Vermont Casting D232 User Manual

Free-Standing
Direct V ented
Fireplaces
MODEL D232
Installation Instructions & Homeowner's Manual
WARNING! IF THE INFORMATION IN THIS MANUAL IS NOT FOLLOWED EXACTLY, A FIRE OR
EXPLOSION MAY RESULT CAUSING PROPERTY DAMAGE, PERSONAL INJURY OR LOSS OF LIFE.
FOR YOUR SAFETY
WHAT TO DO IF YOU SMELL GAS:
* Do not try to light any appliance. * Do not touch any electric switch * Do not use any phone in your building. * Immediately call your gas supplier from
your neighbours phone. Follow the gas suppliers instructions.
* If you cannot reach your gas supplier call
the fire department.
FOR YOUR SAFETY
DO NOT STORE
OR USE GASOLINE OR OTHER
FLAMMABLE VAPOURS AND LIQUIDS
IN THE VICINITY OF THIS OR ANY
* INSTALLATION AND SERVICE MUST BE
PERFORMED BY A QUALIFIED INSTALLER, SERVICE AGENCY OR YOUR GAS SUPPLIER.
INSTALLER: DO NOT DISCARD THIS MANUAL - LEAVE FOR HOMEOWNER
- 1 -
10002735
6/00 Rev. 0
TABLE OF CONTENTS
PLEASE READ THE INSTALLATION & OPERATING INSTRUCTIONS BEFORE USING APPLIANCE.
IMPORTANT:
Installation Instructions.................................................................................................. 3
General Venting Information.......................................................................................... 7
Crimped Ends Venting Components........................................................................... 16
Twist Lock Venting Components ................................................................................ 17
Operating Instructions.................................................................................................. 18
Replacement Parts List .............................................................................................. 24
Options ......................................................................................................................... 26
Read all instructions and warnings carefully before starting installation. Failure to follow these
instructions may result in a possible fire hazard and will void the warranty.
Important Curing/Burn Information ....................................................................... 3
Locating Your Gas Fireplace ................................................................................ 3
Clearance to Combustibles .................................................................................. 3
Fireplace Dimensions ........................................................................................... 4
Gas Specifications................................................................................................ 5
Preparation ........................................................................................................... 5
Gas Line Installation ............................................................................................. 5
Installation of Remote Switch for RN/RP gas valve.............................................. 6
Termination Clearances ....................................................................................... 8
General Information on Assembling Vent Pipes................................................... 9
Vertical Sidewall Installations ............................................................................. 10
Vertical Sidewall Applications............................................................................. 10
Sidewall Venting Graph ...................................................................................... 11
Vent Pipe Assembly ........................................................................................... 12
Below Grade Installations (Snorkel) ................................................................... 13
Vertical Through the Roof Applications .............................................................. 14
To Install Vertical Venting................................................................................... 15
General Glass Information.................................................................................. 18
Louvre Removal ................................................................................................. 18
Trim Removal ..................................................................................................... 18
Glass Removal ................................................................................................... 18
Glass Cleaning ................................................................................................... 19
Log Set Installation & Small Lava Rock.............................................................. 19
Ceramic Refractory............................................................................................. 19
Maintenance ....................................................................................................... 20
Cleaning Procedure............................................................................................ 20
Flame Adjustment & Characteristics .................................................................. 20
Lighting and Operating Instructions.................................................................... 21
Troubleshooting Gas Control (Honeywell).......................................................... 22
Troubleshooting Gas Control (SIT Nova 820) .................................................... 23
Replacement Parts Pictorial ............................................................................... 26
- 2 -
INSTALLATION AND OPERA TING INSTRUCTIONS
This gas fireplace should be installed by a qualified installer in accordance with local building codes and with current CAN / CGA-B149 (. 1 or .2) Installation codes for Gas Burning Fireplaces and Equipment and CAN/CSA Z 240 .4 Canada.
FOR U.S.A Installations follow local codes and/or the current National Fuel Gas Code. ANSI Z223.1.
FOR SAFE INSTALLATION AND OPERATION PLEASE NOTE THE FOLLOWING:
1 . This fireplace gives off high temperatures and should
be located out of high traffic areas and away from furniture and draperies.
2. Children and adults should be alerted to the hazards of the high surface temperatures of this fireplace and should stay away to avoid burns or ignition of cloth­ing.
3. Children should be carefully supervised when they are in the same room as your fireplace.
4. Under no circumstances should this fireplace be modified.Parts removed for servicing should be re­placed prior to operating the fireplace again.
5. Installation and any repairs to this fireplace should be carried out by a qualified service person. A profes­sional service person should be contacted to inspect this fireplace annually.Make it a practice to have all of your gas fireplaces checked annually. More frequent cleaning may be required due to excess lint and dust from carpeting, bedding material, etc.
6. Control compartments, burners and air passages in this fireplace should be kept clean and free of dust and lint. Make sure that the gas valve and pilot light are turned off before you attempt to clean this fire­place.
7, The venting system(chimney) of this fireplace should
be checked at least once a year and if needed your venting system should be cleaned.
8. Keep the area around your fireplace clear of combus­tible materials, gasoline and other flammable vapour and liquids. This fireplace should not be used as a drying rack for clothing,nor should Christmas stock­ings or decorations be hung in the area of it.
9. Under no circumstances should any solid fuels (wood,coal,paper or cardboard etc.)be used in this fireplace.
10.The flow of combustion and ventilation air must not be obstructed in any way.
11.When the fireplace is installed directly on carpeting, vinyl tile or any combustible material other than wood, the fireplace must be installed on a metal or wood panel extending the full width and depth of the fireplace.
12.This fireplace requires adequate ventilation and combustion air to operate properly.
13.This fireplaces must not be connected to a chimney flue serving a separate solid fuel burning fireplace.
IMPORTANT: PLEASE REVIEW THE FOLLOWING CAREFULLY
Remove any plastic from trim parts before turning the fireplace ON.
It is normal for fireplaces fabricated of steel to give off some expansion and/or contraction noises during the start up or cool down cycle. Similar noises are found with your furnace heat exchanger or car engine.
It is not unusual for your gas fireplace to give off some odour the first time it is burned. This is due to the curing of the paint and any undetected oil from the manufacturing process.
Please ensure that your room is well ventilated - open all windows.
It is recommended that you burn your fireplace for a least six (6) hours the first time you use it. If optional fan kit has been installed, place fan in the "OFF" position during this time.
LOCATING YOUR GAS FIREPLACE
12" (305mm)
A
12" (305mm)
E
A) *Flat on wall corner B) *Room divider C) Island D) Cross corner E) Flat on wall
* A & B must maintain a 12" (305mm) clearance between the wall
and side glass of fireplace.
There is a minimum vertical rise required for the venting which varies depending on the application. The maximum horizontal run also has restrictions. Become familiar with the venting instructions starting on page 7, before starting the installation.
B
C
D
Fig. 1
CLEARANCE TO COMBUSTIBLES
Adequate clearances as listed below must be maintained for servicing and proper operation:
Back ............................................. 0"
Side ............................................ 12"
Floor ............................................. 0"
Top ............................................. 36"
Corner .................. 0" to Back Edges
Vent Pipe...................................... 1"
- 3 -
A
FIREPLACE DIMENSIONS
MODEL D232
K
B
C
D
E
MODEL D232
A 25" 635mm B 24 C 16" 406mm D 20" 508mm E 19" 483mm F 21" 533mm G 31 H 17 I 29
1/8"
3/4"
3/4"
5/8"
F
613mm
806mm 451mm 752mm
G
I
J
H
J 9" 229mm K6 L— — M— — N—
1/2"
165mm
- 4 -
GAS SPECIFICATIONS
1/2" Gas Supply
1/2" X 3/8" Reducer
3/8" Nipple
3/8" Nipple
3/8" Nipple
3/8" X 3/8" Shut Off Valve
3/8" Union
TYPICAL GAS LINE CONNECTION
PREPARATION
MAX. MIN.
MODEL FUEL GAS CONTROL B.T.U.H B.T.U.H.
D232RN Natural Gas Millivolt Hi/Lo 30,000 21,000 D232RP Propane Gas Millivolt Hi/Lo 30,000 22,500
This appliance may be installed in an aftermarket permanently located, manufactured (mobile) home, where not prohibited by local codes.
This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases, unless a certified kit is available and used.
INPUT INPUT
The installation of your Fireplace must conform with local codes, or in the absence of local codes, with National Fuel Gas Code, ANSI Z223.1 latest edition, or CAN 1 B1-149.1 and .2 Installation Code. (EXCEPTION: Do not derate this appliance for elevations up to 4,500 ft (1,370m). Maintain the manifold pressure at 3.5 inches W.C. for Natural Gas and 10 inches W.C. for LP gas.)
The use of wall paper adjacent to this fire­place is not recommended, as the high heat given off by this fireplace may adversely effect the binders in the adhesive used to apply the wallpaper.
Before beginning, remove the glass door from the fireplace. Also check to make sure there is no hidden damage to the fireplace. Take a minute and plan out the gas, vent and electrical supply. See Glass Removal Section.
GAS LINE INSTALLATION
When purging gas line, the front glass must be removed.
The gas pipeline can be brought in through the rear of the fireplace as well as the bottom. Knockouts are provided on the bottom behind the valve to allow for the gas pipe installation and testing of any gas connection. It is most
convenient to bring the gas line in from the rear right side of the valve, as this allows fan installation or removal without disconnecting the gas line.
The gas line connection can be made with properly tinned 3/8" copper tubing, 3/8" rigid pipe or an approved flex connector. Since some municipalities have some additional local codes, it is always best to consult your local authority and the CAN/CGA- B149 (.1 or .2) installation code.
FOR U.S.A Installations consult the current National
Fuel Gas Code, ANSI Z223.1
D232 CERTIFIED TO
ANSI.Z21.88b-1999 / CSA 2.33b - M99
Vented Gas Fireplace Heaters
GAS INLET & MANIFOLD PRESSURES
NATURAL Input Minimum Input Maximum Manifold Pressure
4.5" wc
3.5" wc
7" wc
Always check for gas leaks with a mild soap
and water solution. Do not use an open flame for leak testing. The gas control is equipped with a captured screw type pressure test point, therefore it is not necessary to provide a 1/8" test point up stream of the control.
LP (Propane)
11" wc 13" wc 10" wc
Fig. 2
- 5 -
P
I
L
O
T
TPTH
TP
TH
ON/OFF SWITCH OR
MILLIVOLT THERMOSTAT
VALVE
THERMOPILE
When using copper or flex connector use only approved
PILOT
ADJ
fittings. Always provide a union when using back iron pipe so that gas line can be easily disconnected for burner
or fan servicing. See Fig. 2. See gas specification for pressure details and ratings.
The fireplace valve must not be subjected to any test pressures exceeding 1/2 psi. Isolate or disconnect this or any other gas appliance control from the gas line when pressure testing.
DO NOT USE THIS FIREPLACE IF ANY PART OF THIS FIREPLACE HAS BEEN UNDER WATER. IMMEDIATELY CALL A QUALIFIED SERVICE TECHNICIAN TO INSPECT THE HEATER AND TO REPLACE ANY PART CONTROL WHICH HAS BEEN UNDER WATER.
INSTALLATION OF REMOTE
SWITCH FOR RN/RP GAS VALVE
Install on/off switch assembly on either the rear right or left side of the Fireplace.
1. Remove the screw at the back of the cabinet top either on the left or the right side of the fireplace.
2. Position switch assembly onto the back of the fireplace, then fasten two screws as shown in Fig. 5.
3. Attach wiring under the clips on the rear casing (Fig. 5) and install wiring through the rear opening of the fireplace before connecting to the valve as shown in Fig. 4.
TH
TP
TP
TH
Fig. 4
Screw
On/off switch
assembly
Clips
(through existing hole)
Screw
Wiring for milli-volt
gas valves
Fig. 5
- 6 -
GENERAL VENTING INFORMATION
Your fireplace is approved to be vented either through the side wall, or vertically through the roof. – Only venting components specifically approved and
labelled for this fireplace may be used.
Minimum clearances between vent pipes and com-
bustible materials is one (1") inch (25 mm).
Venting terminals shall not be recessed into a wall or
siding.
Horizontal venting must be installed on a level plane
without any incline or decline.
D
E
V
B
L
C
Fixed
Fixed
Closed
Closed
F
Openable
V
B
V
Openable
B
Fixed
Closed
V A
There must not be any obstruction such as bushes, garden sheds, fences, decks or utility buildings within 24" from the front of the termination hood.
Do not locate termination hood where excessive snow or ice build up may occur. Be sure to check vent termination area after snow falls, and clear to prevent accidental blockage of venting system. When using snow blowers, make sure snow is not directed towards vent termination area.
Location of Vent Termination
It is imperative that the vent termination be located observing the minimum clearances as shown on this page.
*
Check with local codes or in absence of same with CAN/CGA B149 (.1 or .2) Installation Codes (1991) for Canada or for U.S.A. Installations follow the current National Fuel Gas Code, ANSI Z223.1.
H
B
V
B
X
J
G
N
I
M
N
G
V
G
X
K
V
V
A
TERMINATION CAP AIR SUPPLY INLET GAS METER RESTRICTED AREA
V
X
A = clearance above grade, veranda, porch, deck, or bal-
cony [* 12 inches (305mm) minimum]
B = clearance to window or door that may be opened 12"
(306mm).
C = clearance to permanently closed window [minimum 12
inches (305mm) recommended to prevent condensa­tion on window]
D = vertical clearance to ventilated soffit located above the
termina/ within a horizontal distance of 24 inches (610mm) from the centre-line of the terminal [18 inches (458mm) minimum]
E = clearance to unventilated soffit [12 inches (305mm)
minimum F = clearance to outside comer see next page G = clearance to inside comer see next page H = * not to be installed above a meter/regulator assembly
within 36 inches (914mm) horizontally from the centre-
line of the regulator
a vent shall not terminate directly above a side-walk or paved driveway which is located between two single family
dwellings and serves both dwellings * ‡ only permitted if veranda, porch, deck, is fully open on a minimum 2 sides beneath the floor * * as specified in CAN/CGA B149 (.1 or .2) Installation Codes (1991) for Canada or for U.S.A. Installations follow the
current National Fuel Gas Code, ANSI Z223.1.
Note: Local codes or regulations may require different clearances.
G
(TERMINATION PROHIBITED)
I = clearance to service regulator vent outlet [*72 inches
(1828mm) minimum]
J = clearance to non-mechanical air supply inlet to building
or the combustion air inlet to any other fireplace [ *12 inches (305mm) minimum]
K = clearance to a mechanical air supply inlet [* 72 inches
(1828mm) minimum]
L = † clearance above paved side-walk or a paved driveway
located on public property [*84 inches (2133mm) mini­mum]
M = clearance under veranda, porch, deck [*12 inches
(305mm) minimum ‡]
N = Clearance above a roof shall extend a minimum of 24"
(610mm) above the highest point when it passes through
A
the roof surface, and any other obstruciton within a horizontal distance of 18" (450mm).
- 7 -
Termination Clearances
Termination clearances for buildings with combustible and noncombustible exteriors.
Inside Corner
A
V
Balcony ­with no side wall
G = Combustible& Non-Combustible
12"(305mm)
A =
Combustible 6"(152mm)
Noncombustible 2"(50mm)
G
V
Outside Corner
B =
Combustible 6"(152mm)
V
Noncombustible 2"(50mm)
B
Balcony ­with perpendicular side wall
H
V
Combustible & Non-Combustible
H = 24"(610mm) J = 20"(508mm)
J
Recessed Location
D
C
C
E
V
C = Maximum depth of 48"
(1219mm) for recessed location.
D = Minimum width for back wall of a recessed location. Combustible 38"(965mm) Noncombustible 24"(610mm)
E = Clearance from corner in recessed location. Combustible 6"(152mm) Noncombustible 2"(50mm)
- 8 -
GENERAL INFORMATION ON ASSEMBLING
THE VENT PIPES
CRIMPED END PIPES
Before joining elbows and pipes apply a bead of high temperature sealant to crimped end of elbow or pipe. (Fig. 6).
Join pipes and secure joints with three (3) sheetmetal screws. (See Fig. 6) Wipe off excess sealant.
There are polished brass decorative rings provided to hide the exposed piping joints. Wrap the brass ring over the joint fitting the stud into the notch and tighten down the 3/8" nut
BEAD LOCATION
1" (25mm) FROM CRIMPED END OF PIPE
1'' (25mm)
TWIST LOCK PIPES
When using twist lock pipe it is not necessary to use sealant at the twist lock joints.
The only areas of the venting that need to be sealed with high temperature silicone sealant are the collars on the fireplace and termination, and the sliding joint of any telescopic vent pipes used in the system.
To join the twist lock pipes together, simply align the beads of the male end with the grooves of the female end, then while bringing the pipes together, twist the pipe until the flange on the female end contacts the external flange on the male end.
It is recommended that you secure the joints with 3 sheet metal screws however this is not mandatory with twist lock pipe.
To make it easier to assemble the joints we suggest putting a lubricant (Vaseline or similar) on the male end of the twist lock pipe.
Screw Holes
Fig. 6
CANADIAN INSTALLATIONS:
The venting system must be installed in accordance with the current CAN/CGA-B149 (.1 or .2) installation code.
U.S.A. INSTALLATIONS:
The venting system must conform with local codes and/or the current National Fuel Gas Code, ANSI Z223.1.
Only venting components manufactured by The CFM Majestics Products Company may be used.
TWIST LOCK PIPE JOINT
Screw Holes
Fig. 7
- 9 -
VERTICAL SIDEWALL INSTALLATIONS
Since it is very important that the venting system maintain its balance between the combustion air intake and the flue gas exhaust, certain limitations as to vent configurations apply and must be strictly adhered to.
The graph showing the relationship between vertical and horizontal side wall venting will help to determine the various lengths allowable. Fig. 11a or 11b.
Minimum clearance between vent pipes and combustible materials is one (1") inch (25mm) on top, bottom and sides unless otherwise noted.
When vent termination exits through foundations less than 20" below siding outcrop, the vent pipe must flush up with the siding. A 7DVSS must also be used.
It is always best to locate the fireplace in such a way that minimizes the number of offsets and horizontal vent length.
For each 45 degree elbow installed in the hori­zontal run, the length of the horizontal run MUST be reduced by 18" (45cm). This does not apply if the 45 degree elbows are installed on the vertical part of the vent system.
The maximum number of elbow degrees in a system is 270 (See Fig. 8).
Sample: 1 - 90
2-45 3-45 4-90
Total 270
o o o o
o
o
The horizontal vent run refers to the total length of vent pipe from the flue collar of the fireplace to the face of the outer wall.
Horizontal plane means no vertical rise exists on this portion of the vent assembly.
VERTICAL SIDEWALL APPLICATIONS
The maximum number of 90 degree elbows per side wall installation is three (3).
For D232 the maximum horizontal run off a minimum 12" vertical rise is 3'. (See Fig. 9)
If a 90 degree elbow is used in the horizontal vent run (level height maintained) the maximum horizontal vent length is reduced by 36 inches. Fig. 10. This does not apply if the 90 degree elbows are used to increase or redirect a vertical rise (Fig. 11).
Example: According to the chart the maximum horizontal vent length is 20' and if a 90 degree elbow is required in the horizontal vent it must be reduced to 17'. (Fig. 10 Dimension A plus B must not be greater than 17').
The maximum number of 45 degree elbows permitted per side wall installation is two (2). These elbows can be installed in either the vertical or horizontal run (Fig. 8).
x
3 FT
(92cm)
D232x=12"
7.5FT (2286m)
Fig. 9
PIPE STRAPS
EVERY 3'
(92cm)
7.5 ft.
2286mm
(610cm)
20 FT
A + B = 17ft.
PIPE STRAPS
EVERY 3'
(92cm)
FIRESTOP/ZERO
CLEARANCE SLEEVE
Fig. 8
Fig. 10
- 10 -
Fig. 11
TO USE THE VENT GRAPH
1. Determine the height of the centre of the horizontal vent pipe exiting through the outer wall. Using this dimension on the Sidewall Vent Graph (Fig. 12 ), locate the point it intersects with the slanted graph line.
2. From the point of this intersection, draw a vertical line to the bottom of the graph.
3. Select the indicated dimension, and position the fire­place in accordance with same.
EXAMPLE A:
If the vertical dimension from the floor of the fireplace is 11 feet (335cm) the horizontal run to the face of the outer wall must not exceed 14 feet (427cm).
EXAMPLE B:
If the vertical dimension from the floor of the fireplace is 7 feet (214cm), the horizontal run to the face of the outer wall must not exceed 8-1/2 feet (259cm).
SIDEWALL VENTING GRAPH
(Dimensions in Feet)
For D232
30 29 28 27 26 25 24 23 22 21 20 19 18 17 16 15 14 13 12 11 10
eg: A
9 8 7 6 5 4 3
eg: B
TO THE CENTRE OF THE HORIZONTAL VENT PIPE
SIDEWALL VENTING GRAPH
(Dimensions in Feet)
For FSDV42
30 29 28 27 26 25 24 23 22 21 20 19 18 17 16 15 14 13 12 11 10
VERTICAL DIMENSION FROM THE FLOOR OF THE FIREPLACE
9 8 7 6 5 4 3
3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
HORIZONTAL DIMENSION
SEE PAGE 14 FOR VENTING
REQUIREMENTS FOR SNORKELS.
RFSDV42
ONL Y
eg: A
eg: C
Fig. 14b
VERTICAL DIMENSION FROM THE FLOOR OF THE FIREPLACE
TO THE CENTRE OF THE HORIZONTAL VENT PIPE
3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
HORIZONTAL DIMENSION
SEE PAGE 13 & 14 FOR VENTING REQUIREMENTS FOR SNORKELS.
Fig. 12
- 11 -
VENT PIPE ASSEMBLY
BEAD OF SEALANT
STEP 1
Locate vent opening on the wall. It may be necessary to first position the fireplace and measure to obtain hole location. Depending on whether the wall is combustible or non­combustible, cut opening to size. Fig. 13 or 15. (For combustible walls first frame in opening. Fig. 14).
Vent Opening Combustible Wall
(240mm)
9-
3/8
"
Fig. 13
COMBUSTIBLE WALLS (Fig. 13): Cut a 9-3/8"H x 9-3/8"W (240 mm x 240 mm) hole through the exterior wall and frame as shown (Fig. 14).
NON-COMBUSTIBLE WALLS (Fig. 14): Hole opening must be
7.5" (190 mm) in diameter.
9-
3/8
"
(240mm)
Vent Opening Noncombustible Wall
7-
1/2
"
(190mm)
(framing detail)
Fig. 14
Fig. 15
STEP 3
Place fireplace into position. (Fig. 17). Measure the vertical length (X) required from the base of the flue collars to the centre of the wall opening.
X
Fig. 17
STEP 4
Apply a bead of silicone to the inner and outer flue collars of the fireplace (Fig. 18) and using appropriate length of pipe section(s) attach to fireplace with three (3) screws. Follow with the installation of the inner and outer elbow, again secure joints as described on page 9.
STEP 2
Measure wall thickness and cut zero clearance sleeve parts to proper length (MAXIMUM 12"). Assemble sleeve and attach to firestop with #8 sheetmetal screws (sup­plied). Install firestop assembly (Fig. 16)..
Zero clearance sleeve is only required for combustible walls.
#8 SCREWS(2)
ADJUSTABLE ZERO
CLEARANCE SLEEVE
Maximum Length
12" (294mm)
#8 SCREWS(2)
FIRESTOP
#8 SCREWS(2)
ADJUSTABLE
ZERO CLEARANCE
SLEEVE
Fig. 16
Fig. 18
- 12 -
STEP 5
STEP 7
Measure the horizontal length requirement including a 2" overlap , i.e. from the elbow to the outside wall face plus 2" (or the distance required if installing a second 90) elbow. (Fig. 19).
X
Fig. 19
Always install horizontal venting on a level plane.
Apply high temperature sealant to 4" and 7" collars or the termination one inch away from crimped end. Guide the vent terminations 4" and 7" collars into their respective vent pipes. Double check that the vent pipes overlap the collars by 2". Secure the termination to the wall with screws provided and caulk around the wall plate to weatherproof.
Fig. 21
STEP 6
Note: If using the charcoal wall plate, Part #52202-CG, and collar, Part #52203-CG, put them in place before putting the pipe sections through the wall.
Use appropriate length of pipe sections - telescopic or fixed
- and install. The sections which go through the wall are
packaged with the starter kit, and can be cut to suit if necessary. (Fig. 20).
Support horizontal pipes every 3 feet (91 cm) with metal pipe straps.
Check fireplace to make sure it is levelled and properly positioned.
BELOW GRADE INSTALLATIONS
When it is not possible to meet the required vent terminal clearances of 12 inches (305mm) above grade level a starter vent kit is recommended. It allows installation depth of down to 7 inches (178mm) below grade level. The 7 inches is measured from the centre of the horizontal vent pipe as it penetrates through the wall.
If venting system is installed below ground, we recommend a window well with adequate and proper drainage.
Fig. 20
Sealing vent pipe and firestop gaps with high temperature sealant will restrict cold air being drawn in around fireplace.
- 13 -
Ensure sidewall venting clearances are observed.
If installing a snorkel a minimum 24" vertical rise is necessary. The maximum horizontal run with the 24" vertical pipe is 36" (915mm). This measurement is taken from the collar of the fireplace to the face of the exterior wall. See vent graph for extended horizontal run if the vertical exceeds 24".
1. Establish vent hole through the wall (Fig. 13,14 & 15).
2. Remove soil to a depth of approximately 16" below base of snorkel. Install drain pipe. Install window well (not supplied). Refill hole with 12" of coarse gravel leaving a clearance of approximately 4" below snorkel. See Fig. 22.
3. Install vent system.
4. Ensure a watertight seal is made around the vent pipe coming through the wall.
5. Apply high temperature sealant caulking (supplied) around the 4 and 7 inch snorkel collars.
DO NOT BACK FILL AROUND SNORKEL. SOIL SHOULD NOT BE LESS THAN 4" BELOW SNORKEL.
FOUNDATION
RECESS
WATERTIGHT
SEAL
AROUND
PIPE
SNORKEL
WALL
SCREWS
SHEET METAL
SCREWS
Fig. 23
If the foundation is recessed, use recess brackets (not supplied) for securing lower portion of the snorkel. Fasten brackets to wall first and then secure to snorkel with self drilling #8 x 1/2 sheet metal screws. It will be necessary to extend the vent pipes out as far as the protruding wall face (Fig. 22).
6. Slide into vent pipe and secure to the wall.
7. Level the soil so as to maintain a 4" clearance below snorkel. See Fig. 22.
FIRESTOP
7" PIPE
24"/608mm
MINIMUM*
SCREWS
FOUNDATION WALL
*
A minimum of 24"/608mm vertical pipe must be installed when using the snorkel kit.
The 22" vertical rise (center to
*
center) of the snorkel may be included for calculation of max. horizontal run.
SNORKEL
4" CLEARANCE
GROUND WINDOW WELL
GRAVEL
DRAIN
Fig. 22
VERTICAL THROUGH THE ROOF
APPLICATIONS
MAXIMUM
10 FT
(305cm)
MINIMUM
8 FT./
MAXIMUM
40 FT.
VERTICAL
RISE
PIPE STRAPS
EVERY 3
(92cm)
Fig. 24
This Gas Fireplace has been approved for, a) Vertical installations up to 40 feet (12 metres) in height.
Up to a 10 ft. horizontal vent run can be installed within the vent system using a maximum of two 90o elbows. (Fig. 24)
b) Up to two 45o elbows may be used within the horizontal
run. For each 45o elbow used on the horizontal level the maximum horizontal length must be reduced by 18 inches.
Example: Maximum horizontal length
0- 45o elbows 10 ft. 1- 45o elbows 8.5 ft. 2- 45o elbows 7 ft.
- 14 -
VERTICAL THRU THE ROOF APPLICATIONS
TO INSTALL VERTICAL VENTING
c) A minimum of an 8 ft. vertical rise. d) Two sets of 45 degree elbow offsets within these
vertical installations. From 0 to a maximum of 8 ft. of vent pipe can be used between elbows. (Fig. 25)
e) 7DVCS must be used to support offsets. (Fig. 26)
This application will require that you first determine the roof pitch and use the appropriate starter kit. (See Venting Components List)
MAX.
8 FEET
2.44m
Fig. 25
MAX.
8 FEET
2.44m
45°
45°
40'(12m)
Fig. 26
TYPICAL 7DVCS
APPLICATION
1. Locate your fireplace.
2. Plumb to centre of the (4") flue collar from ceiling above and mark position.
3. Cut opening equal to 9-3/8" x 9-3/8"
(240 mm x 240 mm).
4. Proceed to plumb for additional openings through the roof. In all cases, the opening must provide a minimum of 1 inch clearance to the vent pipe, i.e., the hole must be at least 9-3/8" x 9-3/8" (240 mm x 240 mm).
5. Place fireplace into position.
6. Place firestop(s) #7DVFS or Attic Insulation Shield #7DVAIS into position and secure. (Fig. 29)
7. Install roof support (Fig. 27) and roof flashing making sure upper flange of flashing is below the shingles. Fig. 30.
8. Install appropriate pipe sections until above the flash­ing. (See Fig. 30).
9. Install storm collar and seal around the pipe.
10. Add additional vent lengths for proper height. Fig. 28.
11. Apply high temperature sealant to 4" and 7" collars of vertical vent termination and install.
Attic Insulation Shield
11"
11"
JOIST
TYPICAL ROOF
SUPPORT
APPLICATION
Fig. 27
TYPICAL OFFSET INSTALLATION
VENT TERMINATION
STORM COLLAR
ROOF FLASHING
ROOF SUPPORT
CEILING JIOSTS
Fig. 28
40 FEET
(12.2mm)
ROOF
2' Min.
ATTIC INSULATION
JOISTS
ATTIC INSULATION
SHIELD
TYPICAL STRAIGHT-UP INSTALLATION
The minimum height of the vent above the highest point of penetration through the roof is 2 feet. See Fig. 28.
Ceiling Installation
11"
11"
UPPER FLOOR
JOIST
FIRESTOP SPACER
NAILS (4)
Fig. 29
Fig. 29 If there is a room above ceiling level, firestop spacer must be installed on both the bottom and the top side of the ceiling joists. If an attic is above ceiling level a 7DVAIS (Attic Insulation Shield) must be installed.
Fig. 30 The enlarged ends of the vent section
always face downward.
SHEETMETAL SCREWS (#5) 3 PER JOINT
SEALANT
STORM COLLAR
SHEETMETAL SCREWS (#5) 3 PER JOINT
SEALANT
STORM COLLAR
Fig. 30
- 15 -
CRIMPED ENDS VENTING COMPONENTS
Starter Kit -Model 7DVSK - Sidewall Venting Starter Kit - Model 7TDVSKV - Vertical Venting
for 7DVSKV-A order 1/12 to 6/12 roof pitch for 7DVSKV-B order 7/12 to 12/12 roof pitch for 7DVSKV-F order flat roof
Starter Kit - Model 7TDVSKS -Snorkel Kit
for Below Grade Installation
45º elbow kit
7DVT45 for Vertical Installation Offsets
90º transition elbow kit
7DVRT90 for Vertical Sidewall Applications or thru-the-roof.
Telescopic vent sections
7DVP610 - 6" to 10" adjustable length 7DVP1018 - 10" to 18" adjustable length 7DVP1834 - 18" to 34" adjustable length 7DVP3466 - 34" to 66" adjustable length
Pipe sections for vertical or horizontal venting
Model 7DVP8" - 4 per box Model 7DVP12" - 4 per box Model 7DVP24" - 4 per box Model 7DVP36" Model 7DVP48"
Firestop Spacer
Model 7DVFS
Attic Insulation Shield
Model 7DVAIS
Vertical/Horizontal Combination Offset Support
Model 7DVCS
7DVSS Siding Shield (to protect siding)
- 16 -
TWIST LOCK VENTING COMPONENTS
Starter Kit -Model 7TDVSK - Sidewall Venting Starter Kit - Model 7TDVSKV - Vertical Venting
for 7TDVSKV-A order 1/12 to 6/12 roof pitch for 7TDVSKV-B order 7/12 to 12/12 roof pitch for 7TDVSKV-F order flat roof
Starter Kit - Model 7TDVSKS -Snorkel Kit
for Below Grade Installation
45º elbow kit
7TDV45 for Vertical Installation Offsets
90º transition elbow kit
7TDVRT90 for Vertical Sidewall Applications or thru-the-roof.
Telescopic vent sections
7TDVP1218 - 12" to 18" adjustable length 7TDVP3566 - 35" to 64" adjustable length
Pipe sections for vertical or horizontal venting
Model 7TDVP8" Model 7TDVP12" Model 7TDVP24" Model 7TDVP36" Model 7TDVP48"
Firestop Spacer
Model 7DVFS
Attic Insulation Shield
Model 7DVAIS
- 17 -
Vertical/Horizontal Combination Offset Support
Model 7DVCS
7DVSS Siding Shield (to protect siding)
OPERATING INSTRUCTIONS
GENERAL GLASS INFORMATION
Only glass approved for use in with this product may be used for replacement.
1. The use of substitute glass will void all product warranties.
2. Care must be taken to avoid breakage of the glass.
Under no circumstances should this fireplace be operated without the front glass or with a broken glass. Replacement of the glass (with gasket) as supplied by the manufacturer should be done by a licenced qualified service person.
LOUVRE REMOVAL
D232
To remove louvres first remove the two (2) screws (Fig. 31) fastening the louvre assembly to the fireplace. Lift the louvre assembly straight out sliding the back guides out of the fireplace body. (To reinstall, reverse).
GLASS REMOVAL
D232
1 . Remove frame window brass trim (See Trim Removal
section)
2. Remove remaining bottom 3/8" nut at the bottom of the frame window.
3. Remove 3/8" nut from each side of the frame window (Fig. 32).
4. Remove frame window by pulling it forward and up.
GLASS FRAME
OUTER NUTS
DRAWING 1
DRAWING 2
Front View
Screws
Fig. 31
TRIM REMOVAL
D232
1. Remove the two (2) outer 3/8" nuts holding the frame window brass trim in place. (Fig. 32)
2. Remove the frame window brass trim by moving it straight forward.
Side Nuts
BOTTOM NUT
Fig. 32
- 18 -
GLASS CLEANING
It will be necessary to clean the glass periodically. During start-up condensation, which is normal, forms on the inside of the glass and causes lint, dust and other airborne particles cling to the glass surface. Also initial paint curing may deposit a slight film on the glass. It is therefore recommended that the glass be cleaned two or three times with a non-ammonia household cleaner and warm water (we recommend gas fireplace glass cleaner). After that the glass should be cleaned two or three times during each heating season depending on the circumstances present.
Clean glass after first two weeks of operation.
INSTALLATION OF LOGS &
BURNER LAVA ROCK MATERIAL
D232
1 . Remove front glass. (See "Glass Removal" section)
2. Remove logs from packaging.
3. Place rear log (KR4) on rear bracket (ensure log is seated properly, leveled and centered to the unit), so it will not move from side to side and it is firmly positioned on the bracket.
4. Slip front ember log (KR1) down in the front deflector.
5. Place front left log (KR2) on top burner, left side. Use log's bottom holes to locate it into the left bracket log locator studs.
6. Place front right log (KR3) on top of burner, right side. Use log's bottom holes to locate it into the right bracket log locator studs.
7. Place small lava rocks and ember material on top of burner. (See Fig. 34 for proper location).
8. Place top left log (KR5) onto locator notches. Ensure log is secure.
9. Place top right log (KR6) onto locator notches. Ensure log is secure.
D232
KR2
Top logs must be placed properly into notches
KR5
Burner Lava Rock Placement
KR6
KR4
KR3
KR1
Fig. 34
- 19 -
MAINTENANCE
L
O
H
I
Turn
counterclockwise
to decrease
flame height.
Turn clockwise
to increase
flame height.
FLAME ADJUSTMENT (RN/RP MODELS)
1. It is important to keep the burner and the burner compartment clean. This must be done periodically, at least once per season. (See Cleaning Procedure).
2. Clean the brass trim using a soft clean cloth, slightly dampened with lemon oil and buff with a soft clean cloth. Do NOT use brass polish or household cleaners as these products will damage the brass trim. Lemon oil can be obtained at supermarkets or hardware stores.
3. The optional FK12 and FK24 Fan requires periodic cleaning. Check the fan and the area around the fan assembly and wipe or vacuum at least once per month during the operating season.
4. Contact your local representative to arrange an annual service program.
CLEANING PROCEDURE
1. Turn off pilot light at gas valve.
2. Remove front glass.
3. Remove logs.
For units equipped with Hi/Lo valves, flame adjustment is accomplished by rotating the Hi/Lo adjustment knob located near the centre of the gas control. (Fig. 38 & 39)
I
H
Turn
counterclockwise
to increase
flame height.
L
O
Turn clockwise
to lower
flame height.
Fig. 38
Fig. 39
CAUTION: LOGS MAY BE HOT
4. Vacuum burner compartment especially around orifice/primary air openings.
5. Reinstall logs.
6. Check pilot and main burner operation.
7. Reinstall glass front.
8. Recheck pilot and main burner operation.
9. Check visually the flame pattern and compare with Fig. 39, 40a & b or 41.
3/8" - 1/2"
SIT PILOT
D232
FLAME CHARACTERISTICS
It is important to periodically perform a visual check of the pilot and the burner flames. Compare them to the pictorials illustrated below (Fig. 40a & b, or 41). If any of the flames appear abnormal call a service person.
PSE PILOT
Fig. 40a
Fig. 40b
- 20 -
Fig. 41
LIGHTING AND OPERATING INSTRUCTIONS
it
P
I
L
O
T
OF
F
O
N
FOR YOUR SAFETY READ BEFORE LIGHTING
WARNING: If you do not follow these instructions exactly, a fire or explosion may result
causing property damage, personal injury or loss of life.
A. This fireplace has a pilot which must be lit manually.
When lighting the pilot follow these instructions exactly.
B. BEFORE LIGHTING smell all around the fireplace area for
gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor.
WHAT TO DO IF YOU SMELL GAS
Do not try to light any fireplace.
Do not touch any electric switch
Do not use any phone in your building
Immediately call your gas supplier from a neighbor's phone. Follow the gas supplier's instructions.
If you cannot reach your gas supplier, call the Fire Department
LIGHTING INSTRUCTIONS
1. STOP! Read the safety information above on this page.
2. Turn off all electrical power to the fireplace.
3. For MN/MP/TN/TP appliances ONLY, go on to Step 4. For RN/RP appliances turn the On/Off switch to off position or set thermostat to lowest level.
4. Open control access panel.
5. Push in gas control knob slightly and turn clockwise to "OFF". Do not force.
OFF
LO
HI
OFF
PILOT
PILOT
ON
C. Use only your hand to push in or turn the gas control
knob. Never use tools. If the knob will not push in or turn by hand, do not try to repair it, call a qualified service technician. Applying force or any attempted repair may result in a fire or explosion.
D. Do not use this fireplace if any part has been under water.
Immediately call a qualified service technician to inspect the fireplace and to replace any part of the control system and any gas control which has been under water.
10. Push the control knob all the way in and hold. Immediately light the pilot by repeatedly depressing the piezo spark ignitor until a flame appears. Continue to hold the control knob in for about one (1) minute after the pilot is lit. Release knob and it will pop back up. Pilot should remain lit. If it goes out, repeat steps 5 through 8.
OR
EURO SIT SIT NOVA HONEYWELL
6. Wait five (5) minutes to clear out any gas. Then smell for gas, including near the floor. If you smell gas, STOP! Follow "B" in the safety information above on this page. If you don't smell gas, go to the next step.
7. Remove glass door before lighting pilot. (See Glass Frame Removal in manual).
8. Visibly locate pilot by the main burner.
9. Turn knob on gas control counterclockwise to "PILOT".
TO TURN OFF GAS TO APPLIANCE
TO TURN OFF GAS TO FIREPLACE
1. Turn the On/Off switch to Off position or set the thermostat to lowest setting.
2. Turn off all electric power to the fireplace if service is to be performed.
• If knob does not pop up when released, stop and immediately call your service technician or gas
supplier.
• If after several tries, the pilot will not stay lit, turn the gas control knob to "OFF" and call your service technician or gas supplier.
11. Replace glass door.
12. Turn gas control knob to "On" position.
13. For RN/RP appliances turn the On/Off switch to "On" position or set thermostat to desired setting.
14. Turn on all electrical power to the fireplace.
4. Push in gas control knob slightly and turn clockwise to "OFF". Do not force.
5. Close control access panel.
3. Open control access panel.
- 21 -
TROUBLE SHOOTING THE GAS CONTROL SYSTEM
HONEYWELL MILLIVOLT VALVE
START
CHECK
GAS SUPPLY ON
YES
PILOT LIGHTS WITH PIEZO IGNITOR
YES
PILOT STAYS LIT
YES
NO
NO
NO
SUPPLY LINE HOOKED UP
SHUTOFF VALVE OPEN
LOCKOUT HAS ENGAGED. WAIT
60 SECONDS AND TRY AGAIN.
FOR SPARK AT ELECTRODE WHILE DEPRESSING PIEZO 1/8" GAP TO PILOT HOOD NEEDED.
ALL WIRING CONNECTIONS
REPLACE PIEZO IGNITOR
FOR AIR IN THE LINES
THERMOPILE NEEDS A
MINIMUM 325mV. ADJUST PILOT FLAME HEIGHT.
ALL WIRING CONNECTIONS.
REPLACE THERMOPILE
THERMOCOUPLE NEEDS A
MINIMUM OF 14mV.
DEFECTIVE VALVE. TURN TO PILOT, METER SHOULD READ GREATER THAN 100 mV. IF NOT, REPLACE.
PILOT LIGHTS MAIN BURNER
YES
SYSTEM OK.
NO
VALVE IS TURNED ON
ON/OFF SWITCH IS NOT
TURNED ON. WATCH FOR GROUNDED WIRES!
THERMOPILE NEEDS A MINIMUM 325mV.
PLUGGED BURNER ORIFICE.
- 22 -
TROUBLE SHOOTING THE GAS CONTROL SYSTEM
SIT NOVA 820 MILLIVOLT VALVE
Note: Before trouble shooting the gas control system, be sure external gas shut off is in the "On" position.
WARNING: BEFORE DOING ANY GAS CONTROL SERVICE WORK, REMOVE GLASS FRONT.
SYMPTOM POSSIBLE CAUSES CORRECTIVE ACTION
1. Spark ignitor will not light. A. Defective or misaligned Using a match, light pilot. If pilot lights, turn off pilot and electrode at pilot. push the red button again. If pilot will not light - check gap
at electrode and pilot-should be 1/8" to have a strong spark.
B. Defective ignitor (Push Button) Push Piezo Ignitor Button. Check for spark at electrode and
pilot. If no spark to pilot, and electrode wire is properly connected, replace ignitor.
2. Pilot will not stay lit after A. Defective pilot generator 1.Check pilot flame. Must impinge on thermocouple/
carefully following lighting (thermocouple), remote wall thermopile. Note: this pilot burner assembly utilizes both instructions. switch. a thermocouple and a thermopile. The thermocouple
operates the main valve operation (On and Off). Clean and or adjust pilot for maximum flame impingement on thermopile and thermocouple.
B. Defective automatic valve Turn valve knob to "Pilot". Maintain flow to pilot; millivolt
operator. meter should read greater than 10 mV. If the reading is
okay and the pilot does not stay on, replace the gas valve. Note: An interrupter block (not supplied) must be used to conduct this test.
3. Pilot burning, no gas to A. Wall switch or wires Check wall switch and wires for proper connections. Jumper
burner. replace defective wall switch. If okay, jumper wires across
wall switch wires at valve, if burner comes on, wires are faulty or connections are bad.
B. Thermopile may not be 1. Be sure wire connections from thermopile at gas valve
generating sufficient terminals are tight and thermopile is fully inserted into pilot millivoltage. bracket.
2. One of the wall switch wires may be grounded. Remove wall switch wires from valve terminals if pilot now stays lit, trace wall switch wiring for ground. May be grounded to fireplace or gas supply.
3. Check thermopile with millivolt meter. Take reading at thermopile terminals of gas valve. Should read 250-300 millivolts (minimum 150) while holding valve knob de­pressed in pilot position and wall switch "Off". Replace faulty thermopile if reading is below specified minimum.
C. Plugged burner orifice. Check burner orifices for debris and remove.
D. Defective automatic valve Turn valve knob to "On", place wall switch to "On" millivolt
operator. meter should read greater than 100 mV. If the reading is
okay and the burner does not come on, replace the gas valve.
4. Frequent pilot outage A. Pilot flame may be too low Clean and/or adjust pilot flame for maximum flame problem. or blowing (high) causing the impingement on thermopile and thermocouple.
pilot safety to drop out.
B. Possible blockage of the vent
terminal.
Check the vent terminal for blockage (recycling the flue gases)
- 23 -
REPLACEMENT PARTS LIST
DESCRIPTION D232
1. Log Set Complete 10000160 1a. Log Ember Front KR1 1b. Log Front Left KR2 1c. Log Front Right KR3 1d. Log Rear KR4 1e. Log Top Left KR5 1f. Log Top Right KR5
2. Burner Lava Rock (Package) 57897 3a. Burner with Tiles Nat. 57903 3b. Burner with Tiles Prop. 57904
4. Ceramic Tile (Single) 57803 5a. Orifice Front Nat. 5b. Orifice Front Prop. 6a. Orifice Main Nat. 6b. Orifice Main Prop. 7a. Orifice Pilot SIT Nat. 54273 7b. Orifice Pilot SIT Prop. 54272 8a. Orifice Pilot PSE Nat. 10001822 8b. Orifice Pilot PSE Prop. 10001823 9a. Pilot Assembly SIT Nat. 10000674 9b. Pilot Assembly SIT Prop. 10000675 10a. Pilot Assembly PSE Nat. 10001741 10b. Pilot Assembly PSE Prop. 10001742
11. Pilot SIT-Top Convertible 10001295
12. Pilot w/ignitor and cable PSE 10001824
13. Pilot Tubing w/fittings 53211
14. Manifold Tubing w/fittings 57318
15. Thermocouple SIT 53373
16. Thermocouple PSE 10001825
17. Thermopile 51827
18. Electrode Ignitor w/cable SIT 10001297
19. Ignitor Piezo SIT 52464
20. Ignitor Piezo Honeywell 20000062 21a. Valve SIT 820 Nat. 52677 21b. Valve SIT 820 Prop. 52678
22. Extension Knob Hi/Lo SIT (RN/RP) 10000165 23 Extension Knob On/Off SIT (RN/RP) 10000166 24a. Valve Honeywell Nat. 10001782 24b. Valve Honeywell Prop. 10001759 25a. Valve Eurosit 630 Nat. 53448 25b. Valve Eurosit 630 Prop. 53446
26. Fan with Bracket 54103
27. Electrical Cord (6ft.) 51865
28. Fan Temperature Sensor 51704
29. Speed Control 51738
30. Speed Control Knob 51882
31. Glass with Gasket - Front 52035
32. Glass with Gasket - Side 52032
33. Gasket Glass 57316 36a. Frame Window - Left Side 52145 36b. Frame Window - Right Side 52860
37. Frame Window - Front 57244
39. Trim Frame Window (PB) 52027
41. Top Louvre 52019
42. Front Louvre Assembly 57908
43. Access Door Assembly (with handle) 52030
44. Latch 52057
45. Remote Switch 53606
46. Remote Wire Harness with Terminals 57265
SEE RATING PLATE FOR ORIFICE SIZE SEE RATING PLATE FOR ORIFICE SIZE SEE RATING PLATE FOR ORIFICE SIZE SEE RATING PLATE FOR ORIFICE SIZE
- 24 -
FREESTANDING REPLACEMENT PARTS
42
41
33
39
37
43
31
44
33
32
36 a/b
28
39
30
29
43
43
5/6 a,b
21a,b
3a/b
10
47
4
26
11
17
9 a/b
18
15
23
22
13
19
T
O
O
L
L
I
P
O
F
F
it
H I
7 a/b
42
43
39
41
25a,b
40
2
46
45
20
27
L
I
O
H
OFF
PILOT
ON
24a,b
PILOT
10a/b
ADJ
8 a/b
16
12 17
13
#1 - COMPLETE LOG SET
1d
1e
1b
1a
1f
1c
D232
- 25 -
OPTIONS
FAN KIT - FK24
It will be easier to install the fan before connecting the gas line to the fireplace.
1. Open front access door panel by pulling forward on
brass lip.
2. Install the fan through the opening at the back of the
pedestal, with the outlet pointed up and the fan mounting bracket facing the back of the fireplace (Fig. 44). . The fan mounts over two studs which hold the fan just below the firebox floor. Hold the fan in place with the two nuts provided.
3. Locate the fan speed control/junction box on screw
studs provided on base of the fireplace. Tighten with nuts.
4. Install thermal sensor element on screw studs located
to the right of the gas valve on the burner base.
5. Plug in grounded service cord to a convenient wall
receptacle.
This fan assembly comes completely wired to eliminate the need for electricians. This electrical device, when installed, must be electrically connected and grounded in accordance with local codes. In the absence of local codes, with the current CSA C22.1 CANADIAN ELECTRICAL CODE.
For U.S.A. installation: Follow local codes and the NATIONAL ELECTRICAL CODE ANSI/ NFPA No.70-1984.
Stud
Fan is installed at the back of the pedestal
Fig. 44
Fan speed control/ Junction box
Thermal sensor location
Valve
TOP VIEW
Should this fan require servicing, the power supply must be disconnected. For rewiring
of any replacement components see Fig. 43.
REMOTE CONTROL
Only for units with RN/RP valve. MRC1 - On/Off Button Remote Control MRC2 - Temperature Control Remote MRC3 - Temperature Control w/digital display &
24 hour programmable clock
IMT - Wall Mounted Thermostat
Black White
Ground
A: SPEED CONTROL B: TEMPERATURE SENSOR C: FAN
C
B
A
Fig. 43
- 26 -
- 27 -
LIMITED WARRANTY & EXTENDED LIFE TIME PROTECTION
For Gas Appliance Products*
BASIC WARRANTY: The CFM Majestic, Inc. (hereinafter referred to collectively as the "Company") warrants that your new Vermont Castings Gas Appliance is free from manufacturing and material defects for a period of one year from date of installation, subject to the following conditions and limitations.
EXTENDED LIFE TIME WARRANTY: The heat exchanger, combustion chamber and ceramic burner parts of every *CFM Majestic, Inc. product are warranted for life to the original owner, subject to proof of purchase and the following conditions and limitations:
1.
This new CFM Majestic, Inc. product must be installed by a competent, authorized service contractor. It must be installed and operated at all times in accordance with the Installation and Operating instructions furnished with the product. Any alteration, willful abuse, accident, or misuse of the product shall nullify this warranty.
2.
This warranty is non-transferrable, and is made to the original owner, provided that the purchase was made through an authorized supplier of the Company.
3.
This warranty is limited to the repair or replacement of part(s) found to be defective in material or workmanship, provided that such part(s) have been subjected to normal conditions of use and service, after said defect is confirmed by the Company's inspection.
4.
The Company may, at its discretion, fully discharge all obligations with respect to this warranty by refunding the wholesale price of the defective part(s).
5.
Any installation, labour, construction, transportation, or other related costs/ expenses arising from defective part(s), repair, replacement, or otherwise of same, will not be covered by this warranty, nor shall the Company assume responsibility for same. Further, the Company will not be responsible for any incidental, indirect, or consequential damages, except as provided by law.
6.
All other warranties - expressed or implied - with respect to the product, its components and accessories, or any obligations/liabilities on the part of the Company are hereby expressly excluded.
7.
The Company neither assumes, nor authorizes any third party to assume, on its behalf, any other liabilities with respect to the sale of this CFM Majestic, Inc. product.
8.
The warranties as outlined within this document do not apply to chimney components or other non CFM Majestic, Inc. accessories used in conjunction with the installation of this product.
9.
The Company will not be responsible for . . . a) Down drafts or spillage caused by environmental conditions such as
near-by trees, buildings, roof tops, hills, or mountains.
b) Inadequate ventilation or negative air pressure caused by mechanical
systems such as furnaces, fans, clothes dryers, etc.
10.
This warranty is void if: a) The fireplace has been operated in atmospheres contaminated by
chlorine, fluorine or other damaging chemicals.
b) The fireplace is subjected to prolonged periods of dampness or
condensation.
c) Any damage to the fireplace, combustion chamber, heat exchanger
or other components due to water, or weather damage which is the result of, but not limited to, improper chimney/venting installation.
d) Any alteration, willful abuse, accident, or misuse of the product.
Glass doors are not warranted for breakage due to misuse or accident. Brass parts should be cleaned with lemon oil only. Brass cleaners cannot be used. Mortar mix and masonry cleaners may corrode the brass finish. The Company will not be responsible for, nor will it warrant any brass parts which are damaged by external chemicals or down draft conditions.
1) Contact your supplier. Make sure you have your warranty , your sales receipt, and the model/serial number of your CFM Majestic, Inc. product.
2) DO NOT ATTEMPT TO DO ANY SERVICE WORK YOURSELF.
GLASS DOORS & BRASS PLATED PARTS
IF WARRANTY SERVICE IS NEEDED . . .
GARANTIE DE BASE: The CFM Majestic. Inc. (aux présentes nommée la "Société") garantit votre nouveau foyer au gaz CFM Majestic, Inc. contre tous défauts de fabrication et de matières premières pour une période d'un an à compter de la date d'installation, sujet aux conditions et limitations suivantes.
GARANTIE A VIE PROLONGEE: Les pièces de l'échangeur de chaleur, de la chambre à combustion et du brûleur en céramique de tout produit *CFM Majestic, Inc. sont garanties pour la vie de l'acheteur d'origine, le tout sujet à une preuve d'achat et aux conditions et limitations suivantes:
1.
Ce nouveau produit CFM Majestic, Inc. doit être installé par un entrepreneur de service autorisé et compétent. Il doit être installé et utilisé en tout temps selon les instructions d'installation et de fonctionnement fournies avec le produit. Toute altération, abus volontaire, accident ou mauvais usage du produit annulera cette garantie.
2.
Cette garantie n'est pas transférable et est offerte à l'acheteur au détail d'origine, à condition que l'achat soit effectué par l'entremise d'un détaillant autorisé de la Société.
3.
Cette garantie est limitée à la réparation ou au remplacement de(des) pièce(s) trouvée(s) défectueuse(s) en matières premières ou main-d'oeuvre, à condition que lesdites pièces aient été sujettes aux conditions normales d'usage et de service, après que ledit défaut a été confirmé par une inspection par la Société.
4.
La Société peut, à sa discrétion, se décharger entièrement de toutes obligations se rapportant à cette garantie en remboursant le prix de gros de la(des) pièce(s) défectueuse(s).
5.
Tous les frais/dépenses d'installation, de main-d'oeuvre, de construction, de transport ou autres causés par une (des) pièce(s) défectueuse(s), une réparation, un remplacement ou autre, ne seront pas couverts sous cette garantie, et la Société n'assume aucune responsabilité pour ceux-ci. De plus, la Société ne pourra être tenue responsable pour tous dommages fortuits ou indirects sauf la ou prévu par la loi.
6.
T outes autres garanties, exprimées ou sous-entendues, en ce qui a trait au produit, ses composants et accessiores, ou toutes obligations/responsabilités de la part de la Société sont aux présentes expressment excluses.
7.
La Société n'assume et n'autorise personne à assumer, en son nom, toutes responsabilités en ce qui a trait à la vente de ce produit CFM Majestic, Inc..
8.
Les garanties, telles que décrites dans ce document, ne s'appliquent pas aux compasants de cheminée ou aux autres accessoires non CFM Majestic, Inc. utilisés conjointement pour l'installation de ce produit.
9.
La Société n'encourrera aucune responsabilité pour . . . a) Les refoulements de cheminées ou débordements causés par les conditions
environnementales comme par les arbres, les édifices, les toits, les côteaux ou les montagnes adjacents.
b) Une ventilation inadéquate ou une pression d'air négative causée par des
systèmes mécaniques comme les fournaises, les ventilateurs, les sécheuses, etc.
10.
Cette garantie est nulle si: a) Le foyer a été utilisé dans une atmosphère contaminée par du chlore, du
fluor ou tous autres produits chimiques.
b) Le foyer est assujetti à de longues périodes d'humidité ou de condensation. c) Des dommages sont causés au foyer, à la chambre de combustion. à
l'échangeur de chaleur ou aux autres composants par de l'eau ou par la température qui est le résultat mais sans y être limité, d'une mauvaise installation de cheminée/ventilation.
d) Toute altération, abus volontaire, accident ou mauvais usage du produit
annulera cette garantie.
Les portes en verre ne sont pas garanties contre le bris causé par un mauvais usage ou un accident. Les pièces en laiton devraient être nettoyées qu'avec de l'essence de citron. Les nettoyeurs de laiton ne peuvent pas être utilisés. La Société ne sera pas responsable pour, et ne garantit pas les pièces en laiton qui sont endommagées par des conditions chimiques externes ou de refoulement.
1. Communiquez avec votre détaillant. Assurez-vous que vous avez votre garantie, votre reçu de caisse ainsi que le numéro de modèle/série de votre produit CFM
Majestic, Inc.
2. NE TENTEZ PAS D'EFFECTUER DES REPARATIONS VOUS-MEME.
PORTES EN VERRE & PIECES PLAQUEES LAITON
SI UN SERVICE SOUS GARANTIE EST REQUIS . . .
CFM Majestic, Inc.
410 Admiral Blvd. Mississauga, Ontario, Canada L5T 2N6 905-670-7885
www.vermontcastings.com
- 28 -
© Copyright
CFM Majestic, Inc.
10002735 6/00
Loading...