Vermason 222700, 222690 Installation And Operating Instructions Manual

TECHNICAL BULLETIN TB-7535
Dual Independent Footwear and Wrist Strap Tester Installation and Operating Instructions
Daily checks, clause 9.6.2 Wrist strap) “Where toe and heel straps are used as ESD
Tester
Description
The Vermason Dual Independent Footwear and Wrist Strap Tester is designed to test personal grounding devices, wrist strap and ESD footwear, to satisfy the requirements and the recommendations of EN 61340-5-1.
Use the Vermason Dual Independent Footwear and Wrist Strap Tester to fulfill the requirements of EN 61340-5-1. Per EN61340-5-1 Table 1 ESD protective item requirements, the Resistance to be for Wrist Strap as worn to be 1M = 1 X 10E6 ohms </= Rp </= 3.5 x 10E7 ohms.
“When footwear/floor systems are used as primary means of grounding personnel, the resistance of the combination shall be determined by the ESD co-ordinator, and is recommended to be 1M = 1 X 10E6 ohms and 3.5 x 10E7 ohms” (EN 61340-5-1 Table 1 ESD protective item requirements NOTE
2).
footwear, once these are worn outside the EPA (ESD protected area, particularly on carpets, they are likely to accumulate fluff and become ineffective; this requires that they be checked or replaced on every visit to the EPA. …When ESD footwear is used, it should be noted that ESD footwear alone cannot achieve protection, but needs to be used in conjunction with a suitable ESD floor.” (EN 61340-5-2 clause 5.2.8 Footwear)
“All wearers shall check that their heel and toe straps meet requirements. The check shall be made before entering the EPA.” (EN 61340-5-1 Daily checks, clause 9.6.3 Non-permanent footwear)
Packaging
1 Dual Independent Footwear and Wrist Strap Tester 1 Dual Foot Plate 1 Stereo Plug to Stereo Plug Cord 1 Banana Plug to Ring Terminal
Cord
1 Certificate of Calibration
Installation
The resistance limits for footwear and wrist strap tests are controlled by the DIP switches located on the left-side of the tester (see Figure 2). See the following tables for the DIP switch settings and their corresponding
test values.
Footwear Rresistance
DIP switches 1 and 2 control the “HIGH” test limit.
HIGH Limit Switch 1 Switch 2 Resistance
ON ON 10 Megohms (1 X 10E7)
OFF OFF 35 Megohm (3.5 X 10E7)*
ON OFF 100 Megohm (1 X 10E8)
OFF ON 1 Gigohm (1 X 10E9)
LOW Limit Switch 3 Switch 4 Resistance
ON OFF 100 Kilohms (1 X 10E5)
OFF ON 1 Megohm (1 X 10E6 ohms)*
* Default Setting
NOTE: At 1 Gigohm high limit resistance, a dirty foot plate could result in a false pass. Be sure to keep the foot plate clean when using this setting.
Wrist Strap Resistance
DIP switches 5 and 6 control the “HIGH” test limit.
* Default Europe Setting
DIP switch 5 must be ON (default setting) for the wrist strap test to be active. If the wrist strap test is disabled by DIP switch 5 being OFF, the 3 LEDs for this test will remain OFF at all times.
The “LOW” limit for the wrist strap test is set to 1 Megohms and cannot be changed by the user.
Made in America
DIP switches 3 and 4 control the “LOW” test limit.
HIGH Limit Switch 5 Switch 6 Resistance
OFF OFF Wrist Strap Test Disabled
ON OFF 35 Megohm (3.5 X 10E7)*
ON ON 10 Megohm (1 X 10E7)
“Wrist straps shall be checked before use. Each check shall be made with the wrist band worn in contact with the wearer’s skin and with the ground cord attached to the appropriate tester.” (EN 61340-5-1 clause 9.6
UNIT C, 4TH DIMENSION, FOURTH AVENUE, LETCHWORTH, HERTS, SG6 2TD UK
Phone: 0044 (0) 1462 672005, Fax: 0044 (0) 1462 670440 • e-mail: Service@Vermason.co.uk, Internet: Vermason.co.uk
TB-7535 August 2009 Page 1 of 3 © 2009 Vermason
* Default Setting
Audio Adjustment
Foot Plate Jack
Wrist Strap
Relay
Ground Jack
FRONT VIEW
DIP Switch Power Jack
SIDE VIEW
Data Output
(for SmartLog X3)
TOP VIEW
Figure 2. Dual Independent Footwear and Wrist Strap Tester side views
Installing The Tester And Foot Plate
Mount the tester at the desired location using the four mounting holes in the corners of the yellow mounting plate. Set the foot plate below the tester.
Insert one end of the Stereo Plug to Stereo Plug cord into the stereo jack located at the bottom of the tester (see Figure 2). Insert the other end of the cord into the stereo jack at the back of the foot plate.
Insert the banana plug end of the Banana Plug to Ring Terminal cord into the ground jack located at the bottom of the tester (see Figure 2). Connect the ring terminal end of the cord to earth ground. This connection will remove any static charge from the user before the test. NOTE: Failure to correctly ground the tester may result in damage not covered under warranty.
Insert the power supply plug into the power jack located on the left-side of the tester (see Figure 2). Plug the power supply into an appropriate power outlet.
Phone: 0044 (0) 1462 672005, Fax: 0044 (0) 1462 670440 • e-mail: Service@Vermason.co.uk, Internet: Vermason.co.uk
UNIT C, 4TH DIMENSION, FOURTH AVENUE, LETCHWORTH, HERTS, SG6 2TD UK
Single Wire Jack
Test Push Button
1 2 3 1 & 2 = Normally closed Relay 2 & 3 = Normally open 1 A @ 30 VDC (Rating)
Dual-Wire Jack
Right FootLeft Foot
Figure 3. Dual Independent Footwear and Wrist Strap Tester features and components
Relay Terminal
A relay with both “normally open” and “normally closed” contacts is included for your convenience. Going from left to right, the terminal block on the bottom of the tester has terminals for “normally closed,” “common,” and “normally open” (see Figure
3). The relay can be used for opening an electric lock to an ESD sensitive area. The maximum contact rating is: 1A@30VDC.
Operation
Upon power up, the alarm will sound and all of the LEDs for the activated tests will be illuminated. The tester is now ready for use.
Pushing the touch plate on the front panel starts the test. During the test all LEDs will turn off to indicate that a test is in progress. The touch plate must remain depressed until the test results are displayed. Depending on the configuration of the tester, the test could require up to three (3) seconds.
The resistance is checked from the touch plate to the corresponding foot plate for each foot and from the touch plate to the wrist strap connector jacks through the operator. A wrist strap must be plugged into the appropriate jack before the touch plate is depressed if the wrist strap option is activated.
The Dual Independent Footwear and Wrist Strap Tester can test both single and dual wrist straps. Single-wire wrist straps are to be plugged into the banana jack labeled “SINGLE-WIRE” located on the front panel of the tester (see Figure 3). Dual-wire wrist straps are to be plugged into the phono jack labeled “DUAL-WIRE” located on the front panel of the tester (see Figure 3). The tester automatically determines what type of wrist strap is being tested.
The LED(s) will turn off while the test is in progress. The test results for each foot and wrist strap will then be displayed for approximately three (3) seconds. If all tests result in a “PASS” condition, the internal relay will activate.
If any of the test results fail “HIGH” or “LOW,” an audible alarm will sound. The LED(s) indicating the failed test will be displayed for approximately three (3) seconds, and the internal relay will not activate.
Specifications
Rated tester voltage:
12 VDC, 600 mA, (2.5 mm connector - center positive)
Relay contact rating:
1 A @ 30 VDC max
Temperature range:
41°F - 104°F (5°C - 40°C)
Operating conditions:
Indoor use only at altitudes less than 6500 ft. (2 km).
Maximum relative humidity of 80% up to 88°F (31°C) decreasing linearly to 50% @ 104°F (40°C).
Pollution degree:
2 per IEC 644
Calibration
The Vermason Dual Independent Footwear and Wrist Strap Tester is calibrated to standards traceable to NIST. Frequency of recalibratrion should be based on the critical nature of those ESD sensitive items handled and the risk of failure for the ESD protective equipment and materials.
TB-7535 Page 2 of 3 © 2009 Vermason
Loading...
+ 1 hidden pages