![](/html/8f/8f5c/8f5c47dd3f94d9a08bcabf5754a9b77ca067b52ef84e079e8fd00201025b0e64/bg1.png)
Setpoint Devices | Room Temperature Controller
VT8300 SERIES
Network Ready, BACnet MS/TP,
and Wireless Models Available
VT8300
Smart energy management has never been easier than with the VT8300
Series Fan Coil Room Controllers. Designed for new construction
and retrofit projects, the Room Controllers dramatically decrease
project delivery costs by reducing installation, configuration and
commissioning time. No complex software or tools are required
to customize functionality in order to meet your applications
requirements. The Room Controllers provide all the advanced features
and monitoring functions required by modern building automation
systems in a simple compact enclosure.
The Room Controllers are specifically designed to provide exceptional
temperature control of multi-speed Fan Coil units. All models can
provide advanced occupancy routines and automatic energy savings
during occupied periods without sacrificing occupant comfort.
When compared to traditional building automation controllers, the
VT8300 series Fan Coil Room Controllers provide unmatched return on
investment.
SPECIFICATIONS
Thermostat Power
Requirements
Operating Conditions 0 to 50 °C (32 to 122 °F); 0 to 95% RH
Storage Conditions -30 to 50 °C (-22 to 122 °F); 0 to 95% RH
Temperature Sensor Local 10k NTC type 2 thermistor
Temp. Sensor Resolution ± 0.1 °C (± 0.2 °F)
Temp. Control Accuracy ±0.5 °C (±0.9 °F ) @ 21 °C (70 °F) typical
Humidity Sensor and
Calibration
Humidity Sensor Precision Reading range from 10 to 90% RH non-
Humidity Sensor Stability <1.0% annual drift (typical)
Dehumidification Setpoint
Range
Occupied and Unoccupied
Setpoint Range Cooling
7.0 Vdc ± 10%, 2.4 W min.; 24 Vac ± 15%; 50/60
Hz; 6 to 100 VA (rating max.)
non-condensing
non-condensing
calibrated
Single point calibrated bulk polymer sensor
condensing 10 to 20% precision is 10%; 20 to
80% precision is 5%; 80 to 90% precision is 10%
30 to 95% RH
12 to 38 °C (54 to 100 °F)
Commercial and
hospitality
Suitable for both commercial and
hospitality markets and systems
Digital touch
screen
Customizable color digital touch
screen interface with
multi-language support
7-day occupancy
scheduling
2 to 4 events
Occupied and Unoccupied
Setpoint Range Heating
Room and Outdoor Air
Temperature Display
Proportional Band for Room
Temperature Range Control
Binary Inputs Dry contact across terminal BI1, BI2 and UI3
Economizer Analog Output
Rating
Economizer Analog Output
Accuracy
Wire Gauge 18 gauge maximum, 22 gauge recommended
WARRANTY
Limited Warranty 18 months
AGENCY APPROVALS
*
*The CE mark indicates RoHS2 compliance.
UL: 61010-1 (2nd edition); CSA: 61010-1 (3rd edition); IEC: 61010-1 (3rd edition), EN 60950-1:
2006A2: 2013, UL 873, CSA 22.2 No. 24-93; 61326-1:2005; FCC: Part 15, Subpart B; CE: EMC
Directive 2004/108/EC (European Union); wireless models: FCC Part 15, Subpart C; R&TTE
Directive 1999/5/EC; EN: 301 489-1 V1.9.2, 301 328 V1.8.1; RSS 210
5 to 32 °C (40 to 90 °F)
-40 to 50 °C (-40 to 122 °F)
Cooling & Heating: 1.8 °C (3.2 °F )
to Scom
0 to 10 Vdc into 2k Ω resistance min.
±3% typical
Optional
humidity sensor
Humidity sensor with on-board
humidification strategy (optional)
Optional cover
Optional occupancy sensor cover
Advanced
occupancy
functions
For commercial and lodging
applications
TM
![](/html/8f/8f5c/8f5c47dd3f94d9a08bcabf5754a9b77ca067b52ef84e079e8fd00201025b0e64/bg2.png)
indow Switches
(U026-0006, U026-0007)
Terminal Equipment Controller
3-Speed FanCooling Coil Heating Coil
Cooling Only VAVHeating Coil
Setpoint Devices | VT8300 SeriesSetpoint Devices | Room Temperature Controller
TYPICAL ZONE CONTROLLER APPLICATION
Wiring Examples
Supply Air
Baseboard Reheat
BACnet MS/TP
VT8300 as a
Zone Controller
TYPICAL LOW VOLTAGE FAN COIL APPLICATION
Wiring Examples
H
C
Standard wired BACnet MS/TP
communication and optional
U026-0005 ZigBee Pro
communication module upgrade
To Diffuser
DIMENSIONAL DRAWING
4.7”
(120 mm)
3.4”
(86 mm)
SELECTABLE COLOR SCHEMES
AND LANGUAGES
1.0”
(25 mm)
Return Air Supply Air
Standard wired BACnet MS/TP
communication and optional
U026-0005 ZigBee Pro
communication module
upgrade
ORDERING INFORMATION
MANUF. PART # ORDERING # DESCRIPTION
VT8300U5000B U026-0001 Fancoil Control, Low Voltage, BACnet
VT8350U5000B U026-0002 Fancoil Control, Low Voltage, RH, BACnet
VT8300U5500B U026-0003 Fancoil Control, Low Voltage, PIR, BACnet
VT8350U5500B U026-0004 Fancoil Control, Low Voltage, RH, PIR, BACnet
VCM8000V5000P U026-0005 Wireless Communication Card - ZigBee Pro
VWA5000D5000W U026-0006 Wireless Door Switch Accessory
VWA5000W5000W U026-0007 Wireless Window Switch Accessory
HQ0005799.C 0117
Filter
Status
Switch
Existing Field Wires
VT8300 Low Voltage Fan Coil
Fan
Status
Switch
TM
Optional Wireless Accessories
Door & W
Dark grey / English HMI
White / Chinese HMI
Blue / French HMI
Green / English HMIGrey / Spanish HMI