4
Max. Height 40’ (12.2m)
Min. Height 8’ (2.4m)
Max. 10’ (3m)
Max. Height
40’ (12.2m)
Min. Height 8’
(2.4m)
Max. 10’ (3m)
5. Place firestop(s) #7DVFS into position and secure.
(Fig. 43)
6. Install roof support (Fig. 44) and roof flashing
making sure upper flange of flashing is below the
shingles. (Fig. 46)
7. Install appropriate pipe sections until above the
flashing. (Fig. 46)
8. Install storm collar and seal around the pipe.
9. Add additional vent lengths for proper height.
10. Apply high temperature sealant to 4” and 7” collars
of vent termination and install.
If there is a room above ceiling level, firestop spacers
must be installed on both the bottom and the top side
of the ceiling joists. If an attic is above ceiling level
a 7DVAIS (Attic Insulation Shield) must be installed.
The enlarged ends of the vent section always face
downward.
Attic Insulation Shield
FP1183
Fig. 41 Support straps for horizontal runs.
1 + 2 + 3 + 4 = 270°
Fig. 42 Maximum elbow usage.
11”
Joist
Ceiling
Installation
VR404
Fig. 43 Place firestop spacer(s) and secure.
FP1179
11”
Upper Floor
Firestop
Spacer
Nails (4)
Vertical Through-the-Roof Installation
1. Locate your fireplace.
2. Plumb to center of the (4”) 90° transition elbow
(7DVRT90) from ceiling above and mark position.
3. Cut opening equal to 9³⁄₈" x 9³⁄₈" (240 x 240 mm).
4. Proceed to plumb for additional openings through
the roof. In all cases, the opening must provide a
minimum of 1” (25 mm) clearance to the vent pipe,
i.e., the hole must be a minimum of 9³⁄₈" x 9³⁄₈" (240
Fig. 44 Venting supports.
x 240 mm).
20
Typical Roof
Support Ap-
plication
Typical Ceiling Sup
port Application
-
FP1184
20000584
DVBR Series Direct Vent Gas Fireplace
Min.
2' (610 mm)
Fig. 45 Minimum termination to roof clearance.
FP1185
Sealant
Fig. 46 Roof flashing.
3 #5 Sheet
Metal Screws
per Joint
Storm
Collar
3 #5 Sheet
Metal Screws
per Joint
Sealant
Storm
Collar
TWL101a
20000584
21
DVBR Series Direct Vent Gas Fireplace
Venting Components
7TDVRVT - Through the wall Rear Vent Termination
Starter Kit Model 7TDVSK - Sidewall Venting (Twist Lock Pipe)
Model 7FDVSK - Sidewall Venting (Flex Vent Pipe)
Model 7TTVTK/TV Hot Touch Termination Kit
Model 7TDVTVTK/TV Cool Touch Termination Kit
Starter Kit - Model 7TDVSKV - Vertical Venting
for 7TDVSKV-A order 1/12 to 6/12 roof pitch
for 7TDVSKV-B order 7/12 to 12/12 roof pitch
for 7TDVSKV-F order flat roof
Starter Kit for Below Grade Installation
Model 7TDVSKS -Snorkel Kit (Twist Lock Pipe)
Model 7FDVSKS -Snorkel Kit (Flex Vent Pipe)
Starter Pipe
Model 7TDVP 20/8 - 24” Starter Pipe Bulk
Model 7FDVP 30/8 - 30” Flex Pipe Bulk
45o Elbow
7TDV45 for Rear Vent to Vertical Vent
or Vertical/Horizontal Offsets
90o Transition Elbow
7TDVRT90 for Rear Vent to Vertical Vent
90° Elbow
7TDV90 Vertical/Horizontal Offset
Telescopic vent sections
7TDVP1117 -11” to 17” adjustable length
7TDVP3567 -35” to 67” adjustable length
Pipe sections for vertical or horizontal venting
Model 7TDVP8” - 4 per box
Model 7TDVP12” - 4 per box
Model 7TDVP24” - 4 per box
Model 7TDVP36”
Model 7TDVP48”
Firestop Spacer
Model 7DVFS
Attic Insulation Shield
Model 7DVAIS
22
Vertical/Horizontal Combination Offset Support
Model 7DVCS
20000584
Operating Instructions
Glass Information
DVBR Series Direct Vent Gas Fireplace
Only glass approved by CFM Corporation
may be used for replacement.
• The use of any non-approved replacement glass will
void all product warranties.
• Care must be taken to avoid breakage of the glass.
• Do not operate appliance with glass front
removed, cracked or broken.
• Replacement glass (complete with gasket) is
available through your CFM Corporation dealer
and should only be installed by a licensed
qualified service person.
Glass Frame Removal
1. Turn off gas.
2. Let the fireplace cool if it has been operating.
3. Remove valve cover. (Fig.47)
4. Release the two (2) clamps at the bottom of the
window frame by pulling back on the clamp handles.
(Fig. 48)
5. Lift off the glass frame as shown. (Fig. 48)
6. To reinstall glass follow the above procedure in re
verse.
Valve Cover
-
Glass Frame
Fireplace
Front
Clamps
Glass
Panel
Glass
Panel
Pull Clamp
Hook
G584-501
Fig. 48 Glass panel removal.
two or three times with a non-ammonia household
cleaner and warm water (gas fireplace glass cleaner
is recommended). After initial use glass should be
cleaned two or three times during heating season.
Clean glass after first two weeks of
operation.
Do not clean glass when hot.
Do not use abrasive cleaners.
Do not strike or slam the glass.
Replacement of Ceramic Hearth Panels
Valve
Pins
Locating Holes
G584-500
Fig. 47 Valve cover location.
Glass Cleaning
It is necessary to clean the glass periodically. During
start-up condensation, which is normal, forms on the
inside of the glass and causes lint, dust and other
airborne particles to cling to the glass surface. Also
initial paint curing may deposit a slight film on the glass.
It is therefore recommended the glass be cleaned
20000584
1. Remove glass.
2. Remove two (2) hex nuts securing grate to hearth
pan. (Fig. 49)
3. Set left and right panels on hearth and bring towards
front of unit.
4. Replace grate assembly.
Grate
Hearth Panels
Fig. 49 Hearth panel location.
Burner
Front of Unit
H100
23
DVBR Series Direct Vent Gas Fireplace
Installation of Logs
Log Chart
Logs DVBR36 DVBR42
Left Log 20008817 20008508
Right Log 20008819 20008510
Right Rear Log 20008818 20008509
Left Cross Log 20008820 20008515
Log Top Right -- B29
Right Cover Log 20008822 20008515
Left Rear Log 20008513 20008816
Center Log 20008821 20008514
Left Front Log 20008823 20008823
Left Cover Log 20008512 20008512
1 . Remove front glass. (See “Glass Remov-
al” Section, Fig. 48)
2. Remove logs from packaging.
As with all plastics — these are
not toys and should be kept
away from children and infants.
3. Place Right Rear Log onto the two pem
studs on the rear log support. Place the
Left Rear Log on the left side of the rear
log support and push the log up against
the Right Rear Log. (Fig. 50)
4. Place the Left Log on the pem studs on
the left side of the burner. Place the Right
Log on the pem studs on the right side of
the burner. (Fig. 51)
5. Place the front edge of the Left Cover
Log on the front top edge of the burner
between the last two left tines of the
grate. Allow the bottom edge of the log to
sit on the hearth. Place the Right Cover
Log between the right two tines and rest
the log up against the front face of the
burner. (Fig. 52)
6. Place the Center Log between the second and third tines as shown. Place the
v-notch on the left side of the Center Log
against the left tine of the grate. Rest the
right side of the Center log up against the
face of the Right Log. (fig. 52)
7. Place the left Cross Log over the pin of
the Right Rear Log and the pin of the Left
Log. (Fig. 3)
8. DVBR42 only. Place the Right Cross Log
over the Right Rear Log and the Right
Log as shown. (Fig. 53) When positioned
correctly, the right rear flame will come up
through the hole in the Right Cross log.
Carefully adjust the log as needed to allow the flame to come through the hole.
Left Rear
Log
Fig. 50 Place Right and Left Rear Logs on rear log support.
Fig. 51 Place Left and Right Logs on pem studs on burner.
Ember Material Placement
Separate the ember material into small pieces, roughly
1/2” in diameter and place onto the burner in front of
the front logs. Do NOT pack down, leave in fluffy, loose
condition for most realistic ember effect.
Lava Rock
The lava rock provided with this fireplace must be placed
on the firebox base around the burner assembly.
Under no circumstances should this lava
rock be placed on any part of the burner
assembly.
Right Rear Log
LG340
Right Log
Left Log
LG390
24
20000584
DVBR Series Direct Vent Gas Fireplace
L
O
H
I
Turn
counterclockwise
to increase
flame height
Turn clockwise
to decrease
flame height
Turn
counterclockwise
to decrease
flame height
Turn clockwise
to increase
flame height
Right Cover
Log
Flame & Temperature Adjustment
For fireplaces equipped with Hi/Lo valves,
flame adjustment is accomplished by rotating
the Hi/Lo adjustment knob located near the
centre of the gas control. (Fig. 54 & 55)
Flame Characteristics
It is important to periodically perform a visual
check of the pilot and the burner flames.
Compare them to Figures 56, 57 & 58. If any
of the flames appear abnormal call a service
person.
Center Log
Left Cover Log
Fig. 52 Place Left and Right Cover Logs and Center Log on grate.
Log Top Right
Left Cross Log
(DVBR42 ONLY)
LG391
Inspecting the Venting System
This appliance venting system was designed
and constructed to develop a positive flow
adequate to remove flue gases to the outside
atmosphere.
Any foreign objects in the venting system,
except those designed specifically for the
venting system, may cause spillage of flue
gases.
To inspect the venting system, make sure the
main gas valve is off. Remove glass frame
(See Glass Frame Removal Section). Using
a flashlight, check the area above the baffle
in the combustion dome. Clean if necessary.
Fig. 53 Place Left Front Log, Left Cross Log and Log Top Right.
Fig. 54 Flame adjustment knob for Honeywell valve.
20000584
Left Front Log
Top logs must be placed properly onto
notches.
HV102
LG392
Fig. 55 flame adjustment knob for SIT valve.
3/8” - 1/2”
Fig. 56 Correct pilot flame appearance.
25
DVBR Series Direct Vent Gas Fireplace
LG389
Fig. 57 Correct flame appearance for DVBR36 model.
26
LG387
Fig. 58 Correct flame appearance for DVBR42 model.
20000584
Lighting and Operating Instructions
PILOT
ON
OFF
ON
P
I
L
O
T
O
F
F
O
F
F
5
4
3
2
1
O
F
F
P
i
l
o
t
3/8" - 1/2"
FOR YOUR SAFETY READ BEFORE LIGHTING
WARNING:If you do not follow these instructions exactly, a fire or explosion
may result causing property damage, personal injury or loss of life.
A. This heater has a pilot which must be lit manu-
ally. When lighting the pilot follow these instructions exactly.
B. BEFORE LIGHTING smell all around the
heater area for gas. Be sure to smell next to
the floor because some gas is heavier than air
and will settle on the floor.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any fireplace
• Do not touch any electric switch
• Do not use any phone in your building
• Immediately call your gas supplier from a
Lighting Instructions
DVBR Series Direct Vent Gas Fireplace
neighbor’s phone. Follow the gas supplier’s
instructions.
• If you cannot reach your gas supplier, call
the Fire Department
C. Use only your hand to push in or turn the gas
control knob. Never use tools. If the knob will not
push in or turn by hand, do not try to repair it, call a
qualified service technician. Applying force or any
attempted repair may result in a fire or explosion.
D. Do not use this fireplace if any part has been under
water. Immediately call a qualified service technician to inspect the heater and to replace any part of
the control system and any gas control which has
been under water.
1. STOP! Read the safety information above.
2. Turn off all electrical power to the fireplace.
3. For MN/MP/TN/TP appliances ONLY, go on to
Step 4. For RN/RP appliances turn the On/Off
switch to “OFF” position or set thermostat to
lowest level.
4. Open control access panel.
5. Push in gas control knob slightly and turn
clockwise to “OFF”.
Euro SITSIT NOVA
Honeywell
6. Wait five (5) minutes to clear out any gas. Then
smell for gas, including near the floor. If you
smell gas, STOP! Follow “B” in the safety information above. If you do not smell gas, go to the
next step.
7. Remove glass door before lighting pilot. (See
Glass Frame Removal section).
8. Visibly locate pilot by the main burner.
9. Turn knob on gas control counterclockwise
to “PILOT”.
10. Push the control knob all the way in and hold.
Immediately light the pilot by repeatedly depressing the piezo spark ignitor until a flame appears.
Continue to hold the control knob in for about one
(1) minute after the pilot is lit. Release knob and it
will pop back up. Pilot should remain lit. If it goes
out, repeat steps 5 through 8.
• If knob does not pop up when released,
stop and immediately call your service technician or gas supplier.
• If after several tries, the pilot will not stay
lit, turn the gas control knob to “OFF” and call
your service technician or gas supplier.
11. Replace glass door.
12. Turn gas control knob to “ON” position.
13. For RN/RP appliances turn the On/Off switch
to “ON” position or set thermostat to desired
setting.
14. Turn on all electrical power to the fireplace.
To Turn Off Gas To Heater
1. Turn the On/Off switch to Off position or set the
thermostat to lowest setting.
2. Turn off all electric power to the fireplace if
service is to be performed.
20000584
3. Open louvre assembly bottom.
4. Push in gas control knob slightly and turn clockwise to “OFF”. Do not force.
5. Close control access panel.
27
DVBR Series Direct Vent Gas Fireplace
Troubleshooting – Honeywell VS8421
Remove window frame assembly before service work
STARTCHECK
Gas Supply On
YES
Pilot Lights With Piezo
Ignitor
YES
PILOT STAYS LIT
NO
NO
NO
• Supply Line Hooked Up
• Shutoff Valve Open
• Lockout Has Engaged. Wait 60
Seconds And Try Again.
• For Spark At Electrode While
Depressing Piezo
1/8" Gap To Pilot Hood Needed.
• All Wiring Connections
• Replace Piezo Ignitor
• For Air In The Lines
• Thermopile Needs A Min.
325mv. Adjust Pilot Flame
Height.
• All Wiring Connections
• Replace Thermopile
• Thermocouple Needs A Min. Of
14mv
28
YES
PILOT LIGHTS MAIN
BURNER
YES
SYSTEM OK
NO
• Valve Is Turned On
• Wall Switch Is Not Turned On.
Watch For Grounded Wires!
• Thermopile Needs A Min. 325mv.
• Plugged Burner Orifice
• Defective Valve. Turn To Pilot,
Meter Should Read Greater Than
100mv. If Not, Replace.
20000584
DVBR Series Direct Vent Gas Fireplace
Troubleshooting the Gas Control System
SIT NOVA 820 MILLIVOLT VALVE
Note: Before trouble shooting the gas control system, be sure external gas shut off is in the “On” position.
WARNING: BEFORE DOING ANY GAS CONTROL SERVICE WORK, REMOVE GLASS FRONT.
SYMPTOM POSSIBLE CAUSES CORRECTIVE ACTION
1. Spark ignitor will not light A. Defective or misaligned Using a match, light pilot. If pilot lights, turn off
electrode at pilot. pilot and push the red button again. If pilot will not
light - check gap at electrode and pilot-should be
1/8” to have a strong spark.
B. Defective ignitor (Push Button) Push Piezo Ignitor Button. Check for spark at electrode and pilot. If no spark to pilot, and elec
trode wire is properly connected, replace ignitor.
2. Pilot will not stay lit after A. Defective pilot generator Check pilot flame. Must impinge on thermo
carefully following lighting (thermocouple), remote wall couple/thermopile. Note: this pilot burner assem
instructions. switch. bly utilizes both-a thermocouple and a thermopile.
The thermocouple operates the main valve operation (On and Off). Clean and or adjust pilot for
maximum flame impingement on thermopile and
thermocouple.
B. Defective automatic valve Turn valve knob to “Pilot”. Maintain flow to pilot;
milivolt meter should read greater than 10 mV. If
the reading is okay and the pilot does not stay on,
replace the gas valve. Note: An interrupter block
(not supplied) must be used to conduct this test.
3. Pilot burning, no gas to A. Wall switch or wires defective Check wall switch and wires for proper connec
main burner tions. Jumper wire accross terminals at wall switch, if burner comes on, replace defective wall
switch. If okay, jumper wires across wall switch
wires at valve, if burner comes on, wires are faulty
or connections are bad.
B. Thermopile may not be 1. Be sure wire connections from thermopile at
generating sufficient gas valve terminals are tight and thermopile is
millivoltage. fully inserted into pilot bracket.
2. One of the wall switch wires may be grounded.
Remove wall switch wires from valve terminals if
pilot now stays lit, trace wall switch wiring for
ground. May be grounded to fireplace or gas
supply.
3. Check thermopile with millivolt meter. Take reading at thermopile terminals of gas valve.
Should read 250-300 millivolts (minimum 150)
while holding valve knob depressed in pilot position and wall switch “Off”. Replace faulty
thermopile if reading is below specified minimum.
C. Plugged burner orifice. Check burner orifices for debris and remove.
D. Defective automatic valve Turn valve knob to “On”, place wall switch to “On”
operator. millivolt meter should read greater than 100 mV. If
the reading is okay and the burner does not come
on, replace the gas valve.
4. Frequent pilot outage A. Pilot flame may be too low Clean and/or adjust pilot flame for maximum flame
problem. or blowing (high) causing the impingement on thermopile and thermocouple.
pilot safety to drop out.
B. Possible blockage of the vent Check the vent terminal for blockage (recycling the
terminal. flue gases)
20000584
29
DVBR Series Direct Vent Gas Fireplace
L
O
H
I
L
O
H
I
A
B
C
O
F
F
P
I
L
O
T
O
D
E
F
O
F
F
P
I
L
O
T
O
Fuel Conversion Instructions
To convert the DVBR unit from one gas type to another
follow these instructions:
1. Remove control cover to gain access to valve.
Remove glass door. (See “Glass Frame Removal”,
Page 23, Fig. 48)
2. Remove logs if previously installed.
Valve Conversion - Honeywell Valve
3. Remove cap from HI/LO knob. This can be accomplished by lifting the plastic cap off the screw. (Fig.
59)
4. Remove the screw from center of HI/LO knob with
small screwdriver turning counterclockwise. (Fig. 59)
Cap
Lift Open
Remove
Center Screw
CO100
Hi-Lo Knob
Fig. 59 Remove center screw from Hi-Lo knob.
5. Insert conversion screw (supplied in conversion kit)
in center of HI/LO knob. Blue for natural gas, red for
LP.
6. Tighten screw, replace cap.
Valve conversion is complete.
Valve Conversion - SIT Valve
1. Using the TORX T20 bit, remove and discard the
three (3) pressure regulator mounting screws (A),
pressure regulator tower (B) and the spring and
diaphragm assembly (C(). (Fig. 60) NOTE: If the
conversion is for the 822 electronic valve, cut the
metal tab off the regulator as shown in Figure 60.
2. Insure the rubber gasket (D) is properly positioned
and install the new HI/LO pressure regulator assembly to the valve using the new screws (E) supplied
with the kit. Tighten the screws securely. (Ref. torque
= 25 in/lb) (Fig. 60)
3. Install the enclosed conversion label (F) to the valve
Valve conversion is complete.
Burner Orifice Conversion
1. Unscrew manifold assembly from burner using 3/4”
2. Remove burner orifice from manifold assembly using
3. Remove air shutter from burner pan by removing
30
body where it can easily be seen. (Fig. 60)
wrench. (Fig. 61)
1/2” wrench. (Fig. 62)
shutter retaining screw then air shutter. (Fig. 63)
Cut here
for 822
Valve
FC107/108
Fig. 60 Remove mounting screws, pressure regulator tower
and spring and diaphragm assembly. Replace regulator.
Manifold
Assembly
Orifice
Burner Pan
Log Support
Pilot
CO101
Fig. 61 Remove manifold assembly.
4. For conver-
Burner
Orifice
sion to Natural
Gas remove the
manifold mounting
bracket. Replace
CO102
Fig. 62 Remove burner orifice,
replace with conversion orifice.
the nut and screw
removed earlier.
Attach the air shut-
ter to the burner
tube and secure with screw. Tighten screw. For conversion to LP Gas, remove the air shutter retaining
screw and remove air shutter. Remove the hex nut
and screw as shown in Figure 65. Slide the manifold
mounting bracket onto the manifold where the split
nut was removed. Slide the split nut on and install
the orifice. Tighten the orifice. (Fig. 66) Assemble the
manifold mounting bracket to the burner where the
nut and screw were removed. Tighten the nut and
screw.
5. For conversion to natural gas re-install manifold
to burner pan with 3/4” wrench and tighten until
secure.
20000584
DVBR Series Direct Vent Gas Fireplace
Shutter
Retaining
Screw
Air Shutter
Burner Pan
Front View
Fig. 63 Remove air shutter from burner pan.
Burner Pan
Shutter Retaining
Screw
Natural Gas
Slots Open
Fig. 64 Conversion Air shutter.
Burner
Top View
Hex Nut
Front View
CO103
CO127
Pilot Hood
Index
Marks
Pilot Bracket
CO105
Fig. 67 Removing pilot hood.
Pilot Orifice
CO106
Fig. 68 Removing pilot orifice.
Pilot Conversion - SIT
1. Remove pilot hood by lifting up. (Fig. 69)
2. Remove pilot orifice with Allen wrench. (Fig. 70)
3. Install conversion pilot orifice.
4. Reinstall pilot hood. Be sure to align pilot hood with
index tab.
Conversion is complete.
Manifold
Mounting
Bracket
Screw
CO128
Fig. 65 Locating manifold mounting bracket.
Manifold
Bracket
Manifold
Split Nut
Orifice
FP1554
Fig. 66 Manifold mounting bracket.
NOTE: It is not necessary to remove the pilot tube
for conversion.
Pilot Conversion - PSE
1. Loosen pilot hood turning counterclockwise using a
7/16” end wrench. (Fig. 67)
2. Remove pilot orifice with needlenose pliers.
(Fig. 68)
3. Install LP pilot orifice.
4. Re-install pilot hood and tighten until mark on pilot
hood aligns with mark on pilot bracket.
Conversion is complete.
Pilot Hood
Pilot
Bracket
Fig. 69 Remove pilot hood.
Index Tab
Pilot
Bracket
Fig. 70 Remove pilot orifice.
CO105a
Allen Wrench
CO106a
20000584
31
DVBR Series Direct Vent Gas Fireplace
Maintenance
Burner and Burner Compartment
It is important to keep the burner and the burner
compartment clean. At least once per year the logs and
lava rock/ember material should be removed and the
burner compartment vacuumed and wiped out. Remove
and replace the logs as per the instructions in this
manual.
Always handle the logs with care as they
are fragile and may also be hot if the
fireplace has been in use.
FK12 Fan Assembly
The fan unit requires periodic cleaning. At least once
per month in the operating season, open the lower
louvre panels and wipe or vacuum the area around the
fan to remove any build up of dust or lint.
Brass Trim
Clean the brass trim pieces using a soft cloth lightly
dampened with lemon oil. Do not use water or
household cleaners on any brass components.
Contact your local representative to arrange an annual
service program.
Cleaning the Standing
Pilot Control System
To obtain proper operation, it is imperative that the pilot
and burner’s flame characteristics are steady, not lifting
or floating.
Typically, the top 3/8” or 1/2” of the thermopile should
be engulfed in the pilot flame. (Fig. 71)
To adjust pilot burner; (by qualified service technician)
1. Remove pilot adjustment cap.
2. Adjust pilot screw to provide properly sized flame.
3. Replace pilot adjustment cap.
The primary air shutter is set at factory and should only
be adjusted, if necessary, by a qualified service technician.
3/8” - 1/2”
F584-703
Fig. 71 Correct pilot flame appearance.
The burner and control system consists of
• burner tube • gas orifice
• pilot assembly • thermopile
• millivolt gas valve
Most of these components may require only an occasional checkup and cleaning and some may require
adjustment. If repair is necessary, it should be per-
5. Vacuum burner compartment especially around
orifice primary air openings.
6. Visually inspect pilot. Brush or blow away any dust
or lint accumulation.
7. Reinstall logs.
8. Ignite pilot - Refer to Lighting Instructions.
9. Reinstall window frame assembly.
32
20000584
DVBR Series Direct Vent Gas Fireplace
1d
1e
1c
1a
1b
1f
1g
1h
1i
1. DVBR36
2
3
4
5
6
7a
7b
10
11
12
9
8
14
13 a/b
15 a/b
16
28
29
PILOT
ON
OFF
PILOT
ADJ
L
O
H
I
TPTH
TH
TP
17a,b
18a/b
25a/b
26
19
20
21
22
23a/b
24
32
33
36
37
38
1d
1e
1c
1a
1b
1f
1. DVBR42
1g
1h
1i
1j
CFM Corporation reserves the right to make changes in design, materials, specifications, prices and discontinue colors and products at any time,
without notice.
DVBR36/42
Ref. Description DVBR36 DVBR42
1. Log Set Complete 20008744 20008743
1a. Left Log 20008817 20008508
1b. Right Log 20008819 20008510
1c. Right Rear Log 20008818 20008509
1d. Left Cross Log 20008820 20008515
1e. Right Cover Log 20008822 20008515
1f. Left Rear Log 20008513 20008816
1g. Center Log 20008821 20008514
1h. Left Front Log 20008823 20008823
1i. Left Cover Log 20008512 20008512
1j. Log Top Right -- B29
20000584
33
DVBR Series Direct Vent Gas Fireplace
DVBR36/42 (continued)
Ref. Description DVBR36 DVBR42
2. Lava Rock Package 20000198 20000198
3. Mineral Wool Bagged 5110184 5110184
4. Ceramic Tile (Single) 57803 57803
5. Burner Housing with Tile 20008831 20008836
6. Manifold Tubing with Fittings 20000611 20000538
39. Conversion Kit (Nat to LP) SIT 20009082 20009082
40. Conversion Kit (LP to Nat) SIT 20009083 20009083
41. Regulator Head (Nat.) 10001006 10001006
42. Regulator Head (LP) 10001007 10001007
34
Consists of Items 13a, 15a, 29b, 32 (Honeywell)20009084 20009084
Consists of Items 13b, 15b, 29a, 33 (Honeywell)20000975 20000975
20000584
DVBR Series Direct Vent Gas Fireplace
A
A
Optional Accessories
Optional Fk-12 Fan Hook-up
1. Remove control cover from unit.
2. Remove glass door by rotating latches at bottom
corners of door. Refer to Page 23.
3. Remove the 9 screws securing burner to combustion
bottom.
4. Remove burner by lifting up and rotating toward front
of unit.
5. Set burner aside.
6. Install FK-12 fan in back of unit between hearth sup
ports. (Fig. 72)
7. Secure fan on velcro strips.
8. Plug fan into EB-1 receptacle.
9. Be sure fan motor does not touch hearth supports.
Any electrical re-wiring of this fan must be
completed by a qualified electrician.
Turn off all power before hook-up.
Hearth
Support
Cold Air Box
See
Detail
Top View
FK-12 Fan
Base Pan
-
Remote Controls
Optional remote control units are available to control
different functions of the appliance.
Model Functions ControlledRC1ON/OFF
RC2ON/OFF and Temperature
IMTFK Wall mounted thermostat control
Ceramic Refractory Panels
1. Remove glass and logs.
2. Insert supports under ceramic hearth panels.
(Fig. 73)
3. Remove three (3) screws securing heat shield to
combustion dome. (Fig. 74)
4. Place rear ceramic panel in back of unit. (Fig. 75)
5. Place side panels.
6. Replace heat shield, logs and glass.
Ceramic Support
Burner
Grate
EB-1 Receptacle
Cold Air Box
Side View
Front of
Unit
Base Pan
Hearth Pan
Detail
Fig. 72 FK-12 Fan Kit placement.
Access Cover
Hearth Pan
FK-12 Fan
Hearth
Support
584-10
Fig. 73 Ceramic support.
Heat Shield
Fig. 74 Heat shield.
Section A
Front View
Hearth Panel
H101
Heat Shield
(3) Screws
Side View
Section A
H103
20000584
35
DVBR Series Direct Vent Gas Fireplace
Rear Ceramic Panel
Burner
Back of
Firebox
Rear Log Support
Decorative Glass Panels
Brilliance Glass Panels are available to enhance the
beauty and viewing pleasure of your DVBR fireplace.
Decorative Frame Trims
A selection of decorative frame trim kits are available for
mounting around the outside of the appliance to enhance its visual effect on the room. Installation instructions for each decorative frame trim are included with
the frame trim kit. Contact your authorized distributor for
details of the trim kits and ordering information for the
trim kits applicable for each model.
Side View
Fig. 75 Rear ceramic panel placement.
H102
Decorative Face Kit
The Metro Face Kit is designed for use on the DVBR36
only.
Model Beam ColorMADVBR36FKBE01 Espresso
MADVBR36FKBM03 Light Maple
MADVBR36FKBC02 Cognac
36
20000584
DVBR Series Direct Vent Gas Fireplace
20000584
37
DVBR Series Direct Vent Gas Fireplace
38
20000584
LIMITED LIFETIME WARRANTY
DVBR Series Direct Vent Gas Fireplace
PRODUCT COVERED BY THIS WARRANTY
All Vermont Castings gas stoves, gas inserts, and gas fireplaces, and all Majestic or Northern Flame brand gas fireplaces
equipped with an Insta-Flame Ceramic Burner, or standard steel tube burner.
BASIC WARRANTY
CFM Corporation (hereinafter referred to collectively as the Company)
warrants that your new Vermont Castings
Stove is free from manufacturing and material defects for a period of
one year from the date of purchase, subject to the following conditions
and limitations.
EXTENDED LIFETIME WARRANTY
The heat exchanger, where applicable, and combustion chamber
of every Vermont Castings or Majestic gas product is warranted for
life against through wall perforation. All appliances equipped with an
Insta-Flame Ceramic Burner have limited lifetime coverage on the
ceramic burner plaque. Warrantees are made to the original owner
subject to proof of purchase and the conditions and limitations listed
on this Warranty Document
COMPONENT WARRANTY
CAST IRON: All external and internal cast iron parts are warranted for a
period of three years.
Note: On porcelain enamel finished external parts and accessories The
Company offers no Warranty on chipping of enamel surfaces. Inspect
all product prior to accepting it for any damage to the enamel.
The salt air environment of coastal areas or a high humidity environment
can be corrosive to the porcelain enamel finish. These conditions can
cause rusting of the cast iron beneath the porcelain enamel finish,
which will cause the finish to flake off.
Dye lot variations with replacement parts and/or accessories can occur
and are not covered by warranty.
GLASS DOORS: Glass doors are covered for a period of one year.
Glass doors are not warranted for breakage due to misuse or accident.
Glass doors are not covered for discoloration or burned in stains due to
environmental issues, or improper cleaning and maintenance.
BRASS PLATED PARTS AND ACCESSORIES: Brass parts should be
cleaned with Lemon oil only.
mix and masonry cleaners may corrode the brass finish. The Company
will not be responsible for, nor will it warrant any brass parts which are
damaged by external chemicals or down draft conditions.
GAS VALVES: Gas valves are covered for a period of one year
ELECTRONIC AND MECHANICAL COMPONENTS: Electronic and
mechanical components of the burner assembly are covered for one year.
All steel tube burners are warranted for one year.
ACCESSORIES: Unless otherwise noted all components and CFM
Corporation company supplied accessories are covered for a period of
one year.
CONDITIONS AND LIMITATIONS
• This new Vermont Castings or Majestic product must be installed by
a competent, authorized, service contractor. A licensed technician, as
prescribed by the local jurisdiction must perform any installation/service
work. It must be installed and operated at all times in accordance with
the Installation and Operating instructions furnished with the product.
Any alteration, willful abuse, accident, or misuse of the product shall
nullify this warranty.
• This warranty is non-transferable, and is made to the original owner,
provided that the purchase was made through an authorized supplier
of the Company.
• The customer must pay for any Authorized Dealer in-home travel fees
or service charges for in-home repair work. It is the dealers option
whether the repair work will be done in the customer’s home or in the
dealer’s shop.
• If upon inspection, the damage is found to be the fault of the manufacturer,
repairs will be authorized at no charge to the customer parts and/or
labor.
Brass cleaners cannot be used. Mortar
or Majestic Gas Fireplace/
• Any part and/or component replaced under the provisions of this
warranty is covered for six months or the remainder of the original
warranty, whichever is longest.
• This warranty is limited to the repair of or replacement of part(s) found
to be defective in material or workmanship, provided that such part(s)
have been subjected to normal conditions of use and service, after
said defect is confirmed by the Company’s inspection.
• The company may, at its discretion, fully discharge all obligations
with respect to this warranty by refunding the wholesale price of the
defective part(s)
• Any installation, labor, construction, transportation, or other related
costs/expenses arising from defective part(s), repair, replacement,
or otherwise of same, will not be covered by this warranty, nor shall
the Company assume responsibility for same. Further, the Company
will not be responsible for any incidental, indirect, or consequential
damages except as provided by law.
• SOME STATES DO NOT ALLOW FOR THE EXCLUSION OR
LIMITATIONS OF INCIDENTAL AND CONSEQUENTIAL DAMAGES
OR LIMITATIONS ON HOW LONG AN IMPLIED WARRANTY
LASTS, SO THE ABOVE LIMITATIONS MAY NOT APPLY TO YOUR
CIRCUMSTANCES. THIS WARRANTY GIVES YOU SPECIFIC
RIGHTS AND YOU MAY HAVE OTHER RIGHTS WHICH VARY FROM
STATE TO STATE.
• All other warranties-expressed or implied- with respect to the product,
its components and accessories, or any obligations/liabilities on the
part of the Company are hereby expressly excluded.
• The Company neither assumes, nor authorizes any third party to
assume on its behalf, any other liabilities with respect to the sale of
this Vermont Castings or Majestic product
• The warranties as outlined within this document do not apply to
chimney components or other non CFM Corporation accessories used
in conjunction with the installation of this product..
• Damage to the unit while in transit is not covered by this warranty but
is subject to claim against the common carrier. Contact the dealer
from whom you purchased your fireplace/stove (do not operate the
appliance as this might negate the ability to process the claim with the
carrier).
• The Company will not be responsible for:
a) Down drafts or spillage caused by environmental conditions such
as near-by trees, buildings, roof tops, hills, or mountains.
b) Inadequate ventilation or negative air pressure caused by
mechanical systems such as furnaces, fans, clothes dryers, etc.
• This warranty is void if:
a) The fireplace has been operated in atmospheres contaminated by
chlorine, fluorine, or other damaging chemicals.
b) The fireplace has been subjected to prolonged periods of dampness
or condensation
c) Any damages to the fireplace, combustion chamber, heat exchanger
or other components due to water, or weather damage, which is the
result of but not limited to, improper chimney/venting installation.
d) Any alteration, willful abuse, accident, or misuse of the product
has occurred.
IF WARRANTY SERVICE IS NEEDED…
1) Contact your supplier. Make sure you have your warranty,
your sales receipt, and the model/serial number of your
CFM Corporation product.
2) DO NOT ATTEMPT TO DO ANY SERVICE WORK
YOURSELF.