Builder Top Vent
Direct Vent
Models: 33LDVT, 36LDVT
39LDVT, 43LDVT
INSTALLER/CONSUMER
SAFETY INFORMATION
PLEASE READ THIS MANUAL
BEFORE INSTALLING AND USING
APPLIANCE
WARNING!
IF THE INFORMATION IN THIS
MANUAL IS NOT FOLLOWED
EXACTLY, A FIRE OR EXPLOSION
MAY RESULT CAUSING
PROPERTY DAMAGE, PERSONAL
INJURY OR LOSS OF LIFE.
FOR YOUR SAFETY
Installation and service must be
performed by a qualified installer,
service agency or the gas supplier.
WHAT TO DO IF YOU SMELL GAS:
Installation Instructions and
Homeowner’s Manual
• Do not try to light any appliance.
• Do not touch any electric switch; do
not use any phone in your building.
• Immediately call your gas supplier
from your neighbor’s phone. Follow
the gas suppliers instructions.
• If you cannot reach your gas
supplier call the fire department.
DO NOT STORE
OR USE GASOLINE OR OTHER
FLAMMABLE VAPORS AND
LIQUIDS IN THE VICINITY OF THIS
OR ANY OTHER APPLIANCE.
INSTALLER: Leave this manual with the appliance.
CONSUMER: Retain this manual for future reference.
10007852 5/07 Rev. 9
Page 2
LDVT Series Direct Vent Gas Fireplace
Table of Contents
PLEASE READ THE INSTALLATION & OPERATING INSTRUCTIONS BEFORE USING THIS APPLIANCE.
Thank you and congratulations on your purchase of a CFM Corporation fireplace.
IMPORTANT: Read all instructions and warnings carefully before starting installation.
Failure to follow these instructions may result in a possible fire hazard and will void the warranty.
Installation & Operating Instructions
Important Curing/Burning Instructions .................................................................................3
This gas fireplace should be installed by a qualified
installer, preferably NFI or WETT (Canada) certified, in
accordance with local building codes and with current CSA-
B149.1 Installation codes for Gas Burning Appliances and
Equipment. For USA Installations follow local codes and/or
the current National Fuel Gas Code. ANSI Z223.1/NFPA 54.
In the Commonwealth of Massachusetts, all gas fitting
and installation of this heater shall only be done by a
licensed gas fitter or licensed plumber.
FOR SAFE INSTALLATION AND OPERATION PLEASE
NOTE THE FOLLOWING:
1. This fireplace gives off high temperatures and should be
located out of high traffic areas and away from furniture and
draperies.
2. Children and adults should be alerted to the hazards of the
high surface temperatures of this fireplace and should stay
away to avoid burns or ignition of clothing.
3. CAUTION: Due to high glass surface temperature chil-
dren should be carefully supervised when in the same
room as fireplace.
must be installed on a metal or wood panel extending the
full width and depth of the fireplace.
12. This fireplace requires adequate ventilation and combustion
air to operate properly.
13. This fireplace must not be connected to a chimney flue
serving a separate solid fuel burning fireplace.
14. When the fireplace is not in use it is recommended that the
gas control valve be left in the OFF position.
15. These units have been approved for bedroom use.
33LDVT / 36LDVT / 39LDVT / 43LDVT
Certified To
ANSI Z21.88-2005 / CSA 2.33-2005
Vented Gas Fireplace Heaters
WARNING: Check with your electronics manufacturer
before installing a television or other electronic device above this fireplace.
This appliance may be installed in an aftermarket
permanently located, manufactured home or mobile home,
where not prohibited by local codes.
This appliance is only for use with the type of gas indicated
on the rating plate. This appliance is not convertible for
use with other gases, unless a certified kit is used.
Th e LDV T has been appro ved for m obile home
installations.
4. Under no circumstances should this fireplace be modified.
Parts removed for servicing should be replaced prior to
operating this fireplace again.
5. Installation and any repairs to this fireplace must be per
formed by a qualified installer, service agency or gas supplier. A professional service person should be contacted to
inspect the fireplace annually. More frequent cleaning may
be required due to excess lint and dust from carpeting, bedding material, etc.
6. Control compartments, burners and air passages in this fireplace should be kept clean and free of dust and lint. Make
sure that the gas valve and pilot light are turned off before
you attempt to clean this fireplace.
7. The venting system (chimney) of this fireplace should be
checked at least once a year and if needed your venting
system should be cleaned.
8. Keep the area around your fireplace clear of combustible
materials, gasoline and other flammable vapour and liquids.
This fireplace should not be used as a dry-ing rack for cloth
ing, nor should Christmas stockings or decorations be hung
on or around the fireplace.
9. Under no circumstances should any solid fuels (wood, coal,
paper or cardboard etc.) be used in this fireplace.
10. The flow of combustion and ventilation air must not be obstructed in any way.
11. When the fireplace is installed directly on carpeting, vinyl tile
or any combustible material other than wood, this fireplace
10007852
-
IMPORTANT:
PLEASE REVIEW THE FOLLOWING CAREFULLY
Remove any plastic from from parts before turning the
fireplace ON.
It is normal for fireplaces fabricated of steel to give off
some expansion and/or contraction noises during the
start up or cool down cycle. Similar noises are found
with your furnace heat exchanger or car engine.
It is not unusual for your gas fireplace to give off some
odor the first time it is burned. This is due to the curing
of the paint and any undetected oil from the manufacturing process.
Please ensure that your room is well ventilated-open
all windows.
It is recommended that you burn your fireplace for at least
ten (10) hours the first time you use it. If the optional fan
kit has been installed, place the fan switch in the “OFF”
position during this time.
-
Proposition 65 Warning: Fuels used in gas, woodburning or oil fired appliances, and the products of
combustion of such fuels, contain chemicals known to
the State of California to cause cancer, birth defects
and other reproductive harm.
California Health & Safety Code Sec. 25249.6
3
Page 4
LDVT Series Direct Vent Gas Fireplace
F
V - Rough Opening Width
Rough
Opening
Height
Rough
Opening
Depth
S
S
T
R
E
G
J
D
A
Q
B
K
L
M
O
Gas Line
Access
Gas Line
Access
Low
Voltage
Electrical
Access
Electrical
Access
I
U
C
P
Low
Voltage
Access
N
Fireplace Dimensions
Fig. 1 Fireplace specifications and framing dimensions.
A - Flat on wall B - Cross corner C - **Island
D - *Room divider E - *Flat on wall corner F - Chase installation
Y - 6” minimum
Note (Fig. 2):
** Island (C) and Room Divider (D) installation is possible as
long as the horizontal portion of the vent system (X) does not
exceed 20’ (6m). See details in manual Venting Section.
* When you install your fireplace in(D) Room divider or (E)
Flat on wall corner positions (Y), a minimum of 6” (152mm)
clearance must be maintained from the perpendicular wall and
the front side edge of the fireplace. See (Y) in Fig. 2.
Clearance to Combustibles
Top of Unit to Ceiling ................................ 36” (914mm)
Appliance
Top ...........................................................
The height that a combustible mantel is fitted above the
fireplace is dependent on the depth of the mantel. This
also applies to the distance between the mantel leg (if
fitted) and the fireplace.
For the correct mounting height and widths refer to
Figures 3a and 3b.
The fitting of a bay window trim kit does not effect
the distances and reference points referred to in the
diagram and chart.
Noncombustible mantels and legs may be installed at
any height and width around the appliance.
When using paint or lacquer to finish the mantel, such
paint or lacquer must be heat resistant to prevent
discoloration.
10007852
0” (0mm)
0” (0mm)
0” (0mm)
0” (0mm)
1” (25mm)
Top of
CFM146
Combustion
Chamber
Mantel Chart
Mantel Shelf Mantel from Top
Ref. or Breast Plate Ref. of Combustion Chamber
Depth 36/39/43 LDVT 33LDVT
V 10” (254 mm) A 17” (432 mm) 16
W 8” (203 mm) B 15” (381 mm) 14
X 6” (152 mm) C 13” (330 mm) 12¹⁄₂” (318 mm)
Y 4” (101 mm) D 11” (279 mm) 10¹⁄₂” (267 mm)
Z 2” (51 mm) E 9” (229 mm) 8
Fig. 3a Combustible mantel minimum installation.
Black
Surround
Face
Side of
Combustion Chamber
Mantel Mantel Leg FromSide
Ref. Leg Depth Ref. of Comb. Opening
F 10” (254 mm) K 11
G 8” (203 mm) L 9
H 6” (152 mm) M 7¹⁄₂” (191 mm)
I 4” (101 mm) N 5¹⁄₂” (140 mm)
J 2” (51 mm) O 3
Fig. 3b Combustible mantel leg minimum installation.
¹⁄₂” (292 mm)
¹⁄₂” (241 mm)
¹⁄₂” (89 mm)
¹⁄₂” (419 mm)
¹⁄₂” (368 mm)
¹⁄₂” (216 mm)
CFM170
5
Page 6
LDVT Series Direct Vent Gas Fireplace
A
B
Hearth
A hearth is not mandatory but is recommended for
aesthetic purposes. We recommend a noncombustible
hearth which projects out 12” (305mm) or more from the
front of the fireplace.
Cold climate installation recommendation:
When installing this unit against a noninsulated exterior wall or chase, it is
mandatory that the outer walls be insulated
to conform to applicable insulation codes.
Framing and Finishing
Check fireplace to make sure it is levelled
and properly positioned.
To mount the appliance:
1. Choose the location.
2. This unit comes with four (4) flanges pre-mounted
on both sides of the fireplace to allow two different
drywall thicknesses to be used. Flange “A” is for
1/2” drywall while flange “B” is for 5/8” drywall.
3. Bend the desired flanges out 90° on both sides of
the fireplace. Slide the fireplace into the framed
opening until the flanges contact the front surfaces
of the framing. Level the unit and secure it firmly in
place.
Flange Location for Desired Drywall Depth
Flange Drywall
Position Depth
A 1/2” / 13 mm
B 5/8” / 16 mm
Gas Specifications
Max. Min. Air
Gas Input Input Shutter
Model Fuel Control BTU/h BTU/h Adj.
33LDVTRN Nat Millivolt 16,000 11,200 3/16”
Open
33LDVTRP Prop Millivolt 16,000 12,000 Fully Open
33LDVTEN Nat 24V 16,000 11,200 3/16”
Hi/Lo Open
33LDVTEP Prop* 24V 16,000 12,000 Fully Open
Hi/Lo
36LDVTRN Nat Millivolt 19,500 13,650 Top &
Bottom
Hole Half
Closed
36LDVTRP Prop Millivolt 19,500 14,625 Fully Open
36LDVTEN Nat 24V 19,500 13,650 Top &
Hi/Lo Bottom
Hole Half
Closed
36LDVTEP Prop* 24V 19,500 14,625 Fully Open
Hi/Lo
39LDVTRN Nat Millivolt 23,000 16,100 Top &
Bottom
Hole Half
Closed
39LDVTRP Prop* Millivolt 22,500 16,875 Fully Open
39LDVTEN Nat 24V 23,000 16,100 Top &
Hi/Lo Bottom
Hole Half
Closed
39LDVTEP Prop* 24V 22,500 16,875 Fully Open
43LDVTRN Nat Millivolt 26,000 18,200 Top &
Bottom
Hole Half
Closed
43LDVTRP Prop* Millivolt 24,000 18,000 Fully Open
43LDVTEN Nat 24V 26,000 18,200 Top &
Hi/Lo Bottom
Hole Half
Closed
43LDVTEP Prop* 24V 24,000 18,000 Fully Open
Hi/Lo
*Using conversion kit
FP1546
Gas Inlet and Manifold Pressures
Fig . 4 Nailing flanges.
Final Finishing
Noncombustible materials such as brick or tile may be
extended over the edges of the face of the appliance.
DO NOT cover any vent or grille panels.
If a Trim Kit is going to be installed on the fireplace, the
brick or tile will have to be installed flush with the edges
of the appliance.
6
Natural LP (Propane)
Inlet Minimum 5.5” w.c. 11.0” w.c.
Inlet Maximum 14.0” w.c. 14.0” w.c.
Manifold Pressure 3.5” w.c. 10.0” w.c.
10007852
Page 7
LDVT Series Direct Vent GaS Fireplace
TP
TH
TP
TH
High Elevations
Input ratings are shown in BTU per hour and are
certified without deration for elevations up to
4,500 feet (1,370m) above sea level.
For elevations above 4,500 feet (1,370m) in USA,
installations must be in accordance with the current ANSI Z223.1/NFPA 54 and/or local codes having jurisdiction.
In Canada, please consult provincial and/or local
authorities having jurisdiction for installations at
elevations above 4,500 feet (1,370m).
Gas Line Installation
When purging gas line, the front window
frame removed.
The gas pipeline can be brought in through the rear
of the fireplace as well as the bottom. Knockouts are
provided on the bottom behind the valve to allow for the
gas pipe installation and testing of any gas connection.
It is most convenient to bring the gas line in from the
rear right side of the valve as this allows fan installation
or removal without disconnecting the gas line.
The gas line connection can be made with properly
tinned 3/8” copper tubing, 3/8” rigid pipe or an approved
flex connector. Since some municipalities have additional local codes, it is always best to con- sult your
local authority and the National Fuel Gas Code, ANSI
Z223.1/NFPA 54 in the USA or the CSA-B149.1 installation codes.
1/2” Gas Supply
1/2” NPT X 1/2” Flare Shut-off Valve
3/8” Flex line
(from valve)
The fireplace valve must not be subjected to any test
pressures exceeding 1/2 psi. Isolate or disconnect this
or any other gas appliance control from the gas line
when pressure testing.
Remote ON/OFF Switch
Installation:
1. Thread the wiring through holes on the end panels
of appliance. Take care not to cut wire or insulation
on metal edges. Route the wire to a conveniently
located receptacle box.
2. Attach the wire to the ON/OFF switch and install the
switch into the receptacle box.
3. Connect the other ends of the wire to the gas control
valve. (Fig. 6)
Remote ON/OFF
Switch or Thermostat or
Remote Control
Gas
Control
Valve
FP1224
Fig. 6 Remote switch wiring diagram.
Alternate Switch Location
The remote switch can be installed on the front/side of
the access door. Simply mount the switch to the bracket
provided and screw the bracket to either side of the
frame, lining up the screws with the pre-punched holes.
(Fig. 7)
FP297A
Fig. 5 Typical gas supply installation.
Always check for gas leaks with a mild
soap and water solution. Do not use an
open flame for leak testing.
The gas control is equipped with a captured screw type
pressure test point, therefore it is not necessary to provide a 1/8” test point up stream of the control.
When using copper or flex connector use only approved
fittings. Always provide a union when using black iron
pipe so that the gas line can be easily disconnected for
burner or fan servicing . See gas specifications for pressure details and ratings.
10007852
FP1024
Fig. 7 Alternate switch location.
Do not wire the remote ON/OFF wall switch
for the gas fireplace to the 120 volt power
supply.
7
Page 8
LDVT Series Direct Vent Gas Fireplace
OUTSIDE
INSIDE
BACK OF UNIT
EB-1 Electrical Box
The fireplace, when installed, must be electrically connected and grounded in accordance with local codes or, in the absence
of local codes, with the current CSA C22.1
Canadian Electrical Code.
For USA installations follow local codes
and the national electrical code ANSI/
NFPA No. 70.
It is strongly suggested that the wiring of
the EB-1 Electrical Junction Box be carried
out by a licensed electrician.
Ensure that the power to the supply line
has been disconnected before commencing this procedure.
The EB-1 Electrical junction box has been fitted stand
ard on this model to allow for the easy connection of an
optional fan kit.
To connect the EB-1 box to the house electrical supply
follow the steps below.
1. Unscrew retaining screw from EB-1 base plate (Fig.
8) and remove the EB-1 assembly from the appliance.
2. Remove the front cover of the EB box.
3. Remove the plug socket assembly from the EB-1
box.
4. Feed the supply line in through the EB-1 opening in
the side of the appliance and then through the back
of the EB-1 assembly. (Fig. 8)
5. Connect the black wire of the power supply line to
the brass screw (polarized) of the socket assembly.
6. Connect the white wire of the power line to the
chrome screw of the socket assembly.
7. Connect the ground wire of the supply line to the
green screw of the socket assembly.
8. Refit the socket assembly back into the electrical
box and replace the cover plate. Secure the cable
with the clamp on the outside of the EB-1 base
plate and refit the EB-1 assembly to the unit with the
screw removed in step 1.
-
Electrical Box
Retaining Screw
FP580
Fig. 8 EB-1 receptacle.
Electronic Gas Control Valve
This appliance may be fitted with a Synetek ignition
module.
Installation of the remote on/off switch or wall thermostat on electronic ignition units.
1. Thread the wiring through the holes on the side
panels of the appliance. Take care not to cut the wire
or insulation on metal edges. Route the wire to a
conveniently located receptacle box.
2. Attach the wire to the ON/OFF switch and install the
switch into the receptacle box.
3. Connect the white wire from the wall switch or wall
thermostat to the white wire terminal from the electronic module. Connect the black wire from the wall
switch or the red wire from the wall thermostat, to
the red wire terminal from the electronic module.
8
10007852
Page 9
LDVT Series Direct Vent GaS Fireplace
POWER CORD
CIRCUIT BOARD
ON/OFF SWITCH
OR
WALL THERMOSTAT
VALVE
RED
WHITE
BLUE
YELLOW
PURPLE
BLACK
WHITE
GREEN
PILOT SENSING
PILOT IGNITER
ORANGE
L1
L2
M
O
P
O
Fig. 9 SIT822 Valve with Synetek electronic control wiring diagram.
General Venting
Your fireplace is approved to be vented either through
the side wall, or vertically through the roof.
• Only CFM Corporation venting components spe-
cifically approved and labelled for this fireplace
may be used.
• Vent terminations shall not be recessed into a wall
or siding.
• Horizontal venting which incorporates the twist lock
pipe must be installed on a level plane without an
inclining or declining slope.
• Horizontal venting which incorporates the use of flex
venting shall have an inclining slope from the unit of
1” (25 mm) per 24” (610 mm).
FP1571
There must not be any obstruction such as bushes,
garden sheds, fences, decks or utility buildings within
24” (610 mm) from the front of the termination hood.
Do not locate termination hood where excessive snow
or ice build up may occur. Be sure to check vent termination area after snow falls, and clear to prevent accidental blockage of venting system. When using snow
blowers, make sure snow is not directed towards vent
termination area.
Location of Vent Termination
It is imperative the vent termination be located observing the minimum clearances as shown on the next
page.
*Check with local codes or in absence of same with
CSA-B149.1 Installation Codes (1991) for Canada
or follow the current National Fuel Gas Code, ANSI
Z223.1/NFPA 54 for installations in the USA.
10007852
9
Page 10
LDVT Series Direct Vent Gas Fireplace
V
V
V
V
V
V
V
X
X
X
D
E
B
B
B
C
B
M
B
A
J
K
F
L
VENT TERMINATION AIR SUPPLY INLET
AREA WHERE TERMINAL IS NOT PERMITTED
H
I
Operable
Operable
Fixed
Closed
V
B
INSIDE
CORNER DETAIL
V
A
G
N
N
CFM145a
General Venting Information - Termination Location
Canadian Installations1 US Installations
2
A = Clearance above grade, veranda, porch, 12” (30cm) 12” (30cm)
deck, or balcony
B = Clearance to window or door that may be 6” (15cm) for appliances 6” (15cm) for appliances
opened < 10,000Btuh (3kW), 12” (30cm) < 10,000 Btuh (3kW), 9”
for appliances > 10,000 Btuh (3kW) and (23cm) for appliances > 10,000
< 100,000 Btuh (30kW), 36” (91cm) Btuh (3kW) and < 50,000 Btuh
for appliances > 100,000 Btuh (30kW) (15kW), 12” (30cm) for
appliances > 50,000 Btuh (15kW)
C = Clearance to permanently closed window 12” (305mm) recommended to 12” (305mm) recommended to
prevent window condensation prevent window condensation
D = Vertical clearance to ventilated soffit located
above the terminal within a horizontal 18” (458mm) 18” (458mm)
distance of 2’ (610mm) from the center
line of the terminal
E = Clearance to unventilated soffit 12” (305mm) 12” (305mm)
F = Clearance to outside corner see next page see next page
G = Clearance to inside corner (see next page) see next page see next page
H = Clearance to each inside of center line 3’ (91cm) within a height of 15’ (5m) 3’ (91cm) within a height of 15’
extended above meter/regulator assembly above the meter/regulator assembly (5m) above the meter/regulator
assy
I = Clearance to service regulator vent outlet 3’ (91cm) 3’ (91cm)
J = Clearance to nonmechanical air supply inlet 6” (15cm) for appliances < 10,000 6” (15cm) for appliances
to building or the combustion air inlet to any Btuh (3kW), 12” (30cm) for < 10,000 Btuh (3kW), 9”
other appliances appliances > 10,000 Btuh (3kW) and (23cm) for appliances > 10,000
< 100,000 Btuh (30kW), 36” (91cm) Btuh (3kW) and < 50,000 Btuh
for appliances > 100,000 Btuh (30kW) (15kW), 12” (30cm) for
appliances > 50,000 Btuh (15kW)
K = Clearance to a mechanical air supply inlet 6’ (1.83m) 3’ (91cm) above if within 10
feet (3m) horizontally
L = Clearance above paved sidewalk or paved 7’ (2.13m)† 7’ (2.13m)†
driveway located on public property
M = Clearance under veranda, porch, deck or 12” (30cm)‡ 12” (30cm)‡
balcony
N = Clearance above a roof shall extend a minimum of 24” (610mm) above the highest point when it passes through the roof
surface, and any other obstruction within a horizontal distance of 18” (450mm).
1 In accordance with the current CSA-B149 Installation Codes
2 In accordance with the current ANSI Z223.1/NFPA 54 National Fuel Gas Codes
† A vent shall not terminate directly above a sidewalk or paved driveway which is located between two single family dwellings and serves both dwellings
‡ only permitted if veranda, porch, deck or balcony is fully open on a minimum 2 sides beneath the floor:
NOTE: 1. Local codes or regulations may require different clearances.
2. The special venting system used on Direct Vent Fireplaces are certified as part of the appliance, with clearances tested and
approved by the listing agency.
3. CFM Corporation assumes no responsibility for the improper performance of the appliance when the venting system does not
meet these requirements.
Fig. 10 Vent termination locations.
10
10007852
Page 11
Outside Corner
Inside Corner
Termination Clearances
Termination clearances for buildings with combustible and noncombustible exteriors.
G =
Combustible
6" (152 mm)
Noncombustible
2" (51 mm)
F =
Combustible
6" (152 mm)
Noncombustible
2" (51 mm)
G
Balcony with no side wall
M =
Combustible &
Noncombustible
12" (305 mm)
M
Balcony with perpendicular side wall
M = 24" (610 mm)
P = 20” (508 mm)
M
F
Alcove Applications*
C
D
C
E
V
V
Combustible &
Noncombustible
V
V
V
E = Min. 6” (152 mm) for
non-vinyl sidewalls
Min. 12” (305 mm) for
vinyl sidewalls
O = 8’ (2.4 m) Min.
O
P
*NOTE: Termination in an alcove space (spaces open only on one side and with an overhang) is permitted with the dimensions
specified for vinyl or non-vinyl siding and soffits. 1. There must be a 3’ (914 mm) minimum between termination caps. 2. All
mechanical air intakes within 10’ (1 m) of a termination cap must be a minimum of 3’ (914 mm) below the termination cap. 3. All
gravity air intakes within 3’ (914 mm) of a termination cap must be a minimum of 1’ (305 mm) below the termination cap.
Fig. 10a Termination clearances.
Canadian Installations:
General Information on Assembling Vent Pipes
The venting system must be installed in accordance
with the current CSA-B149 .1 installation code.
USA Installations:
The venting system must conform with local codes and/
or the current National Fuel Gas code ANSI Z223.1/
NFPA 54.
Only venting components manufactured by CFM Corporation can be used in Direct Vent systems.
Flex Vent Pipes
Before joining the flex vent pipe to the unit, apply a
bead of high temperature sealant* (provided) to the 4”
pipe exiting the fireplace. Secure flex vent pipe in place
with a hose clamp (provided).
*Be sure the flex pipe overlaps at least 1” (25 mm) onto
the collars of the fireplace and termination. If the ter
mination has an internal bead, be sure to overlap and
secure 1” (25 mm) past the bead.
-
10007852
LDVT Series Direct Vent GaS Fireplace
No.
of Caps D
1 3’ (914 mm) 2 x D
2 6’ (1.8 m) 1 x D
3 9’ (2.7 m) 2/3 x D
4 12’ (3.7 m) 1/2 x D
D
= # of Termination caps x 3
Min.
C
= (2 / # termination caps) x D
Max.
* Be sure the vent is actually crushed before proceeding. Apply a tug to be sure the vent will not slip off the
collars.
Repeat process with 7” flex vent pipe. The same procedure must be performed on the vent side.
Hose Clamp
Fig. 11 Apply high temperature sealant to 4” and 7” pipes.
C
Min.
Apply High Temperature
Sealant
Max.
Actual
Actual
Actual
Actual
Actual
584-15
FP1471
11
Page 12
LDVT Series Direct Vent Gas Fireplace
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
eg: A
eg: B
Twist Lock Pipes
When using CFM Corporation twist-lock pipe it is not
necessary to use sealant on the joints. The only areas
of the venting system that need to be sealed with high
temperature silicone sealant are the sliding joints of any
telescopic vent section used in the system.
To join the twist lock pipes together, simply align the
beads of the male end with the grooves of the female
end, then while bringing the ends together, twist the
pipe until the flange on the female end contacts the
external flange on the male end. It is recommended that
you secure the joints with three (3) sheet metal screws,
however this is not mandatory with twist lock pipe.
To make it easier to assemble the joints we suggest
putting a lubricant (Vaseline or similar) on the male end
of the twist lock pipe prior to assembly.
Vertical dimension from the floor of the fireplace to
the center of the horizontal vent pipe
Male End
Screw Holes
Fig. 12 Twist-lock pipe joints.
How to Use the Vent Graph
The vent chart should be read in conjunction with the
following vent installation instructions to determine the
relationship of the vertical and horizontal dimensions of
the vent system.
1. Determine the height of the center of the horizontal
vent pipe exiting through the outer wall. Using this
dimension on the Sidewall Vent Graph. (Fig. 13)
locate the point intersecting with the slanted graph
line.
2. From the point of this intersection, draw a vertical
line to the bottom of the graph.
3. Select the indicated dimension, and position the
fireplace in accordance with same.
Example A:
If the vertical dimension from the floor of the fireplace
is 11’ (3.4 m) the horizontal run to the face of the outer
wall must not exceed 14’ (4.3 m).
Example B:
If the vertical dimension from the floor of the unit is 7’
(2.14 m), the horizontal run to the face of the outer wall
must not exceed 8¹⁄₂’ (2.6 m).
12
Female End
TWL100
Horizontal dimension from the outside face of the wall to
the center of the fireplace vent flange
Sidewall vent graph showing the relationship between vertical
and horizontal dimensions for a Direct Vent flue system.
Fig. 13 Sidewall venting graph. (Dimensions in feet)
Vertical Sidewall Applications
Since it is very important that the venting system maintain its balance between
the combustion air intake and the flue
gas exhaust, certain limitations as to vent
configurations apply and must be strictly
adhered to.
The vent graph showing the relationship between vertical and horizontal side wall venting will help to determine the various dimensions allowable.
Minimum clearance between vent pipes
and combustible materials is one 1”
(25mm) on top, bottom and sides unless
otherwise noted.
When the vent termination exits through foundations
less than 20” (508mm) below siding outcrop, the vent
pipe must flush up with the siding.
It is always best to locate the fireplace in such a way
that minimizes the number of offsets and horizontal
vent length of vent pipe from the flue collar of the fireplace to the face of the outer wall.
10007852
Page 13
20' (6m)
7.5' (2.3m)
Pipe
3'
(914mm)
7.5'
(2.3m)
A
B
A + B = 17' (5.2m) Max.
1
2
3
4
Straps Every
3’ (914mm)
Pipe Straps
Every 3’ (914mm)
Firestop/Zero
Clearance Sleeve
FP1012
Fig. 14 Support straps for horizontal runs.
Horizontal plane means no vertical rise exists on this
portion of the vent assembly.
• The maximum number of 90° elbows per side wall
installations is three (3).
• If a 90° elbow is fitted directly onto the fireplace
flange the maximum horizontal vent run before the
termination or a vertical rise is 36” (914mm).
• If a 90° elbow is used in the horizontal vent run
(level height maintained) the maximum horizontal
vent length is reduced by 36” (914mm). This does
not apply if the 90° elbows are used to increase or
redirect a vertical rise.
Example: According to the chart the maximum
horizontal vent length in a system with a 7.5’ (2.3 m)
vertical rise is 20’ (6m) and if a 90° is required in the
horizontal vent it must be reduced to 17’ (5.2 m).
In Figure 16, Dimension A plus B must not be
greater than 17’ (5.2 m).
LDVT Series Direct Vent GaS Fireplace
1 x 90° elbow in horizontal plane = 3’ (914mm)
FP1238
Fig. 16 Maximum vent run with elbows.
• The maximum number of 45° elbows permitted per
side wall installation is two (2). These elbows can be
installed in either the vertical or horizontal run.
• For each 45° elbow installed in the horizontal run,
the length of the horizontal run MUST be reduced by
18” (457 mm). This does not apply if the 45° elbows
are installed on the vertical part of the vent system.
Locate vent opening on the wall. It may be necessary
to first position the fireplace and measure to obtain hole
location. Depending on whether the wall is combustible
or noncombustible, cut opening to size. (Fig. 18)
For combustible walls first frame in opening.
NOTE: When using flex vent, the opening will have to
be measured according to the 1/2” (13 mm) rise in 12”
(305 mm) vent run.
Combustible Walls:
x 240 mm) hole through the exterior wall and frame as
shown.
Noncombustible Walls:
be 7¹⁄₂” (190 mm) in diameter.
Vent Opening for Combustible Wall
9³⁄₈”
(240mm)
(Fig. 18) Cut a 9³⁄₈”H x 9³⁄₈”W (240
(Fig. 18) Hole opening must
9³⁄₈”
(240mm)
Framing
Detail
Adjustable
Zero Clearance
Sleeve
#8 Screws
(2)
Firestop
Adjustable Zero Clearance Sleeve
Fig. 19 Adjustable zero clearance sleeve.
Max. Length
12” (305mm)
#8 Screws (2)
#8 Screws
(2)
ZCS101
Fireplace Hearth
Opening for Noncombustible Wall
7¹⁄₂”
(190mm)
VO584-100
Fig. 18 Locate vent opening on wall.
STEP 2
Measure wall thickness and cut zero clearance sleeve
parts to proper length (MAXIMUM 12”/305 mm). As
semble sleeve and attach to firestop with #8 sheet
metal screws (supplied). Install firestop assembly. (Fig.
19)
Zero clearance sleeve is only required for
combustible walls.
STEP 3
Place fireplace into position. (Fig. 20) Measure the ver
tical height (X) required from the base of the flue collars
to the center of the wall opening.
FP1240
Fig. 20 Vertical height requirement.
STEP 4
Attach the appropriate venting component(s) to the
inner and outer flue collars of the fireplace using three
(3) screws. (Fig. 21) Follow with the installation of the
inner and outer elbow. Again secure joints with three (3)
sheet metal screws.
Fig. 21 Horizontal length requirement.
14
FP1241
10007852
Page 15
STEP 5
12"
(305mm)
6"
(152mm)
5"
(127mm)
6"
(172mm)
Measure the horizontal length requirement including
a 2” (51 mm) overlap, ie from the elbow to the outside
wall face plus 2” (51 mm) (or the distance required if
installing a second 90° elbow). (Fig. 21)
Always install horizontal venting on a level
plane.
STEP 6
Use appropriate length of pipe sections - telescopic or
fixed - and install the horizontal vent sections. The sections which go through the wall are packaged with the
starter kit, and can be cut to suit if necessary. (Fig. 22)
Sealing vent pipe and firestop gaps with
high temperature sealant will restrict cold
air being drawn in around fireplace.
LDVT Series Direct Vent GaS Fireplace
FP1243
Fig. 23 Apply high temperature sealant to collars or terminations.
Support horizontal pipes every 3’ (914 mm) with metal
pipe straps. Make sure the horizontal vent pipe is installed on a level horizontal plane.
FP1242
Fig. 22 Through the wall.
STEP 7
Guide the vent terminations 4” and 7” collars into their
respective vent pipes. Double check that the vent pipes
overlap the collars by 2” (51 mm). Secure the termination to the wall with screws provided and caulk around
the wall plate to weatherproof. (Fig. 23) As an alternative to screwing the termination directly to the wall you
may also use expanding plugs or an approved exterior
construction adhesive. You may also attach the termination with screws through the inner body into the 4”
(102 mm) vent pipe however for this method you must
extend the 4” (102 mm) pipe approximately 6” (152
mm) beyond the outer face of the wall.
Vertical Sidewall Installation
Flex Vent Pipe
NOTE: The 40” (1016 mm) flex vent is used for 90° off
the top of the unit then out the back wall.
Follow Step 1 and 2 on Page 14.
Step 3
Install the four (4) spacer springs on the 4” flex vent
pipe. When installing the spacer springs around the 4”
pipe, stretch the spring to approximately 15” (381 mm),
wrap the spring around the pipe and interlock the ends
of the spacer spring approximately 2” (51 mm). Measure 6³⁄₄” (172 mm) from the end of the pipe. Place the
next spring 5” (127 mm) from the previously installed
spring. Place the next spring 6” (152 mm) from the last
spring. Finally place the last spring 12” (305 mm) from
the last spring installed. (Fig. 24)
4” Flex Vent
Pipe
Spacer Spring
10007852
FP1474
Fig. 24 Install spacer springs.
15
Page 16
LDVT Series Direct Vent Gas Fireplace
6" (165mm)
Step 4
Install the 4” (102 mm) flex vent pipe to the appliance
collar as described on Page 11. Secure the end with the
first spring 6³⁄₄” (172 mm) from the flex pipe end to the
unit.
Step 5
Slide the 7” (178 mm) flex vent pipe over the 4” flex
vent pipe and secure the 7” collar as described on Page
11.
Step 6
Bend the flex pipe horizontal so the bottom of the
horizontal pipe measure 6¹⁄₂” (165mm) from the top of
the unit immediately after the 90° formation. (Fig. 25)
Be sure to follow the 1” (25mm) rise in a 24” (610mm)
horizontal run rule.
Step 7
Install the 4” flex then 7” flex to the termination.
1. Establish vent hole through the wall. (Fig. 18)
2. Remove soil to a depth of approximately 16” (406
mm) below base of snorkel. Install drain pipe. Install
window well (not supplied). Refill hole with 12” (305
mm) of coarse gravel leaving a clearance of approximately 4” (102 mm) below snorkel. (Fig. 26)
3. Install vent system.
4. Ensure a watertight seal is made around the vent
pipe coming through the wall.
5. Apply high temperature sealant caulking (supplied)
around the 4” and 7 “ snorkel collars.
6. Slide the snorkel into the vent pipes and secure to
the wall.
7. Level the soil to maintain a 4” (102 mm) clearance
below snorkel. (Fig. 26)
Do not back fill around snorkel. A clearance
of at least 4” (102 mm) must be maintained
between snorkel and the soil.
Zero Clearance
Sleeve
(if required)
Firestop
7” Pipe
Screws
7TDVSNORK
(Snorkel)
4” (102mm)
Clearance
Min.
FP1475
Fig. 25 Bend flex vent at 90° so horizontal portion is 6¹⁄₂”
(165 mm) off top of unit.
Below Grade Installations
When it is not possible to meet the required vent terminal clearances of 12” (305mm) above grade level a
snorkel vent kit is recommended. It allows installation
depth of down to 7” (178mm) below grade level. The 7”
is measured from the center of the horizontal vent pipe
as it penetrates through the wall.
If venting system is installed below
ground, we recommend a window well with
adequate and proper drainage.
Ensure sidewall venting clearances are observed.
If installing a snorkel a minimum 24” (610 mm) vertical
rise is necessary. The maximum horizontal run with
the 24” (610 mm) vertical pipe is 36” (914 mm). This
measurement is taken from the collar of the fireplace
(or transition elbow) to the face of the exterior wall.
Refer to the Sidewall Vent Graph for extended
horizontal run if the vertical rise exceeds 24” (610 mm).
Window
24” (610mm)
Minimum*
Drain
Foundation Wall
*A minimum of 24” (610mm) ver
tical pipe must be installed when
using the 7TDVSNORK Kit.
*The 22” (559mm) vertical rise
(center to center) of the snorkel
may be included for calculationof
max. horizontal run.
BG402
Fig. 26 Below grade installation.
Well
Gravel
-
If the foundation is recessed, use recess brackets (not
supplied) for securing lower portion of the snorkel.
Fasten brackets to wall first, then secure to snorkel
with self drilling #8 x 1/2 sheet metal screws. It will be
necessary to extend vent pipes out as far as protruding
wall face. (Fig. 27)
• Vertical installations up to 40’ (12 m) in height. Up
to a 10’ (3 m) horizontal vent run can be installed
within the vent system using a maximum of two 90°
elbows. (Fig. 28)
LDVT Series Direct Vent GaS Fireplace
Example: Maximum horizontal length
0 x 45° elbows = 10’ (3 m)
1 x 45° elbows = 8
¹⁄₂’ (2.6 m)
2 x 45° elbows = 7’ (2.1 m)
• A minimum of an 8’ (2.4 m) vertical rise.
• Two sets of 45° elbows offsets within these vertical
installations. From 0 to a maximum of 8’ (2.4 m) of
vent pipe can be used between elbows. (Fig. 29)
• 7DVCS must be used to support offsets. (Fig. 31)
This application will require that you first determine
the roof pitch and use the appropriate starter kit.
(Refer to Venting Components List)
• The minimum height of the vent above the highest
point of penetration through the roof is 2’ (610 mm).
(Fig. 33)
Pipe Straps Every
3’ (914mm)
Fig. 28 Support straps for horizontal runs.
• Up to two 45° elbows may be used within the
horizontal run. For each 45° elbow used on the
horizontal level the maximum horizontal length must
be reduced by 18” (457 mm).
1 + 2 + 3 + 4 = 270°
FP1244
FP1245
Fig. 29 Typical offset application.
10007852
17
Page 18
LDVT Series Direct Vent Gas Fireplace
11"
(279mm)
11"
(279mm)
Min.
2' (610 mm)
Vertical Through-the-Roof Installation
1. Locate your fireplace.
2. Plumb to center of the (4” (102 mm) flue collar from
ceiling above and mark position.
3. Cut opening equal to 9
4.
Proceed to plumb for additional openings through
the roof. In all cases, the opening must provide a
minimum of 1” (25mm) clearance to the vent pipe, i.e.,
the hole must be at least 9³⁄₈” x 9³⁄₈” (240 x 240 mm).
5. Place fireplace into position.
6. Place firestop(s) #7DVFS or Attic Insulation Shield
#7DVAIS into position and secure. (Fig. 30)
Attic Insulation
Shield
³⁄₈” x 9³⁄₈” (240 x 240 mm).
Typical Roof Support
Application
Fig. 31 Roof and ceiling supports.
Typical Ceiling Sup
-
port Application
CFM110
Joist
Ceiling Installation
Fig. 30 Place firestop spacer(s) and secure.
Upper Floor
Joist
Firestop Spacer
Nails (4)
CFM100a
7. Install roof support (Fig. 31) and roof flashing making
sure upper flange of flashing is below the shingles.
(Fig. 32)
8. Install appropriate pipe sections until the venting is
above the flashing. (Fig. 32)
9. Install storm collar and seal around the pipe.
10. Add additional vent lengths for proper height. (Fig.
33)
#8 Sheet Metal Screws
(3 per joint)
Sealant
Storm Collar
TWL101a
Fig. 32 Roof flashing.
CFM190
Fig. 33 Minimum termination to roof clearance.
18
If there is a room above ceiling level,
firestop spacer must be installed on both
the bottom and the top side of the ceiling
joists. If an attic is above ceiling level a
7DVAIS (Attic Insulation Shield) must be
installed.
The enlarged ends of the vent section
always face downward. (Fig. 32)
10007852
Page 19
Vertical Restrictor Plate
36LDVT, 39LDVT, 43LDVT
When installing the 36LDVT, 39LDVT or 43LDVT with a
vertical through-the-roof configuration flue system, the
restrictor plate (#10008048) supplied with the appliance
MUST BE FITTED TO THE APPLIANCE at the installation.
NOTE: Do not use the restrictor plate supplied with
the vertical termination cap.
1. Remove the rear log support. Save the two (2)
screws.
2. Remove the two (2) nuts and save them.
3. Place the restrictor plate (Fig. 34) and secure it with
the two (2) nuts.
4. Replace the rear log support to the same location
as before and secure it with the screws removed in
Step 1.
LDVT Series Direct Vent GaS Fireplace
Rear Log Support
Restrictor Plate
Fig. 34 Assembling the restrictor plate.
FP1555
10007852
19
Page 20
LDVT Series Direct Vent Gas Fireplace
Venting Components
7TDVRVT - Through the wall Rear Vent Termination
Starter Kit Model 7TDVSK - Sidewall Venting (Twist Lock Pipe)
Model 7FDVSK - Sidewall Venting (Flex Vent Pipe)
Models 7TDVTK/TV - Hot Touch Termination Kits
Model 7TDVTVTK/TV - Cool Touch Termination Kit
Starter Kit - Model 7TDVSKV - Vertical Venting
for 7TDVSKV-A order 1/12 to 6/12 roof pitch
for 7TDVSKV-B order 7/12 to 12/12 roof pitch
for 7TDVSKV-F order flat roof
Starter Kit for Below Grade Installation
Model 7TDVSKS -Snorkel Kit (Twist Lock Pipe)
Model 7FDVSKS -Snorkel Kit (Flex Vent Pipe)
Starter Pipe
Model 7TDVP 20/8 - 24” Starter Pipe Bulk
Model 7FDVP 30/8 - 30” Flex Pipe Bulk
45o Elbow
7TDV45 for Rear Vent to Vertical Vent
or Vertical/Horizontal Offsets
90o Transition Elbow
7TDVRT90 for Rear Vent to Vertical Vent
90° Elbow
7TDV90 Vertical/Horizontal Offset
Telescopic vent sections
7TDVP1117 -11” to 17” adjustable length
7TDVP3567 -35” to 67” adjustable length
Pipe sections for vertical or horizontal venting
Model 7TDVP8” - 4 per box
Model 7TDVP12” - 4 per box
Model 7TDVP24” - 4 per box
Model 7TDVP36”
Model 7TDVP48”
Firestop Spacer
Model 7DVFS
20
Attic Insulation Shield
Model 7DVAIS
Vertical/Horizontal Combination Offset Support
Model 7DVCS
10007852
Page 21
LDVT Series Direct Vent GaS Fireplace
1.
2.
�
Operating Instructions
Glass Information
Only glass approved by CFM Corporation
should be used on this fireplace.
• The use of any non-approved replacement glass will
void all product warranties.
• Care must be taken to avoid breakage of the glass.
• Do not operate appliance with glass front
removed, cracked or broken.
• Replacement glass (complete with frame
window) is available through your CFM
Corporation dealer and should only be installed
by a licensed qualified service person.
Louvre Removal
6. Tilt the glass frame out slightly at the bottom, lift the
frame up and away from the fireplace.
7. To replace the glass frame reverse the procedure.
Lower Clamps
Window
Frame Assembly
Window
Frame
Assembly
Fig. 36 Window frame assembly removal.
Push
Clamp
Handle
Pull
Clamp
Hook
FP1228
The top louvre
panel is removed
by lifting the
panel vertically
and pulling it
away from the
appliance. (Fig.
35)
The lower access
door is hinged
along the bottom
edge and is
folded down to
allow access
FP1227
Fig. 35 Remove top louvre assembly.
Window Frame Assembly Removal
1. Turn the fireplace OFF (including the pilot)
2. If the unit has been operating allow time for the
components to cool.
3. Remove the top louvre assembly.
4. Open the lower louvre panel.
5. Release the two clamps securing the lower edge of
10007852
the frame by pulling down on the handles. (Fig. 36)
Louvre
Glass Panel
Glass Cleaning
It is necessary to periodically clean the glass. During
start-up condensation, which is normal, forms on the
inside of the glass. This condensation causes lint, dust
and other airborne particles to cling to the glass surface.
Also initial paint curing may deposit a slight film on the
glass. It is therefore recommended that the glass be
cleaned two or three times with a non-ammonia based
household cleaner and warm water (We recommend
gas fireplace glass cleaner) within the first few weeks of
operation.
After the initial cleaning process the glass should be
cleaned two or three times during each operating
season depending on the environment in the house.
Clean the glass after the first two weeks of
operation.
Do not clean glass when hot.
Do not use abrasive cleaners.
Do not strike or slam glass.
21
Page 22
LDVT Series Direct Vent Gas Fireplace
Installation of Logs, Lava Rock & Ember Material
The logs are fragile and should be handled
with care. Keep the packaging material out
of the reach of children and dispose of the
material in a safe manner.
The individual logs can be easily identified
by the numbers cast on the underside of
each log.
Log Identification Chart
Location 33LDVT 36LDVT 39LDVT 43LDVT
Front Left A43 B160 BC15 BD16
Front Right -- B159 BC16 BD17
Front Center -- B161 B138 B138
Rear -- B158 BC14 BD15
Rear Left A41 -- -- - Rear Right A42 -- -- - Top Center A44 -- -- BD18
Log Installation
1. Remove the top louvre assembly.
2. Open the bottom louvre.
3. Remove the window frame assembly.
4. Remove log box from inside firebox.
5. Unpack the logs from packaging and remove each
log from its wrapping material. Set aside the ember
and the lava rock bags.
As with all plastic bags - these are not toys
and should be kept away from children and
infants.
33LDVT
1. Place rear log left (A41) on rear bracket (ensure the
notch on the left end locates against the bend up on
the left side of rear bracket.)
2. Place rear log right (A42) on rear bracket (ensure
the notch on the right end locates against the bend
up on the right side of rear bracket) and just rest the
cut out from front log onto the front support.
3. Place front log left (A43). Use the log’s bottom hole
to locate it onto rear log left (A41) and just rest bottom cut out log onto the front support.
4. Place top log center (A44). Use the log’s bottom
hole to locate it onto the knob on the rear log right
(A42) and the top log center rest onto rear log left.
5. Place ember material on top of burner. Scatter the
ember material over the tiles on the front area of the
burner housing. (Fig. 44) Do not pack the ember
material. Separate it when unpacked and keep it
in a fluffy and loose condition for a more realistic
ember effect.
6. Scatter the lava rock material around the firebox
base.
Do not place any of the lava rock material
on the burner housing assembly.
22
Top Center
Rear Left
(A41)
Front Left
(A43)
Fig. 37 Correct log placement for 33LDVT.
(A44)
Rear Right
(A42)
LG382
10007852
Page 23
36LDVT
LDVT Series Direct Vent GaS Fireplace
1. Place rear log (B158) on rear bracket (ensure log is seated properly to
the bracket and located to the two
pins), so it will not move from side to
side and is firmly positioned on the
bracket.
2. Place front left log (B160). Use the
log’s bottom hole to locate it onto
the front support and just rest on top
of the rear log.
3. Place front right log (B159). Use the
log’s bottom hole to locate it onto
the front support and the top hole to
the knob onto the rear log.
4. Place front center log (B161) on top
of the two small shelves at the front
log support and between the left
and right logs.
5. Place ember material on top of
burner. Scatter the ember material
over the tiles on the front area of
the burner housing. (Fig. 45) Do not
Fig. 38 Correct log placement for 36LDVT.
pack the ember material. Separate it when unpacked
and keep it in a fluffy and loose condition for a more
realistic ember effect.
6. Scatter the lava rock material around the firebox
base.
Front Left
(B160)
Rear
(B158)
Front Right
Front Center
(B161)
(B159)
LG481
Do not place any of the lava rock material
on the burner housing assembly.
39LDVT
1. Place rear lob (BC14) on rear bracket
(ensure log is centered and seated
properly to the log support).
2. Place front left log (BC15). Use log’s
bottom hole to locate it onto the front
support and just rest on top of the
rear log.
3. Place front right log (BC16). Use log’s
bottom hole to locate it onto the front
support and the top hole to the knob
on the rear log.
4. Place front center log (B138) on top
of the two small shelves at the front
log support, and between the left and
right logs.
5. Place ember material on top of
burner. Scatter the ember material
over the tiles on the front area of the
burner housing. (Fig. 46) Separate it
when unpacked and keep it in a fluffy
and loose condition for a more realistic ember effect.
Front Left
(BC15)
Fig. 39 Correct log placement for 39LDVT.
Do not place any of the lava rock material
on the burner housing assembly.
Front Right
(BC16)
Front Center
(B138)
Rear
(BC14)
LG414
10007852
23
Page 24
LDVT Series Direct Vent Gas Fireplace
Turn
counterclockwise
to decrease
flame height
Turn clockwise
to increase
flame height
L
O
H
I
Turn
counterclockwise
to increase
flame height
Turn clockwise
to decrease
flame height
43LDVT
1. Place rear log (BD15) on rear bracket
(ensure log is centered and seated
properly to the log support).
2. Place front left log (BD16). Use log’s
bottom notch to locate it onto the front
support and just rest on top of the
burner housing assembly.
3. Place front right log (BD17). Use log’s
Front
Left
(BD16)
bottom notch to locate it onto the front
support and just rest on top of the
burner housing assembly.
4. Place ember material on top of burner.
5. Scatter the ember material over the
tiles on the front area of the burner
housing. (Fig. 40) Do not pack the
ember material. Separate it when
unpacked and keep it in a fluffy and
loose condition for a more realistic
ember effect.
6. Place front center log (B138) on top of
the two small shelves at the front log
support, and between the left and right
logs.
Fig. 40 Correct log placement for 43LDVT.
7. Place top center log (BD18) on top of
the rear log using the hole locator under the log and
on top of front right log.
8. Scatter lava rock material round the firebox base.
Rear
(BD15)
Lava Rock
Top Center
(BBD18)
Front Right
(BD17)
Lava
Rock
Ember Material
Front Center
(B138)
LG434
Do not place any of the lava rock material
on the burner housing assembly.
Flame Characteristics
Flame & Temperature Adjustment
RN/RP & EN/EP Models
For units equipped with ‘HI/LO’ valves the flame
adjustment is accomplished by rotating the ‘HI/LO’
adjustments knob located near the center of the gas
control valve. (Fig. 41-42)
Fig. 41 Flame adjustment knob for Honeywell valve.
Fig. 42 Flame adjustment knob for SIT valve.
It is important to periodically perform a visual check of
the pilot and burner flames. Compare them to Figures
43 and 44.
If the flame patterns appear abnormal contact a
qualified service provider for service and adjustment.
SIT RN/RP
SIT EN/EP
FP1541
Fig. 43 Correct pilot flame appearance.
24
10007852
Page 25
LG384
LDVT Series Direct Vent GaS Fireplace
33LDVT
Glowing Embers
36LDVT
LG415
LG482
Glowing Embers
39LDVT
Glowing Embers
43LDVT
LG435
Fig. 44 Correct burner flame appearance for the LDVT fireplaces.
10007852
Glowing Embers
25
Page 26
LDVT Series Direct Vent Gas Fireplace
P
I
L
O
T
O
F
F
O
F
F
5
4
3
2
1
O
F
F
P
i
l
o
t
3/8" - 1/2"
Lighting and Operating Instructions
FOR YOUR SAFETY READ BEFORE LIGHTING
WARNING:If you do not follow these instructions exactly, a fire or explosion
may result causing property damage, personal injury or loss of life.
A. This heater has a pilot which must be lit manu
ally. When lighting the pilot follow these instructions exactly.
B. BEFORE LIGHTING smell all around the
heater area for gas. Be sure to smell next to
the floor because some gas is heavier than air
and will settle on the floor.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any fireplace
• Do not touch any electric switch
• Do not use any phone in your building
• Immediately call your gas supplier from a
neighbor’s phone.
Lighting Instructions
-
Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call
the Fire Department
C. Use only your hand to push in or turn the gas
control knob. Never use tools. If the knob will not
push in or turn by hand, do not try to repair it, call a
qualified service technician. Applying force or any
attempted repair may result in a fire or explosion.
D. Do not use this fireplace if any part has been under
water. Immediately call a qualified service technician to inspect the heater and to replace any part of
the control system and any gas control which has
been under water.
1. STOP! Read the safety information above.
2. Turn off all electrical power to the fireplace.
3. For MN/MP/TN/TP appliances ONLY, go on to
Step 4. For RN/RP appliances turn the ON/OFF
switch to “OFF” position or set thermostat to
lowest level.
4. Open control access panel.
5. Push in gas control knob slightly and turn clockwise to “OFF”.
Euro SITSIT NOVA
Honeywell
6. Wait five (5) minutes to clear out any gas. Then
smell for gas, including near the floor. If you
smell gas, STOP! Follow “B” in the safety information above. If you do not smell gas, go to the
next step.
7. Remove glass door before lighting pilot. (See
Glass Frame Removal section).
8. Visibly locate pilot by the main burner.
9. Turn knob on gas control counterclockwise
to “PILOT”.
10. Push the control knob all the way in and hold.
Immediately light the pilot by repeatedly depressing the piezo spark ignitor until a flame appears.
Continue to hold the control knob in for about one
(1) minute after the pilot is lit. Release knob and it
will pop back up. Pilot should remain lit. If it goes
out, repeat steps 5 through 8.
• If knob does not pop up when released, stop
and immediately call your service technician or
gas supplier.
• If after several tries, the pilot will not stay lit,
turn the gas control knob to “OFF” and call your
service technician or gas supplier.
11. Replace glass door.
12. Turn gas control knob to “ON” position.
13. For RN/RP appliances turn the ON/OFF switch to
“ON” position or set thermostat to desired setting.
14. Turn on all electrical power to the fireplace.
To Turn Off Gas To Heater
1. Turn the ON/OFF switch to Off position or set
the thermostat to lowest setting.
2. Turn off all electric power to the fireplace if
service is to be performed.
26
3. Open control access panel.
4. Push in gas control knob slightly and turn clockwise to “OFF”. Do not force.
5. Close control access panel.
10007852
Page 27
LDVT Series Direct Vent GaS Fireplace
HI
LO
Lighting and Operating Instructions
For Fireplaces equipped with SIT822 Gas Valve (EN or EP)
Warning:If you do not follow these instructions exactly, a fire or explosion
may result causing property damage, personal injury and loss of life.
FOR YOUR SAFETY READ THE FOLLOWING WARNINGS
BEFORE LIGHTING THE APPLIANCE
A. This fireplace is equipped with an ignition device
which automatically lights the pilot. DO NOT try to
light the pilot by hand.
B. BEFORE OPERATING, smell all around the
appliance area for gas. Be sure to smell next to
the floor because some gas is heavier than the air
and will settle on the floor.
What to do if you smell gas
• Do not try to light any appliance
• Do not operate any electrical switch.
• Do not use any phone in your building.
• Immediately call your gas supplier from a
neighbor’s phone.
Lighting Instructions
1. STOP! Read the safety information above before
continuing.
2. Turn off all electrical power to the appliance.
3. This appliance is equipped with an ignition device
which automatically lights the pilot. DO NOT try to
light the pilot by hand.
4. Access the gas control by lowering the lower
access door (louvre assembly).
Follow the gas suppliers instructions.
• If you cannot contact your gas supplier call
the Fire Department
C. Use only your hand to push in or turn the gas
control knob. Never use tools. If the knob will not
push in or turn by hand do not try to repair it, call
a qualified service technician. Force or attempting
repair may result in a fire or explosion.
D. Do not use this appliance if any part has been
under water. Immediately call a qualified service
technician to inspect the appliance and replace
any part of the control system and any gas control
that has been under water.
5. Turn the remote switch, if used, OFF. Turn the
wireless remote, if used, OFF.
6. Wait five (5) minutes to clear out any gas. Then
smell for gas, including near the floor. If you smell
gas STOP. Follow instructions B in the safety
warnings above. If you do not smell gas go onto the
next step.
7. Close the access door.
8. Turn ON all electrical power to the appliance.
9. Turn remote switch or wireless remote to “ON”.
10. If the appliance will not operate, follow the
instructions TURNING OFF THE GAS TO THE
APPLIANCE and call your service technician or
gas supplier.
Turning Off the Gas to the Appliance
1. Turn the remote switch to the “OFF” position.
2. Turn OFF all electrical power to the fireplace if
service is required.
3 Open the lower access panel.
4. Turn the shut-off valve on the flexible gas line to
the “OFF” position.
10007852
1/2” Gas Supply
1/2” NPT x 1/2” Flare Shut-Off
Valve
Valve in the on position
3/8” Flex Line
(From Valve)
FP297A
27
Page 28
LDVT Series Direct Vent Gas Fireplace
Troubleshooting Honeywell Millivolt Valve
Remove Window Frame Assembly Before Service Work
STARTCHECK
Gas Supply On
YES
Pilot Lights With Piezo
Ignitor
YES
Pilot Stays Lit
YES
NO
NO
NO
• Supply Line Hooked Up
• Shutoff Valve Open
• Lockout Has Engaged. Wait 60
Seconds And Try Again.
• For Spark At Electrode While
Depressing Piezo
1/8" Gap To Pilot Hood Needed.
• All Wiring Connections
• Replace Piezo Ignitor
• For Air In The Lines
• Thermopile Needs A Min.
325mv. Adjust Pilot Flame
Height.
• All Wiring Connections
• Replace Thermopile
• Thermocouple Needs A Min. Of
14mv
• Defective Valve. Turn To Pilot,
Meter Should Read Greater
Than 100mv. If Not, Replace.
28
Pilot Lights Main Burner
YES
SYSTEM OK
NO
• Valve Is Turned On
• Wall Switch Is Not Turned On.
Watch For Grounded Wires!
• Thermopile Needs A Min. 325mv.
• Plugged Burner Orifice
10007852
Page 29
LDVT Series Direct Vent GaS Fireplace
Troubleshooting the Gas Control System
SIT 822 Valve with Synetek Electronic Control
Operating Diagram
Normal Operation
ON/OFF Switch Closed?
YES
Safe Start Check On?
YES
0 Sec Purge
Ignition Trial: 30 sec Spark ON
Pilot Valve ON. Has Flame
been Detected within 30 sec?
Spark Off. Main Valve ON.
Pilot Flame Continuously
Monitored
NO
NO
Abnormal Operation
5 sec Inter-Trial Delay
LED: Steady Flash?
Lockout: Flame detected out of sequence
Reset by interrupting ON/OFF switch or
power for 10 sec
LED: 5 Flashes?
Reverse power cord polarity
LED: 2 Flashes?
Reset by interrupting ON/OFF
switch for power for 10 sec
YES
Pilot, Valve OFF, Spark OFF
Have three ignition trials been completed?
NO
Pilot Flame Sense OK?
ON/OFF Switch Opened?
YES
Pilot and Main Valve OFF?
YES
0 sec Post Purge?
Heating Cycle Complete LED:
OFF
NO
LED: 3 Flashes?
Lockout: Flame Loss
Reset by interrupting ON/OFF switch or
power for 10 sec
Main Valve OFF, Spark ON
YES
Has flame been detected within 30 sec?
NO
Have three pilot flame losses been
detected?
YES
10007852
29
Page 30
LDVT Series Direct Vent Gas Fireplace
A
B
C
O
F
F
P
I
L
O
T
O
D
E
F
O
F
F
P
I
L
O
T
O
CONVERTING THE APPLIANCE FROM LP TO
NATURAL GAS OR NATURAL GAS TO LP
The conversion of this appliance from one
gas to another must be carried out by an
authorized service provider.
The procedure for converting from one gas
to another is the same regardless of the
initial gas used. The only variation is in the
orifice-sizes and component part numbers.
Your authorized service provider will
ensure the correct parts are used.
1. Disconnect power to unit and shut off gas supply.
2. Remove window frame assembly.
3. Carefully remove the logs & lava rock material.
4. Remove the screws that are holding the burner
housing assembly in place.
5. Remove the burner housing assembly. Depending
on the model of the appliance you may have to loosen the pilot bracket retaining screw/nut to allow the
pilot and bracket assembly to tilt and give enough
clearance to remove the burner housing assembly.
6. For Model 36LDVT ONLY: Remove the rear log
support and relocate the two (2) screws that locate
the rear log as shown in Figure 45.
9. PSE PilotUsing a suitable wrench on the hexagonal body, un-
screw the pilot hood assembly from the pilot, do not
twist the hood itself. Remove the orifice and replace
it with the new orifice supplied in the kit. Refit the
pilot hood assembly. Do not over-tighten the pilot
hood. The hood must return to its original alignment.
Take care not to damage the thermocouple, thermopile or igniter.
10.SIT 820 NOVA Gas Control Valve (Fig. 46)a. Using a Torx T20 or slotted screwdriver, remove
and save the three pressure regulator mounting screws (A), pressure regulator tower (B) and
diaphram (C).
Natural Gas
Log Locator
Pin
Propane Gas
Log Locator
Pin
Fig. 45 Move log locator pins to new locations on rear log
support.
7. Remove the main burner orifice and replace it with
the orifice supplied in the conversion kit.
8. SIT top Convertible Pilot
Gently lift off the pilot hood from the pilot. (Do not
remove the spring clip holding the hood in place).
Using a 5/32” Allen key, unscrew the exposed orifice.
Insert the new orifice supplied in the kit, do not over
tighten the orifice. Replace the pilot hood ensuring
the index tab aligns with the notch on the hood.
30
KT615
820
Fig. 46 Nova SIT 820 gas valve.
b. Ensure the rubber gasket (D) is properly posi
tioned and install the new Hi/Lo pressure regulator to the valve using the new screws (E) supplied
with the kit. Tighten screws securely. (Reference
torque - 25 in.LB)
c. Install the enclosed identification label (F) to the
valve body where it can be easily seen.
Honeywell Gas Control Valve (Fig. 47)
The Honeywell valve fitted to this unit is suitable for
use with LP or Natural Gas. It is converted to the
required gas application by the installation of a color
coded “conversion screw”.
a) Using a suitable small screwdriver lift out the
central regulator cap from the “Hi - Lo” knob on
the valve.
b) Unscrew the exposed conversion screw.
c) Insert the new color coded conversion screw.
Do not over-tighten the screw, it must be finger
tight.
d) Refit the regulator cap.
e) Mount the conversion label supplied with con-
version screw to the valve in a visible position.
11. Reassemble the fireplace in the reverse order, except for the window frame assembly. Leave this off
until after the unit has been checked for leaks and
the gas supply has been bled.
10007852
Page 31
12. After bleeding the gas line and checking for leaks
L
O
with a soap solution, replace the window frame
assembly. Fire up the unit, check for flame impingement on the logs, adjusting them if necessary. Check
manifold and supply pressures against appliance
specifications.
Maintenance
LDVT Series Direct Vent GaS Fireplace
Regulator Cap
Fig. 47 Honeywell gas valve.
Conversion Screw
Pressure Regulator Housing
HV120
Burner and Burner Compartment
It is important to keep the burner and the burner
compartment clean. At least once per year the logs and
lava rock/ember material should be removed and the
burner compartment vacuumed and wiped out. Remove
and refit the logs as per the instructions in this manual.
Always handle the logs with care as they
are fragile and may also be hot if the
fireplace has been in use.
FK24/FK12 Fan Assembly
The fan unit requires periodic cleaning. At least once
per month in the operating season open the lower
louvre panels and wipe or vacuum the area around the
fan to remove any build up of dust or lint.
Brass Trim
Clean the brass trim pieces using a soft cloth lightly
dampened with lemon oil. Do not use water or
household cleaners on any brass components.
Cleaning the Standing
Pilot Control System
The burner and control system consist of:
• burner • gas orifice
• pilot assembly • thermopile
• millivolt gas valve
Most of these components may require only an
occasional checkup and cleaning and some may
require adjustment. If repair is necessary, it should
be performed by a qualified technician.
1. Turn off pilot light at gas valve.
2. Allow fireplace to cool if it has been operating.
5. Vacuum burner compartment especially around
orifice primary air openings.
6. Visually inspect pilot. Brush or blow away any dust
or lint accumulation.
7. Reinstall logs.
8. Ignite pilot - Refer to Lighting Instructions.
9. Reinstall window frame assembly.
To obtain proper operation, it is imperative that the pilot
and burner’s flame characteristics are steady, not lifting
or floating.
Typically, the top 3/8” to 1/2” of the thermopile should
be engulfed in the pilot flame. (Refer to Page 24, Figure
43)
To adjust pilot burner: (by qualified service technician)
1. Remove pilot adjustment cap
2. Adjust pilot screw to provide properly sized flame.
3. Replace pilot adjustment cap.
The primary air shutter is set at factory and should
only be adjusted, if necessary, by a qualified service
technician.
10007852
31
Page 32
LDVT Series Direct Vent Gas Fireplace
43LDVT
1b
1c
1a
1d
1g
HI
LO
22
21
19a,b
18a,b
17
30
33LDVT
1
1a
1b
1c
1d
1e
1f
1a
36LDVT
1
1g
1h
1i
2
3
6a,b
8
7a,b
9
11
12
13
14
15
16
20
23
24
25
26
29
31
32
33
34
35
37
42
41
40
39
1
39LDVT
1a
1b
1c
1d
43
44
CFM Corporation reserves the right to make changes in design, materials, specifications, prices and discontinue colors and products at any time,
with out notice.
This auxiliary fan system increases the efficiency of the
circulation of the heating air.
The FK24 fan kit allows variable speed control of the
circulation fan and also incorporates a heat sensor in
the circuit.
Specifications
115 Volt / 60Hz / 56 Watts
Maintenance
The fan itself does not require regular maintenance,
however periodic cleaning of the fan and the
surrounding area is required.
Check the area under the control door (lower louvre
assembly) and in front of the fan and wipe or vacuum this
area at least once a month during the operating season.
Installation
The fan assembly and other components are supplied
fully wired eliminating the need for a licensed electrician
to carry out the installation.
If hard wiring the fan using Method B (following), we
strongly recommend the use of a licensed electrician.
1. Open the lower louvre assembly. Maneuver the fan
& bracket assembly around the gas valve and lines
to locate the unit onto the screw studs on the back of
the fireplace.
2. Install the thermal sensor under the bottom of the of
the firebox, locating it over the two 10 mm studs and
secure it with nuts.
3. Locate the fan speed control unit. This can be fitted
behind the lower louvre assembly as in Figure 48
or located remotely in a conveniently located wall
mounted electrical box. Remote location of the
speed control will require suitable extension of the
component wiring.
4. The power supply may be connected in two ways:
Method ARoute the 6’ lead fitted to the unit to a conveniently
located wall socket.
Method B (Using EB-1 Receptacle Box)
The EB-1 receptacle box (Pt. # ZA1200) may be
hard wired into the house supply. The fan lead is
then plugged into the EB-1 box. For instruction on
wiring the EB-1 Electrical Junction Box see the
earlier chapter in the Installation section of this
manual.
Thermal Sensor
Fan Speed
Switch
FP1230
Fig. 48 FK24 fan placement.
Lines
Gas
Fan
EB-1
Receptacle
Box
FK12
This auxiliary fan system increases the efficiency of the
circulation of the heating air.
The FK12 Fan Assembly is a fixed speed fan system
and does not allow for variable speed control. It does
not use the speed control unit or the heat sensor used
in the FK24 Kit.
Specifications
115 Volts / 60 Hz / 56 Watts.
Maintenance
The fan itself does not require regular maintenance,
however periodic cleaning of the fan and the
surrounding area is required.
Check the area under the control door (lower louvre
assembly) and in front of the fan and wipe or vacuum this
area at least once a month during the operating season.
Installation
The fan assembly is supplied fully wired eliminating the
need for a licensed electrician to carry out the installation.
1. Open the lower Louvre assembly. Maneuver the
fan & bracket assembly around the gas valve and
lines to locate the unit against the back wall of the
appliance, resting on the base.
2. With the protective cover removed from the selfadhesive ‘Velcro’ strips apply mild pressure to the
fan & bracket unit to secure the strips to the metal
panels. No further securing is required.
3. Power to the fan can be supplied by plugging the
supplied lead into a conveniently located wall socket
or by using a hard-wired EB-1 connector box.
10007852
35
Page 36
LDVT Series Direct Vent Gas Fireplace
Black
White
Ground
The fireplace, when installed, must be
electrically connected and grounded in
accordance with local codes or, in the
absence of local codes, with the current
CSA C22.1 Canadian Electric Code.
For USA installations follow the local
codes and the national electrical code
ANSI/NFPA No. 70.
Should this fan require servicing or repair
the power supply must be disconnected.
For rewiring of any replacement parts refer
to Figure 49.
Any electrical re-wiring of this fan must be
done by a licensed electrician.
Temperature Sensor
Speed Control
Wiring Instructions
Fan
For aesthetic purposes we recommend
lining up the horizontal mortar lines.
Side
Panel
Fig. 50 Ceramic panel installation.
Rear Refractory
Panel
Rear Panel Support Brackets
Back Panel
Log Support
Burner Tray
Side
Panel
FP1231
Firebox Back
Panel
FP1025
Fig. 49 FK24 fan wiring.
Ceramic Refractory Panels
Ceramic refractory panels are available for the LDV
series appliances
36DVARFKB Black
36DVARFKR Rustic Bronze
36DVARFKS Pewter
Romanesque - Square
36DVSRFKB Black
36DVSRFKR Rustic Bronze
36DVSRFKS Pewter
Marquette - Arch
36DVAMTKB Black
36DVAMTKR Rustic Bronze
36DVAMTKS Pewter
Marquette - Square
36DVSMTKB Black
36DVSMTKR Rustic Bronze
36DVSMTKS Pewter
10007852
37
Page 38
LDVT Series Direct Vent Gas Fireplace
38
10007852
Page 39
LIMITED LIFETIME WARRANTY
LDVT Series Direct Vent GaS Fireplace
PRODUCT COVERED BY THIS WARRANTY
All Vermont Castings gas stoves, gas inserts, and gas fireplaces, and all Majestic brand gas fireplaces equipped with
an Insta-Flame Ceramic Burner, or standard steel tube burner.
BASIC WARRANTY
CFM Corporation (hereinafter referred to collectively as the Company)
warrants that your new Vermont Castings
Stove is free from manufacturing and material defects for a period of
one year from the date of purchase, subject to the following conditions
and limitations.
EXTENDED LIFETIME WARRANTY
The heat exchanger, where applicable, and combustion chamber of
every Vermont Castings or Majestic gas product is warranted for life
against through wall perforation. All appliances equipped with an InstaFlame Ceramic Burner have limited lifetime coverage on the ceramic
burner plaque. Warrantees are made to the original owner subject
to proof of purchase and the conditions and limitations listed on this
Warranty Document
COMPONENT WARRANTY
CAST IRON: All external and internal cast iron parts are warranted for a
period of three years.
Note: On porcelain enamel finished external parts and accessories The
Company offers no Warranty on chipping of enamel surfaces. Inspect
all product prior to accepting it for any damage to the enamel.
The salt air environment of coastal areas or a high humidity environment
can be corrosive to the porcelain enamel finish. These conditions can
cause rusting of the cast iron beneath the porcelain enamel finish,
which will cause the finish to flake off.
Dye lot variations with replacement parts and/or accessories can occur
and are not covered by warranty.
GLASS DOORS: Glass doors are covered for a period of one year. Glass
doors are not warranted for breakage due to misuse or accident. Glass doors
are not covered for discoloration or burned in stains due to environmental
issues, or improper cleaning and maintenance.
BRASS PLATED PARTS AND ACCESSORIES: Brass parts should be
cleaned with Lemon oil only.
and masonry cleaners may corrode the brass finish. The Company will not
be responsible for, nor will it warrant any brass parts which are damaged
by external chemicals or down draft conditions.
GAS VALVES: Gas valves are covered for a period of one year
ELECTRONIC AND MECHANICAL COMPONENTS: Electronic and
mechanical components of the burner assembly are covered for one year.
All steel tube burners are warranted for one year.
ACCESSORIES: Unless otherwise noted all components and CFM
Corporation company supplied accessories are covered for a period of
one year.
CONDITIONS AND LIMITATIONS
• This Vermont Castings or Majestic product must be installed or serviced
by a qualified installer, preferably NFI or WETT (Canada) certified, as
prescribed by the local jurisdiction. It must be installed and operated at
all times in accordance with the Installation and Operating instructions
furnished with the product. Any alteration, willful abuse, accident, or
misuse of the product shall nullify this warranty.
• This warranty is non-transferable, and is made to the original owner,
provided that the purchase was made through an authorized supplier
of the Company.
• The customer must pay for any Authorized Dealer in-home travel fees
or service charges for in-home repair work. It is the dealers option
whether the repair work will be done in the customer’s home or in the
dealer’s shop.
• If upon inspection, the damage is found to be the fault of the manufacturer,
repairs will be authorized at no charge to the customer parts and/or
labor.
Brass cleaners cannot be used. Mortar mix
or Majestic Gas Fireplace/
• Any part and/or component replaced under the provisions of this
warranty is covered for six months or the remainder of the original
warranty, whichever is longest.
• This warranty is limited to the repair of or replacement of part(s) found
to be defective in material or workmanship, provided that such part(s)
have been subjected to normal conditions of use and service, after
said defect is confirmed by the Company’s inspection.
• The company may, at its discretion, fully discharge all obligations
with respect to this warranty by refunding the wholesale price of the
defective part(s)
• Any installation, labor, construction, transportation, or other related
costs/expenses arising from defective part(s), repair, replacement,
or otherwise of same, will not be covered by this warranty, nor shall
the Company assume responsibility for same. Further, the Company
will not be responsible for any incidental, indirect, or consequential
damages except as provided by law.
• SOME STATES DO NOT ALLOW FOR THE EXCLUSION OR
LIMITATIONS OF INCIDENTAL AND CONSEQUENTIAL DAMAGES
OR LIMITATIONS ON HOW LONG AN IMPLIED WARRANTY
LASTS, SO THE ABOVE LIMITATIONS MAY NOT APPLY TO YOUR
CIRCUMSTANCES. THIS WARRANTY GIVES YOU SPECIFIC
RIGHTS AND YOU MAY HAVE OTHER RIGHTS WHICH VARY FROM
STATE TO STATE.
• All other warranties-expressed or implied- with respect to the product,
its components and accessories, or any obligations/liabilities on the
part of the Company are hereby expressly excluded.
• The Company neither assumes, nor authorizes any third party to
assume on its behalf, any other liabilities with respect to the sale of
this Vermont Castings or Majestic product
• The warranties as outlined within this document do not apply to
chimney components or other non CFM Corporation accessories used
in conjunction with the installation of this product..
• Damage to the unit while in transit is not covered by this warranty but
is subject to claim against the common carrier. Contact the dealer
from whom you purchased your fireplace/stove (do not operate the
appliance as this might negate the ability to process the claim with the
carrier).
• The Company will not be responsible for:
a) Down drafts or spillage caused by environmental conditions such
as near-by trees, buildings, roof tops, hills, or mountains.
b) Inadequate ventilation or negative air pressure caused by
mechanical systems such as furnaces, fans, clothes dryers, etc.
• This warranty is void if:
a) The fireplace has been operated in atmospheres contaminated by
chlorine, fluorine, or other damaging chemicals.
b) The fireplace has been subjected to prolonged periods of dampness
or condensation
c) Any damages to the fireplace, combustion chamber, heat exchanger
or other components due to water, or weather damage, which is the
result of but not limited to, improper chimney/venting installation.
d) Any alteration, willful abuse, accident, or misuse of the product
has occurred.
IF WARRANTY SERVICE IS NEEDED…
1) Contact your supplier. Make sure you have your warranty,
your sales receipt, and the model/serial number of your CFM
Corporation product.
2) D O NOT ATTEMP T TO DO ANY SERVICE W ORK
YOURSELF.
10007852
39
Page 40
Efficiency Ratings
Model EnerGuide Ratings Steady State (%) D.O.E. Fireplace Efficiency (%) Fan-OFF Fan-ON (AFUE%)