Setpoint Devices | Communicating Thermostats:
Analog or Floating Outputs, Zone Control
VT7200 SERIES
BACnet, Echelon, and Wireless
Models Available
VT7200C5000 VT7200C5500
The VT7200C5x00 Series features a backlit LCD display with
dedicated function menu keys for simple operation. Accurate
temperature control is achieved using the PI proportional control
algorithm. Models have two 3-point floating outputs (can be set for On/
Off). In addition, remote room sensing is available. All models contain an
auxiliary contact that can be used to control lighting or auxiliary reheat.
All devices are also available with Echelon, BACnet MS/TP, or wireless
network adapters.
Advanced
occupancy
functions
Advanced occupancy functions
through the network or smart
local occupancy sensing
Auxiliary output
Can be used for lighting or
reheating
Pre-configured
sequences
Pre-configured sequences of
operation…one model meets
more applications and reduces
project delivery cost
APPLICATIONS
• Heating/Cooling valves
• Electric duct heaters
Minimize
parameter
tampering
Unique local configuration utility
Lockable keypad
Tamper resistant, no need for
thermostat guards
Configurable
inputs
Three configurable inputs for
added functionality
• Changeover sensors
SPECIFICATIONS
Thermostat Power
Requirements
Operating Conditions 0 to 50 °C (32 to 122 °F); 0 to 95% RH
Storage Conditions -30 to 50 °C (-22 to 122 °F); 0 to 95% RH
Temperature Sensor Local 10k NTC thermistor
Resolution ± 0.1 °C (± 0.2 °F)
Control Accuracy Temp. ±0.5 °C (±0.9 °F ) @ 21 °C (70 °F) typical,
Occupied and Unoccupied
Setpoint Range Cooling
Occupied and Unoccupied
Setpoint Range Heating
Room and Outdoor Air
Temperature Display
Proportional Band for Room
Temperature Range Control
Binary Inputs Dry contact across terminal BI1, BI2 & UI3
Outputs Rating Triac output: 30 Vac, 1 A max., 3 A in-rush;
19 to 30 Vac; 50 or 60 Hz; 2 VA Class 2
non-condensing
non-condensing
calibrated
12 to 38 °C (54 to 100 °F)
4.5 to 32 °C (40 to 90 °F)
-40 to 50 °C (-40 to 122 °F)
Cooling & Heating: 1.8 °C (3.2 °F )
to Scom
Analog: 0 to 10 Vdc into 2k Ω resistance min.
Economizer Analog Output
Rating
Economizer Analog Output
Accuracy
Wire Gauge 18 gauge maximum, 22 gauge recommended
Dimensions 4.94” x 3.38” x 1.13”
Approximate Shipping
Weight
WARRANTY
Limited Warranty 2 years
AGENCY APPROVALS
*
*The CE mark indicates RoHS2 compliance. Please refer to the CE Declaration of
Conformity for additional details.
UL: 873 (US) and CSA C22.2 No. 24 (Canada), File E27734 with CCN , XAPX (US) and XAPX7
(Canada)
FCC: Compliant to CFR 47, Part 15, Subpart B, Class A (US)
Industry Canada: ICES-003 (Canada)
CE: EMC Direc tive 2004/108/EC (European Union)
0 to 10 Vdc into 2k Ω resistance min.
±3% typical
0.75 lb (0.34 kg)
TM
HQ0005797.C 0117
24 Vac ON/OFF relay (4 C.P.H.)
or 24 Vac PWM ( 10 seconds )
11 10 4
4 7
4
24 V
5
Com.
6
BO57BO5
BO3
Ui3
Bi2
Scom
RS
Bi1
BO18BO4
BO2
Viconics
R800
series
SSR
Triacs
24 Vac
Transformer
Heating/
Cooling
Valve
15 13
Changeover
Sensor
15 16141312119 10
=
=
= = =
24 Vac ON/OFF relay (4 C.P.H.)
or 24 Vac PWM ( 10 seconds )
10 4 9
4 7
4
24 V
5
Com.
6
BO57BO58BO3
15 16
Ui314Bi213Scom12RS11Bi1
9
BO110BO4
BO2
11
Cooling
valve
Heating
valve
Viconics
R800
series
SSR
Triacs
24 Vac
Transformer
8 4
=
=
= = =
24 Vac ON/OFF relay (4 C.P.H.)
or 24 Vac PWM ( 10 seconds )
8 44 5 5
4 7
4
24 V
5
Com.
6
BO57BO5
15
Ui314Bi213Scom12RS11Bi1
9
AO1
108
AO2
0 to 10
Vdc
9
Cooling
valve
Heating
valve
Viconics
R800
series
SSR
Triacs
24 Vac
Transformer
0 to 10
Vdc
24 Vac ON/OFF relay (4 C.P.H.)
or 24 Vac PWM (10 seconds )
9 4 5
4 7
4
24 V
5
Com.
6
BO57BO5
15
Ui314Bi213Scom12RS11Bi1
9
AO1
108
AO2
0 to 10
Vdc
Viconics
R800
series
SSR
Triacs
24 Vac
Transformer
Heating/
Cooling
Valve
15 13
Changeover
Sensor
Setpoint Devices | VT7200 Series
TYPICAL 4-PIPE APPLICATION
Wiring Examples
* Use for heating and cooling valves and electric duct heaters.
TYPICAL 2-PIPE APPLICATION
Wiring Examples
TYPICAL 4-PIPE APPLICATION
Wiring Examples
* Use for heating and cooling valves and electric duct heaters.
TYPICAL 2-PIPE APPLICATION
Wiring Examples
* Use for heating and cooling valves, electric duct heaters, and changeover sensors.
ORDERING INFORMATION
MANUF. PART # ORDER # DESCRIPTION COMM .
VT7200C5000 U008-0001
VT7200C5000B U008-0002 BACnet (MS/TP)
VT7200C5000E U008-0003 Echelon
VT7200C5000W U008-0004 Wireless (Zigbee)
VT7200C5500 U008-0005
VT7200C5500B U008-0006 BACnet (MS/TP)
VT7200C5500E U008-0007 Echelon
VT7200C5500W U008-0008 Wireless (Zigbee)
VT7200F5000 U008-0009
VT7200F5000B U008-0010 BACnet (MS/TP)
VT7200F5000E U008-0011 Echelon
VT7200F5000W U008-0012 Wireless (Zigbee)
VT7200F5500 U008-0013
VT7200F5500B U008-0014 BACnet (MS/TP)
VT7200F5500E U008-0015 Echelon
VT7200F5500W U008-0016 Wireless (Zigbee)
HQ0005797.C 011
Zone Thermostat with
2 Floating + 1 Digital;
PIR ready
(PIR cover not included)
Zone Thermostat with
2 Floating + 1 Digital;
PIR factory-equipped
Zone Thermostat with
2 Analog + 1 Digital;
PIR ready
(PIR cover not included)
Zone Thermostat with
2 Analog + 1 Digital;
PIR factory-equipped
TM
Stand alone
Stand alone
Stand alone
Stand alone
DIMENSIONAL DRAWING
4.9”
(125 mm)
(28 mm)
3.4”
(87 mm)
1.1”
1.25”
(32 mm)
1.5”
(37 mm)