Vermont Casting 360DVSL, 360DVSR, 360DVS2, 360DVS3 User Manual

Multisided Top/Rear Vent
  
D
E
S
I
G
N
C
E
R
T
I
F
I
E
D
Convertible Direct Vent Fireplaces: 360DVS2 360DVS3 360DVSL 360DVSR
INSTALLER/CONSUMER
SAFETY INFORMATION
PLEASE READ THIS MANUAL BEFORE INSTALLING AND USING
APPLIANCE IMPORTANT: Read all instructions
and warnings carefully before starting installation. Failure to follow these instructions may result in a possible fire hazard, and will void the warranty.
WARNING: manual is not followed exactly, a fire or
explosion may result, causing property damage, personal injury, or loss of life.
If the information in this
FOR YOUR SAFETY:
• Installation and service must be per formed by a qualified installer, service agency, or the gas supplier.
• Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
If you smell gas:
1. Open windows
2. Do not touch electrical switches.
3. Do not try to light any appliance.
4. Extinguish any open flame.
5. Do not use any telephone in your
building.
6. Immediately call your gas supplier
from a neighbor’s phone.
7. Follow your gas supplier’s
instructions.
8. If you cannot reach your gas supplier,
call the fire department.
-
Homeowner’s Installation
and Operating Manual
INSTALLER: Leave this manual with the appliance. CONSUMER: Retain this manual for future reference.
10006326 6/06 Rev. 1
Installation & Operating Instructions
X
X
X
Y
Y
Y
Z
A
A
B
This gas appliance should be installed by a qualified installer in accordance with local building codes and current CSA-B149.1 Installation Codes for Gas Burning Appliances and Equipment. If the unit is being installed in a mobile home, the installation should comply with the current CAN/CSA Z 240.4 code. For U.S.A. Instal lations, follow local codes and/or the current National Fuel Gas Code, ANSI Z223.1/NFPA 54.
In the Commonwealth of Massachusetts, all gas fittings and installation of this appliance shall be done by a licensed gas fitter or licensed plumber. FOR SAFE INSTALLATION AND OPERATION PLEASE NOTE THE FOLLOWING:
1. This fireplace gives off high temperatures and should be located out of high traffic areas and away from furniture and draperies.
2. Children and adults should be alerted to the hazards of high surface temperatures of this fireplace and should stay away to avoid burns or ignition of clothing.
3. CAUTION: Due to high glass surface temperature, chil-
dren should be carefully supervised when in the same room as fireplace.
4. Under no circumstances should this fireplace be modified. Parts removed for servicing should be replaced prior to operating this fireplace again.
5. Installation and any repairs to this fireplace must be per formed by a qualified installer, service agency or gas sup plier. A professional service person should be contacted to inspect this fireplace annually. Make it a practice to have all of your gas fireplaces checked annually. More frequent cleaning may be required due to excess lint and dust from carpeting, bedding material, etc.
6. Control compartments, burners and air passages in this fireplace should be kept clean and free of dust and lint. Make sure the gas valve and pilot light are turned off be fore you attempt to clean this fireplace.
7. The venting system (chimney) of this fireplace should be checked at least once a year, and if needed, your venting system should be cleaned.
8. Keep the area around your fireplace clear of combustible materials, gasoline and other flammable vapor and liquids. This fireplace should not be used as a drying rack for clothing, nor should Christmas stockings or decorations be hung on or around the fireplace.
9. Under no circumstances should any solid fuels (wood, coal, paper or cardboard, etc.) be used in this fireplace.
10. The flow of combustion and ventilation air must not be obstructed in any way.
11. When the fireplace is installed directly on carpeting, vinyl tile, or any combustible material other than wood, it must be installed on a metal or wood panel extending the full width and depth of the fireplace.
12. This fireplace requires adequate ventilation and combus tion air to operate properly.
13. This fireplace must not be connected to a chimney flue serving a separate solid fuel-burning fireplace.
14. When the fireplace is not in use, it is recommended the gas valve be left in the “OFF” position.
10006326
360DVS Series Direct Vent Fireplaces
This appliance may be installed in an aftermarket, per­manently located, manufactured home, or mobile home where not prohibited by local codes.
-
This appliance is only for use with type of gas indicated on the rating plate. This appliance is not convertible for use with other gases, unless a certified kit is used.
IMPORTANT:
PLEASE REVIEW THE FOLLOWING CAREFULLY
Remove any plastic from trim parts before turning the fireplace ON. It is normal for fireplaces fabricated of steel to give off some expansion and/or contraction noises during the start up or cool down cycle. Similar noises are found with your furnace heat exchanger or car engine. It is not unusual for your gas fireplace to give off some odor the first time it is burned. This is due to the curing of the paint and any undetected oil from the manufacturing process.
Please ensure that your room is well ventilated
- open all windows.
-
-
It is recommended that you burn your fireplace for at least ten (10) hours the first time you use it. If the optional fan kit has been installed, place the fan switch in the “OFF” position during this time.
Proposition 65 Warning: Fuels used in gas, wood­burning or oil fired appliances, and the products of combustion of such fuels, contain chemicals known
-
to the State of California to cause cancer, birth de­fects and other reproductive harm. California Health & Safety Code Sec. 25249.6
Locating Your Fireplace
LU584-2
-
Fig. 1 Locating your gas fireplace
A Wall Location (Fig. 1)
Y (Minimum distance between a glass panel and a
parallel wall) = 3’ (914mm)
Z (Minimum distance between edge of a glass panel
and an adjacent wall) = 3” (76mm) B Island Location (Fig. 1) X (Maximum length of horizontal venting) = 20’ (6.1m)
Refer to the venting section in this manual for specific dimen-
sions.
3
360 DVS Series Direct Vent Fireplaces
J
J
K
K
H
D
A
E
B
I
E
A
F
C
H
Electrical Access
Gas Line Access
Electrical Access
Gas Line Access
K
J
J
K
J
J
G
J
J
K
K
H
D
A
E
B
E
A
F
CK
H
G
I
Electrical Access
Gas Line Access
Electrical Access
Gas Line Access
J
J
K
J
J
Fireplace Dimensions - 360DVS2
Rear Vent Configuration
Top Vent Configuration
Fig. 2a Fireplace specifications—360DVS2
Appliance Dimensions
Ref. Rear Vent Configuration Top Vent Configuration
A 38¹⁄₈ (968 mm) 38¹⁄₈ (968 mm)
B 43¹⁄₄ (1099 mm) 43¹⁄₄ (1099 mm)
C 24” (610 mm) 24” (610 mm) D 24” (610 mm) 24” (610 mm) E 37 F 35 G 30 H 12” (305 mm) 12” (305 mm) I 3 J 2 K 1
4
³⁄₈ (949 mm) 37³⁄₈ (949 mm) ⁷⁄₈ (911 mm) 35⁷⁄₈ (911 mm) ¹⁄₂ (775 mm) 7” (178 mm)
¹⁄₈ (80 mm) 3¹⁄₈ (80 mm) ³⁄₄ (70 mm) 2³⁄₄ (70 mm) ¹⁄₄ (33 mm) 1¹⁄₄ (33 mm)
10006326
I
J
K
K
ROD
B
E
C
G
F
D
A
H
H
B
Electrical Access
Gas Line Access
C
K
J
J
I
J
K
K
B
E
C
F
D
A
H
H
B
Electrical Access
Gas Line Access
K
J
J
G
Fireplace Dimensions - 360DVS3 / 306DVSL / 360DVSR
Rear Vent Configuration
Top Vent Configuration
360DVS Series Direct Vent Fireplaces
Fig. 2b Fireplace specifications—360DVS3/ 360DDVSL/ 360DVSR
Appliance Dimensions
Ref. Rear Vent Configuration Top Vent Configuration A 38 B 40 C 24” (610 mm) 24” (610 mm) D 24” (610 mm) 24” (610 mm) E 37 F 35 G 30 H 12” (305 mm) 12” (305 mm) I 3 J 2 K 1
10006326
¹⁄₈ (968 mm) 38¹⁄₈ (968 mm) ⁵⁄₈ (1032 mm) 40⁵⁄₈ (1032 mm)
³⁄₈ (949 mm) 37³⁄₈ (949 mm) ⁷⁄₈ (911 mm) 35⁷⁄₈ (911 mm) ¹⁄₂ (775 mm) 7” (178 mm)
¹⁄₈ (80 mm) 3¹⁄₈ (80 mm) ³⁄₄ (70 mm) 2³⁄₄ (70 mm) ¹⁄₄ (33 mm) 1¹⁄₄ (33 mm)
5
360 DVS Series Direct Vent Fireplaces
ROH
ROD
ROW
ROD
ROH
ROW
Framing Dimensions - 360DVS2
Rear Vent Configuration
Top Vent Configuration
CFM121
CFM122
Fig. 3a Fireplace framing dimensions—360DVS2
Framing Dimensions
Ref. Rear Vent Configuration Top Vent Configuration
ROD 24” (610 mm) minus two times finishing material thickness to be even with face of unit. ROH
due to 3¹⁄₈” (79 mm) allowance for flue collar ROW Not to be framed until unit is set in place 43
due to 3¹⁄₈” (79 mm) allowance for flue collar
6
38⁵⁄₈” (981 mm)
Not to be framed until unit is set in place,
³⁄₄” (1111 mm)
10006326
ROD
ROW
ROD
ROH
ROH
ROH
ROD
360DVSL
360DVS/3/L/R
360DVS3
360DVSR
ROD
ROD
ROH
ROW
ROH
ROH
ROD
360DVSL
360DVS/3/L/R
360DVS3
360DVSR
Framing Dimensions - 360DVS3 / 360DVSL / 360DVSR
Rear Vent Confiration
Top Vent Configuration
360DVS Series Direct Vent Fireplaces
CFM123
Fig. 3b Fireplace framing dimensions—360DVS3/ 360DVSL/ 360DVSR
Framing Dimensions
Ref. Rear Vent Configuration Top Vent Configuration Model 360DVS3 360DVSL/R 360DVS3 360DVSL/R ROD (See Note 1) (See Note 2) (See Note 1) ( See Note 2) ROH 38
to 3¹⁄₈” (79 mm) allowance for flue collar ROW 40
NOTE 1: 24” (610 mm) minus two times (2x) finishing material thickness to be even with face of unit. NOTE 2: 24³⁄₄” (629 mm) minus one time (1x) finishing material thickness to be even with face of unit.
10006326
⁵⁄₈” (981 mm) Not to be framed until unit is set in place, due
⁵⁄₈” (1032 mm) minus one time (1x) finishing material thickness to be even with face of unit.
CFM124
7
360 DVS Series Direct Vent Fireplaces
O
N
M
L
K
A B C D E
V
W
X
Y
Z
J
F
G
H
I
Clearance to Combustibles
Appliance
Top .........................................0” (0 mm) to standoff
Bottom ..................................................... 0” (0 mm)
Vent End ....................... 1/2” (13 mm) to rear panel
Nonvent End (DVS2) .............................. 0” (0 mm)
Venting Concentric sections of DV Vent:
Top, bottom & sides ..............................
1” (25 mm) Nonconcentric sections of DV Vent:
Side and bottom .................................... 1” (25 mm)
Top ........................................................ 2” (51 mm)
Mantels
The height at which a combustible mantel is fitted above the fireplace is dependent on the depth of the mantel. This also applies to the distance between the mantel leg (if so fitted) and the fireplace. For correct mounting height and width, refer to Fig. 4a and 4b and the Mantel Chart below.
The fitting of a bay window trim kit does not affect the distances and reference points referred to in the dia­gram and chart.
Noncombustible mantels and legs may be installed at any height and width around the appliance.
When using paint or lacquer to finish the mantel, such paint or lacquer must be heat resistant to prevent dis­coloration.
Top View
Mantel Leg
CFM197
Front View
Side of Combustion Chamber
Mantel Leg
CFM170
Mantel Mantel Leg From Side
Ref. Leg Depth Ref. of Comb. Opening
F 10” (254 mm) K 11 G 8” (203 mm) L 9 H 6” (152 mm) M 7 I 4” (102 mm) N 5 J 2” (51 mm) O 3
¹⁄₂” (292 mm) ¹⁄₂” (241 mm) ¹⁄₂” (191 mm) ¹⁄₂” (140 mm)
¹⁄₂” (89 mm)
Fireplace
Louvre Assembly Top
Top of Combustion Chamber
Bottom of Door Trim
Mantel Shelf Mantel from Top
Ref. or Breast Plate Ref. of Comb. Chamber
V 10” (254 mm) A 19” (483 mm)
Mantel Chart
W 8” (203 mm) B 17” (432 mm) X 6” (152 mm) C 15” (381 mm) Y 4” (102 mm) D 13” (330 mm) Z 2” (51 mm) E 11” (297 mm)
Fig. 4a Combustible mantel minimum installation.
8
CFM146
Fig. 4b Combustible mantel leg minimum installation.
Hearth
A hearth is not mandatory; however, for aesthetic purposes, we recommend installing a noncombustible hearth that projects out 12” (305mm) or more from the front of the fireplace.
Cold climate installation recommendation:
When installing this unit against a noninsu­lated exterior wall or chase, it is mandatory the outer walls be insulated to conform to applicable insulation codes.
10006326
360DVS Series Direct Vent Fireplaces
Framing & Finishing
1. Choose the unit location.
2. Place the unit into position and secure it to the floor with 1¹⁄₂” (38mm) screws or nails. Holes to secure the unit to the floor are located behind the access door grille on the left and right sides of the unit.
3. Frame in the fireplace with a header across the top. It is important to allow for the finished wall face when setting the depth of the frame.
4. Drywall (sheetrock) or wood material may be placed with a zero clearance to the top edges of the appli­ance when finishing walls above sides of the appli­ance with glass windows. NOTE: Attach wall finish-
ing to constructed frame, not the appliance.
5. On 360DVSL and 360DVSR, drywall, wood, or wood molding may be placed with zero clearance to the rear wall of the unit, along the vertical edge formed by the standoffs, to intersection of the rear wall, to the side wall having the small glass window. NOTE:
Attach wall finishing to constructed frame, not the appliance.
Final Finishing
Noncombustible materials such as brick or tile may be extended over the edges of the face of the appliance. DO NOT cover any vent or grille panels.
If a Trim Kit is going to be installed on the fireplace, the brick or tile will have to be installed flush with the edges of the appliance.
Gas Specifications
Model Fuel Gas Control BTU/h BTU/h
360DVS2RN Nat Millivolt 38,000 26,600
360DVS2RP Prop Millivolt 38,000 28,500
360DVS2EN Nat 24V Hi/Lo 38,000 26,600 360DVS2EP Prop 24V Hi/Lo 38,000 28,500 360DVS3RN Nat Millivolt 38,000 26,600 360DVS3RP Prop Millivolt 38,000 28,500 360DVS3EN Nat 24V Hi/Lo 38,000 26,600 360DVS3EP Prop 24V Hi/Lo 38,000 28,500 360DVSLRN Nat Millivolt 38,000 26,600 360DVSLRP Prop Millivolt 38,000 28,500 360DVSLEN Nat 24V Hi/Lo 38,000 26,600 360DVSLEP Prop 24V Hi/Lo 38,000 28,500 360DVSRRN Nat Millivolt 38,000 26,600 360DVSRRP Prop Millivolt 38,000 28,500 360DVSREN Nat 24V Hi/Lo 38,000 26,600 360DVSREP Prop 24V Hi/Lo 38,000 28,500
Max. Max.
Input Input
Gas Inlet & Manifold Pressures
Natural LP (Propane)
Inlet Minimum 4.5” w.c. 11.0” w.c.
Inlet Maximum 14.0” w.c. 14.0” w.c. Manifold Pressure 3.5” w.c. 10.0” w.c.
Input ratings are shown in BTU per hour and are certified without deration for elevations up to 4,500 feet (1,370 m) above sea level.
For elevations above 4,500 feet (1,370 m) in USA, installations must be in accordance with the current ANSI Z223.1/NFPA 54 and/or local codes having jurisdiction.
In Canada, please consult provincial and/or local authorities having jurisdiction for installations above 4,500 feet (1,370 m).
360DVS2/ 360DVS3/ 360DVSL/ 360DVSR
CERTIFIED TO
ANSI Z21.88-2005 / CSA 2.33-2005
Vented Gas Fireplace Heaters
Gas Line Installation
When purging the gas lines, the window frame assembly must be removed.
The gas pipeline can be brought in through the vent end of the fireplace as well as the bottom. Knockouts (to allow gas pipe installation and testing any gas con­nection) are provided on the bottom behind the valve. It is most convenient to bring the gas line in from the vent end of the valve, as this allows fan installation or removal without disconnecting the gas line.
The gas line connection can be made with properly tinned 3/8” copper tubing, 3/8” rigid pipe, or an ap­proved flex connector. Since some municipalities have additional local codes, it is always best to consult your local authority and the CSA-B149.1 installation codes.
For USA installations, consult the current National Fuel Gas Code, ANSI Z223.1/NFPA 54.
Always check for gas leaks with a mild soap and water solution. Do not use an open flame for leak testing.
1/2” Gas Supply
1/2” NPT X 1/2” Flare Shut-Off Valve
3/8” Flex Line (From Valve)
10006326
FP297a
Fig. 5 Gas shutoff valve and flex connector.
9
360 DVS Series Direct Vent Fireplaces
TP TH
TP
TH
The gas control is equipped with a captured-screw type pressure test point, therefore it is not necessary to pro­vide a 1/8” test point upstream of the control.
When using copper or flex connector, use only ap
­proved fittings. Always provide a union when using black iron pipe so that the gas line can be easily discon­nected for burner or fan servicing. Refer to the gas specification for pressure details and ratings.
Isolate or disconnect this or any other gas appliance control from the gas line when pressure testing.
DO NOT subject the fireplace valve to test pressures exceeding 1/2 psi.
EB-1 Electrical Junction Box Connection
The fireplace, when installed, must be electrically connected and grounded in ac­cordance with local codes; in the absence of local codes, use the current CSA C22.1
Canadian Electrical Code.
For USA installations, follow the local codes and National Electrical Code ANSI/ NFPA No. 70.
It is strongly suggested the wiring of the EB-1 Electrical Junction Box be carried out by a licensed electrician.
Ensure power to the supply line has been disconnected before commencing with this procedure.
The EB-1 electrical junction box has been supplied standard on this model to allow for easy connection of the optional fan kits. (Fig. 6)
To connect the EB-1 box to the house electrical supply follow the steps below.
1. Remove the front cover of the EB-1 box.
2. Remove the plug socket assembly from the EB-1
box.
3. Feed the supply line in from the out through the elec
trical knockout.
4. Connect the ground wire of the supply line to the
green screw of the socket assembly.
5. Connect the white wire of the power line to the
chrome screw of the socket assembly.
6. Connect the black wire of the power supply line to
the brass screw (polarized) of the socket assembly.
7. Refit the socket assembly back into the electrical
box and replace the cover plate.
8. The EB-1 electrical junction box is now ready to sup
ply power to the FK12 or FK24 fan kit, if used.
Electrical Inlet Hole
Gas Inlet Hole
EB-1 Electrical box Depend­ing on the specific model, this box may be installed on
FP1428
Fig. 6 EB-1 attachment.
either side of the appliance.
Remote ON/OFF Switch Installation
Do not wire the remote ON/OFF wall switch for this gas appliance into a 120V power supply.
1. Thread the wiring through the holes on the end panels of the appliance. Take care not to cut the wire or insulation on metal edges. Route the wire to a conveniently located receptacle box.
2. Attach the wire to the ON/OFF switch and install the switch into the receptacle box.
3. Connect the other ends of the wire to the gas control valve, as shown in Figure 7.
Remote ON/OFF Switch
Gas Control Valve
-
FP1429
Fig. 7 Remote switch wiring diagram for R models.
Alternate Switch Location
The remote switch can be installed on the front or the side of the access door. Simply mount the switch to the
-
bracket provided and screw the bracket to either side of the frame, lining up the screws with the prepunched holes. (Fig. 8)
10
10006326
FP1430
Fig. 8 Alternate switch location.
Optional Top Vent Application
This appliance is shipped as a rear vent unit. If the installation layout requires the unit to be a top vent con­figuration, the appliance can be converted by following the steps below.
When removing and refitting the plates and adapter, be sure the associated gasket is undamaged and refitted as required.
1. Remove the ten (10) screws securing the outer col­lar adapter to the fireplace body. (Fig. 9)
2. Set the collar aside, complete with the gasket.
NOTE: Do not damage the gasket, as the adapter and gasket must be refitted.
3. Remove the insulation material (exposed in Step
2) from the top of the unit. (Fig. 10) This material can be discarded; however, if the unit is converted back to rear-vent, a new piece of insulation material approved by CFM Corporation must be used for this purpose.
NOTE: When converting appliance to top vent,
ensure the insulation material referred to in step 3 is completely removed.
4. Remove the 4 screws securing the flue cover plate to the top of the intake box and remove the cover and gasket. (Fig. 11)
5. Remove 4 screws securing the flue pipe to back of the intake box and remove pipe and gasket. (Fig. 11)
6. Secure the plate and gasket removed in step 4 over the flue opening in the back of the intake box. En sure the gasket is in place and undamaged.
7. Install the flue pipe and gasket removed in step 5 over the flue opening in the top of the intake box.
8. Refit the outer collar adapter and gasket to the unit with the round collar on the top. Secure the adapter with the 10 screws removed in step 1.
-
360DVS Series Direct Vent Fireplaces
Remove These Screws
Remove These Screws
Outer Collar Adapter
FP1431
Fig. 9 Remove screws from outer collar adapter.
Insulation Pad (Must be removed)
Flue Pipe
FP1432
Fig. 10 Remove flue cover and pipe.
Flue Cover Plate
Flue Pipe
10006326
FP1433
Fig. 11 Flue pipe removal.
11
360 DVS Series Direct Vent Fireplaces
PILOT
HONEYWELL IGNITION MODULE
ORANGE
BLUE
BLACK
WHITE
NOVA SIT 822 VALV
E
HI
LO
POWER CORD
W/FEMALE SPADE
120 VAC RTN
WHITE
GREEN
BLACK
120 VAC HOT
BLACK
YELLOW
24 VAC RET
40VA TRANSFORMER
24 VAC HOT
BLACK
WHITE
WALL SWITCH
WHITE
OFF
1 2 3 5 6 8 9
MV MV/VP PV GRD 24V SENSE SPARK
24V
ORANGE
RED
GREEN
BLACK
Electronic Gas Control Valve
This appliance may be fitted with a Honeywell ignition module.
Installation of the remote ON/OFF starter switch on electronic ignition units (Fig. 12):
1. Thread the wiring through the holes on the side panels of the appliance. Take care not to cut the wire or insulation on metal edges. Route the wire to a conveniently located receptacle box.
2. Attach the wire to the ON/OFF switch and install the switch into the receptacle box.
3. Connect the white wire from the wall switch to the black wire from the transformer, using an approved wire nut. Connect the black wire from the wall switch to the black wire running from the #6 position of the ignition module, also using an approved wire nut.
General Venting
Your fireplace is approved to be vented either through the side wall, or vertically through the roof.
Only CFM Corporation venting components, specifi-
cally approved and labeled for this fireplace, may be used.
Venting terminals shall not be recessed into a wall or
siding.
Horizontal venting must be installed on a level plane
without an inclining or declining slope.
There must not be any obstruction such as bushes,
FP1225
Fig. 12 Honeywell ignition module.
garden shed, fencing, deck or utility building within 24” (610mm) from the front of the termination hood.
Do not locate the termination hood where excessive snow or ice buildup may occur. Be sure to check the vent termination area after snow falls; clear it to prevent accidental blockage of the venting system. When using a snow blower, make sure snow is not directed toward the vent termination area.
Location of Vent Termination
It is imperative the vent termination be located observ­ing minimum clearances as shown on the following page.
12
10006326
360DVS Series Direct Vent Fireplaces
V
V
V
V
V
V
V
X
X
X
D
E
B
B
B
C
B
M
B
A
J
K
F
L
VENT TERMINATION AIR SUPPLY INLET
AREA WHERE TERMINAL IS NOT PERMITTED
H
I
Fixed
Closed
Fixed
Closed
Operabl
e
Operable
Fixed
Closed
V
B
INSIDE
CORNER DETAIL
V
A
G
V
N
N
V
V
G
G
A
CFM145a
General Venting Information - Termination Location
Canadian Installations1 US Installations
2
A = Clearance above grade, veranda, porch, 12” (30cm) 12” (30cm) deck, or balcony
B = Clearance to window or door that may be 6” (15cm) for appliances 6” (15cm) for appliances opened < 10,000Btuh (3kW), 12” (30cm) < 10,000 Btuh (3kW), 9” for appliances > 10,000 Btuh (3kW) and (23cm) for appliances > 10,000 < 100,000 Btuh (30kW), 36” (91cm) Btuh (3kW) and < 50,000 Btuh for appliances > 100,000 Btuh (30kW) (15kW), 12” (30cm) for appliances > 50,000 Btuh (15kW)
C = Clearance to permanently closed window 12” (305mm) recommended to 12” (305mm) recommended to prevent window condensation prevent window condensation D = Vertical clearance to ventilated soffit located above the terminal within a horizontal 18” (458mm) 18” (458mm) distance of 2’ (610mm) from the center line of the terminal
E = Clearance to unventilated soffit 12” (305mm) 12” (305mm) F = Clearance to outside corner see next page see next page G = Clearance to inside corner (see next page) see next page see next page H = Clearance to each inside of center line 3’ (91cm) within a height of 15’ (5m) 3’ (91cm) within a height of 15’
extended above meter/regulator assembly above the meter/regulator assembly (5m) above the meter/regulator assy
I = Clearance to service regulator vent outlet 3’ (91cm) 3’ (91cm) J = Clearance to nonmechanical air supply inlet 6” (15cm) for appliances < 10,000 6” (15cm) for appliances
to building or the combustion air inlet to any Btuh (3kW), 12” (30cm) for < 10,000 Btuh (3kW), 9” other appliances appliances > 10,000 Btuh (3kW) and (23cm) for appliances > 10,000 < 100,000 Btuh (30kW), 36” (91cm) Btuh (3kW) and < 50,000 Btuh for appliances > 100,000 Btuh (30kW) (15kW), 12” (30cm) for appliances > 50,000 Btuh (15kW)
K = Clearance to a mechanical air supply inlet 6’ (1.83m) 3’ (91cm) above if within 10 feet (3m) horizontally
L = Clearance above paved sidewalk or paved 7’ (2.13m)† 7’ (2.13m)† driveway located on public property
M = Clearance under veranda, porch, deck or 12” (30cm)‡ 12” (30cm)‡ balcony
N = Clearance above a roof shall extend a minimum of 24” (610mm) above the highest point when it passes through the roof surface, and any other obstruction within a horizontal distance of 18” (450mm).
1 In accordance with the current CSA-B149 Installation Codes 2 In accordance with the current ANSI Z223.1/NFPA 54 National Fuel Gas Codes † A vent shall not terminate directly above a sidewalk or paved driveway which is located between two single family dwellings and serves both dwellings ‡ only permitted if veranda, porch, deck or balcony is fully open on a minimum 2 sides beneath the floor: NOTE: 1. Local codes or regulations may require different clearances.
2. The special venting system used on Direct Vent Fireplaces are certified as part of the appliance, with clearances tested and approved by the listing agency.
10006326
Fig. 13 Vent termination clearances.
13
360 DVS Series Direct Vent Fireplaces
Outside Corner
Inside Corner
Termination Clearances
Termination clearances for buildings with combustible and noncombustible exteriors.
A =
Combustible 6"(152mm)
Noncombustible 2"(50mm)
B =
Combustible 6"(152mm)
Noncombustible 2"(50mm)
A
Balcony -  with no side wall
G =  Combustible & Noncombustible
12"(305mm)
G
Balcony -  with perpendicular side wall
H = 24"(610mm)  J = 20"(508mm)
H
J
B
Recessed Location
C = Maximum depth of 48"
(1219mm) for recessed location.
D = Minimum width for back wall of a recessed location. Combustible 38"(965mm) Noncombustible 24"(610mm)
E = Clearance from corner in recessed location. Combustible 6"(152mm) Noncombustible 2"(50mm)
C
D
C
E
V
V
Combustible &
Noncombustible
  
V
V
V
Fig. 14 Termination clearances.
General Information Assembling Vent Pipes
Canadian Installations:
Venting system must be installed in accordance with the current CSA-B149.1 installation code.
USA Installations:
The venting system must conform with local codes and/ or current National Fuel Gas Code ANSI Z223.1/NFPA
54.
Only venting components manufactured by CFM Corpo ration can be used in Direct Vent systems.
When using twist-lock pipe, it is not necessary to use sealant on the joints. The only areas of the venting system that need to be sealed with high-temperature silicone sealant are the collars on the fireplace and ter­mination, and sliding joints of telescopic vent sections
used in the system.
14
Twist Lock Pipes
To join the twist lock pipes together, align the beads of the male end with the grooves of the female end. While bringing the pipes together, twist the pipe until the flange on the female end contacts the external flange on the male end. It is recommended that you secure the joints with three (3) sheet metal screws; however, this is not mandatory with twist lock pipe.
NOTE: For ease of assembly, use a lubricant (Vaseline
­or similar substance) on male end of twist lock pipe
prior to assembly.
Fig. 15 Twist lock pipe joints.
Male End
Screw Holes
584-15
Female End
TWL100
10006326
360DVS Series Direct Vent Fireplaces
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
eg: A
eg: B
How to Use the Vent Graph
The vent chart should be read in conjunction with the following vent installation instructions to determine the relationship of the vertical and horizontal dimensions of the vent system.
1. Determine the height of the center of the horizontal vent pipe exiting through the outer wall. Using this dimension on the Sidewall Vent Graph bellow, locate the point intersecting with slanted graph line.
2. From the point of this intersection, draw a vertical line to the bottom of the graph.
3. Select the indicated dimension, and position the fireplace in accordance with same.
Example A:
If vertical dimension from floor of the fireplace is 11’
(3.4 m), horizontal run to the face of outer wall must not exceed 14’ (4.3 m).
Example B:
If vertical dimension from floor of the unit is
7’ (2.14 m), horizontal run to the face of outer wall must not exceed 8¹⁄₂’ (2.6 m).
Rear Wall Application
When installed as a rear vent unit this appliance may be vented directly to a termination located on the rear wall
behind the appliance.
Specific rear vent starter kits must be used in these
applications (see ‘venting components’). The appli-
ance has been approved for installation flat against a rear wall. (Fig. 17)
Maximum horizontal distance between the rear of
the appliance and the outside face of the rear wall is 20” (508 mm). (Fig. 17)
Minimum clearances between any combustible ma-
terial and the vent pipe sections are:
Top ..............................................2” (51 mm)
Sides ...........................................1” (25 mm)
Bottom .........................................1” (25 mm)
Max. 20” (508mm)
Horizontal dimension from outside of the wall
to the center of the fireplace vent flange
Sidewall vent graph showing the relationship between vertical and
horizontal dimensions for a Direct Vent flue system.
Fig. 16 Sidewall vent graph.
10006326
Vertical dimension from floor of the unit
to center of the horizontal vent pipe
Fig. 17 Rear vent application.
Rear Wall Installation
Step 1
Locate and cut vent opening in the rear wall.
Combustible walls: Cut a rectangular hole measuring 10³⁄₈” H x 9³⁄₈” W (265 x 240 mm) through the exterior wall and frame. Frame in the opening per Figure 18.
Noncombustible walls: Cut a round hole measuring 7¹⁄₂” (190 mm) diameter through the exterior wall and frame. (Fig. 18)
STEP 2
For combustible walls: Measure wall thickness and cut zero clearance sleeve parts to proper length.
DV Graph
Max. length is 12” (305 mm). Assemble sleeve to its maximum opening of 10³⁄₈” x 9³⁄₈” (265 x 240 mm), and attach to firestop with #8 sheetmetal screws (supplied). Install firestop assembly. (Fig. 19)
NOTE: Zero clearance sleeve is required only for com­bustible walls.
FP1434
15
360 DVS Series Direct Vent Fireplaces
Vent Opening for Combustible Wall
9³⁄₈
(240mm)
10³⁄₈
(265mm)
Framing Detail
Vent Opening for Noncombustible Wall
7¹⁄₂
(190mm)
VO584-100
Fig. 18 Locate vent opening on rear wall.
Maximum Length 12” (305mm)
#8 Screws (2)
#8 Screws (2)
Firestop
CFM135a
Fig. 19 Adjustable zero clearance sleeve.
Side View
STEP 3
Measure the horizontal length requirement for the vent­ing including a 2” (51 mm) overlap, i.e. from the elbow to the outside wall face plus 2” (51 mm), or the distance required if installing a second 90˚ elbow. (Fig. 20)
STEP 4
Install the 4” (102 mm) vent to the appliance collar and secure with three (3) sheetmetal screws. Install the 7” (178 mm) vent pipe to the appliance collar and secure with three (3) sheetmetal screws. It is not neces­sary to seal this connection.
It is critical there be no downward slope away from the appliance when connecting the vent or elbow.
STEP 5
Guide vent through the vent hole as you place the appli­ance in its installed position. Guide the 4” (102 mm) and 7” (178 mm) collars of the vent termina­tion into the outer ends of the venting.
Do not force the termination. If the vent pipes do not align with the termination, remove and realign the vent­ing at the appliance flue collars.
Attach the termination to the wall as outlined in the instruction sheet supplied with the termination.
Vertical Sidewall Application
It is very important the venting system maintain its bal­ance between the combustion air intake and the flue gas exhaust, certain limitations concerning vent con­figurations must be strictly adhered to.
The vent graph (Fig. 16), showing relationship be-
tween vertical and horizontal side wall venting, will help determine allowable dimensions.
Minimum clearance between vent pipes and com-
bustible materials is 1” (25 mm) on top, bottom, and sides, unless otherwise noted.
When the vent termination exits through foundations
less than 20” (508 mm) below siding outcrop, the vent pipe must flush up with the siding.
It is best to locate the fireplace in such a way that
minimizes the number of offsets and horizontal vent length. The horizontal vent run refers to the total length of vent pipe from the flue collar of the fire­place to the face of the outer wall.
NOTE: When installing the appliance as a rear vent unit, the 90˚ transition elbow attached directly to the rear of the unit is not included in the following criteria and calculations. Unless it is specifically mentioned, this elbow should be ignored when calculating venting layouts.
FP1435
Fig. 20 Maximum three (3) 90° elbows per installation.
16
10006326
360DVS Series Direct Vent Fireplaces
A
B
90
o
1
2
3
4
1
2
3
4
Horizontal plane means no vertical rise exists on this portion of the vent assembly.
The maximum number of 90˚ elbows per side wall
installation is three (3).
If a 90˚ elbow is fitted directly on top of the fireplace
flange, the maximum horizontal vent run before the termination or a vertical rise is 36” (914mm).
The maximum number of 45° elbows permitted per
side wall installation is two (2). These elbows can be
installed in either the vertical or horizontal run.
For each 45° elbow installed in the horizontal run,
the length of the horizontal run MUST be reduced by
18” (45 cm). This does not apply if 45° elbows are
installed on the vertical part of the vent system.
The maximum number of elbow degrees in a system
Max. 20” (508mm)
Fig. 21 Maximum horizontal run w/no rise.
Max. 36” (914mm)
FP1436
is 270°. Example shown in Figure 23: Elbow 1 = 90°
Elbow 2 = 45° Elbow 3 = 45° Elbow 4 = 90° Total angular variation = 270°
1 + 2 + 3 + 4 = 270°
If a 90° elbow is used in the horizontal vent run
(level height maintained), the maximum horizontal vent length is reduced by 36” (914 mm). (Fig. 21) This does not apply if the 90° elbows are used to increase or redirect a vertical rise.
Example: According to the vent graph (Fig. 16),
the maximum horizontal vent length in a system with a 7¹⁄₂” (191mm) vertical rise is 20 ft. (6.1m), but if a 90° is required in the horizontal vent, it must be reduced to 17 ft. (5.2m).
NOTE: The sum of Dim. A and Dim. B must not be
greater than 17 ft. (5.2m). (Fig. 22)
Fig. 23 Maximum elbow usage.
Vertical Side Wall Installation
STEP 1
Locate and cut vent opening in the side wall. It may be necessary to first position the fireplace and measure to obtain the hole location. Depending on whether the wall is combustible or noncombustible, cut the opening to
size per Figure 24.
Combustible walls: Cut a rectangular hole measuring 9³⁄₈” H x 9³⁄₈” W (240 x 240mm) through the exterior wall and frame. Frame in the opening per Figure 24.
A + B = 17’ (5.2m) Max.
Noncombustible walls: Cut a round hole measuring 7¹⁄₂” (190 mm) diameter through the exterior wall and frame. (Fig. 24)
7’6” (2.3m)
STEP 2
For combustible walls: Measure wall thickness and cut zero clearance sleeve parts to proper length. Max. length is 12” (305mm). Assemble the sleeve and attach it to the firestop with #8 sheet metal screws (supplied). Install the firestop assembly. (Fig. 25)
Fig. 22 Horizontal run reduction.
FP1437
Zero clearance sleeve is required only for combustible walls.
10006326
FP1438
17
360 DVS Series Direct Vent Fireplaces
X
X
X
X
Vent Opening for Combustible Wall
9³⁄₈
(240mm)
9³⁄₈
(240mm)
Vent Opening for Noncombustible Wall
7¹⁄₂
(190mm)
Fig. 24 Locate vent opening on rear wall.
Framing Detail
VO584-100
Maximum Length 12” (305mm)
#8 Screws (2)
STEP 4
Apply a bead of silicone to the inner and outer flue collars of the fireplace and using appropriate length of pipe section(s) attach to fireplace with three (3) screws. Follow with the installation of the inner and outer elbow, again secure joints as described in “Connecting Vent Pipes” section.
STEP 5
Measure the horizontal length requirement including a 2” (51 mm) overlap, i.e. from the elbow to the outside wall face plus 2” (51 mm) (or the distance required if installing a second 90° elbow. (Fig. 27)
Always install horizontal venting on a level plane.
#8 Screws (2)
Firestop
CFM135a
Fig. 25 Adjustable zero clearance sleeve.
Side View
STEP 3
Place fireplace into position. (Fig. 26) Measure the verti­cal height (X) required from the base of the flue collars to the center of the wall opening.
Fig. 26 Vertical height requirement.
FP1439
FP1441
Fig. 27 Horizontal length requirement.
STEP 6
Use appropriate length of pipe section—telescopic or fixed—and install. The 20” (508 mm) section of pipe which goes through the wall is packaged with the 7DVSK starter kit, and can be cut to suit if necessary.
Seal vent pipe and firestop gaps with high temperature sealant to restrict cold air being drawn in around the fireplace.
STEP 7
Apply high temperature sealant to 4” (102 mm) and 7” (178 mm) collars, or to the termination 1” (25 mm) away from the crimped end. Guide 4” and 7” collars of vent terminations into respective vent pipes. Double check vent pipes to see that they overlap the collars by
18
10006326
360DVS Series Direct Vent Fireplaces
2” (51 mm). Secure termination to the wall with screws provided, and caulk around the wall plate to weather­proof.
One alternative to screwing the termination directly to the wallis the use of expanding plugs or an approved exterior construction adhesive.
Or, you may attach the termination with screws through the inner body into the 4” (102 mm) vent pipe; however, for this method, you must extend the 4” (102mm) pipe approximately 6” (153 mm) beyond the outer face of the wall.
Support the horizontal pipes with metal pipe straps every 36” (914mm).
Below Grade Installation
When it is not possible to meet required vent terminal clearances of 12” (305 mm) above grade level, we rec­ommend using a starter kit. It allows installation depth down to 7” (178 mm) below grade level. Measure 7” (178 mm) from the center of the horizontal vent pipe as it penetrates through the wall.
NOTE: Ensure sidewall venting clearances are ob­served. If venting system is installed below ground, we recommend a window well with adequate and proper drainage.
If installing a snorkel, a minimum 24” (610 mm) vertical rise is necessary. The maximum horizontal run with 24” (610 mm) vertical pipe is 36” (914mm). The measurement is taken from the collar of the fireplace (or transition elbow) to the face of exterior wall. See sidewall vent graph, Page 15, for extended horizontal runs if the vertical exceeds 24” (610 mm).
1. Establish vent hole through the wall. (Fig. 24)
2. Remove soil to depth of about 16” (406 mm) below base of snorkel. Install window well (not supplied). Refill hole with 12” (305 mm) of coarse gravel, leav­ing a clearance of about 4” (102 mm) below snorkel. (Fig. 28)
3. Install vent system.
4. Ensure a watertight seal is made around the vent pipe coming through the wall.
5. Apply high-temperature sealant caulking (supplied) around 4 in. and 7 in. snorkel collars.
6. Slide snorkel into vent pipes and secure to wall.
7. Level the soil so as to maintain a 4” (102 mm) clear ance below snorkel. (Fig. 29)
-
Zero Clearance Sleeve (if required)
Firestop
7” Pipe
24” (610mm)
Minimum
FP1442
Fig. 28 Below grade installation.
Screws
A minimum of 24” (610mm)
The 22” (559mm) vertical rise
Foundation Wall
vertical pipe must be installed when using the 7TDVSNORK Kit.
(center to center) of the snorkel may be included for calculation of maximum horizontal run.
7TDVSNORK (Snorkel)
Min. 4” (102mm) Clearance
(Ground)
Window Well
Gravel
Drain
Do not backfill around the snorkel. A clear­ance of at least 4” (102mm) must be main­tained between the snorkel and the soil.
If the foundation is recessed, use recess brackets (not supplied) for securing lower portion of the snorkel. Fas­ten brackets to wall first, then secure to snorkel with self drilling #8 x 1/2 sheetmetal screws. It will be necessary to extend vent pipes out as far as protruding wall face. (Fig. 29)
Snorkel
Foundation Wall
Wall Screws
Watertight Seal Around Pipe
Fig. 29 Snorkel installation / recessed foundation.
Sheet Metal Screws
CFM139
10006326
19
360 DVS Series Direct Vent Fireplaces
1
2
3
4
1
2
3
4
Min. 2' (610 mm)
Vertical Through-the-Roof Application
This Gas Fireplace has been approved for:
Vertical installations up to 40’ (12 m) in height. Up
to a 10’ (3 m) horizontal vent run can be installed within the vent system using a maximum of two 90° elbows. (Fig. 30)
Max. Height 40’
(12.2m)
Min. Height 8’
(2.4m)
Max. Height
40’ (12.2m) Min. Height
8’ (2.4m)
Max. 10’ (3m)
Support Straps
Every 36”
(914mm)
Max. 10’ (3m)
1 + 2 + 3 + 4 = 270°
FP1444
Fig. 31 Maximum elbow usage.
FP1443
Fig. 30 Support straps for horizontal runs.
Up to two 45° elbows may be used within the hori-
Fig. 32 Maximum termination to roof clearance.
FP1185
zontal run. For each 45° elbow used on the hori­zontal level the maximum horizontal length must be reduced by 18” (457 mm).
Example: Maximum horizontal length:
Zero elbows = 10’ (3 m) 1 x 45° elbows = 8¹⁄₂’ (2.6 m) 2 x 45° elbows = 7’ (2.1 m)
A minimum of an 8 ft. (2.43 m) vertical rise.
Two (2) sets of 45° elbow offsets may be used within
the vertical sections. From zero to max 8 ft. (2.43 m) vent pipe can be used between elbows. (Fig. 30)
7DVCS supports offsets. (Fig. 33) This application
will require you first determine the roof pitch and use the appropriate starter kit. See Venting Components List, Page 22.
The maximum angular variation allowed in the sys-
tem is 270˚. (Fig. 31)
The minimum height of the vent above the highest
point of penetration through the roof is 2’ (610mm). (Fig. 32)
20
10006326
360DVS Series Direct Vent Fireplaces
11" (279 mm)
11"
(279 mm)
Vertical Through-the-Roof Installation
1. Locate your fireplace.
2. Plumb to center of the (4”) flue collar from ceiling above and mark position.
3. Cut an opening equal to 9
4. Proceed to plumb for additional openings through the roof. In all cases, the opening must provide a minimum of 1” (25 mm) clearance to the vent pipe, i.e., the hole must be at least 9³⁄₈” x 9³⁄₈” (240 x 240mm).
5. Place fireplace into position.
6. Place firestop(s) #7DVFS or Attic Insulation Shield #7DVAIS into position and secure. (Fig. 35)
7. Install roof support (Fig. 33) and roof flashing making sure upper flange is below the shingles. (Fig. 34)
8. Install appropriate pipe sections until the venting is above the flashing. (Fig. 34)
9. Install storm collar and seal around the pipe.
10. Add additional vent lengths for proper height. (Fig. 32)
11. Apply high temperature sealant to 4” and 7” collars of vertical vent termination and install.
³⁄₈” x 9³⁄₈” (240 x 240mm).
If there is a room above ceiling level, a firestop spacer must be installed on both the bottom and the top sides of the ceiling joists. (Fig. 35) If an attic is above ceiling level, a 7DVAIS (Attic Insulation Shield) must be installed.
NOTE: The enlarged ends of the vent sections are to always face downward.
Attic Insulation Shield
Joist
Ceiling In­stallation
Upper Floor
Typical Roof Sup-
port Application
Fig. 33 Chimney support.
Typical Ceiling Sup
port Application
Sheet Metal Screws (#5) (3 per joint)
Sealant
Storm Collar
-
CFM110
Joist
Firestop Spacer
Nails (4)
CFM100
Fig. 35 Firestop and attic insulation shield.
Fig. 34 Roof flashing.
10006326
TWL101a
21
360 DVS Series Direct Vent Fireplaces
Twist Lock Venting Components
7TDVRVT Through-the-Wall Rear Vent Termination
Starter Kit Model 7TDVSK - Sidewall Starter Kit Model 7TDVSKV - Vertical Venting for 7TDVSKV-A: order 1/12 to 6/12 roof pitch for 7TDVSKV-B: order 7/12 to 12/12 roof pitch for 7TDVSKV-F: order flat roof Starter Kit Model 7TDVSKS - Snorkel Kit Snorkel Termination - 7TDVSNORK for Below Grade Installation
45˚ Elbow 7TDVT45 for Rear Vent to Vertical Vent or Vertical/Horizontal Offsets
90˚ Transition Elbow 7TDVRT90 for Rear Vent to Vertical Vent 90° Elbow 7TDV90 Vertical/Horizontal Offset
Telescopic Vent Sections: 7TDVP1218 - 12” to 18” adjustable length 7TDVP3564 - 35” to 64” adjustable length
Pipe Sections for vertical or horizontal venting: Model 7TDVP8” 4 per box Model 7TDVP12” 4 per box Model 7TDVP24” 4 per box Model 7TDVP36” Model 7TDVP48”
Firestop Spacer Model 7DVFS
Attic Insulation Shield Model 7DVAIS
22
Vertical/ Horizontal Combination Offset Support Model 7DVCS
10006326
360DVS Series Direct Vent Fireplaces
1.
2.
Operating Instructions
Glass Information
Only glass approved by CFM Corporation should be used on this fireplace.
The use of any non-approved replacement glass will
void all product warranties.
Care must be taken to avoid breakage of the glass.
Do not operate appliance with glass front
removed, cracked or broken.
Replacement glass (complete with gasket) is
available through your Majestic Fireplaces dealer and should only be installed by a licensed qualified service person.
Louvre Removal
The top side and top end louvres are removed by
simply lifting the louvre assembly and pulling the as­sembly away from the fireplace. (Fig. 36)
The lower side louvres are hinged along there lower
edge and are folded down for access to components in the base cavity of the fireplace.
The lower end louvre assembly on the 360DVS3/
SL/ SR units is removed in the same manner as the top louvre assemblies.
Louvre
7. To reinstall the window frame assembly reverse this procedure.
Front Window Frame Assembly
1. Remove the top and bottom louvre assembly.
2. Remove the lower window trim (held in place with magnets).
3. Remove both lower retaining screws. Access to these screws is gained through the holes along the lower edge of the frame behind the trim. (Fig. 38)
4. Tilt lower edge of frame out slightly and lift window frame assembly up and away from the fireplace.
5. To reinstall the window frame assembly reverse the process.
Lower Clamps
Window
Window Frame Assembly
Push Clamp Han-
Frame Assembly
Pull Clamp Hook
FP1227
Fig. 36 Remove louvre assembly top.
Glass Panel
Window Frame Assembly Removal
Side Window Frame Assemblies
1. Shut off the gas supply.
2. Allow the fireplace to cool if it has been in operation.
3. Remove the top louvre assembly.
4. Lower the bottom louvre assembly.
5. Release the two clamps along lower edge of the frame by pulling down on clamp handles. (Fig. 37)
6. Tilt lower edge of frame out slightly and lift window frame assembly up and away from the fireplace.
10006326
Fig. 37 Window frame assembly removal.
Location of Lower Retaining Screws
Fig. 38 Retaining screw.
FP1228
FP1445
23
360 DVS Series Direct Vent Fireplaces
Glass Cleaning
It is necessary to periodically clean glass. During start­up, condensation, which is normal, forms on the inside of the glass. This condensation causes lint, dust and other airborne particles to cling to glass surface.
Also initial paint curing may deposit a slight film on the glass. It is therefore recommended glass be cleaned two or three times with a non-ammonia based house­hold cleaner and warm water. The use of fireplace glass cleaner is recommended within the first few weeks of operation.
After the initial cleaning process the glass should be cleaned two or three times during each operating sea­son depending on the environment in the house.
Clean the glass after the first two weeks of operation.
Do not clean the glass when hot.
Do not use an abrasive cleaner.
Do not strike or slam the glass.
Ceramic Refractory Installation
The vertical refractory panels are installed in the unit prior to shipment. For assembly procedures, refer to Figure 39.
1. Unpack the ceramic refractory panels from the car ton.
Handle the refractory material carefully, the panels are fragile.
2. Place the two end floor refractory panels on the base of the fireplace.
3. Place both side panels along the side of the base.
NOTE: 360DVS2 is the only 360DV unit that is fitted
with two (2) end vertical panels, as shown in Figure
39. 360DVSL and 360DVSR units are each fitted with one end vertical panel and two side vertical panel. The 360DVS3 has only one end vertical panel.
Vertical Panels in Place When Shipped
Floor Panels Placed
FP1446
Fig. 39 Ceramic panel installation.
During Installation
-
Log Installation
Refer to Figures 40 and 41 for log location and align­ment.
Because of the log stack design, these instructions can be followed from either side of the fireplace. To follow these instructions, identify the logs by the number cast into the underside.
For correct operation of the fireplace, the logs must be correctly placed in the sequence described below:
1. Unpack the logs from the shipping carton. The logs are fragile; handle them carefully.
Handle and dispose of plastic bags in which logs were shipped in a safe manner. As with all plastics, they are not toys and should be kept away from infants.
2. Remove both sides of the window frame assembly (where applicable).
3. Place the hole located on the underside of the log is to be placed over the center of the grate. The inner end of the log ensures that the bottom hole is located on the pin of the support.
4. Place the square hole located on the underside of the log is to place over the corner leg of the grate. The inner end of the log ensures the bottom holes are located on the pin of the support.
5. Place the square hole fits over the corner leg of the grate. The inner end of this log maintains a recess on the underside, which locates over the knob on the top of the log front left (B121) to secure the inner end in place.
6. Place the the log rests on the grate. The notch at the back of the log locates over the knob on the top of the log rear (B120). The bottom of the log rests on top of the log front left (B121).
7. Place the a step on the outer end, which rests against the prong of the grate. The alternate end rests on the side floor refractory panel.
8. Place the hole on the underside, which rests over the knob on the top of the log rear (B120). The bottom of the log rests against the side floor refractory panel, and the side rests against the last prong of the grate.
9. Place the hole on the underside, which rests over the knob on the top of the log front right (B122). The alternate end rests against the side floor refractory panel and positions between the two (2) prongs of the grate.
log rear (B120) on the grate. The square
log front left (B121) on the grate. The
log front right (B122). Once more, the
log rear left (B123). The bottom back of
log bottom left (B124). The log maintains
log rear right (B125). The log maintains a
log center (B126). The log maintains a
24
10006326
B120
B121
B122
B123
B124
B126
B125
Side of Fireplace
B120
B121
B122
B123
B126
B125
LO
HI
Turn
counterclockwise
to decrease
flame height
Turn clockwise
to increase
flame height
Fig. 40 360DVS log placement.
Side of Fireplace
360DVS Series Direct Vent Fireplaces
Venting Side
LG320
Venting Side
Fig. 41 360DVS log placement.
Lava Rock and Ember Material Placement
Your log set contains Ember Material and two types of Lava Rocks. Set these materials in place after the logs have been installed.
Ember Material (Pt. #51915)
Remove ember material from the bag and separate it into small pieces, then scatter it over burner tiles in a random fashion. Do not pack down ember material; leave it in a ‘fluffy’ state.
Lava Rock (Pt. #10001454)
Remove lav rock material from packaging and spread it over ceramic floor panels outside log stack. Do not
place this lava rock material on burner tiles.
LG321
Flame & Temperature Adjustment
RN/ RP Models
For units equipped with ‘HI/LO’ valves the flame adjust­ment is accomplished by rotating the ‘HI/LO’ adjustment knob located near the center of the gas control valve. (Fig. 42 and Fig. 43)
Fig. 42 Flame adjustment knob for Honeywell valve.
10006326
25
360 DVS Series Direct Vent Fireplaces
L
O
H
I
Turn
counterclockwise
to increase
flame height
Turn clockwise
to decrease
flame height
Fig. 43 Flame adjustment knob for SIT valve.
Flame Characteristics
It is important to periodically perform a visual check of the pilot and burner flames. Compare them to the pictorials illustrated below. (Figs. 45 & 46) If the flame patterns appear abnormal, contact a qualified service provider for service and adjustment.
3/8” - 1/2”
(10 - 13mm)
F584-703
Fig. 45 Correct pilot flame appearance.
26
Fig. 46 Correct log flame appearance.
LG322
LG323
10006326
360 DVS Series Direct Vent Fireplaces
Maintenance
Burner and Burner Compartment
It is important to keep the burner and the burner com­partment clean. At least once per year remove the logs and lava rock/ember material. Vacuum and wipe out the burner compartment. Remove and refit the logs per the instructions in this manual.
Always handle the logs with care as they are fragile and may also be hot if the fire­place has been in use.
FK24/FK12 Fan Assembly
The fan unit requires periodic cleaning. At least once per month in the operating season, open the lower lou­vre panels and wipe or vacuum the area around the fan to remove any build up of dust or lint.
Brass Trim
Clean the brass trim pieces using a soft cloth lightly dampened with lemon oil. Do not use water or house­hold cleaners on any brass components.
Cleaning the
Standing Pilot Control S
The burner and control system consists of:
• burner tube • gas orifice
• pilot assembly • thermopile
• millivolt gas valve
Most of these components may require only an occa­sional checkup and cleaning and some may require ad­justment. If repair is necessary, it should be performed by a qualified technician.
1. Turn off pilot light at gas valve side.
2. Let fireplace cool if it has been running.
3. Remove window frame assembly. (Refer to Window Frame Assembly Removal section)
4. Remove logs.
5. Vacuum burner compartment especially around orifice primary air openings.
6. Visually inspect pilot. Brush or blow away any dust or lint accumulation.
7. Reinstall logs.
8. Ignite pilot; refer to Lighting Instructions.
9. Reinstall window frame assembly.
ystem
To obtain proper operation, it is imperative that the pilot and burner’s flame characteristics are steady, not lifting or floating.
Typically, the top 3/8 – 1/2” (10 – 13 mm) of the thermo pile should be engulfed in the pilot flame. (Page 26, Fig.
46)
To adjust pilot burner (to be done by a qualified service technician):
1. Remove pilot adjustment cap.
2. Adjust pilot screw to provide properly sized flame.
3. Replace pilot adjustment cap.
The primary air shutter is set at factory and should be adjusted, if necessary, only by a qualified service tech­nician.
Cleaning Electronic Ignition System
The Electronic Ignition burner/control system consists of:
• main burner
• gas orifice
• pilot burner
• 24VAC valve with transformer
The process for taking care of Electronic Ignition units is identical to that for taking care of Standing Pilot models.
-
34
10006326
360DVS Series Direct Vent Fireplaces
L
O
H
I
PILOT
ADJ
PILOT
ON
OFF
4a/b
5a/b
6
11
9
11
8
10
7
12
18
24
27
17
2
29
28
22
23
26
21
20
25
19
13
14
3a/b
15a/b
16a/b
31a/b
32
35
33
HI
LO
34a/b
25
36
37
30
1
1a
1b
1c
1d
1e
1f
1g
CFM Corporation reserves the right to make changes in design, materials, specifications, prices and discontinue colors and products at any time, without notice.
360DVS Series
10006326
35
360 DVS Series Direct Vent Fireplaces
360DVS Series (Items marked ‘*’ are not shown in the parts illustration)
Ref. Description 360DVS2 360DVS3 360DVSL 360DVSR
1. Log Set (complete) 10006350 10006350 10006350 10006350
1a. Log - Rear (B120) 10006315 10006315 10006315 10006315 1b. Log - Front Left (B121) 10006316 10006316 10006316 10006316 1c. Log - Front Right (B122) 10006317 10006317 10006317 10006317 1d. Log - Rear Left (B123) 10006318 10006318 10006318 10006318 1e. Log - Bottom Left (B124) 10006319 10006319 10006319 10006319 1f. Log - Rear Right (B125) 10006320 10006320 10006320 10006320 1g. Log - Center Right (B126) 10006321 10006321 10006321 10006321
2. Grate Assembly 10006014 10006014 10006014 10006014
3a. Burner Housing Assembly, Nat. 10006148 10006148 10006148 10006148 3b. Burner Housing Assembly, Prop. 10006299 10006299 10006299 10006299 * Ceramic Burner Tile 10002165 10002165 10002165 10002165 * Orifice/s, Main burner (Nat.) Refer to the rating plate for specific orifice information * Orifice/s, Main Burner (Prop.) Refer to the rating plate for specific orifice information 4a. Pilot assembly PSE (Nat.) 10001741 10001741 10001741 10001741 4b. Pilot assembly PSE (Prop.) 10001742 10001742 10001742 10001742 5a. Pilot assembly SIT Top Conv. (Nat.) 10002264 10002264 10002264 10002264 5b. Pilot assembly SIT Top Conv. (Prop.) 10002265 10002265 10002265 10002265
6. Pilot, PSE (with cable & electrode) 10001824 10001824 10001824 10001824
7. Pilot SIT Top Convertible 10002266 10002266 10002266 10002266
8. Pilot Hood, SIT Top Convertible 10002385 10002385 10002385 10002385
* Orifice, Pilot PSE (Nat.) 10001822 10001822 10001822 10001822 * Orifice, Pilot PSE (Prop.) 10001823 10001823 10001823 10001823 * Orifice, Pilot SIT Top convertible (Nat.) 10002268 10002268 10002268 10002268 * Orifice, Pilot SIT Top conv. (Prop.) 10002269 10002269 10002269 10002269 * Pilot tube & fittings (Top convertible) 10001296 10001296 10001296 10001296 * Manifold tube & fittings 10002492 10002492 10002492 10002492 * Flexible Gas Line (18”) with fittings 20002500 20002500 20002500 20002500
9. Thermocouple, PSE 10001828 10001828 10001828 10001828
10. Thermocouple, SIT Top Convertible 53373 53373 53373 53373
11. Thermopile 51827 51827 51827 51827
12. Ignitor electrode (with cable), SIT 10001297 10001297 10001297 10001297
13. Ignitor (Piezo), SIT 820 valve 52464 52464 52464 52464
14. Ignitor (Piezo), Honeywell Valve 20000062 20000062 20000062 20000062
15a. Valve, SIT 820 (Nat.) 52677 52677 52677 52677 15b. Valve, SIT 820 (Prop.) 52678 52678 52678 52678 16a. Valve, Honeywell (Nat.) 10001782 10001782 10001782 10001782 16b. Valve, Honeywell (Prop.) 10001759 10001759 10001759 10001759
17. Fan & Bracket FK12 (optional) ZA1110 ZA1110 ZA1110 ZA1110
18. Fan & Bracket FK24 (optional) 54103 54103 54103 54103
* Temperature Sensor (optional) 51704 51704 51704 51704 * Fan Speed Control (optional) 51738 51738 51738 51738 * Fan Speed Control Knob (optional) 51882 51882 51882 51882 * Electric Cord 51865 51865 51865 51865
19. Remote ON/OFF switch (RN/RP models) 51842 51842 51842 51842
* Wiring Harness (remote switch) 55923 55923 55923 55923 * Remote ON/OFF Switch Kit (incls. bracket) 53875 53875 53875 53875
20. Louvre Assembly, side top. 10000039 10000039 10000039 10000039
36
10006326
360DVS Series Direct Vent Fireplaces
360DVS Series (continued) (Items marked ‘*’ are not shown in the parts illustration)
Ref. Description 360DVS2 360DVS3 360DVSL 360DVSR
21. Louvre Assembly, side bottom 10000040 10000040 10000040 10000040
22. Louvre Assembly, end top N/A 10002411 10002411 10002411
23. Louvre Assembly, end bottom N/A 10002412 10002412 10002412
24. Hinge, lower louvre assemblies 52356 52356 52356 52356
25. Trim Window Top/Bottom w/Magnets PB 57483 57483 57483 57483
26. Trim Window Top/Bottom w/Magnets PB n/a 10006197 10006197 10006197 * Window Frame Assembly, side 10002483 10002483 10002483 10002483 * Window Frame Assembly, end N/A 10002484 10002484 10002484 * Window Glass (complete with gasket), side 10002533 10002533 10002533 10002533 * Window Glass (complete with gasket), end N/A 10002534 10002534 10002534 * Gasket Kit (glass replacement, 1x11’ length) 57317 57317 57317 57317
27. Window Frame Clamp 54174 54174 54174 54174
28. Refractory Lining (vertical end walls) 10006254 10006254 10006254 10006254
29. Refractory Lining (vertical side wall) N/A N/A 10006285 10006285
30. CR Bottom Kit w/out Rear 10006257 10006257 10006257 10006257 * Air Inlet Cover Plate Assembly 10006174 10006174 10006174 10006174 * Air Inlet Cover Plate Gasket 10006171 10006171 10006174 10006171 * Flue Pipe Plate Assembly 10002554 10002554 10002554 10002554 * FluePipe Plate Gasket 10002237 10002237 10002237 1000223 * Flue Cover Plate 10002298 10002298 10002298 10002298 * Flue Cover Plate Gasket 10002233 10002233 10002233 10002233 * Relief Plate (with gasket) 10002429 10002429 10002429 10002429 * Deflector, Cabinet Top Short N/A 10002260 10002260 10002260 * Corner Post (left) N/A 10006190 10006190 10006190 * Corner Post (right) N/A 10006191 10006191 10006191 * Corner Post Mounting Bracket N/A 10006195 10006195 10006195 * Deflector Cabinet Top Long 54364 54364 54364 54364 31a. Pilot Assembly SIT Top Convertible EN 10002387 10002387 10002387 10002387 31b. Pilot Assembly SIT Top Convertible EP 10002388 10002388 10002388 10002388
32. Ignitor Electrode SIT EN/EP 52465 52465 52465 52465
33. Cable Ignitor SIT EN/EP 10000696 10000696 10000696 10000696 34a. SIT822 Gas Control Valve EN 57884 57884 57884 57884 34b. SIT822 Gas Control Valve EP 57883 57883 57883 57883
35. Sensing Electrode (w/ Cable) EN/EP 57885 57885 57885 57885
36. Transformer 24V EN/EP 7522409 7522409 7522409 7522409
37. Ignition Module Honeywell EP 20000005 20000005 20000005 20000005 * Wire Harness Honeywell EN/EP 10001979 10001979 10001979 10001979
10006326
37
360DVS Series Direct Vent Fireplaces
LIMITED LIFETIME WARRANTY
PRODUCT COVERED BY THIS WARRANTY
All Vermont Castings gas stoves, gas inserts, and gas fireplaces, and all Majestic brand gas fireplaces equipped with an Insta-Flame Ceramic Burner, or standard steel tube burner.
BASIC WARRANTY
CFM Corporation (hereinafter referred to collectively as the Company)
warrants that your new Vermont Castings or Majestic Gas Fireplace/ Stove is free from manufacturing and material defects for a period of one year from the date of purchase, subject to the following conditions and limitations.
EXTENDED LIFETIME WARRANTY
The heat exchanger, where applicable, and combustion chamber
of every Vermont Castings or Majestic gas product is warranted for life against through wall perforation. All appliances equipped with an Insta-Flame Ceramic Burner have limited lifetime coverage on the ceramic burner plaque. Warrantees are made to the original owner subject to proof of purchase and the conditions and limitations listed on this Warranty Document
COMPONENT WARRANTY
CAST IRON: All external and internal cast iron parts are warranted for a period of three years.
Note: On porcelain enamel finished external parts and accessories The
Company offers no Warranty on chipping of enamel surfaces. Inspect all product prior to accepting it for any damage to the enamel.
The salt air environment of coastal areas or a high humidity environment
can be corrosive to the porcelain enamel finish. These conditions can cause rusting of the cast iron beneath the porcelain enamel finish, which will cause the finish to flake off.
Dye lot variations with replacement parts and/or accessories can occur
and are not covered by warranty.
GLASS DOORS: Glass doors are covered for a period of one year. Glass doors are not warranted for breakage due to misuse or accident. Glass doors are not covered for discoloration or burned in stains due to environmental issues, or improper cleaning and maintenance.
BRASS PLATED PARTS AND ACCESSORIES: Brass parts should be cleaned with Lemon oil only. mix and masonry cleaners may corrode the brass finish. The Company will not be responsible for, nor will it warrant any brass parts which are damaged by external chemicals or down draft conditions.
GAS VALVES: Gas valves are covered for a period of one year
ELECTRONIC AND MECHANICAL COMPONENTS: Electronic and mechanical components of the burner assembly are covered for one year. All steel tube burners are warranted for one year.
ACCESSORIES: Unless otherwise noted all components and CFM Corporation company supplied accessories are covered for a period of one year.
CONDITIONS AND LIMITATIONS
• This new Vermont Castings or Majestic product must be installed by a competent, authorized, service contractor. A licensed technician, as prescribed by the local jurisdiction must perform any installation/service work. It must be installed and operated at all times in accordance with the Installation and Operating instructions furnished with the product. Any alteration, willful abuse, accident, or misuse of the product shall nullify this warranty.
• This warranty is non-transferable, and is made to the original owner, provided that the purchase was made through an authorized supplier of the Company.
• The customer must pay for any Authorized Dealer in-home travel fees or service charges for in-home repair work. It is the dealers option whether the repair work will be done in the customer’s home or in the dealer’s shop.
• If upon inspection, the damage is found to be the fault of the manufacturer, repairs will be authorized at no charge to the customer parts and/or labor.
Brass cleaners cannot be used. Mortar
10006326
• Any part and/or component replaced under the provisions of this warranty is covered for six months or the remainder of the original warranty, whichever is longest.
• This warranty is limited to the repair of or replacement of part(s) found to be defective in material or workmanship, provided that such part(s) have been subjected to normal conditions of use and service, after said defect is confirmed by the Company’s inspection.
• The company may, at its discretion, fully discharge all obligations with respect to this warranty by refunding the wholesale price of the defective part(s)
• Any installation, labor, construction, transportation, or other related costs/expenses arising from defective part(s), repair, replacement, or otherwise of same, will not be covered by this warranty, nor shall the Company assume responsibility for same. Further, the Company will not be responsible for any incidental, indirect, or consequential damages except as provided by law.
SOME STATES DO NOT ALLOW FOR THE EXCLUSION OR LIMITATIONS OF INCIDENTAL AND CONSEQUENTIAL DAMAGES OR LIMITATIONS ON HOW LONG AN IMPLIED WARRANTY LASTS, SO THE ABOVE LIMITATIONS MAY NOT APPLY TO YOUR CIRCUMSTANCES. THIS WARRANTY GIVES YOU SPECIFIC RIGHTS AND YOU MAY HAVE OTHER RIGHTS WHICH VARY FROM STATE TO STATE.
• All other warranties-expressed or implied- with respect to the product, its components and accessories, or any obligations/liabilities on the part of the Company are hereby expressly excluded.
• The Company neither assumes, nor authorizes any third party to assume on its behalf, any other liabilities with respect to the sale of this Vermont Castings or Majestic product
• The warranties as outlined within this document do not apply to chimney components or other non CFM Corporation accessories used in conjunction with the installation of this product..
• Damage to the unit while in transit is not covered by this warranty but is subject to claim against the common carrier. Contact the dealer from whom you purchased your fireplace/stove (do not operate the appliance as this might negate the ability to process the claim with the carrier).
• The Company will not be responsible for: a) Down drafts or spillage caused by environmental conditions such
as near-by trees, buildings, roof tops, hills, or mountains.
b) Inadequate ventilation or negative air pressure caused by
mechanical systems such as furnaces, fans, clothes dryers, etc.
• This warranty is void if: a) The fireplace has been operated in atmospheres contaminated
by chlorine, fluorine, or other damaging chemicals.
b) The fireplace has been subjected to prolonged periods of dampness
or condensation
c) Any damages to the fireplace, combustion chamber, heat exchanger
or other components due to water, or weather damage, which is the result of but not limited to, improper chimney/venting installation.
d) Any alteration, willful abuse, accident, or misuse of the product
has occurred.
IF WARRANTY SERVICE IS NEEDED…
1) Contact your supplier. Make sure you have your warranty, your sales receipt, and the model/serial number of your CFM Corporation product.
2) D O N OT ATTEMPT TO DO ANY SE RVI CE W ORK YOURSELF.
43
Efficiency Ratings
Model EnerGuide Ratings Steady State (%) D.O.E. Fireplace Efficiency (%) Fan-OFF Fan-ON (AFUE%)
360DVS2RN 62.4 83 84 65 360DVS2RP 62.4 83 84 65 360DVS2EN 62.4 83 84 65 360DVS2EP 62.4 83 84 65 360DVS3RN 62.4 83 84 65 360DVS3RP 62.4 83 84 65 360DVS3EN 62.4 83 84 65 360DVS3EP 62.4 83 84 65 360DVSLRN 62.4 83 84 65 306DVSLRP 62.4 83 84 65 360DVSLEN 62.4 83 84 65 360DVSLEP 62.4 83 84 65 360DVSRRN 62.4 83 84 65 360DVSRRP 62.4 83 84 65 360DVSREN 62.4 83 84 65 360DVSREP 62.4 83 84 65
CFM Corporation
2695 Meadowvale Blvd. • Mississauga, Ontario, Canada L5N 8A3
800-668-5323 • www.cfmcorp.com
Loading...