Veris Industries Victory 321, Victory 421 Data Sheet

E150462
Relays | Enclosed Victory Relays: 20 A DPST with HOA Switch
VICTORY 321 & 421
HOA Switch Provides Local Control
V321
V421
Cover conceals HOA switch
The Victory 321 and 421 DPST power duty enclosed relays combine an industrial strength relay with installation flexibility. Use the nipple mount to attach to any enclosure. One coil input controls the state of two power rated contacts for simultaneous control of two devices or both poles of a single phase load. Each output is enabled with a Hand­Off-Auto switch for local control. The Victory series does not require a dedicated field enclosure, so it is ideal for retrofit projects. Field­selectable high and low voltage coil inputs provide on-site versatility.
SPECIFICATIONS
Operating Temp. Range -40 to 40 °C (-40 to 104 °F)
Operating Humidity Range 10 to 90% RH non-condensing
Expected Relay Life Electrical (@ rated current) 100,000 cycles;
Mechanical (unpowered) 10,000,000 cycles
Relay Status LED ON=energized
Insulation Class 277 Vac RMS
WIRE SPECIFICATIONS
Lead Length 14” (356 mm) min.
Coil: 18 AWG; Contacts: 12 AWG; HOA monitor wires: 16 AWG
WARRANTY
Limited Warranty 5 years
AGENCY APPROVALS
Agency Approvals UL 508
Nipple mount
Can be mounted to any electrical enclosure, easing installation
Versatile ratings
Versatile coil and contact ratings minimize the number of models to choose
Protective cover
Conceals and protects the HOA switch, reducing the likelihood of tampering
APPLICATIONS
• Command contactors
• Control motors
• Isolation
TYPICAL COIL PERFORMANCE
Voltage Coil Current
24 V 120 mA 64 mA
120 V 84 mA
277 V 102 mA
CONTACT RATINGS
Resistive 20 A @ 240 Vac
8 A @ 28 Vac
14 A @ 14 Vac
Motor 120 Vac, 1 HP
Flexible wire
Flexible tinned stranded wire… fits easily in tight spaces and provides secure connections to wire nuts
UL508 Listed
Designed and listed for field installation…makes electrical inspection a snap
Sleek enclosure
Reduces the need for panel space
• Device interlocking
• Relay logic
• Sense voltages for alarm conditions
AC DC
TM
HQ0001846.F 0117
4.0"
Common
CONTACT OUTPUT #1 N.O.
CONTROL SYSTEM INPUT
wht/y
Relays | Victory 321 & 421
NIPPLE MOUNT DIRECTLY TO A PANEL
Wiring Diagram
To Load
CONTACTS
CONTROL
COIL
PANEL
To Controls
NIPPLE MOUNT TO ANY 2X OR 4X ELECTRIC AL BOX
Wiring Diagram
To Load
Contacts
CONTACTS
To Controls
To Load
L
I
O
C
Wire Nut
DIMENSIONAL DRAWING
(103 mm)
3.8"
(97 mm)
3/4" NPT Nipple
2.3"
(59 mm)
2.0"
(52 mm)
2.5"
(64 mm)
WIRE COLOR CODES
HI (421)
wht/brown
b
r
own
208 to 277 Vac
HI (321)
wht/black
bla
ck
LOW
wht/blue
COMM
ellow
ye
llo
w
White
White
120 Vac
White
24 Vac/dc
White
b
r
own
b
l
a
ck
ye
llo
w
ORDERING INFORMATION
HOA Switch
or
Hand
Off
Auto
CONTACT OUTPUT #2 N.O.
HOA Switch
Hand
Off
Auto
ORANGE
ORANGE
BROWN
BROWN
MODEL RE LAY COI L AMPERAGE RATING HOA RELAY POWER LED UL
V321
V421 24 Vac/dc, 208 to 277 Vac
DPST
24 Vac/dc,120 Vac
20 A
Note: Some units are Plenum rated per UL 1995. For details, see White Paper VWP01, UL 1995 and Plenum Ratings, at www.veris.com.
HQ0001846.F 0117
TM