Veris Industries TWS SERIES Data Sheet

Setpoint Devices | Wall Mount Temperature Transmitter
with Thermostat Functions
TWS SERIES
Independent RH, Temp, and Analog Setpoint Outputs
TWS
All TWS Series institutional grade temperature transmitters are field­programmable and designed to satisfy the demanding requirements of pharmaceutical labs, hospitals, science labs, and other exacting applications. Internal jumpers control access to a feature which allows field adjustment of calibration offsets. Tampering can be discouraged by setting a jumper to disable keypad program functions.
Analog Output
Analog output models feature a keypad to make adjusting temperature setpoint values easy. They are unique in reporting the setpoint values back to a control system by means of 4 to 20 mA or 0 to 5/0 to 10 Vdc (output selected by slide-switch) signals.
Setpoint Relay
The TWS Series setpoint relay models measure temperature and offer thermostat functionality. Two separate relays can be configured to control heat/cool in thermostat mode.
Flexibility
Independent heat/cool (TWS relay) or analog setpoint outputs (TWS analog) provide application exibility
LCD display
LCD for local display of readings and setup values…easy visibility under any lighting conditions
Offset function
Offset function adjusts calibration offsets for temperature
APPLICATIONS
• Hospitals and operating rooms, pharmaceutical labs
• Clean rooms
• Food processing plants
Switch­selectable
Switch-selectable 4 to 20 mA or 0 to 5/0 to 10 Vdc analog outputs
Semiconductor
Semiconductor temperature sensor can be field-calibrated
• Environmental testing facilities and other institutional applications
SPECIFICATIONS
Input Power Class 2; 15 to 30 Vdc or 24 Vac 50/60Hz, 100 mA
Outputs, Analog Switch-selectable 4 to 20 mA (clipped and
Outputs, Relay (Relay Models Only)
Physical UL 94V-0 fire retardant ABS
TEMPERATURE
Accuracy ±0.5 °C (±1 °F)
Scaling 10 to 35 °C (50 to 95 °F) or 0 to 50 °C (32 to 122 °F),
Calibration Offset Adjustable ±10° in 0.1° (C or F) increments
Setpoint Range Minimum to full scale in 1° (C or F) increments
Hysteresis (Deadband) 1 to 10 °F in 1 °F increments
TM
max.
capped)/0 to 10 V/0 to 5 Vdc (switch affects all outputs)
menu selectable
WARRANTY
Limited Warranty 5 years
AGENCY APPROVALS
*
*The CE mark indicates RoHS2 compliance. Please refer to the CE Declaration of Conformit y for additional details.
HQ0001873.F 0117
TEMP
SENSOR
AMP VOLT
YES
RUN
CAL
NO
TEMP
Minus Select Plus
+
(29 mm)
Setpoint Devices | TWS Series
ANALOG MODELS
Wiring Diagrams
RELAY MODELS
Wiring Diagrams
CONFIGURATION
DIMENSIONAL DRAWING
4.75"
(121 mm)
Enter
-+
3.5"
(89 mm)
1.2"
ORDERING INFORMATION
Setpoint
TWS
A = Analog R = Relay
Example:
SA 1 CTWS
TWS models include standard temperature transmitter outputs. Optiona l RTDs and thermi stors are availabl e as shown for TWSA m odels.
*Not avail able in W or Y high accur acy thermistors.
S
= CE (standard)
Cal Certicate
0 = None 1 = 1 point Cal Va lidation* 2 = 2 point Cal Va lidation*
Option
Blank = Non e B = 100R Platinu m, RTD C = 1k Platinum, RT D D = 10k T2, Ther mistor E = 2.2k, T hermistor F = 3k, The rmistor G = 10k CPC, The rmistor H = 10k T3, Ther mistor J = 10k Dale, The rmistor K = 10k w/11k shunt,Th ermistor M = 20k NTC, T hermistor N = 1800 ohm TAC, Ther mistor Q = 1uA/C, Lini temp R = 10k US, Ther mistor S = 10k 3A 221, Thermisto r T = 100k, Th ermistor U = 20k “D”, Ther mistor W = 10k T2 high acc uracy, Thermis tor Y = 10k T3 high acc uracy, Thermist or
HQ0001873.F 0117
TM
Loading...