Veris Industries Victory 320, Victory 420 Data Sheet

E150462
Relays | Enclosed Victory Relays: 20 A DPDT
VICTORY 320 & 420
DPDT Relays Provide Versatility
V320
V420
The Victory 320 and 420 DPDT power duty enclosed relays combine industrial strength and ease of use. With the nipple mount enclosure, installation could not be easier. The V320/V420 need no dedicated field enclosure, so they are the ideal retrofit devices. One coil input controls the state of two power rated contacts for the simultaneous control of two devices or both poles of a single-phase circuit, e.g. motor loads. Field-selectable high and low voltage coil inputs provide on-site versatility.
SPECIFICATIONS
Operating Temp Range -40° to 40°C (-40° to 104°F)
Operating Humidity Range 10 to 90% RH non-condensing
Expected Relay Life Electrical (@ rated current) 100,000 cycles;
Mechanical (unpowered) 10,000,000 cycles
Relay Status LED ON=energized
Insulation Class 277 Vac RMS
WIRE SPECIFICATIONS
Lead Length 14” (356 mm) min.
Coil: 18 AWG; Contacts: 12 AWG; HOA monitor wires: 16 AWG
WARRANTY
Limited Warranty 5 years
AGENCY APPROVALS
Agency Approvals UL 508
Sleek enclosure
Reduces the need for panel space
Nipple mount
Can be mounted to any electrical enclosure, easing installation
APPLICATIONS
• Command contactors
• Control motors
• Isolation
TYPICAL COIL PERFORMANCE
Voltage Coil Current
24 V 150 mA 64 mA
120 V 84 mA
277 V 102 mA
CONTACT RATINGS
Resistive 20 A @ 277 Vac, 28 Vdc
Motor 120 Vac, 1 HP
277 Vac, 2 HP
Pilot Duty A300
Ballast 20 A @ 277 Vac N.O.
10 A @ 277 Vac N.C.
Tungsten 10 A @ 120 Vac N.O.
2 A @ 120 Vac N.C.
Flexible wire
Flexible tinned stranded wire… fits easily in tight spaces and provides secure connections to wire nuts
UL508 Listed
Designed and listed for field installation…makes electrical inspection a snap
• Device interlocking
• Relay logic
• Sense voltages for alarm conditions
AC DC
TM
HQ0001842.F 0117
4.0"
Common
Relays | Victory 320 & 420
Wiring Diagram
To Load
CONTACTS
CONTROL
COIL
PANEL
To Controls
NIPPLE MOUNT TO ANY 2X OR 4X ELECTRIC AL BOX
Wiring Diagram
To Load
Contacts
CONTACTS
To Controls
To Load
L
I
O
C
Wire Nut
DIMENSIONAL DRAWINGNIPPLE MOUNT DIRECTLY TO A PANEL
(103 mm)
3.8"
(97 mm)
2.3"
(59 mm)
3/4" NPT Nipple
2.0"
(52 mm)
2.5"
(64 mm)
WIRE COLOR CODES
CONTACT OUTPUTCONTROL SYSTEM INPUT
wht/brown
wht/black
LOW
wht/blue
COMM
wht/yellow
HI
b
r
ow
n
208 to 277 Vac
b
HI
l
a
c
k
b
l
u
e
y
e
ll
o
w
120 Vac
24 Vac/dc
White
White
White
White
b
r
ow
n
BLUE
N.C. #1
or
b
l
a
c
k
b
l
u
e
y
e
ll
o
w
YELLOW
ORANGE
GREY
VIOLET
BROWN
Common #1
N.O. #1
N.C. #2
Common #2
N.O. #2
ORDERING INFORMATION
MODEL RE LAY COIL AMPERAGE RATING RELAY POWER LED UL
V320
V420 24 Vac/dc, 208 to 277 Vac
DPDT
Note: Some units are Plenum rated per UL 1995. For details, see White Paper VWP01, UL 1995 and Plenum Ratings, at www.veris.com.
24 Vac/dc,120 Vac
20 A
HQ0001842.F 0117
TM