Veris Industries TWS Series Installation Guide

Installation Guide
Temperature
• This product is not intended for life or safety applications.
• Read and understand the instructions before installing this product.
• Turn off all power supplying equipment before working on it.
• The installer is responsible for conformance to all applicable codes.
No responsibility is assumed by Veris Industries for any consequences arising out of the
use of this material.
NOTICE
TWS Series
Wall Mount with Analog Setpoints, LCD and
Thermostat Control
Product Overview
The TWS analog series measures the temperature of the air inside a room. Devices are designed for use in hospital rooms, laboratories, and other spaces that require precise environmental control. The keypad allows control of setpoint values. The slide switch position determines the output type (amp or volt). To maintain accuracy, keep vents clear of dust, debris, etc. The TWS is warranted for period of ve years.
Product Identification
Temp Cal
TWS
Setpoint
A
= Analog
S
= CE
Certificate
0 = None 1 = 1 point Cal Validation 2 = 2 point Cal Validation
Option
B = 100R Platinum, RTD C = 1k Platinum, RTD D = 10k T2, Thermistor E = 2.2k, Thermistor F = 3k, Thermistor G = 10k CPC, Thermistor H = 10k T3, Thermistor I = 1k Balco (nickel-iron) RTD J = 10k Dale, Thermistor K = 10k w/11k shunt,Thermistor M = 20k NTC, Thermistor
N = 1800 ohm TAC, Thermistor Q = 1uA/C, Linitemp R = 10k US, Thermistor S = 10k 3A 221, Thermistor T = 100k, Thermistor U = 20k “D”, Thermistor W = 10k T2 high accuracy, Thermistor Y = 10k T3 high accuracy, Thermistor Z = 10k E1, Thermistor CC= 15k, Thermistor
TM
Specifications
Input Power
Outputs
Physical
Temperature Accuracy
Operating Humidity Range
Operating Temperature Range
Analog Output Scaling
Calibration Offset
Setpoint Range
* If the 0° to 50°C (32° to 122°F) scaling range is selected, the device’s operating temperature range still applies. One side of the transformer secondary is connected to the signal common, so an isolation transformer or
dedicated power supply may be required. RTD/Thermistors in wall packages are not compensated for internal heating of the product. EMC Special Note: Connect this product to a DC distribution network or an AC/DC power adaptor with proper
surge protection (EN 61000-6-1:2007 specification requirements).
Z204455-0E Page 1 of 4 ©2014 Veris Industries 02141
Alta Labs, E nercept, Ensp ector, Hawkeye, Trus tat, Aerospo nd, Veris, and th e Veris ‘V’ log o are tradema rks or registe red tradema rks of Veris Ind ustries, L. L.C. in the USA and /or other countri es.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
15-30VDC/24VAC, 100mA max.
Switch-selectable amp or volt
If volt is selected, the configuration menu allows selection between 0- 5V or 0 -10V
UL 94 -V- O fire retardant ABS
±0 .5° C (±1° F)
0-100% RH (non-condensing)
10° to 35°C (50° to 95°F)
10° to 35°C (50° to 95°F) or 0° to 5 0°C ( 32° to 122°F), menu selectable*
Adjustable ±9.9° (C or F) in 0.1° increments
Minimum to Full Scale in 1° (C or F) increments
Installation Guide
1.2"
(29 mm)
3.5"
(89 mm)
4.75"
(121 mm)
- +
Temperature TWSSeries
Dimensions
TM
Installation
Observe precautions for handling static sensitive devices to avoid damage to the circuitry that is not covered under the factory warranty.
1. Locate the tab at the top of the sensor housing. Using only the minimum required force, press this tab down and pull the cover outward from the top. Set the cover aside.
Housing, Top View
Tab
2. Remove the backplate by unfastening the sensor from the bottom of the backplate and pivoting the sensor outward.
3. Punch out wire opening in the backplate.
4. Position the backplate vertically on the wall, 4 ½ feet (1.4 m) above the oor. Locate away from windows, vents, and other sources of draft. If possible, do not mount on an external wall, as this might cause inaccurate temperature readings.
Z204455-0E Page 2 of 4 ©2014 Veris Industries 02141
Alta Labs, E nercept, Ensp ector, Hawkeye, Trus tat, Aerospo nd, Veris, and th e Veris ‘V’ log o are tradema rks or registe red tradema rks of Veris Ind ustries, L. L.C. in the USA and /or other countri es.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.